Outback Power Systems GS3548E Operators Manual

Radian Series Inverter/Charger
GS7048E
GS3548E
Address:
Corporate Headquarters
Arlington, WA 98223 USA
European Office
Schwabach, Germany
Telephone:
+1.360.435.6030
+1.360.435.6019 (Fax)
+49.9122.79889.0
Email:
Support@outbackpower.com
Website:
http://www.outbackpower.com
About OutBack Power Technologies
OutBack Power Technologies is a leader in advanced energy conversion technology. OutBack products include true sine wave inverter/chargers, maximum power point tracking charge controllers, and system communication components, as well as circuit breakers, batteries, accessories, and assembled systems.
Grid/Hybrid™
As a leader in off-grid energy systems designed around energy storage, OutBack Power is an innovator in Grid/Hybrid system technology, providing the best of both worlds: grid-tied system savings during normal or daylight operation, and off-grid independence during peak energy times or in the event of a power outage or an emergency. Grid/Hybrid systems have the intelligence, agility and interoperability to operate in multiple energy modes quickly, efficiently, and seamlessly, in order to deliver clean, continuous and reliable power to residential and commercial users while maintaining grid stability.
Contact Information
17825 – 59th Avenue N.E. Suite B
+1.360.618.4363 (Technical Support)
Hansastrasse 8 D-91126
+49.9122.79889.21 (Fax)
Disclaimer
UNLESS SPECIFICALLY AGREED TO IN WRITING, OUTBACK POWER TECHNOLOGIES:
(a) MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF ANY TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION.
(b) ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSS OR DAMAGE, WHETHER DIRECT, INDIRECT, CONSEQUENTIAL OR INCIDENTAL, WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION. THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USER’S RISK.
OutBack Power Technologies cannot be responsible for system failure, damages, or injury resulting from improper installation of their products.
Information included in this manual is subject to change without notice.
Notice of Copyright
Radian Series Inverter/Charger Operator’s Manual © 2014 by OutBack Power Technologies. All Rights Reserved.
Trademarks
OutBack Power, the OutBack Power logo, FLEXpower ONE, and Grid/Hybrid are trademarks owned and used by OutBack Power Technologies, Inc. The ALPHA logo and the phrase “member of the Alpha Group” are trademarks owned and used by Alpha Technologies Inc. These trademarks may be registered in the United States and other countries.
Date and Revision
February 2014, Revision A (firmware revision 001.005.xxx)
Part Number
900-0145-01-01 Rev A

Table of Contents

Introduction ................................................................................................. 5
Audience ................................................................................................................................................................................. 5
Symbols Used ........................................................................................................................................................................ 5
General Safety ....................................................................................................................................................................... 5
Welcome to OutBack Power Technologies ................................................................................................................. 6
Inverter Functions ................................................................................................................................................................ 6
GS7048E ................................................................................................................................................................................................... 7
GS3548E ................................................................................................................................................................................................... 7
Inverter Controls ................................................................................................................................................................... 8
On/Off Switch ......................................................................................................................................................................................... 8
MATE3 System Display and Controller ......................................................................................................................................... 8
Commissioning ............................................................................................ 9
Functional Test ...................................................................................................................................................................... 9
Pre-startup Procedures ....................................................................................................................................................................... 9
Startup ...................................................................................................................................................................................................... 9
Powering Down ................................................................................................................................................................................... 11
Adding New Devices ......................................................................................................................................................................... 11
Firmware Updates .............................................................................................................................................................................. 12
Operation .................................................................................................. 13
Inverter Functionality ...................................................................................................................................................... 13
Description of AC Input Modes .................................................................................................................................... 13
Generator ............................................................................................................................................................................................... 14
Support ................................................................................................................................................................................................... 14
Grid Tied ................................................................................................................................................................................................. 15
UPS ........................................................................................................................................................................................................... 17
Backup .................................................................................................................................................................................................... 18
Mini Grid ................................................................................................................................................................................................. 18
Grid Zero ................................................................................................................................................................................................ 19
Description of Inverter Operations ............................................................................................................................. 22
Inverting ................................................................................................................................................................................................. 22
DC and AC Voltages .................................................................................................................................................................................... 22
AC Frequency ................................................................................................................................................................................................ 23
Search ............................................................................................................................................................................................................. 23
Input ........................................................................................................................................................................................................ 24
AC Current Settings ..................................................................................................................................................................................... 24
AC Source Acceptance ............................................................................................................................................................................... 25
Generator Input ............................................................................................................................................................................................ 26
Transfer ........................................................................................................................................................................................................... 26
Battery Chargin .................................................................................................................................................................................... 27
Charge Current ............................................................................................................................................................................................. 27
Charge Cycle .................................................................................................................................................................................................. 27
Charging Graphs .......................................................................................................................................................................................... 28
Charging Steps.............................................................................................................................................................................................. 29
New Charging Cycle .................................................................................................................................................................................... 31
Equalization ................................................................................................................................................................................................... 33
Battery Temperature Compensation ..................................................................................................................................................... 33
Offset ....................................................................................................................................................................................................... 35
900-0145-01-01 Rev A 1
Table of Contents
Multiple-Inverter Installations (Stacking) .................................................................................................................................. 36
Parallel Stacking (Dual-Stack and Larger) ............................................................................................................................................. 37
Three-Phase Stacking (Three Inverters) ................................................................................................................................................ 38
Power Save ..................................................................................................................................................................................................... 39
Auxiliary Terminals ............................................................................................................................................................................. 43
System Display-Based Functions ................................................................................................................................. 47
Advanced Generator Start (AGS) .................................................................................................................................................. 47
Grid Functions ...................................................................................................................................................................................... 47
High Battery Transfer (HBX) ...................................................................................................................................................................... 47
Grid Use Time ................................................................................................................................................................................................ 48
Load Grid Transfer ....................................................................................................................................................................................... 48
Metering .................................................................................................... 49
MATE3 Screens ................................................................................................................................................................... 49
Inverter Screens ................................................................................................................................................................................... 49
Battery Screen ...................................................................................................................................................................................... 50
Troubleshooting ......................................................................................... 51
Basic Troubleshooting ..................................................................................................................................................... 51
Module Select ...................................................................................................................................................................................... 56
Error Messages ................................................................................................................................................................... 57
Warning Messages ............................................................................................................................................................ 58
Temperature Events .......................................................................................................................................................................... 59
Disconnect Messages ...................................................................................................................................................... 60
Sell Status ............................................................................................................................................................................. 61
Specifications ............................................................................................. 63
Electrical Specifications ................................................................................................................................................... 63
Mechanical Specifications .............................................................................................................................................. 64
Environmental Specifications ....................................................................................................................................... 64
Temperature Derating ...................................................................................................................................................................... 65
Certifications ....................................................................................................................................................................... 65
Compliance.......................................................................................................................................................................... 66
Firmware Revision ............................................................................................................................................................. 67
Default Settings and Ranges ......................................................................................................................................... 67
Definitions ............................................................................................................................................................................ 70
Index ......................................................................................................... 71
2 900-0145-01-01 Rev A
Table of Contents

List of Tables

Table 1 Summary of Input Modes .......................................................................................................... 21
Table 2 Charge Currents for Radian Models ....................................................................................... 27
Table 3 Offset Interaction with AC Source .......................................................................................... 35
Table 4 Changing Master Power Save Levels (GS7048E)................................................................ 42
Table 5 Aux Mode Functions ................................................................................................................... 46
Table 6 Troubleshooting ........................................................................................................................... 51
Table 7 Error Troubleshooting ................................................................................................................ 57
Table 8 Warning Troubleshooting ......................................................................................................... 58
Table 9 Temperature Events .................................................................................................................... 59
Table 10 Disconnect Troubleshooting .................................................................................................... 60
Table 11 Sell Status Messages .................................................................................................................... 61
Table 12 Electrical Specifications for Radian Models ......................................................................... 63
Table 13 Mechanical Specifications for Radian Models .................................................................... 64
Table 14 Environmental Specifications for Radian Models .............................................................. 64
Table 15 AS4777.3 Acceptance Settings ................................................................................................ 66
Table 16 Radian Inverter Settings ............................................................................................................. 67
Table 17 Terms and Definitions ................................................................................................................. 70

List of Figures

Figure 1 Radian Series Inverter/Charger .................................................................................................. 7
Figure 2 MATE3 System Display and Controller .................................................................................... 8
Figure 3 AC Test Points ................................................................................................................................ 10
Figure 4 Charging Stages Over Time ...................................................................................................... 28
Figure 5 Charging Stages Over Time (24/7) .......................................................................................... 28
Figure 6 Repeated Charging Cycles ........................................................................................................ 32
Figure 7 OutBack HUB4 and MATE3 ........................................................................................................ 36
Figure 8 Example of Parallel Stacking Arrangement (Three Inverters)........................................ 37
Figure 9 Example of Three-Phase Stacking (Three Inverters) ......................................................... 38
Figure 10 Example of Three-Phase Stacking (Nine Inverters) ........................................................... 38
Figure 11 Power Save Levels and Loads................................................................................................... 39
Figure 12 GS3548E Power Save Priority ................................................................................................... 40
Figure 13 GS7048E Power Save Priority ................................................................................................... 41
Figure 14 Home Screen .................................................................................................................................. 49
Figure 15 Inverter Screens ............................................................................................................................ 49
Figure 16 Battery Screen ............................................................................................................................... 50
Figure 17 AC Test Points ................................................................................................................................ 51
Figure 18 Temperature Derating ................................................................................................................ 65
900-0145-01-01 Rev A 3
Table of Contents
This page intentionally left blank.
4 900-0145-01-01 Rev A

Introduction

WARNING: Hazard to Human Life
CAUTION: Hazard to Equipment
This type of notation indicates that the hazard may cause damage to the equipment.
IMPORTANT:
recommendations in such a notation could result in voiding the equipment warranty.
MORE INFORMATION
Inverter/Charger Installation Manual. Another common reference is the system display manual.
WARNING: Limitations on Use
equipment or devices.
WARNING: Reduced Protection
internal safety protection may be impaired.
CAUTION: Equipment Damage
Technologies or its authorized agents.

Audience

This manual provides instructions for setup and operation of the product. It does not cover installation. The manual is intended to be used by anyone required to operate the Radian Series Inverter/Charger. Operators must be familiar with all the safety regulations pertaining to operating power equipment of this type as required by local code. Operators are advised to have basic electrical knowledge and a complete understanding of this equipment’s features and functions. Do not use this product unless it has been installed by a qualified installer in accordance with the Radian Series Inverter/Charger Installation Manual.

Symbols Used

This type of notation indicates that the hazard could be harmful to human life.
This type of notation indicates that the information provided is important to the installation, operation and/or maintenance of the equipment. Failure to follow the
When this symbol appears next to text, it means that more information is available in other manuals relating to the subject. The most common reference is to the Radian Series

General Safety

This equipment is NOT intended for use with life support equipment or other medical
If this product is used in a manner not specified by GS product literature, the product’s
Only use components or accessories recommended or sold by OutBack Power
900-0145-01-01 Rev A 5
Introduction

Welcome to OutBack Power Technologies

IMPORTANT:
Display and Controller.
Thank you for purchasing the OutBack Radian Series Inverter/Charger. It is designed to offer a complete power conversion system between batteries and AC power. As part of an OutBack Grid/Hybrid™ system, it can provide off-grid power, grid backup power, or grid-interactive service which sells excess renewable energy back to the utility.

Inverter Functions

Battery-to-AC inverting which delivers power to run backup loads and other functions
Provides single-phase output Adjustable range of output voltage Settable nominal output frequency
AC-to-battery charging (OutBack systems are battery-based)
Accepts a wide variety of AC sourcesRequires single-phase input
Uses battery energy stored from renewable resources
Can utilize stored energy from many sources (PV arrays, wind turbines, etc.) OutBack FLEXmax charge controllers will optimize PV power production as part of a Grid/Hybrid system
Dual AC inputs allow direct connection to utility grid and AC generator
Rapid transfer between AC source and inverter output with minimal delay time
Uses MATE3 System Display and Controller (sold separately) for user settings as part of a Grid/Hybrid system
Stackable in parallel configuration up to ten inverters
Stackable in three-phase configuration with up to nine inverters (using HUB10.3 Communications Manager)
Field-upgradeable firmware
Seven selectable input modes for different applications
Generator SupportGrid Tied UPSBackupMini Grid Grid Zero
The Radian Series Inverter/Charger is not intended for use with the OutBack MATE or MATE2 System Display and Controller. It is only compatible with the MATE3 System
6 900-0145-01-01 Rev A
Introduction
Figure 1 Radian Series Inverter/Charger

GS7048E

7000 watts (7 kW) continuous power at 48 Vdc
16.3 kVA peak surge capacity
Modular internal design allows low idle consumption and high efficiency at high or low power operation

GS3548E

3500 watts (3.5 kW) continuous power at 48 Vdc
8.2 kVA peak surge capacity
Certified by ETL to IEC 62109-1
: This product has a settable AC output range. In this book, many references to the output refer
NOTE
to the entire range. However, some references are made to 230 Vac or 50 Hz output. These are intended as examples only.
900-0145-01-01 Rev A 7
Introduction

Inverter Controls

IMPORTANT:
The Radian inverter has no external controls. It can operate normally without an external control or interface. Basic modes and settings are pre-programmed at the factory. (See page 67 for default settings.) However, certain external devices can be used to operate or program the Radian.

On/Off Switch

The inverter can be equipped with a switch to turn it on and off. This switch is not sold as an inverter accessory; a common toggle switch can be used. It is wired to the (See the Radian Series Inverter/Charger Installation Manual for more information on wiring the switch.) This switch controls the inverting function only; it does not control the charger or any other function.
Switch INV

MATE3 System Display and Controller

The Radian inverter has no display or LED indicators. It is not possible to monitor its status or operating mode without a metering device. The MATE3 System Display and Controller (sold separately) is designed to accommodate programming and monitoring of a Grid/Hybrid power system. The MATE3 provides the means to adjust the factory default settings to correctly match the installation where needed. It provides the means to monitor system performance and troubleshoot fault or shutdown conditions. It also has data logging and interface functions using the Internet.
auxiliary terminals.
Once settings are modified using a MATE3, the MATE3 can be removed from the installation. The settings are stored in the nonvolatile memory of the Radian inverter. However, it is highly recommended to include a MATE3 as part of the system. This provides the means to monitor system performance and respond quickly should it be necessary to correct a fault or shutdown condition.
The MATE3’s Configuration Wizard is capable of automatically configuring inverters to a series of preset values. This is often more efficient than attempting to manually program each setting in each inverter. Affected fields include system type, battery charging, and AC source configuration.
NOTE:
Model GS7048E can only be used with MATE3 firmware revision 002.010.xxx or higher.
Model GS3548E can only be used with MATE3 firmware revision 002.017.xxx or higher.
Some functions are not based in the inverter, but are part of the MATE3 system display’s firmware. They will not function if the system display is removed. These functions are listed beginning on page 46.
8 900-0145-01-01 Rev A
Figure 2 MATE3 System Display and Controller

Commissioning

WARNING: Shock Hazard and Equipment Damage
carry hazardous voltages. Use appropriate care to avoid the risk of electric shock or equipment damage.
CAUTION: Equipment Damage
This damage is not covered by the warranty.
IMPORTANT:
correct AC operation. The default setting is 50 Hz, but this can be changed to 60 Hz.

Functional Test

It is necessary to remove the inverter cover to perform these tests. The components are close together and

Pre-startup Procedures

1. Ensure all DC and AC overcurrent devices are opened, disconnected, or turned off.
2. Double-check all wiring connections.
3. Confirm that the total load does not exceed the inverter’s wattage. (See page 22.)
4. Inspect the work area to ensure tools or debris have not been left inside.
5. Using a digital voltmeter (DVM) or standard voltmeter, verify battery voltage. Confirm the
voltage is correct for the inverter model. Confirm the polarity.
6. Connect the MATE3 system display, if present.
Incorrect battery polarity will damage the inverter. Excessive battery voltage also may damage the inverter.
Prior to programming (see Startup), verify the operating frequency of the AC source. This is necessary for

Startup

It is highly recommended that all applicable steps be performed in the following order. However, if steps are inapplicable, they can be omitted.
If the results of any step do not match the description, see the Troubleshooting section on page 50.
To start a single-inverter system:
1. Close the main DC circuit breakers (or connect the fuses) from the battery bank to the inverter.
Confirm that the system display is operational, if present.
2. If a system display is present, perform all programming for all functions.
These functions may include AC input modes, AC output voltage, input current limits, battery charging, generator starting, and others.
AC input modes are described beginning on page 13 and are summarized on page 21. The inverter’s individual operations are described beginning on page 22.
3. Turn on the inverter using the MATE3 or external switch. The Radian’s default condition is Off.
Do not turn on any AC circuit breakers at this time.
900-0145-01-01 Rev A 9
Commissioning
Metal pads are located at these
locations. In commissioning, AC voltages can be measured at this series of test points.
Figure 3 AC Test Points
4. Using a DVM or voltmeter, verify 230 Vac (or appropriate voltage) between the “L” and “N” OUT
terminals. (See Figure 3 for AC test points.) The inverter is working correctly if the AC output reads within 10% of 230 Vac or the programmed output voltage.
5. Proceed past the items below to Step 6 on the next page.
To start a multiple-inverter (stacked) system:
1. Close the main DC circuit breakers (or connect the fuses) from the battery bank to the inverter.
Repeat for every inverter present.
2. With the system display, perform any programming for stacking and all other functions.
These functions may also include AC input modes, AC output voltage, input current limits, battery charging, generator starting, and others.
When stacking in parallel, all slave inverters will observe the programming settings for the master. They do not need to be programmed individually.
When stacking in three-phase configuration, all subphase masters will observe the AC input mode and many of the settings used by the master inverter. However, they need to be individually programmed as appropriate for AC output voltage and frequency. They also need to be programmed for AC input voltage and frequency (for both AC inputs). All slaves will observe the programming settings for the master or for their individual subphase master. They do not need to be programmed individually.
AC input modes are described beginning on page 13 and are summarized on page 21. The inverter’s individual operations are described beginning on page 22. Stacking is described beginning on page 36. The MATE3 Configuration Wizard may be used to assist programming.
3. Turn on the master inverter using the system display (or external switch, if one has been installed).
The Radian’s default condition is Off. Do not turn on any AC circuit breakers at this time.
4. Using a DVM or voltmeter, verify 230 Vac (or appropriate voltage) between the master “L” and “N”
OUT terminals. (See Figure 3 for AC test points.)
The inverter is working correctly if the AC output reads within 10% of 230 Vac or the programmed output voltage.
10 900-0145-01-01 Rev A
If subphase masters are used in three-phase configuration, perform this test on each subphase master. If necessary, confirm appropriate voltages from one inverter to the next.
Commissioning
5. Using the system display, temporarily bring each slave out of Silent mode by raising the Power
Save Level of the master. (See page 39.)
As each slave is activated, it will click and create an audible hum.
Confirm that the system display shows no fault messages. Confirm that the output voltages are still correct. Individual slave voltage readings are not necessary since all slave inverters are in parallel.
When this test is finished, return the master to its previous settings.
After output testing is completed, perform the following steps:
6. Close the AC output circuit breakers. If AC bypass switches are present, place them in the normal
(non-bypass) position. Do not connect an AC input source or close any AC input circuits.
7. Use a DVM to verify correct voltage at the AC load panel.
8. Connect a small AC load and test for proper functionality.
9. Close the AC input circuit breakers and connect an AC source.
Using a DVM on the correct input, check the “L” and “N” input terminals for 230 Vac (or appropriate voltage from the AC source.)
If a system display is present, confirm that the inverter accepts the AC source as appropriate for its programming. (Some modes or functions may restrict connection with the source. If one of these modes has been selected for the system, it may not connect.) Check the system display indicators for correct performance.
NOTE: If any Phase B or Phase C inverters are wired to the wrong AC source phases, the inverters will not connect to the AC source and will display a Phase Loss warning. See page 58.
10. If the charger is activated, the inverter will perform a battery charging cycle after powering up.
This can take several hours. If restarted after a temporary shutdown, the inverter may skip most or all of the charging cycle. Confirm that it is charging as appropriate by using the system display.
11. Test other functions which have been enabled, such as generator start, selling, or search mode.
12. Compare the DVM’s readings with the system display meter readings. If necessary, the system
display’s readings can be calibrated to match the DVM more accurately. Calibrated settings include AC input voltage for the Grid and Gen inputs, AC output voltage, and battery voltage.

Powering Down

If steps are inapplicable, they can be omitted. However, it is highly recommended that all applicable steps be performed in the following order. These steps will completely isolate the inverter.
To remove power from the system:
1. Turn off all load circuits and AC input sources.
2. Turn off all renewable energy circuits.
3. Turn each inverter OFF using the MATE3 system display or external switch.
4. Turn off the main DC overcurrent devices for each inverter.

Adding New Devices

When adding new devices to the system, first turn off the system according to the preceding instructions. After adding new devices, perform another functional test, including programming.
900-0145-01-01 Rev A 11
Commissioning
Each requires about 5 minutes.
NOTES:

Firmware Updates

IMPORTANT:
All inverters will shut down during firmware updates. If loads need to be run while updating the firmware, bypass the inverter with a maintenance bypass switch. Communication cables must remain connected and DC power must remain on. Interrupted communication will cause the update to fail and the inverter(s) may not work afterward. Inverters automatically update one at a time beginning with Port 1.
Updates to the Radian’s internal programming are periodically available at the OutBack website www.outbackpower.com. If multiple inverters are used in a system, all units must be upgraded at the
same time. All units must be upgraded to the same firmware revision.
If multiple stacked Radian inverters are used with different firmware revisions, any inverter with a revision different from the master will not function. (See the stacking section on page 36.) The MATE3 will display the following message:
An inverter firmware mismatch has been detected. Inverters X, Y, Z
www.outbackpower.com for current inverter firmware.
1
are disabled. Visit
1 The port designations for the mismatched inverters are listed here.
12 900-0145-01-01 Rev A

Operation

AC IN
DC
TRANSFER
These items represent the input from the AC source, the output to the AC loads, DC functions (inverting, charging, etc Arrows on each symbol represent power flow.

Inverter Functionality

The inverter is capable of being used for many applications. Some of the inverter’s operations occur automatically. Others are conditional or must be enabled manually before they will operate.
Most of the inverter’s individual operations and functions can be programmed using the system display. This allows customization or fine tuning of the inverter’s performance.
The Radian inverter has two sets of input connections, which are labeled AC sources can be connected during inverter installation.
Before operating the inverter:
The operator needs to define the application and decide which functions will be needed. The Radian inverter is programmed with seven AC input modes. Each mode has certain advantages which make it ideal for a particular application. Some modes contain functions unique to that mode.
The modes are described in detail following this section. To help decide which mode will be used, the basic points of each mode are compared in Table 1 on page 21.
Apart from the input modes, Radian inverters possess a set of common functions or operations. These operations are described in detail beginning on page 22. Most of these items operate the same regardless of which input mode is selected; however, this is not always true. The exceptions are noted where appropriate.
NOTE:
which input is used. It does not have independent charger settings on each input.
Each distinct mode, function, or operation is accompanied by a symbol representing the inverter and that operation:
The Radian’s battery charger uses the same programming and settable limits regardless of
and
Grid
), and the transfer relay.
. Two different
Gen
The symbols may have other features depending on the operation.

Description of AC Input Modes

These modes control aspects of how the inverter interacts with AC input sources. Each mode is intended to optimize the inverter for a particular application. The names of the modes are
Support, Grid Tied, UPS, Backup, Mini Grid
compared in Table 1.
Both of the Radian’s inputs,
The
The
NOTE:
because of inverter requirements. Each input can accept any AC source as long as it meets the requirements of the Radian inverter and the selected input mode. If necessary, the
900-0145-01-01 Rev A 13
input can be set in the
Grid
input can be set in the
Gen
The input terminals are labeled for grid and generator due to common conventions, not
Grid
, and
Grid Zero
and
Grid AC Input Mode and Limits
Gen AC Input Mode and Limits
, can be programmed for separate modes.
Gen
. The modes are summarized and
menu.
menu.
Generator
terminals can
Gen
,
Operation
accept grid power. The opposite is also true. However, if using the generator must use the
terminals. See page 43 (
Gen
Gen Alert
) and page 47 (
Gen Alert
or
AGS
functions, the
AGS
).)
When multiple inverters are stacked together in parallel, the master inverter’s input mode is imposed on all slaves. The slave settings are not changed; they retain any mode that was previously programmed. However, the slave will ignore its own input mode and use that of the master. This also applies to any parameters in the mode menu (
Voltage Limit, Connect Delay
, and so on).
If inverters are stacked using subphase masters, the subphase masters will observe the AC input mode and many of the settings used by the master inverter. However, they need to be individually programmed as appropriate for AC output voltage and frequency. They also need to be programmed for AC input voltage and frequency (for both AC inputs).
See the stacking section on page 36 for explanation of both parallel and subphase master (three-phase) stacking.
The following pages compare the various aspects of each input mode.

Generator

The
Generator
mode allows the use of a wide range of AC sources, including generators with a rough or imperfect AC waveform. In other modes, a “noisy” or irregular waveform may not be accepted by the inverter. (Self-excited induction generators may require this mode when used with the Radian.)
Generator
allows these waveforms to be accepted. The charging algorithm of this mode is designed to work well with AC generators regardless of power quality or regulation mechanism. The generator must still comply with the inverter’s nominal input specifications. (See page 24.)
BENEFITS:
The Radian inverter will charge the batteries from the generator even when the generator is undersized, of low quality, or has other problems. See page 26 for recommended parameters for sizing a generator.
In cases where utility grid power is unstable or unreliable, accept the power.
A programmable delay time is available which will allow a generator to stabilize before connection. In the MATE3, this menu item is the
NOTES
Any AC fluctuations that are accepted by the inverter will be transferred to the output. The loads will be exposed to these fluctuations. It may not be advisable to install sensitive loads under these conditions.
The name of mode. The use of this mode does not require the use of the Conversely, the Radian is not required to be placed in this mode just because a generator is installed.
Connect Delay
Gen AC Input Mode and Limits
:
Generator
mode does not mean that the Radian requires a generator input when using this
Generator
. It is available in both the
menus, depending on which input is being programmed.
Gen
mode may allow the Radian inverter to
Grid AC Input Mode and Limits
input; either input can be used.
and
Support
The

Support

amount of current available from the source is limited due to size, wiring, or other reasons. If large loads need to be run, the Radian inverter augments (supports) the AC source. The inverter uses battery power and additional sources to ensure that the loads receive the power they demand.
In the MATE3 system display, the
14 900-0145-01-01 Rev A
mode is intended for systems that use the utility grid or a generator. In some cases the
Grid Input AC Limit
dictates the maximum AC draw for the
Grid
Operation
input. The
IMPORTANT:
of power, load use should be planned accordingly.
IMPORTANT:
common with generators smaller than the wattage of the inverter.
IMPORTANT:
check with the utility company and obtain their permission before using this mode.
Gen Input AC Limit
sets the maximum draw for the Gen input. The Support function takes
effect if the AC demand on either input exceeds the
AC Limit
setting.
BENEFITS
Large inverter loads can be powered while staying connected to the AC input, even if the input is limited. The added battery power prevents overload of the input source, but the batteries are not in constant use.
The Radian inverter will offset the loads with excess renewable energy if it is available from the batteries. See page 35 for more information.
NOTES
:
:
The inverter will draw energy from the batteries when the loads exceed the appropriate batteries may discharge to the Low Battery Cut-Out point. The inverter will shut down with a Low Battery error. (See pages 22 and 57
AC Limit
. With sustained loads and no other DC source, the
.) To prevent the loss
A “noisy” or irregular AC source may prevent The inverter will transfer the power, but will not support the source, charge the batteries, or interact with the current in any other way. This problem is more
A programmable delay time is available which will allow an AC source to stabilize before connection. In the MATE3, this menu item is the
Gen AC Input Mode and Limits
Connect Delay
. It is available in both the
menus, depending on which input is being programmed.
Support
from working normally.
Grid AC Input Mode and Limits
and
Grid Tied
The to using power from the utility grid for charging and loads, the inverter can also convert excess battery power and sell it to the utility grid. Excess battery power usually comes from renewable energy sources, such as PV arrays, hydroelectric turbines, and wind turbines.
900-0145-01-01 Rev A 15
Because the inverter limits the current draw from the AC source, it will reduce the charge rate as necessary to support the loads. If the loads equal the appropriate
If the AC loads reverse. It will take power
The
Support
exceed
function is not available in any other input mode.
the
AC Limit
from
setting, the Support function is activated by operating the charger in
the batteries and use it to support the incoming AC current.
AC Limit
setting, the charge rate will be zero.
Selling power to the utility company requires the authorization of the local electric jurisdiction. How the utility company accommodates this will depend on their policies on the issue. Some may pay for power sold; others may issue credit. Some policies may prohibit the use of this mode altogether. Please

Grid Tied

mode allows the Radian inverter to become grid-interactive. This means that in addition
Operation
The grid-interactive function is integrally tied with Offset operation and with the battery charger. See pages 35 and 27 for more information on these items.
BENEFITS
:
Excess power is returned to the utility grid.
The inverter will offset the loads with excess renewable energy if it is available from the batteries.
If the excess energy is greater than the AC demand (the load size), the excess will be sold to the utility grid.
Due to varying requirements in different locations around the world, the grid-interactive settings are adjustable. These adjustments are made in the
This menu is only available to operators with installer-level access. There are firm rules concerning the
acceptable voltage range, frequency range, clearance time during power loss, and reconnect delay when exporting power to the utility. Generally it is expected that the end user cannot alter the settings.
The installer password must be changed from the default in order to get access to these settings. Once
this password has been changed, the settings can only be accessed by using the installer password. See pages 67 and 69 for more information.
The inverter’s operating frequency can be changed between 50 and 60 Hz using the Grid Interface
Protection menu. This setting changes the inverter’s input acceptance parameters, as well as its output.
See Table 16 beginning on page 67 for the locations of all menu items in the MATE3 menus.
NOTES
:
The inverter has a delay before selling will begin. This delay has a default setting of one minute. During this time, the inverter will not connect to the utility grid. This setting is adjustable in the menu. Upon initial connection to the utility grid, the inverter may be required to perform a battery charging cycle. This may delay the operation of the grid-interactive function.
Grid Interface Protection
menu.
Grid Interface Protection
The grid-interactive function only operates when excess DC (renewable) power is available.
The grid-interactive function is not available in any of the other input modes.
When power is returned to the utility grid, it may be possible to reverse the utility meter. However, this depends on other loads in the system. Loads on the main panel (not on the inverter’s output) may consume power as fast as it is sold. The meter would not run backwards, even if the system display showed the inverter selling power. The result of selling would be to reduce AC power consumption, not reverse it.
The amount of power an inverter can sell is not equal to its specified output wattage. The
Current Protection
The amount of power that is sold is controlled by the utility grid voltage. The wattage sold is
This recommendation is specifically for the inverter’s grid-interactive function. In some cases, the
The grid-interactive function can only operate while the utility grid power is stable and within specific limits.
In Grid Tied mode, the inverter will operate in accordance with the Grid Interface Protection settings.
can be decreased if it is necessary to limit the power sold. This item is available in the
menu.
determined by this voltage multiplied by the current. For example, if the inverter sells 30 amps and the voltage is 231 Vac, the inverter will sell 6.93 kVA. If the voltage is 242 Vac, the inverter will sell 7.26 kVA. Additionally, output will vary with inverter temperature, battery type, and other conditions.
source may be sized larger to account for environmental conditions or the presence of DC loads. This depends on individual site requirements.
The default settings and ranges are listed in Table 16
If the AC voltage or frequency vary outside the Grid Interface Protection limits, the inverter will disconnect from the utility grid to prevent selling under unacceptable conditions. These limits override the AC source acceptance limits described on page 24, which are used in other input modes.
, which begins on page 67.
Maximum Sell
Grid Interface
16 900-0145-01-01 Rev A
Operation
If the inverter stops selling or disconnects due to Grid Interface Protection, the MATE3 will show the
Failure
reason. Sell Status messages are listed on page 61. Disconnect messages are listed on page 60. Often these messages will be the same.
Due to varying requirements in different locations around the world, the grid-interactive settings are
adjustable. However, this is only available to operators with installer-level access. There are firm rules concerning the acceptable voltage range, frequency range, clearance time during power loss, and reconnect delay when exporting power back to the utility. Generally it is expected that the settings cannot be altered by the end user. For this reason, it is necessary to change the installer password from the default in order to get access to these settings. Once this password has been changed, the settings can only be accessed by using the installer password. See pages 67 and 69 for more information.
Before operating in Grid Tied mode, contact the utility company that provides power to the installation. They can provide information regarding the rules that must be followed in order to export power back to the utility. The items below are the selectable options for Grid Interface Protection. It may be necessary to provide these options to the utility company to make certain their standards are met.
The utility may simply name a standard to be followed, as with AS 4777.3 for Australia. It may be necessary to look up the requirements for a local standard and program them accordingly.
STAGE 1 Voltage (basic settings)
Over Voltage Clearance Time (seconds) Over Voltage Trip (AC Voltage) Under Voltage Clearance Time (seconds) Under Voltage Trip (AC Voltage)
STAGE 2 Voltage (if required by utility)
Over Voltage Clearance Time (seconds) Over Voltage Trip (AC Voltage) Under Voltage Clearance Time (seconds) Under Voltage Trip (AC Voltage)
See Table 16 on page 67 for the default settings and ranges.
Frequency Trip
Over Frequency Clearance Time (seconds) Over Frequency Trip (Hertz) Under Frequency Clearance Time (seconds) Under Frequency Trip (Hertz)
The
NOTE:
dependent on the inverter’s operating frequency, which must be set correctly. See pages 9 and 69.
Mains Loss
Clearance Time (seconds) Reconnect Delay (seconds)
Frequency Trip
settings are
UPS
In times. If the utility grid becomes unstable or is interrupted, the Radian can transfer to inverting in minimal time. This allows the system to support sensitive AC loads without interruption.
mode, the Radian’s parameters have been optimized to reduce the response and transfer
UPS
BENEFITS
Constant power is provided to the loads with virtually no drop in voltage or current.
NOTES
Due to the need for the Radian inverter to react quickly to AC source fluctuations, it must remain fully active
:
:
at all times. The inverter requires a continuous consumption of 42 watts.
For this reason, the Search function does not operate in this mode. (See page 23.)
900-0145-01-01 Rev A 17
Operation
Failure

Backup

The
Backup
mode is intended for systems that have utility grid available as the primary AC source. This source will pass through the Radian inverter’s transfer circuit and will power the loads unless utility power is lost. If utility grid power is lost, then the Radian inverter will supply energy to the loads from the battery bank. When the utility power returns, it will be used to power the loads again.
BENEFITS
This mode will continuously maintain the batteries in a fully-charged state, unlike the does not have the overhead consumption of the

Mini Grid

In
Mini Grid
:
mode. It
UPS
Support
mode.
mode, the Radian inverter automatically rejects an AC source and runs solely from battery (and renewable) energy. The inverter only connects to the AC source (usually the utility grid) when the batteries run too low.
The Radian inverter runs on battery-supplied power for as long as the batteries can be sustained. It is expected that the batteries will also be charged from renewable sources such as PV. When the batteries become depleted, the system reconnects to the utility grid to operate the loads.
The inverter will reconnect to the utility grid if the battery voltage decreases to the set point and remains there for the
time period. These items are shown in Table 16 on page 67.
Delay
Connect to Grid
While connected to the utility grid, the inverter’s charger can be set either on or off. If the charger is turned on, the inverter will proceed through a full charging cycle. Upon reaching float stage, the inverter will disconnect from the grid.
If the inverter is connected to the utility grid and the charger is turned off, another DC source such as renewable energy should be present to charge the batteries. The inverter will observe the batteries as if it was performing the charge. When the batteries reach the required voltages and charging times to achieve float stage, the inverter will disconnect from the grid. This means that the regulator for the renewable source must be set to the same settings as the Radian (or higher). Check the settings of
both devices as needed.
See page 27 for more information on the battery charging cycle.
BENEFITS
Mini Grid
possible if certain conditions are met. See the Notes below.
NOTES
The Radian inverter will offset the loads with excess renewable energy if it is available from the batteries. See page 35 for more information on Offset operation. However, the Offset function is inapplicable when the Radian disconnects from an AC source. The renewable energy supports the inverting function instead.
This mode has similar priorities to the high-battery transfer ( display. However, it is not compatible with
Grid
:
mode allows a system to minimize or eliminate dependence on the utility grid. This is only
:
) function used by the MATE3 system
HBX
and cannot be used at the same time. When using
HBX
mode, the system display should disable
to prevent conflicts.
HBX
Mini
18 900-0145-01-01 Rev A
Operation
Mini Grid
system display. These functions do not have similar priorities to inverter’s connection and disconnection with the grid.
When deciding whether to use
Mini Grid logic is based in the Radian inverter and can function in the absence of the MATE3. HBX logic
Mini Grid can use utility grid power to fully recharge the batteries every time it reconnects to the
HBX set points have a wide range of settings. Mini Grid uses settings intended to protect the batteries
HBX works more efficiently with a larger renewable source, but there is no specification for renewable
HBX can be combined with the settings of any other input mode (Generator, UPS, etc.). The Mini Grid
See page 47 for more information on HBX, Grid Use Time, and Load Grid Transfer.
mode is also incompatible with the
Mini Grid
is based in the MATE3 and cannot function unless the MATE3 is installed and operating.
grid. HBX can only do so under specific circumstances.
from excessive discharge; however, most of its settings are automatic and do not allow customization.
size. Mini Grid cannot work properly unless the source is larger than the size of the loads. If this condition is not met, Mini Grid will not disconnect the inverter from the utility grid.
input mode is limited to its own settings and does not have access to certain functions of other modes.
Grid Use Time
mode or
HBX
and
Load Grid Transfer
Mini Grid
Mini Grid
, the user should consider the aspects of each.
should not be used with these functions.
or
HBX
functions of the MATE3
, but they do control the

Grid Zero

In
Grid Zero
mode, the Radian inverter runs primarily from battery (and renewable) energy while remaining connected to an AC source. The inverter only draws on the AC source (usually the utility grid) when no other energy is available. Using the DC sources, the inverter attempts to decrease the use of the AC source to zero.
In the MATE3 system display, the selectable options are batteries exceed the
DoD Volts
the battery voltage decreases to the
setting, the Radian will send power from the batteries to the loads. As
DoD Volts
setting, the inverter will reduce the rate of flow toward
DoD Volts
and
DoD Amps
. Any time the
zero. It will maintain the batteries at this setting.
The Radian inverter can manage large quantities of power. To prevent damage to the batteries from rapid discharge, the rate of discharge can be limited using the
DoD Amps
setting. This item should be
set lower than the amperage provided by the renewable source.
When
DoD Volts
the loads. However, it will also leave less of a battery reserve in the event of a grid failure.
When
DoD Volts
reserve. However, not as much renewable energy will be sent to the loads.
is set low, this mode allows more renewable energy to be delivered from the batteries to
is set high, the batteries will not be discharged as deeply and will retain more of a backup
The renewable energy source needs to exceed the size of the loads after accounting for all possible losses. The renewable source is also required to charge the batteries after this mode discharges them. The inverter’s battery charger does not function in
Grid Zero
mode.
BENEFITS
Grid Zero
possible if certain conditions are met. See the Notes section.
This mode puts battery and renewable energy to the most effective use without selling power to the utility grid and without dependence on the grid.
900-0145-01-01 Rev A 19
:
mode allows a system to minimize or eliminate dependence on the utility grid. This is only
Operation
The inverter remains connected to the utility grid in case the grid is needed. If large loads require the use of grid power, no transfer is necessary to support the loads.
NOTES
:
If the renewable energy source is not greater than the size of the inverter loads, this mode will not work well over time. The renewable source must be capable of charging the batteries as well as running the loads. This occurs when renewable energy production exceeds the
The inverter will offset the loads with excess renewable energy if it is available from the batteries. See page 35 for more information on Offset operation. However, the behavior of Offset in Grid Zero mode is different because it uses the
The inverter’s battery charger cannot be used in this mode. However, the menu settings and timer operations are not changed when this mode is selected.
The battery should be discharged whenever possible in the attempt to “zero” the grid usage. If the
setting is limited or loads are not present, the batteries will be unable to accept much renewable
Amps
recharging the next time it is available. The renewable energy will be wasted, leaving the system dependent on the utility grid more than necessary.
DoD Volts
exclusively.
DoD Amps
setting.
DoD
20 900-0145-01-01 Rev A
Operation
Table 1 Summary of Input Modes
Mode
Summary
Benefits
Cautions
Intended
Charger
devices
AC source
response time
reacts accordingly
Generator
Support
Grid­Tied
UPS
Accepts power from an irregular or low-quality AC source
Adds battery power to augment an AC source that has limited output
Inverter sells excess power (renewable) to utility
In grid failure, unit switches to batteries with fastest possible
Can use AC that may be unusable in other modes
Can charge even with a poor generator or low-quality AC source
Can use battery power in conjunction with AC source
Offset operation sends excess DC to loads
Bidirectional input
Can reduce utility bills and still provide backup
Offset operation sends excess DC to loads
Any additional Offset excess is sold to the grid
Quick backup for sensitive devices during grid outage
Will pass irregular or low-quality power to the output; could damage sensitive loads
Offset unavailable
Drains batteries during support; intended for intermittent use only
May not function with low-quality AC source
Requires utility approval
Other approvals may be required depending on electrical codes
Has exact requirements for accepting AC input
Requires renewable energy source
Uses higher idle power than other modes
Search function unavailable
Offset unavailable
Source:
Generator
Loads:
Non­sensitive
Source:
Grid or Generator
Loads:
Can be larger than
Source:
Grid
Loads:
Any type
Source:
Grid
Loads:
PC, audio, video, etc.
Performs three-stage charge and goes silent as specified by settings.
Performs three-stage charge and goes silent as specified by user settings.
Performs three-stage charge and goes silent as specified by user settings.
Performs three-stage charge and goes silent as specified by user settings.
Backup
In grid failure, unit switches batteries to support loads; this is the default mode
Mini Grid
Stays off grid most of the time; only uses grid when batteries low
Grid Zero
On-grid but actual grid use is “zeroed out” with battery and renewable power; does not sell or charge
900-0145-01-01 Rev A 21
Simple use compared to other modes; often used with generators for this reason
Less idle power than
Does not drain battery as in
Support
Can minimize/eliminate dependence on grid
Offset operation sends excess DC to loads (but only when on grid)
Can minimize/eliminate dependence on grid
Offset operation sends excess DC to loads at adjustable rate
Remains on-grid to avoid transfer problems
UPS
Has none of the special functions described in other modes, including Offset
Will not work properly unless renewable source is above a certain size
Conflicts with related modes in MATE3
Discharges batteries while remaining on grid
Will not work properly unless renewable source is above a certain size
Battery charger inoperative
Source:
Grid or Generator
Loads:
Any type
Source:
Grid
Loads:
Any type
Source:
Grid
Loads:
Any type
Performs three-stage charge and goes silent as specified by user settings.
Performs three-stage charge on reconnect; if charger is disabled, inverter emulates charge cycle from external source and
Charger inoperative; batteries must be charged using an external (renewable) energy source
Loading...
+ 53 hidden pages