Orion OE392-10-GPCXP Technical Manual

Page 1
System Manager TS II
For GPC-XP
Technical Guide
GPC-XP Controller Code: YS102432 Revision 4.0 and up
Page 2
Zone
TABLE OF CONTENTS
OVERVIEW ........................................................................................................................................................ 3
Flush Wall Mount Dimensions and Components .........................................................................................................................5
Surface Mount Dimensions and Components ..............................................................................................................................6
SMTS II to GPC-XP Controller Wiring ..........................................................................................................................................7
NAVIGATION .................................................................................................................................................... 8
Main Screen Icons and Button Functions.....................................................................................................................................8
Logging In.....................................................................................................................................................................................9
Editing Passcodes ......................................................................................................................................................................10
Setting The System Clock ..........................................................................................................................................................11
System Manager Settings ..........................................................................................................................................................12
Unit Selection .............................................................................................................................................................................13
Status & Con guration Screens .................................................................................................................................................13
Viewing and Setting Schedules .................................................................................................................................................16
Viewing and Setting Holidays .....................................................................................................................................................17
Schedule Override......................................................................................................................................................................18
Zone
ALARMS.......................................................................................................................................................... 18
Viewing & Enabling/Disabling Alarms ........................................................................................................................................18
APPENDIX ...................................................................................................................................................... 19
Troubleshooting - System Manager TS II LEDs, Buttons, Dipswitches, and Jumpers ...............................................................19
Military Time Conversion ............................................................................................................................................................20
INDEX ............................................................................................................................................................. 21
WattMaster Controls Inc. 8500 NW River Park Drive · Parkville, MO 64152 Toll Free Phone: 866-918-1100 PH: (816) 505-1100 · FAX: (816) 505-1101 E-mail: mail@wattmaster.com Visit our web site at www.orioncontrols.com
www.orioncontrols.com
Form: OR-SMTSII-GPCXP-TGD-01A Copyright May 2014 WattMaster Controls, Inc. AAON® is a registered trademark of AAON, Inc., Tulsa, OK. WattMaster Controls, Inc. assumes no responsibility for errors or omissions. This document is subject to change without notice.
Page 3
OVERVIEW
System Manager TS II
Features
The OE392-10-GPCXP System Manager TS II (Touch Screen) for the GPC-XP Controller provides a direct, graphic-enhanced, menu­driven link to enable you to view the status, perform force modes, and set schedules for your GPC-XP Controller. (See Figure 1.)
The System Manager TS II provides the following useful functions:
• Provides a 4.3” 480 x 272 WQVGA RGB TFT LCD Graphical Touch Screen LCD display with 16 million colors
• Utilizes a graphical touch screen menu system with easy­to-understand menu trees and icons and non-cryptic, plain English language messages
• Makes entering data quick and easy with instructions on each screen
• Graphic status screens provide easy monitoring of the GPC-XP without specialized training
• Provides protection from unauthorized users through inte­gral multi-level passcode authorization programming
• Comes equipped with real-time clock backup power supply for short power losses
System Requirements
The System Manager TS II is packaged and assembled for
fl ush wall mounting. Surface mount components are also included for your convenience.
If using the surface mount version, you will need a double
duplex outlet box (by others).
• The System Manager TS II for GPC-XP only communicates with the GPC-XP Controller
NOTE: Initial programming of the GPC-XP must fi rst be
done with a personal computer using our Prism 2 software. The Prism 2 software can be downloaded from our website—orioncontrols.com. See the GPC-XP Controller Technical Guide for detailed instructions. The GPC-XP contains an on-board CommLink, allowing you to directly connect to a computer using a USB cable.
• Provides icons to indicate alarm conditions
• LEDs behind plastic panel indicate power, communica­tions, and operation
• Plastic enclosure allows for easy fl ush wall mounting in hollow drywall or surface mounting on solid wall surface
Figure 1: System Manager TS II for the GPC-XP
SMTS II for GPC-XP Technical Guide
3
Page 4
COMPONENTS & WIRING
Mounting, Wiring, Initializing, and Updating
Environmental Requirements
The System Manager TS II needs to be installed in an environment that can maintain a temperature range between 14°F and 158°F with less than 90% RH levels (non-condensing).
Mounting
The System Manager TS II is housed in a plastic enclosure designed for mounting in hollow drywall construction or a control panel cover with the fl ush wall mount version (shown in Figure 3, page 5) or on a concrete, brick, or other solid wall surface with the surface mount version (shown in Figure 4, page 6).
The fl ush wall mount version has integral wingnut paddles that are tightened after installation to grip the drywall and hold the System Manager TS II in place. For mounting in a control panel cover or other thin material, (4) adhesive backed rubber pads are provided to assist in securing the System Manager TS II into the cutout in the panel. These pads are applied to the wingnut paddles to provide a non-slip mounting against the panel’s sheet metal surface. See Figure 2, below, for pad placement details.
The surface mount version is designed to be installed in a double duplex outlet box (by others). Both mounting styles of the System Manager TS II feature an integral, magnetically-secured face plate which can be easily removed for reset of the display when required.
The System Manager TS II should be mounted at approximately eye level to allow for ease of programming and reading of the display. The System Manager TS II is typically mounted in the building manager’s or superintendent’s offi ce or in an equipment room, but is also quite suitable for mounting in any location.
Wiring
The System Manager TS II is connected to the local communications loop of the Orion system via 18 AWG 2-conductor, twisted pair with shield wire connected to the T , SHLD & R communication terminals on the back of the System Manager TS II. The communications wire used can be either our W attMaster # WR-LL-WG-18 communications wire or Belden #82760 wire or its equivalent.
The System Manager TS II also requires that 24 VAC (6 V A) power be supplied (by others) to its + and – wiring terminal located on the back of the System Manager TS II.
See Figur e 5, page 7 for wiring details. This wiring diagram depicts wiring the System Manager TS II to the GPC-XP Controller. The System Manager TS II can also be wired to the local loop terminals on the MiniLink PD, Power Comm Board, or any other add-on controller’s local loop terminals. It will still require a transformer to be wired as shown in Figure 5, page 7.
Dipswitch and Jumper Settings
If the GPC-XP Controller is set at high speed, Dipswitch OPT1 should be set to ON. Otherwise, it should be set to OFF . As of April 2014, Dipswitch OPT4 should be set to ON by default. If you see your screen is not centered correctly, switch OPT4 to the opposite position. Dipswitches OPT2 and OPT3 should always be set to OFF . See Figure 5, page 7 for details.
If you have a Stand-Alone system (no CommLink or MiniLink, the TERM Jumpers must be ON. For applications with CommLink(s) and/or MiniLink(s), the TERM Jumpers must be OFF. See Figure 5, page 7 for details.
Care
The System Manager TS II should be cleaned with a soft, dust-free cloth. Do not use any liquid to clean your System Manager TS II. You should press the < Suspend> button located behind the cover to temporarily freeze the touch pad before you attempt to clean your screen. See the Troubleshooting section on page 19 for details.
Rubber Pads
USE 4
Left Side View
Technical Support
Call (866) 918-1100 to talk to a WattMaster Controls T echnical Sup­port Representative. Support is available Monday through Friday, 7:00 AM to 5:00 PM central standard time.
Place (2) On Each Paddle Arm As Shown When Mounting In Sheet Metal Panel Or Other Thin Mounting Material. Pads Are Not Required For Drywall Mounting
Front View (Cover Removed)
Rubber Pads
Figure 2: System Manager TS II - Control Panel Mounting Pad Placement Detail ( Flush Wall Mount)
4
SMTS II for GPC-XP Technical Guide
Page 5
COMPONENTS & WIRING
Flush Wall Mount Dimensions and Components
Figure 3: System Manager TS II Dimensions and Components ( Flush Wall Mount)
SMTS II for GPC-XP Technical Guide
5
Page 6
COMPONENTS & WIRING
Surface Mount Dimensions and Components
Figure 4: System Manager TS II Dimensions and Components ( Surface Mount)
6
SMTS II for GPC-XP Technical Guide
Page 7
BLACK (R)
BARE (S) WHITE (T)
WHITE (T)
BARE (S)
BLACK (R)
COMPONENTS & WIRING
SMTS II to GPC-XP Controller Wiring
GPC-XP
To S Terminal On
T
GPC-XP
To R Terminal On
BROWN (GND)
RED (24 VAC)
+
To (24 VAC) Transformer -
To (24 VAC) Transformer +
BROWN (GND)
RED (24 VAC)
24 VAC Transformer
5 VA Minimum
Line Voltage
GPC-XP
To T Terminal On
Run 2 Conductor Twisted Pair W/Shield Cable. WattMaster WR-LL-WG-18 Cable Or Equivalent From System Manager TS To VCB-X Controller
System Manager TS - Back View
WHITE (T)
BARE (S)
BLACK (R)
Run 2 Conductor 20 Ga. Minimum Cable From System Manager TS Terminals To 24 VAC Transformer.
WattMaster Controls, Inc
WattMaster Controls, Inc
C13
C11
C10
C9
C13
C11
C10
C9
WQVGAGraphical Interface
WQVGAGraphical Interface
.1uF
.1uF
.1uF
.1uF
YS102178 R4
YS102178 R4
X3
X3
C14
.1uF .1uF
.1uF
C23
R20
C26
1002
C25
R10
.1uF
1002
R22
1002
R24
1002
R27
R36
1002
1002
1002
R17
R29
1002
R26
1002
C45
R12
.1uF
1002
R14
1002
RTC
1002
R40
CAL
1002
R42
C39
C39
C14
.1uF
66.000Mhz
C20
C20
.1uF
C19
C19
.1uF
.1uF
C18
C6
J1
.1uF
.1uF
C16
C8
.1uF
C17
TERM
X2
8.00Mhz
J3
R46
.1uF
.1uF
R43
C5 C4
1002
R47
1002
1002
C50
RRSST
C51
C51
L5
.1uF
1002
D12
R48
1002
1002
R49
1002
1002
330uF 50V 330uF
R44
R37
R45
MADE IN USA
1002
5V 3.3V 2.5V
.1uF
D1
U10
.1uF
R15
C27
C29
.1uF
1002
C28
1002
LTC3824
R11
R33
.1uF
1002
R25
C31
R19U9R28
C32 R30
SERIAL#
C34 C40
.1uF
SW1
R13R8
1002 1002
1002 1002
R34 R16
GND
OFF
R
T
OPT4
OPT3
OPT2
OPT1
5V
1002
R21
1002
R35
R23
1002
1002
C36
R39
D11
.1uF
U13
.1uF
.1uF
C41
1002
R32R31
1002
1002
L4
1002
R41 U11 Q2
L1
R18
.1uF
.1uF
C30
D2
C35
C2C3
1002
1002
.1uF
1002
1002 1002
OFF
OPT2
OPT1
TERM
SW1
NOTE: Dip Switch OPT1 Should Be Set To ON When GPC-XP Is Set To High Speed.
OPT3
Set To OFF
OPT2 & OPT3
OPT4
Should Be
. As Of April 2014, OPT4 Should Be Set To ON By Default. Previous Versions Should Be Set To OFF. If You See Your Screen Is Not Centered Correctly, Switch
.1uF
R1
R1
1002
C12
C12
C1
C1
.1uF
.1uF
C15
C15
C7
C7
R7
R7
.1uF
1002
1002
R9
R9
1002
1002
R6R5R2
R6R5R2
V1
+
C24
C24
OPT4 To The Opposite Position.
L
O
O
C
P
O
M
M
T-
RS-485 C
O
M
M
TIO
UN
N LO
IC
A
. W
O
P
IRE
H
S
“R”TO “R”, “T” TO “T” “SH
R
+
1
B
T
O
N
B
O
A
w
w
w
.w
B
IN
A
Y
R
C
O
M
M
L
I
IN
P
U
T
S
C
O
N
N
E
C
R38
1
IN
B
0
0
3
D
6
R41
2
IN
B
0
0
3
D
7
R43
0
0
3
3
IN
B
R47
D
8
0
0
3
4
IN
B
D
9
5
IN
T
S
R
B
0
0
3
0
D
1
0
0
3
6
IN
B
D
1
1
0
0
3
7
IN
B
R61R59R55R51
2
D
1
0
0
3
8
IN
B
3
D
1
C
O
M
CUTTO ISOLATE
COMFROM GND
C
O
M
C
O
M
C
O
M
4-20mA
THERM
3
B
T
0-10v
0-5v
A
N
A
L
O
G
IN
P
U
T
S
I1
A
I1
A
I2
A
I3
A
I2
A
I4
A
I5
A
I3
A
I6
A
I7
A
I4
A
I8
A
G
N
D
I5
A
G
N
D
I6
A
G
N
D
G
N
D
I7
A
7
B
T
V
D
C
O
U
T
P
U
T
S
I8
A
V
4
2
+
V
5
+
G
N
D
8
B
T
attm
OE338-23-GPC-XP
GPC-XP CONTROLLER
RLY1 =
RLY2 =
RLY3 =
RLY4 =
AI1 =
BI1 = A
AI2 = BI2 = A
AI3 = BI3 = A
A
I4 = BI4 = AO
AI5 = BI5 =
AI6 = BI6 =
AI7 = BI7 =
AI8 = BI8 =
ANALO
G
IN
PUT
JUM
PERS
LEDNAME
NORMAL OP ERATION 0 1
SCHEDULE OV ERRIDE 0 2
4-20mA
0-5V
0-10V
THERM
A
I1
N
OTES:
A
I2
1.)ANALO SETFO
A
I3
R
EQ
UIREM
A
I4
2.) ITIS R D
ESC
A
I5
O
U
TPUTS
C
O
NT
A
I6
U
SIN
G
FU
TUR
A
I7
A
I8
VDC
O
U
TPUTS
+ 24V
D
C
+ 5V
DC
GND
G
N
D
+24VAC
LD
aster
.com
RLY5 =
RLY6 =
RLY7 =
RLY8 =
G
R
Y
OU EN
ECO
RIPTIO
YO
RO
LLER APE E
R
EFEREN
24 VA
C PO
WA
RN
O
R
THE CO
”TO“SHLD”
LED BLINK CODES
INP
JUM
U
T
PER SETTING
R SPECIFIC IN
.
T
M
M
EN
D
ED
TH
N
O
E INPU
F
U
ARE CO
NN
TH
E
IN
BO
RM
AN
ENT
M
ARKER
CE
.
W
ER
O
NL
IN
PO
G
!
LAR
ITY
NTR
O
LLER W
U
SB
PO
T
R
TH
X
Y
STATUS1
E ES PR
M
E PO
R RATING M
CO
CO
O
1 =
O
2 =
O
3 =
4 =
D
PUT
TYO
A
U
,AND
T
/O
CTIN
G O
VIDED
(SHAR
U
ST BE O
BE
ILL
-BU
S T
R
ELA
AX @
R
ELA
RELAY2
RE
RELAY4
RE
RELAY6
RELAY7
RELAY8
EVIC
W
R
TOTH
D
M
LA
M
S M
YCO
LA
STATUS2
RITE
PIE) FO
BSER AM
Wa
Y
S
1
0
2
4
3
2
R
E
V
3
WAT
S
R
O
O
R
C
N
L
T
E
M
T
S
T
A
N
ACT
T
IS 1
A
24 V
A
C
Y1
Y3
M
O
N
Y5
M
ON
BE
U
ST
E
TH
E
E ABO
VE
®
R
VED
A
G
ED
ttM
a
s
te
r L
#
L
B
1
0
2
0
9
R
e
.: 1
v
C
A
S
U
M
IN
D
E
A
M
P
R
L
1
Y
R
L
2
Y
R
L
3
Y
R
L
4
Y
C
O
M
M
O
N
2
B
T
R
E
Y
L
A
O
U
T
P
U
T
S
4
B
T
R
L
1
Y
R
L
2
Y
R
L
3
Y
R
L
4
Y
C
O
M
M
O
N
SERIAL #
A
N
A
L
O
G
O
U
T
P
U
T
S
2
0
0
1
4
R
7
7
U
1
1
O
A
U
T
AOUT1-2
2
O
A
U
T
.1
F
u
3
O
A
U
T
6
C
3
7
R
9
2
0
0
1
4
O
A
U
T
9
U
1
AOUT3-4
G
N
D
G
N
D
.1
F
u
6
C
4
6
B
T
G
N
D
S
AT
T
U
S
1
S
AT
T
U
S
2
E
B
U
S
P
O
W
E
R
2
0
0
1
1
R
2
2
0
0
1
9
0
R
1
2
0
0
1
6
R
1
2
0
0
1
4
R
1
.1
F
u
1
C
2
ADDRESS
D
D
A
2
0
0
1
1
2
0
0
1
2
2
0
0
1
4
2
0
0
1
8
2
0
0
1
16
2
0
0
1
a
b 5
32
e
l
2
0
0
1
BAUD
LOOP
1
2
0
0
1
2
1
W
S
4
C
1
.0
F
u
1
NOTE: For Stand-Alone Installations (No CommLink or MiniLink), Both TERM Jumpers Must Be ON. For All Applications With CommLink(s) Or MiniLink(s), Both Jumpers Must Be OFF.
GPC-XP Controller -
Front View
Figure 5: System Manager TS II to GPC-XP Controller Wiring
SMTS II for GPC-XP Technical Guide
7
Page 8
Zone
NAVIGATION
Main Screen Icons and Button Functions
Zone
Icons and Button Functions
System settings and screens are easily accessible by simply touch-
one of the fi ve icons on the Main Screen. The subscreens contain
ing
green outlined data entry boxes with accessible number keypads for data entry and screen maneuvering buttons such as <Esc>, <Bac k>, and <OK>.
NOTE: Do not attempt to make changes to the Touch Screen
while the GPC-XP is initializing. This can cause programming errors.
Main Screen Icons
There are fi ve Main Screen icons. See Table 1 for a list of the Main
icons and their functions.
Screen
Icon Main Screen Icons
The < Login> icon takes you to the Login Screen where you enter your passcode.
In a networked system, the < My System> icon takes you to a Unit Selection Screen which takes you directly to the GPC-XP Controller’s Status Screen. In a stand-alone system, the < My System> icon takes you directly to the Status Screen.
The < User Passcodes> icon takes you to the System Manager Passcode Levels Screen if you are a Level 3 user.
The < Settings> icon takes you to the System Settings Screen where you can change the Backlight settings, set the System Manager address, or choose One to One Unit Connection (stand-alone connection). System settings are only accessible to a Level 3 user.
The < Set Time & Date> icon takes you to the Set Time and Date Screen. Any level of user can set the time and date.
Navigation Buttons
See Table 2 for a list of Navigation buttons and their functions.
Button Function
Use the < Back> button while in a Data Entry
Back
+
-
Screen to return to the Status Screen. Use the < Back> button while in a Status Screen to return to the Main Screen.
Use the < +> key to step to the next screen.
Use the < -> key to step to the previous screen.
Table 2: Navigation Button Functions
Data Entry, Selection, and Alarm Buttons
See Table 3 for a list of data entry, selection, and alarm buttons and their functions.
Button Function
Esc
OK
No Alarms
Use the < Esc> (Escape) key to exit from data entry without saving any new data.
Use the < OK> key to save the data you just selected or entered.
Touch the gray radio button to make your selection. A white circle will designate that the item is selected. You can only select one radio button item per screen.
Touch the gray square to make your selection. A white square will designate that the item is selected. You can select more than one square per list of items.
The <No Alarms> or < ALARM> button, ap- pearing on each Status Screen, takes you directly to the GPC-XP Alarm Status Screen where you can program alarms and view active alarms. If red, alarm(s) are present. If black, no alarm(s) are present.
Table 1: Main Screen Icon Functions
8
Table 3: Confi guration Selection Buttons
SMTS II for GPC-XP Technical Guide
Page 9
MAIN SCREEN FUNCTIONS
Logging In
First Things First
The fi rst thing you need to do when setting up your T ouch Screen is to log in. The second thing you need to do is establish user passcodes. The third thing you need to do is set the clock. After you complete these simple tasks, you are ready to set your system’s settings, view GPC-XP status screens, change schedules, and perform force modes.
NOTE: Do not attempt to make changes to the Touch Screen
while the GPC-XP is initializing. This can cause programming errors.
Main Screen
Once you have connected your System Manager TS II to a control­ler and have powered it up with the proper power supply, the Main
will appear. See Figure 6.
Screen
Entering Your System Manager Passcode
NOTE: There are three available passcode levels. Level 1 defaults
to 1111, Level 2 defaults to 2222, and Level 3 defaults to 3333. These defaults can be changed by anyone who logs in at Level 3.
When you power-up your System Manager TS II, the message
System Secured is displayed under the time display at the upper
right of the Main Screen.
Touch the < Login> icon found on bottom left of the Main Screen and type the default Level 3 passcode of
3333” using the number keypad to gain access to all setpoint and confi guration items. See Figure 7.
Esc
Currently: ****
2
1
4
5
7
8
-
0
<<
3
6
9
OK
.
DATA ENTRY
Enter the 4 digit Passcode for the required Level.
Level #1: Can change space setpoints. Level #2: Can change schedules. Level #3: Can change all setpoints.
Figure 6: Main Screen
Figure 7: Login Screen
NOTE: For security reasons, the current passcode characters
displayed at the top of the screen are never shown and appear as asterisks.
Touch <OK>. The Login Screen will automatically close, and the
passcode will be tested against all previously defi ned passcodes to determine the passcode’s access level.
If 3333 is still the active Level 3 code, the status message
Access Level 3
the upper right of the
NOTE: System Access will automatically default to System
will now be displayed under the time display at
Main Screen.
System
Secured after the time set for Backlight Timeout
in the System Manager Settings Screen (see Figure 12, page 12). If timeout is set to zero, the passcode
will timeout after two minutes.
SMTS II for GPC-XP Technical Guide
9
Page 10
MAIN SCREEN FUNCTIONS
Editing Passcodes
Zone
Zone
Passcode Clearance Levels
Below is a list of the passcode levels, default codes, and actions that can be performed at the various levels.
Level 0—No Passcode Needed, System Secured
Level 0 users can view status screens. They can also change the system date and time. No other changes can be made at this level.
Level 1—Default: 1111
Level 1 users can view status screens. They can also change the system date and time. A level 1 user can also temporarily override a schedule.
Level 2—Default: 2222
Level 2 users can view status screens. They can also change the system date and time. Level 2 users can also set schedules and holidays and temporarily override a schedule.
Level 3—Default: 3333
Level 3 users have system manager access and can change all confi gurations, including default passcodes. Level 3 users can also access force modes. This Level is normally reserved for qualifi ed HVAC service per- sonnel.
Passcode Levels
You can limit access to critical settings by giving the user access only to those items needed to maintain comfort levels or to modify operating hours. All critical setpoints and configurations are protected by Level #3 and should not be accessed except by a service technician.
Back
{ Temporary Schedule Overrides }
{ Can change Schedules & Holidays }
{ Can change All Setpoints }
1111
Level #1 Passcode
2222
Level #2 Passcode
3333
Level #3 Passcode
Figure 8: System Manager Passcode Levels Screen
To change a passcode, touch the blue highlighted box containing the current passcode. The keypad will appear with instructions for changing the passcode. See Figure 9.
Esc
Currently: ****
2
1
4
5
7
8
-
0
<<
3
6
9
OK
.
DATA ENTRY
Enter the 4 digit Passcode for the required Level.
Level #1: Can temporarily override schedules. Level #2: Can change schedules and holidays. Level #3: Can change user passcodes and access force modes.
Edit Passcodes
WARNING: MAKE SURE YOU CHANGE ALL PASS­CODES AS SOON AS POSSIBLE TO SECURE THE SYSTEM!
NOTE: Only a Level 3 use r (system man age r level) can cha nge
Level 1, 2, and 3 passcodes.
NOTE: Do not use the same p a s s c od e for al l 3 levels. If you do,
each passcode will default to Level 1.
From the
codes>
Screen
Main Screen, touch the < User Pass-
icon. The System Manager Passcode Levels
will appear. See Figure 8.
Figure 9: Change Passcode Screen
The current passcode will appear on the top menu bar.
Type in the
new four-digit passcode. You cannot use the period or minus char­acters in your passcode. Use the <<<> key if you make a mistake.
Touch <Esc> to return to the previous screen without changing the
passcode. When you have typed in the new passcode,
touch <OK>.
The System Manager Passcode Levels Screen should now display the passcode that you entered.
NOTE: If you change the Level 3 passcode, make sure to write
it down. If you should happen to forget the Level 3 passcode, contact WattMaster Technical Support.
Touch <Back> to return to the Main Screen.
10
SMTS II for GPC-XP Technical Guide
Page 11
MAIN SCREEN FUNCTIONS
Setting the System Clock
Set Time and Date
When you fi rst power up your System Manager TS II, you will need to change the day of the week, the time, and the month, day, and year to the current time and date. If your system has been turned off or has been down for a long time, you may have to do the same, although the time and date can maintain itself for several days. Any level of user can change the time and date settings.
The day of the week, the time, and the date appear at the top right
Main Screen. See Figure 6, page 9.
on the
From the
Date> icon. The Set Time & Date Scr een will appear .
See Figure 10.
System Manager Settings
Hour Minute
14
Mon
Sun
Back
Figure 10: Set Time & Date Screen
In the example above, the current time and date is 2:12 PM, January 16, 2014. There is no day of the week selected yet.
Main Screen, touch the < Set Time &
Set Time & Date
Month
12
Tue
1
Wed
Day Year
16
Thu
Sun
Thu
Fri
Sun
Fri
14
Sat
Sat
Sun
Broadcast
DATA ENTRY
Set Clock Hour Enter the Current Hour in 24 hour military format. Example:
5:00 AM = 5 5:00 PM = 17
Hi Limit: 23 Lo Limit: 0
Esc
Currently: 10
2
1
4
5
7
8
-
0
<<
3
6
9
OK
.
Figure 11: Set Clock Hour
Set Clock Hour: Touch the number buttons to enter the current hour
in 24 hour military format. Valid entries are from 0-23. Press <OK>.
NOTE: See Appendix on page 20 for a Military Time
Conversion table.
Set Clock Minute: Touch the number buttons to enter the current
minutes. Valid entries are from 0-59. Press <OK>.
Set Clock Month: Touch the number buttons to enter the current
month. Valid entries are from 1-12. Press <OK>.
Set Clock Day: Touch the number buttons to enter the current day
of the month. Valid entries are from 1-31. Touch <OK>.
Set Clock Year: Touch the number buttons to enter the current year.
Valid entries are from 0-99. Touch <OK>. Note: The year is based on the current century; therefore, 14 = 2014. If you enter more than two digits, e.g. 2014, the system will not recognize your entry.
Set Day of the Week: Select the day of the week by simply
touching your selection. The day of the week text will change from
white to blue.
Set Hour, Minute, Month, Day, and Year: Touch the blue high-
lighted box to have each selection screen appear. See Figur es 10 &
11. Read the instructions on each screen for entering data.
Broadcast: When you are nished setting the clock, touch the
<Broadcast> button to broadcast the Time and Date to all Units.
The following message will appear:
Time & Date Broadcast to All Units.
SMTS II for GPC-XP Technical Guide
OK
11
Page 12
MAIN SCREEN FUNCTIONS
System Manager Settings
Zone
Zone
System Manager Settings
Additional system settings are available under the <Settings> icon. These include setting the Backlight Timeout, the Backlight Intensity Percentage, the System Manager Address, and One to One Unit Connection.
From the The System Manager Settings Screen will appear. See Figure 12.
System Manager Settings
One to One Unit Connection
Back
Figure 12: System Manager Settings Screen
Backlight Timeout: This setting is actually a setting for three
separate functions—Backlight Timeout, Main Screen Timeout, and Passcode Timeout. To set the Backlight Timeout, enter the amount of time you wish the screen to maintain the active intensity level after the last touch pad activity occurs. The High limit is 30 and the Low limit is 0. 0 = No Timeout. The System Manager TS II will return to the Main Screen display at the same rate as the Backlight Timeout, except that if set to 0, the Main Scr een will display after 2 minutes. The Passcode will timeout at the same rate as the Backlight Timeout, except that if set to 0, the Passcode will timeout after 2 minutes and will return to System Secured Setting.
Main Screen, touch the < Settings> icon.
30
30
Minutes
Backlight Timeout
3050
Backlight Intensity
3063
System Manager Address
System Manager Version: 1.02
%
System Manager Address: Enter the address of the System
Manager TS II. 0 = Stand Alone Mode. 63 = Network System. 1-60 = Multiple Managers based on the following defi nitions:
Stand AloneIf your System Manager TS II is connected to
• one controller and you are not using a CommLink or MiniLink anywhere on the loop, your system is Stand Alone. If your System Manager TS II is connected to more than one controller daisy-chained together and you are not using a CommLink or MiniLink anywhere on the loop, your system is Interconnected. If you have either a Stand Alone or Interconnected system, you must enter <0> for Stand Alone Mode. In order to view all controllers on an Interconnected System, make sure that One to One Unit Connection, described below, is not selected.
Network—If you are using this System Manager TS II on a com-
• munications loop that has a MiniLink or CommLink installed and you have a single System Manager TS II for your entire system, you must enter <63> for Network System.
Multiple Managers—If you are using this System Manager TS
• II on a communications loop, have a MiniLink or CommLink installed, and have more than one System Manager TS II, then you need to operate in Multiple Managers Mode. Enter the ad­dress <1-60> at which you want this particular System Manager TS II to be set. When more than one System Manager TS II is used on a local loop, each must be set with a unique address different from any other device on that loop. If you want one of the System Manager TS II’ s to be able to indicate alarms for the entire system, you must enter <63> for Network System for that particular System Manager TS II.
One to One Unit Connection: If your System Manager TS II
is directly connected to the GPC-XP Controller, you may wish to select this option to bypass the Unit Selection Screen and go directly to the unit’s Status Screen. The controller must be set to address #1 for this to work. Touch the black box to the left of this item on the screen to select it. The box will turn white. If you wish to deselect this option, simply touch the box again.
Backlight Intensity Percentage: Enter the percentage of light
level you wish to maintain whenever touch pad activity occurs. The High limit is 100 and the Low limit is 0.
12
System Manager Version: The version number of the System
Manager software appears on the bottom menu bar. This version number is important to know for troubleshooting purposes.
SMTS II for GPC-XP Technical Guide
Page 13
My System Unit Selection
From the Main Screen, touch the < My System> icon. The Selected Unit Screen will appear. See Figure 13.
NOTE: If you have chosen the One to One Unit Connection
in the System Manager Settings Screen, this screen (Figure 13) will not appear. Instead, the unit’s fi rst
Status Screen will appear.
Selected Unit [Loop 1 - Unit 1]
+ + + +
1
0
10
- - - -
GPC-XP CONTROLLER SCREENS
Unit Selection and Analog Inputs
Figure 14: Analog Inputs Screen
Analog Inputs: Thermistor sensors can be calibrated and all read-
ings can be overridden to specifi c values by Level 3 users. To do this, while in the Analog Input Screen, touch the value fi eld for the sensor you would like to calibrate or override.
In this example below (Figure 15), Analog Input #1 - OSA Tem­perature Sensor is selected.
Back
GO
Figure 13: Unit Selection Screen
In Figur e 13, Loop 1 and Unit 1 are selected as indicated in the fi gure with white text. They also appear in the Top Menu Bar in brackets.
<+> and <-> buttons to move up and down through the loops
Use the and units. Enter the desired Loop # and Unit # and then touch <GO> to access the unit’s Status Screen.
Viewing / Confi guring GPC-XP Status Screens
Figures 14-27 depict the GPC-XP Status Screens and corresponding
data entry screens associated with them
is identifi ed by loop number and unit number - in this case, 0001 represents Unit 1 with a stand-alone connection.
While in each Status Screen, touch the <+> and <-> buttons to view more status screens. These screens roll back to the fi rst Status Scr een.
. Notice that the controller
Figure 15: Analog Input Details Screen
Calibrate Sensor: T o calibrate a thermistor sensor , touch the Cali-
brate Sensor value fi eld. The Data Entry Screen will appear. Type a positive value to increase the reading or a negative value to decrease the reading. High Limit: +100. Low Limit: -100. Press <OK> to save.
SMTS II for GPC-XP Technical Guide
Figure 16: Calibrate Sensor Data Entry Screen
13
Page 14
Zone
GPC-XP CONTROLLER SCREENS
Zone
Analog Inputs, Binary Inputs, and Relay Outputs
Override Reading: To override a reading for a thermistor sensor,
touch the Override Reading value fi eld. The Data Entry Screen will appear. (Figur e 17) Type a value that will override the actual sensor reading and press
Clear Sensor Override: T o clear an override for a thermistor sen-
sor, touch the Override Reading value fi eld. The Data Entry Screen will appear. (Figur e 17) Type -90 to clear a sensor override that was entered. Press <OK> to save.
<OK> to save. High Limit: 3000. Low Limit: -80.
Figure 19: Binary Input Force Mode Screen
Figure 17: Sensor Override Data Entry Screen
Figure 18: Binary Inputs Screen
Binary Inputs: Level 3 users can force a binary input on or off or
to return it back to normal operation. T o do this, while in the Binary Inputs Screen (Figure 18), touch the value eld for the binary input
you would like to force on or off.
Figure 20: Relay Outputs Screen
Relay Outputs: Level 3 users can force a relay on or off or to return
it back to normal operation. To do this, while in the Relay Outputs Screen (Figure 20), touch the value eld for the Relay you would
like to force on or off. In the example below (Figure 21), Relay Output #5 - Tower Fan
- is selected. Touch the Tower Fan’s data fi eld. The Relay Output Force Mode Screen will appear (Figure 22).
In this example that follows (Figure 19), Binary Input #1 - Chilled Water Flow - is selected.
You can now select the radio button for the force mode—Normal Operation, Force Input Active, or Force Input Off.
14
Figure 21: Relay Output Details Screen
SMTS II for GPC-XP Technical Guide
Page 15
GPC-XP CONTROLLER SCREENS
Relay Output Force Modes, Analog Outputs, and Analog Force
Figure 22: Relay Output Force Mode Screen
Relay Force: You can now select the radio button for the force
mode—Normal Operation, Force Relay On, or Force Relay Off.
Runtime Reset: You can also touch the Runtime Hrs and Runtime
Minutes data fi eld to reset Runtimes (Figure 21).
Figure 23: Analog Outputs Screen
Analog Outputs: From the Analog Outputs Screen (Figure 23)
you can access the detail screen by selecting one of the data fi elds. In the example below (Figure 24), Tower Fan Speed is selected.
Figure 25: Analog Output Force Screen
Force Analog Output: From the Analog Output Detail Screen
(Figure 24), you can access the Force Screen (Figure 25 above) by selecting the Force Value data fi eld. Enter a percentage between 0 and 100. Enter -1 to Cancel the Force Mode.
Figure 26: Outdoor and AVC Status Screen
Outdoor and A VC Status: This screen (Figur e 26) is for view-
ing only.
Figure 24: Analog Output Detail Screen
SMTS II for GPC-XP Technical Guide
Figure 27: Schedules and Holidays Screen
Schedules & Holidays: Refer to the next section for instructions.
15
Page 16
SCHEDULES
Viewing and Setting Schedules
Viewing and Setting Schedules
Y ou can view and set schedules from GPC-XP Status Screen #6. Y ou can set up to 8 different schedules. See Figure 28 below.
Figure 28: Status Screen #6 - Schedules
Figure 30: Schedule Times Screen
Touch <OK> to save the time you entered or touch <Esc> to exit the Schedule Times Screen without changing the time and return to the
Week Schedules Screen (Figure 29).
To set a schedule, Schedule #. The Week Schedules Screen will appear. See Figure 29.
The default day will be Sunday and the default event start/stop times will be midnight.
touch the <ON> or <OFF> button to the right of the
Figure 29: Week Schedules Screen
A Level 2 user can set two schedules per day for individual days of the week, all weekdays, weekends, and holidays. All times are entered in military time format.
To eliminate a schedule from any event, simply enter a zero for the Start and Stop time for that day. The screen will display 12:00 am for both the Start and Stop times, indicating that the equipment will not activate on that day.
Once back at the schedules day by day or use following options:
SEND TO <All Days> - Touch this button to send the schedule ap-
pearing on the screen to all days of the week, except for holidays.
SEND TO <Weekdays> - Touch this button to send the schedule
to weekdays only. You will need to set up a separate schedule for Saturday and Sunday when selecting this option.
CLEAR <All Schedules> - Touch this button to clear all schedules. SET <24 Hr Mode> - Touch this button to have the system run
continuously, 24 hours a day, 7 days a week including holidays. All event times will display 11:59 PM.
Week Schedules Screen, you can continue setting
If you wish to enter a schedule for a certain day of the week, fi rst touch the day of the week at the top of the screen. Otherwise, the day defaults to Sunday.
Touch the start and stop time for each Event and enter the desired
times. See Figure 29. All times must be entered in military time format. See the Military Time Table in the Appendix, page 20.
16
SMTS II for GPC-XP Technical Guide
Page 17
HOLIDAYS & SCHEDULE OVERRIDE
Viewing and Setting Holidays & Schedule Override
Viewing and Setting Holidays
You can set holidays from Status Screen #6. See Figure 31 below. Y ou can set up to 8 dif ferent holiday schedules. You must be a Level 2 user in order to set holidays.
Figure 31: Status Screen #6 - Schedules
To view and set holidays, Schedule #. The Holidays Schedule Screen will appear, starting with the current month and year. See Figure 32.
touch the < NORMAL> button for the desired
Every defi ned holiday uses the Holiday operating schedule pro- grammed in the controller’s
Holidays can only be programmed for the current year. Y ou cannot program holidays before the next year occurs. Holidays do not automatically adjust for the new year, so you will need to access this screen after the new year and make necessary adjustments to the days that fl oat, such as Memorial Day.
Schedules Screen.
Schedule Override
Level 1, 2, and 3 users can override schedules. T o override a schedule, while at Status Screen #6 (Figure 31), touch the <AUTO>, <ON>, or
<OFF> button next to the <NORMAL> button. The Schedule Over-
ride Screen will appear (Figure 33 below):
Figure 32: Holidays Schedule Screen
The holidays in the screen will initially not be set. You can only set holidays for the current year. Simply touch the day(s) of the month to select holidays. Touch the
<>> button to go forward one month.
the There are 14 holiday periods available for each year. These holiday
periods can be a single day or they can span days, weeks, or even months.
For example, if you want to schedule a summer break, you need only schedule one holiday period to defi ne a two or three month break from operating in the occupied mode.
<<> button to go back one month and
Figure 33: Schedule Override Screen
Touch the radio button to select the schedule option. Default is
Schedule AUTO Mode. This selection will remain in effect unless it is changed again on this screen. Schedule overrides do not auto­matically time out after a certain period of time.
  Schedule AUT O Mode—Select this to restore normal
schedule operation.
  Schedule FORCED ON—Select this to Force the unit into
continuous Occupied Mode operation.
  Schedule FORCED OFF—Select this to Force the unit
into continuous Unoccupied Mode operation.
SMTS II for GPC-XP Technical Guide
17
Page 18
Zone
ALARMS
Viewing and Enabling/Disabling Alarms
Viewing/Enabling/Disabling Alarms
No Alarms
NOTE: The < ALARM> button only appears red on the
To view or confi gure alarms, touch the <No Alar ms>
<ALARM> button on any of the Status Screens. See
or Figure 34. The GPC-XP See Figure 35.
screen if the unit has an active alarm condition. Only a Level 3 user has the option to enable or disable each type of alarm.
Alarm Status Screen will display .
Figure 35: GPC-XP Controller Alarm Status Screen
In addition to simply viewing alarms, the Alarm Status Screen can also be used for enabling and disabling alarms that will be emailed or texted. The emailing and texting feature will only work if Prism 2 is running and has emailing capability.
Zone
VCM-X CoVCM-X Co
Figure 34: GPC-XP Status Screen 1
The alarms must fi rst be confi gured using Prism 2 software. Once the alarm settings have been established in Prism 2, the settings you choose in the that you will not have to reconfi gure the alarms for that controller in Prism 2. Once confi guration is complete, Prism 2 does not have to be running in order to view alarms on the Alarm Status Screen in
the System Manager TS II
2 does have to be running for emailing or texting alarms to occur. To enable an alarm, simply
A white box designates that the alarm is enabled. T o disable the alarm, simply touch the square again. A gray box designates that the alarm category is disabled.
When an alarm is enabled and there is no alarm condition, the word OK appears in a box next to the type of alarm. When an alarm occurs, this box will turn red and will read ALARM.
Alarm Status Screen will be stored in the controller so
. However, as mentioned previously , Prism
touch the gray square next to each alarm.
18
SMTS II for GPC-XP Technical Guide
Page 19
APPENDIX
Troubleshooting
ntrollersntrollers
System Manager TS II LEDs, Buttons, Dipswitches & Jumpers
LEDs and system function buttons are located behind your System Manager TS II’s cover. See Figure 36 for locations. Dipswitches and jumpers are located on the back of your System Manager TS.
Power LED
This LED will light up and stay on as long as power is supplied to your TS.
Operation LED
This LED will blink once a second to indicate that the system is alive.
Update LED
This LED will turn on when the Update program is running.
Screen Refresh LED
This LED will turn on when the screen refreshes.
Communications LED
This LED will light up and blink when there is a connection with the CommLink and/or network. If you are using your TS in stand-alone mode, this LED will not light up.
Reset Button
Press this button to reset the screen. The screen should refresh itself to the Main Screen within 2 minutes.
Diagnostics Button
Under the direction of W attMaster Controls Technical Support, you may have to perform diagnostics on your System Manager TS II.
Press this button to do so.
Touch Screen Suspend Button
Press this button to temporarily freeze the touch screen function of
your System Manager TS II in order to clean the screen. Always use a dry, dust-free cloth to clean the screen.
OPT1 Dipswitch
OPT1 Dipswitch should be ON if the GPC-XP is set to High Speed. This Dipswitch is located on the back of the System Manager TS. See Figure 5, page 7 for location.
OPT4 Dipswitch
As of April 2014, Dipswitch OPT4 should be set to ON by default. Previous versions should be set to OFF. If you see your screen is not centered correctly, switch OPT4 to the opposite position. This Dipswitch is located on the back of the System Manager TS. See Figure 5, page 7 for location.
TERM Jumpers
Both TERM Jumpers must be ON for Stand-Alone applications (No CommLink or MiniLink). Both TERM Jumpers must be OFF for applications with CommLink(s) and/or MiniLink(s). See Figure 5, page 7 for location.
Not Used Not Used
Power LED
Reset Button
Figure 36: System Manager TS II LEDs and Buttons
SMTS II for GPC-XP Technical Guide
Diagnostics Button Operation LED Update LED Screen Refresh LED Communications LED Suspend Button
A302-12
19
Page 20
APPENDIX
Military Time Conversion
Zone
Zone
Military Time Conversion
The main difference between regular and military time is how hours are expressed. Regular time uses numbers 1 to 12 and a.m. and p.m. to identify each of the 24 hours in a day. In military time, the hours are numbered from 0000 to 2300.
Military time is based on a 24-hour day. Hours are numbered 0000 through 2300 and are recorded fi rst. The last two digits indicate the minute after the hour. Military time does not exceed 2359 hours. For example, midnight is recorded as 0000, one minute past midnight is 0001, 1 a.m. is 0100, 1 p.m. is 1300, and so on.
Regular and military time express minutes and seconds in exactly the same way. When converting from regular to military time and vice versa, the minutes and seconds do not change.
Regular time requires the use of a.m. and p.m. to clearly identify the time of day. Since military time uses a unique two-digit number to identify each of the 24 hours in a day, a.m. and p.m. are unnecessary .
The following table summarizes the relationship between regular and military time.
Regular
Time
12:00 a.m. 0000 12:30 a.m. 0030
1:00 a.m. 0100 1:30 a.m. 0130 2:00 a.m. 0200 2:30 a.m. 0230 3:00 a.m. 0300 3:30 a.m. 0330 4:00 a.m. 0400 4:30 a.m. 0430 5:00 a.m. 0500 5:30 a.m. 0530 6:00 a.m. 0600 6:30 a.m. 0630 7:00 a.m. 0700 7:30 a.m. 0730 8:00 a.m. 0800
8:30 a.m. 0830 9:00 a.m. 0900
9:30 a.m. 0930 10:00 a.m. 1000 10:30 a.m. 1030 11:00 a.m. 1100
Military
Time
Regular
Time
11:30 a.m. 1130 12:00 p.m. 1200 12:30 p.m. 1230
1:00 p.m. 1300 1:30 p.m. 1330 2:00 p.m. 1400 2:30 p.m. 1430 3:00 p.m. 1500 3:30 p.m. 1530 4:00 p.m. 1600 4:30 p.m. 1630 5:00 p.m. 1700 5:30 p.m. 1730 6:00 p.m. 1800 6:30 p.m. 1830 7:00 p.m. 1900 7:30 p.m. 1930 8:00 p.m. 2000 8:30 p.m. 2030 9:00 p.m. 2100
9:30 p.m. 2130 10:00 p.m. 2200 10:30 p.m. 2230 11:00 p.m. 2300 11:30 p.m. 2330
Military
Time
Table 6, cont.: Military Time Conversion
VCM-X CoVCM-X Co
Table 6: Military Time Conversion
20
SMTS II for GPC-XP Technical Guide
Page 21
INDEX
A-N
ntrollersntrollers
24-Hour Military Format..........20
1111..........9
2222..........9
3333..........9
A
Address..........12
Alarm Button..........18
Function..........8
Alarm Settings..........18
Analog Input Details Screen..........13
Analog Inputs Screen..........13
Analog Output Detail Screen..........15
Analog Output Force Screen..........15
Analog Outputs Screen..........15
Arrow Keys, Defi ned..........8
Asterisks..........9
AVC Status..........15
B
Back Key, Function..........8
Backlight Intensity Percentage..........12
Backlight Timeout..........9
Belden #82760 wire..........4
Binary Input Force Mode Screen..........14
Binary Inputs Screen..........14
Broadcasting Time & Date..........11
Broadcast Time..........1 1
Button Descriptions..........8
Buttons
Alarm..........18
Diagnostics Button..........19
Holidays..........17
Login..........9
Reset Button..........19
Suspend..........4
Suspend Button..........19
C
Calibrate Sensor Data Entry Screen..........13
Care of System Manager TS..........4
Change Passcode Screen..........10
CLEAR <All Schedules>..........16
Clear Sensor Override..........14
Communications LED..........19
Confi guration Selection Buttons..........8
Confi guring GPC-XP Alarms..........18
D
Date..........11
Descriptions
Buttons..........8
Icons..........8
Diagnostics Button..........19
Dimensions..........5
Dipswitch Settings..........4
Down Arrow Key Function..........8
E
Edit Passcodes..........10
Environmental Requirements..........4
Esc Key Function..........8
F
Features..........3
Flush W all Mount..........4, 5
Force Analog Output..........15
Force Modes..........17
G
GPC-XP Alarms
Confi guring..........18
Enabling/Disabling..........18
GPC-XP Controller
Wiring to SMTS..........7
GPC-XP Controller Alarm Status
Screen..........18
H
Holidays..........17
Setting..........17
Viewing..........17
Holidays Button..........17
Holidays Schedule Screen..........17
I
Icons, Descriptions..........8
Installing
System Manager TS..........4
L
LCD Display
Described..........3
LEDs
Communications LED..........19
Operation LED..........19
Power LED..........19
Screen Refresh LED..........19
Update LED..........19
Level 0 Access..........10
Level 1 Access..........10
Level 1 Passcode..........9
Level 2 Access..........10
Level 2 Passcode..........9
Level 3 Access..........9, 10
Level 3 Passcode..........9
Logging In..........9
Login Icon
Description..........8
Login Screen..........9
M
Main Screen..........9
Main Screen Icon Functions..........8
Main Screen Icons
Login..........9
My System..........13
Set Time & Date..........11
Settings..........12
User Passcodes..........10
Menu Items
Edit Passcodes..........10
Military Time Conversion..........20
Mounting..........4
System Manager TS..........4
Mounting Pad Placement..........4
Multiple Managers..........12
My System Icon..........13
Description..........8
N
Navigation Button Functions..........8
Network..........12
SMTS II for GPC-XP Technical Guide
21
Page 22
INDEX
O-Z
Zone
Zone
O
OK Key
Function..........8
One to One Unit Connection..........12, 13
Operation LED..........19
OPT1 Dipswitch..........19
OPT4 Dipswitch..........19
Outdoor Status..........15
Override..........17
Override Reading..........14
P
Passcode
System Manager..........9
Passcode Level
9288..........10
Level 0..........10
Level 1..........10
Level 2..........10
Level 3..........10
Passcode Levels..........9
Passcodes
Changing..........10
Edit..........10
Editing..........10
Level 3..........9
Passcode Timeout..........9
Power LED..........19
Prism 2..........3, 18
R
Real-Time Clock..........3
Relay Force..........15
Relay Output Details Screen..........14
Relay Output Force Mode Screen..........15
Relay Outputs Screen..........14
Requirements
Environmental..........4
Reset Button..........19
Runtime Reset..........15
S
Schedule AUTO Mode..........17
Schedule FORCED OFF..........17
Schedule FORCED ON..........17
Schedule Override..........17
Schedules..........16
Setting..........16
Viewing..........16
Schedules & Holidays..........15
Schedule Times Screen..........16
Screen Refresh LED..........19
Secure System..........10
Selecting Units..........13
Selection Buttons
Defi ned..........8
SEND TO <All Days>..........16
SEND TO <W eekdays>..........16
Sensor Override Data Entry
Screen..........14
SET <24 Hr Mode>..........16
Set Clock Hour..........11
Set Time and Date..........11
Set Time & Date Icon
Description..........8
Set Time & Date Screen..........11
Settings Icon
Description..........8
Setting the System Clock..........11
Stand Alone..........12
Surface Mount..........6
Suspend Button..........4, 19
System Manager Address..........12
System Manager Passcode..........9
System Manager Passcode Levels
Screen..........10
System Manager Settings..........12
System Manager TS
Care of..........4
Components..........3, 4, 5, 6
Dimensions..........3, 4, 5, 6
Features..........3
Flush Wall Mount..........3, 4, 5
LEDs and Buttons..........19
Mounting..........4
Power Supply..........4
Surface Mount..........6
Wiring to GPC-XP..........7
System Manager Version..........12
T
Technical Support..........4
TERM Jumpers..........19
Time
Military Time Conversion..........20
Time and Date..........11
Setting..........11
Troubleshooting..........19
LEDs and Buttons..........19
U
Unit Selection..........13
Unit Selection Screen..........13
Up Arrow Key
Function..........8
Update LED..........19
User Passcodes Icon..........10
Description..........8
V
Viewing Alarm Status..........18
Viewing and Setting Holidays..........16
Viewing and Setting Schedules..........16
View Status Only..........9
W
Wiring..........4
GPC-XP Controller..........7
System Manager TS..........4, 7
WR-LL-WG-18..........4
22
SMTS II for GPC-XP Technical Guide
Page 23
NOTES
SMTS II for GPC-XP Technical Guide
23
Page 24
Form: OR-SMTSII-GPCXP-TGD-01A Printed in the USA May 2014 All rights reserved. Copyright 2014
WattMaster Controls Inc. 8500 NW River Park Drive Parkville, MO  64152 Phone: 866-918-1100 www.orioncontrols.com Fax (816) 505-1101
Loading...