Outback Power Systems FLEXpower ONE User Manual

System Overview –
Recommended Wire Sizes and Torque Requirements……..…… 1
Application Overviews
On-Grid Applications………………………………………..………. 2 Grid-Interactive Applications………………………………..……… 3 Off-Grid Applications……………………………………..…………. 4
Wiring Overviews
Contents
Off-Grid Applications (with FLEXnet DC)……………….....……… 7
Off-Grid Applications ………………………..………………..…….. 8
WARNING: SHOCK HAZARD
This information is for use by qualified personnel who meet all local and governmental code requirements for licensing and training for the installation of electrical power systems with AC and DC voltage up to 240 Vac and 150 Vdc.
Consult the FLEXpower ONE Installation Manual for detailed information on safety and installation procedures.
900-0094-01-00 Rev A.vsd\TOC\2012-03-02 ©2011 OutBack Power Technologies. All Rights Reserved.
Major Components
OutBack Power Technologies Products:
Inverter/Charger (FX, VFX, GVFX or GTFX models) FW250-AC-120V-NA FW250-DC-125, FW250-DC-175, or FW250-DC-250 System Display and Controller (MATE2 or MATE3) Charge Controller (FLEXmax 80 or FLEXmax 60) Remote Temperature Sensor (RTS) Communications Manager (HUB4 or HUB10) FLEXnet DC Monitor Surge Protector
Customer Supplied Components:
AC Source: ~ Utility Grid (if available) or ~ AC Generator with circuit breaker or
overcurrent device Main AC Distribution Panel AC Distribution Sub-Panel (Load Panel) Battery Bank (24 or 48 Vdc) Photovoltaic (PV) Array and PV Combiner Box
Reference Documentation:
FLEXpower ONE Installation Manual FX Inverter/Charger Installation Manuals FX Operator’s Manuals MATE Series or MATE3 Owner’s Manual HUB Owner’s Manual FLEXmax Series Charge Controllers Owner’s Manual FLEXnet DC Monitor Owner’s Manual
IMPORTANT:
All configurations must comply with local and national electric codes. Consult your local electric authority to ensure compliance. Actual wiring requirements may vary.
Factory wiring is not shown.
FLEXnet DC
FW250-AC-120V-
NA
Surge Protector
(Inside)
RTS
MATE
MATE RTS
FW250-DC-125
(175 or 250)
HUB Communication Manager
(HUB4 or HUB10)
System Display and
Controller (MATE2)
MAIN----------------
AC IN
3:02:14P
SUM STATUS SETUP ADV
INV
Inverter/
Charger
Charge Controller
(FLEXmax 80)
In 23.2 V 0.0 A Out 27.6 V 0.0 A
0.000 kW 0.0 kWH
AUX: OFF Sleeping
GFCI Outlet
(240V models only)
Side View
AC Breakers
(120V models only)
DC Breakers
Mechanical
GFCI Outlet
Battery Bank
Battery Status Monitor
GFDI Charge
Controller PV Array
Interlock (Bypass)
AC Wire Sizes and Torque Values
Wire Size Torque
AWG In-lb
#14 - 10 20
#8 25
#6 - 4 35
#3 35 #2 40 #1 50
1/0 50
It is recommended that conductors
be #6 AWG THHN copper, or larger,
unless local code requires otherwise.
AC Terminal
Compartment
DC Terminals
Torque Data for Breaker Lugs
Breaker Stud
Minimum DC Conductor based on DC Breaker
DC
Breaker
125 1/0 (70 mm2) 175 2/0 (70 mm2) 250 4/0 (120 mm2)
2
mm
2.5 – 6 10
16 – 25
35 35 50 70
rated to 75 °C (minimum)
Torque
In-lb Nm
M8 20 2.3
¼ - 20 35 4.0
5/16 - 18 50 5.6
3/8 - 16 225 25.4
Conductor
Size
Torque
In-lb Nm
50 5.6 225 25.4 225 25.4
IMPORTANT:
Not intended for use with
life support equipment.
Nm
2.3
2.8
4.0
4.0
4.5
5.6
5.6
System Overview
900-0094-01-00 Rev A.vsd\Wiring Info\2012-03-02 ©2011 OutBack Power Technologies. All Rights Reserved.
Page 1
Utility
Grid
or...
AC
Generator
HONDA
AC IN
FLEXnet DC
FW250-AC-120V-
NA
Surge Protector
(Inside)
MATE RTS
HUB Communication Manager
(HUB4 or HUB10)
System Display and
Controller (MATE2)
MAIN----------------
Inverter/
Charger
AC IN
Charge Controller
3:02:14P
SUM STATUS SETUP ADV
(FLEXmax 80)
INV
Major Components
OutBack Power System Products:
Inverter/Charger (FX or VFX models) FW250-AC-120V-NA FW250-DC-125, FW250-DC-175, or FW250-DC-250 System Display and Controller (MATE2 or MATE3) Charge Controller (FLEXmax 80 or FLEXmax 60) Remote Temperature Sensor (RTS) Communications Manager (HUB4 or HUB10) FLEXnet DC Monitor Surge Protector
Customer Supplied Components:
AC Source: ~ Utility Grid AC or ~ AC Generator with circuit breaker or
overcurrent device Main AC Distribution Panel AC Distribution Sub-Panel (Load Panel) Battery Bank (24 or 48 Vdc) Photovoltaic (PV) Array
On-Grid Overview
Renewable Energy (RE)
Loads
IMPORTANT: Example only. Actual configuration will vary
depending on the specific installation requirements.
AC OUT
FW250-DC-125
(175 or 250)
In 23.2 V 0.0 A Out 27.6 V 0.0 A
0.000 kW 0.0 kWH
AUX: OFF Sleeping
DC IN
PV Harvest
Battery
Charging
Inverter
Out
FLEXware
PV8 or PV12
I
OIOIOIOIOIOIOIO
Combiner
Box
AC
or
DC
DC OUT
Photovoltaic Array
(PV)
Battery Bank
Vented
24 or 48 Vdc
Battery
Enclosure
900-0094-01-00 Rev A.vsd\On Grid Overview\2012-03-02 ©2011 OutBack Power Technologies. All Rights Reserved.
Page 2
Utility Grid
AC IN
FLEXnet DC
FW250-AC-120V-
NA
HUB Communication Manager
(HUB4 or HUB10)
Major Components
OutBack Power System Products:
Inverter/Charger (GVFX or GTFX models only) FW250-AC-120V-NA FW250-DC-125, FW250-DC-175, or FW250-DC-250 System Display and Controller (MATE2 or MATE3) Charge Controller (FLEXmax 80 or FLEXmax 60) Remote Temperature Sensor (RTS) Communications Manager (HUB4 or HUB10) FLEXnet DC Monitor Surge Protector
OPTIONAL: An AC Generator with a circuit breaker or overcurrent device can be used in this application for backup purposes. However, a specific kind of generator is required. See the inverter literature for additional details.
AC OUT
1
(Selling)
1
Excess RE not being used by the AC Loads. The loads get priority over selling back to the grid.
Surge Protector
(Inside)
RTS
MATE
MATE RTS
Inverter/
Charger
System Display and
Controller (MATE2)
MAIN----------------
AC IN
Charge Controller
3:02:14P
SUM STATUS SETUP ADV
(FLEXmax 80)
INV
DC IN
PV Harvest
Customer Supplied Components:
AC Source: ~ Utility Grid AC Main AC Distribution Panel AC Distribution Sub-Panel (Load Panel) Battery Bank (24 or 48 Vdc) Photovoltaic (PV) Array
Renewable Energy (RE)
FLEXware
PV8 or PV12
I
OIOIOIOIOIOIOIO
Combiner
Box
Photovoltaic Array
(PV)
Loads
AC OUT2
2
from utility grid by default. IF RE is available, it gets 1 priority here. The remainder is sold. (See note 1 above).
IMPORTANT: Example only. Actual configuration will vary depending on the specific installation requirements.
900-0094-01-00 Rev A.vsd\Grid Tie Overview\2012-03-02 ©2011 OutBack Power Technologies. All Rights Reserved.
Grid-Tie Overview
In 23.2 V 0.0 A Out 27.6 V 0.0 A
0.000 kW 0.0 kWH
AUX: OFF Sleeping
Battery Bank
AC
Battery
Charging
st
FW250-DC-125
(175 or 250)
DC
Inverter Out
or
Vented Battery
Enclosure24 or 48 Vdc
DC OUT
Page 3
Major Components
AC
Generat
or
HONDA
Circuit Breaker
or Overcurrent
Device
AC IN
FLEXnet DC
FW250-AC-120V-
NA
Surge Protector
(Inside)
RTS
MATE
MATE RTS
HUB Communication Manager
(HUB4 or HUB10)
System Display and
Controller (MATE2)
MAIN----------------
AC IN
Inverter/
Charger
Charge Controller
3:02:14P
SUM STATUS SETUP ADV
(FLEXmax 80)
OutBack Power System Products:
Inverter/Charger (FX or VFX models) FW250-AC-120V-NA FW250-DC-125, FW250-DC-175, or FW250-DC-250 System Display and Controller (MATE2 or MATE3) Charge Controller (FLEXmax 80 or FLEXmax 60) Remote Temperature Sensor (RTS) Communications Manager (HUB4 or HUB10) FLEXnet DC Monitor Surge Protector
Customer Supplied Components:
AC Source: ~ AC Generator with a circuit breaker or
overcurrent device AC Distribution Sub-Panel (Load Panel) Battery Bank (24 or 48 Vdc)
INV
Photovoltaic (PV) Array
Renewable Energy (RE)
Loads
IMPORTANT: Example only. Actual configuration will vary
depending on the specific installation requirements.
AC OUT
FW250-DC-125
(175 or 250)
In 23.2 V 0.0 A Out 27.6 V 0.0 A
0.000 kW 0.0 kWH
AUX: OFF Sleeping
DC IN
PV Harvest
Battery
Charging
Inverter Out
FLEXware
PV8 or PV12
I
OIOIOIOIOIOIOIO
Combiner
Box
AC
or
DC
DC OUT
Photovoltaic Array
Battery Bank
Vented
24 or 48 Vdc
Battery
Enclosure
(PV)
Off-Grid Overview
900-0094-01-00 Rev A.vsd\Off Grid Overview\2012-03-02 ©2011 OutBack Power Technologies. All Rights Reserved.
Page 4
AC LEGEND
Neutral
N
AC Distribution
Panel
(Main Panel)
(120/240 Vac)
L1
L2
Input
Output
Bypass
Outlet
(with FLEXnet DC)
IMPORTANT: Example only. Actual wiring may vary.
L1
Factory wiring not shown. All configurations must comply
with local and national electric codes. Consult your local
electric authority to ensure compliance.
Photovoltaic Array
N
(PV)
L1
On-Grid Wiring
HOT L1
L1
Ground
Primary System
Ground
(Ground Electrode
Conductor)
GROUND ROD
AC Sub-Panel
60 A Circuit
(Maximum)
(120 Vac)
Breaker
GROUND
NEUTRAL
L1
N
FLEXware PV8
L1
MATE RTS
AC IN
MAIN----------------
3:02:14P
SUM STATUS SETUP ADV
INV
Combiner Box
I
OIOIOIOIOIOIO
O
I
DC LEGEND
Negative
Positive
HOT
Loads
L1
(120 Vac)
900-0094-01-00 Rev A.vsd\On Grid Wiring\2012-03-02 ©2011 OutBack Power Technologies. All Rights Reserved.
NEUTRAL
N
GROUND
Ground
In 23.2 V 0.0 A
N
Out 27.6 V 0.0 A
0.000 kW 0.0 kWH
AUX: OFF Sleeping
Battery Bank
Battery
Status
GFDI
CC
PV Circuit
Breaker
1
Connects to the terminal on the circuit breaker that is opposite the inverter DC cable.
1
(RTS)
24 or 48 Vdc
Vented Battery
Enclosure
Page 5
AC LEGEND
Neutral
HOT L1
N
L1
AC Distribution
Panel
(Main Panel)
(120/240 Vac)
L1
L2
NEUTRAL
Input
Output
Bypass
Outlet
IMPORTANT: Example only. Actual wiring may vary.
L1
Factory wiring not shown. All configurations must
comply with local and national electric codes. Consult
your local electric authority to ensure compliance.
N
L1
Photovoltaic Array
(PV)
On-Grid Wiring
Ground
Primary System
Ground
(Ground Electrode
Conductor)
GROUND ROD
AC Sub-Panel
(120 Vac)
HOT
60 A Circuit
Breaker
(Maximum)
GROUND
N
FLEXware
L1
MATE RTS
L1
AC IN
MAIN----------------
3:02:14P
SUM STATUS SETUP ADV
INV
PV8
I
OIOIOIOIOIOIO
O
I
DC LEGEND
Negative
Positive
Ground
Loads
L1
(120 Vac)
900-0094-01-00 Rev A.vsd\On Grid Wiring No FNDC\2012-03-02 ©2011 OutBack Power Technologies. All Rights Reserved.
NEUTRAL
N
GROUND
In 23.2 V 0.0 A
N
Out 27.6 V 0.0 A
0.000 kW 0.0 kWH
AUX: OFF Sleeping
Battery Bank
(RTS)
1
GFDI
CC
Vented
PV Circuit
Breaker
1
Connects to the terminal on the circuit breaker that is opposite the inverter DC cable.
24 or 48 Vdc
Battery
Enclosure
Page 6
(with FLEXnet DC)
AC LEGEND
AC
Generator
Neutral
HOT L1
Ground
Some generators may have
1
an integrated circuit breaker or disconnect device. If not, one must be provided.
Primary System Ground
(Ground Electrode Conductor)
N
L1
Generator
1
Terminals
(120 Vac)
HOT
(L1)
Neutral
NL1
Input
Output
Bypass
Outlet
MATE RTS
N
L1
IMPORTANT: Example only. Actual wiring may vary.
Factory wiring not shown. All configurations must
comply with local and national electric codes. Consult your
local electric authority to ensure compliance.
N
Photovoltaic Array
L1
FLEXware
MAIN----------------
AC IN
3:02:14P
SUM STATUS SETUP ADV
INV
PV8
I
OIOIOIOIOIOIO
O
I
(PV)
Off-Grid Wiring
GROUND ROD
AC Distribution Panel
(120 Vac)
Loads
(120 Vac)
HOT
L1
N
GROUND
NEUTRAL
DC LEGEND
Negative
Positive
L1
Ground
In 23.2 V 0.0 A Out 27.6 V 0.0 A
N
0.000 kW 0.0 kWH
AUX: OFF Sleeping
Battery Bank
(RTS)
2
Battery
Status
GFDI
CC
Vented
PV Circuit
Breaker
24 or 48 Vdc
Battery
Enclosure
900-0094-01-00 Rev A.vsd\off grid wiring\2012-03-02 ©2011 OutBack Power Technologies. All Rights Reserved.
2
Connects to the terminal on the circuit breaker that is opposite the inverter DC cable.
Page 7
AC LEGEND
Neutral
N
AC
Generator
(120 Vac)
N
L1
IMPORTANT: Example only. Actual wiring may vary.
Factory wiring not shown. All configurations must
comply with local and national electric codes. Consult your
local electric authority to ensure compliance.
HOT L1
L1
Ground
Generator
1
Terminals
Some generators may have
1
an integrated circuit breaker or disconnect device. If not, one must be provided.
Primary System Ground
(Ground Electrode Conductor)
GROUND ROD
HOT
(L1)
L1
Neutral
Input
Output
Bypass
Outlet
N
L1
N
Photovoltaic Array
(PV)
FLEXware
PV8
I
OIOIOIOIOIOIO
O
I
MATE RTS
MAIN----------------
AC IN
3:02:14P
SUM STATUS SETUP ADV
INV
Off-Grid Wiring
DC LEGEND
AC Distribution Panel
Loads
(120 Vac)
(120 Vac)
HOT
N
L1
NEUTRAL
GROUND
Negative
L1
Positive
Ground
In 23.2 V 0.0 A Out 27.6 V 0.0 A
N
0.000 kW 0.0 kWH
AUX: OFF Sleeping
Battery Bank
(RTS)
2
GFDI
CC
Vented
PV Circuit
Breaker
24 or 48 Vdc
Battery
Enclosure
900-0094-01-00 Rev A.vsd\Off Grid Wiring No FNDC\2012-03-02 ©2011 OutBack Power Technologies. All Rights Reserved.
2
Connects to the terminal on the circuit breaker that is opposite the inverter DC cable.
Page 8
About OutBack Power Technologies
OutBack Power Technologies is a leader in advanced energy conversion technology. Our products include true sine wave inverter/chargers, maximum power point tracking charge controllers, and system communication components, as well as circuit breakers, batteries, accessories, and assembled systems.
Contact Information
Telephone: +1.360.435.6030 (Main)
+1.360.618.4363 (Technical Support) +1.360.435.6019 (Fax)
Mailing Address: OutBack Power Technologies Sales & Marketing
5917 - 195th Street N.E. 6115 – 192nd Street NE Arlington, WA 98223 USA Arlington, WA 98223 USA
E-mail: Support@outbackpower.com
Web Site: www.outbackpower.com
Disclaimer
UNLESS SPECIFICALLY AGREED TO IN WRITING, OUTBACK POWER TECHNOLOGIES: (a) MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF
ANY TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION.
(b) ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSS OR DAMAGE, WHETHER DIRECT, INDIRECT, CONSEQUENTIAL OR INCIDENTAL, WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION. THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USER’S RISK.
Warranty Summary
OutBack Power Technologies warrants that the products it manufactures will be free from defects in materials and workmanship for a period of five (5) years subject to the conditions set forth in the warranty detail, found in the product manual.
OutBack Power Technologies cannot be responsible for system failure, damages, or injury resulting from improper installation of their products.
Notice of Copyright
FLEXpower ONE System Overview © January 2012 by OutBack Power Technologies. All Rights Reserved.
Trademarks
OutBack Power is a registered trademark of OutBack Power Technologies.
Date and Revision
January 2012, Revision A
Part Number
900-0094-01-00 Rev A
North America: 5917 - 195th Street N.E. Arlington, WA USA +1.360.435.6030
900-0131-01-00 Rev A
Loading...