Ouellet OHX User Manual

Page 1
OHX
OHX
OHX
Explosion-Proof Unit Heater
Owner’s Manual, Version: OHX-OM-E
This manual covers installation, maintenance,
repair, and replacement parts.
Forced-Air Heater for Hazardous Locations
Class I, Divisions 1 & 2, Groups C & D
Class II, Divisions 1 & 2, Groups F & G
Temperature Code T3B (35 kW = T3A)
————————————————————————————————————-
Class I, Zones 1 & 2 , Groups IIA & IIB, T3
235730
WARNING!
Please adhere to all instructions published in this manual.
Failure to do so may be dangerous and may void your warranty.
Note: OHX heaters should not be exposed to rain or snow. This applies to installed & stored heaters.
The OHX heater should not be modified in any way.
www.Ouellet.com
Printed in Canada
Part No. OHX-OM-E
Page 2
OHX Model Coding
Model Code Sequence
Factory Assigned
OHX 100 3 6 - A - T - A
Model Series
Power Output
5 kW 050
7.5 kW 075 10 kW 100 15 kW 150 20 kW 200 25 kW 250 30 kW 300 35 kW 350
12 inch fan size 12 inch fan size 12 inch fan size 16 inch fan size 16 inch fan size 20 inch fan size 20 inch fan size 20 inch fan size
Phase
1 Phase
0
3 Phase 3
OHX Physical Dimensions
G max
11"
[279]
A
0.375" [10]
1" NPT, Main electrical entry for disconnect option
1" NPT, Main electrical entry no disconnect fitted
3.75"
8.4"
[214]
5.0"
[127]
[95]
4 x Ø 9/16" [14] mounting holes
B
2.25" [57]
3.375" [86]
3/4" NPT, External thermostat entry
Louvres
1.4" [36] max
4.7"
[118]
Product Revision No.
For minor revisions
Factory Built-in Options
N No options selected
Integral thermostat only
T D Disconnect switch only
Disconnect switch &
C
integral thermostat
Control Voltage
A 120 Volt B 24 Volt
Heater Line Voltage
8 208 Volt 0 240 Volt 4 480 Volt 6 600 Volt
6.6"
[168]
Heater Size
Dim.
A
B
C
D
E
F
G
12
(5-10kW)
Inches
(mm)
7.5
(190.5)
18.19 (462)
16.3
(414)
19
(483)
19.45 (494)
3.1
(79)
22.25 (565)
E
C
16
(15-20kW)
Inches
(mm)
7.5
(190.5)
22.28 (566)
20.28 (515)
23
(584)
23.46 (596)
5.1
(130)
22.25 (565)
20
(25-35kW)
Inches
(mm)
7.5
(190.5)
26.26 (667)
24.29 (617)
27
(686)
27.44 (697)
7.1
(180)
23.25 (591)
0.25" [6]
F
F
3.375" [86]
2
D
0.25" [6]
Page 3
OHX Specifications By Model Size
Model 5 to 10 kW 15 to 20 kW 25 to 35 kW Fan Diameter in. (mm) 12 (304.8) 16 (406.4) 20 (508.0) Nominal kW 5 7.5 10 15 20 25 30 Air Delivery CFM 400 600 800 1200 1700 2100 3000
m Approx. Air Velocity FPM 47 718 958 808 1145 916 1309 m/s 2.4 3.6 4.9 4.1 5.8 4.6 6.6 Approx. Horizontal Air Throw ft. 15 22 30 33 46 41 61 m 4.6 6.7 9.1 10.1 14.0 12.5 18.6 Motor Power HP (Watts) ¼ (186) ¼ (186) ½ (373) Maximum Mounting Height ft. 7 7.5 9.5 10 11 12 15
(to underside of heater) m Approx. Net Weight
Lbs (kg) Approx. Shipping Weight
Lbs (kg) (with disconnect)
OHX General Specifications
Certification
(without disconnect)
(with disconnect)
(without disconnect)
3
/hr 680 1019 1359 2039 2888 3568 5097
2.1 2.3 2.9 3.0 3.4 3.6 4.6 129 (58.5) 133 (60.3) 161 (73.0) 192 (87.1)
142 (64.4) 146 (66.2) 174 (78.9) 205 (92.9) 188 (85.3) 192 (87.1) 224 (101.6) 261 (118.4) 201 (91.2) 205 (93.0) 237 (107.5) 274 (124.3)
CSA
- 235730 - Certified to Canadian and U.S. standards
C/US
Class I, Divisions 1 & 2, Groups C & D Class II, Divisions 1 & 2, Groups F & G Temperature Code T3B (35 kW = T3A)
Class I, Zones 1 & 2, Groups IIA & IIB, T3
Approvals
Cabinet
North American Hazardous Location Classifications
Temperature Code
Cabinet Material
Fan Guard
Division System - T3B 165°C (329°F); [35 kW = T3A 180°C (356°F)] Zone System - T3 200°C (392°F)
14-gauge (0.075 in.) (1.9 mm) steel. Red epoxy/polyester powder coated with five-stage pretreatment, including iron phosphate.
Split design with close wire spacing. A 3/8 in. (9.5 mm) diameter probe will not enter. Black polyester powder coated.
————————————————————————————————————————
Louver Blades Anodized extruded aluminum. Conduit Materials & Fittings Plated steel an d aluminum alloy for corrosion resistance. Fasteners Zinc plated steel for corrosion resistance. Enclosures Cast aluminum (non-copper alloy) NEMA Type 7 & 9 with O-ring. Mounting Holes 9/16 in. diameter holes – Four located on the top face of heater.
Explosion-proof, thermally protected, 1725 RPM permanently lubricated b all bearing type with 56 frame and “easy-off” fan blade replacement feature.
Motor/Fan
Motor Type Fan Three-blade aluminum, steel spider and hub with 5/8 in. bore
Heating Elements Long-life, low watt-density, high grade metal-sheathed elements. Heat Transfer Fluid Ethylene glycol and water including corrosion inhibitors.
Heat
Exchanger
Header Material Carbon steel.
Carbon steel shells and carbon steel tubes with copper-free, roll-formed aluminum fins @ 10 fins per in. Evacuated and sealed. Sprayed
ExCaliber
TM
Core
with black, high heat enamel paint. One automatic reset rated for 100,000 cycles, and one manual reset. Both
are snap-action bimetal type, open on temperature rise.
Protection
Temperature High Limits Pressure Relief High-quality preset 100 psig (689 kPa) stainless steel pressure relief device.
Control Circuit Built in 120 V control. Optional 24V control (recommended) is available.
40 FLA (50 A resistive per pole) Definite Purpose. Rated for 500,000 mechanical operations.
x 1 1/4 in., 120V = 1/4 A, 24V = 1 A.
Controls
Control Contactor Control Transformer Multitap primary, 120V or 24V secondary.
Fuse Protection Thermal delay fuse with spare, 1/4 in. Room Thermostat (optional) Built in, OHX-T explosion-proof thermostat, 40°F to 80°F (5°C to 27°C)
Load
Isolation
Operating
Limits
Disconnect Switch (optional) Ambient Temperature -40°F to 104°F (-40°C to 40°C). Storage: -40°F to 140°F (-40°C to 60°C)
Maximum Altitude 10,000 ft (3048 m) above sea level.
Built-in, OHX-DIS explosion-proof disconnect switch, 600V, 50A max with lock-out feature. Also available in a wall mount version.
35
3
Page 4
— WARNING! —
Read and follow the instructions in this manual. Failure to do so may result in severe or fatal injury.
IMPORTANT SAFETY INFORMATION
1. Heater is to be connected and serviced only by qualified electrician experienced with hazardous location equipment. It is the responsibility of the installer to verify the safety and suitability of the installation.
2. Installation and wiring of the heater must adhere to all applicable codes. Heater must be effectively grounded to eliminate shock hazard.
3. Heater is to be used only in atmospheres having an ignition temperature higher than the heat er’s maximum rated operating temperature as shown on the heater data plate. For details of hazardous locations with potential for explosion, refer to the Canadian Electrical Code, Part 1, Section 18 or Articles 500 through 516 of the National Electrical Code.
4. Do not operate heater in ambient temperatures above 40
5. Do not plug heater outlet with gloves, clothing, etc. or operate heater with louvers fully closed.
6. Explosion/Electric Shock Hazard. Disconnect heater from power supply or fuse box before o pening en­closures or servicing heater. Lock the switch in the “OFF” (open) position and/or tag the switch to prevent unexpected power application.
7. Operate the heater only while it is permanently mounted in an upright position. Failure to comply will cause overheating of the heat exchanger and shutting down of the unit by tripping the high temperature cutout.
8. This heater is equipped with two bimetal thermal high-limit cutouts, one automatic reset type and one manual reset type. The heater is not to be operated with the high-limit cutouts disabled or disconnected from the control circuit.
9. Keep all electrical enclosure covers tightly closed and secured with all bolts and threads. Cover joints must be clean before replacing covers. Keep away from rain or snow. Heater is for dry indoor use only.
10. All unused threaded openings not used for supply wiring or remote mount room thermostat must be fitted with threaded plugs approved for use in hazardous locations.
11. The heat exchanger is a factory vacuum-sealed unit. Do not attempt to loosen or tighten the vacuum plug or pressure relief device. A loss of vacuum could cause nuisance tripping of the thermal cutouts or high pressures which will cause the relief device to actuate with an accompanying loss of fluid.
12. The heat exchanger is filled with a mixture of water and inhibited ethylene glycol which is poisonous. Contact with the fluid at operating temperatures may produce a burn hazard. Suggested first aid consists of flushing eyes with plenty of water and to wash off skin in flowing water or shower. If any fluid leakage occurs from the heater, disconnect it from the power supply and have the heat exchanger replaced with a factory supplied unit.
°C (104°F).
13. Heater must be kept clean. When operating in a dirty environment, regularly clean the fin tubes, fan, and fan guard. Refer to recommended maintenance procedures.
14. Do not operate heater in atmospheres which are corrosive to aluminum or steel.
15. See applicable electrical codes for seal requirements in field installed conduits. Factory installed conduits require no further sealing.
16. Crackling or pinging noises within the heat exchanger during start up may occur. This is normal.
17. Air discharge at the bottom of the heater may be warmer than at the top. This is normal.
18. Do not attempt to install a Remote Fan Only Switch. Do not modify the heater in any way.
19. Use factory approved replacement parts only.
20. Contact factory for any questions or concerns.
4
Page 5
— WARNING! —
Read and follow the instructions in this manual. Failure to do so may result in severe or fatal injury.
— INSTALLATION —
Mechanical
Location
Please follow guidelines below for optimum heating results:
1. Do not install heaters such that airflow is blocked or impeded by equipment or walls.
2. For occupant comfort, position heaters so that air discharge is dire cted across areas of highest heat loss, such as doors, windows, and outside walls.
3. For large areas, arrange heaters such that the air discharge of on e heater is directed towards the inlet of the next heater. This sets up a rotational airflow with air circulation in the central area of the building.
4. For equipment freeze protection, direct air discharge at equipment.
5. For large workshops or warehouses it may be acceptable to use fewer, larger heaters.
6. Locate remote mount room thermostat on interior partition walls or posts away from cold drafts, internal heat sources, and away from heater discharge air streams.
Mounting
1. A variety of mounting brackets are available from the factory to aid in installation.
2. The heater is designed to be installed in an upright and level position. All models should not be more than ±15 degrees or 2.5 in. (63.5 mm) from level when measured front-to-back, and ± 5 degrees 1.7 in. (43.2 mm) on 5 to 10 kW models, 2.0 in. (50.8 mm) on 15 to 20 kW models, and 2.4 in. (60.9 mm) on 25 to 35 kW models from level when measured side-to-side. Failure to comply will cause high limit shut down. Refer to heater data plate for tilt angles.
3. If using mounting hardware or a supporting structure n ot supplied by the factory, the unit should be suspended through the four 9/16 in. (14 mm) mounting holes on top of the unit with 1/2 in. UNC bolts. Lock washers should be used on all mounting nuts and bolts to ensure they don’t vibrate or work loose due to fan vibration or other vibration transmitted to the heater. If in doubt consult factory.
4. It is essential that adequate structural support be provided for in stallation. The mounting structure must be strong enough to support the heaters weight, provide sufficient stiffness to prevent excessive vibration, and withstand all probable abusive situations such as transportable installations wh ere truck off­loading impacts, etc. may occur. Refer to table on Page 3, OHX Specifications by Model Size
, for heater net
weights.
Mounting Heights and Clearances
1. To ensure that warm air reaches the floor observe the recommended maximum mounting heights in table on Page 3, OHX Specifications by Model Size. Heaters may be mounted at higher elevations and still pro­vide warm air at floor level however, the maximum mounting elevation at which this occurs depends on lo­cation and operational conditions.
2. Louvers may be adjusted to provide greater downward deflection of the discharge air. However, louvers must not be set less than 30 degrees of the closed position.
3. Leave at least 10 in. (254 mm) clearance between the rear of the motor and the nearest obstruction.
4. For easy removal of the core, leave clearance beneath the heater equal to the height of the heater cabinet plus 2 in. (51 mm).
5
Page 6
— WARNING! —
Read and follow the instructions in this manual. Failure to do so may result in severe or fatal injury.
— INSTALLATION —
Electrical
1. Heater is to be connected and serviced only by qualified electrician experienced with hazardous location equipment. It is the responsi­bility of the installer to verify the safety and suitability of the installation.
2. Explosion/Electric Shock Hazard. Disconnect heater from power supply or fuse box before opening enclosures or servicing heater. Lock the switch in the “OFF” (open) position and/or tag the switch to prevent unexpected power application.
3. Use copper conductors only rated wire. Refer to “Supply Wire Requirements” table and heater data plate for conductor wire rating.
4. Installation must include appropriate over-current protection de­vices (fusing or circuit breakers) as required by the CEC or NEC. Refer to “Supply Wire Requirements” table and heater data plate for current ratings. Supply voltage is to be within 10% of the data plate voltage.
5. Confirm that the electrical power supply matches the nameplate voltage, phase, amperage and frequency rating of the heater to be connected.
6. Supply conductors and ground conductor pass through the 1 in. NPT rigid conduit opening on the control enclosure.
7. Proper installation of the heater requires that an adequate ground­ing conductor be connected to the ground terminal. This terminal is made of copper and is located on the top right-hand corner of the printed circuit board within the control enclosure.
8. Heater may be supplied with a factory installed integral room ther­mostat (See Figure 1). On heaters not supplied with this option, it is recommended that an external explosion-proof room ther- mostat be used. The wiring to the external thermostat must be copper wire, 16 gauge minimum (for Class II) or 14 gauge mini­mum (for Class I). Thermostat conductors may also be passed through the 1 in. NPT conduit opening or through the convenient 3/4 in. NPT dedicated external thermostat conduit opening in the enclosure. Connect the external thermostat conductors to the printed circuit board terminal block marked “T’STAT”. The built-in control transformer supplies the heater with either 120V or 24V for internal unit operation. This voltage will appear across the thermo­stat contacts when they are open. The minimum thermostat con­tact rating should be 1 amp @ 120 VAC. Refer to nameplate for control voltage of unit.
9. Refer to wiring diagram on Page 9 to ensure that all connections are as required and securely fastened.
10. For heaters supplied with a factory installed integral disconnect switch (See Figure 1), field wiring is as fol­lows:
a. Remove the Disconnect cover assembly from the base by removing the six (6) cover bolts. Set the cover
assembly aside. CAUTION: Damaging the mating surfaces of the enclosure could destroy the flame path and jeopardize the integrity of the flame proof enclosure.
b. Supply conductors and ground conductor pass through the 1 in. NPT rigid conduit opening located on the
top or bottom of Disconnect Enclosure. Supply conductors to be wired to DIN rail mounted Disconnect Switch inside. Ground conductor to be wired to Ground Lug fastened to inside of Disconnect Enclosure. Refer to wiring diagram on Page 9.
c. Attach cover to the enclosure using the six (6) bolts. Tighten to 150 inch-pounds ± 5 in-lbs.
11. All unused threaded openings in enclosures, not used for supply wiring or external room thermostat, must be fitted with threaded plugs approved for use in hazardous locations (included). Factory installed conduits require no additional sealing.
12. Installer must seal each conduit run within 18” (457 mm) of enclosure. This seal must be suitable and listed for hazardous locations.
13. Ensure that input conductors and conduit have adequate strain relief at installation.
14. Before application of electrical power, recheck all connections to ensure compliance with the wiring diagram and any code require­ments. Remove any foreign objects from the control box and heater. Reinstall cover tightly.
15. On all three-phase heaters, it is necessary to verify that the fan rotation is correct (counter clockwise when facing the rear of the heater). If air delivery is not from the front of the heater, reverse any two supply leads at the main power contactor located in the control enclosure.
16. The explosion-proof control enclosure and element enclosures are designed with O-rings, threaded joints and metal-to-metal contact at the lid or cover joint to prevent an explosion. Do not attempt to install gasket material of any type at these joints. A light coating of anti­seize compound may be applied to the threads to prevent seizing.
for supply wires and approved explosion-proof means of wiring during installation. Use minimum 90°C
OHX Supply Wire Requirements
Model
OHX05008­OHX05000­OHX05038­OHX05030­OHX05034­OHX05036­OHX07508­OHX07500­OHX07538­OHX07530­OHX07534­OHX07536­OHX10000­OHX10038­OHX10030­OHX10034­OHX10036­OHX15038­OHX15030­OHX15034­OHX15036­OHX20034­OHX20036­OHX25034­OHX25036­OHX30034­OHX30036-
OHX35034­OHX35036-
kW Volts Ø
5 208 1 26.5 33.2 35 8 5 240 1 23.3 29.2 30 10 5 208 3 14.6 18.2 20 12 5 240 3 12.7 15.9 20 12 5 480 3 6.7 8.4 15 14 5 600 3 5.5 6.9 15 14
7.5 208 1 38.6 48.2 50 6
7.5 240 1 33.8 42.2 50 8
7.5 208 3 21.5 26.9 30 10
7.5 240 3 18.7 23.4 30 10
7.5 480 3 9.7 12.2 15 14
7.5 600 3 7.9 9.9 15 14 10 240 1 44.2 55.2 60 6 10 208 3 28.5 35.6 40 8 10 240 3 24.8 30.9 35 8 10 480 3 12.7 15.9 20 12 10 600 3 10.3 12.9 15 14 15 208 3 42.3 52.9 60 6 15 240 3 36.8 46.0 50 6 15 480 3 18.7 23.4 25 10 15 600 3 15.1 18.9 20 12 20 480 3 24.8 30.9 35 8 20 600 3 19.9 24.9 25 10 25 480 3 31.1 38.8 40 8 25 600 3 25.1 31.3 35 8 30 480 3 37.1 46.4 50 6 30 600 3 29.9 37.3 40 8 35 480 3 43.1 53.9 60 6 35 600 3 34.7 43.3 50 6
Current
Amps
Minimum Ampacity
Circuit
Max F
use
Amps
Supply
Wire
90°C (AWG)
Total
Figure 1
6
Page 7
— WARNING! —
Heater is to be serviced only by qualified electrician experienced with hazardous location equipment. Explosion/Electric Shock Hazard. Disconnect heater from power supply or fuse box before opening
enclosures or servicing heater. Lock the switch in the “OFF” (open) position and/or tag the switch to prevent
unexpected power application.
— Repair and Replacement —
Heat Exchanger Replacement
The heat exchanger has been air evacuated, fluid filled, and sealed at factory and is not field repairable. Replacement heat exchangers are available from the factory and are inspected and electrically tested for correct heat output and proper operation of the high-limits.
1. Explosion/Electric Shock Hazard. Disconnect heater from power supply or fuse box before op ening enclosures or servicing heater. Lock the switch in the “OFF” (open) position and/or tag the switch to prevent unexpected power appli­cation.
2. To prevent burn hazard, be sure heat exchanger and fluid has been allowed to cool before proceeding.
3. Remove cabinet bottom panel, element housing cover, element enclosure cover, & control enclosure cover.
4. From the control enclosure, disconnect two high-limit wires from printed circuit board terminal block marked 3 & 4 and disconnect three output heating element wires from contactor terminals marked T1, T2, & T3.
5. Slightly loosen all cabinet bolts and louver screws to prevent heat exchanger from binding.
6. The heat exchanger is secured by three 1/4 in. bolts on the right-side cabinet panel (when facing front of heater) and one 1/4 in. bolt located on the left side of heater. On 5 - 10kW models the left-side bolt is located at the top right-hand foot of control enclosure. On 15 - 35kW models the left-side bolt is located above the control enclosure. With an assis­tant supporting the weight of the heat exchanger remove these 4 bolts. Carefully lower the heat exchanger from the cabinet.
7. Reverse the above procedure when installing a new heat exchanger.
Temperature High-Limit Replacement
This heat-exchanger includes one automatic reset & one manual reset temperature high-l imit that are wired in series. The automatic reset high-limit is rated for 100,000 cycles and is for a temporary failure condition. Continuo us nuisance tripping of the automatic reset is generally not the fault of the high-limit but is usually caused by incorrect operating voltage, blocked air inlet or outlet, fan/motor malfunction, high ambient temperatures, excessively dirty heat exchanger or leaking heat ex­changer. Care should be taken to determine the exact reason that the automatic reset high-limit control tripped so the problem can be resolved immediately. The automatic reset high-limit normally fails in the open position, however, it can also fail closed.
If the automatic reset fails in the open position the heater will not function and the high-limit should be replaced. The
occurrence of the manual reset high-limit control to trip is an abnormal condition and indicates that the automatic reset high-limit has failed in the closed position. If this occurs remove the heater from service immediately and replace the automatic reset high-limit. Determine the exact reason that the automatic reset high-limit control tripped so the problem can be resolved immediately. If the manual reset high-limit shuts down the heater it will have to
be reset by pressing on the small reset button protruding from the center of the high-limit device.
1. De-energize the heater electrical supply circuit.
2. Remove element housing cover, and element enclosure cover.
3. Remove spade connection from the automatic reset high limit lugs.
4. Remove automatic reset high-limit assembly by unscrewing, and clean the inside of the thermowell. A clean thermowell ensures good thermal contact.
5. Replace high-limit with a factory supplied unit only. Apply a small drop of heat sink conductive cement aroun d the base of the high-limit, but not on the threads, and screw into thermowell. Attach spades to automatic reset high-limit .
6. Replace control enclosure cover, element housing cover, and element enclosure cover.
7. Energize the heater electrical supply circuit and let run for 15 minutes to reach a stable operating temperature.
8. If heater operation appears to be normal, place unit into service.
7
Page 8
— WARNING! —
Heater is to be serviced only by qualified electrician experienced with hazardous location equipment. Explosion/Electric Shock Hazard. Disconnect heater from power supply or fuse box before opening
enclosures or servicing heater. Lock the switch in the “OFF” (open) position and/or tag the switch to prevent
unexpected power application.
— Repair and Replacement, Continued —
Fan, Fan Guard or Motor Replacement
The motor is a sealed unit that requires no lubrication. If the motor is defective, it must be replaced with an original factory supplied motor.
1. Remove four bolts holding motor to the motor mount, and covers from junction box and control enclosure. On units with an integral room thermostat, remove 4 bolts on front face of thermostat enclosure .
2. Detach and remove two-piece fan guard assembly by removing top and bottom screws that attach the fan guard to the cabinet.
3. Loosen fan blade set screw and remove fan blade from end of motor shaft leaving it in fan panel opening.
4. Unscrew the expansion union fitting between motor and motor enclosure (or integral thermostat enclosure).
5. If replacing motor, note wire connections for future reference and cut all wires leading to the motor close to the terminations. All motor wires are permanently marked according to the nameplate on the motor. Lift the motor assembly off the motor mount.
6. If replacing fan blade only do not cut any wires and move the motor assembly back sufficient to assist fan blade removal.
7. To reassemble, place fan blade inside fan panel opening and then place motor onto motor mount. Slip fan blade onto motor shaft and ensure fan hub is flush with end of motor shaft. Tighten set screw to 150 in-lbs torque.
8. Fasten the two-piece fan guards to the cabinet.
9. Tighten conduit fittings between motor and motor enclosure (or integral thermostat enclosure). Center fan in fan-panel opening and leave approximately 1/16” to 3/16” (1.6 to 4.8 mm) gap between motor face and fan guard.
10. Bolt motor to motor mount, tighten nuts to 250 in-lbs torque. Manually spin the fan blade to ensure it rotates freely before reconnecting heater to power supply. Fan must rotate counterclockwise when viewed from rear of heater.
Fan blade set screw (1 only) 150 5/16 - 18 UNC motor nuts 250 5/16 - 18 UNC motor mount bolts 250 1/4 - 20 UNC fan panel bolts 100 1/4 - 20 UNC fan guard self tapping screws 100 #10 - 24 UNC louver blade screws 28
Torque Settings
Item Torque (in-lbs)
Contactor
1. Loosen, but do not remove contactor mounting screws. Slide contactor off mounting screws.
2. Replace with a factory supplied contactor of the same rating.
Transformer
1. Replace with a factory supplied transformer of the same rating.
2. On the new transformer, select primary wires to match heater voltage. Ensure that the correct trans-
former secondary lead is grounded (see wiring diagram). Individually terminate all unused wires using closed end connections.
Printed Circuit Board
1. Replace with a factory supplied P.C. Board.
Thermal Delay Fuse
1. Replace fuse with one of the same type and rating as indicated on P.C. Board or refer to parts list. An
extra fuse should be stored in the clips marked “SPARE”.
8
Page 9
— Warning —
Wiring should only be connected by qualified personnel experienced in electrical work.
— Electrical Wiring —
9
Page 10
— Assembly Diagram —
14
Optional built-in disconnect switch
16
21
36
25
27
28
34
24
33
26
30
29
35
31
32
3 Phase
10
1 Phase
Page 11
— Parts List —
*** Please have model & serial number available before calling ***
Item
No.
Description
5 & 7.5 kW 10 kW 15 & 20 kW 25, 30 & 35 kW
1 Core assembly ( with bus bars) Specify Voltage, phase, and kilowatts ( V-Ph-kW) 2 Bottom panel OHX1-12-2 OHX1-16-2 OHX1-20-2 3 Left side panel OHX1-12-3 OHX1-16-3 OHX1-20-3 4 Louver blades OHX1-12-4 OHX1-16-4 OHX1-20-4 5 Top panel OHX1-12-5 OHX1-16-5 OHX1-20-5 6 Right side panel OHX1-12-6 OHX1-16-6 OHX1-20-6 7 Fan panel OHX1-12-7 OHX1-16-7 OHX1-20-7
8 Fan blades
5.0 kW = OHX-12-050
7.5 kW = OHX-12-075
9 Fan guard (2 pieces) OHX1-12-9 OHX1-16-9 OHX1-20-9
10 Motor, explosion-proof
11 Right side motor bracket OHX1-11 12 Motor base OHX1-12-12 OHX1-16-12 OHX1-20-12 13 Left side motor bracket OHX1-13 14 Expansion union, female OHX1-14 15 Conduit, expansion union to elbow OHX1-12-15 OHX1-16-15 OHX1-20-15
15A Reducing bushing OHX1-15A
16 Thermostat, ex-proof OHX-TM
16A Elbow, 90° OHX1-16A
17 Conduit, potted 18 Conduit, vertical OHX1-12-18 OHX1-16-18 OHX1-20-18
19 O-ring, element enclosure cover OHX1-19 20 Cover, element enclosure OHX1-20 21 Guard, element enclosure OHX1-21 22 Conduit, motor box to enclosure OHX1-12-22 OHX1-20-22
22A Union OHX1-22A
23 Box, motor outlet OHX1-23
23A Conduit, motor to motor box OHX1-12-23A OHX1-16-23A OHX1-20-23A
24 Enclosure, control OHX1-24 25 Contactor 120V = OHX1-25, 24V = OHX1-25A 26 Transformer 120V = OHX1-26, 24V = OHX1-26A 27 Bracket, Transformer ground OHX1-27 28 Grounding lug OHX1-28 29 Fuse 120V = 1/4 Amp (OHX1-29), 24V = 1 Amp (OHX1-29A) 30 Printed circuit board assembly 120V = OHX1-30, 24V = OHX1-30A 31 High limit, automatic reset OHX1-31 (also requires Part # OHX1-32) 32 Conductive cement, high limit OHX1-32 33 Bracket, transformer OHX1-33 34 O-ring, control enclosure cover OHX1-34 35 Cover, control enclosure OHX1-35 36 Plug, 3/4” NPT explosion-proof OHX1-36
37 Nut, bus bar OHX1-37 38 Bus bar, long straight OHX1-38
39 Bus bar, short straight OHX1-39 40 Bus bar, short curved OHX1-40
41 Bus bar, long curved OHX1-41 42 High limit, manual reset OHX1-42 (also requires Part # OHX1-32)
43 Handle, Disconnect OHX1-43 44 Switch, Disconnect 60A Non-Fused OHX1-44
12" fan size 16" fan size 20" fan size
10.0 kW = OHX-12-100
115/208-230V, 1Ø, 60Hz = G639 208-230/460V, 3Ø, 60Hz = G646
575V, 3Ø, 60Hz = G664
OHX1-12-17 with thermostat
OHX1-12-17A without thermostat
15.0 kW = OHX-16-150
20.0 kW = OHX-16-200
25.0 kW = OHX-20-250
30.0 & 35.0 kW = OHX-20-300
208-230/460V, 3Ø, 60Hz = G649
575V, 3Ø, 60Hz = G666
OHX1-20-17 with thermostat
OHX1-20-17A without thermostat
11
Page 12
— WARNING! —
Heater should only be service by qualified personnel experienced in electrical work.
Disconnect unit heater from power supply before starting any service or repair work. Lock the disconnect
switch in the “OFF” (open) position and/or tag the switch to prevent unexpected power application.
Failure to follow these procedures may result in severe or fatal injury.
— Maintenance Program —
Regular inspection, based on a schedule determined by the amount of dirt in the atmosphere, assures maximum operating economy and heating capacity.
Annual Inspection (before each heating season)
1. Check all terminal connections and electrical conductors for damage, looseness, defects, fraying, etc. and replace or tighten where applicable.
2. Inspect contactor contacts. If badly pitted, burned or welded shut, replace with factory supplied contactor. It is recommended that the contactor be replaced every three (3) years.
3. Inspect thermal delay fuses. Fuse rating and type are printed on circuit board. Correct fuse must be in the “ACTIVE” fuse clip. An extra fuse should be stored in the clips marked “SPARE”.
4. Check for fluid leakage from heat-exchanger. The heat exchanger is filled with a mixture of water and inhib­ited ethylene glycol, which is poisonous, and is factory vacuum-sealed. If fluid leakage occurs, remove heater from service and have the heat-exchanger replaced by a factory replacement unit. Refer to “Repair and Replacement” section for complete details. Do not attempt to loosen or tighten the vacuum plug or pressure relief device. A loss of vacuum could cause nuisance tripping of the thermal cutouts or high pressures which will cause the relief device to actuate with an accompanying loss of fluid.
5. Check all explosion-proof conduit and fittings. Replace damaged components. All threaded con duit connections must have a minimum 5 turns of engagement. Taper threaded conn ections must be at least hand tight. Inside of enclosures must be clean, dry, and free from any foreign materials. Enclosure covers must also be completely on and tight.
6. Check electrical resistance on all load side legs. Reading should be balanced (± 5%).
7. Check motor shaft bearing play. Replace motor if play is excessive or if motor does not run quietly and smoothly. Motor bearings are permanently lubricated.
8. Check fan blade. Replace immediately if cracked or damaged.
9. Check louvers. Louver screws should be tight. Louvers must not be set less than 30 degrees of the closed position.
10. Check the tightness of all hardware. All nuts and bolts, including mounting hardware, must be tightened to correct torque settings on Page 8.
11. Turn heater motor on for a minimum of 10 minutes. Crackling or pinging noises within heater during start­up are normal. Check for air exiting heater through louvers and smooth running of motor.
Periodic Maintenance (before and as required during heating season)
1. Clean the following (remove dust using compressed air):
Finned tubes
Fan
Fan Guard
Motor
2. Check the following:
Louvers
Motor for smooth and quiet operation
Louvers for proper angle and tightness
All explosion-proof covers and fittings for tightness
Contactor for signs of wear of pitting
12
Page 13
HEATER MAINTENANCE RECORD
Heater Model: _________________________ Serial No.: ______________________________
Date of
Maintenance
Performed
By
Maintenance Performed
13
Page 14
NOTES
14
Page 15
NOTES
15
Page 16
Limited 36-Month Warranty
Ouellet warrants all OHX series of explosion-proof electric heaters
against defects in materials and workmanship under normal conditions of use for a period of thirty-six (36) months from date of purchase based on the following terms:
1. The heater must not be modified in any way.
2. The heater must be stored, installed and used only in accordance with the owner’s manual and attached data plate information.
3. Replacement parts will be provided free of charge as necessary to restore any unit to normal operating condition, provided that the defective parts be returned to us freight prepaid and that the replacement parts be accepted freight collect.
4. The complete heater may be returned to our manufacturing plant for repair or replacement (at our discretion), freight charges prepaid.
5. Components damaged by contamination from dirt, dust, etc. or corrosion will not be considered as defects.
6. This warranty shall be limited to the actual equipment involved and, under no circumstances, shall include or extend to installation or removal costs, or to consequential damages or losses.
180, 3e Avenue L’Islet, QC G0R 2C0 Canada T: 1 800 463-7043 · (418) 247-3947 F: 1 800 662-7801 · (418) 247-7801 Info@ouellet.com · www.ouellet.com
PRINTED IN CANADA
©Copyright 2014
The information contained in this manual has been carefully checked and verified for accuracy. Specifica-
tions subject to change without
notice.