Orion Water Source Heat Pump X Module User Manual

Factory Packaged Controls
Water Source
Heat Pump X Module
Field Technical Guide
ALARM
M
www.aaon.com
www.orioncontrols.com
OE334-26-WSHPX-A WSHP-X MODULE AAON NO.: V18330
NON-DIGITAL COMPRESSORS
SUCT. PR. SENSOR
+5V
PRES 1=A1, PRES 2=A2
PRES
PRES 3=B1, PRES 4=B2
GND
+5 TO RED, PRES TO WHT & GND TO BLK
DIGITAL COMRESSORS
+5V
PRES
BIN 1 BIN 2 BIN 3 BIN 4
NOT USED PRES 1=A1, PRES 2=A2
GND
PRES 3=B1, PRES 4=B2
+5 NOT USED, PRES TO P6 & GND TO P5
- COMP.A1 EN.
- COMP.A2 EN.
- COMP. B1 EN.
- COMP. B2 EN.
T1
- LEAVING WATER TEMP A
T2
- LEAVING WATER TEMP B
- GROUND
GND
WattMaster Label
#SW000054
Rev.: 1A
BIN 5
- HEAT ENABLE
- WATER POF
BIN 6 BIN 7
- WATER POF
COM
- COMMON
E-BUS
CONNECT
MENU
E-BUS
CONNECT
ENTER
DOWN
RELAY CONTACT RATING
IS 1 AMP MAX @ 24 VAC
COMP. A1 ENABLE
COMP. A2 ENABLE
COMP. B1 ENABLE
COMP. B2 ENABLE
ALARM OUTPUT
RELAY COMMON
DIGITAL COMP. A1, A2, B1, B2
STAGE 1- COMP. A1/B1­STAGE 2 - COMP. A2/B2
CONNECT TO CNTLR C2 TERM.
GND
+24 VAC
WATTMASTER CONTROLS
R1 R2
R3
R4
R5 RC
AO1 A2O
Y 102374 REV 0S
MADE IN USA
Table of Contents
OVERVIEW ........................................................................................................................................................ 3
INSTALLATION AND WIRING ........................................................................................................................... 4
Environmental Requirements .......................................................................................................................................................4
Mounting and Dimensions ............................................................................................................................................................4
Important Wiring Considerations ..................................................................................................................................................5
Stand-Alone Wiring for Single Water Circuit ................................................................................................................................5
Stand-Alone Wiring for Dual Water Circuit ...................................................................................................................................6
Connection Wiring Details ............................................................................................................................................................7
VCM-X WSHP or SA Controller to WSHP-X Module Wiring Diagram Single Water Circuit .........................................................8
VCM-X WSHP E-BUS or SA E-BUS Controller to WSHP-X Module Wiring Single Water Circuit..............................................10
VCM-X WSHP or SA Controller to WSHP-X Module Wiring Diagram Dual Water Circuit..........................................................12
VCM-X WSHP E-BUS or SA E-BUS Controller to WSHP-X Module Wiring Dual Water Circuit ................................................14
START-UP AND COMMISSIONING .................................................................................................................. 16
Unit Confi gurations .....................................................................................................................................................................16
SEQUENCE OF OPERATION ........................................................................................................................... 17
WSHP-X Module Setpoints ........................................................................................................................................................17
Stand-Alone Input Commands ..................................................................................................................................................18
Input Commands (VCM-X WSHP or SA Connection) ................................................................................................................18
Modes of Operation ....................................................................................................................................................................19
LCD DISPLAY SCREENS ................................................................................................................................. 20
TROUBLESHOOTING ...................................................................................................................................... 26
Safety Monitoring for Single Water Circuit .................................................................................................................................26
Safety Monitoring for Dual Water Circuit ....................................................................................................................................27
Temperature Sensor Testing ......................................................................................................................................................28
Pressure Transducer T roubleshooting .......................................................................................... ............................................29
Using LEDs to Verify Operation..................................................................................................................................................30
LED Diagnostics .........................................................................................................................................................................31
PART NUMBER CROSS REFERENCE TABLE
PART DESCRIPTION ORION AAON
WSHP-X Module OE334-26-WSHPX-A V18330 VCM-X WSHP E-BUS Controller OE332-23E-VCMX-WSHP-A V07140 VCM-X WSHP Controller OE332-23-VCMX-WSHP-A R90810 SA E-BUS Controller OE332-23E-SA-A V07160 SA Controller OE332-23-SA-A R96070 E-BUS Distribution Module OE365-23-EBD R82930
www.aaon.com
WattMaster Controls Inc. 8500 NW River Park Drive · Parkville , MO 64152 Toll Free Phone: 866-918-1100 PH: (816) 505-1100 · FAX: (816) 505-1101 · E-mail: mail@wattmaster.com Visit our web site at www.orioncontrols.com WattMaster Form : AA-WSHPX-FIELD-TGD-01C Copyright December 2013 WattMaster Controls, Inc.
AAON Manual Part Number: V23560
®
AAON
is a registered trademark of AAON, Inc., Tulsa, OK.
Neither WattMaster Controls, Inc. nor AAON assumes any responsibility for errors or omissions in this document. This document is subject to change without notice.
®
WSHP-X Module
Module Overview
Overview
The OE334-26-WSHPX-A Water Source Heat Pump X (WSHP-X) Module monitors the compressors on an AAON Pump unit and can disable the compressors based on low Suction Pres­sure, Leaving Water Temperature, and Water Proof of Flow inputs. It also utilizes a Delay Timer to prevent the compressors from turning on at the same time.
The WSHP-X Module’s water circuit con fi guration can be either single or dual. There are eight R410-A glycol con fi gurations for the WSHP-X Module—0%-40% in increments of 5%. There are two refrigerant selec­tions—R410-A refrigerant and R-22 refrigerant. If R-22 refrigerant is selected, the glycol will automatically default to 0%.
The WSHP-X Module can be used stand-alone. It can also be connected to the VCM-X WSHP Controller or the SA Controller using the E-BUS Distribution Module or the module can be directly connected to the VCM-X WSHP E-BUS Controller or SA E-BUS Controller, allowing the Module to receive setpoints from the Controllers. See chart on page 2 for part numbers. Please note: The SA series of controllers only work with the R410-A dual water circuit confi gurations.
The WSHP-X Module requires a 24 VAC power connection with an appropriate VA rating.
NOTE: The WSHP-X Module is factory set for R410-A and 0%
glycol.
®
Water Source Heat
Features
The WSHP-X Module provides the following:
 Can be operated stand-alone or connected to a
VCM-X WSHP Controller or SA Controller using the E-BUS Distribution Module to E-BUS interface
 Can be directly connected to a VCM-X WSHP E-BUS
Controller or SA E-BUS Controller
 Capable of controlling digital compressors when
connected to a VCM-X WSHP Series Controller or SA Series Controller
 Monitors suction pressure, leaving water
temperature, and water proof of fl ow
 Provides Delay Timer to prevent compressors
from turning on at the same time
 Contains a 2x8 LCD character display and 4 buttons
that allow for status display, setpoint changes, and confi guration changes
NOTE: The WSHP-X Module contains no user-serviceable parts.
Contact qualifi ed technical personnel if your Module is not operating correctly.
ALARM
UP
M
ENTER
DOWN
GND
+24 VAC
- HEAT ENABLE
- WATER POF
- WATER POF
- COMMON
CONNECT
MENU
RELAY CONTACT RATING
IS 1 AMP MAX @ 24 VAC
COMP.A1 ENABLE
COMP.A2 ENABLE
COMP. B1 ENABLE
COMP. B2 ENABLE
ALARM OUTPUT
RELAY COMMON
DIGITAL COMP. A1, A2, B1, B2
STAGE 1- COMP. A1/B1­STAGE 2 - COMP. A2/B2
CONNECT TO CNTLR C2 TERM.
E-BUS
www.aaon.com
www.orioncontrols.com
OE334-26-WSHPX-A WSHP-X MODULE AAON NO.: V18330
NON-DIGITAL COMPRESSORS
SUCT. PR. SENSOR
+5V
PRES 1=A1, PRES 2=A2
PRES
PRES 3=B1, PRES 4=B2
GND
+5 TO RED, PRES TO WHT & GND TO BLK
DIGITAL COMRESSORS
+5V
NOT USED
PRES
PRES 1=A1, PRES 2=A2
GND
PRES 3=B1, PRES 4=B2
+5 NOT USED, PRES TO P6 & GND TO P5
BIN 1
- COMP.A1 EN.
- COMP.A2 EN.
BIN 2 BIN 3
- COMP. B1 EN.
- COMP. B2 EN.
BIN 4
T1
- LEAVING WATER TEMP A
T2
- LEAVING WATER TEMP B
- GROUND
GND
WattMaster Label
#SW000054
Rev.: 1A
BIN 5 BIN 6 BIN 7 COM
E-BUS
CONNECT
WATTMASTER CONTROLS
R1 R2
R3
R4
R5 RC
AO1 A2O
Y 102374 REV 0S
MADE IN USA
Figure 1: Water Source Heat Pump X Module
Technical Guide
3
WSHP-X Module
Installation & Wiring
Environmental Requirements
The WSHP-X Module needs to be installed in an environment that can maintain a temperature range between -30°F and 150°F and not exceed 90% RH levels (non-condensing).
Mounting
The WSHP-X Module is housed in a plastic enclosure. It is designed to be mounted by using the 3 mounting holes in the enclosure base. It is important to mount the module in a location that is free from extreme high or low temperatures, moisture, dust, and dirt. Be careful not to damage the electronic components when mounting the module. See Figure 2 for Module dimensions (in inches).
0.18 DIA. TYP. 3 PL.
Power Supply
The WSHP-X Module requires a 24 VAC power connection with an appropriate VA rating.
If you will be connecting the WSHP-X Module to a VCM-X WSHP Series Controller or SA Series Controller, one of the most important checks to make before powering up the system for the fi rst time is to make sure that the Controller is confi gured properly for your applica- tion. Refer to the VCM-X Controller Technical Guide, VCM-X Modular
E-BUS Controller Technical Guide, SA Controller Technical Guide, or SA E-BUS Controller Technical Guide for more information.
WARNING: Observe polarity! All boards must be wired
GND-to-GND and 24 VAC-to-VAC. Failure to observe polarity could result in damage to the boards.
2.07
0.29
5.64
ALARM
UP
M
DOWN
GND
ENTER
+24 VAC
- HEAT ENABLE
- WATER POF
- WATER POF
- COMMON
MENU
RELAY CONTACT RATING
IS 1 AMP MAX @ 24 VAC
COMP.A1 ENABLE
COMP.A2 ENABLE
COMP. B1 ENABLE
COMP. B2 ENABLE
ALARM OUTPUT
RELAY COMMON
DIGITAL COMP. A1,A2, B1, B2
STAGE 1- COMP. A1/B1­STAGE 2 - COMP. A2/B2
CONNECT TO CNTLR C2 TERM.
E-BUS
CONNECT
www.aaon.com
www.orioncontrols.com
OE334-26-WSHPX-A WSHP-X MODULE AAON NO.: V18330
NON-DIGITAL COMPRESSORS
SUCT. PR. SENSOR
+5V
PRES 1=A1, PRES 2=A2
PRES
PRES 3=B1, PRES 4=B2
GND
+5 TO RED, PRES TO WHT & GNDTO BLK
DIGITAL COMRESSORS
+5V
NOT USED
PRES
PRES 1=A1, PRES 2=A2
GND
PRES 3=B1, PRES 4=B2
+5 NOT USED, PRES TO P6 & GND TO P5
BIN 1
- COMP.A1 EN.
- COMP.A2 EN.
BIN 2 BIN 3
- COMP. B1 EN.
- COMP. B2 EN.
BIN 4
T1
- LEAVING WATER TEMP A
T2
- LEAVING WATER TEMP B
- GROUND
GND
WattMaster Label
#SW000054
Rev.: 1A
BIN 5 BIN 6 BIN 7 COM
E-BUS
CONNECT
4.14
5.83
WATTMASTER CONTROLS
R1 R2
R3
R4
R5 RC
AO1 A2O
0.56
5.05
Note: Height is 1.49 inches.
Figure 2: Water Source Heat Pump X Module Dimensions
4
Technical Guide
WSHP-X Module
Installation & Wiring
Important Wiring Considerations
Please read carefully and apply the following information when wiring the WSHP-X Module:
1. To operate the WSHP-X Module in Stand-Alone mode, you must connect power to the 24 VAC input terminal block. Do not allow wire strands to stick out and touch adjoining terminals. This could potentially cause a short circuit.
2. The 1 to 5 VDC signals for the Compressor modulation need to use 18-gauge shielded twisted pair cable, and the Drain wire
must be the GND signal.
3. All 24 VAC wiring must be connected so that all ground
wires remain common. Failure to follow this procedure can result in damage to the module and connected devices.
4. Be sure all modular wiring harness connectors are seated
fi rmly in their respective modular connectors on the circuit board.
OE334-36-WSHPX-A
Water Source Heat Pump X
Module
CIRCUIT A SUCTION PRESSURE TRANSDUCER
RD
WH
BK
CIRCUIT B SUCTION PRESSURE TRANSDUCER
COMPRESSOR A1 ENABLE CONTACT
COMPRESSOR A2 ENABLE CONTACT COMPRESSOR B1 ENABLE CONTACT
COMPRESSOR B2 ENABLE CONTACT
WATER POF SYSTEMA CONTACT WATER POF SYSTEM B CONTACT
RD
WH
BK
HEAT ENABLE CONTACT
SIG 1
GND
SIG 1
GND
BIN1 BIN2 BIN3 BIN4 BIN5 BIN6 BIN7 COM
GND
+V
ALARM
+V
T1
www.aaon.com
www.orioncontrols.com
OE334-26-WSHPX-A WSHP-X MODULE AAON NO.: V18330
NON-DIGITALCOMPRESSORS
SUCT. PR. SENSOR
+5V
PRES 1=A1, PRES 2=A2
PRES
PRES 3=B1, PRES 4=B2
GND
+5 TO RED, PRESTO WHT & GND TO BLK
DIGITALCOMRESSORS
+5V
NOT USED
PRES
PRES 1=A1, PRES 2=A2
GND
PRES 3=B1, PRES 4=B2
+5 NOT USED, PRES TO P6 & GNDTO P5
BIN 1
- COMP.A1 EN.
BIN 5 BIN 6 BIN 7 COM
E-BUS
CONNECT
- HEATENABLE
- WATER POF
- WATER POF
- COMMON
- COMP.A2 EN.
BIN 2 BIN 3
- COMP. B1 EN.
- COMP. B2 EN.
BIN 4
T1
- LEAVING WATERTEMP A
T2
- LEAVING WATERTEMP B
- GROUND
GND
WattMaster Label
#SW000054
Rev.: 1A
5. All wiring is to be in accordance with local and national electrical codes and specifi cations.
6. Check all wiring leads at the terminal block for tightness.
Be sure that wire strands do not stick out and touch adjacent terminals. Confi rm that all transducers required for your system are mounted in the appropriate location and wired into the correct terminals.
Stand-Alone Wiring Single Water Circuit
To operate the WSHP-X Module as Stand Alone, connect the Module to a 24 VAC power connection with an appropriate VA rating. See Figure 3 for wiring.
NOTE: NORMALLY
ALL RELAY OUTPUTS ARE
OPEN AND RATED FOR 24 VAC POWER ONLY
- 1 AMP MAXIMUM LOAD
WATTMASTER CONTROLS
UP
M
MENU
DOWN
RELAYCONTACT RATING
IS 1 AMP MAX @ 24 VAC
COMP.A1 ENABLE
COMP.A2 ENABLE
COMP. B1 ENABLE
COMP. B2 ENABLE
ALARM OUTPUT
RELAYCOMMON
DIGITALCOMP. A1, A2, B1, B2
STAGE 1- COMP.A1/B1­STAGE 2 - COMP.A2/B2
CONNECTTO CNTLR C2 TERM.
GND
E-BUS
CONNECT
+24 VAC
ENTER
R1 R2 R3 R4 R5
COMM
R1 R2
R3
R4
R5 RC
AO1 A2O
NOTE: OUTPUTS ARE NOT USED ON STAND ALONE APPLICATIONS
COMPRESSOR A1 ENABLE OUTPUT
COMPRESSOR A2 ENABLE OUTPUT
COMPRESSOR B1 ENABLE OUTPUT
COMPRESSOR B2 ENABLE OUTPUT ALARM OUTPUT
HVAC UNIT CONNECTIONS
GND
24 VAC
E
R
LEAVING WATER TEMPERATURE
Figure 3: Water Source Heat Pump X Module as Stand-Alone for Single Water Circuit
Technical Guide
5
WSHP-X Module
Installation & Wiring
Stand-Alone Wiring Dual Water Circuit
To operate the WSHP-X Module as Stand Alone, connect the Module to a 24 VAC power connection with an appropriate VA rating. See Figure 4 for wiring.
OE334-43-WSHPX-A
Water Source Heat Pump X
RD
CIRCUIT A1 SUCTION PRESSURE TRANSDUCER
CIRCUIT A2 SUCTION PRESSURE TRANSDUCER
CIRCUIT B1 SUCTION PRESSURE TRANSDUCER
CIRCUIT B2 SUCTION PRESSURE TRANSDUCER
COMPRESSOR A1 ENABLE CONTACT
COMPRESSOR A2 ENABLE CONTACT COMPRESSOR B1 ENABLE CONTACT
COMPRESSOR B2 ENABLE CONTACT
HEAT ENABLE CONTACT WATER POF SYSTEMA CONTACT WATER POF SYSTEM B CONTACT
WH BK
RD WH
BK
RD
WH BK
RD WH
BK
SIG 1
GND
SIG 2
GND
SIG 1
GND
SIG 2
GND
BIN1 BIN2 BIN3 BIN4 BIN5 BIN6 BIN7 COM
GND
+V
+V
+V
+V
T1 T2
ALARM
www.aaon.com
www.orioncontrols.com
OE334-26-WSHPX-A WSHP-X MODULE AAON NO.: V18330
NON-DIGITALCOMPRESSORS
SUCT. PR. SENSOR
+5V
PRES 1=A1, PRES 2=A2
PRES
PRES 3=B1, PRES 4=B2
GND
+5 TO RED, PRESTO WHT & GND TO BLK
DIGITALCOMRESSORS
+5V
NOT USED
PRES
PRES 1=A1, PRES 2=A2
GND
PRES 3=B1, PRES 4=B2
+5 NOT USED, PRES TO P6 & GNDTO P5
BIN 1
- COMP.A1 EN.
- COMP.A2 EN.
BIN 2 BIN 3
- COMP. B1 EN.
- COMP. B2 EN.
BIN 4
T1
- LEAVING WATERTEMP A
T2
- LEAVING WATERTEMP B
- GROUND
GND
WattMaster Label
#SW000054
Rev.: 1A
Module
BIN 5
- HEATENABLE
- WATER POF
BIN 6 BIN 7
- WATER POF
COM
- COMMON
E-BUS
CONNECT
UP
M
MENU
DOWN
RELAYCONTACT RATING
IS 1 AMP MAX @ 24 VAC
COMP.A1 ENABLE
COMP.A2 ENABLE
COMP. B1 ENABLE
COMP. B2 ENABLE
ALARM OUTPUT
RELAYCOMMON
DIGITALCOMP. A1, A2, B1, B2
STAGE 1- COMP.A1/B1­STAGE 2 - COMP.A2/B2
CONNECT TO CNTLR C2TERM.
GND
E-BUS
CONNECT
NOTE: NORMALLY
ALL RELAY OUTPUTS ARE
OPEN AND RATED FOR 24 VAC POWER ONLY
- 1 AMP MAXIMUM LOAD
WATTMASTER CONTROLS
ENTER
R1 R2 R3 R4 R5 COMM
COMPRESSOR A1 ENABLE
COMPRESSOR A2 ENABLE
COMPRESSOR B1 ENABLE COMPRESSOR B2 ENABLE
ALARM OUTPUT
HVAC UNIT CONNECTIONS
R1 R2
R3
R4
R5 RC
AO1 A2O
+24 VAC
NOTE: OUTPUTS ARE NOT USED ON STAND ALONE APPLICATIONS
GND
24 VAC
E
R
LEAVING WATER TEMPERATURE FOR SYSTEM A
LEAVING WATER TEMPERATURE FOR SYSTEM B
Figure 4: Water Source Heat Pump X Module as Stand-Alone for Dual Water Circuit
6
Technical Guide
WSHP-X Module
Installation & Wiring
E-BUS to WSHP-X Module Wiring
The WSHP-X Module connects to the E-BUS Distribution Module us­ing a modular HSSC cable. The WSHP-X Module requires a 24 VAC power connection with an appropriate VA rating.
The E-BUS Distribution Module connects to the VCM-X WSHP Con­troller, VCM-X Expansion Module, SA Controller (Dual W ater Circuit only), SA Expansion Module (Dual Water Circuit only), or 12 Relay Expansion Module using the I Figure 7 on page 12 for wiring.
Any E-BUS Module can be connected to each of the four E-BUS Dis­tribution Module’s output ports or can be daisy-chained together using HSSC cables.
If using a spliced terminal connection for longer runs, one module can be connected to the E-BUS Distribution Module and any additional modules would be daisy-chained to the fi rst module. For more information, refer to the E-BUS Distribution Module Technical Guide.
2
C port. See Figure 5 on page 8 and
VCM-X WSHP E-BUS or SA E-BUS Controller to WSHP-X Module Wiring
The WSHP-X Module connects to the E-BUS Controller using a modular HSSC cable. The WSHP-X Module requires a 24 VAC power connection with an appropriate VA rating. See Figure 6 on page 10 and Figure 8 on page 14 for wiring.
WARNING: Be sure all controllers and modules are
powered down before connecting or disconnecting HSSC cables.
Addressing
When the WSHP-X Module is connected to the E-BUS Distribution Module, set the WSHP-X Module’s address to 1. Set the address con­secutively for each WSHP-X Module you are using.
NOTE: Address zero defaults to address 1.
Any E-BUS Module can be connected to the E-BUS Controller’s E-BUS port or can be daisy-chained together using HSSC cables.
NOTE: Contact Factory for the correct HSSC cable length
for your application. Cables are available in 1/4, 1/2, 1, 2, 3, 4, and 5 Meter lengths and 100 and 150 Foot lengths.
Technical Guide
7
WSHP-X Module
Installation & Wiring
VCM-X WSHP to WSHP-X Module Wiring for Single Water Circuit
The VCM-X WSHP Controller or SA Controller communicates with the WSHP-X Module using the E-BUS Distribution Module. See Figure 5 for wiring details.
For Stand Alone Applications, Connect To System Manager.
For Network Applications
Connect To Next Controller
And/Or MiniLink PD On Local Loop.
Local Loop
RS-485
9600 Baud
All Comm Loop Wiring Is
Straight Thru
T to T, R to R & SHLD to SHLD
See Individual Component
Wiring Diagrams For
Detailed Wiring Of Analog
Inputs And Outputs
AI1 SET AI2 SET AI3 SET
AI4 SET AI5 SET AI7 SET
AI1
AI2
AI3
AI4
AI5
AI7
(OE332-23-WSHP-C)
VCM-X WSHP Controller
AI1 SET AI2 SET AI3 SET
AI4 SET AI5 SET AI7 SET
NOTE: When using the WSHP-X Module, all compressors
will be wired from the WSHP-X Module, not the VCM-X WSHP Controller
Note:
All Relay Outputs Are Normally Open And Rated For 24 VAC Power Only. 1 Amp Maximum Load.
R - 24VAC
G - Fan ON/OFF Only
Relay Output Contacts R2 Through R5 May Be User Configured For The Following:
1 - Heating Stages 2 - See Note 1 Below 3 - Warm-up Mode Command (VAV Boxes) 4 - Reversing Valve (Air To Air Heat Pumps) 5 - Reheat Control (Dehumidification) 6 - Exhaust Fan Interlock 7 - Preheater For Low Ambient Protection 8 - Alarm 9 - Override 10 - Occupied 11 - OA Damper 12 - Heat Wheel Note:
1.) When Using The WSHP-X Module, All Compressors Will Be Wired From The Module, Not The VCM-X Controller.
2.) A Total Of 20 Relays Are Available ByAdding Relay Expansion Modules. All Expansion Module Relay Outputs Are User-Configurable As ListedAbove.
GND
24VAC
Size Transformer For Correct Total Load. VCM-X Controller = 8 VA
Line Voltage
Connect To
E-BUS
Distribution
Module
GND
24 VAC
Jumpers
Splice If Required
OE271
Static Pressure
Transducer
Connect FRP Tubing To High Pressure Port (Bottom Tube) And Route To Static Pressure Pickup Probe Located In Unit Discharge. Leave Port Marked “Lo” Open ToAtmosphere
Connect To E-BUS Distribution Module or Expansion Module(s) (When Used)
Warning: 24 VAC Must Be Connected So That All Ground Wires Remain Common. Failure To Do So Will Result In Damage To The Controllers.
Connect To Digital Room Sensor And/Or Digital CO Sensor
2
Figure 5: VCM-X WSHP Controller to WSHP-X Module Wiring Diagram for Single Water Circuit
8
Technical Guide
Line Voltage
OE365-23-EBD E-BUS
Distribution Module
YS102308 REV 1 I2CTO COMM DIST. BOARD
OUTPUT
+COMM
SHLD
-COMM
GND
+VDC
INPUT
+COMM
SHLD
-COMM
GND
24VAC
GND
PWR
WSHP-X Module
Installation & Wiring
CIRCUIT B SUCTION PRESSURE TRANSDUCER
BK WH
RD
CIRCUIT A
SUCTION PRESSURE TRANSDUCER
BK
WH RD
NOTE:
OE334-26-WSHPX-A Water Source
Heat Pump X Module
Y 102374 REV 0S
ENTER
GND
R1 R2
R3
R4
R5 RC
AO1 A2O
24 VAC
WATTMASTER CONTROLS
MADE IN USA
ALARM
UP
M
BIN 5 BIN 6 BIN 7 COM
E-BUS
CONNECT
- HEATENABLE
- WATER POF
- WATER POF
- COMMON
MENU
DOWN
RELAYCONTACT RATING
IS 1 AMPMAX @ 24 VAC
COMP.A1 ENABLE
COMP.A2 ENABLE
COMP. B1 ENABLE
COMP. B2 ENABLE
ALARM OUTPUT
RELAYCOMMON
DIGITALCOMP. A1, A2, B1, B2
STAGE 1- COMP.A1/B1­STAGE 2 - COMP.A2/B2
CONNECTTO CNTLR C2 TERM.
GND
E-BUS
CONNECT
+24 VAC
www.aaon.com
www.orioncontrols.com
OE334-26-WSHPX-A WSHP-X MODULE AAON NO.: V18330
NON-DIGITALCOMPRESSORS
SUCT. PR. SENSOR
+5V
PRES 1=A1, PRES 2=A2
PRES
PRES 3=B1, PRES 4=B2
GND
+5TO RED, PRES TO WHT & GND TO BLK
DIGITALCOMRESSORS
+5V
NOT USED
PRES
PRES 1=A1, PRES 2=A2
GND
PRES 3=B1, PRES 4=B2
+5 NOTUSED, PRES TO P6 & GND TO P5
BIN 1
- COMP.A1 EN.
- COMP.A2 EN.
BIN 2 BIN 3
WATER POF CONTACT
BIN6
COM
T1
485 DRV
GND
- COMP. B1 EN.
- COMP. B2 EN.
BIN 4
T1
- LEAVING WATERTEMP A
T2
- LEAVING WATERTEMP B
- GROUND
GND
WattMaster Label
#SW000054
Rev.: 1A
ALL RELAY OUTPUTS
NORMALLY OPEN AND
ARE RATED FOR 24 VAC POWER ONLY
R1 R2 R3 R4 R5
COMM
AO1
DIGITAL STAGE 1 (1.5-5V)
AO2
DIGITAL STAGE 2 (1.5-5V)
HVAC UNIT CONNECTIONS
COMP.A1 ENABLE
COMP.A2 ENABLE
COMP. B1 ENABLE
COMP. B2 ENABLE ALARM OUTPUT
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24 VAC­to-24 VAC. Failure to observe polarity could result in damage to the boards.
Modular Cable
Connect To
VCM-X WSHP Controller
HSSC Cable
HSSC Cable
Connect To Other
WattMaster-Approved
E-BUS Expansion Module(s)
E
LEAVING WATER TEMPERATURE
Figure 5, cont.: VCM-X WSHP Controller to WSHP-X Module Wiring Diagram for Single Water Circuit
Technical Guide
24 VAC Transformer
3 VA Minimum
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24 VAC-to-24 VAC. Failure to observe polarity could result in damage to the boards.
9
WSHP-X Module
Installation & Wiring
VCM-X WSHP E-BUS or SA E-BUS Controller to WSHP-X Module Wiring for Single Water Circuit
The WSHP-X Module connects to the E-BUS Controller using a modular HSSC cable. The WSHP-X Module requires a 24 VAC power connection with an appropriate VA rating. See Figure 6 below for wiring.
OE334-26-WSHPX-A Water Source
+V
CIRCUIT A SUCTION PRESSURE TRANSDUCER
CIRCUIT B SUCTION PRESSURE TRANSDUCER
WARNING!! Observe Polarity! All boards must be wired with GND­to-GND and 24 VAC-to-24 VAC. Failure to observe polarity could result in damage to the boards.
Connect To Other
WattMaster-Approved
E-BUS Expansion Module(s)
WATER POF
WH
WH
RD
SIG 1
BK
GND
+V
RD
SIG 1
BK
GND
BIN6
COM
T1
GND
HSSC Cable
Any E-BUS Module can be connected to the E-BUS Controller’s E-BUS port or can be daisy-chained together using HSSC cables.
NOTE: When using the WSHP-X Module, all compressors
will be wired from the WSHP-X Module, not the VCM-X WSHP E-BUS Controller.
NOTE:
ALL RELAY OUTPUTS
NORMALLY OPEN AND
Heat Pump X Module
ALARM
UP
M
ENTER
DOWN
RELAYCONTACT RATING IS 1 AMP MAX @ 24 VAC
ALARM OUTPUT
CONNECTTO CNTLR C2 TERM.
GND
+24 VAC
GND
E
BIN 5 BIN 6 BIN 7 COM
E-BUS
CONNECT
- HEATENABLE
- WATER POF
- WATER POF
- COMMON
MENU
COMP.A1 ENABLE
COMP.A2 ENABLE
COMP. B1 ENABLE
COMP. B2 ENABLE
RELAYCOMMON
DIGITALCOMP. A1, A2, B1, B2
STAGE 1- COMP.A1/B1­STAGE 2 - COMP.A2/B2
E-BUS
CONNECT
www.aaon.com
www.orioncontrols.com
OE334-26-WSHPX-A WSHP-X MODULE AAON NO.: V18330
NON-DIGITALCOMPRESSORS
SUCT. PR. SENSOR
+5V
PRES 1=A1, PRES 2=A2
PRES
PRES 3=B1, PRES 4=B2
GND
+5 TO RED, PRESTO WHT & GND TO BLK
DIGITALCOMRESSORS
+5V
NOT USED
PRES
PRES 1=A1, PRES 2=A2
GND
PRES 3=B1, PRES 4=B2
+5 NOT USED, PRESTO P6 & GND TO P5
BIN 1
- COMP.A1 EN.
- COMP.A2 EN.
BIN 2 BIN 3
- COMP. B1 EN.
- COMP. B2 EN.
BIN 4
T1
- LEAVING WATERTEMP A
T2
- LEAVING WATERTEMP B
- GROUND
GND
WattMaster Label
#SW000054
Rev.: 1A
R1 R2
R3
R4
R5 RC
AO1 A2O
24 VAC
Y 102374 REV 0S
WATTMASTER CONTROLS
MADE IN USA
ARE RATED FOR 24 VAC POWER ONLY
HVAC UNIT CONNECTIONS
R1 R2 R3 R4 R5
COMM
AO1 AO2
COMP. A1 ENABLE
COMP. A2 ENABLE
COMP. B1 ENABLE
COMP. B2 ENABLE ALARM OUTPUT
DIGITAL STG 1 (1.5-5V) DIGITAL STG 2 (1.5-5V)
Line Voltage
24 VAC Transformer
3 VA Minimum
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24 VAC-to-24 VAC. Failure to observe polarity could result in damage to the boards.
HSSC Cable
Connect To VCM-X WSHP
E-BUS Controller
LEAVING WATER TEMPERATURE
Figure 6: VCM-X E-BUS Controller to WSHP-X Module Wiring Diagram for Single Water Circuit
10
Technical Guide
WSHP-X Module
NOTE: Contact Factory for the correct HSSC cable length for
your application. Cables are available in ¼, ½, 1, 2, 3, 4, and 5 Meter lengths and 100 and 150 Foot lengths.
WARNING: Be sure all controllers and modules are
powered down before connecting or disconnecting HSSC cables.
For Stand Alone Applications,
Connect To System Manager. For Network
Applications Connect To Next Controller
And/Or MiniLink PD On Local Loop.
Local Loop
RS-485
9600 Baud
All Comm Loop Wiring Is
Straight Thru
T to T, R to R & SHLD to SHLD
HSSC Cable Connect To
VCM-X E-BUS Port
AI1 SET AI2 SET AI3 SET
See Individual
Component
Wiring Diagrams
For Detailed
Wiring Of Analog
Inputs And
Outputs
AI4 SET AI5 SET AI7 SET
OE332-23E-VCMX-WSHP
E-BUS Controller
RS-485 COMMUNICATION LOOP. WIRE “R” TO“R”, “T” TO “T” “SHLD” TO “SHLD”
VCM-X MODULAR E-BUS CONTROLLER
Orion No.:OE332-23E-VCMX-MOD-A
AI1 = SPC (SPACETEMPERATURE SENSOR)
= SAT(SUPPLY AIR TEMPERATURE SENSOR)
AI2
= RAT(RETURN AIR TEMPERATURE SENSOR)
AI3
= OAT(OUTDOOR AIR TEMPERATURE SENSOR)
AI4
= SUCTION PRESSURE SENSOR (FROM EXP. MODULE)
AI5
= SPACETEMPERATURE SENSOR SLIDE ADJUST
AI7
= ECONOMIZER (2-10 VDC OUTPUT)
A01
= SUPPLYFAN VFD (0-10 VDC OUTPUT)
A02
CONNECTOR
ANALOG INPUT
JUMPER SETTINGS
THERM
4-20mA
AI1
0-10V 0-5V
THERM
4-20mA
AI2
0-10V 0-5V
THERM
4-20mA
AI3
0-10V 0-5V
THERM
4-20mA
AI4
0-10V 0-5V
THERM 4-20mA
AI5
0-10V
0-5V
THERM
4-20mA
AI7
0-10V 0-5V
ANALOG INPUTJUMPER SETTINGS MUSTBE SET AS SHOWN FOR PROPER OPERATION
STATIC
PRESSURE
VCM-X Modular
OR VOLTAGE RESETSOURCE
E-BUS
LED BLINK CODES
LED NAME STATUS1 STATUS2
NORMALOPERATION 0 1
SATFAIL 1 2
OATFAIL 2 2
SPCFAIL 3 2
MODULEALARM 4 2
MECHCOOL FAIL 1 3
MECHHEAT FAIL 2 3
FANPROOF FAIL 3 3
DIRTYFILTER 4 3
EMERGENCYSHUTDOWN 5 3
LOWSAT 1 4
HIGHSAT 2 4
CONT.TEMP COOL FAIL 3 4
CONT.TEMP HEAT FAIL 4 4
PUSHBUTTON OVR 1 5
ZONEOVR 2 5
OUTPUTFORCE ACTIVE 0 6
WARNING!POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILLBE DAMAGED
2
WattMasterLabel
IC
#LB102073-01-A
EXPANSION
Rev.: 1A
RELAYCONTACT RATING IS 1AMP MAX @ 24 VAC
RELAY COMMON
FAN
RELAY2
RELAY3
RELAY4
RELAY5
AAON No.:
V07150
24 VAC POWER ONLY
2
IC DIGITAL
SENSOR
Installation & Wiring
Note:
All Relay Outputs Are Normally Open And Rated For 24 VAC Power Only. 1 Amp Maximum Load.
R - 24VAC
G - Fan ON/OFF Only
Relay Output Contacts R2 Through R5 May Be User-Configured For The Following:
1 - Heating Stages 2 - Cooling Stages 3 - Warm-up Mode Command (VAV Boxes) 4 - Reversing Valve (Air To Air Heat Pumps) 5 - Reheat Control (Dehumidification) 6 - Exhaust Fan Interlock 7 - Preheater For Low Ambient Protection 8 - Alarm 9 - Override 10 - Occupied 11 - OA Damper 12 - Heat Wheel 13 - Emergency Heat Note: 1.) When Using the WSHP-X Module, All Compressors Will Be Wired From the Module, Not the VCM-X Controller.
2.) A Total Of 20 RelaysAre Available By Adding Relay Expansion Modules. All Expansion Module Relay Outputs Are User Configurable As ListedAbove.
GND
24VAC
Size Transformer For Correct Total Load. VCM-X Controller = 8 VA
Line Voltage
Jumpers
Splice If Required
OE271
Static Pressure
Transducer
Connect FRP Tubing To High Pressure Port (Bottom Tube) And Route To Static Pressure Pickup Probe Located In Unit Discharge. Leave Port Marked “Lo” Open ToAtmosphere.
Connect To Expansion Module(s) (When Used)
Connect To Digital Room Sensor And/Or Digital CO Sensor
2
Warning: 24 VAC Must Be Connected So That All Ground Wires Remain Common. Failure To Do So Will Result In Damage To The Controllers.
Figure 6, cont.: VCM-X E-BUS Controller to WSHP-X Module Wiring Diagram for Single Water Circuit
Technical Guide
11
WSHP-X Module
Installation & Wiring
VCM-X WSHP or SA Controller to WSHP-X Module Wiring for Dual Water Circuit
The VCM-X WSHP Controller or SA Controller communicates with the WSHP-X Module using the E-BUS Distribution Module. See Figure 7 for wiring details (VCM-X WSHP Controller shown).
For Stand Alone Applications, Connect To System Manager.
For Network Applications
Connect To Next Controller
And/Or MiniLink PD On Local Loop.
Local Loop
RS-485
9600 Baud
All Comm Loop Wiring Is
Straight Thru
T to T, R to R & SHLD to SHLD
See Individual Component
Wiring Diagrams For
Detailed Wiring Of Analog
Inputs And Outputs
AI1 SET AI2 SET AI3 SET
AI4 SET AI5 SET AI7 SET
(OE332-23-WSHP-A)
VCM-X WSHP Controller
AI1 SET AI2 SET AI3 SET
AI1
AI2
AI3
AI4
AI5
AI4 SET AI5 SET AI7 SET
AI7
NOTE: When using the WSHP-X Module, all compressors
will be wired from the WSHP-X Module, not the VCM-X WSHP Controller or SA Controller.
Note:
All Relay Outputs Are Normally Open And Rated For 24 VAC Power Only. 1 Amp Maximum Load.
R - 24VAC
G - Fan ON/OFF Only
Relay Output Contacts R2 Through R5 May Be User Configured For The Following:
1 - Heating Stages 2 - See Note 1 Below 3 - Warm-up Mode Command (VAV Boxes) 4 - Reversing Valve (Air To Air Heat Pumps) 5 - Reheat Control (Dehumidification) 6 - Exhaust Fan Interlock 7 - Preheater For Low Ambient Protection 8 - Alarm 9 - Override 10 - Occupied 11 - OA Damper 12 - Heat Wheel Note: 1.) When Using the WSHP-X Module, All Compressors Will Be Wired From the Module, Not the VCM-X Controller.
2.) A Total Of 20 Relays Are Available By Adding Relay Expansion Modules. All Expansion Module Relay Outputs Are User Configurable As Listed Above.
GND
24VAC
Size Transformer For Correct Total Load. VCM-X Controller = 8 VA
Line Voltage
Connect To
E-BUS
Distribution
Module
24 VAC
GND
Jumpers
Splice If Required
OE271
Static Pressure
Transducer
Connect FRP Tubing To High Pressure Port (Bottom Tube) And Route To Static Pressure Pickup Probe Located In Unit Discharge. Leave Port Marked “Lo” Open ToAtmosphere
Connect To E-BUS Distribution Module Or Expansion Module(s) (When Used)
Warning: 24 VAC Must Be Connected So That All Ground Wires Remain Common. Failure To Do So Will Result In Damage To The Controllers.
Connect To Digital Room Sensor And/Or Digital CO Sensor
2
Figure 7: VCM-X WSHP Controller to WSHP-X Module Wiring Diagram for Dual Water Circuit
12
Technical Guide
Line Voltage
OE365-23-EBD E-BUS
Distribution Module
YS102308 REV 1 I2CTO COMM DIST. BOARD
OUTPUT
+COMM
SHLD
-COMM
GND
+VDC
INPUT
+COMM
SHLD
-COMM
GND
24VAC
GND
PWR
WARNING!!
Observe Polarity! All boards must be wired with GND-to­GND and 24 VAC-to-24 VAC. Failure to observe polarity could result in damage to the boards.
485 DRV
Modular Cable
Connect To
VCM-X WSHP Controller
LEAVING WATER TEMPERATURE
FOR SYSTEM A
WSHP-X Module
Installation & Wiring
CIRCUIT B2 SUCTION PRESSURE TRANSDUCER
BK WH
RD
CIRCUIT B1
SUCTION PRESSURE TRANSDUCER
BK WH
RD
CIRCUIT A2 SUCTION PRESSURE TRANSDUCER
BK WH
RD
CIRCUIT A1 SUCTION PRESSURE TRANSDUCER
BK
WH RD
NOTE:
ALL RELAY OUTPUTS
NORMALLY OPEN AND
ARE RATED FOR 24 VAC POWER ONLY
HVAC UNIT CONNECTIONS
R1
COMP.A1 ENABLE
R2
COMP.A2 ENABLE
R3
COMP. B1 ENABLE
R4
COMP. B2 ENABLE
R5
COMM
ALARM OUTPUT
AO1
DIGITAL STG 1 (1.5-5V)
AO2
DIGITAL STG 2 (1.5-5V)
Line Voltage
3 VAMinimum
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24 VAC-to-24 VAC. Failure to observe polarity could result in damage to the boards.
WATER POFA WATER POF B
BIN6 BIN7
COM
T1 T2
GND
OE334-26-WSHPX-A Water Source
Heat Pump X Module
ALARM
UP
M
BIN 5
- HEATENABLE
- WATER POF
BIN 6 BIN 7
- WATER POF
COM
- COMMON
E-BUS
CONNECT
HSSC Cable
Module(s)
MENU
DOWN
RELAYCONTACT RATING
IS 1AMP MAX @ 24 VAC
COMP.A1 ENABLE
COMP.A2 ENABLE
COMP. B1 ENABLE
COMP. B2 ENABLE
ALARM OUTPUT
RELAYCOMMON
DIGITALCOMP. A1, A2, B1, B2
STAGE 1- COMP.A1/B1­STAGE 2 - COMP.A2/B2
CONNECTTO CNTLR C2 TERM.
GND
E-BUS
CONNECT
+24 VAC
E
HSSC Cable
www.aaon.com
www.orioncontrols.com
OE334-26-WSHPX-A WSHP-X MODULE AAON NO.: V18330
NON-DIGITALCOMPRESSORS
SUCT. PR. SENSOR
+5V
PRES 1=A1, PRES 2=A2
PRES
PRES 3=B1, PRES 4=B2
GND
+5TO RED, PRES TO WHT & GND TO BLK
DIGITALCOMRESSORS
+5V
NOT USED
PRES
PRES 1=A1, PRES 2=A2
GND
PRES 3=B1, PRES 4=B2
+5 NOTUSED, PRES TO P6 & GND TO P5
BIN 1
- COMP.A1 EN.
- COMP.A2 EN.
BIN 2 BIN 3
- COMP. B1 EN.
- COMP. B2 EN.
BIN 4
T1
- LEAVING WATERTEMP A
T2
- LEAVING WATERTEMP B
- GROUND
GND
WattMaster Label
#SW000054
Rev.: 1A
Connect To Other
WattMaster-Approved
E-BUS Expansion
ENTER
GND
R1 R2
R3
R4
R5 RC
AO1 A2O
24 VAC
Y 102374 REV 0S
WATTMASTER CONTROLS
MADE IN USA
24 VAC Transformer
LEAVING WATER TEMPERATURE
FOR SYSTEM B
Figure 7, cont.: VCM-X WSHP Controller to WSHP-X Module Wiring Diagram for Dual Water Circuit
Technical Guide
13
WSHP-X Module
Installation and Wiring
VCM-X WSHP E-BUS or SA E-BUS Controller to WSHP-X Module Wiring for Dual Water Circuit
The WSHP-X Module connects to the E-BUS Controller using a modular HSSC cable. The WSHP-X Module requires a 24 VAC power connection with an appropriate VA rating. See Figur e 8 below for wiring. (VCM-X WSHP E-BUS Controller shown.)
OE334-26-WSHPX-A Water Source
+V
CIRCUIT A1 SUCTION PRESSURE TRANSDUCER
CIRCUIT A2 SUCTION PRESSURE TRANSDUCER
CIRCUIT B1 SUCTION PRESSURE TRANSDUCER
CIRCUIT B2 SUCTION PRESSURE TRANSDUCER
WARNING!! Observe Polarity! All boards must be wired with GND-to­GND and 24 VAC-to-24 VAC. Failure to observe polarity could result in damage to the boards.
Connect To Other
WattMaster-Approved
E-BUS Expansion Module(s)
WATER POFA
WATER POF B
RD WH
WH
RD WH
RD WH
SIG 1
BK
GND
+V
RD
SIG 2
BK
GND
+V
SIG 1
BK
GND
+V
SIG 2
BK
GND
BIN6 BIN7
COM
T1 T2
OE334-26-WSHPX-A WSHP-X MODULE AAON NO.: V18330
NON-DIGITALCOMPRESSORS
+5V
PRES
GND
+5 TO RED, PRESTO WHT & GND TO BLK
+5V
PRES
GND
+5 NOT USED, PRESTO P6 & GND TO P5
BIN 1 BIN 2 BIN 3 BIN 4
T1 T2
GND
WattMaster Label
GND
HSSC Cable
Any E-BUS Module can be connected to the E-BUS Controller’s E-BUS port or can be daisy-chained together using HSSC cables.
NOTE: When using the WSHP-X Module, all compressors
will be wired from the WSHP-X Module, not the VCM-X WSHP E-BUS Controller or SA E-BUS Controller.
NOTE:
ALL RELAY OUTPUTS
NORMALLY OPEN AND
Heat Pump X Module
ALARM
UP
M
BIN 5 BIN 6 BIN 7 COM
E-BUS
CONNECT
- HEATENABLE
- WATER POF
- WATER POF
- COMMON
MENU
DOWN
RELAYCONTACT RATING
IS 1 AMPMAX @ 24 VAC
COMP.A1 ENABLE
COMP.A2 ENABLE
COMP. B1 ENABLE
COMP. B2 ENABLE
ALARM OUTPUT
RELAYCOMMON
DIGITALCOMP. A1, A2, B1, B2
STAGE 1- COMP.A1/B1­STAGE 2 - COMP.A2/B2
CONNECTTO CNTLR C2 TERM.
GND
E-BUS
CONNECT
+24 VAC
E
www.aaon.com
www.orioncontrols.com
SUCT. PR. SENSOR PRES 1=A1, PRES 2=A2 PRES 3=B1, PRES 4=B2
DIGITALCOMRESSORS
NOT USED PRES 1=A1, PRES 2=A2 PRES 3=B1, PRES 4=B2
- COMP.A1 EN.
- COMP.A2 EN.
- COMP. B1 EN.
- COMP. B2 EN.
- LEAVING WATERTEMP A
- LEAVING WATERTEMP B
- GROUND
#SW000054
Rev.: 1A
ENTER
GND
R1 R2
R3
R4
R5 RC
AO1 A2O
24 VAC
Y 102374 REV 0S
WATTMASTER CONTROLS
ARE RATED FOR 24 VAC POWER ONLY
MADE IN USA
R1 R2 R3 R4 R5
COMM
AO1 AO2
Line Voltage
24 VAC Transformer
3 VA Minimum
HVAC UNIT CONNECTIONS
COMP. A1 ENABLE
COMP. A2 ENABLE
COMP. B1 ENABLE
COMP. B2 ENABLE ALARM OUTPUT
DIGITAL STG 1 (1.5-5V) DIGITAL STG 2 (1.5-5V)
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24 VAC-to-24 VAC. Failure to observe polarity could result in damage to the boards.
HSSC Cable
Connect To VCM-X E-BUS
Controller or SA E-BUS Controller
LEAVING WATER TEMPERATURE
LEAVING WATER TEMPERATURE
FOR SYSTEM A
FOR SYSTEM B
Figure 8: VCM-X E-BUS Controller to WSHP-X Module Wiring Diagram for Dual Water Circuit
14
Technical Guide
WSHP-X Module
NOTE: Contact Factory for the correct HSSC cable length for
your application. Cables are available in ¼, ½, 1, 2, 3, 4, and 5 Meter lengths and 100 and 150 Foot lengths.
WARNING: Be sure all controllers and modules are
powered down before connecting or disconnecting HSSC cables.
For Stand Alone Applications,
Connect To System Manager. For Network
Applications Connect To Next Controller
And/Or MiniLink PD On Local Loop.
Local Loop
RS-485
9600 Baud
All Comm Loop Wiring Is
Straight Thru
T to T, R to R & SHLD to SHLD
HSSC Cable Connect To
VCM-X E-BUS Port
See Individual
AI1 SET AI2 SET AI3 SET
Component Wiring
Diagrams For Detailed Wiring Of Analog Inputs And
Outputs
AI4 SET AI5 SET AI7 SET
OE332-23E-VCMX-WSHP
VCM-X Modular
E-BUS Controller
RS-485 COMMUNICATION LOOP. WIRE “R” TO“R”, “T” TO “T” “SHLD” TO “SHLD”
VCM-X MODULAR E-BUS CONTROLLER
Orion No.:OE332-23E-VCMX-MOD-A
AI1 = SPC (SPACETEMPERATURE SENSOR) AI2
= SAT(SUPPLY AIR TEMPERATURE SENSOR)
AI3
= RAT(RETURN AIR TEMPERATURE SENSOR)
AI4
= OAT(OUTDOOR AIR TEMPERATURE SENSOR)
AI5
= SUCTION PRESSURE SENSOR (FROM EXP. MODULE)
AI7
= SPACETEMPERATURE SENSOR SLIDE ADJUST
OR VOLTAGE RESETSOURCE
A01
= ECONOMIZER (2-10 VDC OUTPUT)
A02
= SUPPLYFAN VFD (0-10 VDC OUTPUT)
E-BUS
CONNECTOR
ANALOG INPUT
JUMPER
SETTINGS
THERM
4-20mA
AI1
0-10V
NORMALOPERATION 0 1
0-5V
SATFAIL 1 2
THERM
OATFAIL 2 2
4-20mA
AI2
SPCFAIL 3 2
0-10V 0-5V
MODULEALARM 4 2
THERM
MECHCOOL FAIL 1 3
4-20mA
AI3
MECHHEAT FAIL 2 3
0-10V 0-5V
FANPROOF FAIL 3 3
THERM
DIRTYFILTER 4 3
4-20mA
AI4
EMERGENCYSHUTDOWN 5 3
0-10V 0-5V
LOWSAT 1 4
THERM
HIGHSAT 2 4
4-20mA
AI5
CONT.TEMP COOL FAIL 3 4
0-10V
CONT.TEMP HEAT FAIL 4 4
0-5V
PUSHBUTTON OVR 1 5
THERM
4-20mA
ZONEOVR 2 5
AI7
0-10V
OUTPUTFORCE ACTIVE 0 6
0-5V
ANALOG INPUTJUMPER SETTINGS MUSTBE SET AS SHOWN FOR PROPER OPERATION
WattMasterLabel
STATIC
#LB102073-01-A
PRESSURE
Rev.: 1A
RELAYCONTACT RATING IS 1AMP MAX @ 24 VAC
RELAY COMMON
RELAY2
RELAY3
RELAY4
RELAY5
AAON No.:
V07150
LED BLINK CODES
LED NAME STATUS1 STATUS2
24 VAC POWER ONLY
WARNING!POLARITY MUST BE OBSERVED OR THE CONTROLLER WILLBE DAMAGED
2
IC
EXPANSION
FAN
2
IC DIGITAL
SENSOR
Installation and Wiring
Note:
All Relay Outputs Are Normally Open And Rated For 24 VAC Power Only. 1 Amp Maximum Load.
R - 24VAC
G - Fan ON/OFF Only
Relay Output Contacts R2 Through R5 May Be User-Configured For The Following:
1 - Heating Stages 2 - Cooling Stages 3 - Warm-up Mode Command (VAV Boxes) 4 - Reversing Valve (Air To Air Heat Pumps) 5 - Reheat Control (Dehumidification) 6 - Exhaust Fan Interlock 7 - Preheater For Low Ambient Protection 8 - Alarm 9 - Override 10 - Occupied 11 - OA Damper 12 - Heat Wheel 13 - Emergency Heat Note: 1.) When Using the WSHP-X Module, All Compressors Will Be Wired From the Module, Not the VCM-X Controller.
2.) A Total Of 20 Relays Are Available ByAdding Relay Expansion Modules. All Expansion Module Relay Outputs Are User Configurable As Listed Above.
GND
24VAC
Size Transformer For Correct Total Load. VCM-X Controller = 8 VA
Line Voltage
Jumpers
Splice If Required
OE271
Static Pressure
Transducer
Connect FRP Tubing To High Pressure Port (Bottom Tube) and Route To Static Pressure Pickup Probe Located In Unit Discharge. Leave Port Marked “Lo” Open ToAtmosphere
Connect To Expansion Module(s) (When Used)
Connect To Digital Room Sensor And/Or Digital CO Sensor
2
Warning: 24 VAC Must Be Connected So That All Ground Wires Remain Common. Failure To Do So Will Result In Damage To The Controllers.
Figure 8, cont.: VCM-X E-BUS Controller to WSHP-X Module Wiring Diagram for Dual Water Circuit
Technical Guide
15
WSHP-X Module
Start-Up & Commissioning
General
In order to have a trouble free start-up, it is important to follow a few simple procedures. Before applying power for the fi rst time, it is very important to run through a few simple checks.
One of the most important checks to make before powering up the system for the fi rst time is to make sure that the VCM-X WSHP Series Controller or SA Series Controller is confi gured properly for your ap- plication. Refer to the VCM-X Controller Technical Guide, VCM-X
Modular E-BUS Controller Technical Guide, SA Controller Technical Guide, or SA E-BUS Controller Technical Guide for more information.
A handheld Modular Service Tool, Modular System Manager, or System Manager T ouch Screen connected to the VCM-X WSHP Series Control­ler or SA Series Controller will allow you to confi gure your application. Refer to the VCM-X Operator’ s Interfaces T echnical Guide, SA Operator Interfaces T echnical Guide, or System Manager TS Technical Guide for more information.
UNIT CONFIGURATIONS
SYSTEM A SYSTEM B
PERMUTATION
Comp A1 Comp A2 Comp B1 Comp B2
NOTE: The SA Series Controller does not utilize the System
Manager Touch Screen.
Check all wiring leads at the terminal block for tightness. Be sure that wire strands do not stick out and touch adjacent terminals. Confi rm that all sensors required for your system are mounted in the appropriate location and wired into the correct terminals.
WARNING: Observe polarity! All boards must be wired
GND-to-GND and 24 VAC-to-VAC. Failure to observe polarity could result in damage to the boards.
VCM-X WSHP
CONFIGURATION
CONFIGURATION
SA
Relay 1 Relay 2 Relay 3 Relay 4
1 On/Off On/Off 2 Digital On/Off
3 Digital Digital 4 On/Off On/Off On/Off On/Off 4 Compressors
5 Digital On/Off On/Off On/Off Not Available 6 Digital On/Off Digital On/Off
7 Digital Digital Digital Digital
In the Cooling Mode, the Compressors will stage in the following order:
Permutations 1, 2 & 3: Compressor A1 -> Compressor A2 Permutations 4: Compressor A1 -> Compressor B1 -> Compressor A2 -> Compressor B2 Permutations 6: Compressor A1 & Compressor B1 -> Compressor A2 -> Compressor B2 Permutations 7: Compressor A1 & Compressor B1 -> Compressor A2 & Compressor B2
In the Dehumidi cation Mode, the Compressors will stage in the following order: Permutation 4: Compressor A1 & Compressor B1 -> Compressor A2 -> Compressor B2 All other permutations in the Dehumidifi cation Mode stage as described in the Cooling Mode.
2 Compressors 2 Compressors
Digital Compressor 2 Compressors
Full Digital
4 Compressors Digital Compressor
4 Compressors Full Digital
2 Compressors Single Unit SA
2 Compressors Single Unit SA
— —
4 Compressors Dual Unit SA
4 Compressors Dual Unit SA
Table 1: Unit Confi gurations Chart
16
Technical Guide
WSHP-X Module
Sequence of Operation
General
The following inputs and outputs are available on the WSHP-X Module. See Table 2 below to reference the Input/Output Map.
Binary Inputs
1 Compressor A1 Enable (BIN 1) 2 Compressor A2 Enable (BIN 2) 3 Compressor B1 Enable (BIN 3) 4 Compressor B2 Enable (BIN 4) 5 Heat Enable (BIN 5) 6 Water Proof of Flow System A (BIN 6)
7 Water Proof of Flow System B (BIN 7)
Analog Inputs
1 Suction Pressure A1 (Pres 1) 2 Suction Pressure A2 (Pres 2) 3 Suction Pressure B1 (Pres 3) 4 Suction Pressure B2 (Pres 4) 5 Leaving Water Temperature System A (T1) 6 Leaving Water Temperature System B (T2)
Analog Outputs (1-5 VDC or 0-10 VDC)
1 Digital Stage 1 (Compressors A1 & B1) (AOUT1) 2 Digital Stage 2 (Compressors A2 & B2) (AOUT2)
NOTE: Analog Outputs are not used on Stand Alone Application
Relay Outputs (24 VAC)
1 Compressor A1 Enable Output (RLY1) 2 Compressor A2 Enable Output (RLY2) 3 Compressor B1 Enable Output (RLY3) 4 Compressor B2 Enable Output (RLY4) 5 Alarm Output (RLY5)
WSHP-X Module Setpoints
The WSHP-X Module setpoints are preset at AAON and are based on the unit’s design as well as the type of coolant being used in the water loop. See Tables 3 & 4 for default settings.
NOTE: These are default settings only. The setpoints may be
different based on the unit’s design and coolant being used.
Water-Only Default Setpoints
Description R410-A R22
UNSAFE SUCTION 40 PSIG 20 PSIG
LOW SUCTION HEAT MODE 100 PSIG 57 PSIG
LOW SUCTION COOL MODE 85 PSIG 57 PSIG
LOW LEAVING WATER TEMP 37ºF 37ºF
Table 3: Factory-Set Default Setpoints - Water Only
Table 2: WSHP-X Module Inputs & Outputs
Technical Guide
17
WSHP-X Module
Sequence of Operation
Glycol Default Setpoints
Description
UNSAFE SUCTION
LOW SUCTION HEAT MODE
LOW SUCTION COOL MODE
LOW LEAVING WATER TEMP
R22
0%
Glycol
20 PSIG 40 PSIG 40 PSIG 40 PSIG 40 PSIG 40 PSIG 40 PSIG 40 PSIG 40 PSIG 40 PSIG
57 PSIG 100 PSIG 93 PSIG 87 PSIG 82 PSIG 75 PSIG 65 PSIG 58 PSIG 49 PSIG 45 PSIG
57 PSIG 87 PSIG 85 PSIG 85 PSIG 85 PSIG 85 PSIG 85 PSIG 85 PSIG 85 PSIG 85 PSIG
37ºF 37ºF 34ºF 30ºF 27ºF 20ºF 15ºF 9ºF 2ºF 0ºF
R410-A
0%
Glycol
R410-A
5%
Glycol
R410-A
10%
Glycol
Table 4: Factory-Set Default Setpoints - Glycol
Stand-Alone Input Commands
Compressor On/Off
A 24 volt signal to Binary Inputs #1-4 initiates each Compressor’s On function. The source for this signal would typically come from Y1 to Y4 calls from the thermostat.
Heat Enable On/Off
A 24 volt signal on this input indicates the unit is in the Heating Mode. Typically, the source for this signal is the “O” call from the thermo­stat.
R410-A
15%
Glycol
R410-A
20%
Glycol
R410-A
25%
Glycol
R410-A
30%
Glycol
R410-A
35%
Glycol
R410-A
40%
Glycol
Input Commands (VCM-X WSHP or SA Connection)
NOTE: When the term “ON” is used, it means there is either 24
VAC on the appropriate Binary Input or a call-to-run signal is being received from the VCM-X WSHP Series or SA Series Controller. When the term “OFF” is used, it means there is either 0 VAC on the appropriate Binary Input or the call-to-run signal from the VCM-X WSHP or SA has been removed.
Water Proof of Flow System On/Off
A 24 volt signal to Binary Inputs #6-7 indicates Water Proof of Flow for each system.
Suction Pressure Analog Inputs
Sensors from Analog Inputs #1-4 correlate with the Suction Pressure of each Compressor (250 PSI).
Leaving Water Temperature Thermistor Inputs
T1 correlates with Compressors A1 & A2 (RLY1 and RLY2). T2 cor­relates with Compressors B1 & B2 (RLY3 and RLY4).
18
Revised: 6/13/13
Compressor On/Off
Instead of a physical input signaling the Compressor On/Off function, the VCM-X WSHP Series Controller or SA Series Controller commu­nications drives the Compressor On/Off function.
Heat Enable On/Off
As with the Compressor On/Off function, the VCM-X WSHP Series or SA Series Controller communicates to the Module that it is in Heat Mode.
Technical Guide
WSHP-X Module
Sequence of Operation
Modes of Operation
NOTE: See the Unit Con gurations Chart on page 16 for more
information about compressor staging.
Digital Stage 1 / Digital Stage 2
On units with two Digital Scroll Compressors, the fi rst compressor (A1) will be designated as Digital Stage 1 and the second compressor (A2) will be designated as Digital Stage 2.
On units with four Digital Scroll Compressors, there may be instances where compressor numbers on the module do not correlate with the mechanical compressors’ numbers. Therefore, Digital Stage 1 refers to the fi rst set of Digital Scroll Compressors (A1/B1) that will stage on together and Digital Stage 2 refers to the second set of Digital Scroll Compressors (A2/B2) that will stage on together. Please refer to AAON’ s wiring diagram for specifi c wiring of the unit.
Compressor Operation (Heat/Cool)
A compressor can energize if the following is true:
1. There is 24 VAC applied to the appropriate Binary Input for the Compressor.
2. If two compressors are enabled simultaneously, a 5 second staging delay will occur.
3. Suction Pressure is above the Low Suction Pressure Cooling (Heating) Setpoint.
4. Proof of Flow for the appropriate water loop is made.
5. Leaving Water Temp is above the Leaving Water Safety Setpoint (Heating Only).
6. A minimum off time of 3 minutes is met for that compressor.
NOTE: If the WSHP-X Module receives a signal on the Heat
Enable input, it will operate using the Heating Mode Setpoints.
Cooling Mode
Digital Scroll Compressor Control
When a Cool Signal is received, the WSHP-X Module will go into Cool­ing Mode. Once Proof of W ater Flow has been made and a start-up delay has been met, Compressor A1 (and B1*) will energize and Digital Stage 1 Analog Output will go to 50% and modulate as necessary to maintain the Supply Air Temperature at the Active Supply Air Setpoint that is broad­cast from the VCM-X WSHP Series Controller or SA Series Controller.
When Digital Stage 1 reaches 100%, a stage up timer is started. If Digital Stage 1 stays at 100% for the stage up timer, Compressor A2 (and B2*) will energize and both Digital Stage 1 and Digital Stage 2 outputs will go to 50% and will begin to modulate together.
If both systems are energized and they go below 30% and the Supply Air is below the Supply Air Setpoint by the Cooling Stage Window value, the stage down timer is started. If the systems remain below 30% for the duration of the stage down timer, Digital Stage 2 will deactivate and Digital Stage 1 will go to 60%. Digital Stage 1 will stage down if it is at 0% for the duration of the stage down timer.
* If confi gured for 4 modulating compressors.
Heat Pump Heating Mode
Heating Mode works the same as Cooling Mode except the Reversing Valve is switched and the sequence is opposite. Compressors modulate up when below the Heating Supply Air Setpoint and modulate down when above the setpoint.
Dehumidifi cation Mode
Fixed Compressors Only
In the Dehumidifi cation Mode, if this unit has only fi xed compressors, they will sequentially stage according to T able 1 on page 16 to maintain the Suction Pressure Setpoint. Compressors A1 & B1 will stage on to­gether fi rst followed sequentially by A2 & then B2. Stage Up and Stage Down delays will apply.
Digital Scroll Compressor Control
In Dehumidifi cation Mode, compressors will be controlled to maintain the Suction Pressure T emperature Setpoint. Digital Stage 1—Compres­sor A1 (and B1*) will modulate up to 100% before Digital Stage 2— Compressor A2 (and B2*) can be energized. When Digital Stage 2 is energized, Digital Stage 1 will be locked at 100%.
NOTE: Control of digital compressor(s) is only available when
the WSHP-X Module is connected to the VCM-X WSHP Series Controller or SA Series Controller.
Fixed Compressors Only
When a Cool Signal is received, the WSHP-X Module will go into Cooling Mode. Once Proof of Water Flow has been made, they will sequentially stage according to T able 1 on page 16, using Stage Up and Stage Down delays to maintain the Supply Air Setpoint that is broadcast from the VCM-X WSHP Series Controller or SA Series Controller.
Technical Guide
* If confi gured for 4 modulating compressors.
Staging Delays
Staging Delays minimum run times and minimum off times are sent from the VCM-X WSHP Series Controller or SA Series Controller.
Revised: 12/16/13
19
WSHP-X Module
Navigation Keys
LCD Display Screen & Navigation Keys
The WSHP-X Controller allows you to make confi guration changes, view status, change setpoints, create force modes, and perform diagnostics using the keypad next to the LCD display. See Figure 9 and refer to Table 5 for descriptions.
Figure 9: LCD Display and Navigation Keys
Navigation Key Key Function
MENU
UP
DOWN
ENTER
Use the MENU key to navigate through the Main Menu Screens
Use this key to adjust setpoints and change confi gurations. This key is also used to turn Valve Force Mode on.
Use this key to adjust setpoints and change confi gurations. This key is also used to turn Valve Force Mode off.
Use the Enter key to move through screens within Main Menu categories. Also, use this key to save setpoints and confi guration changes.
Table 5: Navigation Key Functions
20
Technical Guide
WSHP-X Module
Main Screens Map and WSHP Screens
Main Screens Map
Refer to the following map when navigating through the LCD Main Screens. The fi rst screen is the address screen. To scroll through the rest of the screens, press the <MENU> button.
ADDRESS
#
WSHP
AAON
Press to scroll through WSHP Screens.
Press to go to ALARM Screens.
ALARMS
Press to scroll through ALARMS Screens.
WSHP Screens
Refer to the following map when navigating through the Main Screens. From the WSHP AAON Screen, press <ENTER> to scroll through the screens.
WSHP
AAON
S/A or
COMM MODE or
COM T/O ERROR
In Stand-Alone Mode, the screen will only display S/A MODE. In Communications Mode, the screen will display COMM MODE and the
items below will scroll through the screen:
1. Number of good packets being received. This will roll over after 9999. Example: +XXXX
2. Number of checksum errors. This will stop at 9999. Example: C-XXXX
3. Number of packet length errors. This will stop at 9999 until power is cycled. Example: P-XXXX
Press to go to STATUS SYSTEM A Screens.
STATUS
SYSTEM A
Press to scroll through STATUS SYSTEM A Screens.
Press to go to STATUS SYSTEM B Screens.
STATUS
SYSTEM B
Press to scroll through STATUS SYSTEM B Screens.
Press to go to SETPOINT Screens.
SETPOINT
Press to scroll through SETPOINT Screens.
SOFTWARE
1053v100
CURRENT SOFTWARE VERSION
H20 CNFG
SINGLE or DUAL
WATER CIRCUIT CONFIGURATION
SINGLE (Typical for AAON Coil) or DUAL (Typical for AAON Tulsa)
REV VALV
OFF=COOL or
OFF=HEAT
REVERSING VALVE CONFIGURATION
OFF=COOL (No signal on reversing valve input equals cool mode) OFF=HEAT (No signal on reversing valve input equals heat mode)
Technical Guide
ADDRESS
#
21
WSHP-X Module
Alarm Screens
Alarm Screens
Refer to the following map when viewing the Alarm Screens. These screens will display automatically when alarms are present.
ALARMS
ALARMS
The alarms are as follows:
NO ALARMS: This will be shown if there are no current alarms. COMPRESSOR LOCKOUT (1-4):
• If a circuit’s Suction Pressure falls below the Low Suction Pressure Setpoint for longer than one minute twice within a two hour window, the compressor on that circuit will be locked out. Manual reset or change of mode is required to return to normal operation.
• If the Suction Pressure falls below the Unsafe Suction Setpoint for 5 seconds, that circuit’s compressor will locked out. Power will need to be cycled to restart the unit.
• If the Leaving Water Temperature falls below setpoint, the last compressor will be locked out until the Leaving Water
Temperature rises 6 degrees above setpoint.
• The Leaving Water Temperature remains below setpoint for 1 minute or falls 3 degrees below setpoint. This alarm will disable when the leaving water temperature rises 12 degrees
above the setpoint.
LOW H2O: The Leaving Water Temperature has dropped below set-
point. This alarm will disable when the leaving water temperature rises 6 degrees above the setpoint.
NO PROOF OF FLOW: There is a call for a compressor and there is
no Proof of Flow Input Enable for more than 3 minutes or if during Heat Pump heating, the Proof of Flow Enable is open for more than 2 sec­onds. This alarm will disable when Proof of Flow is enabled.
LOW SUCTION PRESSURE: The Circuit’s Suction Pressure has
dropped below the Low Suction Pressure for longer than one minute. This alarm will disable ten minutes after Suction Pressure rises above
the setpoint.
22
Technical Guide
WSHP-X Module
System Status A Screens
System Status A Screens
Refer to the following map when navigating through the System Status A Screens. From the SYSTEM STATUS A Screen, press scroll through the screens.
SYSTEM
STATUS A
Status Screens shown below will scroll automatically if LCD display is
left on this screen for 20 seconds.
A1 COMP
OFF,PENDING,ON or
Reason for Fail
SYSTEM A, COMPRESSOR 1
This screen displays the current status of the A1 Compressor.
OFF
PENDING: Compressor is off, but a request is made to be on, but the
1 minimum off time has not been met.
ON: HEAT or Cool
REASON FOR FAILURE: Low Pres, Lockout, Low H2O, No Flow
<ENTER> to
PO FLOW
YES or NO
PROOF OF WATER FLOW
A1 PRES
XXX
SYSTEM A, COMPRESSOR 1 PRESSURE READING
A2 PRES
XXX or NOT USED
SYSTEM A, COMPRESSOR 2 PRESSURE READING
If Single Water Confi guration, this screen will display “NOT USED.”
A2 COMP
OFF,PENDING,ON or
Reason for Fail
SYSTEM A, COMPRESSOR 2
This screen displays the current status of the A2 Compressor.
OFF
PENDING: Compressor is off, but a request is made to be on, but the
1 minimum off time has not been met.
ON: HEAT or Cool
REASON FOR FAILURE: Low Pres, Lockout, Low H2O, No Flow
H2O TEMP NO SENSR
LEAVING WATER TEMPERATURE READING
OR “NO SENSOR”
AOUT1
X%
ANALOG OUTPUT 1 PERCENT
0 - 100%
AOUT2
X%
ANALOG OUTPUT 2 PERCENT
0 - 100%
Technical Guide
23
WSHP-X Module
System Status B Screens
System Status B Screens
Refer to the following map when navigating through the System Status B Screens. From the SYSTEM ST ATUS B Screen, press scroll through the screens.
SYSTEM B DISABLED
If System B is disabled, the above screen will appear.
SYSTEM
STATUS B
Status Screens shown below will scroll automatically if LCD display is
left on this screen for 20 seconds.
B1 COMP
OFF,PENDING,ON or
Reason for Fail
<ENTER> to
H2O TEMP NO SENSR
LEAVING WATER TEMPERATURE READING
OR “NO SENSOR”
PO FLOW
YES or NO
PROOF OF WATER FLOW
B1 PRES
XXX
SYSTEM B, COMPRESSOR 1 PRESSURE READING
SYSTEM B, COMPRESSOR 1
This screen displays the current status of the B1 Compressor.
OFF
PENDING: Compressor is off, but a request is made to be on, but the
1 minimum off time has not been met.
ON: HEAT or Cool
REASON FOR FAILURE: Low Pres, Lockout, Low H2O, No Flow
B2 COMP
OFF,PENDING,ON or
Reason for Fail
SYSTEM B, COMPRESSOR 2
This screen displays the current status of the B2 Compressor.
OFF
PENDING: Compressor is off, but a request is made to be on, but the
1 minimum off time has not been met.
ON: HEAT or Cool
REASON FOR FAILURE: Low Pres, Lockout, Low H2O, No Flow
B2 PRES
XXX or NOT USED
SYSTEM B, COMPRESSOR 2 PRESSURE READING
If Single Water Confi guration, this screen will display “NOT USED.”
AOUT1
X%
ANALOG OUTPUT 1 PERCENT
0 - 100%
AOUT2
X%
24
ANALOG OUTPUT 2 PERCENT
0 - 100%
Technical Guide
WSHP-X Module
Setpoint Screens
Setpoint Status Screens
Refer to the following map when navigating through the Setpoint Sta­tus Screens. From the SETPOINTS Screen, press through the screens.
NOTE: The following screens are Status Screens. The Setpoints
can’t be changed from these screens.
SETPOINTS
LOWSP HT
XXX-XXX PSI
LOW SUCTION PRESSURE HEAT MODE SETPOINT
See Table below.
<ENTER> to scroll
UNSAFESP
40 PSI
UNSAFE SUCTION PRESSURE SETPOINT
See Table below.
Refrigerant
Unsafe
Suction
Setpoint Refrigerant
Unsafe
Suction
Setpoint
R410A 40 PSI R22 20 P S I
GLYCOL
xx%
GLYCOL SETPOINT
0%, 5%, 10%, 15%, 20%, 25%, 30%, 35%, 40%
Glycol %
Low Suction
Heat Setpoint Glycol %
Low Suction
Heat Setpoint
0% (R22) 57 PSI 20% 75 PSI
0% (410A) 100 PSI 25% 65 PSI
5% 93 PSI 30% 58 PSI 10% 87 PS I 35% 49 PSI 15% 82 PS I 40% 45 PSI
LOWSP CL
57 PSI or
85 PSI
LOW SUCTION PRESSURE COOL MODE SETPOINT
See Table below.
Refrigerant
Low Suction
Cool Setpoint Refrigerant
Low Suction
Cool Setpoint
R410A 85 P S I R22 57 PSI
REFRIGNT
410A or R22
REFRIGERANT
401A or R22
(If R22, Glycol Setpoint will default to 0%)
LOW H2O
XX DEG
LOW LEAVING WATER TEMPERATURE SETPOINT
See Table below.
Glycol %
Low Leaving
Water
Temperature
Setpoint Glycol %
Low Leaving
Water
Temperature
Setpoint
0% (R22) 37 ºF 20% 20 ºF
0% (410A) 37 ºF 25% 15 ºF
5% 34 10% 30 15% 27
ºF 30% 9 ºF ºF 35% 2 ºF ºF 40% 0 ºF
Technical Guide
25
WSHP-X Module
Troubleshooting
Safety Monitoring for Single Water Circuit
Proof of Flow
1. If there is a call for a compressor and there is no Proof of Flow Input Enable:
The module will wait up to 3 minutes to activate the Proof of Flow Alarm LED(s) which will blink the code indicating failure.
2. If the compressor(s) is (are) running and contact is opened for 2 seconds during Heat Pump Heating:
Compressor(s) will be turned off.
3. If the compressor(s) are running and contact is opened for 2 seconds during Cooling:
Proof of Flow Input will be ignored.
No alarm will be generated.
Low Suction Pressure Detection
1. If any Circuit’s Suction Pressure falls below the Low Suction Pressure Setpoint for longer than 1 minute, then the following will occur:
Low Leaving Water Temperature
NOTE: This safety monitoring is only performed in the Heat
Mode.
1. If the Leaving Water Temperature falls below setpoint, the following will occur:
The last compressor will turn off.
Alarm LED will indicate Compressor Low Water
Temp Shutoff.
Last compressor will be locked out until the
Leaving temperature is 6 degrees above setpoint.
2. If the Leaving Water Temperature remains below setpoint for 1 minute or falls 3 degrees below setpoint, the following will occur:
All compressors will deactivate.
Alarm LED will indicate Compressor Low
Water Temperature Shutoff.
All compressors will be locked out until the
Leaving Temperature is 12 degrees above setpoint.
The compressor(s) on that circuit will turn off.
Alarm LED will indicate Low Suction Pressure.
Compressor(s) will be enabled again after 10
minutes if Suction Pressure rises above setpoint.
2. If any Circuit’s Suction Pressure falls below the Low Suction Pressure Setpoint for longer than 1 minute a second time within a two hour window, then the following will occur:
The compressor(s) on that circuit will be locked out.
Alarm LED will indicate a Compressor Lockout.
Manual reset or change of mode (i.e., Cool to Heat)
must occur to reset back to normal operation.
Unsafe Suction Pressure Detection
If the Suction Pressure falls below the Unsafe Suction Setpoint for 5 seconds, the circuit’s compressor will be locked out immediately and will not be allowed to restart. You will need to reset the Power to restart the unit.
26
Technical Guide
WSHP-X Module
Troubleshooting
Safety Monitoring for Dual Water Circuit
Proof of Flow
There are separate inputs for System A and System B. System A pro­vides water for Compressors A1 & A2 and System B provides water for Compressors B1 & B2.
1. If there is a call for a compressor and there is no Proof of Flow Input Enable:
The module will wait up to 3 minutes to activate the Proof of Flow Alarm LED(s) which will blink the code indicating failure.
Proof of Water Flow A will disable compressors A1 and A2.
Proof of Water Flow B will disable compressors B1 and B2.
2. If the compressor(s) is (are) running and contact is opened for 2 seconds during Heat Pump Heating:
Compressor(s) will be turned off.
Proof of Water Flow A will disable compressors A1
and A2.
Proof of Water Flow B will disable compressors B1
and B2.
3. If the compressor(s) are running and contact is opened for 2 seconds during Cooling:
Proof of Flow Input will be ignored.
No alarm will be generated.
Low Suction Pressure Detection
1. If any Compressor’s Suction Pressure falls below the Low Suction Pressure Setpoint for longer than 1 minute, then the following will occur:
The compressor will turn off.
Alarm LED will indicate Low Suction Pressure.
Compressor will be enabled again after 10 minutes
if Suction Pressure rises above setpoint.
2. If any Compressor’s Suction Pressure falls below the Low Suction Pressure Setpoint for longer than 1 minute a second time within a two hour window, then the following will occur:
That compressor will be locked out.
Alarm LED will indicate a Compressor Lockout.
Manual reset or change of mode (i.e., Cool to Heat)
must occur to reset back to normal operation.
Unsafe Suction Pressure Detection
If the Suction Pressure falls below the Unsafe Suction Setpoint for 5 seconds, the compressor will be locked out immediately and will not be allowed to restart. You will need to reset the Power to restart the unit.
Low Leaving Water Temperature
NOTE: This safety monitoring is only performed in the Heat
Mode.
On the larger units, there are two separate condenser/water sections and each section (water system) has its own Leaving Water Temperature Sensor. Each sensor will only affect the compressors associated with that condenser/water section. The description below describes System A. System B works the same but will affect Compressors B1 & B2.
1. If the Leaving Water Temperature for System A falls below setpoint, the following will occur:
Compressor A2 will deactivate if active.
Alarm LED will indicate Compressor A2 Low
Water Temp Shutoff.
Compressor A2 will be locked out until the Leaving
temperature is 6 degrees above setpoint.
2. If the Leaving Water Temperature for System A remains below setpoint for 1 minute or falls 3 degrees below setpoint, the following will occur:
Compressor A1 will deactivate.
Alarm LED will indicate Compressor A1 & A2 Low
Water Temperature Shutoff.
Both Compressors will be locked out until the
Leaving Temperature is 12 degrees above setpoint.
Technical Guide
27
WSHP-X Module
Troubleshooting
Temperature Sensor Testing
The following sensor voltage and resistance tables are provided to aid in checking sensors that appear to be operating incorrectly. Many system operating problems can be traced to incorrect sensor wiring. Be sure all sensors are wired per the wiring diagrams in this manual.
If the sensors still do not appear to be operating or reading correctly, check voltage and/or resistance to confi rm that the sensor is operating correctly per the tables. Please follow the notes and instructions below each chart when checking sensors.
Temperature – Resistance – Voltage for
Type III 10 K Ohm Thermistor Sensors
Temp
(ºF)
-10 93333 4.620
-5 80531 4.550 0 69822 4.474 5 60552 4.390
10 52500 4.297 15 45902 4.200 20 40147 4.095 25 35165 3.982 30 30805 3.862 35 27140 3.737 40 23874 3.605 45 21094 3.470 50 18655 3.330 52 17799 3.275 54 16956 3.217 56 16164 3.160 58 15385 3.100 60 14681 3.042 62 14014 2.985 64 13382 2.927 66 12758 2.867 68 12191 2.810 69 11906 2.780 70 11652 2.752 71 11379 2.722 72 11136 2.695 73 10878 2.665
Resistance
(Ohms)
Voltage @
Input (VDC)
Temperature – Resistance – Voltage for
Type III 10 K Ohm Thermistor Sensors
Temp
(ºF)
74 10625 2.635 75 10398 2.607 76 10158 2.577 78 9711 2.520 80 9302 2.465 82 8893 2.407 84 8514 2.352 86 8153 2.297 88 7805 2.242 90 7472 2.187
95 6716 2.055 100 6047 1.927 105 5453 1.805 110 4923 1.687 115 4449 1.575 120 4030 1.469 125 3656 1.369 130 3317 1.274 135 3015 1.185 140 2743 1.101 145 2502 1.024 150 2288 0.952
Resistance
(Ohms)
Voltage @
Input (VDC)
Table 5, cont.: Temperature/Resistance for Type III 10K Ohm Thermistor Sensors
Thermistor Sensor Testing Instructions
Use the resistance column to check the thermistor sensor while discon­nected from the controllers (not powered).
Use the voltage column to check sensors while connected to powered controllers. Read voltage with meter set on DC volts. Place the “-” (minus) lead on GND terminal and the “+” (plus) lead on the sensor input terminal being investigated.
If the voltage is above 5.08 VDC, then the sensor or wiring is “open.” If the voltage is less than 0.05 VDC, then the sensor or wiring is shorted.
Table 5: Temperature/Resistance for Type III 10K Ohm Thermistor Sensors
28
Technical Guide
WSHP-X Module
Troubleshooting
OE275-01 Suction Pressure Transducer T esting for R-22 & R410-A Refrigerant
The Evaporator Coil Temperature is calculated by converting the Suc­tion Pressure to T emperature. The Suction Pressure is obtained by using the OE275-01 Suction Pressure Transducer , which is connected into the Suction Line of the Compressor.
Use the voltage column to check the Suction Pressure Transducer while connected to the WSHP-X Module. Read voltage with a meter set on DC volts. If the temperature/voltage or pressure/voltage readings do not align closely with the chart, your Suction Pressure Transducer is probably defective and will need to be replaced.
See the OE275-01 Suction Pressure Transducer , Pressure, T emperature, and Voltage Charts for R-22 and R410-A Refrigerant testing (Tables 6 & 7). The charts show a temperature range from 20°F to 80°F. For troubleshooting purposes, the DC Voltage readings are also listed with their corresponding temperatures and pressure.
OE275-01 Suction Pressure Transducer Coil Pressure
– Temperature – Voltage Chart for R-22 Refrigerant
OE275-01 Suction Pressure Transducer Coil Pressure
– Temperature – Voltage Chart for R410-A Refrigerant
°F
Temperature
21.19 80.94 1.8 59.03 168.10 3.2
24.49 87.16 1.9 61.17 174.32 3.3
27.80 93.39 2.0 63.19 180.55 3.4
30.99 99.62 2.1 65.21 186.78 3.5
33.89 105.84 2.2 67.23 193.00 3.6
36.80 112.07 2.3 69.24 199.23 3.7
39.71 118.29 2.4 71.15 205.46 3.8
42.30 124.52 2.5 72.95 211.68 3.9
44.85 130.75 2.6 74.76 217.91 4.0
47.39 136.97 2.7 76.57 224.14 4.1
49.94 143.2 2.8 78.37 230.36 4.2
52.23 149.42 2.9 80.18 236.59 4.3
54.50 155.65 3.0
56.76 161.88 3.1
PSI
Pressure
Signal
DC Volts
°F
Temperature
PSI
Pressure
Signal
DC Volts
°F
Temperature
20.00 31.13 1.0 55.32 93.39 2.0
20.00 37.36 1.1 58.86 99.62 2.1
20.46 43.58 1.2 62.13 105.84 2.2
25.71 49.80 1.3 65.27 112.07 2.3
30.84 56.03 1.4 68.42 118.29 2.4
35.41 62.26 1.5 71.39 124.52 2.5
39.98 68.49 1.6 75.20 130.75 2.6
44.00 74.71 1.7 77.00 136.97 2.7
48.00 80.94 1.8 79.80 143.20 2.8
51.78 87.16 1.9 80.00 149.42 2.9
PSI
Pressure
Signal
DC Volts
°F
Temperature
Pressure
PSI
Signal
Table 6: Coil Pressure/Voltage/Temp for OE275-01 Suction Pressure Transducers - R-22 Refrigerant
Table 7: Coil Pressure/Voltage/Temp for OE275-01 Suction Pressure Transducers - R410-A Refrigerant
DC Volts
Technical Guide
29
WSHP-X Module
Troubleshooting
Using LEDs to Verify Operation
The WSHP-X Module is equipped with LEDs that can be used to verify operation and perform troubleshooting. There are LEDs for communi­cation, operation modes, diagnostic codes, and relays. The Module has twenty LEDs—one used for power, one used for communications, one used for operation status, one used for alarms, fi ve used for compressor relays, four used for Suction Pressure Transducer status, and seven used for Binary Input status. See Figures 10 & 11 on page 31 for the LED locations. The LEDs associated with these inputs and outputs allow you to see what is active without using a voltmeter.
Operation Status LEDs
“STATUS” - This is the status blink code LED. It will light up and
rst blink the address of the Module. It will then blink out the Mode of Operation. See Table 8 below for Status Blink Code descriptions. The blink code descriptions are also located on the Module’s front cover. See Figure 10 for location.
No. of Blinks
1 Off Mode 2 Cool Mode 3 Heat Mode
Table 8: STATUS LED Blink Codes
Status
Y 102374 REV 0S
WATTMASTER CONTROLS
MADE IN USA
“COMM” - This LED will light up to indicate Communications with the VCM-X WSHP Series Controller or SA Series Controller. If Com­munications are established, the COMM LED will blink. You should not see this LED light up in stand-alone mode, because there would be no communications with the VCM-X WSHP Series Controller or SA Series Controller. See Figure 10 for location.
“ALARM” - This is the diagnostic blink code LED. It will light up and blink out diagnostic codes. See Table 9 below for Diagnostic Blink Code descriptions. The blink code descriptions are also located on the Module’s front cover. See Figure 10 for location.
No. of
Blinks
1 Low Suction Pressure 2 Compressor Lockout
3 Water Flow Failure 4 Low Leaving Water Temp
Alarm
Table 9: ALARM LED Blink Codes
Figure 10: Operation Status LED Locations
30
Technical Guide
WSHP-X Module
Troubleshooting
Suction Pressure Transducer LEDs
“PRES 1-4” - There are LEDs for each of the Suction Pressure Transducers. Since each compressor has a sensor, these LEDs which are located on the top left of the WSHP-X Module will give a better indication of which compressor is causing an alarm. See Table 10 for PRES LED status descriptions. See Figure 11 for locations.
No. of
Blinks
Solid On Sensor is Detected and is OK Solid Off Sensor is Not Detected
1 Low Suction Pressure on this Compressor 2 Compressor is Locked Out
Table 10: PRES 1-4 LED Blink Codes
Status
LED Diagnostics
“POWER” LED: When the WSHP-X Module is powered up, the POWER LED (located above the address switches) should light up and stay on continuously. If it does not light up, check to be sure that the power wiring is connected to the board, the connections are tight, and the VCM-X WSHP Series Controller or SA Series Controller is powered (if connected). If after making all these checks, the POWER LED does not light up, the module is probably defective.
“COMM” LED: When the WSHP-X Module is powered up while in Stand Alone Mode, the COMM LED does not light up. When the module is connected to the VCM-X WSHP Series Controller or SA Series Con­troller, the COMM LED should light up, indicating Communications. Each time Communications are detected, this LED should continuously blink on and off for a half second. This LED should never stop checking for a Communications signal. If it does not light up, check to be sure that the power wiring is connected to the board, the connections are tight, and the VCM-X WSHP Series Controller or SA Series Controller is powered. If after making all these checks, the COMM LED does not light up, the board is probably defective.
“ST A TUS” LED: As previously described, when the WSHP Module is rst powered up, the STA TUS LED will b
link out the Mode of Operation.
“ALARM” LED: As previously described, this LED will blink on and off to indicate alarms and diagnostics.
NOTE: The WSHP-X Module contains no user-serviceable parts.
Contact qualifi ed technical personnel if your Module is not operating correctly.
Figure 11: PRES 1-4 LED Locations
Technical Guide
31
www.aaon.com
2425 So. Yukon Ave • Tulsa, OK 74107-2728
Ph: (918) 583-2266 • Fax: (918) 583-6094
AAON® Manual Part No. V23560
WattMaster Manual Form No: AA-WSHPX-FIELD-TGD-01C
Loading...