Orion VCB-X, OE335-26B-VCBZ, OR-VCMXRNEOISD-TGD Technical Manual

www.orioncontrols.com
VCB-X Controller Code: SS1051 Version 2.00 & up
VAV/Zone Controller Code: SS1001, SS1005, SS1025
Requires Modular Service Tool SD Code: SS1063
Requires Modular System Manager SD Code: SS1064
VCB-X Controller
Operator Interface SD
Technical Guide
Zone
Zone
IMPORTANT NOTICE
This technical guide provides instructions for using the Modular Service Tool and Modular System Manager SD with the VCB-X & VAV/Zone Controllers only. If you are using a different controller, you can download the applicable SD Technical Guide listed below from our website— orioncontrols.com. The technical guides can also be printed from the SD card.
VCM-X & VCM-X E-BUS Controller - OR-VCMXRNEOISD-TGD RNE Controller - OR-VCMXRNEOISD-TGD SA E-BUS Controller - AA-SAOISD-TGD VCM Controller - OR-VCMOISD-TGD VAV/CAV and MUA II Controllers - OR-VAVCAVMUAOISD-TGD
SD CARD UPDATING INSTRUCTIONS
The Modular Service Tool and Modular System Manager are equipped with an SD memory card. This SD card can be removed and easily updated through a computer by downloading updates, as they become available, from our website to your computer.
In order to perform any updates, your computer needs an SD card drive or you will need to purchase an SD card adapter.
Download instructions are found in Appendix B on page 82 of this manual.
WattMaster Controls, Inc. 8500 NW River Park Drive · Parkville , MO 64152 Toll Free Phone: 866-918-1100 PH: (816) 505-1100 · FAX: (816) 505-1101 E-mail: mail@wattmaster.com Visit our website at www.orioncontrols.com
www.orioncontrols.com
®
AAON
is a registered trademark of AAON, Inc., Tulsa, OK. WattMaster Controls, Inc. assumes no responsibility for errors or omissions. This document is subject to change without notice. Form: OR-VCBXOISD-TGD-01Q Copyright March 2017 WattMaster Controls, Inc.
TABLE OF CONTENTS
OVERVIEW & SYSTEM CONNECTION ............................................................................... 4
Modular Service Tool ............................................................................................................................... 4
Modular System Manager SD ................................................................................................................. 6
MODULAR SERVICE TOOL SD ........................................................................................ 10
Display Screens and Data Entry Keys ................................................................................................... 10
Initialization & Setting the Time & Date ................................................................................................. 11
Setting the Operating Mode & Energy Timer ......................................................................................... 12
Alarm Search & Override Search .......................................................................................................... 13
Schedules & Holidays ............................................................................................................................ 14
Schedule Override ................................................................................................................................. 15
SYSTEM MANAGER SD ................................................................................................... 16
Display Screens and Data Entry Keys ................................................................................................... 16
Initialization & Setting the Time & Date ................................................................................................. 17
Setting the Operating Mode ................................................................................................................... 18
Changing Passcodes ............................................................................................................................. 19
Loop Search and System Alarm Search ................................................................................................20
Unit Alarm Search & Override Search ................................................................................................... 21
Schedules & Holidays ............................................................................................................................ 22
Schedule Override ................................................................................................................................. 23
PROGRAMMING ............................................................................................................... 24
VCB-X Confi guration Screen Index ....................................................................................................... 24
Confi guring VCB-X Controllers .............................................................................................................. 25
VCB-X Setpoint Screen Index ............................................................................................................... 40
Confi guring VCB-X Setpoints ................................................................................................................ 41
VCB-X Status Screen Index .................................................................................................................. 56
VCB-X Status Screens .......................................................................................................................... 57
VAV/Zone Confi guration Screens .......................................................................................................... 66
VAV/Zone Setpoint Screens .................................................................................................................. 69
VAV/Zone Status Screens ..................................................................................................................... 73
VAV/Zone Damper Force Modes ........................................................................................................... 75
MiniLink PD Confi guration Screens ....................................................................................................... 76
MiniLink PD Status Screens .................................................................................................................. 77
TROUBLESHOOTING ....................................................................................................... 78
VCB-X Outputs Force ............................................................................................................................ 78
APPENDIX A - SAVING, LOADING, AND COPYING SETPOINTS ..................................... 80
APPENDIX B - UPDATING YOUR SD MEMORY CARD ..................................................... 82
APPENDIX C - UPDATING CONTROLLERS & E-BUS MODULE SOFTWARE .................... 83
INDEX .............................................................................................................................. 85
VCB-X Operator Interface SD
3
SYSTEM CONNECTION
Modular Service Tool SD
Modular Service Tool SD
The OE391-12 Modular Service Tool is a system operator interface that provides a direct link to enable the system operator to view the status, confi gure, and adjust the setpoints of the VAV/CAV, MUA, VCB-X, VCM, VCM-X, VCM-X E-BUS, RNE, SA E-BUS or VAV/Zone Con­troller on the control system communications loop. However, this manual only applies to VCB-X and VAV/Zone Controllers. See note in the inside front cover for the list of manuals that pertain to other controllers.
The Modular Service Tool is housed in an attractive black plastic enclo­sure. The display area is covered with a clear plastic bezel for protec­tion of the display screen. The Modular Service Tool has a 4-line-by­20-character display panel with adjustable contrast control and a 27-key membrane keypad for data selection and entry. All keypad operations are simple and straight forward, utilizing non-cryptic plain English language messages. Menu-driven programming allows for easy setup and operation without the need for specialized training. The Modular Service Tool is supplied with a programmable 4 Gigabyte SD memory card, (4) AA 1.5 V batteries, a wall mount, a DC power supply, a mini­Din communication cable, and an E-BUS communication cable. The mini-Din cable allows you to connect the Modular Service Tool to any Orion controller which has a mini-Din connector socket for program­ming, monitoring, and troubleshooting purposes.
Zone
Zone
The Modular Service Tool is also equipped with an EBC E-BUS port and an RS-485 three conductor terminal block port. The E-BUS port and included E-BUS cable are used for updating E-BUS Module software (described in Appendix C). The RS-485 port is used for hard-wiring to older controllers that do not have a mini-DIN connector socket.
The Modular Service Tool is designed to be hand-carried. Its rugged plastic housing provides superior protection for the electronic compo­nents housed inside. The Modular Service Tool is a top-quality service tool that will stand up to the demands of the typical job site environment for many years.
Figure 1: Modular Service Tool SD Dimensions
4
VCB-X Operator Interface SD
SYSTEM CONNECTION
Modular Service Tool
Modular Service Tool
Whether you have a Stand Alone, Interconnected, or Networked VCB-X Control System, the Modular Service Tool always connects to the controller via a prefabricated cable that is supplied with the service tool. The Modular Service Tool cable is terminated on both ends with a mini-DIN connector. Attach one end to the Modular Service Tool and the other end to the mini-DIN connector on the controller. If this is an Interconnected System, all controllers that are interconnected with com­munications cable can be programmed from any controller on the loop. If this is a Networked System, all controllers on the entire Networked System can be programmed from one controller.
Male DIN Connector
Connector Cable
RS-485 Port
Be sure that the Modular Service Tool has fresh batteries installed or
that it is connected to a power source using the supplied power pack
before attempting any programming of the controller. See Figure 2 for
connection details.
Female DIN Connector
Typical Controller Board
EBC E-BUS Port
The Modular Service Tool Can Be Connected To Or VAV/Zone Controlle r By Plugging One End Of The Supplied Cable Into the Modular Service Tool DIN Connector And The Other End Into The DIN Connector On The Controllers.
A Unit Controller
SD Memory Card
Figure 2: Modular Service Tool SD
VCB-X Operator Interface SD
Power On Button
Modular Service Tool SD
Be Sure The Modular Service Tool Is Connected To The Supplied Power Pack Or Has Fresh Batteries Installed Before Attempting Programming Of The Controller. Be Sure The Power Is Turned Off On The Modular Service Tool Before Connecting The Cable To The Controller.
5
SYSTEM CONNECTION
Modular System Manager SD
Zone
Zone
Modular System Manager SD
9.00"
13
2
5
6
4
708
9
DEC
MINUS
-
UP
PREV
ESC
DOWN
ENTER
Figure 3: Modular System Manager SD Dimensions
STATUS
SETPOINTS
NEXT
SCHEDULES
CLEAR
OVERRIDES
ALARMS
6.25"
1.81"
The OE392-12 Modular System Manager SD provides a direct link to enable you to view the status and adjust the setpoints of the VCM-X, VCM-X E-BUS, VCB-X, RNE, SA E-BUS, VCM, VAV/CAV, MUA II or VAV/Zone Controller on the control system communications loop. The System Manager SD is housed in a beige-colored plastic enclosure. The System Manager has a programmable 4 Gigabyte SD card and is equipped with a 4-line-by-20-character backlighted display panel and a 24-key membrane keypad for data selection and entry. All keypad operations are simple and straight forward, utilizing non-cryptic plain English language messages. Menu-driven programming allows for easy setup and operation without the need for specialized training. The System Manager also has 2 integral LEDs for user notifi cation of system alarm conditions and override initiations. Protection from unauthorized users is provided by the System Manager’s integral multi-level passcode authorization programming.
On a Networked System, the Modular System Manager is connected to the communications and power loop of the system via modular cables that simply plug into the System Manager board and the Power/Comm Distribution Board. This virtually eliminates wiring errors and makes installation fast and easy. When it is to be connected to a Stand-Alone system, a cable with modular connectors on one end and stripped wire ends on the other end is provided to facilitate connecting communications and power to the Modular System Manager from the 24 VAC power source and the HVAC unit controller communication wiring terminals.
The Modular System Manager is designed for wall mounting. Mounting holes are provided to attach the Modular System Manager to a standard handy box. It is recommended that the System Manager be mounted at approximately eye level to allow for ease of programming and reading of the display. The System Manager is typically mounted in the build­ing manager’s or superintendent’s offi ce or in an equipment room. The attractive enclosure is quite suitable for mounting in any location.
6
VCB-X Operator Interface SD
SYSTEM CONNECTION
Modular System Manager SD Network Connection
Network Connection
As previously described, when you are connecting the Modular System Manager to a Networked System, the Modular System Manager is con­nected to the communications and power loop of the system via modular cables. These cables simply plug into the System Manager board and to any device with modular connectors on any local loop on the system. Devices with modular connectors include the Power/Comm Distribution Board, VAV/Zone controller, and MiniLink Polling Device. By using these plug-in connections, wiring errors are virtually eliminated and system installation is fast and easy. See Figure 4 below for typical con- nection information. See Figure 5 on page 8 for typical Power/Comm board wiring and connection information.
24VAC Transformer
(By Others)
Modular System Manager SD Back View
Line
Rated for 6 VA
GND
24VAC
When the System Manager is to be connected to a Stand Alone system,
a 12-foot cable with modular connectors on one end and stripped wire
ends on the other end is provided for this purpose. This is used to fa-
cilitate connecting communications and power wiring to the Modular
System Manager from a 24 VAC power source and to the HVAC unit
controller communication wiring terminals. See Figure 6 on page 9
for wiring details. If the supplied cable wire is not long enough for
your installation, a standard modular cable of the correct length can
be purchased through WattMaster and one of the modular connectors
can be cut off to allow for the transformer and communication terminal
wiring connections. It is recommended that you do not splice the com-
munications wire if at all possible. The transformer should be rated at
6 VA minimum power output.
If Desired, Instead Of Using A Power/Comm Cable, You Can Use 2 Conductor Twisted Pair With Shield Cable To Connect To The Power/ Comm Board.
All Comm Loop Wiring Is
Straight Thru
T
T
T
Local Loop RS-485
9600 Baud
SH
SH
R
R
T
SH
SH
R
R
NOTE: For Stand-Alone Installations (No CommLink or MiniLink), All TERM Jumpers Must Be ON. For All Applications With CommLink(s) Or MiniLink(s), All Jumpers Must Be OFF.
GB
4
Power/Comm Cables To Power/Comm Board, MiniLink Polling Device Or VAV/Zone Controllers On Local Loop.
Distribution
All Modular Power/Comm Cables Are To Be WattMaster Part Number PCC-xx Or PCCE-xx Cables.
Figure 4: Modular System Manager SD - Network
VCB-X Operator Interface SD
7
SYSTEM CONNECTION
Power/Comm Board Wiring
Zone
Zone
WARNING!
DO NOT GROUND THE 24V TRANSFORMER THAT IS TO BE USED WITH THE POWER/COMM BOARDS. GROUNDING OF THE TRANSFORMER WILL DAMAGE THE POWER/COMM BOARD AND ALL BOARDS CONNECTED TO IT. A SEPARATE TRANSFORMER MUST BE USED FOR EACH POWER/COMM BOARD. NO EXCEPTIONS. DO NOT CONNECT ANY OTHER DEVICES TO THE TRANSFORMER USED FOR THE POWER/COMM BOARD!
Line Voltage
24VAC
24VAC Transformer (By Others)
4 Amp Slow Blow Fuse
A Power/Comm Connect With The MiniLink PD Instead
2 Conductor Twisted Pair With Shield
Using Cable A Power/Comm
. You Can Also Use Cable To Connect With Board, A System Manager Or A VAV/Zone Controller.
Cable Can Be Used To
Another Power/Comm
Local Loop RS-485
C US
R
Of
If Desired, Instead Of Using A Power/Comm Cable, You Can Use 2 Conductor Twisted Pair With Shield Cable To Connect To The Power/ Comm Board From The Unit Controller, MiniLink PD, Or Another Power/Comm Board.
All Comm Loop Wiring Is
9600 Baud
T
SH
R
Straight Thru
T
SH
R
T
T
SH
SH
R
R
NOTE: Diagram Shown Is For Wiring Of Power/Comm Board When Used For Connecting Local Loop Devices Such As VAV/Zone Controllers, System Manager(s) and Other Power/Comm Boards.
Figure 5: Typical Power/Comm Board Wiring
8
Power/Comm Cable To Power/Comm
System Manager, Or VAV/Zone Controllers On Local Loop Only.
Other Board(s),
VCB-X Operator Interface SD
Local Loop RS-485
9600 Baud
SYSTEM CONNECTION
Stand Alone Connection
NOTE: You Can Use The Three Conductor Communications Terminal Block or a Modular Connection to Connect to the Controller Board. One or the Other Option Can Be Used, Not Both. Alternatively, for Network Connections, A Power Comm Board Can Be Used. See Note Below.
24VAC Transformer
(By Others)
Line
Rated for 6 VA
GB
4
Modular System Manager SD Back View
GND
24VAC
Local Loop
RS-485
9600 or 57,600
Baud
Controller Board
T
SHLD
R
All Comm Loop Wiring Is
Straight Through
T
T
SH
SH
R
R
T
T
SH
SH
R
R
NOTE: If Desired A Power/Comm Board As Used With The Networked System Can Be Installed And Wired Instead Of Using The Pigtail Cable Wiring Shown Below. See The Networked System Wiring Diagram For Details.
Use Supplied Modular Cable With Stripped Ends For Connection To Terminal Block And Transformer
WHITE (T) DRAIN WIRE (SHLD) BLACK (R) RED (24 VAC) BROWN (GND) GREEN (GND)
Rated For 6 VA Minimum
Class 2 Transformer
NOTE: For Stand-Alone Installations (No CommLink or MiniLink), All TERM Jumpers Must Be ON. For All Applications With CommLink(s) Or MiniLink(s), All Jumpers Must Be OFF.
T SHLD
R
Controller Board
Figure 6: Modular System Manager SD - Stand Alone
VCB-X Operator Interface SD
9
MODULAR SERVICE TOOL SD
Modular Service Tool Keys
Operator Interfaces
In order to confi gure and program the VCB-X Controller, you must have an Operator’s Interface or a personal computer with the Prism 2 computer front-end software installed. Two different Operator Interfaces are available for programming of the VCB-X Controls System—the Modular Service Tool SD and/or the System Manager TS. These de­vices allow you to access the status and setpoints of any controller on your communications loop. This manual describes the Modular Service Tool SD. If using the System Manager TS II, please see the System
Manager TS II Technical Guide. If using Prism 2, please see the Prism 2 Technical Guide.
The Modular Service Tool allows you to view any input or output status and change any setpoint to fi ne-tune the operations of the total system. All keypad operations are simple and straightforward, utilizing non­cryptic plain English messages.
Display Screens & Data Entry Keys
See the chart below for a list of the keypad descriptions and functions.
Keypad
Key Function
Description
ESC
ENTER
Clear
Minus
DEC

Use this key to exit from screens or
from data entry or to return to the
Main Screen from any screen in the
system.
Use this key to enter a new value.
If a data entry mistake is made,
press this key to clear the data entry
eld and start over. This key also
turns off the power to the Service
Tool when on the
Main Screen
If a setpoint with a negative value
is required, press this key for the
minus sign.
Press this key when entering data
that requires a decimal point.
Use these keys to change values
in the Confi guration Screens as
prompted.
Use these keys to step backward or
forward through the screens.
Mode Selection Buttons
The Modular Service Tool is provided with “Mode Selection Buttons.”
These buttons give you instant access to the specifi c mode desired without
having to scroll through several menu screens to get there.
Button
Description
STATUS
SETPOINTS
SCHEDULES
OVERRIDES
ALARMS
CONFIGURATION
BALANCE-TEST
Notes:
(1) The Modular Service Tool will only search the Overrides one loop at a time. You must enter the Loop number and the MiniLink PD unit ID (60).
Table 2: Button Descriptions
Mode Selection Buttons
Pressing this button takes you
directly to the controller
“Status” screens.
Pressing this button takes you
directly to the controller
“Setpoints” screens.
Pressing this button takes you
directly to the controller
“Schedules” screens.
Pressing this button takes you directly to the controller “Over­rides” screen. See the “Override
Button” section on page 21 for a
description of this function.
See Note 1 below.
Pressing this button takes you
directly to the controller
“Alarms” screen. See the “Alarms
Button” section on page 20 for a
description of this function.
Pressing this button takes you
directly to the controller
“Confi guration” screens.
Pressing this button takes you
directly to the controller
“Balance-Test” screens.
Table 1: Keypad Descriptions
10 VCB-X Operator Interface SD
MODULAR SERVICE TOOL SD
Initialization & Setting the Time & Date
Modular Service Tool Initialization
Modular Service Tool Initialization Screen and Setup Screens
After connecting the Service Tool to the controller with the supplied cable, press <ON>. The Initialization Screen will appear followed by the Setup Screens as shown below. If there is no SD card installed, the second screen will display, “No SD Card Connected! Powering Down!”
Initializing
Service Tool vX.XX
WattMaster Controls
1) Set Time & Date
2) Communications
NEXT) More Options
ESC) Exit Menu
3) Energy Saving
4) Update Software
NEXT) More Options
ESC) Exit Menu
Although the times are displayed on the Main Screen in a standard 12-hour format, you must program them using the 24-hour military format. If you confi gured the VCB-X Controller to use its own Internal Schedules, the Occupied/Unoccupied modes are calculated on the basis of the current real time clock reading.
The two screens that follow will appear. To scroll through the fi elds, press
<> or <ENTER>. In order to save a new value, you must
press
<ENTER>.
Program Time/Date
Day (Sunday=0): X Enter Hr. (0-23): XX Enter Minutes : XX
Day - Enter the Day of the Week (0 to 6) Sunday = 0
Hours (Hr) - Enter Hours in 24-Hour Military Format (1700 = 5:00 PM)
Minutes - Enter the Minutes (0 to 59)
Programming the Date
NOTE: Once you press <ESC> while at the Setup Screens shown
above, you can access them again by pressing or cycling power.
<NEXT>
Setting The Time & Date
The Modular Service Tool is equipped with a real time clock chip allowing it to maintain the correct time. Once you have programmed the correct time and date, the information is broadcast globally to all controllers on the entire system.
NOTE: If you are in a time zone that has daylight savings, you
will need to manually adjust the time twice a year.
Programming the Time
From the Setup Screen shown below, press <1> on your keypad to access the Set Time & Date Screens.(You may have to press <NEXT> to access this screen).
1) Set Time & Date
2) Communications
NEXT) More Options
ESC) Exit Menu
To scroll through the fi elds, press <> or <ENTER>. In order to save a new value, you must press <ENTER>.
Program Time/Date
Month (1-12): XX Day (1-31): XX Year (00-99): XX
Month - Enter the Month (1 to 12)
Day - Enter the Day of the Month (1 to 31)
Year - Enter the current Year with two digits (00 to 99)
When you have fi nished programming the time and date, press <ESC> to return to the Setup Screen shown below.
1) Set Time & Date
2) Communications
NEXT) More Options
ESC) Exit Menu
VCB-X Operator Interface SD
11
MODULAR SERVICE TOOL SD
Setting the Operating Mode and Energy Saving Timer
Setting the Operating Mode
The Operating Mode is displayed on the last line of the Main Screen as shown below. The factory default setting for the Service Tool is LS (Low Speed) Stand Alone Mode. LS Stand Alone Mode is the correct confi guration for the VCB-X Controller when in Stand Alone Mode.
Service Tool SD vX.XX
01/16/15 02:21 PM
LS Stand Alone
No Communication
If you are using this Service Tool on a communications loop and have an installed MiniLink PD or CommLink, you will need to change the setting to LS (Low Speed) Network Mode.
If you are using a VCB-X Controller that is set for high speed, you will need to change the setting to HS (High Speed) Stand Alone Mode or HS (High Speed) Network Mode.
If your display indicates a different mode than the one you need, press
<2> at the Setup Screen shown below. You may have to press <NEXT>
to access this screen.
1) Set Time & Date
2) Communications
NEXT) More Options
ESC) Exit Menu
The Communications Screen will appear as shown below.
Setting the Energy Saving Timer
The Modular Service Tool has a built-in timer that can be programmed to shut the Service Tool off after a specifi ed period of time if no buttons are pressed. This is a very useful feature if you are powering the Service Tool from the internal batteries.
To set the Energy Saving Timer, press <NEXT> at the fi rst Setup Screen and <3> at the second Setup Screen shown below. (You may have to press
<NEXT> to access these screens).
1) Set Time & Date
2) Communications
NEXT) More Options
ESC) Exit Menu
3) Energy Saving
4) Update Software
NEXT) More Options
ESC) Exit Menu
The Energy Saving Screen will appear as shown below:
Energy Saving
Automatic Power Down
Minutes: xx
Press ESC to Exit
Stand Alone Mode Lo Speed Connection Use Left/Right Arrow To Change Selections
Press <> or <> to select the proper mode of operation.
When you have made your selection, press screen will appear.
You Have Changed The
System Mode
Press Any Key To
Continue
Press any key to continue. The Setup Screen will appear as shown below:
1) Set Time & Date
2) Communications
NEXT) More Options
ESC) Exit Menu
<ENTER>. The following
Enter the number of minutes you want the Service Tool to stay active before it automatically powers down and press <ENTER>. To cancel the automatic power down, enter <99> and press <ENTER>. After you have entered a number between 1 and 99 minutes, press to exit the screen.
The Setup Screen will appear again as shown below:
1) Set Time & Date
2) Communications
NEXT) More Options
ESC) Exit Menu
<ESC>
12 VCB-X Operator Interface SD
MODULAR SERVICE TOOL SD
Alarm and Override Search
Modular Service Tool Alarm Search
NOTE: When you press the <ALARMS> button on the Modular
Service Tool, it will search only the unit ID that you have entered; therefore, you must search each unit individually to access all alarms for that controller.
To search for alarms, press < ALARMS> while on any screen but the Main Screen. The Unit Selection Screen will be displayed.
Enter Unit Address
Then Press Enter
Selected Unit#: XXXX
No Communication
Enter the Unit ID of the controller the Service Tool is connected to and press <ENTER>. Once communication is established, “No Communica-
tion” will be replaced with “Press Down.” Then
NOTE: If “No Communication” remains, it indicates a
communication failure to the controller.
One of the following screens will appear:
press <>.
Modular Service Tool Override Search
When a space sensor with override option is used with any VAV/Zone or Unit Controller, the Modular Service Tool can determine and report any controllers that are currently operating in an override condition on a specifi c Loop by entering a Loop ID number and then doing a search.
NOTE: When you press the <OVERRIDES> button on the
Modular Service Tool, it will search only the Loop number that you enter; therefore, you must search each loop individually to access all overrides.
To access the Overrides Screen, press Modular Service Tool’s keypad. A screen will appear asking you to enter the unit ID.
Enter Unit Address
Then Press Enter
Selected Unit#: XXXX
No Communication
Enter the Unit ID for the MiniLink PD (MLPD) of the loop you wish to search and press each loop. So the unit ID of any particular MLPD would be the loop number followed by 60. In the example above, Loop 1, address 60 has been entered. Once communication is established, “No Communication”
will be replaced with “Press Down.” Then
<ENTER>. The MLPD is always address 60 on
<OVERRIDES> from the
press <>.
VCB-X V.XXX
NO ALARMS
VCB-X V.XXX
ALARMS PRESENT
SCROLL DOWN TO VIEW
Press <> to scroll through all the alarms for the controller that the Modular Service Tool is connected to.
To clear any alarms that are found, you must fi x the problem indicated in the alarm. Once the problem is fi xed, the alarm will clear from the screen the next time the unit is polled.
NOTE: If “No Communication” remains, it indicates a
communication failure to the controller.
Once communications are successful, one of the following screens will appear:
VCB-X V.XXX
NO OVERRIDES
VCB-X V.XXX
OVERRIDES PRESENT
SCROLL DOWN TO VIEW
After the Service Tool completes its search, it will post a message to tell you if there are overrides present. If there are overrides, press
and all units on the loop will be listed showing ‘Override: Yes or No.’ Press <OVERRIDES> again to access overrides on a different loop. Enter the Unit ID of the MLPD of that loop.
<>
VCB-X Operator Interface SD
13
MODULAR SERVICE TOOL SD
Schedules and Holidays
Scheduling
You can access the Unit Controller Scheduling Screens by pressing
<SCHEDULES>. The Unit Selection Screen will be displayed.
Enter Unit Address
Then Press Enter
Selected Unit#: XXXX
No Communication
Enter the Unit ID of the controller the Service Tool is connected to and press
<ENTER>. Once communication is established, “No Communica-
tion” will be replaced with “Press Down.” Then
NOTE: If “No Communication” remains, it indicates a
communication failure to the controller.
Press the
<> button and then press <ENTER> to access the schedul-
ing function you wish to view.
Schedule Menu Schedule Override Week Schedules Holidays
press <>.
The screens will step through the Start Time and then the Stop Time for each day of the week. You can quit at any point in the process by pressing <ESC>. There are two Start/Stop events available per day, so the screen will show which event is being programmed. If you need only one event, keep Event #2’s times set at ZERO.
All times are in 24-hour military format, so 5:00 PM would be entered as 1700.
If both the Start and Stop Times are ZERO, the schedule is in a continu­ous OFF mode. (Also, use for Remote Forced Occupied applications
using the Forced Occupied Binary Input.)
If both the Start and Stop Times are 2359, the schedule is in a continu­ous ON mode.
NOTE: The second line displays which day of the week is cur-
rently being programmed. The day of the week automati­cally increments as you exit the Event #2 screen for the day and continue to the next day’s Event #1 screen.
CAUTION: The controller ships with all schedules set to
zero so that the controller will not attempt to heat or cool before you have confi gured the system.
Week Schedules
Event #1
VCB-X Schd
Sunday Event #1 Start Time..: XXXX Stop Time...: XXXX
Event #2
VCB-X Schd
Sunday Event #2 Start Time..: XXXX Stop Time...: XXXX
If you are using the internal scheduling capability of the Unit Control­ler, set the schedule hours and holiday periods from the menu shown above. You can also force the unit to operate continuously in occupied or unoccupied mode by selecting the Schedule Override menu item and entering the desired command.
If you are using an external contact closure to signal the occupied mode, you must access the Week Schedule Screens and set all start and stop times to zero to prevent the internal schedule from turning the equipment on when you don’t want it to operate.
Holiday Start/Stop Day Selection
VCB-X Hldy
Holiday # 1 Start Mon/Day.: XXXX [ July 4
Stop Mon/Day.: XXXX [ July 5
The screens will step through the fourteen possible holidays, one period at a time. Line 2 shows which holiday is currently being programmed. Since a holiday period can encompass more than one day, you need to program the day the holiday starts and the day the holiday ends. If your holiday only lasts one day, simply set both the Start Day and the Stop Day to the same value. Remember to combine the month and day into a single four-digit value.
EXAMPLE: 704 = July 4
1225 = December 25
th
= 704 ]
VCB-X Hldy
Holiday # 1
th
= 705 ]
th
(NOTE: Leading zero not required)
th
14 VCB-X Operator Interface SD
MODULAR SERVICE TOOL SD
Holiday Scheduling and Schedule Override
Holiday Start/Stop Times
VCB-X Hldy
Holiday Schedule Start Event #1: XXXX Stop Event #1: XXXX
VCB-X Hldy
Holiday Schedule Start Event #2: XXXX Stop Event #2: XXXX
The fourteen holidays all use the same Start and Stop times which you program on this screen and the next. You must enter the time in 24-hour military format, the same as a regular week schedule.
Normally, the holidays will operate in an unoccupied mode or a reduced schedule mode. There are two start/stop events available on holidays to match the standard schedule number of events.
Schedule Override
VCB-X Ovrd
Schedule Override Enter Override...: X [0=Auto 1=ON 2=OFF]
If you want to force the unit to operate in a continuous Occupied or Unoccupied mode, select this menu item to activate the desired method. If a Schedule Override is active, all other methods of schedule control are ignored (Push-Button, Internal, and Remote).
As you can see on the last line of the display, enter ously in the Occupied Mode or <2> to run continuously in the Unoc­cupied Mode. To restore normal schedule operations, enter <0>.
This override remains in effect until canceled and does not time-out like the Output Overrides do after 10 minutes of no communications.
NOTE: Do not use the Force OFF mode in place of setting all
the week schedules to ZERO if you are using a Remote Signal for your scheduling since the Override has priority over the Remote Signal.
<1> to run continu-
VCB-X Operator Interface SD
15
MODULAR SYSTEM MANAGER SD
System Manager SD Keys and Buttons
Zone
Zone
Operator Interfaces
In order to confi gure and program the Orion System controllers, you must have an Operator’s Interface or a personal computer with the Prism 2 computer front-end software installed. Three different Operator Inter­faces are available for programming of the Orion Controls System—the Modular Service Tool SD, the Modular System Manager SD, and/or the System Manager TS II. These devices allow you to access the status and setpoints of the controllers on your communications loop. This manual describes the Modular System Manager SD. If using the Modular Service Tool SD, please see the Modular Service Tool SD Quick Start Guide. If using the System Manager TS II, please see the System Manager TS II Technical Guide. If using Prism 2, please see the Prism 2 Technical Guide.
The Modular System Manager SD allows you to view any input or output status and change any setpoint to fi ne-tune the operations of the total system. All keypad operations are simple and straightforward, utilizing non-cryptic plain English messages.
Display Screens & Data Entry Keys
See the chart below for a list of the keypad descriptions and functions.
Key Function
Keypad
Modular System Manager SD
Description
ESC
ENTER
Clear
Minus
DEC

Use this key to exit from screens or from data
entry or to return to the Main Screen from
any screen in the system.
Use this key to enter a new value.
If a data entry mistake is made, press this key
to clear the data entry fi eld and start over.
If a setpoint with a negative value is required,
press this key for the minus sign.
Press this key when entering data that re-
quires a decimal point.
Use these keys to change values in the Con-
guration Screens as prompted.
Use these keys to step backward or forward
through the screens.
Mode Selection Buttons
The Modular System Manager is provided with “Mode Selection But­tons.” These buttons give you instant access to the specifi c mode desired without having to scroll through several menu screens to get there.
Button
Description
STATUS
SETPOINTS
SCHEDULES
OVERRIDES
ALARMS
Notes:
(1) This button only functions when the system is confi gured for “Network Mode” or “Multiple MGRS Mode.” It will not function in “Stand Alone Mode.”
(2) The “Search for Units” function must be performed on the System Manager upon initial system setup before this function will be available. See the “Network Mode & Multiple Managers Loop Search” on page 20 of this manual for complete instructions on performing a loop search.
Table 4: Button Descriptions
Modular System Manager SD
Pressing this button takes you directly to
the controller “Status” screens.
Pressing this button takes you directly to
the controller “Setpoints” screens and
“Confi guration” menu.
Pressing this button takes you directly to
the controller “Schedules” screens.
Pressing this button takes you directly to
the controller “Overrides” screen. See the
“Override Button” section on page 21 for a
description of this function.
See Notes 1 & 2 below.
Pressing this button takes you directly to
the controller “Alarms” screen. See the
“Alarms Button” section on page 20 for a
description of this function.
See Notes 1 & 2 below.
Table 3: Keypad Descriptions
16
VCB-X Operator Interface SD
MODULAR SYSTEM MANAGER SD
Initialization & Setting the Time & Date
System Manager SD Initialization
System Manager SD Initialization Screen and Setup Screens
After connecting the System Manager to the controller with the supplied cable, press <ON>. The Initialization Screen will appear followed by the Setup Screens as shown below. If there is no SD card installed, the second screen will display, “No SD Card Connected! Powering Down!”
NOTE: After exiting these screens, you can access them again
by pressing <ESC> and then <> or by cycling power.
INITIALIZING
System Manager SD
vX.XX
WattMaster Controls
1) Set Time & Date
2) Communications
NEXT) More Options
ESC) Exit Menu
Programming the Time
From the Setup Screen shown below, press <1> on your keypad to ac-
Set Time & Date Screens.
cess the
1) Set Time & Date
2) Communications
NEXT) More Options
ESC) Exit Menu
Although the times are displayed on the Main Screen in a standard 12-hour format, you must program them using the 24-hour military format. If you confi gured the Unit Controller to use its own Internal Schedules, the Occupied/Unoccupied modes are calculated on the basis of the current real time clock reading.
The two screens that follow will appear. To scroll through the fi elds, press <> or
<ENTER>. In order to save a new value, you must
press <ENTER>.
Program Time/Date
Day (Sunday=0): X Enter Hr. (0-23): XX Enter Minutes : XX
3) Change Passcodes
4) Loop Search
NEXT) More Options
ESC) Exit Menu
5) Alarm Search
NEXT) More Options
ESC) Exit Menu
Setting The Time & Date
The System Manager SD is equipped with a real time clock chip allowing it to maintain the correct time. Once you have programmed the correct time and date, the information is broadcast globally to all controllers on the entire system.
NOTE: A Level 1 or Level 2 User can set the time and date.
NOTE: If you are in a time zone that has daylight savings, you
will need to manually adjust the time twice a year.
Day - Enter the Day of the Week (0 to 6) Sunday = 0
Hours (Hr) - Enter the Hour (0-23) in 24-Hour Military Format (13 = 1:00 PM)
Minutes - Enter the Minutes (0 to 59)
Programming the Date
To scroll through the fi elds, press <> or <ENTER>. In order to save a new value, you must press
Program Time/Date
Month (1-12): XX Day (1-31): XX Year (0-99): XX
<ENTER>.
Month - Enter the Month (1 to 12)
Day - Enter the Day of the Month (1 to 31)
Year - Enter the current Year (0 to 99)
VCB-X Operator Interface SD
When you have fi nished programming the time and date, press <ESC> to return to the Setup Screen.
17
MODULAR SYSTEM MANAGER SD
Setting the Operating Mode
Zone
Zone
Setting the Operating Mode
The Operating Mode is displayed on the last line of the Main Screen as shown below. The factory default setting for the System Manager is LS (Low Speed) Stand Alone Mode.
System Manager SD 01/16/15 02:21 PM
LS Stand Alone
No Communication
The System Manager must be confi gured for the correct mode of op- eration for your system. There are 5 modes of operation available for the Orion System—LS (Low Speed) Stand-Alone, HS (High Speed)
Stand-Alone, LS (Low Speed) Network, HS (High Speed) Network, and LS (Low Speed) & HS (High Speed) Multiple MGRS.
If you are using this System Manager on a communications loop that doesn’t have a MiniLink PD or CommLink connected to it and you have a single System Manager on your system, then you need to operate in LS (Low Speed) Stand-Alone Mode. If you are using a VCB-X Controller or GPC-XP Controller that is set for high speed, and you don’t have a MiniLink PD or CommLink connected to the loop, then you will need to change the setting to HS (High Speed) Stand Alone Mode.
If you are using the System Manager on a communications loop and have an installed MiniLink PD or CommLink, you will need to change the setting to LS (Low Speed) Network Mode. If you are using a VCB­X Controller or GPC-XP Controller that is set for high speed, and are using a MiniLink PD or CommLink, then you will need to change the setting to HS (High Speed) Network Mode.
THIS ACTION REQUIRES
A SPECIAL HIGH LEVEL
PASSCODE CLEARANCE
Enter: XXXXXXX
Enter the seven digit passcode <2337377> to access the next screen.
You will then see the screen below displayed.
Stand Alone Mode Lo Speed Connection Use Left/Right Arrow To Change Selections
Press <> or <> if you need to change the mode of op-
eration to LS (Low Speed) Stand-Alone, HS (High Speed) Stand-Alone, LS (Low Speed) Network, HS (High Speed) Network, LS (Low Speed) Multiple Manager or HS (High Speed) Multiple Manager and then press <ENTER> to save
your selection. If you are not using Multiple Manager Mode, press
<ESC> at the screen below and continue scrolling right and left.
Multiple Manager
Unit Address: 0
Press ESC to Exit
If you are using this System Manager on a communications loop, have a MiniLink PD or CommLink installed, and have multiple System Manag­ers, then you need to operate in Multiple MGRS Mode.
If your display indicates a different mode than the one you need, press
<2> at the Setup Screen shown below. You will have to cycle power to
get to this screen or by pressing <ESC> and <PREV>.
1) Set Time & Date
2) Communications
NEXT) More Options
ESC) Exit Menu
The Passcode Clearance Screen will appear as shown below.
For Multiple MGRS Mode, enter the address at which you want this particular System Manager to be set.
When multiple System Managers are used on a local loop, each must be set with a unique address different from any other device on that loop. You must perform this same operation again for each System Manager installed. If you want one of these System Managers to be able to indicate alarms and overrides for the entire system, you must select either LS or HS Network Mode on that particular System Manager.
Once you have the correct number per the display above displayed, press
<ENTER>. The following screen will appear telling you that you have
changed the system mode:
You Have Changed The
System Manager Mode
Press Any Key To
Continue
Press any key on the keyboard to exit this screen.
18
VCB-X Operator Interface SD
MODULAR SYSTEM MANAGER SD
Changing Passcodes
System Manager Passcodes
Changing the mode of operation, updating software, changing schedules, and changing setpoints and confi gurations require passcode clearance. The screen below will appear if this action requires passcode clearance.
THIS ACTION REQUIRES
PASSCODE CLEARANCE
Enter Passcode: XXXX
The System Manager has three levels of user access. All users can view Status Screens. Level 1 users are limited to changing the Time and Date and Operating Schedules. Level 2 users have complete system access. Any status or setpoint fi eld can be read or reset from the System Manager.
These two levels of passcodes are programmable by any Level 2 user. The default Level 1 passcode is “ 1111” and the default Level 2 passcode is “ 2222.”
If you wish to change either Level 1 or Level 2 passcodes, please see the instructions that follow.
From the Main Status Screen, press The following screen will appear:
<ESC> and then press <PREV>.
Passcodes can only be changed by a Level 2 user. Enter the passcode and press
This screen allows you to enter new Level 1 and/or Level 2 passcodes. Passcodes must always be four digits in length, so the usable range of numbers is 1000 to 9999.
<ENTER>. The following screen will appear:
Enter New Passcode
Level 1.....: XXXX
Level 2.....: XXXX
[Must Be 4 Digits]
CAUTION: If you change the Level 2 passcode and can- not remember what it is, you will be locked out of your system!
1) Set Time & Date
2) Communications
NEXT) More Options
ESC) Exit Menu
Press <> for the Next Menu. The following screen will be displayed:
3) Change Passcodes
4) Loop Search
NEXT) More Options
ESC) Exit Menu
Press <3> for Change Passcodes. The following screen will be displayed:
THIS ACTION REQUIRES
PASSCODE CLEARANCE
Enter Passcode: XXXX
VCB-X Operator Interface SD
19
MODULAR SYSTEM MANAGER SD
Loop Search and System Alarm Search
Zone
Zone
Network Mode & Multiple Managers Loop Search
When the System Manager is confi gured for Network Mode, a loop search must initially be performed for the System Manager to recognize alarms or overrides. Also, when you have a system that has multiple System Managers and you have one of the System Managers set to (63) Network Mode for alarm and override indication, you must also perform a loop search for that System Manager. This allows the System Manager to be aware of all alarms and overrides for all local loops on the entire system.
To access the Loop Search Screen, from the Setup Screen, press and then press <PREV>.
1) Set Time & Date
2) Communications
NEXT) More Options
ESC) Exit Menu
Press <> for Next Menu. The following screen will be displayed:
3) Change Passcodes
4) Loop Search
NEXT) More Options
ESC) Exit Menu
<ESC>
System Alarm Search
The System Manager can be used to search for all active alarms on the system. You must confi gure the MiniLink PD to allow for “ Alarm Poll- ing” for each controller you want polled for alarms. See the MiniLink PD programming section on page 76 of this manual for setting information.
This option will alert you of the number of alarms present on individual units, but will not tell you what type of alarm are present. You will have to perform and individual unit alarm search for detailed alarm information.
To access the Alarm Search Screen, from the Setup Screen, press <ESC> and then press <PREV>. .
1) Set Time & Date
2) Communications
NEXT) More Options
ESC) Exit Menu
Press <> for Next Menu. The following screen will be displayed:
3) Change Passcodes
4) Loop Search
NEXT) More Options
ESC) Exit Menu
Press <4> for Loop Search. The following screen will be displayed:
Loop Search Current Loop = XX Loops Found = XX
Searching
The System Manager will now proceed to search all loops to fi nd the MiniLink PDs that are connected to the system. The screen will display the current loop being searched and the number of loops currently found.
Once the search is completed, the following screen will be displayed:
Loop Search
Finished
Loops Found = XX
Press ESC to Exit
The screen will display the number of loops found on your system. The information will be saved into the System Manager’s memory. No further loop searches will be required unless you add an additional MiniLink PD to the Network System.
Press <> for Next Menu. The following screen will be displayed:
5) Alarm Search
NEXT) More Options
ESC) Exit Menu
Press <5> for Alarm Search. The entire system is searched from this point. The following screen will be displayed:
Alarm Screen
SEARCHING!
Once the Alarm Search is complete, one of the following screens will display:
Alarm Screen
XX ALARMS ON UNIT XX
20
VCB-X Operator Interface SD
MODULAR SYSTEM MANAGER SD
Unit Alarm Search and Override Search
Alarm Screen
NO ALARMS DETECTED
To check controllers individually for alarms, use the <ALARMS> but­ton on the Main Display.
Unit Alarm Search
The System Manager can be used to search for all active alarms one controller at a time.
Press <ALARMS>. The Unit Selection Screen below will be displayed.
Enter Unit Address
Then Press Enter
Selected Unit#: XXXX
No Communication
Enter the Unit ID of the controller you wish to search and press <EN-
TER>. Once communication is established, “No Communication” will
be replaced with “Press Down.” Then
NOTE: If “No Communication” remains, it indicates a
communication failure to the controller.
The following screen will appear. The System Manager will search for any active alarms on the unit and one of the following screens will appear:
press <>.
System Manager Override Search
NOTE: In order for the Override Search to work, a Loop Search
must be performed fi rst. See page 20 for details.
When a space sensor with override option is used with any VAV/Zone Controller or Unit Controller, the System Manager can determine and report any controllers that are currently operating in an override condi­tion. This function requires that a MiniLink PD is installed on each loop where the controllers may be located. The MiniLink PD must be confi gured to allow for “Alarm Polling” for each controller that Override Polling Enabled is desired for this function to work. See the MiniLink PD programming section on page 76 of this manual for setting information.
To access the Space Sensor Overrides Screen, press The following screen will appear.
Overrides Screen
SEARCHING!
After the System Manager completes its search, it will list the fi rst unit on the system that is currently in the override mode. Press the
button to scroll through all units that are in the Override Mode.
Overrides Screen
Loop = 1 Unit = 59
OVERRIDE FOUND
<OVERRIDES>,
<>
CONTROLLER V.XXX
NO ALARMS
CONTROLLER V.XXX
ALARMS PRESENT
SCROLL DOWN TO VIEW
Press <> to scroll through all the alarms for the controller that the Modular Service Tool is connected to.
To clear any alarms that are found, you must fi x the problem indicated in the alarm. Once the problem is fi xed, the alarm will clear from the screen the next time the unit is polled.
VCB-X Operator Interface SD
21
MODULAR SYSTEM MANAGER SD
Schedules and Holidays
Zone
Zone
Scheduling
You can access the Controller Scheduling Screens by pressing <SCHED-
. The screen below will appear because Scheduling requires
ULES>
passcode clearance. A Level 1 or 2 passcode can change schedules.
THIS ACTION REQUIRES
PASSCODE CLEARANCE
Enter Passcode: XXXX
If the correct passcode was entered, the Unit Selection Screen will be displayed.
Enter Unit Address
Then Press Enter
Selected Unit#: XXXX
No Communication
Enter the Unit ID of the controller you wish to change schedules for
press <ENTER>. Once communication is established, “No Com-
and munication” will be replaced with “Press Down.” Then
NOTE: If “No Communication” remains, it indicates a
communication failure to the controller.
The Unit Schedule Menu will be displayed.
Schedule Menu
Schedule Override Week Schedules Holiday Schedules
press <>.
Week Schedules
From the Unit Schedule Menu, select Week Schedules. The following two screens will appear in order:
Event #1
Schd
Sunday Event #1 Start Time..: XXXX Stop Time...: XXXX
Event #2
Schd
Sunday Event #2 Start Time..: XXXX Stop Time...: XXXX
If you are using the internal scheduling capability of the Controller, set the schedule hours and holiday periods from the menu shown above. You can also force the unit to operate continuously in occupied or unoc­cupied mode by selecting the Schedule Override menu item and entering the desired command.
If you are using an external contact closure to signal the occupied mode, you must access the Week Schedule Screens and set all start and stop times to zero to prevent the internal schedule from turning the equipment on when you don’t want it to operate.
The screens will step through the Start Time and then the Stop Time for each day of the week. You can quit at any point in the process by pressing <ESC>. There are two Start/Stop events available per day, so the screen will show which event is being programmed. If you need only one event, keep Event #2’s times set at ZERO.
Press the <> button until the cursor is on the desired option and then
press <ENTER>.
22
All times are in 24-hour military format, so 5:00 PM would be entered as 1700.
If both the Start and Stop Times are ZERO, the schedule is in a continu­ous OFF mode. (Use for Remote Signal Contact.)
If both the Start and Stop Times are 2359, the schedule is in a continu­ous ON mode.
NOTE:
The second line displays which day of the week is currently being programmed. The day of the week automatically increments as you exit the Event #2 screen for the day and continue to the next day’s Event #1 screen.
CAUTION: The controller ships with all schedules set to
zero so that the controller will not attempt to heat or cool before you have confi gured the system.
VCB-X Operator Interface SD
MODULAR SYSTEM MANAGER SD
Holiday Scheduling and Schedule Override
Holiday Start/Stop Day Selection
From the Unit Schedule Menu, select Holiday Schedules. The following four screens will appear in order:
Hldy
Holiday # 1 Start Mon/Day.: XXXX [ July 4
Stop Mon/Day.: XXXX [ July 5
The screens will step through the fourteen possible holidays, one period at a time. Line 2 shows which holiday is currently being programmed. Since a holiday period can encompass more than one day, you need to program the day the holiday starts and the day the holiday ends. If your holiday only lasts one day, simply set both the Start Day and the Stop Day to the same value. Remember to combine the month and day into a single four-digit value.
EXAMPLE: 704 = July 4
th
= 704 ]
Hldy
Holiday # 1
th
= 705 ]
th
(NOTE: Leading zero not required)
1225 = December 25
th
Schedule Override
From the Unit Schedule Menu, select Schedule Override. The following screen will appear:
Ovrd
Schedule Override Enter Override...: X [0=Auto 1=ON 2=OFF]
If you want to force the unit to operate in a continuous Occupied or Unoccupied mode, select this menu item to activate the desired method. If a Schedule Override is active, all other methods of schedule control are ignored (Push-Button, Internal, and Remote).
As you can see on the last line of the display, enter <1> to run continu- ously in the Occupied Mode or cupied Mode. To restore normal schedule operations, enter
This override remains in effect until canceled and does not time-out like the Output Overrides do after 10 minutes of no communications.
NOTE:
Do not use the Force OFF mode in place of setting
<2> to run continuously in the Unoc-
<0>.
all the week schedules to ZERO if you are using a Remote Signal for your scheduling since the Override has priority over the Remote Signal.
Holiday Start/Stop Times
Hldy
Holiday Schedule Start Event #1: XXXX Stop Event #1: XXXX
Hldy
Holiday Schedule Start Event #2: XXXX Stop Event #2: XXXX
The fourteen holidays all use the same Start and Stop times which you program on this screen and the next. You must enter the time in 24-hour military format, the same as a regular week schedule.
Normally, the holidays will operate in an unoccupied mode or a reduced schedule mode. There are two start/stop events available on holidays to match the standard schedule number of events.
VCB-X Operator Interface SD
23
VCB-X CONFIGURATION
VCB-X Confi guration Screen Index
Zone
Zone
VCB-X Confi guration Screen Index
The available Confi guration Screens for the VCB-X Controller are listed on the next few pages by sequential screen number. When each VCB-X Controller is confi gured for the fi rst time, it is best to start with screen #1 and proceed to each screen in numerical order until you have viewed all available Confi guration Screens. This ensures that you have seen all the available VCB-X Controller confi guration possibilities and have the opportunity to change or accept the defaults for each screen.
Once the unit is confi gured and you decide to change one of the screen options, it is helpful to know what screen number contains the confi gura- tion you wish to change. With this in mind, the following is a list of all the VCB-X Confi guration Screens in numerical order with a brief listing of the confi guration feature available on each screen.
Screen #1 Sensor Scaling (Fahrenheit / Celsius)
Screen #2 EM1 Expansion Module Installed
Screen #3 EM2 Expansion Module Installed
Screen #4 MHGRV-X and MODGAS-X Installed
Screen #5 12 Relay E-BUS Expansion Module Installed
Screen #6 Preheat-X Controller Installed
Screen #7 HVAC Mode Enable Source
Screen #8 HVAC Mode Set By Remote Contact
Screen #9 SAT Reset Source
Screen #10 Reset Rate Interval
Screen #11 Return Sensor Type
Screen #12 Static Pressure Control
Screen #13 Static/Fan Control Rate & Max Increment
Screen #14 Fan Voltage Output - Min/Max
Screen #15 Supply Fan Cycle Mode
Screen #16 Fan Proving
Screen #17 Fan Starting Delay
Screen #18 Purge Mode Delay
Screen #19 Heat Type
Screen #20 Modulating Heat Output Signal - Min/Max
Screen #21 Cool Type
Screen #22 Digital Compressor For Mod Cool
Screen #23 Modulating Cooling Output Signal - Min/Max
Screen #24 Mech Heat/Cool Alarm Delay
Screen #25 Economizer Control Type
Screen #26 Title 24 Economizer
Screen #27 Economizer in Unoccupied Mode
Screen #28 Outdoor Air Sensor Installed
Screen #29 E-BUS Outdoor Air/RH Sensor
Screen #30 Economizer Enable Source
Screen #31 Economizer Control Loop Rate/Proportional Window
Screen #32 Economizer Voltage Output - Min/Max
Screen #33 CO
Screen #34 Building Pressure Control
Sensor Installed
2
Screen #35 Building Pressure Control Rate & Max Increment
Screen #36 Exhaust Fan Output
Screen #37 Heat Pump Confi g
Screen #38 WSHP Glycol Percentage
Screen #39 Aux Heat Type
Screen #40 Dehumidifi cation Control
Screen #41 Humidity Control Sensor Type
Screen #42 Suction Pressure Sensor Installed
Screen #43 E-BUS Space and Humidity Sensor Installed
Screen #44 Reheat Control
Screen #45 Defrost Coil Switch
Screen #46 Head Pressure Control
Screen #47 Condenser Fan Min/Max
Screen #48 Has Water Side Condenser
Screen #49 Type of Airfl ow Station
Screen #50 Monitor Outdoor Air Airfl ow
Screen #51 Control Outdoor Air Airfl ow
Screen #52 Outdoor Airfl ow Duct Size
Screen #53 Monitor Supply Air Airfl ow
Screen #54 Supply Airfl ow Duct Size
Screen #55 Monitor Return Air Airfl ow
Screen #56 Return Airfl ow Duct Size
Screen #57 Monitor Exhaust Airfl ow
Screen #58 Exhaust Airfl ow Duct Size
Screen #59 Morning Warm Up Type
Screen #60 AHU Uses Schedule Number
Screen #61 Daylight Adjustment Start/Stop Date
Screen #62 Trend Log Rate
Screen #63
Screen #64 Dirty Filter
Screen #65 Broadcast Outdoor Air Temperature
Screen #66 Broadcast Outdoor RH
Screen #67 Broadcast Building Pressure
Screen #68 Broadcast to Boxes
Screen #69 Cool Stage Up and Down Delays
Screen #70 Cool Stage Min Run and Min Off Delays
Screen #71 Heat Stage Up and Down Delays
Screen #72 Heat Stage Min Run and Min Off Delays
Screen #73 Heat Pump Delays - Aux/Emergency Heat
Screen #74 Heat/Cool Changeover Delay
Screen #75 Return Air Bypass Control
Screen #76 Morning Cool Down
Screen #77-81 VCB-X Relay Confi guration Screens
Screen #82-86 EM1 Relay Confi guration Screens
Screen #87-99 12 Relay Confi guration Screens
Emergency Shutdown
24
VCB-X Operator Interface SD
VCB-X CONFIGURATION
VCB-X Confi guration Screens
Confi guration Screens
In order to correctly set up the VCB-X Controller, you must fi rst confi g- ure several parameters in regard to the type of HVAC unit and system you have installed. Most of these values and operating parameters are only set once at the initial system setup and are never changed.
Modular Service Tool Instructions
No matter what screen or menu you’re in, press <CONFIGURATION>. The Unit Selection Screen will appear, shown below, requesting that you enter the unit ID number.
Enter Unit Address
Then Press Enter
Selected Unit#: XXXX
No Communication
Enter the correct unit ID number of the VCB-X Controller you want to confi gure and then press “No Communication” will be replaced with “Press Down.” Then press
<>. You will then see Unit Con guration Screen #1. Press <ENTER>
to save entered data and press <> to scroll through the screens.
NOTE: If “No Communication” remains, it indicates a
communication failure to the controller.
<ENTER>. Once communication is established,
The following screen will be displayed:
Change Setpoints
Configure Unit
Save/Copy/Restore
Scroll down to the ‘Confi gure Unit’ option and press <ENTER>. This will take you to the fi rst Confi guration Screen shown below.
Confi guration Screen #1 - Sensor Scaling
VCBX Cnfg ID 101
Sensor Scaling
Fahrenheit
Use < Or > To Change
Options are Fahrenheit or Celsius. If you make a change to this screen, the last line will display the following: UNIT RESTARTING XX. The screen will display the countdown of 20 and then the last line will display the prompt Press Enter to Cont. Default is Fahrenheit.
Confi guration Screen #2 - EM1 Expansion Module Installed
System Manager SD Instructions
From any Main screen, press <SETPOINTS>. The screen below will appear because this option requires passcode clearance. Only a Level 2 passcode can change setpoints.
THIS ACTION REQUIRES
PASSCODE CLEARANCE
Enter Passcode: XXXX
If the correct passcode was entered, the Unit Selection Screen will be displayed.
Enter Unit Address
Then Press Enter
Selected Unit#: XXXX
No Communication
Enter the Unit ID of the controller you wish to change schedules for and press
munication” will be replaced with “Press Down.” Then
<ENTER>. Once communication is established, “No Com-
press <>.
NOTE: If “No Communication” remains, it indicates a
communication failure to the controller.
VCBX Cnfg ID 101
EM1 Installed: NO
Use < Or > To Change
If you have expansion module EM1 installed, this confi guration option should be confi gured as YES. Default is NO. If your unit utilizes the following, an EM1 Module is required:
 VAV Capabilities  Water Temperature
 Building Pressure  Hood On/Off
 Head Pressure Control  Proof of Flow
 Return Air Temperature  Condenser Control
 Remote Forced Occupied
 Water Source Heat Pump Monitoring
 Modulating Chilled Water
VCB-X Operator Interface SD
25
VCB-X CONFIGURATION
VCB-X Confi guration Screens
Zone
Zone
Confi guration Screen #3 - EM2 Expansion Module Installed
VCBX Cnfg ID 101
EM2 Installed: NO
Use < Or > To Change
If you have expansion module EM2 installed, this confi guration option should be confi gured as YES. Default is NO. If your unit utilizes the following, an EM2 Module is required:
 Remote SAT Reset  Remote Forced Cooling    Return Air Bypass Control Remote Forced Heating  Remote Forced Dehumidi cation
Confi guration Screen #4 - MHGRV-X & MODGAS-X Installed
VCBX Cnfg ID 101 MHGRV Installed: NO MODGS Installed: NO
Use < Or > To Change
If you have an MHGRV-X Controller installed, the fi rst confi guration option should be confi gured as YES. If you have a MODGAS-X Con- troller installed, the second confi guration option should be confi gured as YES. Defaults are NO.
Confi guration Screen #5 - 12 Relay E-BUS Expansion Module Installed
VCBX Cnfg ID 101
12RLY Installed: NO
Use < Or > To Change
If you have a 12 Relay E-BUS Expansion Module installed, this con­ guration option should be confi gured as YES. Default is NO.
Confi guration Screen #6 - PREHEAT-X Controller Installed
VCBX Cnfg ID 101
Preheat-X
Installed: NO
Use < Or > To Change
If you have a PREHEAT-X Controller installed, this confi guration option should be confi gured as YES. Default is NO.
Confi guration Screen #7 - HVAC Mode Enable Source
VCBX Cnfg ID 101
HVAC Source
Single Zone VAV
Use < Or > To Change
This selection will determine which sensor will determine the mode of operation of the unit and how it will operate. If selecting HVAC Source Set by Remote Contact as YES in the next screen, you should select Outdoor Air as the HVAC Source in this screen. If you will be using a BACnet command to determine the HVAC mode, then you can leave the selection on this screen at the default. Default is Single Zone VAV. Available options are:
Single Zone VAV—Recirculating unit using the Space
Temperature Sensor to determine the mode of operation. Heating and Cooling are controlled to a Leaving Air Setpoint. Space Temperature resets the Supply Fan VFD speed to maintain the Space Temperature. Modulating Heating and Cooling must be used for this operation. Can be confi gured for CAV Heating using staged Heat.
Space Temperature—Typical recirculating unit using a
Space Temperature Sensor to determine the Heating, Cooling, and Vent Modes of operation.
Outdoor Air—This is for a 100% Outdoor Air Unit
(MUA) using the Outdoor Air Temperature Sensor to determine the Heating, Cooling, and Vent Modes of operation. Dehumidifi cation utilizes an Outdoor Air Dewpoint Setpoint. Also use this confi guration if the next screen will be confi gured for Modes Set By Remote Contact.
 Supply Air—This is for a standard Cooling Only VAV
unit with optional Morning Warm Up. In the Occupied Mode, the unit will be in the Cooling Mode controlling to the Cooling Supply Air Setpoint.
Supply Air/Tempering—This selection is for VAV
“cooling only” applications where because of cold outdoor temperatures, heat may need to be added in order to maintain the “Cooling” Supply Air Setpoint. This application requires outdoor Cooling and Heating Setpoints confi gured using the Hood On Enable Setpoints, to initiate Cooling and Heating Modes. The Heating Supply Air Setpoint should be set at least 2 Air Setpoint. See the Sequence of Operations for details.
˚F below the Cooling Supply
Return Air—Optional recirculating unit confi guration
using the Return Temperature Sensor to determine the Heating, Cooling, and Vent Modes of operation.
Space Temperature with High % OA—If it is
preferable to use Space conditions (instead of Outside Air) to control a 100% or high percentage outdoor air unit, this option allows tempering of the outdoor air in the Space Vent Mode of operation to prevent dumping of hot or cold air into the space. See the Sequence of Operations for details.
NOTE: If this option is selected, the Economizer must be
set to Standard Economizer.
26
VCB-X Operator Interface SD
VCB-X CONFIGURATION
VCB-X Confi guration Screens
Confi guration Screen #8 - HVAC Mode Set By Remote Contact
VCBX Cnfg ID 101 HVAC Mode Set By
Remote Contact: NO
Use < Or > To Change
If you have an EM2 Expansion Module, this option allows separate 24 VAC wet contact closures on that module to force the unit into Heat­ing, Cooling, and Dehumidifi cation modes. If this option is selected, it applies to all three modes, and all three modes will only be initiated by these contact closures. If this is con gured for YES, set the previous screen to Outdoor Air. See the VCB-X Remote Contact Control section of the Sequence of Operations in the VCB-X Controller Field Technical Guide for more details. Default is NO.
Confi guration Screen #9 - SAT Reset Source
VCBX Cnfg ID 101
SAT Reset Source
No Reset
Use < Or > To Change
This confi guration option is not available if Single Zone VAV was se- lected as the HVAC source. The Supply Air Setpoint can be “automati­cally” adjusted based on a selected reset source. This screen allows you to choose this source. Default is No Reset. The available selections are as follows:
No Reset—No SAT Setpoint Reset will occur. The SAT
Setpoints remain fi xed.
Space Temperature—The SAT Setpoints will be
adjusted based on the Space Temperature.
Outdoor Temperature—The SAT Setpoints will be
adjusted based on the Outdoor Air Temperature.
Return Air Temperature—The SAT Setpoints will be
adjusted based on the Return Air Temperature.
Fan VFD Signal—The SAT Setpoints will be adjusted
based on the VFD Signal. This is good for Adjusting the Setpoints based on the building’s load by looking at the VFD speed.
Remote Voltage—The SAT Setpoints will be
adjusted based on the Remote Supply Air Temperature Voltage Reset Signal.
If the HVAC Source was set Single Zone VAV in Confi guration Screen #5, then line 3 on this screen will read No SAT Rst Allowed and the line 4 will be blank.
Confi guration Screen #10 - Reset Rate Interval
VCBX Cnfg ID 101
Reset Interval Rate...: 30 s
[1-255 Seconds]
If you selected a Reset Source in Screen #6, enter a value in seconds be­tween 1-255. This value determines how fast the Supply Air Temperature Setpoint is adjusted as the Reset Source changes. Default is 30 seconds.
Confi guration Screen #11 - Return Sensor Type
VCBX Cnfg ID 101
Return Sensor Type
NONE
Use < Or > To Change
If this unit has a Return Air Sensor installed, select RETURN AIR if it is a temperature sensor only. Select RETURN AIR WITH RH if it is a combination communicating temperature and humidity sensor. Default
is NONE.
Confi guration Screen #12 - Static Pressure Control
VCBX Cnfg ID 101
Static Pr Control
Fan VFD / SZ VAV
Use < Or > To Change
This confi guration option is available if expansion module EM1 is installed and confi gured or if using SZ VAV operation. Default is Fan VFD/SZ VAV. The options are:
None— This unit is not controlling Duct Static Pressure.
Fan VFD / SZ VAV—This unit has a Supply Fan VFD that
modulates to control the Duct Static Pressure or this is a Single Zone VAV application.
Bypass Damper—This unit uses a Bypass Damper to
control the Duct Static Pressure.
Confi guration Screen #13 - Static/Fan Control Rate & Max Increment
VCBX Cnfg ID 101
Static/Fan Control
Rate...: 10 s
Max Increment: 5%
This value determines the time interval between changes to the Supply Fan Speed or the Bypass Damper Position during duct static pressure control. It also determines the time interval between changes to the Fan Speed during Single Zone VAV Reset of the Supply Fan VFD Speed.De- fault is 10 seconds. The Maximum Increment is is the maximum amount the Static Control can change per control rate period. Default is 5%.
Description Minimum Default Maximum
Static/Fan Control Rate 1 sec 10 sec 30 sec
Max Increment 1% 5% 30%
VCB-X Operator Interface SD
27
VCB-X CONFIGURATION
VCB-X Confi guration Screens
Zone
Zone
Confi guration Screen #14 - Fan Voltage Output
VCBX Cnfg ID 101
Fan Voltage Output
Min Volts: 0.0 Max Volts: 10.0
Enter a value between 0.0 and 10.0 VDC for the main fan’s minimum and maximum output voltage. The Duct Static Pressure Output Status Screen will display 0% to 100%, but the output will range from the mini­mum value set on this screen to the maximum value set on this screen.
The VCB-X will reverse the logic of the output signal when a Zoning Bypass Damper is used. Defaults are 0 VDC Min and 10 VDC Max.
Description Minimum Default Maximum
Minimum Fan Voltage 0 0 10
Maximum Fan Voltage 0 10 10
Confi guration Screen #15 - Fan Cycle Mode
VCBX Cnfg ID 101
Fan Cycle Mode
NO
Use < Or > To Change
Select YES if you want the HVAC unit’s Supply Fan to only run during Heating or Cooling Mode. If you want the HVAC unit’s Supply Fan to run continuously while in the Occupied Mode, regardless of the Heating or Cooling Mode, select NO. Default is NO.
Confi guration Screen #16 - Fan Proving
VCBX Cnfg ID 101
Fan Proving
NO
Use < Or > To Change
Select YES if the unit is equipped with a Proof of Flow Switch and it is connected to the VCB-X. If selected as YES and the Proof of Flow Switch is open, only the Supply Fan Relay will be active. If any other relays such as Heating Stages or Cooling Stages are active, they will be deactivated when the Proof of Flow Switch input is lost. Default is NO.
Confi guration Screen #17 - Fan Starting Delay
VCBX Cnfg ID 101
Fan Starting Delay: -1 s
[-1 = Unit Addr x 5]
Enter the number of seconds you want the fan to delay starting. This is the Supply Fan Starting Delay initiated whenever the VCB-X initiates Supply Fan operation upon going occupied or after power-up. This is useful when you are using multiple VCB-X-controlled HVAC units and want to be sure that all the units do not start at exactly the same time when the Occupied schedule occurs. Each VCB-X should be set with staggered Fan Starting Delay Setpoint values. When the -1 value is used, it multiplies each VCB-X Controller’s address by 5 and uses this value in seconds as the Fan Starting Delay. This provides a staggered start for each VCB-X Controller on the system without having to individually set each VCB-X Controller for its own time delay. For a MUA unit, this should be set to a minimum of 60 seconds to let the OA Damper open.
Default is -1 second.
Description Minimum Default Maximum
Fan Start Delay Timer -1 Sec -1 Sec 240 Sec
Confi guration Screen #18 - Purge Mode Delay
VCBX Cnfg ID 101
Purge Mode
Delay: 10 Sec
[ 0 - 900 Seconds ]
Enter the number of seconds you want the unit to stay in Purge Mode before going into Occupied Mode. In Purge Mode, the fan runs with the Outdoor Air Damper closed and all Cooling and Heating is de-energized. For a MUA unit, this should be set to 0 seconds to prevent a Purge Mode (which is a damper closed operation). Default is 10 seconds.
Description Minimum Default Maximum
Purge Mode Delay 0 sec 10 sec 900 sec
Confi guration Screen #19 - Heat Type
VCBX Cnfg ID 101
Heat Type
No Heat
Use < Or > To Change
28
Default is No Heat. Available options are:
No Heat—The unit has no Heat.Staged Only— On/Off Hot Water or fi xed stage(s) of Heat. Mod Heat Only—Only fully modulating forms of
Heat which would be Modulating Hot Water or Steam Heat or Modulating SCR Electric Heat. Does not include Modulating Gas using the AAON® MODGAS-X Controller.
VCB-X Operator Interface SD
Loading...
+ 64 hidden pages