F810-2 & F830-4
Automatic Humidifier Units (
OPERATING INSTRUCTIONS & REPLACEMENT PARTS
HUMIDIFIER UNITS:
• F810-2 Automatic Humidifier (Two Spray
Heads) Capacity - 30,000 Cubic Feet, maximum
output 30 Gallons (227 l) in 24 hours.
• F830-4 Automatic Humidifier (Four Spray
Heads) Capacity - 60,000 Cubic Feet, maximum
output 60 Gallons (454 l) in 24 hours.
INTRODUCTION:
For dependable moisture and humidity control, these units
provide an efficient method of maintaining uniform moisture
in paper, fabric, tobacco, etc. at the same time helping to
reduce the possibility of fire hazards. The water is finely
atomized and quickly absorbed into the room atmosphere.
Each Automatic Spray Atomizer requires 1/2 C.F.M. at 50
p.s.i. air pressure for the finest uniform atomization.
2 or 4 Spray Heads)
INSTRUCTIONS AND PARTS SHEET AH-7/12/2012
Supersedes Instructions & Part List AH-8/31/2011
WARNING: This product must be grounded to
prevent electrical shock. Proper use of the three
wire grounding cord installed with each unit is
essential for its safe use. The plug must be plugged
into an outlet that is properly installed and grounded
in accordance with all local codes and ordinances.
This unit is designed for the spraying of water only.
D i s c o n n e c t p o w e r b e f o r e s e r v i c i n g .
F830-4 Automatic Humidifier (4 Spray Heads) Capacity 60,000 Cubic Feet, max imum 60 Gal lons in 24 hours
FIRE PREVENTION:
Paasche Humidifier Units present an inexpensive means of
reducing the danger of spontaneous combustion. Proper
humidification limits dust diffusion and grounds static electricity.
HUMIDIFIER USES:
• Printing and Bindery Plants- They are of great value
for keeping paper quality at its best to assure perfect
registration when printing.
• Tobacco and Similar Industries- require uniform
humidity control when aging and curing.
• Textile Mills, Clothing Factories, Warehouses-
Fabrics tend to gradually deteriorate in dry atmosphere.
When adequate humidity is maintained, goods retain their
original luster and sheen. Dangers from lint and dust
accumulations are greatly minimized with proper humidity.
• Carton Manufacturers- Winter conditions can dry out
materials used to make boxes, causing tears and
improper folding during manufacture or damage by the
customer while in use.
• Dry and Dusty Factories- Factories which are dry and
dusty due to insufficient humidity, are constantly subject
to the dangers of spontaneous combustion. One method
of reducing this hazard is with a uniform, accurate and
dependable Automatic Humidifier Unit by Paasche.
Paasche Airbrush Company
4311 North Normandy Avenue
Chicago, IL 60634-1395
Phone: 773-867-9191 • Fax: 773-867-9198
Website: paascheairbrush.com
E-Mail: info@paascheairbrush.com
Printed in the U.S.A.

PAASCHE F800- Series Automatic Humidifier
Page 2
The F800- Series Automatic Humidifier Units will automatically dispense gallons of finely atomized water, providing controlled humidity
when the dial on the humidistat (Item #1) is adjusted to the humidity required. These Automatic Humidifier Units will automatically start and
stop at the humidity setting. When properly connected
to the water and electric systems of the building and to an air source that supplies
constant air pressure (minimum 50 p.s.i.) to the F800 Series Unit, these units will deliver finely atomized water for extended periods.
HUMIDIFIER INSTALLATION
1. Mount Humidifier Unit in convenient location using SM-42 Mounting Bracket (not
shown).
2. Connect air supply to HF-1/4" Air Inlet Valve.
3. Connect water supply to HF-1/4" Water Inlet Valve.
4. Open air inlet valve and water supply valve under air supply valve
Tighten connections if required.
5. Turn humidistat control dial on item #1 counterclockwise to off position before plugging
cord into grounded outlet.
6. Turn U-3178 Fluid Adjusting Knob on back of Spray Guns to closed position by turning
clockwise -Do Not Over Tighten
knob and then open adjusting knob to number 30.
7. Set Regulator item #7, located behind Gauge #2, at 50 p.s.i. minimum air pressure (60
p.s.i. maximum).
8. Plug units three wire electrical plug into properly grounded receptacle (115V., 60cy).
9. Turn Humidistat control dial to on position and desired humidity. You will hear a “click”
when activated.
10. Water flow rate may be adjusted using the U-3178 Fluid Adjusting Knob on back of
each Spray Gun. Mist should always be absorbed into the surrounding air without
settling out onto the floor under the unit.
CEILING, WALL, MERCHANDISE OR MACHINERY.
. Set “0” on reference dial to line up with “0” on fluid adjusting
CAUTION: DO NOT AIM DIRECTLY AT
check for leaks.
SAFETY NOTE: Do Not allow water vapor to condense or leaks to drip onto floor or
unit, if this condition exists, check for:
a. Water leaks from connections or Spray Gun nozzles.
b. Insufficient atomization. Correct by increasing air pressure and/or decreasing fluid flow.
c. Humidistat setting too high. Lower setting if necessary.
d. Open drain valve on R-75AR Regulator/Condenser item #7 periodically to drain airline
moisture buildup.
CAUTION: Guard Face and Eyes so escaping air and moisture do not cause injury.
F830-4 UNIT
1
behind 845
7
Air Inlet
2
3
5
6
Water
Inlet
WARNING: Humidifier must never be used to create a fog condition in which water
may collect on the unit and produce an electrical hazard.
MAJOR COMPONENTS FOR F800-SERIES HUMIDIFIERS
No. Part No. Description
1. 845 Humidistat
2. GB-1-1/2"-100# Air Pressure Gauge
3. AB-H-AUR-1 Humidifier Spray Gun (Drawing below)
No. Part No. Description
1. AR-15-1 Aircap
2. AU-12 Aircap Nut
3. AU-1 Tip
4. A-AU-3-11/16 Needle
5. AU-7B Fluid Body
9. U-1432A Ball Stud
10. U-1399 Swivel Nut
U-3502 Packing Set
17. U-28-12 Packing Washers (12)
18. U-29 Packing Gland (1)
19. DU-30 Stainless St. Spring (1)
20. U-203 Gland (1)
24. U-322 Cup Leather (1)
AU-1914B Cylinder Assembly
(Note: The AU-1914B includes U-873E & U-2686A)
4. A-AU-3-11/16 Needle
17. U-28-12 Packing Washers (3)
20. U-203 Gland
21. U-1907B Shell Assembly
27. U-2966 Piston Spring
U-873E Piston Assembly
U-2686A Cylinder Cap Assembly
4. HL-3/16-12IN Water Hose W/Cplgs.
5. SM-880 Solenoid Valve
6. HF-1/4 Valve Assembly
7. R-76 Air Regulator/Condenser
22. U-2965 Needle Chuck
23. U-2964 Inner Bushing
24. U-322 Cup Leather
25. U-2465A Outer Disc
26. U-2544 Locknut
28. U-2707A Cylinder Cap
29. U-941 Spring Washer
30. U-951B Fluid Dial
31. U-2675A Friction Nut
32. U-1098 Spring
33. U-2584P Stop Washer
34. 59-57 Lock Stud
35. U-3178 Fluid Adjusting Knob (Don’t over tighten)
36. 59-56 Lock Screw
4