Mounting and Dimensions ............................................................................................................................................................4
Important Wiring Considerations ..................................................................................................................................................5
Stand-Alone Wiring for Single Water Circuit ................................................................................................................................5
Stand-Alone Wiring for Dual Water Circuit ...................................................................................................................................6
VCM-X WSHP or SA Controller to WSHP-X Module Wiring Diagram Single Water Circuit .........................................................8
VCM-X WSHP E-BUS or SA E-BUS Controller to WSHP-X Module Wiring Single Water Circuit..............................................10
VCM-X WSHP or SA Controller to WSHP-X Module Wiring Diagram Dual Water Circuit..........................................................12
VCM-X WSHP E-BUS or SA E-BUS Controller to WSHP-X Module Wiring Dual Water Circuit ................................................14
START-UP AND COMMISSIONING .................................................................................................................. 16
Unit Confi gurations .....................................................................................................................................................................16
SEQUENCE OF OPERATION ........................................................................................................................... 17
Input Commands (VCM-X WSHP or SA Connection) ................................................................................................................18
Modes of Operation ....................................................................................................................................................................19
Safety Monitoring for Single Water Circuit .................................................................................................................................26
Safety Monitoring for Dual Water Circuit ....................................................................................................................................27
Temperature Sensor Testing ......................................................................................................................................................28
Pressure Transducer T roubleshooting .......................................................................................... ............................................29
Using LEDs to Verify Operation..................................................................................................................................................30
LED Diagnostics .........................................................................................................................................................................31
PART NUMBER CROSS REFERENCE TABLE
PART DESCRIPTIONORIONAAON
WSHP-X ModuleOE334-26-WSHPX-AV18330
VCM-X WSHP E-BUS ControllerOE332-23E-VCMX-WSHP-AV07140
VCM-X WSHP ControllerOE332-23-VCMX-WSHP-AR90810
SA E-BUS ControllerOE332-23E-SA-AV07160
SA ControllerOE332-23-SA-AR96070
E-BUS Distribution ModuleOE365-23-EBDR82930
www.aaon.com
WattMaster Controls Inc.
8500 NW River Park Drive · Parkville , MO 64152
Toll Free Phone: 866-918-1100
PH: (816) 505-1100 · FAX: (816) 505-1101 · E-mail: mail@wattmaster.com
Visit our web site at www.orioncontrols.com
WattMaster Form : AA-WSHPX-FIELD-TGD-01C
Copyright December 2013 WattMaster Controls, Inc.
AAON Manual Part Number: V23560
®
AAON
is a registered trademark of AAON, Inc., Tulsa, OK.
Neither WattMaster Controls, Inc. nor AAON
assumes any responsibility for errors or omissions in this document.
This document is subject to change without notice.
®
WSHP-X Module
Module Overview
Overview
The OE334-26-WSHPX-A Water Source Heat Pump X (WSHP-X)
Module monitors the compressors on an AAON
Pump unit and can disable the compressors based on low Suction Pressure, Leaving Water Temperature, and Water Proof of Flow inputs. It
also utilizes a Delay Timer to prevent the compressors from turning on
at the same time.
The WSHP-X Module’s water circuit con fi guration can be either single
or dual. There are eight R410-A glycol con fi gurations for the WSHP-X
Module—0%-40% in increments of 5%. There are two refrigerant selections—R410-A refrigerant and R-22 refrigerant. If R-22 refrigerant is
selected, the glycol will automatically default to 0%.
The WSHP-X Module can be used stand-alone. It can also be connected
to the VCM-X WSHP Controller or the SA Controller using the E-BUS
Distribution Module or the module can be directly connected to the
VCM-X WSHP E-BUS Controller or SA E-BUS Controller, allowing
the Module to receive setpoints from the Controllers. See chart on page 2 for part numbers. Please note: The SA series of controllers only work
with the R410-A dual water circuit confi gurations.
The WSHP-X Module requires a 24 VAC power connection with an
appropriate VA rating.
NOTE: The WSHP-X Module is factory set for R410-A and 0%
glycol.
®
Water Source Heat
Features
The WSHP-X Module provides the following:
Can be operated stand-alone or connected to a
VCM-X WSHP Controller or SA Controller using
the E-BUS Distribution Module to E-BUS interface
Can be directly connected to a VCM-X WSHP E-BUS
Controller or SA E-BUS Controller
Capable of controlling digital compressors when
connected to a VCM-X WSHP Series Controller or
SA Series Controller
Monitors suction pressure, leaving water
temperature, and water proof of fl ow
Provides Delay Timer to prevent compressors
from turning on at the same time
Contains a 2x8 LCD character display and 4 buttons
that allow for status display, setpoint changes, and
confi guration changes
NOTE: The WSHP-X Module contains no user-serviceable parts.
Contact qualifi ed technical personnel if your Module is
not operating correctly.
ALARM
UP
M
ENTER
DOWN
GND
+24 VAC
- HEAT ENABLE
- WATER POF
- WATER POF
- COMMON
CONNECT
MENU
RELAY CONTACT RATING
IS 1 AMP MAX @ 24 VAC
COMP.A1 ENABLE
COMP.A2 ENABLE
COMP. B1 ENABLE
COMP. B2 ENABLE
ALARM OUTPUT
RELAY COMMON
DIGITAL COMP. A1, A2, B1, B2
STAGE 1- COMP. A1/B1STAGE 2 - COMP. A2/B2
CONNECT TO CNTLR C2 TERM.
E-BUS
www.aaon.com
www.orioncontrols.com
OE334-26-WSHPX-A WSHP-X MODULE AAON NO.: V18330
NON-DIGITAL COMPRESSORS
SUCT. PR. SENSOR
+5V
PRES 1=A1, PRES 2=A2
PRES
PRES 3=B1, PRES 4=B2
GND
+5 TO RED, PRES TO WHT & GND TO BLK
DIGITAL COMRESSORS
+5V
NOT USED
PRES
PRES 1=A1, PRES 2=A2
GND
PRES 3=B1, PRES 4=B2
+5 NOT USED, PRES TO P6 & GND TO P5
BIN 1
- COMP.A1 EN.
- COMP.A2 EN.
BIN 2
BIN 3
- COMP. B1 EN.
- COMP. B2 EN.
BIN 4
T1
- LEAVING WATER TEMP A
T2
- LEAVING WATER TEMP B
- GROUND
GND
WattMaster Label
#SW000054
Rev.: 1A
BIN 5
BIN 6
BIN 7
COM
E-BUS
CONNECT
WATTMASTER CONTROLS
R1
R2
R3
R4
R5
RC
AO1
A2O
Y 102374 REV 0S
MADE IN USA
Figure 1: Water Source Heat Pump X Module
Technical Guide
3
WSHP-X Module
Installation & Wiring
Environmental Requirements
The WSHP-X Module needs to be installed in an environment that can
maintain a temperature range between -30°F and 150°F and not exceed
90% RH levels (non-condensing).
Mounting
The WSHP-X Module is housed in a plastic enclosure. It is designed to
be mounted by using the 3 mounting holes in the enclosure base. It is
important to mount the module in a location that is free from extreme
high or low temperatures, moisture, dust, and dirt. Be careful not to
damage the electronic components when mounting the module. See Figure 2 for Module dimensions (in inches).
0.18 DIA. TYP. 3 PL.
Power Supply
The WSHP-X Module requires a 24 VAC power connection with an
appropriate VA rating.
If you will be connecting the WSHP-X Module to a VCM-X WSHP
Series Controller or SA Series Controller, one of the most important
checks to make before powering up the system for the fi rst time is to
make sure that the Controller is confi gured properly for your applica-
tion. Refer to the VCM-X Controller Technical Guide, VCM-X Modular
E-BUS Controller Technical Guide, SA Controller Technical Guide, or
SA E-BUS Controller Technical Guide for more information.
WARNING: Observe polarity! All boards must be wired
GND-to-GND and 24 VAC-to-VAC. Failure to
observe polarity could result in damage to the
boards.
2.07
0.29
5.64
ALARM
UP
M
DOWN
GND
ENTER
+24 VAC
- HEAT ENABLE
- WATER POF
- WATER POF
- COMMON
MENU
RELAY CONTACT RATING
IS 1 AMP MAX @ 24 VAC
COMP.A1 ENABLE
COMP.A2 ENABLE
COMP. B1 ENABLE
COMP. B2 ENABLE
ALARM OUTPUT
RELAY COMMON
DIGITAL COMP. A1,A2, B1, B2
STAGE 1- COMP. A1/B1STAGE 2 - COMP. A2/B2
CONNECT TO CNTLR C2 TERM.
E-BUS
CONNECT
www.aaon.com
www.orioncontrols.com
OE334-26-WSHPX-A WSHP-X MODULE AAON NO.: V18330
NON-DIGITAL COMPRESSORS
SUCT. PR. SENSOR
+5V
PRES 1=A1, PRES 2=A2
PRES
PRES 3=B1, PRES 4=B2
GND
+5 TO RED, PRES TO WHT & GNDTO BLK
DIGITAL COMRESSORS
+5V
NOT USED
PRES
PRES 1=A1, PRES 2=A2
GND
PRES 3=B1, PRES 4=B2
+5 NOT USED, PRES TO P6 & GND TO P5
BIN 1
- COMP.A1 EN.
- COMP.A2 EN.
BIN 2
BIN 3
- COMP. B1 EN.
- COMP. B2 EN.
BIN 4
T1
- LEAVING WATER TEMP A
T2
- LEAVING WATER TEMP B
- GROUND
GND
WattMaster Label
#SW000054
Rev.: 1A
BIN 5
BIN 6
BIN 7
COM
E-BUS
CONNECT
4.14
5.83
WATTMASTER CONTROLS
R1
R2
R3
R4
R5
RC
AO1
A2O
0.56
5.05
Note: Height is 1.49 inches.
Figure 2: Water Source Heat Pump X Module Dimensions
4
Technical Guide
WSHP-X Module
Installation & Wiring
Important Wiring Considerations
Please read carefully and apply the following information when wiring
the WSHP-X Module:
1. To operate the WSHP-X Module in Stand-Alone mode, you
must connect power to the 24 VAC input terminal block.
Do not allow wire strands to stick out and touch adjoining
terminals. This could potentially cause a short circuit.
2. The 1 to 5 VDC signals for the Compressor modulation need
to use 18-gauge shielded twisted pair cable, and the Drain wire
must be the GND signal.
3. All 24 VAC wiring must be connected so that all ground
wires remain common. Failure to follow this procedure can
result in damage to the module and connected devices.
4. Be sure all modular wiring harness connectors are seated
fi rmly in their respective modular connectors on the circuit
board.
WATER POF SYSTEMA CONTACT
WATER POF SYSTEM B CONTACT
RD
WH
BK
HEAT ENABLE CONTACT
SIG 1
GND
SIG 1
GND
BIN1
BIN2
BIN3
BIN4
BIN5
BIN6
BIN7
COM
GND
+V
ALARM
+V
T1
www.aaon.com
www.orioncontrols.com
OE334-26-WSHPX-A WSHP-X MODULE AAON NO.: V18330
NON-DIGITALCOMPRESSORS
SUCT. PR. SENSOR
+5V
PRES 1=A1, PRES 2=A2
PRES
PRES 3=B1, PRES 4=B2
GND
+5 TO RED, PRESTO WHT & GND TO BLK
DIGITALCOMRESSORS
+5V
NOT USED
PRES
PRES 1=A1, PRES 2=A2
GND
PRES 3=B1, PRES 4=B2
+5 NOT USED, PRES TO P6 & GNDTO P5
BIN 1
- COMP.A1 EN.
BIN 5
BIN 6
BIN 7
COM
E-BUS
CONNECT
- HEATENABLE
- WATER POF
- WATER POF
- COMMON
- COMP.A2 EN.
BIN 2
BIN 3
- COMP. B1 EN.
- COMP. B2 EN.
BIN 4
T1
- LEAVING WATERTEMP A
T2
- LEAVING WATERTEMP B
- GROUND
GND
WattMaster Label
#SW000054
Rev.: 1A
5. All wiring is to be in accordance with local and
national electrical codes and specifi cations.
6. Check all wiring leads at the terminal block for tightness.
Be sure that wire strands do not stick out and touch adjacent
terminals. Confi rm that all transducers required for your
system are mounted in the appropriate location and wired into
the correct terminals.
Stand-Alone Wiring Single Water
Circuit
To operate the WSHP-X Module as Stand Alone, connect the Module to
a 24 VAC power connection with an appropriate VA rating. See Figure 3 for wiring.
NOTE:NORMALLY
ALL RELAY OUTPUTS ARE
OPEN AND RATED FOR 24 VAC POWER ONLY
- 1 AMP MAXIMUM LOAD
WATTMASTER CONTROLS
UP
M
MENU
DOWN
RELAYCONTACT RATING
IS 1 AMP MAX @ 24 VAC
COMP.A1 ENABLE
COMP.A2 ENABLE
COMP. B1 ENABLE
COMP. B2 ENABLE
ALARM OUTPUT
RELAYCOMMON
DIGITALCOMP. A1, A2, B1, B2
STAGE 1- COMP.A1/B1STAGE 2 - COMP.A2/B2
CONNECTTO CNTLR C2 TERM.
GND
E-BUS
CONNECT
+24 VAC
ENTER
R1
R2
R3
R4
R5
COMM
R1
R2
R3
R4
R5
RC
AO1
A2O
NOTE:
OUTPUTS ARE NOT USED ON
STAND ALONE APPLICATIONS
COMPRESSOR A1 ENABLE OUTPUT
COMPRESSOR A2 ENABLE OUTPUT
COMPRESSOR B1 ENABLE OUTPUT
COMPRESSOR B2 ENABLE OUTPUT
ALARM OUTPUT
HVAC UNIT CONNECTIONS
GND
24 VAC
E
R
LEAVING WATER TEMPERATURE
Figure 3: Water Source Heat Pump X Module as Stand-Alone for Single Water Circuit
Technical Guide
5
WSHP-X Module
Installation & Wiring
Stand-Alone Wiring Dual Water
Circuit
To operate the WSHP-X Module as Stand Alone, connect the Module to
a 24 VAC power connection with an appropriate VA rating. See Figure 4 for wiring.
HEAT ENABLE CONTACT
WATER POF SYSTEMA CONTACT
WATER POF SYSTEM B CONTACT
WH
BK
RD
WH
BK
RD
WH
BK
RD
WH
BK
SIG 1
GND
SIG 2
GND
SIG 1
GND
SIG 2
GND
BIN1
BIN2
BIN3
BIN4
BIN5
BIN6
BIN7
COM
GND
+V
+V
+V
+V
T1
T2
ALARM
www.aaon.com
www.orioncontrols.com
OE334-26-WSHPX-A WSHP-X MODULE AAON NO.: V18330
NON-DIGITALCOMPRESSORS
SUCT. PR. SENSOR
+5V
PRES 1=A1, PRES 2=A2
PRES
PRES 3=B1, PRES 4=B2
GND
+5 TO RED, PRESTO WHT & GND TO BLK
DIGITALCOMRESSORS
+5V
NOT USED
PRES
PRES 1=A1, PRES 2=A2
GND
PRES 3=B1, PRES 4=B2
+5 NOT USED, PRES TO P6 & GNDTO P5
BIN 1
- COMP.A1 EN.
- COMP.A2 EN.
BIN 2
BIN 3
- COMP. B1 EN.
- COMP. B2 EN.
BIN 4
T1
- LEAVING WATERTEMP A
T2
- LEAVING WATERTEMP B
- GROUND
GND
WattMaster Label
#SW000054
Rev.: 1A
Module
BIN 5
- HEATENABLE
- WATER POF
BIN 6
BIN 7
- WATER POF
COM
- COMMON
E-BUS
CONNECT
UP
M
MENU
DOWN
RELAYCONTACT RATING
IS 1 AMP MAX @ 24 VAC
COMP.A1 ENABLE
COMP.A2 ENABLE
COMP. B1 ENABLE
COMP. B2 ENABLE
ALARM OUTPUT
RELAYCOMMON
DIGITALCOMP. A1, A2, B1, B2
STAGE 1- COMP.A1/B1STAGE 2 - COMP.A2/B2
CONNECT TO CNTLR C2TERM.
GND
E-BUS
CONNECT
NOTE:NORMALLY
ALL RELAY OUTPUTS ARE
OPEN AND RATED FOR 24 VAC POWER ONLY
- 1 AMP MAXIMUM LOAD
WATTMASTER CONTROLS
ENTER
R1
R2
R3
R4
R5
COMM
COMPRESSOR A1 ENABLE
COMPRESSOR A2 ENABLE
COMPRESSOR B1 ENABLE
COMPRESSOR B2 ENABLE
ALARM OUTPUT
HVAC UNIT CONNECTIONS
R1
R2
R3
R4
R5
RC
AO1
A2O
+24 VAC
NOTE:
OUTPUTS ARE NOT USED ON
STAND ALONE APPLICATIONS
GND
24 VAC
E
R
LEAVING WATER
TEMPERATURE
FOR SYSTEM A
LEAVING WATER
TEMPERATURE
FOR SYSTEM B
Figure 4: Water Source Heat Pump X Module as Stand-Alone for Dual Water Circuit
6
Technical Guide
WSHP-X Module
Installation & Wiring
E-BUS to WSHP-X Module Wiring
The WSHP-X Module connects to the E-BUS Distribution Module using a modular HSSC cable. The WSHP-X Module requires a 24 VAC
power connection with an appropriate VA rating.
The E-BUS Distribution Module connects to the VCM-X WSHP Controller, VCM-X Expansion Module, SA Controller (Dual W ater Circuit
only), SA Expansion Module (Dual Water Circuit only), or 12 Relay
Expansion Module using the I
Figure 7 on page 12 for wiring.
Any E-BUS Module can be connected to each of the four E-BUS Distribution Module’s output ports or can be daisy-chained together using
HSSC cables.
If using a spliced terminal connection for longer runs, one module can be
connected to the E-BUS Distribution Module and any additional modules
would be daisy-chained to the fi rst module. For more information, refer
to the E-BUS Distribution Module Technical Guide.
2
C port. See Figure 5 on page 8 and
VCM-X WSHP E-BUS or SA E-BUS
Controller to WSHP-X Module Wiring
The WSHP-X Module connects to the E-BUS Controller using a modular
HSSC cable. The WSHP-X Module requires a 24 VAC power connection
with an appropriate VA rating. See Figure 6 on page 10 and Figure 8 on page 14 for wiring.
WARNING: Be sure all controllers and modules are
powered down before connecting or
disconnecting HSSC cables.
Addressing
When the WSHP-X Module is connected to the E-BUS Distribution
Module, set the WSHP-X Module’s address to 1. Set the address consecutively for each WSHP-X Module you are using.
NOTE: Address zero defaults to address 1.
Any E-BUS Module can be connected to the E-BUS Controller’s E-BUS
port or can be daisy-chained together using HSSC cables.
NOTE: Contact Factory for the correct HSSC cable length
for your application. Cables are available in 1/4, 1/2,
1, 2, 3, 4, and 5 Meter lengths and 100 and 150 Foot
lengths.
Technical Guide
7
WSHP-X Module
Installation & Wiring
VCM-X WSHP to WSHP-X Module
Wiring for Single Water Circuit
The VCM-X WSHP Controller or SA Controller communicates with the
WSHP-X Module using the E-BUS Distribution Module. See Figure 5 for wiring details.
For Stand Alone Applications,
Connect To System Manager.
For Network Applications
Connect To Next Controller
And/Or MiniLink PD On Local Loop.
Local Loop
RS-485
9600 Baud
All Comm Loop Wiring Is
Straight Thru
T to T, R to R & SHLD to SHLD
See Individual Component
Wiring Diagrams For
Detailed Wiring Of Analog
Inputs And Outputs
AI1 SETAI2 SET AI3 SET
AI4 SET AI5 SETAI7 SET
AI1
AI2
AI3
AI4
AI5
AI7
(OE332-23-WSHP-C)
VCM-X WSHP Controller
AI1 SET AI2 SET AI3 SET
AI4 SET AI5 SET AI7 SET
NOTE: When using the WSHP-X Module, all compressors
will be wired from the WSHP-X Module, not the
VCM-X WSHP Controller
Note:
All Relay Outputs Are Normally Open And Rated
For 24 VAC Power Only.
1 Amp Maximum Load.
R - 24VAC
G - Fan ON/OFF Only
Relay Output Contacts
R2 Through R5 May Be User Configured For The
Following:
1 - Heating Stages
2 - See Note 1 Below
3 - Warm-up Mode Command (VAV Boxes)
4 - Reversing Valve (Air To Air Heat Pumps)
5 - Reheat Control (Dehumidification)
6 - Exhaust Fan Interlock
7 - Preheater For Low Ambient Protection
8 - Alarm
9 - Override
10 - Occupied
11 - OA Damper
12 - Heat Wheel
Note:
1.) When Using The WSHP-X Module, All
Compressors Will Be Wired From The Module, Not
The VCM-X Controller.
2.) A Total Of 20 Relays Are Available ByAdding Relay
Expansion Modules. All Expansion Module Relay
Outputs Are User-Configurable As ListedAbove.
GND
24VAC
Size Transformer For Correct
Total Load.
VCM-X Controller = 8 VA
Line Voltage
Connect To
E-BUS
Distribution
Module
GND
24 VAC
Jumpers
Splice If Required
OE271
Static Pressure
Transducer
Connect FRP Tubing To High Pressure
Port (Bottom Tube) And Route To Static
Pressure Pickup Probe Located In Unit
Discharge. Leave Port Marked “Lo” Open
ToAtmosphere
Connect To E-BUS Distribution Module or
Expansion Module(s)
(When Used)
Warning:
24 VAC Must Be Connected So That All Ground
Wires Remain Common. Failure To Do So Will
Result In Damage To The Controllers.
Connect To Digital Room Sensor And/Or
Digital CO Sensor
2
Figure 5: VCM-X WSHP Controller to WSHP-X Module Wiring Diagram for Single Water Circuit
8
Technical Guide
Line Voltage
OE365-23-EBD E-BUS
Distribution Module
YS102308
REV 1
I2CTO COMM
DIST. BOARD
OUTPUT
+COMM
SHLD
-COMM
GND
+VDC
INPUT
+COMM
SHLD
-COMM
GND
24VAC
GND
PWR
WSHP-X Module
Installation & Wiring
CIRCUIT B
SUCTION PRESSURE TRANSDUCER
BK
WH
RD
CIRCUIT A
SUCTION PRESSURE TRANSDUCER
BK
WH
RD
NOTE:
OE334-26-WSHPX-A Water Source
Heat Pump X Module
Y 102374 REV 0S
ENTER
GND
R1
R2
R3
R4
R5
RC
AO1
A2O
24 VAC
WATTMASTER CONTROLS
MADE IN USA
ALARM
UP
M
BIN 5
BIN 6
BIN 7
COM
E-BUS
CONNECT
- HEATENABLE
- WATER POF
- WATER POF
- COMMON
MENU
DOWN
RELAYCONTACT RATING
IS 1 AMPMAX @ 24 VAC
COMP.A1 ENABLE
COMP.A2 ENABLE
COMP. B1 ENABLE
COMP. B2 ENABLE
ALARM OUTPUT
RELAYCOMMON
DIGITALCOMP. A1, A2, B1, B2
STAGE 1- COMP.A1/B1STAGE 2 - COMP.A2/B2
CONNECTTO CNTLR C2 TERM.
GND
E-BUS
CONNECT
+24 VAC
www.aaon.com
www.orioncontrols.com
OE334-26-WSHPX-A WSHP-X MODULE AAON NO.: V18330
NON-DIGITALCOMPRESSORS
SUCT. PR. SENSOR
+5V
PRES 1=A1, PRES 2=A2
PRES
PRES 3=B1, PRES 4=B2
GND
+5TO RED, PRES TO WHT & GND TO BLK
DIGITALCOMRESSORS
+5V
NOT USED
PRES
PRES 1=A1, PRES 2=A2
GND
PRES 3=B1, PRES 4=B2
+5 NOTUSED, PRES TO P6 & GND TO P5
BIN 1
- COMP.A1 EN.
- COMP.A2 EN.
BIN 2
BIN 3
WATER POF
CONTACT
BIN6
COM
T1
485 DRV
GND
- COMP. B1 EN.
- COMP. B2 EN.
BIN 4
T1
- LEAVING WATERTEMP A
T2
- LEAVING WATERTEMP B
- GROUND
GND
WattMaster Label
#SW000054
Rev.: 1A
ALL RELAY OUTPUTS
NORMALLY OPEN AND
ARE
RATED FOR 24 VAC POWER
ONLY
R1
R2
R3
R4
R5
COMM
AO1
DIGITAL STAGE 1 (1.5-5V)
AO2
DIGITAL STAGE 2 (1.5-5V)
HVAC UNIT
CONNECTIONS
COMP.A1 ENABLE
COMP.A2 ENABLE
COMP. B1 ENABLE
COMP. B2 ENABLE
ALARM OUTPUT
WARNING!!
Observe Polarity! All boards must be
wired with GND-to-GND and 24 VACto-24 VAC. Failure to observe polarity
could result in damage to the boards.
Modular Cable
Connect To
VCM-X WSHP Controller
HSSC Cable
HSSC Cable
Connect To Other
WattMaster-Approved
E-BUS Expansion Module(s)
E
LEAVING WATER TEMPERATURE
Figure 5, cont.: VCM-X WSHP Controller to WSHP-X Module Wiring Diagram for Single Water Circuit
Technical Guide
24 VAC Transformer
3 VA Minimum
WARNING!!
Observe Polarity! All
boards must be wired
with GND-to-GND and
24 VAC-to-24 VAC.
Failure to observe
polarity could result in
damage to the boards.
9
WSHP-X Module
Installation & Wiring
VCM-X WSHP E-BUS or SA E-BUS
Controller to WSHP-X Module Wiring
for Single Water Circuit
The WSHP-X Module connects to the E-BUS Controller using a modular
HSSC cable. The WSHP-X Module requires a 24 VAC power connection
with an appropriate VA rating. See Figure 6 below for wiring.
OE334-26-WSHPX-A Water Source
+V
CIRCUIT A
SUCTION PRESSURE
TRANSDUCER
CIRCUIT B
SUCTION PRESSURE
TRANSDUCER
WARNING!! Observe Polarity! All
boards must be wired with GNDto-GND and 24 VAC-to-24 VAC.
Failure to observe polarity could
result in damage to the boards.
Connect To Other
WattMaster-Approved
E-BUS Expansion Module(s)
WATER POF
WH
WH
RD
SIG 1
BK
GND
+V
RD
SIG 1
BK
GND
BIN6
COM
T1
GND
HSSC Cable
Any E-BUS Module can be connected to the E-BUS Controller’s E-BUS
port or can be daisy-chained together using HSSC cables.
NOTE: When using the WSHP-X Module, all compressors
will be wired from the WSHP-X Module, not the
VCM-X WSHP E-BUS Controller.
NOTE:
ALL RELAY OUTPUTS
NORMALLY OPEN AND
Heat Pump X Module
ALARM
UP
M
ENTER
DOWN
RELAYCONTACT RATING
IS 1 AMP MAX @ 24 VAC
ALARM OUTPUT
CONNECTTO CNTLR C2 TERM.
GND
+24 VAC
GND
E
BIN 5
BIN 6
BIN 7
COM
E-BUS
CONNECT
- HEATENABLE
- WATER POF
- WATER POF
- COMMON
MENU
COMP.A1 ENABLE
COMP.A2 ENABLE
COMP. B1 ENABLE
COMP. B2 ENABLE
RELAYCOMMON
DIGITALCOMP. A1, A2, B1, B2
STAGE 1- COMP.A1/B1STAGE 2 - COMP.A2/B2
E-BUS
CONNECT
www.aaon.com
www.orioncontrols.com
OE334-26-WSHPX-A WSHP-X MODULE AAON NO.: V18330
NON-DIGITALCOMPRESSORS
SUCT. PR. SENSOR
+5V
PRES 1=A1, PRES 2=A2
PRES
PRES 3=B1, PRES 4=B2
GND
+5 TO RED, PRESTO WHT & GND TO BLK
DIGITALCOMRESSORS
+5V
NOT USED
PRES
PRES 1=A1, PRES 2=A2
GND
PRES 3=B1, PRES 4=B2
+5 NOT USED, PRESTO P6 & GND TO P5
BIN 1
- COMP.A1 EN.
- COMP.A2 EN.
BIN 2
BIN 3
- COMP. B1 EN.
- COMP. B2 EN.
BIN 4
T1
- LEAVING WATERTEMP A
T2
- LEAVING WATERTEMP B
- GROUND
GND
WattMaster Label
#SW000054
Rev.: 1A
R1
R2
R3
R4
R5
RC
AO1
A2O
24 VAC
Y 102374 REV 0S
WATTMASTER CONTROLS
MADE IN USA
ARE
RATED FOR 24 VAC POWER
ONLY
HVAC UNIT
CONNECTIONS
R1
R2
R3
R4
R5
COMM
AO1
AO2
COMP. A1 ENABLE
COMP. A2 ENABLE
COMP. B1 ENABLE
COMP. B2 ENABLE
ALARM OUTPUT
DIGITAL STG 1 (1.5-5V)
DIGITAL STG 2 (1.5-5V)
Line Voltage
24 VAC Transformer
3 VA Minimum
WARNING!!
Observe Polarity! All
boards must be wired
with GND-to-GND and 24
VAC-to-24 VAC. Failure
to observe polarity could
result in damage to the
boards.
HSSC Cable
Connect To VCM-X WSHP
E-BUS Controller
LEAVING WATER TEMPERATURE
Figure 6: VCM-X E-BUS Controller to WSHP-X Module Wiring Diagram for Single Water Circuit
10
Technical Guide
WSHP-X Module
NOTE: Contact Factory for the correct HSSC cable length for
your application. Cables are available in ¼, ½, 1, 2, 3,
4, and 5 Meter lengths and 100 and 150 Foot lengths.
WARNING: Be sure all controllers and modules are
powered down before connecting or
disconnecting HSSC cables.
For Stand Alone Applications,
Connect To System Manager. For Network
Applications Connect To Next Controller
And/Or MiniLink PD On Local Loop.
Local Loop
RS-485
9600 Baud
All Comm Loop Wiring Is
Straight Thru
T to T, R to R & SHLD to SHLD
HSSC Cable Connect To
VCM-X E-BUS Port
AI1 SETAI2 SET AI3 SET
See Individual
Component
Wiring Diagrams
For Detailed
Wiring Of Analog
Inputs And
Outputs
AI4 SET AI5 SETAI7 SET
OE332-23E-VCMX-WSHP
E-BUS Controller
RS-485 COMMUNICATION LOOP. WIRE
“R” TO“R”, “T” TO “T” “SHLD” TO “SHLD”
VCM-X MODULAR E-BUS CONTROLLER
Orion No.:OE332-23E-VCMX-MOD-A
AI1 = SPC (SPACETEMPERATURE SENSOR)
= SAT(SUPPLY AIR TEMPERATURE SENSOR)
AI2
= RAT(RETURN AIR TEMPERATURE SENSOR)
AI3
= OAT(OUTDOOR AIR TEMPERATURE SENSOR)
AI4
= SUCTION PRESSURE SENSOR (FROM EXP. MODULE)
AI5
= SPACETEMPERATURE SENSOR SLIDE ADJUST
AI7
= ECONOMIZER (2-10 VDC OUTPUT)
A01
= SUPPLYFAN VFD (0-10 VDC OUTPUT)
A02
CONNECTOR
ANALOG INPUT
JUMPER
SETTINGS
THERM
4-20mA
AI1
0-10V
0-5V
THERM
4-20mA
AI2
0-10V
0-5V
THERM
4-20mA
AI3
0-10V
0-5V
THERM
4-20mA
AI4
0-10V
0-5V
THERM
4-20mA
AI5
0-10V
0-5V
THERM
4-20mA
AI7
0-10V
0-5V
ANALOG INPUTJUMPER SETTINGS
MUSTBE SET AS SHOWN FOR
PROPER OPERATION
STATIC
PRESSURE
VCM-X Modular
OR VOLTAGE RESETSOURCE
E-BUS
LED BLINK CODES
LED NAMESTATUS1 STATUS2
NORMALOPERATION01
SATFAIL12
OATFAIL22
SPCFAIL32
MODULEALARM42
MECHCOOL FAIL13
MECHHEAT FAIL23
FANPROOF FAIL33
DIRTYFILTER43
EMERGENCYSHUTDOWN53
LOWSAT14
HIGHSAT24
CONT.TEMP COOL FAIL34
CONT.TEMP HEAT FAIL44
PUSHBUTTON OVR15
ZONEOVR25
OUTPUTFORCE ACTIVE06
WARNING!POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILLBE DAMAGED
2
WattMasterLabel
IC
#LB102073-01-A
EXPANSION
Rev.: 1A
RELAYCONTACT
RATING IS 1AMP
MAX @ 24 VAC
RELAY
COMMON
FAN
RELAY2
RELAY3
RELAY4
RELAY5
AAON No.:
V07150
24 VAC POWER ONLY
2
IC DIGITAL
SENSOR
Installation & Wiring
Note:
All Relay Outputs Are Normally Open And
Rated For 24 VAC Power Only.
1 Amp Maximum Load.
R - 24VAC
G - Fan ON/OFF Only
Relay Output Contacts
R2 Through R5 May Be User-Configured
For The Following:
1 - Heating Stages
2 - Cooling Stages
3 - Warm-up Mode Command (VAV Boxes)
4 - Reversing Valve (Air To Air Heat Pumps)
5 - Reheat Control (Dehumidification)
6 - Exhaust Fan Interlock
7 - Preheater For Low Ambient Protection
8 - Alarm
9 - Override
10 - Occupied
11 - OA Damper
12 - Heat Wheel
13 - Emergency Heat
Note: 1.) When Using the WSHP-X Module,
All Compressors Will Be Wired From the Module,
Not the VCM-X Controller.
2.) A Total Of 20 RelaysAre Available By Adding Relay
Expansion Modules. All Expansion Module Relay
Outputs Are User Configurable As ListedAbove.
GND
24VAC
Size Transformer For Correct
Total Load.
VCM-X Controller = 8 VA
Line Voltage
Jumpers
Splice If Required
OE271
Static Pressure
Transducer
Connect FRP Tubing To High Pressure
Port (Bottom Tube) And Route To Static
Pressure Pickup Probe Located In Unit
Discharge. Leave Port Marked “Lo” Open
ToAtmosphere.
Connect To
Expansion Module(s)
(When Used)
Connect To Digital Room Sensor And/Or
Digital CO Sensor
2
Warning:
24 VAC Must Be Connected So That All Ground
Wires Remain Common. Failure To Do So Will
Result In Damage To The Controllers.
Figure 6, cont.: VCM-X E-BUS Controller to WSHP-X Module Wiring Diagram for Single Water Circuit
Technical Guide
11
WSHP-X Module
Installation & Wiring
VCM-X WSHP or SA Controller to
WSHP-X Module Wiring for Dual
Water Circuit
The VCM-X WSHP Controller or SA Controller communicates with the
WSHP-X Module using the E-BUS Distribution Module. See Figure 7
for wiring details (VCM-X WSHP Controller shown).
For Stand Alone Applications,
Connect To System Manager.
For Network Applications
Connect To Next Controller
And/Or MiniLink PD On Local Loop.
Local Loop
RS-485
9600 Baud
All Comm Loop Wiring Is
Straight Thru
T to T, R to R & SHLD to SHLD
See Individual Component
Wiring Diagrams For
Detailed Wiring Of Analog
Inputs And Outputs
AI1 SETAI2 SET AI3 SET
AI4 SET AI5 SETAI7 SET
(OE332-23-WSHP-A)
VCM-X WSHP Controller
AI1 SET AI2 SET AI3 SET
AI1
AI2
AI3
AI4
AI5
AI4 SET AI5 SET AI7 SET
AI7
NOTE: When using the WSHP-X Module, all compressors
will be wired from the WSHP-X Module, not the
VCM-X WSHP Controller or SA Controller.
Note:
All Relay Outputs Are Normally Open And Rated
For 24 VAC Power Only.
1 Amp Maximum Load.
R - 24VAC
G - Fan ON/OFF Only
Relay Output Contacts
R2 Through R5 May Be User Configured
For The Following:
1 - Heating Stages
2 - See Note 1 Below
3 - Warm-up Mode Command (VAV Boxes)
4 - Reversing Valve (Air To Air Heat Pumps)
5 - Reheat Control (Dehumidification)
6 - Exhaust Fan Interlock
7 - Preheater For Low Ambient Protection
8 - Alarm
9 - Override
10 - Occupied
11 - OA Damper
12 - Heat Wheel
Note: 1.) When Using the WSHP-X Module,
All Compressors Will Be Wired From the
Module, Not the VCM-X Controller.
2.) A Total Of 20 Relays Are Available By
Adding Relay Expansion Modules. All
Expansion Module Relay Outputs Are User
Configurable As Listed Above.
GND
24VAC
Size Transformer For Correct
Total Load.
VCM-X Controller = 8 VA
Line Voltage
Connect To
E-BUS
Distribution
Module
24 VAC
GND
Jumpers
Splice If Required
OE271
Static Pressure
Transducer
Connect FRP Tubing To High Pressure
Port (Bottom Tube) And Route To Static
Pressure Pickup Probe Located In Unit
Discharge. Leave Port Marked “Lo” Open
ToAtmosphere
Connect To E-BUS Distribution Module Or
Expansion Module(s)
(When Used)
Warning: 24 VAC Must Be Connected So That All
Ground Wires Remain Common. Failure To Do
So Will Result In Damage To The Controllers.
Connect To Digital Room Sensor And/Or
Digital CO Sensor
2
Figure 7: VCM-X WSHP Controller to WSHP-X Module Wiring Diagram for Dual Water Circuit
12
Technical Guide
Line Voltage
OE365-23-EBD E-BUS
Distribution Module
YS102308
REV 1
I2CTO COMM
DIST. BOARD
OUTPUT
+COMM
SHLD
-COMM
GND
+VDC
INPUT
+COMM
SHLD
-COMM
GND
24VAC
GND
PWR
WARNING!!
Observe Polarity! All boards
must be wired with GND-toGND and 24 VAC-to-24 VAC.
Failure to observe polarity
could result in damage to the
boards.
485 DRV
Modular Cable
Connect To
VCM-X WSHP Controller
LEAVING WATER TEMPERATURE
FOR SYSTEM A
WSHP-X Module
Installation & Wiring
CIRCUIT B2
SUCTION PRESSURE TRANSDUCER
BK
WH
RD
CIRCUIT B1
SUCTION PRESSURE TRANSDUCER
BK
WH
RD
CIRCUIT A2
SUCTION PRESSURE TRANSDUCER
BK
WH
RD
CIRCUIT A1
SUCTION PRESSURE TRANSDUCER
BK
WH
RD
NOTE:
ALL RELAY OUTPUTS
NORMALLY OPEN AND
ARE
RATED FOR 24 VAC POWER
ONLY
HVAC UNIT
CONNECTIONS
R1
COMP.A1 ENABLE
R2
COMP.A2 ENABLE
R3
COMP. B1 ENABLE
R4
COMP. B2 ENABLE
R5
COMM
ALARM OUTPUT
AO1
DIGITAL STG 1 (1.5-5V)
AO2
DIGITAL STG 2 (1.5-5V)
Line Voltage
3 VAMinimum
WARNING!!
Observe Polarity! All
boards must be wired
with GND-to-GND and 24
VAC-to-24 VAC. Failure
to observe polarity could
result in damage to the
boards.
WATER POFA
WATER POF B
BIN6
BIN7
COM
T1
T2
GND
OE334-26-WSHPX-A Water Source
Heat Pump X Module
ALARM
UP
M
BIN 5
- HEATENABLE
- WATER POF
BIN 6
BIN 7
- WATER POF
COM
- COMMON
E-BUS
CONNECT
HSSC Cable
Module(s)
MENU
DOWN
RELAYCONTACT RATING
IS 1AMP MAX @ 24 VAC
COMP.A1 ENABLE
COMP.A2 ENABLE
COMP. B1 ENABLE
COMP. B2 ENABLE
ALARM OUTPUT
RELAYCOMMON
DIGITALCOMP. A1, A2, B1, B2
STAGE 1- COMP.A1/B1STAGE 2 - COMP.A2/B2
CONNECTTO CNTLR C2 TERM.
GND
E-BUS
CONNECT
+24 VAC
E
HSSC Cable
www.aaon.com
www.orioncontrols.com
OE334-26-WSHPX-A WSHP-X MODULE AAON NO.: V18330
NON-DIGITALCOMPRESSORS
SUCT. PR. SENSOR
+5V
PRES 1=A1, PRES 2=A2
PRES
PRES 3=B1, PRES 4=B2
GND
+5TO RED, PRES TO WHT & GND TO BLK
DIGITALCOMRESSORS
+5V
NOT USED
PRES
PRES 1=A1, PRES 2=A2
GND
PRES 3=B1, PRES 4=B2
+5 NOTUSED, PRES TO P6 & GND TO P5
BIN 1
- COMP.A1 EN.
- COMP.A2 EN.
BIN 2
BIN 3
- COMP. B1 EN.
- COMP. B2 EN.
BIN 4
T1
- LEAVING WATERTEMP A
T2
- LEAVING WATERTEMP B
- GROUND
GND
WattMaster Label
#SW000054
Rev.: 1A
Connect To Other
WattMaster-Approved
E-BUS Expansion
ENTER
GND
R1
R2
R3
R4
R5
RC
AO1
A2O
24 VAC
Y 102374 REV 0S
WATTMASTER CONTROLS
MADE IN USA
24 VAC Transformer
LEAVING WATER TEMPERATURE
FOR SYSTEM B
Figure 7, cont.: VCM-X WSHP Controller to WSHP-X Module Wiring Diagram for Dual Water Circuit
Technical Guide
13
WSHP-X Module
Installation and Wiring
VCM-X WSHP E-BUS or SA E-BUS
Controller to WSHP-X Module Wiring
for Dual Water Circuit
The WSHP-X Module connects to the E-BUS Controller using a modular
HSSC cable. The WSHP-X Module requires a 24 VAC power connection
with an appropriate VA rating. See Figur e 8 below for wiring. (VCM-X
WSHP E-BUS Controller shown.)
OE334-26-WSHPX-A Water Source
+V
CIRCUIT A1
SUCTION PRESSURE
TRANSDUCER
CIRCUIT A2
SUCTION PRESSURE
TRANSDUCER
CIRCUIT B1
SUCTION PRESSURE
TRANSDUCER
CIRCUIT B2
SUCTION PRESSURE
TRANSDUCER
WARNING!! Observe Polarity! All
boards must be wired with GND-toGND and 24 VAC-to-24 VAC.
Failure to observe polarity could
result in damage to the boards.
Connect To Other
WattMaster-Approved
E-BUS Expansion Module(s)
WATER POFA
WATER POF B
RD
WH
WH
RD
WH
RD
WH
SIG 1
BK
GND
+V
RD
SIG 2
BK
GND
+V
SIG 1
BK
GND
+V
SIG 2
BK
GND
BIN6
BIN7
COM
T1
T2
OE334-26-WSHPX-A WSHP-X MODULE AAON NO.: V18330
NON-DIGITALCOMPRESSORS
+5V
PRES
GND
+5 TO RED, PRESTO WHT & GND TO BLK
+5V
PRES
GND
+5 NOT USED, PRESTO P6 & GND TO P5
BIN 1
BIN 2
BIN 3
BIN 4
T1
T2
GND
WattMaster Label
GND
HSSC Cable
Any E-BUS Module can be connected to the E-BUS Controller’s E-BUS
port or can be daisy-chained together using HSSC cables.
NOTE: When using the WSHP-X Module, all compressors
will be wired from the WSHP-X Module, not the
VCM-X WSHP E-BUS Controller or SA E-BUS
Controller.
NOT USED
PRES 1=A1, PRES 2=A2
PRES 3=B1, PRES 4=B2
- COMP.A1 EN.
- COMP.A2 EN.
- COMP. B1 EN.
- COMP. B2 EN.
- LEAVING WATERTEMP A
- LEAVING WATERTEMP B
- GROUND
#SW000054
Rev.: 1A
ENTER
GND
R1
R2
R3
R4
R5
RC
AO1
A2O
24 VAC
Y 102374 REV 0S
WATTMASTER CONTROLS
ARE
RATED FOR 24 VAC POWER
ONLY
MADE IN USA
R1
R2
R3
R4
R5
COMM
AO1
AO2
Line Voltage
24 VAC Transformer
3 VA Minimum
HVAC UNIT
CONNECTIONS
COMP. A1 ENABLE
COMP. A2 ENABLE
COMP. B1 ENABLE
COMP. B2 ENABLE
ALARM OUTPUT
DIGITAL STG 1 (1.5-5V)
DIGITAL STG 2 (1.5-5V)
WARNING!!
Observe Polarity! All
boards must be wired
with GND-to-GND and 24
VAC-to-24 VAC. Failure
to observe polarity could
result in damage to the
boards.
HSSC Cable
Connect To VCM-X E-BUS
Controller or SA E-BUS Controller
LEAVING WATER TEMPERATURE
LEAVING WATER TEMPERATURE
FOR SYSTEM A
FOR SYSTEM B
Figure 8: VCM-X E-BUS Controller to WSHP-X Module Wiring Diagram for Dual Water Circuit
14
Technical Guide
WSHP-X Module
NOTE: Contact Factory for the correct HSSC cable length for
your application. Cables are available in ¼, ½, 1, 2, 3,
4, and 5 Meter lengths and 100 and 150 Foot lengths.
WARNING: Be sure all controllers and modules are
powered down before connecting or
disconnecting HSSC cables.
For Stand Alone Applications,
Connect To System Manager. For Network
Applications Connect To Next Controller
And/Or MiniLink PD On Local Loop.
Local Loop
RS-485
9600 Baud
All Comm Loop Wiring Is
Straight Thru
T to T, R to R & SHLD to SHLD
HSSC Cable Connect To
VCM-X E-BUS Port
See Individual
AI1 SETAI2 SET AI3 SET
Component Wiring
Diagrams For
Detailed Wiring Of
Analog Inputs And
Outputs
AI4 SET AI5 SETAI7 SET
OE332-23E-VCMX-WSHP
VCM-X Modular
E-BUS Controller
RS-485 COMMUNICATION LOOP. WIRE
“R” TO“R”, “T” TO “T” “SHLD” TO “SHLD”
VCM-X MODULAR E-BUS CONTROLLER
Orion No.:OE332-23E-VCMX-MOD-A
AI1 = SPC (SPACETEMPERATURE SENSOR)
AI2
= SAT(SUPPLY AIR TEMPERATURE SENSOR)
AI3
= RAT(RETURN AIR TEMPERATURE SENSOR)
AI4
= OAT(OUTDOOR AIR TEMPERATURE SENSOR)
AI5
= SUCTION PRESSURE SENSOR (FROM EXP. MODULE)
AI7
= SPACETEMPERATURE SENSOR SLIDE ADJUST
OR VOLTAGE RESETSOURCE
A01
= ECONOMIZER (2-10 VDC OUTPUT)
A02
= SUPPLYFAN VFD (0-10 VDC OUTPUT)
E-BUS
CONNECTOR
ANALOG INPUT
JUMPER
SETTINGS
THERM
4-20mA
AI1
0-10V
NORMALOPERATION01
0-5V
SATFAIL12
THERM
OATFAIL22
4-20mA
AI2
SPCFAIL32
0-10V
0-5V
MODULEALARM42
THERM
MECHCOOL FAIL13
4-20mA
AI3
MECHHEAT FAIL23
0-10V
0-5V
FANPROOF FAIL33
THERM
DIRTYFILTER43
4-20mA
AI4
EMERGENCYSHUTDOWN53
0-10V
0-5V
LOWSAT14
THERM
HIGHSAT24
4-20mA
AI5
CONT.TEMP COOL FAIL34
0-10V
CONT.TEMP HEAT FAIL44
0-5V
PUSHBUTTON OVR15
THERM
4-20mA
ZONEOVR25
AI7
0-10V
OUTPUTFORCE ACTIVE06
0-5V
ANALOG INPUTJUMPER SETTINGS
MUSTBE SET AS SHOWN FOR
PROPER OPERATION
WattMasterLabel
STATIC
#LB102073-01-A
PRESSURE
Rev.: 1A
RELAYCONTACT
RATING IS 1AMP
MAX @ 24 VAC
RELAY
COMMON
RELAY2
RELAY3
RELAY4
RELAY5
AAON No.:
V07150
LED BLINK CODES
LED NAMESTATUS1 STATUS2
24 VAC POWER ONLY
WARNING!POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILLBE DAMAGED
2
IC
EXPANSION
FAN
2
IC DIGITAL
SENSOR
Installation and Wiring
Note:
All Relay Outputs Are Normally Open And
Rated For 24 VAC Power Only.
1 Amp Maximum Load.
R - 24VAC
G - Fan ON/OFF Only
Relay Output Contacts
R2 Through R5 May Be User-Configured
For The Following:
1 - Heating Stages
2 - Cooling Stages
3 - Warm-up Mode Command (VAV Boxes)
4 - Reversing Valve (Air To Air Heat Pumps)
5 - Reheat Control (Dehumidification)
6 - Exhaust Fan Interlock
7 - Preheater For Low Ambient Protection
8 - Alarm
9 - Override
10 - Occupied
11 - OA Damper
12 - Heat Wheel
13 - Emergency Heat
Note: 1.) When Using the WSHP-X Module,
All Compressors Will Be Wired From the Module,
Not the VCM-X Controller.
2.) A Total Of 20 Relays Are Available ByAdding Relay
Expansion Modules. All Expansion Module Relay Outputs
Are User Configurable As Listed Above.
GND
24VAC
Size Transformer For Correct
Total Load.
VCM-X Controller = 8 VA
Line Voltage
Jumpers
Splice If Required
OE271
Static Pressure
Transducer
Connect FRP Tubing To High Pressure
Port (Bottom Tube) and Route To Static
Pressure Pickup Probe Located In Unit
Discharge. Leave Port Marked “Lo” Open
ToAtmosphere
Connect To
Expansion Module(s)
(When Used)
Connect To Digital Room Sensor And/Or
Digital CO Sensor
2
Warning:
24 VAC Must Be Connected So That All Ground
Wires Remain Common. Failure To Do So Will
Result In Damage To The Controllers.
Figure 8, cont.: VCM-X E-BUS Controller to WSHP-X Module Wiring Diagram for Dual Water Circuit
Technical Guide
15
WSHP-X Module
Start-Up & Commissioning
General
In order to have a trouble free start-up, it is important to follow a few
simple procedures. Before applying power for the fi rst time, it is very
important to run through a few simple checks.
One of the most important checks to make before powering up the
system for the fi rst time is to make sure that the VCM-X WSHP Series
Controller or SA Series Controller is confi gured properly for your ap-
plication. Refer to the VCM-X Controller Technical Guide, VCM-X
Modular E-BUS Controller Technical Guide, SA Controller Technical
Guide, or SA E-BUS Controller Technical Guide for more information.
A handheld Modular Service Tool, Modular System Manager, or System
Manager T ouch Screen connected to the VCM-X WSHP Series Controller or SA Series Controller will allow you to confi gure your application.
Refer to the VCM-X Operator’ s Interfaces T echnical Guide, SA Operator Interfaces T echnical Guide, or System Manager TS Technical Guide for
more information.
UNIT CONFIGURATIONS
SYSTEM ASYSTEM B
PERMUTATION
Comp A1Comp A2Comp B1Comp B2
NOTE: The SA Series Controller does not utilize the System
Manager Touch Screen.
Check all wiring leads at the terminal block for tightness. Be sure that
wire strands do not stick out and touch adjacent terminals. Confi rm
that all sensors required for your system are mounted in the appropriate
location and wired into the correct terminals.
WARNING: Observe polarity! All boards must be wired
GND-to-GND and 24 VAC-to-VAC. Failure to
observe polarity could result in damage to the
boards.
In the Dehumidifi cation Mode, the Compressors will stage in the following order:Permutation 4: Compressor A1 & Compressor B1 -> Compressor A2 -> Compressor B2
All other permutations in the Dehumidifi cation Mode stage as described in the Cooling Mode.
— —
— —
— —
2 Compressors
2 Compressors
Digital Compressor
2 Compressors
Full Digital
4 Compressors
Digital Compressor
4 Compressors
Full Digital
—
2 Compressors
Single Unit SA
2 Compressors
Single Unit SA
—
—
4 Compressors
Dual Unit SA
4 Compressors
Dual Unit SA
Table 1: Unit Confi gurations Chart
16
Technical Guide
WSHP-X Module
Sequence of Operation
General
The following inputs and outputs are available on the WSHP-X Module.
See Table 2 below to reference the Input/Output Map.
1Suction Pressure A1 (Pres 1)
2Suction Pressure A2 (Pres 2)
3Suction Pressure B1 (Pres 3)
4Suction Pressure B2 (Pres 4)
5Leaving Water Temperature System A (T1)
6Leaving Water Temperature System B (T2)
The WSHP-X Module setpoints are preset at AAON and are based on
the unit’s design as well as the type of coolant being used in the water
loop. See Tables 3 & 4 for default settings.
NOTE: These are default settings only. The setpoints may be
different based on the unit’s design and coolant being
used.
Water-Only Default Setpoints
DescriptionR410-AR22
UNSAFE SUCTION40 PSIG20 PSIG
LOW SUCTION HEAT MODE100 PSIG57 PSIG
LOW SUCTION COOL MODE85 PSIG57 PSIG
LOW LEAVING WATER TEMP37ºF37ºF
Table 3: Factory-Set Default Setpoints - Water Only
A 24 volt signal to Binary Inputs #1-4 initiates each Compressor’s On
function. The source for this signal would typically come from Y1 to
Y4 calls from the thermostat.
Heat Enable On/Off
A 24 volt signal on this input indicates the unit is in the Heating Mode.
Typically, the source for this signal is the “O” call from the thermostat.
R410-A
15%
Glycol
R410-A
20%
Glycol
R410-A
25%
Glycol
R410-A
30%
Glycol
R410-A
35%
Glycol
R410-A
40%
Glycol
Input Commands (VCM-X WSHP or SA
Connection)
NOTE: When the term “ON” is used, it means there is either 24
VAC on the appropriate Binary Input or a call-to-run
signal is being received from the VCM-X WSHP Series
or SA Series Controller. When the term “OFF” is used,
it means there is either 0 VAC on the appropriate Binary
Input or the call-to-run signal from the VCM-X WSHP
or SA has been removed.
Water Proof of Flow System On/Off
A 24 volt signal to Binary Inputs #6-7 indicates Water Proof of Flow
for each system.
Suction Pressure Analog Inputs
Sensors from Analog Inputs #1-4 correlate with the Suction Pressure of
each Compressor (250 PSI).
Leaving Water Temperature Thermistor Inputs
T1 correlates with Compressors A1 & A2 (RLY1 and RLY2). T2 correlates with Compressors B1 & B2 (RLY3 and RLY4).
18
Revised: 6/13/13
Compressor On/Off
Instead of a physical input signaling the Compressor On/Off function,
the VCM-X WSHP Series Controller or SA Series Controller communications drives the Compressor On/Off function.
Heat Enable On/Off
As with the Compressor On/Off function, the VCM-X WSHP Series or
SA Series Controller communicates to the Module that it is in Heat Mode.
Technical Guide
WSHP-X Module
Sequence of Operation
Modes of Operation
NOTE: See the Unit Confi gurations Chart on page 16 for more
information about compressor staging.
Digital Stage 1 / Digital Stage 2
On units with two Digital Scroll Compressors, the fi rst compressor (A1)
will be designated as Digital Stage 1 and the second compressor (A2)
will be designated as Digital Stage 2.
On units with four Digital Scroll Compressors, there may be instances
where compressor numbers on the module do not correlate with the
mechanical compressors’ numbers. Therefore, Digital Stage 1 refers to
the fi rst set of Digital Scroll Compressors (A1/B1) that will stage on
together and Digital Stage 2 refers to the second set of Digital Scroll
Compressors (A2/B2) that will stage on together. Please refer to AAON’ s
wiring diagram for specifi c wiring of the unit.
Compressor Operation (Heat/Cool)
A compressor can energize if the following is true:
1. There is 24 VAC applied to the appropriate Binary Input for
the Compressor.
2. If two compressors are enabled simultaneously, a 5 second
staging delay will occur.
3. Suction Pressure is above the Low Suction Pressure Cooling
(Heating) Setpoint.
4. Proof of Flow for the appropriate water loop is made.
5. Leaving Water Temp is above the Leaving Water Safety
Setpoint (Heating Only).
6. A minimum off time of 3 minutes is met for that compressor.
NOTE: If the WSHP-X Module receives a signal on the Heat
Enable input, it will operate using the Heating Mode
Setpoints.
Cooling Mode
Digital Scroll Compressor Control
When a Cool Signal is received, the WSHP-X Module will go into Cooling Mode. Once Proof of W ater Flow has been made and a start-up delay
has been met, Compressor A1 (and B1*) will energize and Digital Stage 1
Analog Output will go to 50% and modulate as necessary to maintain the
Supply Air Temperature at the Active Supply Air Setpoint that is broadcast from the VCM-X WSHP Series Controller or SA Series Controller.
When Digital Stage 1 reaches 100%, a stage up timer is started. If Digital
Stage 1 stays at 100% for the stage up timer, Compressor A2 (and B2*)
will energize and both Digital Stage 1 and Digital Stage 2 outputs will
go to 50% and will begin to modulate together.
If both systems are energized and they go below 30% and the Supply Air
is below the Supply Air Setpoint by the Cooling Stage Window value,
the stage down timer is started. If the systems remain below 30% for
the duration of the stage down timer, Digital Stage 2 will deactivate and
Digital Stage 1 will go to 60%. Digital Stage 1 will stage down if it is
at 0% for the duration of the stage down timer.
* If confi gured for 4 modulating compressors.
Heat Pump Heating Mode
Heating Mode works the same as Cooling Mode except the Reversing
Valve is switched and the sequence is opposite. Compressors modulate
up when below the Heating Supply Air Setpoint and modulate down
when above the setpoint.
Dehumidifi cation Mode
Fixed Compressors Only
In the Dehumidifi cation Mode, if this unit has only fi xed compressors,
they will sequentially stage according to T able 1 on page 16 to maintain
the Suction Pressure Setpoint. Compressors A1 & B1 will stage on together fi rst followed sequentially by A2 & then B2. Stage Up and Stage
Down delays will apply.
Digital Scroll Compressor Control
In Dehumidifi cation Mode, compressors will be controlled to maintain
the Suction Pressure T emperature Setpoint. Digital Stage 1—Compressor A1 (and B1*) will modulate up to 100% before Digital Stage 2—
Compressor A2 (and B2*) can be energized. When Digital Stage 2 is
energized, Digital Stage 1 will be locked at 100%.
NOTE: Control of digital compressor(s) is only available when
the WSHP-X Module is connected to the VCM-X WSHP
Series Controller or SA Series Controller.
Fixed Compressors Only
When a Cool Signal is received, the WSHP-X Module will go into
Cooling Mode. Once Proof of Water Flow has been made, they will
sequentially stage according to T able 1 on page 16, using Stage Up and
Stage Down delays to maintain the Supply Air Setpoint that is broadcast
from the VCM-X WSHP Series Controller or SA Series Controller.
Technical Guide
* If confi gured for 4 modulating compressors.
Staging Delays
Staging Delays minimum run times and minimum off times are sent from
the VCM-X WSHP Series Controller or SA Series Controller.
Revised: 12/16/13
19
WSHP-X Module
Navigation Keys
LCD Display Screen & Navigation
Keys
The WSHP-X Controller allows you to make confi guration changes, view
status, change setpoints, create force modes, and perform diagnostics
using the keypad next to the LCD display. See Figure 9 and refer to Table 5 for descriptions.
Figure 9: LCD Display and Navigation Keys
Navigation KeyKey Function
MENU
UP
DOWN
ENTER
Use the MENU key to navigate through the
Main Menu Screens
Use this key to adjust setpoints and change
confi gurations. This key is also used to turn
Valve Force Mode on.
Use this key to adjust setpoints and change
confi gurations. This key is also used to turn
Valve Force Mode off.
Use the Enter key to move through screens
within Main Menu categories. Also, use this
key to save setpoints and confi guration
changes.
Table 5: Navigation Key Functions
20
Technical Guide
WSHP-X Module
Main Screens Map and WSHP Screens
Main Screens Map
Refer to the following map when navigating through the LCD Main
Screens. The fi rst screen is the address screen. To scroll through the rest
of the screens, press the <MENU> button.
ADDRESS
#
WSHP
AAON
Press to scroll through WSHP Screens.
Press to go to ALARM Screens.
ALARMS
Press to scroll through ALARMS Screens.
WSHP Screens
Refer to the following map when navigating through the Main Screens.
From the WSHP AAON Screen, press <ENTER> to scroll through
the screens.
WSHP
AAON
S/A or
COMM MODE or
COM T/O ERROR
In Stand-Alone Mode, the screen will only display S/A MODE.
In Communications Mode, the screen will display COMM MODE and the
items below will scroll through the screen:
1. Number of good packets being received. This will roll over after 9999.
Example: +XXXX
2. Number of checksum errors. This will stop at 9999. Example: C-XXXX
3. Number of packet length errors. This will stop at 9999 until power is
cycled. Example: P-XXXX
Press to go to STATUS SYSTEM A Screens.
STATUS
SYSTEM A
Press to scroll through STATUS SYSTEM A Screens.
Press to go to STATUS SYSTEM B Screens.
STATUS
SYSTEM B
Press to scroll through STATUS SYSTEM B Screens.
Press to go to SETPOINT Screens.
SETPOINT
Press to scroll through SETPOINT Screens.
SOFTWARE
1053v100
CURRENT SOFTWARE VERSION
H20 CNFG
SINGLE or DUAL
WATER CIRCUIT CONFIGURATION
SINGLE (Typical for AAON Coil) or DUAL (Typical for AAON Tulsa)
REV VALV
OFF=COOL or
OFF=HEAT
REVERSING VALVE CONFIGURATION
OFF=COOL (No signal on reversing valve input equals cool mode)
OFF=HEAT (No signal on reversing valve input equals heat mode)
Technical Guide
ADDRESS
#
21
WSHP-X Module
Alarm Screens
Alarm Screens
Refer to the following map when viewing the Alarm Screens. These
screens will display automatically when alarms are present.
ALARMS
ALARMS
The alarms are as follows:
NO ALARMS: This will be shown if there are no current alarms.
COMPRESSOR LOCKOUT (1-4):
• If a circuit’s Suction Pressure falls below the Low Suction
Pressure Setpoint for longer than one minute twice within a
two hour window, the compressor on that circuit will be
locked out. Manual reset or change of mode is required to
return to normal operation.
• If the Suction Pressure falls below the Unsafe Suction
Setpoint for 5 seconds, that circuit’s compressor will locked
out. Power will need to be cycled to restart the unit.
• If the Leaving Water Temperature falls below setpoint,
the last compressor will be locked out until the Leaving Water
Temperature rises 6 degrees above setpoint.
• The Leaving Water Temperature remains below setpoint for
1 minute or falls 3 degrees below setpoint. This alarm will
disable when the leaving water temperature rises 12 degrees
above the setpoint.
LOW H2O: The Leaving Water Temperature has dropped below set-
point. This alarm will disable when the leaving water temperature rises 6
degrees above the setpoint.
NO PROOF OF FLOW: There is a call for a compressor and there is
no Proof of Flow Input Enable for more than 3 minutes or if during Heat
Pump heating, the Proof of Flow Enable is open for more than 2 seconds. This alarm will disable when Proof of Flow is enabled.
LOW SUCTION PRESSURE: The Circuit’s Suction Pressure has
dropped below the Low Suction Pressure for longer than one minute.
This alarm will disable ten minutes after Suction Pressure rises above
the setpoint.
22
Technical Guide
WSHP-X Module
System Status A Screens
System Status A Screens
Refer to the following map when navigating through the System Status
A Screens. From the SYSTEM STATUS A Screen, press
scroll through the screens.
SYSTEM
STATUS A
Status Screens shown below will scroll automatically if LCD display is
left on this screen for 20 seconds.
A1 COMP
OFF,PENDING,ON or
Reason for Fail
SYSTEM A, COMPRESSOR 1
This screen displays the current status of the A1 Compressor.
OFF
PENDING: Compressor is off, but a request is made to be on, but the
1 minimum off time has not been met.
ON: HEAT or Cool
REASON FOR FAILURE: Low Pres, Lockout, Low H2O, No Flow
<ENTER> to
PO FLOW
YES or NO
PROOF OF WATER FLOW
A1 PRES
XXX
SYSTEM A, COMPRESSOR 1 PRESSURE READING
A2 PRES
XXX or NOT USED
SYSTEM A, COMPRESSOR 2 PRESSURE READING
If Single Water Confi guration, this screen will display “NOT USED.”
A2 COMP
OFF,PENDING,ON or
Reason for Fail
SYSTEM A, COMPRESSOR 2
This screen displays the current status of the A2 Compressor.
OFF
PENDING: Compressor is off, but a request is made to be on, but the
1 minimum off time has not been met.
ON: HEAT or Cool
REASON FOR FAILURE: Low Pres, Lockout, Low H2O, No Flow
H2O TEMP
NO SENSR
LEAVING WATER TEMPERATURE READING
OR “NO SENSOR”
AOUT1
X%
ANALOG OUTPUT 1 PERCENT
0 - 100%
AOUT2
X%
ANALOG OUTPUT 2 PERCENT
0 - 100%
Technical Guide
23
WSHP-X Module
System Status B Screens
System Status B Screens
Refer to the following map when navigating through the System Status
B Screens. From the SYSTEM ST ATUS B Screen, press
scroll through the screens.
SYSTEM B
DISABLED
If System B is disabled, the above screen will appear.
SYSTEM
STATUS B
Status Screens shown below will scroll automatically if LCD display is
left on this screen for 20 seconds.
B1 COMP
OFF,PENDING,ON or
Reason for Fail
<ENTER> to
H2O TEMP
NO SENSR
LEAVING WATER TEMPERATURE READING
OR “NO SENSOR”
PO FLOW
YES or NO
PROOF OF WATER FLOW
B1 PRES
XXX
SYSTEM B, COMPRESSOR 1 PRESSURE READING
SYSTEM B, COMPRESSOR 1
This screen displays the current status of the B1 Compressor.
OFF
PENDING: Compressor is off, but a request is made to be on, but the
1 minimum off time has not been met.
ON: HEAT or Cool
REASON FOR FAILURE: Low Pres, Lockout, Low H2O, No Flow
B2 COMP
OFF,PENDING,ON or
Reason for Fail
SYSTEM B, COMPRESSOR 2
This screen displays the current status of the B2 Compressor.
OFF
PENDING: Compressor is off, but a request is made to be on, but the
1 minimum off time has not been met.
ON: HEAT or Cool
REASON FOR FAILURE: Low Pres, Lockout, Low H2O, No Flow
B2 PRES
XXX or NOT USED
SYSTEM B, COMPRESSOR 2 PRESSURE READING
If Single Water Confi guration, this screen will display “NOT USED.”
AOUT1
X%
ANALOG OUTPUT 1 PERCENT
0 - 100%
AOUT2
X%
24
ANALOG OUTPUT 2 PERCENT
0 - 100%
Technical Guide
WSHP-X Module
Setpoint Screens
Setpoint Status Screens
Refer to the following map when navigating through the Setpoint Status Screens. From the SETPOINTS Screen, press
through the screens.
NOTE: The following screens are Status Screens. The Setpoints
1. If there is a call for a compressor and there is no Proof of Flow
Input Enable:
• The module will wait up to 3 minutes to activate
the Proof of Flow Alarm LED(s) which will blink
the code indicating failure.
2. If the compressor(s) is (are) running and contact is opened for
2 seconds during Heat Pump Heating:
• Compressor(s) will be turned off.
3. If the compressor(s) are running and contact is opened for 2
seconds during Cooling:
• Proof of Flow Input will be ignored.
• No alarm will be generated.
Low Suction Pressure Detection
1. If any Circuit’s Suction Pressure falls below the Low Suction
Pressure Setpoint for longer than 1 minute, then the following
will occur:
Low Leaving Water Temperature
NOTE: This safety monitoring is only performed in the Heat
Mode.
1. If the Leaving Water Temperature falls below setpoint, the
following will occur:
• The last compressor will turn off.
• Alarm LED will indicate Compressor Low Water
Temp Shutoff.
• Last compressor will be locked out until the
Leaving temperature is 6 degrees above setpoint.
2. If the Leaving Water Temperature remains below setpoint for
1 minute or falls 3 degrees below setpoint, the following will
occur:
• All compressors will deactivate.
• Alarm LED will indicate Compressor Low
Water Temperature Shutoff.
• All compressors will be locked out until the
Leaving Temperature is 12 degrees above setpoint.
• The compressor(s) on that circuit will turn off.
• Alarm LED will indicate Low Suction Pressure.
• Compressor(s) will be enabled again after 10
minutes if Suction Pressure rises above setpoint.
2. If any Circuit’s Suction Pressure falls below the Low Suction
Pressure Setpoint for longer than 1 minute a second time
within a two hour window, then the following will occur:
• The compressor(s) on that circuit will be locked out.
• Alarm LED will indicate a Compressor Lockout.
• Manual reset or change of mode (i.e., Cool to Heat)
must occur to reset back to normal operation.
Unsafe Suction Pressure Detection
If the Suction Pressure falls below the Unsafe Suction Setpoint for 5
seconds, the circuit’s compressor will be locked out immediately and
will not be allowed to restart. You will need to reset the Power to restart
the unit.
26
Technical Guide
WSHP-X Module
Troubleshooting
Safety Monitoring for Dual Water
Circuit
Proof of Flow
There are separate inputs for System A and System B. System A provides water for Compressors A1 & A2 and System B provides water
for Compressors B1 & B2.
1. If there is a call for a compressor and there is no Proof of Flow
Input Enable:
• The module will wait up to 3 minutes to activate
the Proof of Flow Alarm LED(s) which will blink
the code indicating failure.
• Proof of Water Flow A will disable compressors A1
and A2.
• Proof of Water Flow B will disable compressors B1
and B2.
2. If the compressor(s) is (are) running and contact is opened for
2 seconds during Heat Pump Heating:
• Compressor(s) will be turned off.
• Proof of Water Flow A will disable compressors A1
and A2.
• Proof of Water Flow B will disable compressors B1
and B2.
3. If the compressor(s) are running and contact is opened for 2
seconds during Cooling:
• Proof of Flow Input will be ignored.
• No alarm will be generated.
Low Suction Pressure Detection
1. If any Compressor’s Suction Pressure falls below the Low
Suction Pressure Setpoint for longer than 1 minute, then the
following will occur:
• The compressor will turn off.
• Alarm LED will indicate Low Suction Pressure.
• Compressor will be enabled again after 10 minutes
if Suction Pressure rises above setpoint.
2. If any Compressor’s Suction Pressure falls below the Low
Suction Pressure Setpoint for longer than 1 minute a second
time within a two hour window, then the following will occur:
• That compressor will be locked out.
• Alarm LED will indicate a Compressor Lockout.
• Manual reset or change of mode (i.e., Cool to Heat)
must occur to reset back to normal operation.
Unsafe Suction Pressure Detection
If the Suction Pressure falls below the Unsafe Suction Setpoint for 5
seconds, the compressor will be locked out immediately and will not be
allowed to restart. You will need to reset the Power to restart the unit.
Low Leaving Water Temperature
NOTE: This safety monitoring is only performed in the Heat
Mode.
On the larger units, there are two separate condenser/water sections and
each section (water system) has its own Leaving Water Temperature
Sensor. Each sensor will only affect the compressors associated with
that condenser/water section. The description below describes System
A. System B works the same but will affect Compressors B1 & B2.
1. If the Leaving Water Temperature for System A falls below
setpoint, the following will occur:
• Compressor A2 will deactivate if active.
• Alarm LED will indicate Compressor A2 Low
Water Temp Shutoff.
• Compressor A2 will be locked out until the Leaving
temperature is 6 degrees above setpoint.
2. If the Leaving Water Temperature for System A remains below
setpoint for 1 minute or falls 3 degrees below setpoint, the
following will occur:
• Compressor A1 will deactivate.
• Alarm LED will indicate Compressor A1 & A2 Low
Water Temperature Shutoff.
• Both Compressors will be locked out until the
Leaving Temperature is 12 degrees above setpoint.
Technical Guide
27
WSHP-X Module
Troubleshooting
Temperature Sensor Testing
The following sensor voltage and resistance tables are provided to aid in
checking sensors that appear to be operating incorrectly. Many system
operating problems can be traced to incorrect sensor wiring. Be sure all
sensors are wired per the wiring diagrams in this manual.
If the sensors still do not appear to be operating or reading correctly,
check voltage and/or resistance to confi rm that the sensor is operating
correctly per the tables. Please follow the notes and instructions below
each chart when checking sensors.
Table 5, cont.: Temperature/Resistance for Type III
10K Ohm Thermistor Sensors
Thermistor Sensor Testing Instructions
Use the resistance column to check the thermistor sensor while disconnected from the controllers (not powered).
Use the voltage column to check sensors while connected to powered
controllers. Read voltage with meter set on DC volts. Place the “-”
(minus) lead on GND terminal and the “+” (plus) lead on the sensor
input terminal being investigated.
If the voltage is above 5.08 VDC, then the sensor or wiring is “open.”
If the voltage is less than 0.05 VDC, then the sensor or wiring is
shorted.
Table 5: Temperature/Resistance for Type III 10K
Ohm Thermistor Sensors
28
Technical Guide
WSHP-X Module
Troubleshooting
OE275-01 Suction Pressure Transducer
T esting for R-22 & R410-A Refrigerant
The Evaporator Coil Temperature is calculated by converting the Suction Pressure to T emperature. The Suction Pressure is obtained by using
the OE275-01 Suction Pressure Transducer , which is connected into the
Suction Line of the Compressor.
Use the voltage column to check the Suction Pressure Transducer while
connected to the WSHP-X Module. Read voltage with a meter set on
DC volts. If the temperature/voltage or pressure/voltage readings do
not align closely with the chart, your Suction Pressure Transducer is
probably defective and will need to be replaced.
See the OE275-01 Suction Pressure Transducer , Pressure, T emperature,
and Voltage Charts for R-22 and R410-A Refrigerant testing (Tables 6 & 7). The charts show a temperature range from 20°F to 80°F. For
troubleshooting purposes, the DC Voltage readings are also listed with
their corresponding temperatures and pressure.
The WSHP-X Module is equipped with LEDs that can be used to verify
operation and perform troubleshooting. There are LEDs for communication, operation modes, diagnostic codes, and relays. The Module has
twenty LEDs—one used for power, one used for communications, one
used for operation status, one used for alarms, fi ve used for compressor
relays, four used for Suction Pressure Transducer status, and seven used
for Binary Input status. See Figures 10 & 11 on page 31 for the LED
locations. The LEDs associated with these inputs and outputs allow you
to see what is active without using a voltmeter.
Operation Status LEDs
“STATUS” - This is the status blink code LED. It will light up and
fi rst blink the address of the Module. It will then blink out the Mode of
Operation. See Table 8 below for Status Blink Code descriptions. The
blink code descriptions are also located on the Module’s front cover.
See Figure 10 for location.
No. of
Blinks
1Off Mode
2Cool Mode
3Heat Mode
Table 8: STATUS LED Blink Codes
Status
Y 102374 REV 0S
WATTMASTER CONTROLS
MADE IN USA
“COMM” - This LED will light up to indicate Communications with
the VCM-X WSHP Series Controller or SA Series Controller. If Communications are established, the COMM LED will blink. You should
not see this LED light up in stand-alone mode, because there would be
no communications with the VCM-X WSHP Series Controller or SA
Series Controller. See Figure 10 for location.
“ALARM” - This is the diagnostic blink code LED. It will light up and
blink out diagnostic codes. See Table 9 below for Diagnostic Blink
Code descriptions. The blink code descriptions are also located on the
Module’s front cover. See Figure 10 for location.
No. of
Blinks
1Low Suction Pressure
2Compressor Lockout
3Water Flow Failure
4Low Leaving Water Temp
Alarm
Table 9: ALARM LED Blink Codes
Figure 10: Operation Status LED Locations
30
Technical Guide
WSHP-X Module
Troubleshooting
Suction Pressure Transducer LEDs
“PRES 1-4” - There are LEDs for each of the Suction Pressure
Transducers. Since each compressor has a sensor, these LEDs which
are located on the top left of the WSHP-X Module will give a better
indication of which compressor is causing an alarm. See Table 10 for
PRES LED status descriptions. See Figure 11 for locations.
No. of
Blinks
Solid OnSensor is Detected and is OK
Solid OffSensor is Not Detected
1Low Suction Pressure on this Compressor
2Compressor is Locked Out
Table 10: PRES 1-4 LED Blink Codes
Status
LED Diagnostics
“POWER” LED: When the WSHP-X Module is powered up, the
POWER LED (located above the address switches) should light up and
stay on continuously. If it does not light up, check to be sure that the
power wiring is connected to the board, the connections are tight, and
the VCM-X WSHP Series Controller or SA Series Controller is powered
(if connected). If after making all these checks, the POWER LED does
not light up, the module is probably defective.
“COMM” LED: When the WSHP-X Module is powered up while in
Stand Alone Mode, the COMM LED does not light up. When the module
is connected to the VCM-X WSHP Series Controller or SA Series Controller, the COMM LED should light up, indicating Communications.
Each time Communications are detected, this LED should continuously
blink on and off for a half second. This LED should never stop checking
for a Communications signal. If it does not light up, check to be sure
that the power wiring is connected to the board, the connections are
tight, and the VCM-X WSHP Series Controller or SA Series Controller
is powered. If after making all these checks, the COMM LED does not
light up, the board is probably defective.
“ST A TUS” LED: As previously described, when the WSHP Module is
fi rst powered up, the STA TUS LED will b
link out the Mode of Operation.
“ALARM” LED: As previously described, this LED will blink on and
off to indicate alarms and diagnostics.
NOTE: The WSHP-X Module contains no user-serviceable parts.
Contact qualifi ed technical personnel if your Module is
not operating correctly.
Figure 11: PRES 1-4 LED Locations
Technical Guide
31
www.aaon.com
2425 So. Yukon Ave • Tulsa, OK 74107-2728
Ph: (918) 583-2266 • Fax: (918) 583-6094
AAON® Manual Part No. V23560
WattMaster Manual Form No: AA-WSHPX-FIELD-TGD-01C
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.