Orion OE742-XX-VAVZ User Manual

Page 1
OE742-31-VAVZ VAV/Zone
Controller Actuator Package
Description
The OE742-31-VAVZ VAV/Zone Controller Actuator Package with Power/Comm connectors pro­vides a new solution for zone damper applications. The new package includes a VAV/Zone Actuator and a VAV/Zone Con­troller mounted in a plastic enclo­sure. An optional conduit cover is also available that mounts over the control terminals for installa­tions requiring conduit connec­tions. The VAV/Zone Controller Actuator Package is designed for left- or right-hand mounting on a VAV Terminal unit. Each package comes standard with a right-hand label and the actuator positioned for right-hand use. For left-hand units, the actuator can be rotated 180 degrees by removing two screws that secure it to the enclo­sure, rotating the damper actua­tor, and re-fastening the actuator to the enclosure. A left-hand label is also supplied that can be ap­plied over the right-hand label for left-hand applications.
Mounting
The VAV/Zone Actuator package is very easy to mount on your terminal unit. It is installed by simply loosening the damper shaft u-bolt on the actuator and sliding the entire Zone Controller Actuator Package Assembly over the terminal unit’s damper shaft, tightening the actuator u-bolt around the damper shaft, and inserting a self-tapping screw into the anti-rotation bushing located at the opposite end of the enclosure base. Detailed mounting and installation instructions are provided with each package. A conduit enclosure is available as an option which provides conduit knockouts and encloses the electrical connec­tions for applications where code requirements mandate conduit be used for low voltage electrical wiring.
Technical Data OE742-31-VAVZ
VAV/Zone Controller Actuator Package
Zone Controller: Outputs:
Supply Power 24 VAC (1) RJ-45 Cable Connection For Auxiliary Relay Board Power Consumption 6 VA Maximum (1) RJ-45 Cable Connection To Damper Actuator Operating Tempera-
ture Operating Humidity 90% RH Non-Condensing
Communications RS-485 – 9600 Baud Programming Port Mini-DIN Jr. Port
Inputs:
(1) RJ-45 Cable Connection For Digital Temperature Or Analog Temperature
(2) Auxiliary Terminals For Duct Temperature Sen­sor
(1) Molex Connector For Power/Comm In Airflow Ports Barbed Tube Fittings (PI Versions Only)
WattMaster reserves the right to change specifications without notice.
Three Year Warranty
Form: Orion-OE742-31-VAVZ-ZCAP-Sub-01C.doc Page 1 of 1
10F to 149F
Enclosure Material Fire Rated ABS Plastic Zone Controller Factory Mounted Inside The Enclosure Zone Actuator Factory Mounted To The Enclosure Actuator Rating 35 in/lbs (6 ft2 Damper Area Max.) Labeling Right Hand & Left Hand
(1) Molex Connector For Power/Comm Out
Features:
Page 2
OE742-32-VAVZ VAV/Zone
Controller Actuator Package
Description
The OE742-32-VAVZ VAV/Zone Controller Actuator Package with Terminal Block connectors provides a new so­lution for zone damper applica­tions. The new package in­cludes a VAV/Zone Actuator and a VAV/Zone Controller mounted in a plastic enclosure. An optional conduit cover is also available that mounts over the control terminals for installa­tions requiring conduit connec­tions. The VAV/Zone Controller Actuator Package is designed for left- or right-hand mounting on a VAV Terminal unit. Each package comes standard with a right-hand label and the actua­tor positioned for right-hand use. For left-hand units, the actuator can be rotated 180 degrees by removing two screws that secure it to the en­closure, rotating the damper actuator, and re-fastening the actuator to the enclosure. A left­hand label is also supplied that can be applied over the right­hand label for left-hand applica­tions.
Mounting
The VAV/Zone Actuator pack­age is very easy to mount on your terminal unit. It is installed by simply loosening the damper shaft u-bolt on the actuator and sliding the entire Zone Controller Actuator Package Assembly over the terminal unit’s damper shaft, tightening the actuator u-bolt around the damper shaft, and inserting a self-tapping screw into the anti-rotation bushing located at the opposite end of the enclosure base. Detailed mounting and installation in­structions are provided with each package. A conduit enclosure is available as an option which provides conduit knockouts and encloses the electrical connections for applications where code requirements mandate conduit be used for low voltage electrical wiring.
Technical Data OE742-32-VAVZ VAV/Zone Controller Actuator Package
Zone Controller: Outputs:
Supply Power 24 VAC (1) RJ-45 Cable Connection For Auxiliary Relay Board Power Consumption 6 VA Maximum (1) RJ-45 Cable Connection To Damper Actuator Operating Temperature Operating Humidity 90% RH Non-
Communications RS-485 – 9600 Baud Programming Port Mini-DIN Jr. Port
Inputs:
(1) RJ-45 Cable Connection For Digital Temperature Or Analog Temperature
(2) Auxiliary Terminals For Duct Temperature Sensor
(1) Terminal Block Connector For Power In Airflow Ports Barbed Tube Fittings (PI Versions Only) (1) Terminal Block Connector For Comm In
WattMaster reserves the right to change specifications without notice. Three Year Warranty
Form: Orion-OE742-32-VAVZ-ZCAP-Sub-01B.doc Page 1 of 1
10F to 149F
Condensing
Enclosure Material Fire Rated ABS Plastic Zone Controller Factory Mounted Inside The Enclosure Zone Actuator Factory Mounted To The Enclosure Actuator Rating 35 in/lbs (6 ft2 Damper Area Max.) Labeling Right Hand & Left Hand
Uses Same 3 Conductor Terminal Block as Comm Input
Features:
Page 3
OE744-31-VAVZ VAV/Zone
Controller Actuator Package
Description
The OE744-31-VAVZ VAV/Zone Controller Actuator Package with Power/Comm connectors pro­vides a new solution for zone damper applications. The new package includes a VAV/Zone Actuator, a VAV/Zone Controller, and an Airflow Sensor all mount­ed in a plastic enclosure. An op­tional conduit cover is also avail­able that mounts over the control terminals for installations requir­ing conduit connections. The VAV/Zone Controller Actuator Package is designed for left- or right-hand mounting on a VAV Terminal unit. Each package comes standard with a right-hand label and the actuator positioned for right-hand use. For left-hand units, the actuator can be rotated 180 degrees by removing two screws that secure it to the en­closure, rotating the damper ac­tuator, and re-fastening the actu­ator to the enclosure. A left-hand label is also supplied that can be applied over the right-hand label for left-hand applications.
Mounting
The VAV/Zone Actuator package is very easy to mount on your terminal unit. It is installed by simply loosening the damper shaft u-bolt on the actuator and sliding the entire Zone Controller Actuator Package Assembly over the terminal unit’s damper shaft, tightening the actuator u­bolt around the damper shaft, and inserting a self-tapping screw into the anti-rotation bushing located at the opposite end of the enclosure base. Detailed mounting and installation instructions are provided with each package. A conduit enclosure is available as an option which provides conduit knockouts and encloses the electrical connections for applications where code requirements mandate conduit be used for low voltage electrical wiring.
Technical Data OE744-31-VAVZ
VAV/Zone Controller Actuator Package
Zone Controller: Outputs:
Supply Power 24 VAC (1) RJ-45 Cable Connection For Auxiliary Relay Board Power Consumption 6 VA Maximum (1) RJ-45 Cable Connection To Damper Actuator Operating Temperature Operating Humidity 90% RH Non-Condensing
Communications RS-485 – 9600 Baud Programming Port Mini-DIN Jr. Port
Inputs:
(1) RJ-45 Cable Connection For Digital Temperature Or Analog Temperature
(2) Auxiliary Terminals For Duct Temperature Sensor Labeling Right Hand & Left Hand (1) Molex Connector For Power/Comm In Airflow Ports Barbed Tube Fittings (PI Versions Only)
WattMaster reserves the right to change specifications without notice.
Three Year Warranty
Form: Orion-OE744-31-VAVZ-ZCAP-Sub-01C.doc Page 1 of 1
10F to 149F
Enclosure Material Fire Rated ABS Plastic Zone Controller Factory Mounted Inside The Enclosure Zone Actuator Factory Mounted To The Enclosure Actuator Rating 35 in/lbs (6 ft2 Damper Area Max.)
(1) Molex Connector For Power/Comm Out
Features:
Page 4
Description
The OE744-32-VAVZ VAV/Zone Controller Actuator Package with Terminal Block connectors provides a new so­lution for zone damper applica­tions. The new package in­cludes a VAV/Zone Actuator, a VAV/Zone Controller, and an Airflow Sensor all mounted in a plastic enclosure. An optional conduit cover is also available that mounts over the control terminals for installations requir­ing conduit connections. The VAV/Zone Controller Actuator Package is designed for left- or right-hand mounting on a VAV Terminal unit. Each package comes standard with a right­hand label and the actuator positioned for right-hand use. For left-hand units, the actuator can be rotated 180 degrees by removing two screws that se­cure it to the enclosure, rotating the damper actuator, and re­fastening the actuator to the enclosure. A left-hand label is also supplied that can be ap­plied over the right-hand label for left-hand applications.
OE744-32-VAVZ VAV/Zone
Controller Actuator Package
Mounting
The VAV/Zone Actuator pack­age is very easy to mount on your terminal unit. It is installed by simply loosening the damper shaft u-bolt on the actuator and sliding the entire Zone Controller Actuator Package Assembly over the terminal unit’s damper shaft, tightening the actuator u­bolt around the damper shaft, and inserting a self-tapping screw into the anti-rotation bushing located at the opposite end of the enclosure base. Detailed mounting and installation instructions are provided with each package. A conduit enclosure is available as an option which provides conduit knockouts and encloses the electrical connections for applications where code requirements mandate conduit be used for low voltage electrical wiring.
Technical Data OE744-32-VAVZ VAV/Zone Controller Actuator Package
Zone Controller: Outputs:
Supply Power 24 VAC (1) RJ-45 Cable Connection For Auxiliary Relay Board Power Consumption 6 VA Maximum (1) RJ-45 Cable Connection To Damper Actuator Operating Temperature Operating Humidity 90% RH Non-Condensing
Communications RS-485 – 9600 Baud Programming Port Mini-DIN Jr. Port
Inputs:
(1) RJ-45 Cable Connection For Digital Temperature Or Analog Temperature
(2) Auxiliary Terminals For Duct Temperature Sensor Labeling Right Hand & Left Hand (1) Terminal Block Connector For Power In Airflow Ports Barbed Tube Fittings (PI Versions Only) (1) Terminal Block Connector For Comm In
WattMaster reserves the right to change specifications without notice.
Three Year Warranty
10F to 149F
Enclosure Material Fire Rated ABS Plastic Zone Controller Factory Mounted Inside The Enclosure Zone Actuator Factory Mounted To The Enclosure Actuator Rating 35 in/lbs (6 ft2 Damper Area Max.)
Form: Orion-OE744-32-VAVZ-ZCAP-Sub-01B.doc Page 1 of 1
Uses Same 3 Conductor Terminal Block as Comm Input
Features:
Page 5
Description
The OE325-01 4 Relay with Analog Output Expansion board is used in conjunction with the OE742-31­VAVZ, OE742-32-VAVZ, OE744­31-VAVZ, OE744-32-VAVZ VAV/Zone Controller Actuator Packages, the OE736-01, OE736­02 Rectangular Damper Kits,the OE520-XX-M, OE520-XX-T, OE521-XX-M, OE521-XX-M Round Zone Damper Assemblies. It allows for control of fans, including series and parallel flow fan terminal units and/or heat. The OE325-01 Analog Output Expansion board provides 4 relay outputs for pilot duty switching control, (1 fan, 2 heat and 1 auxiliary) relay output and 1 Analog output for control of a 0-10V modulating hot water valve or SCR controlled electric heating coil.
The OE325-01 4 Relay W/ Analog Output Expansion board connects to the VAV/Zone Controller board by means of a 18” long modular cable provided with the board. Power is supplied to the board by means of this modular cable. Screw terminals are provided for connection of field wiring to the relay and analog outputs.
The relay outputs are N.O. contacts with one common terminal. All outputs and the relay common are electrically isolated from all other circuitry on the board. All relay outputs are supplied with transient suppression devices across each set of contacts to reduce EMI and arcing. The relay output contacts are rated for pilot duty control of a maximum of 2 Amps @ 24 VAC or 24 VDC. The analog output provides a 0 – 10 VDC modulating signal output into a 1k Ohm minimum load.
OE325-01 - 4 Relay W/ Analog Output
Expansion Board
Mounting
The OE325-01 4 Relay W/ Analog Output Expansion Board is supplied mounted on a plastic snap track channel. The snap track channel has two mounting holes which are used to field mount the board with the provided screws. The board should be mounted in close proximity to the VAVZ Zone Controller board to allow for connection of the modular cable.
Technical Data OE325-01 4 Relay W/ Analog
Output Expansion board
Operating Temp Weight 4 oz Connection to Controller: Modular Cable
10F to 149F
Operating Humidity 90% RH Non-Condensing
Outputs: Inputs:
Analog Output Qty & Rating
Relay Output Qty. 4 – Electrically Isolated Relay Contact Rating 2 Amp @ 24 VAC
Three Year Warranty
Form: ORION-OE325-01-4RelayW-AnalogOutputExpBrd-1B.doc Page 1 of 1
(1) 0-10 VDC @ 1k Ohm
Minimum load
Analog Input Application Specific
Universal Input
WattMaster reserves the right to change specifications without notice
Page 6
Description
The Orion OE282 Damper Actuator is a shaft mounted, floating point control actuator. Actuators are 24VAC/24VDC with a 10K ohm feedback signal for po­sition monitoring. Wiring connection to the actuator is by means of a modular phone cable connector located on the actuator cover. The actuator is rated for 35 in-lb of torque. All actuators are electronically protected against over­load. The angle of rotation is mechani­cally limited to 95. When the end posi­tion of the actuator or damper is reached, the actuator automatically stops. For adjustment purposes, the gears can be manually disengaged by pushing the manual override button on the actuator cover.
OE282 - Damper Actuator
Applications
The OE282 Damper Actuator is used to provide control of air volume dampers in an Orion VAV or zoning systems. When used in VAV and Zoning applica­tions it is typically used in conjunction with an OE324-00-VAVZ Zone control­ler board.
Technical Data OE282
Power Supply Life Cycle Rating 2.5 Million Cycles with Mechanical Stops Power Consumption 3 VA Maximum Power Connection RJ-11 Modular Jack Operating Temp Operating Humidity 5 to 95% RH Non-Condensing Quality Standard ISO 9001 Overload Protection
Feedback Signal 10K ohm 1W Potentiometer Torque Minimum 35 in-lb Running Time 80-110 Seconds. Weight 1.2 lb.
Three Year Warranty WattMaster reserves the right to change specifications without notice
24VAC 20% 50/60HZ
-22F to 122F
Electronic Throughout 0 to 95 Rotation
Angle of Rotation
Servicing Maintenance Free
Agency Listings UL873 listed
Damper Actuator
Max. 95, Adjustable
CSA 4813 02 Certified
Form: ORION-OE282-ProportionalDamper Actuator-1C.doc Page 1 of 1
Page 7
Description
The OE282 Damper Actuator is a shaft mounted, floating point control actuator. Actuators are 24VAC/24VDC with a 10K ohm feedback signal for position monitoring. Wiring connection to the actuator is by means of a modular phone cable connector located on the actuator cover. The actuator is rated for 45 in-lb of torque. All actuators are electronically protected against overload. The angle of rotation is mechanically limited to 95. When the end position of the actuator or damper is reached, the actuator automatically stops. For adjustment purposes, the gears can be manually disengaged by pushing the manual override button on the actuator cover.
Zone Damper Actuator
OE282-01
Applications
The OE282 Damper Actuator is used to provide control of air volume dampers in an VAV or Zoning system.
When used in VAV and Zoning applications it is normally factory mounted in the OE742-31­VAVZ, OE742-32-VAVZ. P.D. VAV/Zone Controller Actuator Packages or the OE744-31­VAVZ, OE744-32-VAVZ. P.I. VAV/Zone Controller Actuator Packages.
It is also a component of the OE282-03 Slaved VAV/Zone Damper Kit. This kit allows multiple dampers (up to 2 total besides the master) to be connected to a master OE742-31-vVAVZ, OE742-32-VAVZ P.D. Zone/VAV Controller Actuator Package or OE744-31-VAVZ, OE744-32-VAVZ P.I. Zone/VAV Controller Actuator Packages. The OE282-03 Kit is typically used when larger CFM requirements dictate multiple dampers be used.
Technical Data OE282-01 Damper Actuator
Power Supply Life Cycle Rating 2.5 Million Cycles with Mechanical Stops Power Consumption 3 VA Maximum Power Connection RJ-11 Modular Jack Operating Temp Operating Humidity 5 to 95% RH Non-
Overload Protection Electronic Throughout 0 to
Feedback Signal 10K ohm 1W Potentiometer Torque Minimum 45 in-lb Running Time 80-110 Seconds. Weight 1.2 lb.
Three Year Warranty
Form: ORION-OE282-01ZoneDmprAct-Sub-01A.doc Page 1 of 1
24VAC 20% 50/60HZ
-22F to 122F
Condensing
95 Rotation
Angle of Rotation
Servicing Maintenance Free Quality Standard ISO 9001
Agency Listings UL873 listed
WattMaster reserves the right to change specifications without notice
Max. 95, Adjustable
CSA 4813 02 Certified
Page 8
Description
The OE520-XX-M Round Pressure Dependent Zone Damper Assembly with modular connectors consists of a round air damper and Zone Controller Actuator Package with modular wiring connectors. An optional Zone Controller Expansion Module (OE325-01) is available for control of reheat, heat and/or control of series or parallel flow fan terminal units.
The Zone Controller board is microprocessor based and communicates with the HVAC unit controller on the Orion network communications loop. The Zone Controller monitors the space temperature and allocates the proper airflow into its assigned space to achieve the desired comfort and ventilation levels.
Pressure Dependent Zone Dampers are used in air conditioning systems that do not require pressure independent airflow control. If your system requires pressure independent control of the airflow, see the “OE521-XX-M Round Pressure Independent Zone Damper” submittal sheet for the correct specifications. All dampers are tested for performance in accordance with AMCA 500D standards.
OE520-XX-M Round P.D. Zone Damper
Assembly W/ Modular Connectors
Mounting
The Zone Damper Assembly should be mounted according to standard duct installation practices with airflow direction as shown in the illustration above. After installation of the Zone Damper in the ductwork, insulation should be applied around any remaining un-insulated surface on the damper inlet and outlet. The Zone Damper should be mounted so the control enclosure is positioned to the left or right side of the ductwork with the control enclosure in a vertical plane. Do not mount the Zone Damper Assembly with the control enclosure on the top or bottom of the ductwork. Adequate clearance should be maintained between the control panel and any obstruction to allow for removal of the control panel cover and access to the controls.
Technical Data
Zone Damper Assembly W/ Modular Connectors
OE520-XX-M Round Pressure Dependent
Zone Controller: Air Damper Construction:
Supply Power 24 Volt AC Damper Body 20 Ga. Galv. Steel Power Consumption 6 VA Maximum Damper Blade Round -18 Ga. Galv. Steel Operating Temperature Operating Humidity 90% RH Non-Condensing Damper Seal EPDM Rubber Gasket Communications RS-485 - 9600 Baud Leakage < 20 CFM Per Sq. Ft. @ 4” SP
35F to 125F
Damper Bearings Stainless Steel
Insulation ½” Foil Faced Fiberglass
Inputs: Dimensions:
Room Temperature Sensor Setpoint Adjustment OE510-06 (6”) 23.00 5.88 9.88 Actuator Position Feedback OE510-08 (8”) 23.00 7.88 12.13
Communication Connectors: Modular In & Out Outputs:
Expansion Port for Auxiliary Relay Board OE510-14 (14”) 23.00 13.88 18.50 Actuator Port for Connection to Damper Actuator OE510-16 (16”) 23.00 15.88 20.56
WattMaster reserves the right to change specifications without notice
Three Year Warranty On Electronic Components One Year Warranty On Air Damper
Air Damper Model “A” “B” “C”
OE510-10 (10”) 23.00 9.88 14.31 OE510-12 (12”) 23.00 11.88 16.43
Form: Orion-OE520XX-M-RndDmpr-Sub-01G Page 1 of 2
Page 9
OE520-XX-M Round P.D. Zone Damper
Assembly W/ Modular Connectors
Zone Damper Sizing
Use a load program to determine the peak load for each zone. These calculations will be used to select VAV/Zone Damper sizes.
The Orion Systems utilize a typical low pressure duct design. To reduce noise problems, duct pressures should not exceed 1” W.C.
Primary trunk ducts used with Orion systems should not be “undersized”. This is especially true of “pressure dependent” systems. With larger trunk ducts, it is easier to assure relatively constant pressure to each Zone Damper. Runs should be as short as possible, and the trunk duct system kept as symmetrical as possible to facilitate system balancing. Wherever possible, run the trunk ducts above corridors and locate the Zone Dampers above corridors to reduce the noise in the space and facilitate service of the valves. Trunk ducts should be sized for no more than 0.1” W.C. drop per 100 ft. of duct, and a maximum duct velocity of 2000 FPM.
Zone Damper Selection Data
Zone Damper Round Duct Size
(Area Ft
Velocity Through VAV/Zone Damper
FPM
500
750
1000
1250
1500
1750
2000
2
)
WattMaster reserves the right to change specifications without notice
6”
(0.196)
98
(< 0.01)
147
(0.01)
196
(0.015)
245
(0.025)
294
(0.035)
343
(0.045)
392
(0.065)
Using the maximum acceptable velocity for a branch duct (typically 1000-1500 FPM for minimal noise), find the smallest Zone Damper that will deliver the required CFM as determined by the load program. Locate the branch velocity used in the duct design program in the left hand column of the Zone Damper Selection Data table. Move across the table and find the Zone Damper, which will provide the acceptable CFM to meet the zone airflow requirements.
Note: Compare the Zone Damper size selected against the
duct size to determine if the next size up or down will provide acceptable performance without requiring a transition fitting.
Up to a maximum of two Slaved Zone Dampers may be slaved together with the main Zone Damper for large zones. This design should be reserved only for situations when it is not practical to use a single Zone Damper. See the AZ-300-RS Round Slaved Zone Damper submittal sheet for information regarding application and selection of Round Slaved Zone Dampers.
OE520-XX-M Round Pressure Dependent
Zone Damper Assembly W/ Modular Connectors
8”
(0.349)
Airflow Through VAV/Zone Damper - CFM
(P
175
(< 0.01)
262
(0.01)
349
(0.015)
436
(0.02)
523
(0.035)
611
(0.035)
698
(0.043)
10”
(0.545)
inches W.C. w/ Damper Full Open)
S
273
(< 0.01)
409
(0.01)
545
(0.01)
681
(0.015)
818
(0.022)
954
(0.034)
1090
(0.040)
12”
(0.785)
393
(< 0.01)
589
(< 0.01)
785
(< 0.01)
981
(0.015)
1178
(0.020)
1374
(0.030)
1570
(0.040)
(1.069)
(< 0.01)
(< 0.01)
(< 0.01)
(0.015)
(0.030)
(0.040)
14”
535
802
1069
1336
1604
0.020) 1871
2138
16”
(1.396)
698
(< 0.01)
1047
(< 0.01)
1396
(< 0.01)
1745
(0.015)
2094
(0.020)
2443
(0.025)
2792
(0.030)
Form: Orion-OE520XX-M-RndDmpr-Sub-01G Page 2 of 2
Page 10
Description
The OE520-XX-T Round Pressure Dependent Zone Damper Assembly with terminal connectors consists of a round air damper and Zone Controller Actuator Package with terminal wiring connectors. An optional Zone Controller Expansion Module (OE325-01) is available for control of reheat, heat and/or control of series or parallel flow fan terminal units.
The Zone Controller board is microprocessor based and communicates with the HVAC unit controller on the Orion network communications loop. The Zone Controller monitors the space temperature and allocates the proper airflow into its assigned space to achieve the desired comfort and ventilation levels.
Pressure Dependent Zone Dampers are used in air conditioning systems that do not require pressure independent airflow control. If your system requires pressure independent control of the airflow, see the “OE521-XX-T Round Pressure Independent Zone Damper” submittal sheet for the correct specifications. All dampers are tested for performance in accordance with AMCA 500D standards.
OE520-XX-T Round P.D. Zone Damper
Assembly W/ Terminal Connectors
Mounting
The Zone Damper Assembly should be mounted according to standard duct installation practices with airflow direction as shown in the illustration above. After installation of the Zone Damper in the ductwork, insulation should be applied around any remaining un-insulated surface on the damper inlet and outlet. The Zone Damper should be mounted so the control enclosure is positioned to the left or right side of the ductwork with the control enclosure in a vertical plane. Do not mount the Zone Damper Assembly with the control enclosure on the top or bottom of the ductwork. Adequate clearance should be maintained between the control panel and any obstruction to allow for removal of the control panel cover and access to the controls.
Technical Data
Zone Damper Assembly W/ Terminal Connectors
OE520-XX-T Round Pressure Dependent
Zone Controller: Air Damper Construction:
Supply Power 24 Volt AC Damper Body 20 Ga. Galv. Steel Power Consumption 6 VA Maximum Damper Blade Round -18 Ga. Galv. Steel Operating Temperature Operating Humidity 90% RH Non-Condensing Damper Seal EPDM Rubber Gasket Communications RS-485 - 9600 Baud Leakage < 20 CFM Per Sq. Ft. @ 4” SP
35F to 125F
Damper Bearings Stainless Steel
Insulation ½” Foil Faced Fiberglass
Inputs: Dimensions:
Room Temperature Sensor Setpoint Adjustment OE510-06 (6”) 23.00 5.88 9.88 Actuator Position Feedback OE510-08 (8”) 23.00 7.88 12.13
Communication Connectors: Terminals In & Out Outputs:
Expansion Port for Auxiliary Relay Board OE510-14 (14”) 23.00 13.88 18.50 Actuator Port for Connection to Damper Actuator OE510-16 (16”) 23.00 15.88 20.56
WattMaster reserves the right to change specifications without notice
Three Year Warranty On Electronic Components One Year Warranty On Air Damper
Air Damper Model “A” “B” “C”
OE510-10 (10”) 23.00 9.88 14.31 OE510-12 (12”) 23.00 11.88 16.43
Form: Orion-OE520XX-T-RndDmpr-Sub-01G Page 1 of 2
Page 11
OE520-XX-T Round P.D. Zone Damper
Assembly W/ Terminal Connectors
VAV/Zone Damper Sizing
Use a load program to determine the peak load for each zone. These calculations will be used to select Zone Damper sizes.
The Orion Systems utilize a typical low pressure duct design. To reduce noise problems, duct pressures should not exceed 1” W.C.
Primary trunk ducts used with Orion systems should not be “undersized”. This is especially true of “pressure dependent” systems. With larger trunk ducts, it is easier to assure relatively constant pressure to each Zone Damper. Runs should be as short as possible, and the trunk duct system kept as symmetrical as possible to facilitate system balancing. Wherever possible, run the trunk ducts above corridors and locate the Zone Dampers above corridors to reduce the noise in the space and facilitate service of the valves. Trunk ducts should be sized for no more than 0.1” W.C. drop per 100 ft. of duct, and a maximum duct velocity of 2000 FPM.
Zone Damper Selection Data
Zone Damper Round Duct Size
(Area Ft
Velocity Through VAV/Zone Damper
FPM
500
750
1000
1250
1500
1750
2000
2
)
WattMaster reserves the right to change specifications without notice
6”
(0.196)
98
(< 0.01)
147
(0.01)
196
(0.015)
245
(0.025)
294
(0.035)
343
(0.045)
392
(0.065)
Using the maximum acceptable velocity for a branch duct (typically 1000-1500 FPM for minimal noise), find the smallest Zone Damper that will deliver the required CFM as determined by the load program. Locate the branch velocity used in the duct design program in the left hand column of the Zone Damper Selection Data table. Move across the table and find the Zone Damper, which will provide the acceptable CFM to meet the zone airflow requirements.
Note: Compare the Zone Damper size selected against
the duct size to determine if the next size up or down will provide acceptable performance without requiring a transition fitting.
Up to a maximum of two Slaved Zone Dampers may be slaved together with the main Zone Damper for large zones. This design should be reserved only for situations when it is not practical to use a single Zone Damper. See the AZ-300-RS Round Slaved Zone Damper submittal sheet for information regarding application and selection of Round Slaved Zone Dampers.
OE520-XX-T Round Pressure Dependent
Zone Damper Assembly W/ Terminal Connectors
8”
(0.349)
Airflow Through VAV/Zone Damper - CFM
(P
175
(< 0.01)
262
(0.01)
349
(0.015)
436
(0.02)
523
(0.035)
611
(0.035)
698
(0.043)
10”
(0.545)
inches W.C. w/ Damper Full Open)
S
273
(< 0.01)
409
(0.01)
545
(0.01)
681
(0.015)
818
(0.022)
954
(0.034)
1090
(0.040)
12”
(0.785)
393
(< 0.01)
589
(< 0.01)
785
(< 0.01)
981
(0.015)
1178
(0.020)
1374
(0.030)
1570
(0.040)
(1.069)
(< 0.01)
(< 0.01)
(< 0.01)
(0.015)
0.020)
(0.030)
(0.040)
14”
535
802
1069
1336
1604
1871
2138
16”
(1.396)
698
(< 0.01)
1047
(< 0.01)
1396
(< 0.01)
1745
(0.015)
2094
(0.020)
2443
(0.025)
2792
(0.030)
Form: Orion-OE520XX-T-RndDmpr-Sub-01G Page 2 of 2
Page 12
Description
The OE521-XX-M Round Pressure Independent Zone Damper Assembly with modular connectors consists of a round air damper with air flow pickup cross and a Zone Controller Actuator Package (including air flow sensor) with modular connectors. An optional Zone Controller Expansion Module (OE325-01) is available for control of reheat, heat and/or control of series or parallel flow fan terminal units.
The Zone Controller board is microprocessor based and communicates with the HVAC unit controller on the Orion network communications loop. The Zone Controller monitors the space temperature and allocates the proper airflow into its assigned space to achieve the desired comfort and ventilation levels.
Pressure Independent Zone Dampers are used in air conditioning systems require pressure independent airflow control. If your system requires pressure dependent control of the airflow, see the “OE520-XX-M Round Pressure Dependent Zone Damper” submittal sheet for the correct specifications. All dampers are tested for performance in accordance with AMCA 500D standards.
OE521-XX-M Round P.I. Zone Damper
Assembly W/ Modular Connectors
Mounting
The Zone Damper Assembly should be mounted according to standard duct installation practices with airflow direction as shown in the illustration above. After installation of the Zone Damper in the ductwork, insulation should be applied around any remaining un-insulated surface on the damper inlet and outlet. The Zone Damper should be mounted so the control enclosure is positioned to the left or right side of the ductwork with the control enclosure in a vertical plane. Do not mount the Zone Damper Assembly with the control enclosure on the top or bottom of the ductwork. Adequate clearance should be maintained between the control panel and any obstruction to allow for removal of the control panel cover and access to the controls.
Technical Data
OE521-XX-M Round Pressure Independent
Zone Damper Assembly W/ Modular Connectors
Zone Controller: Air Damper Construction:
Supply Power 24 Volt AC Damper Body 20 Ga. Galv. Steel Power Consumption 6 VA Maximum Damper Blade Round -18 Ga. Galv. Steel Operating Temperature Operating Humidity 90% RH Non-Condensing Damper Seal EPDM Rubber Gasket Communications RS-485 - 9600 Baud Leakage < 20 CFM Per Sq. Ft. @ 4” SP
35F to 125F
Inputs:
Air Flow Sensor Room Temperature Sensor
Setpoint Adjustment OE510-06 (6”) 23.00 5.88 9.88 Actuator Position Feedback OE510-08 (8”) 23.00 7.88 12.13
Communication Connectors: Modular In & Out Outputs:
Expansion Port for Auxiliary Relay Board OE510-14 (14”) 23.00 13.88 18.50 Actuator Port for Connection to Damper Actuator OE510-16 (16”) 23.00 15.88 20.56
WattMaster reserves the right to change specifications without notice
Three Year Warranty On Electronic Components One Year Warranty On Air Damper
Damper Bearings Stainless Steel
Insulation ½” Foil Faced Fiberglass
Dimensions:
Air Damper Model “A” “B” “C”
OE510-10 (10”) 23.00 9.88 14.31 OE510-12 (12”) 23.00 11.88 16.43
FormOrion-OE521XX-M-RndDmpr-Sub-01G Page 1 of 2
Page 13
A
OE521-XX-M Round P.I. Zone Damper
Assembly W/ Modular Connectors
Zone Damper Sizing
Use a load program to determine the peak load for each zone. These calculations will be used to select Zone Damper sizes.
The Orion Systems utilize a typical low pressure duct design. To reduce noise problems, duct pressures should not exceed 1” W.C.
Primary trunk ducts used with Orion systems should not be “undersized”. This is especially true of “pressure dependent” systems. With larger trunk ducts, it is easier to assure relatively constant pressure to each Zone Damper. Runs should be as short as possible, and the trunk duct system kept as symmetrical as possible to facilitate system balancing. Wherever possible, run the trunk ducts above corridors and locate the Zone Dampers above corridors to reduce the noise in the space and facilitate service of the dampers. Trunk ducts should be sized for no more than 0.1” W.C. drop per 100 ft. of duct, and a maximum duct velocity of 2000 FPM.
Using the maximum acceptable velocity for a branch duct (typically 1000-1500 FPM for minimal noise), find the smallest Zone Damper that will deliver the required CFM as determined by the load program. Locate the branch velocity used in the duct design program in the left hand column of the Zone Damper Selection Data table. Move across the table and find the Zone Damper, which will provide the acceptable CFM to meet the zone airflow requirements.
Note: Compare the Zone Damper size selected against
the duct size to determine if the next size up or down will provide acceptable performance without requiring a transition fitting.
Pressure Independent Zone Dampers may not be slaved together with Slaved-Zone Damper Assemblies. If more than one damper is required for a zone, all dampers must be selected as pressure dependent. See the Pressure Dependent Zone Damper submittal sheet and Slaved-Zone Damper submittal sheets for selection of master/slave damper configurations.
Zone Damper Selection Data
Zone Damper Round Duct Size
(Area Ft
CFM @ 1” Velocity Pressure (Air Flow Probe “K” Factor)
Velocity Through VAV/Zone Damper
FPM
500
750
1000
1250
1500
1750
2000
2
)
WattMaster reserves the right to change specifications without notice
OE521-XX-M Round Pressure Independent Zone Damper
ssembly W/ Modular Connectors
6”
(0.196)
448 904 1436 1891 3015 3839
8”
(0.349)
Airflow Through VAV/Zone Damper - CFM
(P
10”
(0.545)
inches W.C. w/ Damper Full Open)
S
12”
(0.785)
14”
(1.069)
16”
(1.396)
98
(< 0.01)
147
(0.01)
196
(0.015)
245
(0.025)
294
(0.035)
343
(0.045)
392
(0.065)
175
(< 0.01)
262
(0.01)
349
(0.015)
436
(0.02)
523
(0.035)
611
(0.035)
698
(0.043)
273
(< 0.01)
409
(0.01)
545
(0.01)
681
(0.015)
818
(0.022)
954
(0.034)
1090
(0.040)
393
(< 0.01)
589
(< 0.01)
785
(< 0.01)
981
(0.015)
1178
(0.020)
1374
(0.030)
1570
(0.040)
535
(< 0.01)
802
(< 0.01)
1069
(< 0.01)
1336
(0.015)
1604
0.020) 1871
(0.030)
2138
(0.040)
698
(< 0.01)
1047
(< 0.01)
1396
(< 0.01)
1745
(0.015)
2094
(0.020)
2443
(0.025)
2792
(0.030)
FormOrion-OE521XX-M-RndDmpr-Sub-01G Page 2 of 2
Page 14
Description
The OE521-XX-T Round Pressure Independent Zone Damper Assembly with terminal connectors consists of a round air damper with air flow pickup cross and a Zone Controller Actuator Package (including air flow sensor) with terminal connectors. An optional Zone Controller Expansion Module (OE325-01) is available for control of reheat, heat and/or control of series or parallel flow fan terminal units.
The Zone Controller board is microprocessor based and communicates with the HVAC unit controller on the Orion network communications loop. The Zone Controller monitors the space temperature and allocates the proper airflow into its assigned space to achieve the desired comfort and ventilation levels.
Pressure Independent Zone Dampers are used in air conditioning systems require pressure independent airflow control. If your system requires pressure dependent control of the airflow, see the “OE520-XX-T Round Pressure Dependent Zone Damper” submittal sheet for the correct specifications. All dampers are tested for performance in accordance with AMCA 500D standards.
OE521-XX-T Round P.I. Zone Damper
Assembly W/ Terminal Connectors
Mounting
The Zone Damper Assembly should be mounted according to standard duct installation practices with airflow direction as shown in the illustration above. After installation of the Zone Damper in the ductwork, insulation should be applied around any remaining un-insulated surface on the damper inlet and outlet. The Zone Damper should be mounted so the control enclosure is positioned to the left or right side of the ductwork with the control enclosure in a vertical plane. Do not mount the Zone Damper Assembly with the control enclosure on the top or bottom of the ductwork. Adequate clearance should be maintained between the control panel and any obstruction to allow for removal of the control panel cover and access to the controls.
Technical Data
Zone Damper Assembly W/ Terminal Connectors
OE521-XX-T Round Pressure Independent
Zone Controller: Air Damper Construction:
Supply Power 24 Volt AC Damper Body 20 Ga. Galv. Steel Power Consumption 6 VA Maximum Damper Blade Round -18 Ga. Galv. Steel Operating Temperature Operating Humidity 90% RH Non-Condensing Damper Seal EPDM Rubber Gasket Communications RS-485 - 9600 Baud Leakage < 20 CFM Per Sq. Ft. @ 4” SP
35F to 125F
Inputs:
Air Flow Sensor Room Temperature Sensor
Setpoint Adjustment OE510-06 (6”) 23.00 5.88 9.88 Actuator Position Feedback OE510-08 (8”) 23.00 7.88 12.13
Communication Connectors: Terminals In & Out Outputs:
Expansion Port for Auxiliary Relay Board OE510-14 (14”) 23.00 13.88 18.50 Actuator Port for Connection to Damper Actuator OE510-16 (16”) 23.00 15.88 20.56
WattMaster reserves the right to change specifications without notice
Three Year Warranty On Electronic Components One Year Warranty On Air Damper
Damper Bearings Stainless Steel
Insulation ½” Foil Faced Fiberglass
Dimensions:
Air Damper Model “A” “B” “C”
OE510-10 (10”) 23.00 9.88 14.31 OE510-12 (12”) 23.00 11.88 16.43
Form: Orion-OE521XX-T-RndDmpr-Sub-01G Page 1 of 2
Page 15
OE521-XX-T Round P.I. Zone Damper
Assembly W/ Terminal Connectors
Zone Damper Sizing
Use a load program to determine the peak load for each zone. These calculations will be used to select Zone Damper sizes.
The Orion Systems utilize a typical low pressure duct design. To reduce noise problems, duct pressures should not exceed 1” W.C.
Primary trunk ducts used with Orion systems should not be “undersized”. This is especially true of “pressure dependent” systems. With larger trunk ducts, it is easier to assure relatively constant pressure to each Zone Damper. Runs should be as short as possible, and the trunk duct system kept as symmetrical as possible to facilitate system balancing. Wherever possible, run the trunk ducts above corridors and locate the Zone Dampers above corridors to reduce the noise in the space and facilitate service of the valves. Trunk ducts should be sized for no more than 0.1” W.C. drop per 100 ft. of duct, and a maximum duct velocity of 2000 FPM.
Zone Damper Selection Data
Zone Damper Round Duct Size
(Area Ft
2
)
6”
(0.196)
Using the maximum acceptable velocity for a branch duct (typically 1000-1500 FPM for minimal noise), find the smallest Zone Damper that will deliver the required CFM as determined by the load program. Locate the branch velocity used in the duct design program in the left hand column of the Zone Damper Selection Data table. Move across the table and find the Zone Damper, which will provide the acceptable CFM to meet the zone airflow requirements.
Note: Compare the Zone Damper size selected against
the duct size to determine if the next size up or down will provide acceptable performance without requiring a transition fitting.
Pressure Independent Zone Dampers may not be slaved together with Slaved-Zone Damper Assemblies. If more than one damper is required for a zone, all dampers must be selected as pressure dependent. See the Pressure Dependent Zone Damper submittal sheet and Slaved-Zone Damper submittal sheets for selection of master/slave damper configurations.
OE521-XX-T Round Pressure Independent
Zone Damper Assembly W/ Terminal Connectors
8”
(0.349)
10”
(0.545)
12”
(0.785)
14”
(1.069)
16”
(1.396)
CFM @ 1” Velocity Pressure (Air Flow Probe “K” Factor)
Velocity Through VAV/Zone Damper
FPM
500
750
1000
1250
1500
1750
2000
WattMaster reserves the right to change specifications without notice
448 904 1436 1891 3015 3839
Airflow Through VAV/Zone Damper - CFM
(P
inches W.C. w/ Damper Full Open)
S
98
(< 0.01)
147
(0.01)
196
(0.015)
245
(0.025)
294
(0.035)
343
(0.045)
392
(0.065)
175
(< 0.01)
262
(0.01)
349
(0.015)
436
(0.02)
523
(0.035)
611
(0.035)
698
(0.043)
273
(< 0.01)
409
(0.01)
545
(0.01)
681
(0.015)
818
(0.022)
954
(0.034)
1090
(0.040)
393
(< 0.01)
589
(< 0.01)
785
(< 0.01)
981
(0.015)
1178
(0.020)
1374
(0.030)
1570
(0.040)
535
(< 0.01)
802
(< 0.01)
1069
(< 0.01)
1336
(0.015)
1604
0.020) 1871
(0.030)
2138
(0.040)
698
(< 0.01)
1047
(< 0.01)
1396
(< 0.01)
1745
(0.015)
2094
(0.020)
2443
(0.025)
2792
(0.030)
Form: Orion-OE521XX-T-RndDmpr-Sub-01G Page 2 of 2
Page 16
Description
The OE522-XX Round Bypass Damper Assembly, consists of a round air damper with a bypass actuator and bypass wiring interface card mounted in a control enclosure.
The Bypass Damper controls duct static pressure to insure proper system airflow. The Bypass Damper is controlled by the Orion HVAC Unit Controller. The Unit Controller modulates the Bypass Damper in response to the duct static pressure, based on a signal received from a static pressure sensor located in the main system ductwork.
All dampers are tested for performance in accordance with AMCA 500D standards.
OE522-XX Round Bypass
Damper Assembly
Mounting
The Round Bypass Damper Assembly should be mounted according to standard duct installation practices with airflow direction as shown in the illustration above. After installation of the Bypass Damper in the ductwork, insulation should be applied around any remaining un-insulated surface on the damper inlet and outlet. The Bypass Damper should be mounted so the control enclosure is positioned to the left or right side of the ductwork with the control enclosure in a vertical plane. Do not mount the Bypass Damper Assembly with the control enclosure on the top or bottom of the ductwork. Adequate clearance should be maintained between the control panel and any obstruction to allow for removal of the control panel cover and access to the controls.
Technical Data OE522-XX Round Bypass Damper Assembly
Actuator Air Damper Construction:
Supply Power 24 Volt AC Damper Body 20 Ga. Galv. Steel Power Consumption 3.4 VA Maximum Damper Blade Round -18 Ga. Galv. Steel Operating Temperature Operating Humidity 90% RH Non-Condensing Damper Seal EPDM Rubber Gasket
Inputs: Dimensions:
Actuator Position Feedback OE522-10 (10”) 23.00 9.88 14.31 OE522-12 (12”) 23.00 11.88 16.43 OE522-14 (14”) 23.00 13.88 18.50 OE522-16 (16”) 23.00 15.88 20.56
WattMaster reserves the right to change specifications without notice
Three Year Warranty On Electronic Components One Year Warranty On Air Damper
35°F to 125°F
Damper Bearings Stainless Steel
Leakage < 20 CFM Per Sq. Ft. @ 4” SP Insulation ½” Foil Faced Fiberglass
Air Damper Model “A” “B” “C”
Form: Orion-OE522-RDBypDmpr-Sub-01F Page 1 of 2
Page 17
OE522-XX Round Bypass
Damper Assembly
Bypass Damper Sizing
Because the zones in an Orion System are controlled using variable air volume, it is unlikely that all zones will be at design load at the same time. This zoning allows for load diversity to be taken into account when sizing the central HVAC unit. This typically will provide better comfort with a smaller HVAC unit than with the use of a constant volume system. Use a load program to determine the individual zone loads. Because of zone diversity the HVAC unit should be sized for the correct instantaneous peak load, not the sum of the peak loads as would be the case when sizing a normal constant volume unit system. The Bypass Damper should be sized to provide for the maximum amount of air to be bypassed in the system. This is typically 60 to 70% of the HVAC units rated capacity. These calculations will be used in selecting the appropriate Bypass Damper Size(s).
The Orion Systems utilize a typical low pressure duct design. To reduce noise problems, duct pressures should not exceed 1” W.C..
Using the maximum acceptable velocity for a bypass duct (typically 1750-2250 FPM for minimal noise), find the smallest damper that will deliver the required CFM as determined by the load program.
When determining the bypass duct size, be sure to take into account any transition fittings and their associated pressure drops. Locate the bypass duct velocity used in the duct design program in the left hand column of the Bypass Damper Selection Data table. Move across the table and find the Bypass Damper size which will provide the acceptable CFM to meet the bypass airflow requirements.
Note: Compare the Bypass Air Damper size selected
against the bypass duct size to determine if the next size up or down will provide acceptable performance without requiring a transition fitting.
Up to a maximum of two additional Bypass Dampers may be slaved together with the main Bypass Damper for large bypass airflow requirements. This design should be reserved only for situations when it is not practical to use a single large Bypass Damper. The slaved valves should all be of the same size for proper control. Divide the total CFM by two or three depending on how many bypass and slave dampers you will be using and size accordingly.
Bypass Damper Selection Data OE522-XX Round Bypass Damper Assembly
Bypass Air Damper Round Duct Size
(Area Ft
Velocity Through Bypass Air Damper
2
)
FPM
750
1000
1250
1500
1750
2000
2250
WattMaster reserves the right to change specifications without notice
10”
(0.545)
Airflow Through Bypass Air Damper - CFM
(ΔP
inches W.C. w/ Air Damper Full Open)
S
409
(0.01)
545
(0.01)
681
(0.015)
818
(0.022)
954
(0.034)
1090
(0.040)
1226
(0.07)
12”
(0.785)
589
(< 0.01)
785
(< 0.01)
981
(0.015)
1178
(0.020)
1374
(0.030)
1570
(0.040)
1766
(0.05)
14”
(1.069)
802
(< 0.01)
1069
(< 0.01)
1336
(0.015)
1604
0.020) 1871
(0.030)
2138
(0.040)
2405
(0.05)
16”
(1.396)
1047
(< 0.01)
1396
(< 0.01)
1745
(0.015)
2094
(0.020)
2443
(0.025)
2792
(0.030)
3141
(0.04)
Form: Orion-OE522-RDBypDmpr-Sub-01F Page 2 of 2
Page 18
p
y
OE523-XX Round Slaved Zone
Dam
Description
The OE523-XX Round Slaved Zone Damper Assembly, consists of a round air damper, actuator, (1) slave wiring interface card mounted in the enclosure and also includes (1) slave wiring interface card kit shipped loose for field mounting to the master zone damper assembly. This kit contains a slave wiring interface card and a cable.
The Round Slaved Zone Damper Assembly is used in systems when it is not possible or practical to use a single large Zone Damper to satisfy the zone's CFM requirements.
A total of two Slaved Zone Dampers may be used in conjunction with a master Zone Damper. The Slave Damper(s) are wired in parallel with the master Zone Damper and track the movement of the master Zone Damper. Connection of the master Zone Damper requires a slave wiring interface kit, which is shipped loose for field mounting to the master Zone Damper and is supplied with each Slaved Zone Damper. The kit connects the Zone controller on the master to the master actuator and provides wiring terminals for wiring to the Slaved Zone Dampers. Only (1) of these kits is required for each master/slave installation. All dampers are tested for performance in accordance with AMCA 500D standards.
er Assembl
Mounting
The Slaved Zone Damper Assembly should be mounted according to standard duct installation practices with air flow direction as shown in the illustration above. After installation of the Air Damper in the ductwork, insulation should be applied around any remaining un-insulated surface on the air valve inlet and outlet. The Air Damper should be mounted so the control enclosure is positioned to the left or right side of the ductwork with the control enclosure in a vertical plane. Do not mount the Air Damper Assembly with the control enclosure on the top or bottom of the ductwork. Adequate clearance should be maintained between the control panel and any obstruction to allow for removal of the control panel cover and access to the controls.
Technical Data
Actuator: Air Damper Construction:
Supply Power 24 Volt AC Damper Body 20 Ga. Galv. Steel Power Consumption 3.4 VA Maximum Damper Blade Round -18 Ga. Galv. Steel Operating Temperature Operating Humidity 90% RH Non-Condensing Damper Seal EPDM Rubber Gasket Position Feedback (Bypass) 10Kohm, 1 W Potentiometer Leakage < 20 CFM Per Sq. Ft. @ 4” SP
Dimensions:
Air Damper Model “A” “B” “C” Air Damper Model “A” “B” “C” OE513-06 (6”) 23.00 5.88 9.88 OE513-12 (12”) 23.00 11.88 16.43 OE513-08 (8”) 23.00 7.88 12.13 OE513-14 (14”) 23.00 13.88 18.50 OE513-10 (10”) 23.00 9.88 14.31 OE513-16 (16”) 23.00 15.88 20.56
WattMaster reserves the right to change specifications without notice
Three Year Warranty On Electronic Components One Year Warranty On Air Damper
OE523-XX Round Slaved
Zone Damper Assembly
35°F to 125°F
Damper Bearings Stainless Steel
Insulation ½” Foil Faced Fiberglass
Form: Orion-OE523-RdSlaveDmpr-Sub-01F Page 1 of 2
Page 19
OE523-XX Round Slaved Zone
Damper Assembly
Slaved Zone Damper Sizing
Use a load program to determine the peak load for each zone. These calculations will be used in selecting the appropriate Zone and Slaved Zone Damper sizes. Only pressure dependent Zone Dampers may be slaved.
The Orion Systems utilize a typical low pressure duct design. To reduce noise problems, duct pressures should not exceed 1” W.C.
Primary trunk ducts used with Orion systems should not be “undersized”. With larger trunk ducts, it is easier to assure relatively constant pressure to each Zone Damper. Runs should be
air flow requirements. This design should be reserved only for situations when it is not practical to use a single large Zone Air Damper.
It is recommended that the Slaved Zone Damper(s) should be of the same size as the master Zone Damper. This insures that adequate air flow and minimum noise will occur at all damper positions.
Divide the total zone CFM required by the total number of air valves to be used.
Using the maximum acceptable velocity for a branch duct (typically 1000-1500 FPM for minimal noise), go to the Air Damper Selection Data Chart below and find the quantity and size of Air Dampers that will deliver the required CFM
as determined by the load program as short as possible, and the trunk duct system kept as symmetrical as possible to facilitate system balancing. Wherever possible, run the trunk ducts above corridors and locate the master Zone and Slaved Zone Dampers above corridors to reduce the noise in the space and facilitate service of the valves. Trunk ducts should be sized
Note: Compare the Zone and Slaved Zone Damper
sizes selected against the branch duct sizes to determine if the next size up or down will provide acceptable performance without
requiring a transition fitting. for no more than 0.1” W.C. drop per 100 ft. of duct, and a maximum duct velocity of 2000 FPM.
Up to a maximum of two additional Slaved Zone Dampers may be connected together with the main Zone Damper(s) for large zone
Order one OE520-XX Round Pressure Dependent Zone Damper of the size selected previously. Order one or two OE523-XX Round Slaved Zone Dampers as required, of the same size as the Zone Damper just selected. The Round Slaved Zone Dampers will track and maintain the same damper position as the master Zone Damper.
Slaved Damper Selection Data OE523-XX Slaved Zone Damper Assembly
(Pressure Dependent Only)
Zone Air Damper Round Duct Size
(Area Ft
Velocity Through Zone Air Damper
FPM
500
750
1000
1250
1500
1750
2000
2
)
WattMaster reserves the right to change specifications without notice
6”
(0.196)
98
(< 0.01)
147
(0.01)
196
(0.015)
245
(0.025)
294
(0.035)
343
(0.045)
392
(0.065)
8”
(0.349)
10”
(0.545)
12”
(0.785)
Airflow Through Zone Air Damper – CFM
(ΔP
inches W.C. w/ Air Damper Full Open)
S
175
(< 0.01)
262
(0.01)
349
(0.015)
436
(0.02)
523
(0.035)
611
(0.035)
698
(0.043)
273
(< 0.01)
409
(0.01)
545
(0.01)
681
(0.015)
818
(0.022)
954
(0.034)
1090
(0.040)
393
(< 0.01)
589
(< 0.01)
785
(< 0.01)
981
(0.015)
1178
(0.020)
1374
(0.030)
1570
(0.040)
14”
(1.069)
535
(< 0.01)
802
(< 0.01)
1069
(< 0.01)
1336
(0.015)
1604
0.020) 1871
(0.030)
2138
(0.040)
16”
(1.396)
698
(< 0.01)
1047
(< 0.01)
1396
(< 0.01)
1745
(0.015)
2094
(0.020)
2443
(0.025)
2792
(0.030)
Form: Orion-OE523-RdSlaveDmpr-Sub-01F Page 2 of 2
Page 20
OE524-XX-PD Round Pressure
Dependent Zone Damper
Description
The OE524-XX-PD Round Pressure Dependent Zone Damper consists of a Round Air Damper with a control mounting plate on the side of the damper housing. This plate is designed for mounting of the OE742-31-VAVZ and OE742-32-VAVZ VAVZ Pressure Dependent Zone Controller Actuator Packages which are field mounted on the OE524­XX-PD Round Pressure Dependent Zone Damper.
The Round Air Damper is constructed of 20 gauge galvanized steel with a 14 gauge galvanized steel blade. The damper has a full circumference EPDM rubber gasket seal providing a Class 2 leakage rating. The ½” damper shaft rotates in a stainless steel bushing. A slot is cut into the end of the damper shaft for damper position indication.
All Round Dampers are tested for performance in accordance with AMCA 500-D standards.
When selecting Round Dampers for use as a Pressure Dependent Zone Dampers, select from the Zone Damper Airflow Chart and follow the Zone Damper Guidelines on page 2 of this docu­ment.
Mounting
The Pressure Dependent Round Zone Damper assembly should be mounted according to standard duct installa­tion practices with airflow direction as shown in the illustration above. After installation of the Round Zone Damp­er in the ductwork, insulation should be applied around any remaining uninsulated surface on the air valve inlet and outlet. The Round Zone Damper should be mounted so the control enclosure is positioned to the left or right side of the ductwork with the control enclosure in a vertical plane. Do not mount the Round Zone Damper As­sembly with the control enclosure on the top or bottom of the ductwork. Adequate clearance should be main­tained between the control panel and any obstruction to allow for removal of the control panel cover and access to the controls.
Technical Data
OE524-XX-PD Pressure Dependent Round Zone
Damper
Air Damper Construction: Dimensions:
Damper Body 20 Ga. Galv. Steel Damper Blade Round -14 Ga. Galv. Steel OE524-06-PD (6”) 23.00 5.88 9.88 Damper Bushings Stainless Steel OE524-08-PD (8”) 23.00 7.88 12.13 Damper Seal EPDM Rubber Gasket OE524-10-PD (10”) 23.00 9.88 14.31 Leakage < 20 CFM Per Sq. Ft. @ 4” SP OE524-12-PD (12”) 23.00 11.88 16.43 Insulation ½” Foil Faced Fiberglass OE524-14-PD (14”) 23.00 13.88 18.50 OE524-16-PD (16”) 23.00 15.88 20.56
WattMaster reserves the right to change specifications without notice
Form: Orion-OE524-XX-PD-RndPDDmpr-Sub-01A Page 1 of 2
Air Damper Model “A” “B” “C”
One Year Warranty
Page 21
Round Pressure Dependent Zone Damper Sizing
Use a load program to determine the peak load for each zone. These calculations will be used to select Round Pressure Dependent Zone Damper sizes.
The Orion Systems utilize a typical low pres­sure duct design. To reduce noise problems, pressures should not exceed 1” W.C. in the duct.
Primary trunk ducts used with Orion systems should not be “undersized”. This is especially true of “pressure dependent” systems. With larger trunk ducts, it is easier to assure relative­ly constant pressure to each Round Zone Damper. Runs should be as short as possible, and the trunk duct system kept as symmetrical as possible to facilitate system balancing. Wherever possible, run the trunk ducts above corridors and locate the Round Zone Dampers above corridors to reduce the noise in the space and facilitate service of the valves. Trunk ducts should be sized for no more than 0.1” W.C. drop per 100 ft. of duct, and a maximum duct velocity of 2000 FPM.
OE524-XX-PD Round Pressure
Dependent Zone Damper
Using the maximum acceptable velocity for a branch duct (typi­cally 1000-1500 FPM for minimal noise), find the smallest Round Zone Damper that will deliver the required CFM as de­termined by the load program. Locate the branch velocity used in the duct design program in the left hand column of the Round Zone Damper Selection Data table. Move across the table and find the Round Zone Damper, which will provide the acceptable CFM to meet the zone airflow requirements.
Note: Compare the Round Zone Damper size selected
against the duct size to determine if the next size up or down will provide acceptable performance without requiring a transition fitting.
Up to a maximum of two Slaved Round Zone Dampers may be slaved together with the main Round Zone Damper for large zones. This design should be reserved only for situations when it is not practical to use a single Round Zone Damper. See the Round Slaved Zone Damper specification sheet for information regarding application and selection of Round Slaved Zone Dampers.
Round Zone Damper Selection Data
VAV/Zone Damper Round Duct Size
(Area Ft
Velocity Through VAV/Zone Damper
FPM
500
750
1000
1250
1500
1750
2000
2
)
WattMaster reserves the right to change specifications without notice
6”
(0.196)
98
(< 0.01)
147
(0.01)
196
(0.015)
245
(0.025)
294
(0.035)
343
(0.045)
392
(0.065)
OE524-XX-PD Pressure Dependent
8”
(0.349)
10”
(0.545)
12”
(0.785)
Airflow Through VAV/Zone Damper - CFM
(P
inches W.C. w/ Air Damper Full Open)
S
175
(< 0.01)
262
(0.01)
349
(0.015)
436
(0.02)
523
(0.035)
611
(0.035)
698
(0.043)
273
(< 0.01)
409
(0.01)
545
(0.01)
681
(0.015)
818
(0.022)
954
(0.034)
1090
(0.040)
393
(< 0.01)
589
(< 0.01)
785
(< 0.01)
981
(0.015)
1178
(0.020)
1374
(0.030)
1570
(0.040)
Round Zone Damper
14”
(1.069)
535
(< 0.01)
802
(< 0.01)
1069
(< 0.01)
1336
(0.015)
1604
0.020) 1871
(0.030)
2138
(0.040)
16”
(1.396)
698
(< 0.01)
1047
(< 0.01)
1396
(< 0.01)
1745
(0.015)
2094
(0.020)
2443
(0.025)
2792
(0.030)
Form: Orion-OE524-XX-PD-RndPDDmpr-Sub-01A Page 2 of 2
Page 22
OE524-XX-PI Round Pressure
Independent Zone Damper
Description
The OE524 Round Pressure Independent Zone Damper consists of a Round Air Damper with a control mounting plate on the side of the damper housing. This plate is designed for mounting of the OE744-31-VAVZ and OE744-32-VAVZ VAVZ Pressure Independent Zone Controller Actuator Packages which are field mounted on the OE524 Round Pressure Independent Zone Damper. The Round Pressure Independent Zone Damper also has a patented Tri Averaging Flow Sensor in to provide accurate airflow measurement when connected to the flow sensor provided with the Pressure Independent Zone Controller Actuator Packages.
The Round Air Damper is constructed of 20 gauge galvanized steel with a 14 gauge galvanized steel blade. The damper has a full circumference EPDM rubber gasket seal providing a Class 2 leakage rating. The ½” damper shaft rotates in a stainless steel bushing. A slot is cut into the end of the damper shaft for damper position indication.
All Round Dampers are tested for performance in accordance with AMCA 500-D standards.
When selecting Round Dampers for use as a Pressure Independent Zone Dampers, select from the Zone Damper Airflow Chart and follow the Zone Damper Guidelines on page 2 of this document.
® built
Mounting
The Pressure Independent Round Zone Damper assembly should be mounted according to standard duct instal­lation practices with airflow direction as shown in the illustration above. After installation of the Round Zone Damper in the ductwork, insulation should be applied around any remaining uninsulated surface on the air valve inlet and outlet. The Round Zone Damper should be mounted so the control enclosure is positioned to the left or right side of the ductwork with the control enclosure in a vertical plane. Do not mount the Round Zone Damper Assembly with the control enclosure on the top or bottom of the ductwork. Adequate clearance should be main­tained between the control panel and any obstruction to allow for removal of the control panel cover and access to the controls.
Technical Data
Air Damper Construction: Dimensions:
Damper Body 20 Ga. Galv. Steel Damper Blade Round -14 Ga. Galv. Steel OE524-06-PI (6”) 23.00 5.88 9.88 Damper Bushings Stainless Steel OE524-08-PI (8”) 23.00 7.88 12.13 Damper Seal EPDM Rubber Gasket OE524-10-PI (10”) 23.00 9.88 14.31
Leakage < 20 CFM Per Sq. Ft. @ 4” SP OE524-12-PI (12”) 23.00 11.88 16.43 Insulation ½” Foil Faced Fiberglass OE524-14-PI (14”) 23.00 13.88 18.50 OE524-16-PI (16”) 23.00 15.88 20.56
WattMaster reserves the right to change specifications without notice
OE524-XX-PI Pressure Independent Round Zone
Damper
Air Damper Model “A” “B” “C”
One Year Warranty
Form: Orion-OE524-XX-PI-RndPIDmpr-Sub-01A Page 1 of 2
Page 23
Round Pressure Independent Zone Damper Sizing
Use a load program to determine the peak load for each zone. These calculations will be used in selecting the appropriate zone damper sizes.
The Orion Systems utilize a typical low pres­sure duct design. To reduce noise problems, pressures should not exceed 1” W.C. in the duct.
Primary trunk ducts used with Orion systems should not be “undersized”. This is especially true of “pressure dependent” systems. With pressure independent systems this is not as critical. With larger trunk ducts, it is easier to assure relatively constant pressure to each Round Zone Damper. Runs should be as short as possible, and the trunk duct system kept as symmetrical as possible to facilitate system balancing. Wherever possible, run the trunk ducts above corridors and locate the Round Zone Dampers above corridors to reduce the noise in the space and facilitate service of the valves. Trunk ducts should be sized for no more than 0.1” W.C. drop per 100 ft. of duct, and a maximum duct velocity of 2000 FPM.
OE524-XX-PI Round Pressure
Independent Zone Damper
With pressure independent systems it is possible to exceed this rule by up to 50%. However it is advised that unless you are experienced with VAV duct design the 2000 FPM rule should be used. Using the maximum acceptable velocity for a branch duct (typically 1000-1500 FPM for minimal noise), find the smallest damper that will deliver the required CFM as deter­mined by the load program.
Locate the branch velocity used in the duct design program in the left hand column of the Round Zone Damper Selection Data table. Move across the table and find the damper, which will provide the acceptable CFM to meet the zone airflow require­ments.
Note: Compare the Round Zone Damper size selected
against the duct size to determine if the next size up or down will provide acceptable performance without requiring a transition fitting.
Pressure Independent Round Zone Dampers may not be slaved together with Round Slaved Zone Damper Assemblies. If more than one damper is required for a zone, all dampers must be selected as pressure dependent. See the Round Pres­sure Dependent Zone Damper submittal sheet and Round Slaved Zone Damper submittal sheets for selection of mas­ter/slave damper configurations.
Round Zone Damper Selection Data
VAV/Zone Damper Round Duct Size
(Area Ft
CFM @ 1” Velocity Pressure (Air Flow Probe “K” Factor)
Velocity Through VAV/Zone Damper
FPM
500
750
1000
1250
1500
1750
2000
2
)
WattMaster reserves the right to change specifications without notice
6”
(0.196)
448 904 1436 1891 3015 3839
98
(< 0.01)
147
(0.01)
196
(0.015)
245
(0.025)
294
(0.035)
343
(0.045)
392
(0.065)
OE524-XX-PI Pressure Independent
8”
(0.349)
10”
(0.545)
12”
(0.785)
Airflow Through VAV/Zone Damper - CFM
(P
inches W.C. w/ Air Damper Full Open)
S
175
(< 0.01)
262
(0.01)
349
(0.015)
436
(0.02)
523
(0.035)
611
(0.035)
698
(0.043)
273
(< 0.01)
409
(0.01)
545
(0.01)
681
(0.015)
818
(0.022)
954
(0.034)
1090
(0.040)
393
(< 0.01)
589
(< 0.01)
785
(< 0.01)
981
(0.015)
1178
(0.020)
1374
(0.030)
1570
(0.040)
Round Zone Damper
14”
(1.069)
535
(< 0.01)
802
(< 0.01)
1069
(< 0.01)
1336
(0.015)
1604
0.020) 1871
(0.030)
2138
(0.040)
16”
(1.396)
698
(< 0.01)
1047
(< 0.01)
1396
(< 0.01)
1745
(0.015)
2094
(0.020)
2443
(0.025)
2792
(0.030)
Form: Orion-OE524-XX-PI-RndPIDmpr-Sub-01A Page 2 of 2
Page 24
Description
r
The OE519 Rectangular Damper is used in applications where rectangular duct is specified or required because of space limitations or job requirem ents. The Rec­tangular Damper utilizes opposed blades of airfoil design for im proved air flow con­trol. The Rectangular Damper frame is made of .080 thick extruded aluminum. The blades are also made of extruded aluminum. Blade pins are 7/16” hexagon shaped aluminum f ixed to a Celcon inner bearing rotating within a polycarbonate outer bearing inserted in the damper frame. The Damper linkage is mechani­cally assembled and located in the damper frame. The linkage components are constructed of aluminum, zinc and nickel plated steel. Blade gaskets are made of extruded EPDM mater ial and are secured within an integral slot on the blade. Jamb seals are of extruded TPE material for low leakage through the damper when closed. The control shaf t is 1/2” diameter hexagon shaped rod and can be extended 9” past the damper frame for connection to the damper ac­tuator. The damper shaft is shipped re­tracted into the frame area and must be adjusted to the required length in the field.
OE519 - Rectangular Dampe
Opposed Blade Profile
Flanged to Duct
Installation
Mounting
The Rectangular Damper should be mounted in the ductwork accor ding to standard duct ins tallation practic es. T he rect angular dam per should be se­lected for the nominal inside duc t size. All Rectangular Dampers are supplied with 1” flanges all around damper frame, mak ing the overall damper width and height 2” larger than the nominal inside duct size thus providing for external flange mounting to ductwork . The damper s haft is shipped retracted into the damper f rame. Loosen the two nuts on the U-bolt that secures the damper shaf t to the damper blade and adjust to length. It is recommended that the shaft length be adjusted so approximately 4” of shaf t extends beyond the inside of the damper frame. Retighten the two nuts on the U-bolt that secures the damper shaft to the blade. After installation of the Rectan­gular Damper to the ductwork, it is recom mended that insulation be applied ar ound any non-insulated surface on the ductwork where the Rectangular Damper was installed.
Dimensional Data
Damper Sizing
Use a load program to determ ine the peak load for each zone. These calculations will be used in selecting the appropriate Rectangular Damper sizes. The Or ion Systems utilize a typical low pressure duct design. To reduce noise problems, duct pressures should not exceed 1” W.C.
Primary trunk ducts used with Orion s ystems should not be “undersized”. This is especially true of “ pressure de­pendent” systems. With pressure independent systems this is not as c r itic al. With larger trunk duc ts , it is eas ier to assure relatively constant pressure to each Rectangular Damper. Runs should be as short as possible, and the trunk duct system kept as symmetrical as possible to facilitate system balancing. Wherever possible, run the trunk ducts above corridors and locate the Rectangular Dampers above corridors to reduc e the nois e in the space and facilitate service of the valves. T runk ducts should be sized for no m ore than 0.1” W .C. drop per 100 f t. of duct, and a maximum duct velocity of 2000 FPM.
Form: ORION-OE519-RectDmpr-Sub-01B.doc Page 1 of 2
Page 25
within the ceiling area where the damper will be located. Many
OE519 - Rectangular Dampe
r
Using the maximum acceptable velocity for a branch duct (typically 1000-1500 FPM for minimal noise), find the smallest damper that will deliver the required CFM as determined by the load program.
This is the recom mended velocity for quiet operation and nor­mal pressure drop through the damper. When space consid­erations or design criteria dictate, dampers m ay be selected for other face velocities by using the multipliers listed in the notes associated with the table. Move across the table and find the
damper selection, which will provide the r equired CFM and fit Locate the required CFM on the Rectangular Damper Selection Data table below. This table is based on an airflow velocity of 1000 FPM
size selections are possible for a given CFM. Pressure drop
across the damper is shown in parenthesis below the CFM. across the damper.
Rectangular Damper Selection Data
Damper
Height
“B”
Damper
Width
“A”
8” 410
10” 510
12” 560
14” 660
16” 750
18” 770
20” 850
22” 930
24” 950
26” 990
28” 1070
30” 1020
32” 1090
34” 1150
36” 1060
Notes:
1. The table above is calculated based on 1000 FPM velocity across the full open damper. For other velocities use the
following multipliers to obtain the correct CFM: 500 FPM = 0.5, 1500 FPM = 1.5, 2000 FPM = 2.0. It is recommended the damper velocity does not exceed 1500 FPM for quiet operation.
2. Pressure drop (∆P
8” 10” 12” 14” 16” 18” 20” 22” 24” 26” 28” 30” 32” 34” 36”
Airflow Data with Full Open Damper
CFM @ 1000 FPM Velocity
- inches W.C. @ 1000 FPM Velocity)
(P
S
(0.16)
(0.10)
(0.07)
(0.05)
(0.04)
(0.03)
(0.03)
(0.02)
(0.02)
(0.02)
(0.01)
(0.01)
(0.01)
(0.01)
(0.01)
530
(0.10)
590
(0.07)
650
(0.05)
770
(0.03)
890
(0.03)
980
(0.03)
1090
(0.02)
1210
(0.01)
1290
(0.01)
1390
(0.01)
1500
(0.01)
1550
(0.01)
1660
(0.01)
1770
(0.01)
1790
(0.01)
640
(0.07)
690
(0.05)
730
(0.03)
880
(0.02)
1030
(0.02)
1180
(0.01)
1330
(0.01)
1480
(0.01)
1630
(0.01)
1780
(0.01)
1930
(0.01)
2080
(0.01)
2230
2380
2520
) is based on 1000 FPM Velocity. Any pressure drop less than 0.01” W.C. is shown as (-).
S
740
(0.05)
800
(0.03)
850
(0.02)
1030
(0.02)
1200
(0.01)
1380
(0.01)
1550
(0.01)
1730
(0.01)
1900
(0.01)
2080
(0.01)
2250
2430
2600
(-)
2780
(-)
2670
(-)
WattMaster reserves the right to change speci f ications without notice
850
(0.04)
910
(0.03)
970
(0.02)
1180
(0.01)
1370
(0.01)
1580
(0.01)
1770
(0.01)
1980
(0.01)
2170
2380
2570
(-)
2780
(-)
2970
(-)
3180
(-)
3090
(-)
970
1080
(0.03)
1030
(0.02)
1090
(0.01)
1330
(0.01)
1540
(0.01)
1780
(0.01)
1990
(0.01)
2230
2440
(-)
2680
(-)
2890
(-)
3130
(-)
3340
(-)
3580
(-)
3510
(-)
(0.03)
1150
(0.02)
1210
(0.01)
1480
(0.01)
1710
(0.01)
1980
(0.01)
2210
2480
(-)
2710
(-)
2980
(-)
3210
(-)
3480
(-)
3710
(-)
3980
(-)
3930
(-)
1190
(0.02)
1260
(0.01)
1330
(0.01)
1630
(0.01)
1880
(0.01)
2180
2430
(-)
2730
(-)
2980
(-)
3280
(-)
3530
(-)
3830
(-)
4080
(-)
4370
(-)
4350
(-)
1300
(0.02)
1380
(0.01)
1460
(0.01)
1760
(0.01)
2060
2350
(-)
2650
(-)
2950
(-)
3250
(-)
3550
(-)
3850
(-)
4150
(-)
4450
(-)
4750
(-)
5040
(-)
1410
(0.02)
1500
(0.01)
1580
(0.01)
1910
(0.01)
2230
(-)
(-)
(-)
(-)
(-)
(-)
(-)
(-)
(-)
(-)
(-)
(-)
2550
(-)
2870
(-)
3200
(-)
3520
(-)
3850
(-)
4170
(-)
4500
(-)
4820
(-)
NA NA NA NA NA NA
NA NA NA NA NA NA
1520
1630
1740
(0.01)
(0.01)
(0.01)
(0.02)
1610
(0.01)
1700
(0.01)
2060
(-)
2400
(-)
2750
(-)
3090
(-)
3450
(-)
3790
(-)
4150
(-)
4500
(-)
4850
(-)
NA NA NA NA NA
(0.01)
1730
1840
(0.01)
1820
1940
(-)
2210
2360
(-)
2570
(-)
2950
(-)
3310
(-)
3700
(-)
4060
(-)
4450
(-)
4820
(-)
NA NA NA NA
(-)
2740
(-)
3150
(-)
3530
(-)
3950
(-)
4330
(-)
4750
(-)
NA NA NA
1850
(0.01)
2000
(0.01)
2060
(-)
2510
(-)
2910
(-)
3350
(-)
3750
(-)
4200
(-)
4600
(-)
NA NA
1970
(0.01)
2080
(0.01)
2190
(-)
2640
(-)
3090
(-)
3540
(-)
3990
(-)
4440
(-)
4880
(-)
Form: ORION-OE519-RectDmpr-Sub-01B.doc Page 2 of 2
Page 26
P.D. Rectangular Damper Kit
OE736-02
Description
The OE736-02-VAVZ P.D. Rectangular Damper Kit provides a new solution for rectangular zone damper applications. The Rectangular Damper Kit is used in conjunction with rectangular dampers for applications where rectangular dampers are specified or required because of space limitations or job requirements. The rectangular dampers may be purchased from WattMaster or you may get them from the supplier of your choice. For proper control, WattMaster recommends the use of low leakage opposed blade dampers. The maximum allowable damper face area for the Rectangular Damper Kit is 6 sq. ft. The Rectangular Damper Kit comes packaged with the OE742-32-VAVZ VAV/Zone Controller Actuator Package and a
BK000080-00 stand-off mounting bracket. Each kit
is supplied with mounting hardware and installation instructions.
Mounting
Before mounting the Rectangular Damper Kit, the rectangular damper should be mounted in the ductwork according to standard duct installation practices. The damper should be mounted so the damper shaft turns in a clockwise direction to open the damper. The Rectangular Damper Kit is simply slid over the damper shaft, the actuator shaft collar setscrews tightened and the supplied self-tapping screws are used to mount the stand-off mounting bracket to the ductwork. The standoff mounting bracket connects to the VAV/Zone Controller Actuator Package by securing it with the supplied screw through its anti-rotation bushing. Detailed mounting and installation instructions are provided with each kit. An optional plastic conduit cover (EE000101)is available for applications requiring conduit.
Technical Data OE736-02 P.D. Rectangular Damper Kit
VAV/Zone Controller Actuator Package: Outputs:
Supply Power 24 VAC (1) RJ-45 Cable Connection For Auxiliary Relay Board Power Consumption 6 VA Maximum (1) RJ-45 Cable Connection To Damper Actuator Operating
Temperature Operating Humidity 90% RH Non-Condensing
Communications RS-485 – 9600 Baud Programming Port Mini-DIN Jr. Port
Inputs:
(1) RJ-45 Cable Connection For Digital Temperature Or Analog Temperature
(2) Auxiliary Terminals For Duct Temperature Sensor Labeling Right Hand & Left Hand (1) Terminal Block Connector For Power In Mounting Standoff Galvanized Steel (1) Terminal Block Connector For Comm In Conduit Conn. Available Option
WattMaster reserves the right to change specifications without notice.
10F to 149F
Uses Same 3 Conductor Terminal Block as Comm Input
Features:
Enclosure Material
Zone Controller Factory Mounted Inside The Enclosure Zone Actuator Factory Mounted To The Enclosure Actuator Rating 45 in/lbs (6 ft2 Damper Area Max.)
Three Year Warranty
Fire Rated ABS Plastic
Form: Orion--OE736-02-Rect-PDZoneDmpr-Sub-01C.doc Page 1 of 1
Page 27
OE737 - Bypass Rectangular
Damper Kit
Description
The OE737 Rectangular Bypass Damper Kit mounts to an OE519 Rectangular Damper and controls duct static pressure to insure proper system airflow. The Rectangular By­pass Damper is controlled by the Orion HVAC Unit Controller. The Unit Controller modulates the Rectangular Bypass Damper in response to the duct static pres sure based on a signal received from a static pressure sensor located in the main system ductwork.
The Rectangular Bypass Damper Kit is us ed in conjunction with rectangular dampers for applications where rectangular dampers are specified or required because of space limi­tations or job requirements . The rectangular dampers may be purchased from WattMas­ter or you may get them from the supplier of your choice. For proper control, W attMaster recommends the use of low leakage op­posed blade dampers. The m aximum allow­able damper face area for the Rectangular Bypass Damper Kit is 6 sq. ft. The Rectan­gular Bypass Damper Kit comes packaged with the Damper Actuator and W iring Interfac e pre-mounted in a galvanized steel enclos ure. Each kit is supplied with mounting hardware and installation instructions. For applications where CFM or space requir ements dictate the use of more than a single bypass damper, up to 2 additional bypass dampers can be slaved together. No other components are required. Each bypass is wired to the other bypass damper(s ) by means of the W iring In­terface.
Mounting
Before mounting the Rectangular Dam per Kit, the rectangular damper should be mounted in the ductwork ac­cording to standard duct installation practic es. The damper should be mounted so the dam per shaft turns in a clockwise direction to open the damper. T he Rectangular Damper Kit is simply slid over the damper shaf t, the actuator shaft collar setsc rews tightened and the supplied s elf tapping s crews are us ed to m ount the enc losure to the ductwork. Detailed mounting and installation ins tructions are pr ovided with each kit. A k nockout is provided in the front access cover, which can be punched out to allow for dam per shaf t lengths, which extend past the enc lo­sure depth. When mounting the Rectangular Dam per Kit, be sure to allow clearance for removal of the access cover. Conduit knockouts are provided in the top and bottom of the enclosure for simplified wiring.
Technical Data
Supply Power 24 Volt AC Enclosure Base 22 Ga. Galv. Steel Power Consumption 3.0 VA Maximum Enclosure Cover 22 Ga. Galv. Steel Operating Temp Operating Humidity 90% RH Non-Condensing Bottom - (2) ½ & ¾” Comb. Knockouts Actuator Feedback 10Kohm, 1W Potentiometer Shaft Clearance Front - (1) ½ & ¾” Comb. Knockout Actuator Rating 35 in/lbs (6 ft2 Damper Area Max.) Controls Factory Mounted Inside Enclosure Mounting Hardware (4) Self Tapping Screws Controls Access Cover is Removable by Instructions Included with Each Kit Loosening 2 Screws
WattMaster reserves the right to change specifications without notice
Three Year Warranty
-22°F to 122°F
Conduit Openings Top - (2) ½ & ¾” Comb. Knockouts
OE737 Rectangular Bypass Damper Kit
Form: Orion-OE737-RectBypKit-Sub-01B Page 1 of 1
Page 28
Description
The OE738 Rectangular Slaved-VAV/Zone Damper Kit provides a new solution for rectan­gular damper applications. The OE738 Rec tan­gular Slaved-VAV/Zone Damper Kit is used in conjunction with rectangular dampers for appli­cations in systems when it is not possible or practical to use a single large Rectangular VAV/Zone Air Damper to satisfy the zones CFM requirements.
OE738 - Slaved-VAV/Zone
Rectangular Damper Kit
The rectangular dampers may be purchased from W attMaster or you may get them f rom the supplier of your choice. For proper airf low con­trol, WattMaster recommends the use of low
Component View
5.75
13.5
leakage opposed blade dampers. The Rectan­gular Slaved-VAV/Zone Damper Kit is supplied with the slave wiring interface card and actuator
8.0
factory mounted in a sheet metal enclosure. A total of two Slaved-VAV/Zone Air Dampers may
12.15
be used in conjunction with a master Rectan­gular VAV/Zone Damper Kit. The Rectangular Slaved-VAV/Zone Air Damper(s) are wired in
Dimensional Data
parallel with the master Rectangular VAV/Zone Damper Kit and track the movement of the master Rectangular VAV/Zone Damper. Connection to the m aster Rectangular VAV/Zone Dam per Kit requires a Slave Wiring Adapter Kit, par t # OE267 which is supplied with each Rectangular Slaved-VAV/Zone Damper Kit. The kit connects the zone controller on the m aster to the m aster actuator and provides wiring term inals for wiring to the Rectangular Slaved-VAV/Zone Damper Kit(s). Only one Slaved Wiring Kit is required for each Slaved­VAV/Zone system. Each kit is supplied with mounting hardware and installation instructions.
Mounting
The rectangular damper should be mounted in the ductwork according to standard duct installation practices be­fore installing the Rectangular Slaved-VAV/Zone Damper Kit. The Rectangular Slaved-VAV/Zone Damper Kit is simply slid over the damper shaft, the actuator shaft collar setscrews tightened and the supplied self tapping screws are used to mount the enclosure to the ductwork. Detailed mounting and installation instructions are pro­vided with each kit. A knockout is provided in the front access cover, which can be punched out for damper shaft lengths which extend past the enclosure depth. When mounting the Rectangular Slaved-VAV/Zone Damper Kit, be sure to allow clearance for removal of the access cover. Conduit knockouts are provided in the top and bottom of the enclosure for simplified wiring installation.
Technical Data
OE 738 Rectangular Slaved-Zone Damper Kit
Actuator: OE 738 Damper Kit Features:
Supply Power 24 Volt AC Enclosure Base 22 Ga. Galv. Steel Power Consumption 3.4 VA Maximum Enclosure Cover 22 Ga. Galv. Steel Operating Temperature Operating Humidity 90% RH Non-Condensing Bottom - (2) ½ & ¾” Comb. Knockouts
10°F to 149°F
Inputs:
Actuator Position Feedback Mounting Hardware Supplied with (4) Self Tapping Screws
WattMaster reserves the right to change specifications without notice
Three Year Warranty
Form: Orion-OE738-RectSlvZoneKit-SUB-01B Page 1 of 1
Conduit Openings Top - (2) ½ & ¾” Comb. Knockouts
Shaft Clearance Front - (1) ½ & ¾” Comb. Knockout Controls Factory Mounted inside the Enclosure
Instructions Included with Each Kit Controls Access Cover is Removable by
Loosening 2 Screws
Actuator Rating 35 in/lbs (6 ft2 Damper Area Max.)
Page 29
Description
The OE281-04 Proportional Control Damper Actuator is a shaft mounted, di­rect coupled actuator. The Damper Ac­tuators utilize a 24VAC/24VDC power supply. Wiring connection to the actua­tor is by means of screw wiring termi­nals located on the actuator cover. The actuator is rated for 35 in-lb of torque. All actuators are electronically protect­ed against overload. The angle of rota­tion is mechanically limited to 95. When the end position of the actuator or damper is reached, the actuator au­tomatically stops. For adjustment pur­poses, the gears can be manually dis­engaged by pushing the manual over­ride button on the actuator cover. A vis­ual pointer on the actuator indicates the position of the actuator.
OE281-04 – Proportional Control
Damper Actuator
Applications
The OE281-04 Damper Actuator is used to provide control of bypass air dampers in an Orion zoning system. When used in zoning applications with a bypass damper, it is wired to the air handling unit controller boards 0­10VDC analog output.
Technical Data OE281-04
Damper Actuator
Power Supply Life Cycle Rating 2.5 Million Cycles with Mechanical Stops Power Consumption 3 VA Maximum Power Connection (4) Screw Wiring Terminals for
Operating Temp Operating Humidity 5 to 95% RH Non-Condensing Quality Standard ISO 9001 Overload Protection
Operating Range 2 to 10 VDC Torque Minimum 35 in-lb Running Time 80-110 Seconds. Weight 1.2 lb.
Three Year Warranty WattMaster reserves the right to change specifications without notice
24VAC 20% 50/60HZ
-22F to 122F
Electronic Throughout 0 to 95 Rotation
Angle of Rotation
Servicing Maintenance Free
Agency Listings UL873 listed
Max. 95, Adjustable
26 to 14 Gauge Wire
CSA 4813 02 Certified
Form: ORION-OE281-04-ProportionalDamper Actuator-1D.doc Page 1 of 1
Page 30
Description
The OE282-03 Slaved VAV/Zone Damper Kit consists of an OE282
Slaved VAV/Zone Damper Kit
OE282-03
Damper Actuator, (2) PL101824 Slave Wiring Interface Boards and (2) 18” Long Modular Cables. The OE282 Actuator is a shaft mounted, floating point control actuator. The actuator is a 24VAC/24VDC model with a 10K ohm feedback signal for position monitoring. Wiring connection to the actuator is by means of a modular phone cable connector located on the actuator cover. The actuator is rated for 45 in­lb. of torque. All actuators are electronically protected against overload. The angle of rotation is mechanically limited to 95. When the end position of the actuator or damper is reached, the actuator automatically stops. For adjustment purposes, the gears can be manually disengaged by pushing the manual override button on the actuator cover.
Applications
The OE282-03 Slaved VAV/Zone Damper Kit allows multiple dampers (up to 2 total besides the master) to be connected to a master OE742-31-VAVZ or OE742-32-VAVZ P.D. VAV/Zone Controller Actuator Package. The OE282-03 Kit is typically used when larger CFM requirements dictate multiple dampers are used. One of the Interface Boards connects to the master VAV/Zone Controller via a modular cable. The other Interface Board connects to the Slave Damper Actuator. Three conductor wiring is then routed and connected between the two Interface Boards. For zones requiring more than one Slave Damper Kit a second one can be purchased and installed in the same manner.
Technical Data OE282-03 Slaved VAV/Zone Damper Kit
Actuator Power Supply
Actuator Life Cycle Rating
Actuator Power Consumption
Operating Temp Operating Humidity 5 to 95% RH Non-
Actuator Overload Protection
Actuator Feedback Signal
Actuator Running Time
PL1018224 Board (2) RJ-11 Modular Jacks PL1018224 Board (2) Wiring Terminal Blocks
Three Year Warranty
24VAC 20% 50/60HZ
2.5 Million Cycles with Mechanical Stops
3 VA Maximum Power Connections RJ-11 Modular Jack
-22F to 122F
Condensing
Electronic Throughout 0
to 95 Rotation
10K ohm 1W
Potentiometer
80-110 Seconds. Approx. Kit Weight 2.2 lb.
Actuator Angle of Rotation
Servicing Maintenance Free Actuator Quality Standard ISO 9001
Actuator Agency Listings UL873 listed
Actuator Torque Minimum 45 in-lb.
WattMaster reserves the right to change specifications without notice
Max. 95, Adjustable
CSA 4813 02 Certified
Form: Orion-OE282-03-SlvZoneDmprKit-Sub-01A.doc Page 1 of 1
Page 31
VAV/Zone Cable Length Worksheet
Project Name:
Directions: Estimate cable lengths from building mechanical plans and place in estimated cable length column beside each VAV/Zone controller or
Power/Comm board on loop. Select available cable lengths closest to estimated cable lengths and extensions for each controller or Power/Comm board on list and place checkmarks in these columns. Also Use this information for ordering correct quantity and length of modular or digital cables and extensions. Total each cable length column on each page and add both page totals together.
VAV/Zone
Address
N/A N/A N/A N/A
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 21 22 23 24 25 26 27 28
Page
Totals
Notes:
1.) Available Power/Comm cable lengths with the prefix “E” (E-10 Ft. or E-20 Ft.) are extensions to be used in conjunction with another standard Power/Comm cable length to extend it to a desired length, they cannot be used by themselves without connection to a standard cable.
2.) Available Modular Sensor cable lengths are provided in 5 Ft, 10 Ft., 25 Ft., 40 Ft. and 80 Ft. Lengths. To get longer lengths you can join 2 Modular cables together using the MS000029 Modular Room Sensor Cable Coupler to extend the cables to a desired length in between or greater than the standard cable sizes. Available Digital Sensor cable lengths are provided in 5 Ft., 10 Ft., 25 Ft., 40 Ft., 80 Ft., 120 Ft. and 160 Ft. sizes. You can join 2 Modular cables together using the MS000029 Modular Room Sensor Cable Coupler to extend the cables to a desired length in between the available sizes. It is recommended that you avoid this when using the Digital Sensor cable. The maximum allowable total cable length for Digital Sensor cables is 160 Ft. and should never be exceeded.
_____________________________________________
VAV/Zone Controller Or
Power/Comm Board
Description, Location Or
Tag Number
Power Comm Board 1 Power Comm Board 2 Power Comm Board 3 Power Comm Board 4
Estimated
Incoming
Power/Comm
Cable
Length
3 Ft.
Available Power/Comm Cable Length
25 Ft.
40 Ft.
Local Loop Number:
80 Ft.
120 Ft.
E-10 Ft.
E-20 Ft.
Estimated
Incoming
Modular Or
Digital Room
Sensor Cable
Length
Caution:
Each Power/Comm board has a total of 4 branch circuits. No more than 6 modular devices are allowed per branch circuit. No more than 16 modular devices total can be connected to each Power/Comm board. The longest total run per branch circuit is 240 Feet.
______________________
Modular Or Digital Room
5 Ft.
Available
Sensor Cable Length
See Notes Below
10 Ft.
25 Ft.
40 Ft.
80 Ft.
120 Ft.
160 Ft.
Form: Orion-VAVZoneCableEst-All-1A.doc Page 1 of 2
Page 32
VAV/Zone Cable Length Worksheet
Project Name:
Directions: Estimate cable lengths from building mechanical plans and place in estimated cable length column beside each VAV/Zone controller or
Power/Comm board on loop. Select available cable lengths closest to estimated cable lengths and extensions for each controller or Power/Comm board on list and place checkmarks in these columns. Also Use this information for ordering correct quantity and length of modular or digital cables and extensions. Total each cable length column on each page and add both page totals together.
VAV/Zone
Address
29 30
31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58
Page
Totals
Totals For
Both
Pages
Notes:
1.) Available Power/Comm cable lengths with the prefix “E” (E-10 Ft. or E-20 Ft.) are extensions to be used in conjunction with another standard Power/Comm cable length to extend it to a desired length, they cannot be used by themselves without connection to a standard cable.
2.) Available Modular Sensor cable lengths are provided in 5 Ft, 10 Ft., 25 Ft., 40 Ft. and 80 Ft. Lengths. To get longer lengths you can join 2 Modular cables together using the MS000029 Modular Room Sensor Cable Coupler to extend the cables to a desired length in between or greater than the standard cable sizes. Available Digital Sensor cable lengths are provided in 5 Ft., 10 Ft., 25 Ft., 40 Ft., 80 Ft., 120 Ft. and 160 Ft. sizes. You can join 2 Modular cables together using the MS000029 Modular Room Sensor Cable Coupler to extend the cables to a desired length in between the available sizes. It is recommended that you avoid this when using the Digital Sensor cable. The maximum allowable total cable length for Digital Sensor cables is 160 Ft. and should never be exceeded.
_____________________________________________
VAV/Zone Controller
Or Power/Comm Board
Description, Location
Or Tag Number
Estimated
Incoming
Power/Comm
Cable
Length
3 Ft.
25 Ft.
Available Power/Comm Cable Length
40 Ft.
Local Loop Number:
80 Ft.
120 Ft.
E-10 Ft.
Estimated
Incoming
Modular Or
Digital Room
Sensor Cable
Length
E-20 Ft.
______________________
Modular Or Digital Room
5 Ft.
Available
Sensor Cable Length
See Notes Below
10 Ft.
25 Ft.
40 Ft.
80 Ft.
120 Ft.
160 Ft.
Form: Orion-VAVZoneCableEst-All-1A.doc Page 2 of 2
Page 33
VAV/Zone Worksheet
Project Name:
_____________________________________________
Local Loop Number:
______
Total Qty. Of VAV/Zone Controllers on Loop:
_________
MiniLink PD Address For This Loop:
VAV/Zone
Address
1
2
3
4
5
6
7
8
NF = Non Fan Terminal] [SF = Series Flow Fan Terminal] [PF = Parallel Flow Fan Terminal] [EL-STGD = Electric Heat - Staged] [EL-SCR = Electric Heat - SCR Controller] [HW-ON-OFF = Hot water Heat - On/Off Control] [HW-MOD = Hot Water - Modulating Control]
VAV/Zone Controller
Description,
Location Or
Tag
Number
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
Estimated Power/Comm Cable Length
From
Power/Comm
Board To
Controller
(If Required)
__________
Selected Power/Comm
Cable Length From
Power/Comm Board To
Controller
(If Required)
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
Total Number Of Power/Comm Boards On Loop:
Estimated Power/Comm Cable Length
To Next
Controller
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
Selected Power/Com
Cable Length
To Next Controller
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
_________
Note: See End Of VAV/Zone Controller Address List For Power/Comm Board Cable Selection.
Selected
Room
Sensor Modular
Cable Length
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
120 Ft.
120 Ft.
120 Ft.
120 Ft.
120 Ft.
120 Ft.
120 Ft.
120 Ft.
Type
Of
Terminal
Unit
NF SF PF
NF SF PF
NF SF PF
NF SF PF
NF SF PF
NF SF PF
NF SF PF
NF SF PF
Type Of Heat
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
Form: ORION-VAVZoneWorksheet1B.doc Page 1 of 8
Page 34
VAV/Zone Worksheet
Project Name:
_____________________________________________
Local Loop Number:
______
Total Qty. Of VAV/Zone Controllers on Loop:
_________
MiniLink PD Address For This Loop:
__________
Total Number Of Power/Comm Boards On Loop:
_________
VAV/Zone
Address
9
10
11
12
13
14
15
16
NF = Non Fan Terminal] [SF = Series Flow Fan Terminal] [PF = Parallel Flow Fan Terminal] [EL-STGD = Electric Heat - Staged] [EL-SCR = Electric Heat - SCR Controller] [HW-ON-OFF = Hot water Heat - On/Off Control] [HW-MOD = Hot Water - Modulating Control]
VAV/Zone
Controller Description, Location Or
Tag
Number
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
Estimated
Power/Com
m Cable
Length From
Power/Com
m Board To
Controller
(If Required)
Selected Power/Comm
Cable Length From
Power/Comm Board To
Controller
(If Required)
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
Estimated Power/Comm Cable Length
To Next
Controller
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
Selected Power/Com
Cable Length
To Next Controller
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
Note: See End Of VAV/Zone Controller Address List For Power/Comm Board Cable Selection.
Selected
Room
Sensor Modular
or Digital Cable
Length
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
120 Ft.
120 Ft.
120 Ft.
120 Ft.
120 Ft.
120 Ft.
120 Ft.
120 Ft.
Type
Of
Terminal
Unit
NF SF PF
NF SF PF
NF SF PF
NF SF PF
NF SF PF
NF SF PF
NF SF PF
NF SF PF
Type Of Heat
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
Form: ORION-VAVZoneWorksheet1B.doc Page 2 of 8
Page 35
VAV/Zone Worksheet
Project Name:
_____________________________________________
Local Loop Number:
______
Total Qty. Of VAV/Zone Controllers on Loop:
_________
MiniLink PD Address For This Loop:
VAV/Zone
Address
17
18
19
20
21
22
23
24
NF = Non Fan Terminal] [SF = Series Flow Fan Terminal] [PF = Parallel Flow Fan Terminal] [EL-STGD = Electric Heat - Staged] [EL-SCR = Electric Heat - SCR Controller] [HW-ON-OFF = Hot water Heat - On/Off Control] [HW-MOD = Hot Water - Modulating Control]
VAV/Zone
Controller Description, Location Or
Tag
Number
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
Estimated Power/Comm Cable Length
From
Power/Comm
Board To
Controller
(If Required)
__________
Selected Power/Comm
Cable Length From
Power/Comm Board To
Controller
(If Required)
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
Total Number Of Power/Comm Boards On Loop:
Estimated
Power/Comm
Cable Length
To Next
Controller
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
Selected Power/Com
Cable Length
To Next Controller
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
_________
Note: See End Of VAV/Zone Controller Address List For Power/Comm Board Cable Selection.
Selected
Room
Sensor Modular
or Digital Cable
Length
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
120 Ft.
120 Ft.
120 Ft.
120 Ft.
120 Ft.
120 Ft.
120 Ft.
120 Ft.
Type
Of
Terminal
Unit
NF SF PF
NF SF PF
NF SF PF
NF SF PF
NF SF PF
NF SF PF
NF SF PF
NF SF PF
Type Of Heat
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
Form: ORION-VAVZoneWorksheet1B.doc Page 3 of 8
Page 36
VAV/Zone Worksheet
Project Name:
_____________________________________________
Local Loop Number:
______
Total Qty. Of VAV/Zone Controllers on Loop:
_________
Note: See End Of VAV/Zone Controller Address List For Power/Comm Board Cable Selection.
Selected
Room Sensor Modular or Digital Cable
Length
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
120 Ft.
120 Ft.
120 Ft.
120 Ft.
120 Ft.
120 Ft.
120 Ft.
120 Ft.
Type
Of
Terminal
Unit
NF SF PF
NF SF PF
NF SF PF
NF SF PF
NF SF PF
NF SF PF
NF SF PF
NF SF PF
Type Of Heat
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
From
__________
Selected Power/Comm
Cable Length From
Power/Comm Board To
Controller
(If Required)
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
Total Number Of Power/Comm Boards On Loop:
Estimated Power/Comm Cable Length
To Next
Controller
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
Selected Power/Com
Cable Length
To Next Controller
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
MiniLink PD Address For This Loop:
VAV/Zone
Address
25
26
27
28
29
30
31
32
NF = Non Fan Terminal] [SF = Series Flow Fan Terminal] [PF = Parallel Flow Fan Terminal] [EL-STGD = Electric Heat - Staged] [EL-SCR = Electric Heat - SCR Controller] [HW-ON-OFF = Hot water Heat - On/Off Control] [HW-MOD = Hot Water - Modulating Control]
VAV/Zone
Controller
Description,
Location Or
Tag
Number
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
Estimated
Power/Comm
Cable Length
Power/Comm
Board To
Controller
(If Required)
_________
Form: ORION-VAVZoneWorksheet1B.doc Page 4 of 8
Page 37
VAV/Zone Worksheet
Project Name:
_____________________________________________
Local Loop Number:
______
Total Qty. Of VAV/Zone Controllers on Loop:
_________
Note: See End Of VAV/Zone Controller Address List For Power/Comm Board Cable Selection.
Selected
Room Sensor Modular or Digital Cable
Length
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
120 Ft.
120 Ft.
120 Ft.
120 Ft.
120 Ft.
120 Ft.
120 Ft.
120 Ft.
Type
Of
Terminal
Unit
NF SF PF
NF SF PF
NF SF PF
NF SF PF
NF SF PF
NF SF PF
NF SF PF
NF SF PF
Type Of Heat
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
From
__________
Selected Power/Comm
Cable Length From
Power/Comm Board To
Controller
(If Required)
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
Total Number Of Power/Comm Boards On Loop:
Estimated Power/Comm Cable Length
To Next
Controller
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
Selected Power/Com
Cable Length
To Next Controller
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
MiniLink PD Address For This Loop:
VAV/Zone
Address
33
34
35
36
37
38
39
40
NF = Non Fan Terminal] [SF = Series Flow Fan Terminal] [PF = Parallel Flow Fan Terminal] [EL-STGD = Electric Heat - Staged] [EL-SCR = Electric Heat - SCR Controller] [HW-ON-OFF = Hot water Heat - On/Off Control] [HW-MOD = Hot Water - Modulating Control]
VAV/Zone
Controller
Description,
Location Or
Tag
Number
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
Estimated
Power/Comm
Cable Length
Power/Comm
Board To
Controller
(If Required)
_________
Form: ORION-VAVZoneWorksheet1B.doc Page 5 of 8
Page 38
VAV/Zone Worksheet
Project Name:
_____________________________________________
Local Loop Number:
______
Total Qty. Of VAV/Zone Controllers on Loop:
_________
Note: See End Of VAV/Zone Controller Address List For Power/Comm Board Cable Selection.
Selected
Room Sensor Modular or Digital Cable
Length
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
120 Ft.
120 Ft.
120 Ft.
120 Ft.
120 Ft.
120 Ft.
120 Ft.
120 Ft.
Type
Of
Terminal
Unit
NF SF PF
NF SF PF
NF SF PF
NF SF PF
NF SF PF
NF SF PF
NF SF PF
NF SF PF
Type Of Heat
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
From
__________
Selected Power/Comm
Cable Length From
Power/Comm Board To
(If Required)
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
Total Number Of Power/Comm Boards On Loop:
Controller
Estimated Power/Comm Cable Length
To Next
Controller
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
Selected Power/Com
To Next Controller
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
Cable Length
MiniLink PD Address For This Loop:
VAV/Zone
Address
41
42
43
44
45
46
47
48
NF = Non Fan Terminal] [SF = Series Flow Fan Terminal] [PF = Parallel Flow Fan Terminal] [EL-STGD = Electric Heat - Staged] [EL-SCR = Electric Heat - SCR Controller] [HW-ON-OFF = Hot water Heat - On/Off Control] [HW-MOD = Hot Water - Modulating Control]
VAV/Zone
Controller
Description,
Location Or
Tag
Number
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
Estimated Power/Comm Cable Length
Power/Comm
Board To
Controller
(If Required)
_________
Form: ORION-VAVZoneWorksheet1B.doc Page 6 of 8
Page 39
VAV/Zone Worksheet
Project Name:
_____________________________________________
Local Loop Number:
______
Total Qty. Of VAV/Zone Controllers on Loop:
_________
Note: See End Of VAV/Zone Controller Address List For Power/Comm Board Cable Selection.
Selected
Room
Sensor Modular
or Digital Cable
Length
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
120 Ft.
120 Ft.
120 Ft.
120 Ft.
120 Ft.
120 Ft.
120 Ft.
120 Ft.
Type
Of
Terminal
Unit
NF SF PF
NF SF PF
NF SF PF
NF SF PF
NF SF PF
NF SF PF
NF SF PF
NF SF PF
Type Of Heat
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
From
__________
Selected Power/Comm
Cable Length From
Power/Comm Board To
Controller
(If Required)
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
Total Number Of Power/Comm Boards On Loop:
Estimated Power/Comm Cable Length
To Next
Controller
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
Selected Power/Com
Cable Length
To Next Controller
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
MiniLink PD Address For This Loop:
VAV/Zone
Address
49
50
51
52
53
54
55
56
NF = Non Fan Terminal] [SF = Series Flow Fan Terminal] [PF = Parallel Flow Fan Terminal] [EL-STGD = Electric Heat - Staged] [EL-SCR = Electric Heat - SCR Controller] [HW-ON-OFF = Hot water Heat - On/Off Control] [HW-MOD = Hot Water - Modulating Control]
VAV/Zone Controller
Description,
Location Or
Tag
Number
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
Estimated
Power/Comm
Cable Length
Power/Comm
Board To
Controller
(If Required)
_________
Form: ORION-VAVZoneWorksheet1B.doc Page 7 of 8
Page 40
VAV/Zone Worksheet
Project Name:
_____________________________________________
Local Loop Number:
______
Total Qty. Of VAV/Zone Controllers on Loop:
_________
MiniLink PD Address For This Loop:
__________
Total Number Of Power/Comm Boards On Loop:
_________
VAV/Zon
e
Address
57
58
59
Power/Comm
Qty Of Required
Power/Comm
Boards May Vary
Depending On
Installation
Power/Comm
Power/Comm
Power/Comm
Power/Comm
[NF = Non Fan Terminal] [SF = Series Flow Fan Terminal] [PF = Parallel Flow Fan Terminal] [EL-STGD = Electric Heat - Staged] [EL-SCR = Electric Heat - SCR Controller] [HW-ON-OFF = Hot water Heat - On/Off Control] [HW-MOD = Hot Water - Modulating Control]
Form: ORION-VAVZoneWorksheet1B.doc Page 8 of 8
VAV/Zone
Controller Description, Location Or
Tag
Number
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
This Address Is Reserved For The VCM-X Controller That Is Serving The VAV/Zone Controllers
Boards
Board #1
Board #2
Board #3
Board #4
Estimated Power/Comm Cable Length
From
Power/Comm
Board To
Controller
(If Required)
Estimated Power/Comm Cable Length
From
Power/Comm
Board To MiniLink
PD
Only Required For First Power/Comm
Board On Loop
3 Ft. □ 25 Ft. □ 40 Ft. □
Selected Power/Comm
Cable Length From
Power/Comm Board To
Controller
(If Required)
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
Selected Power/Comm
Cable Length From
Power/Comm Board To
MiniLink PD
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
Estimated
Power/Com
m Cable
Length To
Next
Controller
3 Ft. □ 25 Ft. □ 40 Ft. □
3 Ft. □ 25 Ft. □ 40 Ft. □
Estimated
Power/Com
m Cable
Length To
Next
Power/Com
m Board
(If Required)
Selected Power/Com
To Next Controller
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
Selected Power/Com
To Next Power/Comm
3 Ft. 25 Ft. 40 Ft. 80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
3 Ft. 25 Ft. 40 Ft. 80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft. 3 Ft. 25 Ft. 40 Ft. 80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft. 3 Ft. 25 Ft. 40 Ft. 80 Ft. 120 Ft. Ext.-10 Ft. 20 Ft.
Cable Length
Cable Length
Board
(If Required
Note: See End Of VAV/Zone Controller Address List For Power/Comm Board Cable Selection.
Selected
Room
Sensor Modular
or Digital Cable
Length
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
5 Ft. 10 Ft. 25 Ft. 40 Ft. 80 Ft. 160 Ft.
NOTE: Power/Comm Board maximum transformer size = 100VA. This is due to the board circuitry and fusing. Each modular device is to be calculated at 6VA. This allows for a maximum of 16 devices per Power/Comm board. If more than 16 devices are required, multiple Power/Comm boards must be used.
No more than 6 modular devices allowed per branch circuit. (The Power/Comm board has a total of 4 branch circuits)
The longest total run per branch circuit is 240 Ft. This is due to voltage drop on the prefabricated cable.
120 Ft.
120 Ft.
Type
Of
Terminal
Unit
NF SF PF
NF SF PF
Type Of Heat
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
EL-STGD EL-SCR HW-ON-OFF HW-MOD None
Loading...