Panasonic 1549, 1548, 1550 User Manual

Fire alarm system
EBL512
EBL512 -- an intelligent analog addressable fire alarm system
Up to 512 addresses per control and indicating equipment (c.i.e.)
TLON network for up to 30 c.i.e.:s
Analog addressable system
EBL512 is an intelligent analog addressable fire alarm system, conforming to the EN54-2 and –4 standards.
Features / functions
The fire alarm system EBL512 meets the most stringent requirements relating to fire detection and alarm.
A user-friendly PC software Win512 is used for site specific data editing, download, backup and SW download.
Some features / functions:
Adaptation of each analog detector's
alarm level in relation to its contamina­tion. Service signal when required.
Algorithms for filtering and alarm, to
reduce nuisance alarms. Algorithm for faster detection of smouldering fires.
Functions, customer related: Test mode,
alert annunciation, disablements, etc.
Functions: Fire door closing, inter-
locking combinations of outputs & inputs, time channels, alarm delay, two­unit dependence, user definable text message for each alarm point, etc.
Programmable inputs and outputs and
a large number of trigger conditions.
Expansion boards (options) with zone
line inputs or relay outputs.
Interface (option) for ext. Fire brigade
panels, alert annunciation units, data converters, etc.
Panasonic Electric Works Fire & Security Technology Europe AB Citadellsvägen 23, SE-211 18 Malmö, Sweden Tel: +46 (0)40 697 70 00 • Fax: +46 (0)40 697 70 99 info-fste@eu.pewg.panasonic.com • www.panasonic-fire-security.com
Up to 512 addresses
EBL512 has the capacity of connecting 512 addresses. Basic configurations 128, 256 or 512 addresses. Can be upgraded on site.
Each c.i.e. has four COM loops for connection of up to 512 loop units. Each addressable loop unit uses one address.
Some loop units that can be connected:
Analog detectors (sensors)
Addressable manual call points
Addressable short circuit isolators
Addressable input and output units
Addressable sirens & sounder bases
Addressable external power supply units
Conventional detectors and manual call
points
TLON Network
Up to 30 EBL512 c.i.e.:s can be connected to a TLON network. A TLON connection board 1590 is then required in each c.i.e.
Miscellaneous
EBL512 has space in the cabinet for two sealed Lead Acid 24 (27) Ah batteries.
In each c.i.e. can be mounted up to six expansion boards 1580-1587. The ext. FBPs 182x and the Alert Annunciation units 173x, shall be connected via a 1587 board.
One Web-server II 1598 (option) connects the EBL512 system to Internet / an Intranet (LAN).
Type numbers
1548 EBL512 c.i.e., excl. printer, configured for 128, 256 or 512 addresses. 1549 EBL512 c.i.e., incl. printer, configured for 128, 256 or 512 addresses. 1550 EBL512 c.i.e., excl. front panel, excl. printer, configured for 128, 256 or 512
addresses. 1558 Printer board (option for 1548). 1572 Cabinet for drawings. 1580 8 zones expansion board (8 zone line inputs for conventional detectors). 1581 8 relays expansion board (8 programmable relay outputs). 1582 External FBP interface board (for connection of data converters and the "older"
types of ext. FBPs). 1583 German FBP interface board (for connection of a "Feuerwehr-Bedienfeld", incl.
a VdS Standardschnittstelle "Löschen"). 1584 Autronica interface board (for connection of Autronica, BS100 units). 1585 Connection cable (male-male) for the 1580-1587 boards (no. 1->2 and no. 5->6). 1586 Connection cable (female-female) for the 1580-1587 boards (no. 3->4). 1587 External FBP / DU interface board (for connection of the newest types of display
units, e.g. ext. FBPs (1826 / 1828) and Alert Annunciation units (1735 /1736). 1590 TLON connection board (for TLON network). One board in each c.i.e.
Technical data
Voltage primary (V AC) secondary system (V DC) Current consumption (mA) Depending on type (1548-1550), expansion board(s), etc. See EBL512
Ambient temperature (°C) operating storage Ambient humidity (% RH) max. 90, non-condensing Ingress Protection rating (estimated) IP32
Inputs 4 COM loops for 128, 256 or 512 addresses 4 programmable
Outputs 4 programmable supervised voltage outputs 2 programmable relay outputs Relay outputs for routing equipment (Fire brigade tx and Fault tx) Power supply (24 V DC) for routing equipment and external equipment
Size W x H x D (mm) 400 x 610 x 175 Weight (kg) 1548: 17.6 / 1549: 18 / 1550: 17.4 Colour (metal cabinet) Light grey (NCS S1500-N, PMS Cool Grey 2) Approvals CE; Conforms with EN54-2 and -4. The front conforms with SS3654.
Note! All voltages are nominal.
230 24
Planning Instructions.
0 to +40
-40 to +70
All technical features and data are subject to changes without notice, resulting from continuous development and improvement.
Product Leaflet Date of issue Revision / Date of revision
MEW00006 2000-05-12 6 / 2008-01-24