The OE331-21 General Purpose Controller Plus (GPC Plus) is used for controlling equipment or processes that
cannot be controlled using HVAC controllers. The Prism computer front end
software is used to interface with the
GPC Plus controller functions. The
GPC Plus Controller provides the flexibility to control, schedule and/or monitor
equipment such as unit heaters, exhaust fans, motorized louvers, etc.. The
GPC Plus has (6) configurable inputs
which will accept signals from thermistor temperature sensors, 4-20mA or 05VDC transmitters or dry contact closures. An additional modular input is
provided for connection of an OE271
static pressure sensor. The GPC Plus
has (5) relay outputs for on/off control
and (2) analog outputs. With the addition of the OE352 2 Slot Expansion
Base Board and (1) OE357 4 Relay
Expansion Board, (4) additional relay
outputs are available providing for a
maximum of (9) usable relay outputs.
The GPC Plus also has (5) separate 2
event per day schedules, each with its
own optimal start functions built in. In
addition the GPC Plus provides lead/lag
start capabilities.
The GPC Plus is provided with an integral backplate for mounting inside of a control enclosure. It is recommended that the GPC Plus be mounted in the HVAC unit control enclosure, or in a control enclosure in the
building equipment room. An optional factory control enclosure for the GPC Plus is available.
Technical DataOE331-21-GPCPLUS
GPC Plus Controller
Power24 Volt ACWeight1.5 lb.
Power Consumption8 VA MaximumNetwork ConnectionRS-485
Operating Temp
Total Inputs Available7Analog Output Qty.2
Static Pressure Inputs1 (Modular )Analog Output Signal0-10 VDC
Configurable Inputs6Optimal Start Schedules(5) Total - (1) for Each Schedule
Schedules Available(5) 2 Event per dayLead Lag Scheduling(1) Output can be Configured
Three Year WarrantyWattMaster reserves the right to change specifications without notice
Total Relay Qty. Available With
Optional Expansion Board
9
Form: ORION-OE331-21-GPCPlusController-01A.doc Page 1 of 1
Page 4
All Communication Loop Wiring Is
Straight Through
T To T, R To R, SHLD To SHLD
Local Loop RS-485
Connect To
9600 Baud
Next Device On
The Local Loop
Mini DIN Connector
For Connection Of Modular
Service Tool
Pull-up Resistor- Typical
Analog Inputs AIN1Thru AIN7
Can Be Used For 10kOhm
Type III Thermistor, 0-5VDC
Signal, 4-20mA Signal Or Dry
Contact Closure Inputs.
As Required.
Note: When Using Sensors or
Transducers With 4-20 mA Input
Signal, The Pull-up Resistor For
The Input Being Used Must Be
Removed From The Controller
Board And A 250 Ohm Resistor
Must Be Wired Between The Input
Terminal And The Ground Terminal
On The Controller Board
C21
TB1
COMM
T
SHLD
R
CX5
LD6
COMM
LD7
PWR
LD8
LED1
LD9
LED2
R1
U7
RV1
VREFADJ
INPUTS
+VDC
AIN1
AIN2
AIN3
AIN4
AIN5
GND
GND
AOUT1
AOUT2
AIN7
GND
PJ1
TB3
PRESSURE
SENSOR
OE331-21-GPCPLUS
GPC Plus Controller
CX1
RN1
1
U5
RS-485
COMM
1
RN3
P1
+VREF
5.11V
TEST POINT
EWDOG
RN5
C10
C12
C17
R26
EXPANSION
CX2
U2
U1
RAM
HH
U6
C1
PHILIPS
R28
ADD
ADDRESS
1
2
PU1
4
D6
8
PU2
16
32
D7
PU3
TOKEN
NETWORK
D8
PU4
SW1
D9
PU5
D11
PU7
0-1
0-5
VDC
VDC
D14
JP1
U13
CX13
D15
U15
C20
CX15
PJ3
PJ2
X2
R15
C14
R19
C15
R22
R24
R25
U3
EPROM
TUC-5R PLUS
YS101816 REV.2
C2
CX10
U10
C11
U12
CX14
U14
D17
T'STAT
CX4
CX3
U4
PAL
(1 MEG)
CX6
X1
C3
1
RN4
U9
D10
CX12
D12
R13
D18
C18
VR1
Not Used
D1
COM1-3
COM4-5
NE5090NPB3192
0PS
R6
C9
R11
R27
V6
R1
R2
R3
R4
R5
U8
9936
V1
V2
V3
TB2
V4
V5
U11
MC34064A
C13
C16
TB4
GND
POWER
24VAC
24VAC Power
For Relay Outputs
5 Relay Outputs Are
Available On Board For
On/Off Control Of
Equipment. When
Required 4 Additional
Relay Outputs Are
Available By Using The
Optional OE357 4 Relay
Output Expansion
Board. See Below.
GND
Line Voltage
24VAC
24VAC Transformer
10 VA Mini mum
RLY1
D2
RLY2
D3
1
RLY3
D4
RN2
RLY4
D5
RLY5
C7
SC1
CX8
R7
L1
R10
D13
D19
D16
C19
VR2
Analog Input AIN6 Can Only Be Used
Splice If Req’d
For Connection Of A Static Pressure
Transducer With Modular Connector
Warning:
24 VAC Must Be Connected So That All
Ground Wires Remain Common. Failure To
Do So Will Result In Damage To The
Controller
Connect Tubing To High Pressure
Port (Bottom Tube) and Route To Static
Pressure Pickup Probe Located In Unit
Discharge. Leave Port Marked “Lo” Open
To Atmosphere
Connect To
Expansion Board
Base (When Used)
S.P.
Transducer
4 Additional Relay Outputs
Are Available By Using The
OE357 4 Relay Output
Expansion Board. The
OE352 2 Slot Expansion
Base Board Is also
Required To Mount The
OE357 Board.
TB2
TB1
+24VDC-OUT
C6
GND
R14
D3
V1
TB1
V4
4RLY IO BD.4RLY IO BD.
VR4
MC
7812CT
VR5
MC
7824CT
VR6
MC
7824CT
24VAC-IN
24VAC-IN
K1
UL 5A250VACUL 5A250VAC
CONTACT:
24VDC
G5L-114P-PS
OMRON
UL 5A250VAC
UL 5A250VAC
CONTACT:
24VDC
G5L-114P-PS
OMRON
K4
LD1
PWR
YS101790
GND
C3
C4
C5
+24VDC-OUT
K2
UL 5A250VAC
UL 5A250VAC
CONTACT:
24VDC
G5L-114P-PSG5L-114P-PS
OMRON
UL 5A250VAC
UL 5A250VAC
CONTACT:
24VDC
G5L-114P-PSG5L-114P-PS
OMRON
K3
YS101780
2 SLOT MODULAR I/O2 SLOT MODULAR I/O
PJ2
PJ1
CX1
P1
ULN2803A/
K1
74HC04N
K2
K3
RN1
PCF8574P
K4
U2
LM358N
CX2
VR1
R10
R4
R5
R6
R12
OE357
U1
4 Relay Output
CX2
Board
U2
CX3
U3
P2
JP2
OE352 2 Slot Expansion Base Board
Jumper
Setting
1.)24 VAC Must Be Connected So
That All Ground Wires Remain
Common.
2.)All Wiring To Be In Accordance With
Local And National Electrical Codes
3.)All Communication Wiring To Be 18
Ga. Minimum, 2 Conductor Twisted
Pair With Shield. Belden #82760 Or
Equivalent.
4.)It Is Recommended That All
and Specifications.
Controllers Address Switches Are
Set Before Installation.
FILENAME
G-GPC-PlusCNTRL1A.CDR
DATE:
03/08/05
PAGE
DESCRIPTION:
OE331-21-GPCPLUS
1Of2
GPC Plus Controller
JOB NAME
DRAWN BY:
B. Crews
Page 5
This Switch Should Be
In The OFF Position
As Shown
ADDRESSADD
Address Switch Shown Is
Set For Address 1
The Address For Each Controller
Must Be Unique To The Other Controllers
For Auto-Zone Systems The Address Must Be
For All Other Systems The Address Can Be Set
ADDRESSADD
Controller
Address Switch
On The Local Loop.
Set Between 18 to 30
Between 1 to 59
1
2
4
8
16
32
TOKEN
NETWORK
ADDRESSADD
Address Switch Shown Is
Set For Address 13
Note:
The Power To The Controller Must Be Removed
And Reconnected After Changing The Address
Switch Settings In Order For Any Changes To
Take Effect.
Caution
Disconnect All Communication Loop Wiring
From The Controller Before Removing Power
From The Controller. Reconnect Power And
Then Reconnect Communication Loop Wiring.
INPUTS
+VDC
AIN1
AIN2
AIN3
AIN4
AIN5
GND
GND
AOUT1
AOUT2
AIN7
GND
PJ1
TB3
PRESSURE
SENSOR
EXPANSION
C10
RN5
C17
C12
R26
C20
D15
PU1
D6
PU2
D7
PU3
D8
PU4
D9
PU5
D11
PU7
D14
PJ2
ADDRESS
U13
CX13
CX15
ADD
1
2
4
8
16
32
TOKEN
NETWORK
SW1
X2
0-1
0-5
VDC
VDC
JP1
R15
C14
R19
U15
C15
R22
R24
R25
PJ3
CX10
U10
D17
U12
CX14
D18
CX12
C18
C11
U14
D10
D12
R13
C7
R6
R7
SC1
D19
C19
L1
R10
D13
D16
C9
R11
U11
C13
C16
TB4
GND
R27
V6
POWER
24VAC
VR1
VR2
1.)24 VAC Must Be Connected So
That All Ground Wires Remain
Common.
2.)All Wiring To Be In Accordance With
Local And National Electrical Codes
and Specifications.
3.)All Communication Wiring To Be 18
Ga. Minimum, 2 Conductor Twisted
Pair With Shield. Belden #82760 Or
Equivalent.
4.)It Is Recommended That All
Controllers Address Switches Are
Set Before Installation.
FILENAME
G-GPC-PlusCNTRL1A.CDR
DATE:
03/08/05
PAGE
DESCRIPTION:
OE331-21-GPCPLUS
2Of2
GPC Plus Controller
JOB NAME
DRAWN BY:
B. Crews
Page 6
Page 7
General Purpose Controller
(GPCPlus )
January 31, 2005
Description
The GPCPlus is a controller designed to “fill in the blanks” between standard off the
shelf programs and minor non-standard applications. An example of a non-standard
application might be exhaust fan control, based on building pressure or a simple boiler
enable controller based on schedules or outdoor air temperature.
The remainder of this document will describe the I/O configurations that are possible and
will also include a few sample applications to aid the user in determining if this controller
will meet their specific requirements.
Main Status Screen
The Main Status Screen provides real-time live updates of the current operating
conditions and is used to access the various setpoint and configuration options.
No control takes place until the user “configures” the operation of the GPCPlus. Access
to the various configuration screens is made by a simple left mouse-click on the
individual reading or output status box for each I/O Point. As a general rule, a left click
1
Page 8
accesses the configuration for the selected item and a right click accesses the force mode
options if any are available.
Analog Inputs
Relays
Analog Outputs
2
Page 9
Week Schedules & Holidays
3
Page 10
Analog Input
Configurations
The first five analog inputs and input #7 can be configured in several different ways.
Input #6 can be used for Static Pressure and accepts the standard pressure sensor with the
phone jack connector, available from WattMaster Controls.
The following configurations are available:
1. Thermister Type III Temperature Sensors (Scaled for Fahrenheit)
2. Thermister Type III Temperature Sensors (Scaled for Celsius)
3. 4 – 20ma User Scaled
4. 0 – 5 vdc User Scaled
5. Wall Sensor Slide Offset
6. Binary Contact Closure
7. Read Global Analog Broadcast from another Controller
4
Page 11
8. Read Global Binary Broadcast from another Controller
9. Sensor #6 can be assigned to read Static Pressure
Each input is separately configured so combinations of any type of input on the same
controller are possible.
All readings can be overridden to specific values for test purposes. All thermister sensors
can also be calibrated by entering positive or negative offsets to be applied to the current
readings. All 4 – 20ma readings can be calibrated if the user has the exact current or
resistance values available for entering in the calibration fields.
Right-Click on the desired analog input reading to access the pop-up menu shown above
and then select the desired function. If you are calibrating or overriding the reading, the
following window will pop-up. Enter the desired calibration offset or specific reading
you wish to force the input to and press the Enter key. The window will automatically
close and send the command to the controller. If you select the Clear Sensor Override
option, a window will not appear but the clear command will be sent to the controller.
- OR -
5
Page 12
Any or all readings can also be “broadcast” to other controllers on the communications
loop. For example, the Outdoor Air Temperature is broadcast on channel #2 by any unit
that happens to have the sensor attached. If none of the standard package units have the
outdoor air sensor attached, you could attach it to the GPCPlus and select it for broadcast
on channel #2. All other controllers would “hear” the broadcast and use it in their normal
operations. On the other hand, if you are measuring something like return air humidity,
do NOT select channel #2 to broadcast it on, since all the package unit controls are
expecting the outdoor air temperature. If no package controllers exist on your system
then you are free to use any available global channel for broadcast. There are 32 possible
global analog channels and 16 possible global binary channels.
Select global analogs to broadcast readings and global binary channels to broadcast
contact closure (on/off) information.
If you select one of the unassigned channels for broadcast, it is assumed that you have
other GPCPlus units installed that expect to receive information on those channels since
the standard package code does not listen for broadcasts on unassigned channels.
CAUTION: If you elect to broadcast a reading from the GPCPlus to all
other controllers on your installation, be sure to check the
HELP screen to identify which Global Channels have
already been assigned.
Each input also provides high and low alarm limits if the user requires out of range
values to notify service personnel. The alarm limits can be widened at night and they can
also be forced to be out of limits for a user defined amount of time before an alarm
occurs. This prevents false alarms if the reading temporarily exceeds the limit but then
recovers and stays within the limits the remainder of the time.
All readings are user scalable. That means you can display values with ± 1, ± 0.1, ± 0.1±
0.01 or higher resolutions. Just keep in mind that the maximum value that can be sent
from the controller is ±30,000 so if you have scaled your reading to ± 0.001 then the
maximum value you can send is ± 30 with the 3 additional decimal values (30.000).
6
Page 13
Each input can also have an appendix selected to display with the reading to make them
more user friendly. The possible appendix values are:
• (None) No Appendix Required
• RH%Relative Humidity
• %Percentage
• °FDegrees Fahrenheit
• °CDegrees Celsius
• PPMParts Per Million
• PSIPounds Per Square Inch
• “WGInches of Water Gauge
• “Inches
• Ft.Feet
• RPMRevolutions Per Minute
• VDCVolts Direct Current
• BTUBritish Thermal Units
On inputs selected for Binary Input Contact Closure, the user can select Normally Open
or Normally Closed Contacts.
7
Page 14
Wall Sensor Slide Offset
If you have configured a specific input to be connected to one of WattMasters’ standard
OE212 or OE213 Flush Mount Wall Sensors which contain the optional slide offset, be
sure to enter a value for “Maximum Slide Offset Effect”. This tells the controller how
much effect to have on the selected setpoints when the slide is fully deflected up or down.
When the slide is in the “center” position, it has no effect on the current setpoints.
Note: There are separate outputs on the Flush Mount Wall Sensors
for measuring the room temperature and reading the slide
offset. Be sure to configure the correct input for the slide offset
and do not use the temperature signal coming from the wall
sensor for this option.
The slide offset is normally used by one or more relay outputs, configured to “look” at
this value and include its effect on their normal setpoints.
As you can see on the sample screen, Relay #4 is set to activate if the LoadTemp rises
above 72.0°F. It is also monitoring the Sensor Slide Adjust input on Analog Input #5. If
the slide is pushed up, the Hi Limit Setpoint will rise to 74.0°F and the Lo Limit Setpoint
8
Page 15
to 72.0°F. If the slide is pushed down, the Hi Limit Setpoint will drop to 70.0°F and the
Lo Limit Setpoint to 68.0°F.
Push-Button Override
If you have configured a specific input to be connected to one of WattMasters’ standard
OE211 or OE213 Flush Mount Wall Sensors which contain the optional push-button
override, be sure to enter a value for “Push-Button Override Duration”. To use this option
you must select which schedule will be affected by the override event. (See screen
below).
Optimal Start Temperatures
You can configure any of the first five inputs to be used as the Optimal Start “Target
Temperature” sensor. As with the override option, you must select which schedule will
use this temperature for its optimal start calculations.
You also must enter a Cooling and a Heating Target setpoint for this feature to work
correctly.
9
Page 16
Analog Input #6
This analog input is reserved for Duct Static Pressure. This value can then be used to
monitor the duct static or to actually control the duct static using an analog output and
driving either inlet vanes or a VFD controller. It is not recommended that you attempt to
use relays to control the duct static pressure, although this reading can be selected as a
control source on the relay configuration screen.
CAUTION: If you select two relays to control duct static, WattMaster
Controls cannot assume any liability for equipment
damage caused by over-pressurization of the duct work!
If you require a Duct Static Pressure Sensor, you must use an OE271 sensor provided by
WattMaster Controls for proper sensor readings. No other sensors are currently supported
for this input.
All setpoints related to duct static control pressures and alarm points are programmed on
this screen which activates when you left-click on the pressure reading box.
10
Page 17
Relay Output
Configuration
Control Methods
Each individual output relay can be configured separately for one of the following
methods of control listed below.
0 = Not Configured
1 = On Above High Limit Setpoint and Off Below Low Limit Setpoint
2 = On Above High Limit Setpoint and On Below Low Limit Setpoint
3 = Off Above High Limit Setpoint and On Below Low Limit Setpoint
4 = Off Above High Limit Setpoint and Off Below Low Limit Setpoint
5 = On with Contact Closure on Selected Input
6 = Off with Contact Closure on Selected Input
7 = Follow Schedule Only
11
Page 18
8 = Follow Global Binary Only
9 = Ventilation Control
10 = Lead Relay for Lead/Lag Control
11 = Lag Relay for Lead/Lag Control
Control/Reset Sources
The Control Source is also selectable. This control source can be an analog value or an
on/off contact closure. The list of possible sources is shown below.
The Logical AND Source and the Logical OR Source also use the same list of available
sources for their control also.
Enabling Relay
Interaction between relays is possible via an Enabling Relay feature. This allows the user
to prevent a specific relay from activating until one of the other relays has had a chance
to activate (See Sample Configurations Section). This can include such things as waiting
for a fan to start before operating a heating or cooling stage.
Delay & Run Times
The relay can also be forced to remain on for a minimum amount of time or remain off
for a minimum amount of time to prevent rapid cycling on and off under borderline
operating conditions. A Starting Delay Period is also available so that a relay must also
wait this amount of time, once it is enabled to activate before the relay output is actually
energized.
Reset Source Limits
The Reset Source Limits are only required if you need the controlling setpoint to vary
between the Hi Limit Setpoint and Lo Limit Setpoint based on some other condition
12
Page 19
such as outdoor air temperature. If no reset is required, simply enter the same values for
the Control Source Hi and Lo Limit Setpoints. No Reset Source is required.
If you do need the main Control Source Setpoint to reset, this is the range over which
the Reset Source must change to cause the controlling setpoint to reset from the Lo Limit
to the Hi Limit values you entered. For example: you want to reset the enable/disable
point for a boiler enable signal based on the changing outdoor air temperature. You
would enter the Minimum outdoor air temperature that would cause the Hi Limit
Setpoint to be calculated and the Maximum outdoor air temperature that would cause the
Lo Limit Setpoint to be calculated.
Controlling Setpoint Deadband
You should always enter a small deadband to prevent the relay from cycling on and off
continuously due to a control source reading that is toggling right around the current
setpoint. The deadband you enter is added to both sides of the setpoint to create an area
where the relay does not stage on or off. For example: if your setpoint was 72°F and the
deadband was set for 0.5°F, the relay can change state when the temperature rises above
72.5°F or drops below 71.5°F. If you do not need unoccupied setback control, you must
leave this setpoint = 0.0°F and use the High and Low setpoints to create a deadband.
Controlling Schedule
You can select one of the Internal Schedules to set the occupied or unoccupied mode of
operation for the selected relay. If the relay does not require a schedule to be part of its
control strategy, leave the selection at “None Selected”.
AND/OR Conditional Tests
If more than one criterion is required to make a decision, there are two other options
available to aid in the decision process. An AND condition and an OR condition. If you
don’t need additional tests, simply select the Not Configured option under the Control
Method for each of these sources.
If you need two events to be true before the output can activate, use the AND ControlMethod and select a Logical AND Source.
If you want either the main Control Method OR an Alternate Control Method to activate
the output, use the OR Control Method and select a Logical OR Source.
You can combine all three options to create a condition where two events must be true or
a third separate event must be true to activate the output.
13
Page 20
Run Time Alarm
If the selected relay output is controlling a device that needs periodic maintenance, you
can enter a Run Time Alarm Delay period that, once exceeded, generates an alarm
condition that will notify the user when it occurs. If you need to protect the equipment
you can select the Disable Relay box and the relay will de-activate once this run time has
been exceeded.
Relay Output Type
Some control methods require the relay contacts to be closed when the output is
activated, others require the contacts to be open. You can select which method of control
to use with this option.
Global Binary Channel
If this output was configured to follow a global binary broadcast, enter which channel (1
- 16) the relay should follow. The output will be active when the binary value is “1” and
will de-activate when the value is “0”.
Lead/Lag Control
If you have configured this relay as the Lead relay in a Lead/Lag control scheme then
you will also need to set the Changeover Interval and the Proof Failure Timeout Delay
shown on the right hand side of the relay configuration screen.
The Changeover Delay is used to toggle the Lag output into the Lead once the runtime
hours of the Lead output exceed this amount of time on the Lag output.
The Proof Failure Time Delay is the amount of time given for the “Proof of Flow” input
to become active once the Lead or Lag output is energized. If this proof is not made
within the specified amount of time, the controller switches to the Lag output in an
attempt to get the controller running and then sets an alarm to flag the user that
something is wrong.
Hi/Lo Limit Setpoints
All On/Off control methods require setpoints to be entered for control purposes. The
relay state changes based on the control method selected and the current reading versus
the Hi Limit Setpoint or Lo Limit Setpoint. If you have selected the On Above andOff Below method, then the relay would be active when the reading exceeds the Hi Limit
Setpoint and it would not be active below the Lo Limit Setpoint. In either case, the user
defined Deadband would also need to be satisfied before the actual relay change of state
occurs.
14
Page 21
Ventilation Control
You can configure an output to operate in a ventilation control mode. This means that the
output is active for the Vent Mode ON Time and then cycles off for the Vent Mode OFF
Time. If the output is not enabled by a schedule or another relay, it will continue to cycle
indefinitely at this On/Off rate.
15
Page 22
Analog Output
Configuration
Two Proportional Outputs ( 0 - 10 VDC ) are available to the user. This output operates
using standard floating point control or a modified Proportional/Derivative control as
configured by the user. The controlling setpoint can be reset by any other sensor reading
or the outdoor air temperature and the output voltage range can be limited by the user to
some range other than the standard 0 - 10 VDC.
Possible Control Modes
0 = Not Configured
1 = Direct Acting Floating Point
2 = Reverse Acting Floating Point
3 = Direct Acting PID
4 = Reverse Acting PID
5 = Relief Pressure Control
6 = Duct Static Pressure Control
16
Page 23
7 = Proportional Reset Signal
8 = Economizer Control
9 = Lead/Lag Pump VFD Control
If you select Direct or Reverse Acting Floating Point Control, this means that the output
voltage on Direct Acting increases as the control signal goes above the setpoint and drops
as the signal falls below the setpoint. In Reverse Acting mode, the voltage drops as the
control signal goes above setpoint and falls when the control signal goes below setpoint.
This type of control works best on very slow changing applications where the amount of
time it would take to drive full on or full off is not critical. For faster response, the PID
Control method is recommended.
A deadband setpoint is available if you wish to set the Hi/Lo setpoints the same and only
change the voltage if the control signal is further from setpoint than the deadband
amount.
PID Control
The PID control is a WattMaster modified version of Proportional and Derivative Rate of
Change Control. The only user setpoints required are the Calculation Interval which can
speed up or slow down the control changes and whether or not to use the Rate of Change
feature. Also, the minimum and maximum output range can be set to something other
than full on or full off.
This Rate of Change control is the preferred method for most valve or actuator control
situations. It “self-adapts” to changing load conditions and “remembers” where it was the
last time it was de-activated and attempts to restart the process at that known point
whenever it is called back into action.
17
Page 24
Economizer Control
If you have configured the GPCPlus as a very simple Air Handling Unit, it has the ability
to control the outside air dampers in a true first stage economizer cooling mode. This
mode requires a Minimum Ventilation position that it maintains whenever the
economizer is not enabled for cooling. It also needs to know which relay has been
configured as the first compressor stage. Use the Outdoor Air Enable limits to set when
the free cooling mode can be used in conjunction with scheduling and temperature
demands.
Alternate Override
There are situations where we want normal control to be suspended temporarily
whenever an unusual situation occurs. For example: we are using the economizer control
method and we have installed a CO² sensor on this controller to use for Indoor Air
Quality. If the CO² reading exceeds a specified level, this Alternate Override can take
charge and move the output signal to a pre-designated level to bring the IAQ back under
control.
Proportional Reset Signal
As the Reset Source goes from its Maximum Reset Source to its Minimum Reset
Source the Controlling Setpoint goes from its Minimum Reset Setpoint limit to its
Maximum Reset Setpoint limit.
Since the reset limits can be set to any desired value, the user can initiate a reverse acting
proportional reset or a direct acting proportional reset of the setpoint simply by crossing
the min and max values if direct acting is required.
Direct Acting = As Temperature Rises the Setpoint Drops
Reverse Acting = As Temperature Rises the Setpoint Rises
An example of using Proportional Reset would be for Boiler Control. As the outside air
temperature rises, we would like the boiler output temperature to drop. We would use the
outside air temperature as the control source and set the Max Setpoint and Min Setpoint
to the range we want to vary the voltage from 0 to 10.0 vdc. If we set the Max Setpoint to
50° and the Min Setpoint to 60° then as the outside air rose from 50° to 60°, the output
signal would drop from 10.0 vdc @ 50° to 0.0 vdc @ 60°. This is because we made the
output Reverse Acting by setting the Max Setpoint lower than the Min Setpoint.
18
Page 25
Lead/Lag Pump VFD Control
If you are using the GPCPlus as a Lead/Lag controller and you need to maintain loop
pressure or some other analog signal, configure an output for this method of control.
Then all you need to do is enter the control setpoint on the Lead Relay configuration
screen and this output will attempt to modulate and maintain that level of control while
the Lead/Lag control is active.
19
Page 26
Sample Configurations
Sample #1
The user would like to control 4 boilers. Each boiler is controlled from the same Water
Temperature sensor but at a different temperature reading. Once a boiler is activated it
must remain on at least 5 minutes and if a boiler is de-activated it must remain off at least
10 minutes. Additionally, the boilers are locked out when the Outdoor Air Temperature is
above 65°F.
Analog Input #1 Configured as Thermister Type III Sensor
Note that some Hi and Lo alarm limits were set and that the reading is in degrees
Fahrenheit.
20
Page 27
Analog Input #2 Configured as Outdoor Air Thermister Sensor
Notice that we set this reading to broadcast on Global Analog Channel #2. That is
because the Outside Air is normally read by one controller on a job and the remaining
controllers look at Global Analog #2 for this value, including the GPC Plus. Even if this
is the only controller on the job, you must set it to broadcast the outside air so the GPC
Plus can “see” what the OA Temperature is.
Analog Input #3 Configured as Not Configured
Analog Input #4 Configured as Not Configured
Analog Input #5 Configured as Not Configured
Analog Input #6 Duct Static Pressure Sensor is not Required
Analog Input #7 Configured as Not Configured
21
Page 28
Relay Output #1 Programming ( Used for Outdoor Air Enable / Disable )
NOTE: Nothing is physically connected to Relay #1. Its only use is to
enable or disable the other relays.
22
Page 29
Relay Output #2 Programming ( Used for Boiler #1 )
As you can see, the first boiler stage is enabled to operate if the water temperature is
below 175°F and will remain on until it rises to 190°F. This first stage can only operate if
the outdoor air enabling relay #1 is active. Once activated, the boiler must remain on for
5 minutes (300 seconds) and once de-activated it must remain off for 10 minutes (600
seconds).
Since we are not resetting the operating setpoint, the Reset Source has been left as “None
Selected”. We also don’t require a “Logical AND” or “Logical OR” condition so they
have been left Not Configured. There is no need to enable this output from a schedule
since it uses an Enabling Relay (OAT Enable) which does require the schedule before it
can activate based on the Outside Air Temperature.
23
Page 30
Relay Output #3 Programming ( Used for Boiler #2 )
The second boiler stage is enabled to operate if the water temperature is below 170°F and
will remain on until it rises to 180°F. The second stage can only operate if the first boiler
stage relay #2 has been active for at least 5 minutes. Once activated, this stage must
remain on for 5 minutes and once de-activated it must remain off for 10 minutes.
24
Page 31
Relay Output #4 Programming ( Used for Boiler #3 )
The third boiler stage is enabled to operate if the water temperature is below 160°F and
will remain on until it rises to 175°F. The third stage can only operate if the second boiler
stage relay #3 has been active for at least 5 minutes. Once activated, this stage must
remain on for 5 minutes and once de-activated it must remain off for 10 minutes.
25
Page 32
Relay Output #5 Programming ( Used for Boiler #4 )
The fourth boiler stage is enabled to operate if the water temperature is below 150°F and
will remain on until it rises to 170°F. The fourth stage can only operate if the third boiler
stage relay #4 has been active for at least 5 minutes. Once activated, this stage must
remain on for 5 minutes and once de-activated it must remain off for 10 minutes.
The Starting Delay Period that was set for stages 2 to 4 prevent all four boiler stages
from activating at the same time as soon as they are enabled to begin operation. Each
stage must run for 5 minutes before the next stage can be activated.
Analog Output Programming
Control SourceNot Configured
Since no analog output control is required, simply leave the Control Source set to Not
Configured on both outputs and no analog output control will take place.
26
Page 33
Operation
Relay #1 enables the boilers to operate if the outdoor air temperature is below the low
setpoint and the schedule is occupied. Each boiler is enabled to operate if the previous
boiler is currently active and has been on for at least 5 minutes. All four boilers monitor
the same analog input sensor for the Water Temperature reading. The #1 Enable Relay
can monitor a global broadcast from another controller on the RS-485 communications
loop for the outdoor air temperature but, in this case, we are reading the Outdoor Air
Temperature on Analog Input #2. Notice on the Analog Output #2 configuration screen
that it was also configured to broadcast on Global Analog Channel #2. That is because
the GPC Plus doesn’t have any other way of knowing that it is the one reading the
outdoor air temperature.
The voltage output is not used so no control source is selected, and no other related
setpoints require modification.
Shown below is a sample Status Screen for this sample application. Notice that the
boilers are not enabled even though the schedule is active because the outdoor air
temperature is too high.
27
Page 34
This next sample screen shows that the outdoor air temperature has dropped enough to
enable the boilers to operate. The system has been running long enough to satisfy all 4
Boilers 5 Minute Starting delay so they are all active at this point. It took roughly 20
minutes to get all 5 relays active since each has a 5 minute Staging Delay time period.
Keep in mind that although Relay #1 (OAT Enable) is active, nothing is connected to the
output because its only function is to provide an outdoor air enable signal for the boiler
staging.
28
Page 35
Sample #2
The user would like to use the GPC Plus as a Lead/Lag Air Handling Unit Controller.
The installation is located in a critical area that does not tolerate the space temperature
going out of control. The method chosen was to install a backup AHU that would take
over in case of failure on the Lead AHU. Also, since the units are identical, the owner
wanted to equalize the run-times to lengthen the time between routine maintenance
service calls. The easiest method for handling this was to use two, standard, off the shelf
AHU controllers and a GPC Plus controller that would enable the appropriate AHU
based on changeover and failure mode conditions. The GPC Plus would use contact
closures to the Forced Occupied inputs of the AHU controllers to activate and de-activate
the units. A failure mode would be indicated by the failure of the Supply Air
Temperature to drop below or stay below a 60°F setpoint. Any temperature excursions
above 60°F for more than one minute would indicate a failure had occurred and that the
Lag AHU should be activated and an Alarm generated to let building maintenance know
there was a problem.
Analog Input #1 Configured as Thermister Type III Sensor to measure Supply Air
As you can see, this input does not use a schedule for Night Setbacks since the unit will
run 24 hours a day. It does however, monitor the Supply Air Temperature for values that
are out of limits for more than a half hour and generates an alarm condition. This is a fall
29
Page 36
back alarm condition because the Lead/Lag control should have already generated an
alarm if something was wrong and the standby AHU was called into action. Be sure to
check the Alarming Enabled box if you want this alarm to be reported back to the PRISM
screen or to a Remote Pager.
Analog Input #2 - #7 The remaining inputs are not required for this program.
Relay Output #1 Programming ( Used for Lead AHU Enable Signal )
This relay was chosen to be the Lead control output and was connected to AHU #1.
Either AHU could have been selected as AHU #1, this was an arbitrary decision. The
Supply Air was selected as the Control Source and the Proof Setpoint was set to 60.0°F.
The AHU’s will change the Lead every 24 Hours and if the Supply Air rises above 60°
for more than 60 seconds, it will be considered to be in failure mode and the Lag AHU
will be activated. Also, an alarm will be generated so that an immediate service call can
be made to determine the cause of failure. If both units should happen to fail, there is no
further redundant capabilities and service personnel will need to correct the problems and
then Reset the control from the Alarm Indicator Screen (shown later in this section).
30
Page 37
Relay Output #2 Programming ( Used for Lag AHU Enable Signal )
There are no other settings required for the Lag Controller. All control logic from the
Lead relay is used in the decision making process.
Analog Outputs (No Analog Output Control is Required for this Program)
31
Page 38
Main Status Screen ( Normal Operations )
As you can see on the Status Screen shown above, the unit is operating normally and the
Supply Temperature is at 51.9°F, well within the normal operating range and no alarms
are currently active.
There are no schedules active since this unit is required to operate 24 hours a day. The
relay outputs will operate their control modes around the clock if no schedule was
selected on the relay configuration screen.
32
Page 39
Main Status Screen ( Failure Mode )
The Supply Air rose to 61.9°F and the Lag AHU was activated.
The alarm screen indicates the Lead AHU failure.
33
Page 40
Both AHU’s are now off because the Lag AHU failed to lower the Supply Air below
60°F.
34
Page 41
The alarm screen indicates both outputs failed to control the Supply Temperature. At this
point, the service personnel will need to correct the problem and then select the Reset
Pump/Fan button to restart the GPC Plus Lead/Lag control sequence.
Although the button and alarm indicators show Lead Pump / Fan indicators, the outputs
are not limited to those types of control. You just need to understand that the Lead Pump
/ Fan controls AHU #1 in this sample and Standby Pump / Fan controls AHU #2.
35
Page 42
Form: OR-GPCPlus-APP-01APrinted in the USAMarch 2005
All rights reservedCopyright 2005
WattMaster Controls Inc. • 8500 NW River Park Drive • Parkville MO • 64152