Panasonic 1728 User Manual

Fire alarm systems
External Presentation unit
For presentation of pre-warnings, fire alarms, faults & disablements
Compact size
Presentation unit 1728
This unit (S/W V1.2) is intended for pre­warning, fire and heavy smoke / heat alarm presentation. Point or zone alarm presentation is like in the c.i.e. it is connected to. You can scroll amongst two or more alarms in the system but the fire alarms can not selected alarms will be presented in a display light). An alarm text will be presented together with each alarm, if programmed in the c.i.e. Furthermore, > selected alarms can be stored in the unit and will in such a case be shown, instead of the texts sent from the c.i.e. for these alarms. A built-in buzzer can be silenced but the alarm devices in the installation can not Any fault in the system will be presented as "General fault in system" and the buzzer will sound. It can be silenced. Any disablement in the system will be presented as "General disablement in system". The unit is power supplied via the c.i.e. or external power supply.
(LCD, 2x40 characters with back-
be reset via this unit. All or
617 texts for
will sound like in the c.i.e. It
be silenced via this unit.
LEDs, push buttons etc.
The unit has the following LEDs:
Fire (Brand) and Alarms queued
(Flera larm), indicating pre-warning, co-incidence and fire alarms.
Operation (Drift), indicating that the
unit is connected to a c.i.e. and power supplied, i.e. it is in operation.
Extinguishing (Släckanläggning
aktiverad), indicating activated output for extinguishing equipment.
Ventilation (Brandventilation
aktiverad), indicating activated output for ventilation equipment.
Fire brigade tx (Larmsändare
aktiverad), indicating activated output for Fire brigade tx (routing equipment).
The unit has the following push buttons:
Alarms queued (Flera larm), used to
scroll amongst the alarms.
Silence buzzer (Summer tyst), used to
silence the buzzer new alarm).
The designation texts on the front are in 1728SE in Swedish and in 1728UK in English.
(it will re-sound for a
Compact size
The compact size enclosure is made of grey high impact ABS. Fitted with a supple­mentary "O" ring gasket, it will comply with IP61, in respect of dust and moisture. The push buttons on the front are disabled until they are supposed to be used. The unit shall be wall mounted. Two compression glands are attached.
SW mode and address setting
The display and the push buttons are used to set the SW mode and address, see the opposite side of this page.
Product application
The 1728 unit is intended for indoor use and in dry premises. SW mode 1728 - 1587 is intended to be used in the systems EBL512 and EBL128 and SW mode 1728 – 1582 in the systems EBL500 / 512 / 1000 / 2000.
Panasonic Electric Works Fire & Security Technology Europe AB Citadellsvägen 23, SE-211 18 Malmö, Sweden Tel: +46 (0)40 697 70 00 • Fax: +46 (0)40 697 70 99 info-fste@eu.pewg.panasonic.com • www.panasonic-fire-security.com
Type numbers
1728 External Presentation unit (S/W V1.2). 1728SE / 1728UK: Designation texts on
the front in Swedish / English. NOTE! In Swedish convention (SBF): "General fault" presentation but no buzzer and no "General disablement" presentation.
1582 External FBP interface board. (Required in EBL512 / 500 when SW mode 1826/28
– 1582 shall be used.)
1587 External FBP / DU interface board. (Required in EBL512 when SW mode 1826/28
– 1587 shall be used. EBL512 software V>
2.3.2 1 required.)
4552 RS485 Transceiver component / comm. module. (Required in EBL128. SW mode
1826/28 – 1587 only. EBL128 software V>
1
Only required if the new functions (buzzer for fault and "General disablement" presentation)
1.0.5 1 required.)
shall be used. NOTE! The number of units that can be power supplied via the c.i.e. / board / external power
supply is also depending on all other units connected to the same c.i.e. / board / external power supply.
2
Up to 1200 m cable can be used.
The 1728 unit can run in one of two different SW modes: a) 1728 in SW mode 1728 – 1587 has the highest performance with regard to functionality,
response time, ability to store fire alarms, etc. In this mode it is intended to succeed the Display unit 2236SE but not as a spare part
, since 2236SE is connected to a COM loop and 1728 requires an Ext. FBP / DU interface board 1587 in the EBL512 c.i.e. It is also intended to succeed the Ext. presentation display 2428SE but not as a spare part
, since 2428SE requires an Ext. FBP interface board 1582 in the c.i.e. and 1728 requires an Ext. FBP / DU interface board 1587 in the EBL512 c.i.e.
b) 1728 in SW mode 1728 – 1582. In this mode it has the same functionality as the ext. Presentation display 2428SE and can be used as a spare part
, i.e. the performance is the same but the look, dimensions, etc. are not the same. In this mode 1728 requires an Ext. FBP interface board 1582 in the c.i.e.
Regarding 2236SE / 2428SE: These units have designation texts in Swedish (SE).
Technical data
Voltage (V DC) rated
allowed normal (in the system)
normal (in the system by battery back-up) Current consumption at norm. volt. (mA) quiescent / active
Ambient temperature (°C) operating
storage Ambient humidity (% RH) max. 90, non condensing Ingress Protection rating (estimated) IP61 (with the "O" ring gasket) Size W x H x D (mm) 220 x 145 x 50 Weight (g) 687 Colour (high impact ABS) Grey (RAL 7035) Approvals CE; Compliant with EN 54-2 whenever applicable.
2
On each 1582 board are up to eight addresses available and on each 1587 board up to sixteen addresses. In EBL128
are up to four addresses
available.
24 12-30
24 21-27
26 (at 24 V), 48 (at 12 V) / 49 (at 24 V), 88 (at 12 V)
0 to +40
-40 to +70
All technical features and data are subject to changes without notice, resulting from continuous development and improvement.
Product Leaflet Date of issue Revision / Date of revision
MEW00280 2005-03-31 3 / 2007-01-29