Orion OE217-00 User Manual

Page 1
Description
The OE217 series of Touch Screen Digital Room Sensors are used to sense Space Temperature only or Space Temperature & Space Humidity. The OE217-00 model is the Space Temperature Sensor only model and can be used with the VCM-X Controller (OE332-23-VCMX) and the VAV/Zone Controller (OE324-02). The OE217-01 is a combination Space Temperature & Space Humidity Sensor model and can only be used with the VCM-X Controller.
Besides sensing Temperature & Humidity, the Digital Room Sensors also provide these other useful features:
• User Friendly Graphical LCD Display with LED Backlight
• Display the Current Space and Outdoor Air Temperature
• Display the Current Space Humidity and Outdoor Air Relative Humidity (OE217-01 Model Only)
OE217-00 & OE217-01
Digital Room Sensors
• Display the current Zone Setpoint Temperature
• Equipped With Push Buttons for Changing the Zone Setpoint Temperature
• Equipped With an Override Button for Forcing the VAV/Zone Controller or VCM-X Controller into Occupied Operation from Unoccupied Operation
Provides graphics to indicate the mode of operation
• Provides LEDs to indicate Schedule Override, Button Push, and Alarms
Both sensors connect to the controllers using TSDRSC modular cables of multiple lengths connected between the controller and the sensor. The TSDRSC modular cables should not run in conduit with other AC line voltage wiring or with any conductors carrying highly inductive loads.
Mounting
The Digital Room Sensor is designed to be mounted to a vertical, 2” x 4” electrical box recessed in the wall. If the wall cannot be penetrated, a plastic surface mount box such as those made by Wiremold sensor to the wall surface. The Sensor is mounted by removing the front cover and fastening the housing base to the electrical box using the supplied (2) 6/32” x 1” machine screws. The Modular cable is then plugged into the phone jack located on the circuit board that is mounted on the cover. The cover is then placed onto the housing base and the Allen Screw on the bottom of the base is adjusted to hold the cover in place.
TM
, may be used to mount the
Technical Data OE217-00 & OE217-01 Digital Room Sensor
Sensor Element Type III Thermistor 10k ohm
@ 77 F Digital Sensing Device
Sensor Reading Range
Ambient Temperature Limits
Accuracy
Three Year Warranty WattMaster reserves the right to change specifications without notice
Form: ORION-OE217-01-DigitalRoomSensor-1C.doc Page 1 of 1
RH +/-2%, Temp +/- .5F
40F to 120F
RH = 0-100%
-40F to 180F
Display 112 x 64 Monochrome Graphical LCD
w/LED Backlight
Connection
Weight
RJ-45 Modular Female Jack
3.2 oz.
Page 2
Description
Digital Sensor Cable
TSDRSC-XX
The TSDRSC Cables are used to connect power and communica­tions between the WattMaster Digi­tal Room Sensor or Digital CO
2
Sensor and the VCM-X Controller or VAV/Zone Controller.
The TSDRSC Cables are prefabri­cated plenum-rated cables with RJ­45 Connectors on both ends of the cable for connection between the Digital Room Sensor, Digital CO
2
Sensor, and the VCM-X or VAV/Zone Controller.
The TSDRSC Cables are labeled near each end with the cable part number.
The TSDRSC Cables are available in 5, 10, 15, 25, 40, 80, 120 & 160 feet lengths. These lengths should satisfy most job requirements. For length requirements other than those listed, the MS000029 Modular Room Sensor Cable Coupler can be used to connect two of the TSDRSC Cables together to provide for your specific-length requirements.
The plug-in design of the TSDRSC Cables eliminates costly wiring errors and makes system installa­tion easy. The cable components are all UL approved.
Technical Data TSDRSC Digital Sensor Cables
TSDRSC Cable Available Lengths and Part Numbers
Cable Type Plenum-rated Wire Colors Brown, Blue, White W/ Blue Stripe, White
Wire Size 24 AWG Stranded
Terminations (2) RJ-45
Three Year Warranty
Form: ORION-ModularCable-TSDRSC-1A.doc Page 1 of 1
TSDRSC-5 (5 Ft.) TSDRSC-10 (10 Ft.) TSDRSC-15 (15 Ft.)
TSDRSC-25 (25 Ft.) TSDRSC-40 (40 Ft.)
TSDRSC-80 (80 Ft.)
TSDRSC-120 (120 Ft.) TSDRSC-160 (160 Ft.)
8 Conductor
Connectors
Current Rating of Cable Wire
UL Listing No. CMP-UL As Per UL 910
Cable Sheath Color
WattMaster reserves the right to change specifications without notice
24 AWG Wire = 0.577 Amps
(Maximum Amps
For Power Transmission)
W/ Brown Stripe, Orange,
White W/ Orange Stripe, Green,
White W/ Green Stripe
Gray
Page 3
Description
The OE217 series of Touch Screen E-BUS Digital Room Sensors are used to sense Space Temperature only or Space Temperature & Space Humidity. The OE217-02 model is the Space Temperature Sensor only model and can be used with the VCB-X Controller (OE335-23-VCBX) and the VAV/Zone Controller (OE3XX-0X). The OE217-03 is a combination Space Temperature & Space Humidity Sensor model and can only be used with the VCB-X Controller.
Besides sensing Temperature & Humidity, the E-BUS Digital Room Sensors also provide these other useful features:
• User Friendly Graphical LCD Display with LED Backlight
• Display the Current Space and Outdoor Air Temperature
• Display the Current Space Humidity and Outdoor Air Relative Humidity (OE217-03 Model Only)
OE217-02 & OE217-03
E-BUS Digital Room Sensors
1.00
4.55”
2.80
OVERRIDE ALARM
Display
Override
Front View
Cover Set Screw
0.69
Side View
• Display the current Zone Setpoint Temperature
• Equipped With Push Buttons for Changing the
E-BUS Cable Connection
MICROCHIP
256GP206
PIC24HJ
0.81
Zone Setpoint Temperature
SHLD
-COM
• Equipped With an Override Button for Forcing the VAV/Zone Controller or VCB-X Controller into Occupied Operation from Unoccupied Operation
Provides graphics to indicate the mode of operation
1.87
Remote Thermistor Sensor Connector
GND +12Vdc
• Provides LEDs to indicate Schedule Override, Button Push, and Alarms
Both sensors connect to the controllers using E-BUS cables of multiple lengths connected between the
1.81
Back View
0.49
controller and the sensor. The E-BUS cables should not run in conduit with other AC line voltage wiring or with any conductors carrying highly inductive loads.
Mounting
The Digital Room Sensor is designed to be mounted to a vertical, 2” x 4” electrical box recessed in the wall. If the wall cannot be penetrated, a plastic surface mount box such as those made by Wiremold sensor to the wall surface. The Sensor is mounted by removing the front cover and fastening the housing base to the electrical box using the supplied (2) 6/32” x 1” machine screws. The E-BUS cable is then plugged into the E-BUS connector located on the circuit board that is mounted on the cover. The cover is then placed onto the housing base and the Allen Screw on the bottom of the base is adjusted to hold the cover in place.
Technical Data OE217-02 & OE217-03 E-BUS Digital Room Sensor
Sensor Element Type III Thermistor 10k ohm
@ 77 F Digital Sensing Device
Sensor Reading Range
Ambient
40F to 120F
RH = 0-100%
-40F to 180F Temperature Limits
Accuracy
Three Year Warranty WattMaster reserves the right to change specifications without notice
RH +/-2%, Temp +/- .5F
Display 112 x 64 Monochrome Graphical LCD
Connection
Weight
TM
, may be used to mount the
w/LED Backlight
E-BUS
3.2 oz.
Form: ORION-OE217-02-03-EBUS-DRS-1A.doc Page 1 of 1
Page 4
Description
The OE217-04 E-BUS Digital Room Space & Humidity Sensor is used to sense Space Temperature & Space Humidity. The E-BUS Digital Room Sensor can be used with the VCB-X Controller (Orion Part No. OE335-23-VCB-X; AAON Part No. V04740).
The E-BUS Digital Room Sensor connects to the controller using E-BUS cables of multiple lengths connected between the controller and the sensor. The E-BUS cables should not run in conduit with other AC line voltage wiring or with any conductors carrying highly inductive loads.
Mounting
The E-BUS Digital Room Sensor is designed to be mounted to a vertical, 2” x 4” electrical box recessed in the wall. If the wall cannot be penetrated, a plastic surface mount box such as those made by Wiremold wall surface. The Sensor is mounted by removing the front cover and fastening the housing base to the electrical box using the supplied (2) 6/32” x 1” machine screws. The E-BUS cable is then plugged into the E­BUS connector located on the circuit board that is mounted on the cover. The cover is then placed onto the housing base and the Allen Screw on the bottom of the base is adjusted to hold the cover in place.
TM
, may be used to mount the sensor to the
OE217-04
E-BUS Digital Room Sensor
1.00
4.55”
E-BUS Cable Connection
Remote Thermistor Sensor Connector
2.80
Front View
1.87
MICROCHIP
256GP206
PIC24HJ
Cover Set Screw
SHLD
-COM
GND +12Vdc
0.69
Side View
0.81
1.81
Back View
0.49
Technical Data OE217-04 E-BUS Digital Room Sensor
Sensor Element Digital Sensing Device Accuracy Sensor Reading
Range Ambient
40F to 120F
RH = 0-100%
-40F to 180F
Connection
Weight Temperature Limits
Three Year Warranty WattMaster reserves the right to change specifications without notice
RH +/-2%, Temp +/- .5F
E-BUS
3.2 oz.
Form: ORION-OE217-04-EBUS-DRS-1A.doc Page 1 of 1
Page 5
BK000081 – Sensor Mounting Plate
Description
The BK00081 Sensor Mounting Plate is used, if necessary, to cover the Sensor sheet rock opening. It is provided with the following Sensors:
OE217-00 - Digital Room Temperature Sensor
OE217-01 - Digital Room Temperature and Humidity Sensor
OE217-02 - E-BUS Digital Room Temperature Sensor
OE217-03 - E-BUS Digital Room Temperature and Humidity Sensor
OE217-04 - E-BUS Digital Room Temperature Sensor (No LCD Display)
OE256-01 - Wall Mounted CO
OE256-05 - E-BUS Wall Mounted CO
Sensor
2
Sensor
2
Mounting
The Mounting Plate screws onto the back of the Sensor’s housing base. The mounting plate is then mounted and covers the recessed space in the wall. A locking screw secures the Sensor to the wall.
Form: ORION-BK000081-Sensor-Mounting-Plate-1A.doc Page 1 of 1
Page 6
MS000248 - E-BUS Adapter Hub
Description
The MS000248 E-BUS Adapter Hub is used to provide a connection point for multiple E­BUS Sensors or Modules. This E­BUS Adapter Hub has four ports. One port is used to connect the Hub to an E-BUS Expansion Port on the VCB-X Controller or a VCB-X Expansion Module using EBC E-BUS cables. This leaves three ports available for E-BUS Sensors and other Modules.
The EBC Cables are plenum-rated high flex wire cables with an EBC Connector on each end of the cable for connection between the Sensors, Modules, and the VCB-X Controller.
ADAPTER HUB
RIGHT END
-AMP 1234
0.405
ADAPTER HUB
SIDE VIEW
MS000248 E-BUS ADAPTER HUB
0.762
ADAPTER HUB
TOP VIEW
ADAPTER HUB
LEFT END
VIEW
0.327
VIEW
Technical Data MS000248 E-BUS Adapter Hub
Terminations Hub - (4) EBC Connectors
Three Year Warranty
WattMaster reserves the right to change specifications without notice
.
Form: AAON-MS000248-E-BUS-Adapter-1A.doc Page 1 of 1
Page 7
Description
The HZ-EBC-248 (AAON Part No. V17180) MS000248 E-BUS Adapter Hub and a 1.5 Foot EBC Cable (Part No. EBC-1.5F).
The E-BUS Adapter Hub is used to provide a connection point for multiple E-BUS Sensors or Modules. This E-BUS Adapter Hub has four ports. One port is used to connect the Hub to an E-BUS Expansion Port on the VCB-X Controller or a VCB-X Expansion Module using the supplied EBC-
1.5F cable. This leaves three ports available for E-BUS Sensors and other Modules.
The EBC Cable is a plenum-rated high flex cable with EBC Connectors on each end of the cable for connection between the Sensors, Modules, and the VCB-X Controller.
is comprised of the
HZ-EBC-248 - E-BUS Adapter Hub
with 1.5 Ft. EBC Cable
Technical Data HZ-EBC-248 E-BUS Adapter Hub with 1.5 Ft. EBC Cable
EBC E-BUS Cable Available Length and Part Number
Cable Type Plenum-rated High Flex Wire Wire Colors Red/Black First Pair; White/Blue Second
Wire Size 19 Strands of 32 Gage Wire, 4
Terminations Hub - (4) EBC Connectors
Three Year Warranty
Form: AAON-HZ-EBC-248-E-BUS-Adapter-1A.doc Page 1 of 1
EBC-1.5F (1.5 Foot) Current Rating of
Cable Wire
UL Listing No. CMP/CL3P/FPLP
Conductor
Cable Sheath
Cable – 2 EBC Connectors
Color
WattMaster reserves the right to change specifications without notice
300 Vrms Min = 10.15 Ohms per 1000
feet @ 20 Deg Celsius, Nominal
White, Plenum Rated CL3P/CMP
with “WATTMASTER EBUS”
marking every foot.
Pair
Page 8
OE365-15-EBA-A - E-BUS Adapter Board
Description
The OE365-15-EBA-A E-BUS Adapter Board is used to provide a
4.12
1.33
connection point for multiple E­BUS Sensors or Modules.
The E-BUS Adapter Board is also used for connecting an EBTRON GTC-116 Airflow Measurement Digital Transmitter or a Green-
TM
Trol
GA-200-N Transmitter Mod-
P2P1
J2 J3
MODULAR EBUS
YS102478 REV 0 MADE IN USA
®
J1
MSTP EBUS
R+ SH T-
R+ SH T-
3.00
ule with GF Series Airflow Monitor­ing Station to the VCM-X E-BUS Modular Controller*, RNE Controller*, or VCB-X Controller.
You must wire the EBTRON GreenTrol
TM
Airflow Measurement Digital Transmitter to this Adapter Board. Up to (3) EBTRON GreenTrol
TM
Airflow Measurement Digital Transmitters can be attached to the Adapter Board when using the VCM-X E-BUS Controller or RNE Controller and up to (4) EBTRON
®
®
or
or
®
or GreenTrol
TM
Airflow Measurement Digital Transmitters can
be attached to the Adapter Board when using the VCB-X Controller. The E-BUS Adapter Board has (3) HSSC Connections. One of these E-BUS ports is used to connect
the Board to the E-BUS Port on the VCM-X E-BUS Controller or RNE Controller using an HSSC E­BUS cable.
The E-BUS Adapter Board also has (4) Modular E-BUS ports. One of these Modular E-BUS ports is used to connect the Board to the E-BUS Port on the VCB-X Controller.
The EBUS Adapter Board also has (2) MSTP E-BUS Connections. The AirFlow Monitoring Station(s) connect to one of the MSTP E-BUS Connections.
*NOTE: With custom VCM-X software, the Paragon MicroTrans EQ series Air Flow Monitoring Station can be used and would wire into the E-BUS Adapter Board the same way.
Technical Data OE365-15-EBA-A E-BUS Adapter Board
Terminations (4) EBC Connections
(2) MSTP E-BUS Connections
(3) HSSC Connections
Three Year Warranty
EBTRON GreenTrol Paragon
®
is a registered trademark of Ebtron, Inc., Loris, SC.
TM
is a registered trademark of GreenTrol Automation, Inc. Loris, SC.
®
is a registered trademark of Paragon Controls, Inc. Santa Rosa, CA
.
WattMaster reserves the right to change specifications without notice
Form: ORION-OE365-15-EBA-A-E-BUS-Adapter-Board-1C.doc Page 1 of 1
Page 9
EBC-XXXF – EBC E-BUS Cables
3M
Description
4321
The EBC E-BUS Cables are used to connect power and communications between the VCB-X Controller, VCB-X Expansion Module, E-BUS Modules, and E-BUS Sensors.
The EBC E-BUS Cables are plenum­rated high flex wire cables with an EBC Connector on each end of the
F
XX
EBC-
cable. The EBC E-BUS Cables are labeled
with “WATTMASTER E-BUS” marking every foot.
Length
in Feet
The EBC E-BUS Cables are available in 1, 1.5, 3, 10, 15, 25, 50, 75, 100, 150, and 250 foot lengths and additionally a 1000 foot long spool.
"WATTMASTEREBUS" "WATTMASTEREBUS"
These lengths should satisfy most job requirements. For length requirements other than those listed, the MS000248
F
XX
EBC-
E-BUS Adapter Hub can be used to connect EBC E-BUS Cables together to provide for your specific-length requirements.
The plug-in design of the EBC E-BUS Cables eliminates costly wiring errors and makes system installation easy. The cable components are all UL approved.
Technical Data EBC-XXXF EBC E-BUS Cables
EBC E-BUS Cable Available Lengths and Part Numbers
EBC-SPOOL-F (1000 Foot
Cable Type Plenum-rated High Flex Wire Wire Colors Red/Black First Pair; White/Blue Second
Wire Size 19 Strands of 32 Gage Wire, 4
Terminations Cable – 2 EBC Connectors Cable Sheath
Three Year Warranty
EBC-1-F (1 Foot)
EBC-1.5-F (1.5 Foot)
EBC-3-F (3 Foot) EBC-25-F (25 Foot) EBC-50-F (50 Foot) EBC-75-F (75 Foot)
EBC-100-F (100 Foot) EBC-150-F (150 Foot)
EBC-250-F (250 Foot)
Spool)
Conductor
Current Rating of Cable Wire
UL Listing No. CMP/CL3P/FPLP
Color
WattMaster reserves the right to change specifications without notice
432 1
3M
CABLE SIDE
VIEW
EBC-XXF
E-BUS CABLE
300 Vrms Min = 10.15 Ohms per 1000
feet @ 20 Deg Celsius, Nominal
White, Plenum Rated CL3P/CMP
with “WATTMASTER EBUS”
marking every foot.
Pair
Form: ORION-EBC-XXXF-E-BUS-Cable-1B.doc Page 1 of 1
Page 10
Description
The patented design, OE21x-02 series Modular Room
OE210-02, 211-02, 212-02, 213-02
Modular Room Sensors
2.75“
0.88“
Sensor provides accurate sensing of the room tempera­ture. Its design allows for flush wall mounting yet rejects the influence of surface and internal wall temperatures. The Modular Room Sensor is used in conjunction with the Orion VAV/Zone Controller. Connection between the VAV/Zone Controller board and the Modular Room Sen­sor is by means of an RJ-45 Modular Cable. The Modular
3.25“
W
A R M E R
C O O L E
R
4.50“
2.50"
Room Sensor cannot be used for connection to the VCM­X controller. For these applications the Standard Room Sensor must be used. Please see the Orion Standard Room Sensor submittal sheet for information.
Sensors provided with the setpoint adjustment option can
2.00“
0.25“
be programmed to allow a temperature range adjustment of ± 6° with the pushbutton override option can be programmed to provide a timed override duration of up to 8.0 hours.
The Room Sensor’s attractive styling and off white casing color make it suitable for most building decors. If interior
F from their standard setpoint. Sensors provided
YS101858 REV 0
MODULAR
SENSOR
Wall Cut-Out Dimensions
PJ1
R2
THERM1
R1
When Sensor Is To Be Mounted Without
2.75“
Handy Box (By Others)
decoration requires, the Modular Room Sensor casing can also be painted or wall papered without affecting the sensor's performance. Modular Room Sensors are avail­able in 4 different configurations:
OE210-02 - Sensor Plain  OE211-02 - Sensor with Override  OE212-02 - Sensor with Setpoint Adjustment  OE213-02 - Sensor with Setpoint Adjustment and Override
Modular cable from the VAV/Zone Controller to the Modular Room Sensor should not be run in conduit with other AC line voltage wiring, or with any conductors carrying highly inductive loads.
Mounting
The Room Sensors are designed to be mounted on a vertical, 2” x 4” electrical box recessed in the wall. If the wall cannot be penetrated, a plastic surface mount box such as those made by Wiremold, may be used to mount the sensor to the wall surface.
Technical Data OE210-02, OE211-02, OE212-02, OE213-02
Modular Room Sensor
Sensor Element Type III Thermistor
10k ohm @ 77º F
Accuracy
0.4º F between 40º F to 95º F
Range -30º F to 150º F Weight 4 oz.
3 Year Warranty WattMaster reserves the right to change specifications without notice
Form: ORION-ModularRoomSensor-1F.doc Page 1 of 1
Mounting Designed to be Flush Mounted to Wall
using Vertical 2” x 4” Handy Box (by others)
Connection RJ-45 Modular Female Jack
Page 11
Description
Modular Room Sensor Cable
FMRSC-XX
Description
The FMRSC Cables are used to connect power and communica­tions between the Modular Room Sensor and the Orion VAV/Zone Controller.
The FMRSC Cables are prefabri­cated plenum-rated cables with RJ­45 Connectors on both ends of the cable for connection between the Modular Room Sensor and the Orion VAV/Zone Controller.
The FMRSC Cables are labeled near each end with the cable part number.
The FMRSC Cables are available in 5, 10, 25, 40 and 80 feet lengths. These lengths should satisfy most job requirements. For length requirements outside of this range, the MS000029 Modular Room Sensor Cable Coupler can be used to connect two of the FMRSC Cables together to provide for your specific­length requirements. Not more than one coupler should be used on a run. Maximum run is 160 feet.
The plug-in design of the FMRSC Cables eliminates costly wiring errors and makes system installation easy. The cable components are UL approved.
Technical Data FMRSC Modular Sensor Cables
FMRSC Cable Available Lengths and Part Numbers
Cable Type Plenum-rated Wire Colors White W/ Green Stripe, Green W/ White
Wire Size 24 AWG Stranded
Terminations (2) RJ-45
Three Year Warranty
FMRSC-5 (5 Ft.) FMRSC-10 (10 Ft.) FMRSC-25 (25 Ft.)
FMRSC-40 (40 Ft.) FMRSC-80 (80 Ft.)
6 Conductor
Connectors
Current Rating of Cable Wire
Stripe, White W/ Orange Stripe, Orange
W/ White Stripe, White W/ Blue Stripe,
UL Listing No. CMP-UL As Per UL 910
Cable Sheath Color
WattMaster reserves the right to change specifications without notice
24 AWG Wire = 0.577 Amps
(Maximum Amps
For Power Transmission)
Blue W/ White Stripe
Gray
Form: ORION-ModularCable-FMRSC-1B.doc Page 1 of 1
Page 12
Description
The patented design, OE21x series Standard Room Sen­sor provides accurate sensing of the room temperature. Its design allows for flush wall mounting yet rejects the influence of surface and internal wall temperatures. The Standard Room Sensor is used in conjunction with the Orion controllers. Wire terminals are provided on the sen­sor for connection to the controllers. The Standard Room Sensor cannot be used for connection to the VAV/Zone controller. For this application the Modular Room Sensor must be used. Please see the Orion Modular Room Sen­sor submittal sheet for information.
Sensors provided with the setpoint adjustment option can be programmed to allow a temperature range adjustment of ± 6°F from their standard setpoint. Sensors provided with the pushbutton override option can be programmed to provide a timed override duration of up to 8.0 hours.
The Room Sensor’s attractive styling and off white casing color make it suitable for most building decors. If interior decoration requires, the Room Sensor casing can also be painted or wall papered without affecting the sensor's per­formance. Room Sensors are available in 4 different con­figurations:
OE210 Sensor Plain  OE211 Sensor with Override  OE212 Sensor with Setpoint Adjustment  OE213 Sensor with Setpoint Adjustment and
Override
OE210, 211, 212 & 213
Standard Room Sensors
2.00“
TMP
GND
AUX OUT
4.50“
0.88“
0.25“
Wall Cut-Out Dimensions When Sensor Is To Be Mounted Without
2.75“
Handy Box (By Others)
2.50"
3.25“
2.75“
W
A R M
E
R
C O O
L
E
R
Mounting
The Room Sensors are designed to be mounted on a vertical, 2” x 4” electrical box recessed in the wall. If the wall cannot be penetrated, a plastic surface mount box such as those made by Wiremold, may be used to mount the sensor to the wall surface.
W W A A R R M M E E R R
C C O O
OVR OVR
OE210 OE211
Room Sensor - Plain
Room Sensor With Override
With Setpoint Adjust
Technical Data OE210, OE211, OE212, OE213 Standard Room Sensor
Sensor Element Type III Thermistor
Mounting Designed to be Flush Mounted to Wall
10k ohm @ 77º F
Accuracy
0.4º F between 40º F to 95º F
Line Loss 0.25º F max. error, using 22 AWG wire at 1000 ft
Range -30º F to 150º F Weight 4 oz.
3 Year Warranty WattMaster reserves the right to change specifications without notice
O O L L E E R R
OE212
Room Sensor
using Vertical 2” x 4” Handy Box (by others)
OE213
Room Sensor
With Setpoint Adjust
& Overide
Form: ORION-StandardRoomSensor-1D.doc Page 1 of 1
Page 13
OE230 (6" Probe) & OE231 (12" Probe)
Technical Specifications
Sensor Element:
Type III Thermistor 10k ohm @ 77ºF
Accuracy:
± 0.4º F between 40º F to 95º F
Range:
-30º F to 150º F
Caution!
The Duct Sensor Is Used For Sensing Supply Or Return Air Temperatures. Location Of The Sensors Is Very Important In Order To Obtain Accurate Temperature Readings. The Following Recommendations Should Be Followed:
Supply Air
When Used As A Supply Air Sensor The Sensor Should Be Mounted In The Supply Air Duct As Close To The HVAC Unit As Possible And Upstream Of The Bypass Damper (If Used) For Best Results. For Best Accuracy, Apply Insulation On The Outside Of The Ductwork Over The Sensor. This Will Help Thermal Gradients From Affecting The Sensor.
Return Air
When Used As A Return Air Sensor The Sensor Should Be Mounted In The Return Air Duct As Close To The HVAC Unit As Possible And Upstream Of The Bypass Damper (If Used) For Best Results. For Best Accuracy, Apply Insulation On The Outside Of The Ductwork Over The Sensor. This Will Help Thermal Gradients From Affecting The Sensor.
See The Systems Installation And Operation Manual For Other Design Considerations And Recommendations Regarding Duct Temperature Sensor Location.
Duct Temperature Sensors
Thread Together
5-1/2" (OE230) 11-1/2" (OE231)
Leads Are Non-polarized. Butt Splice Leads To 24 Gauge Wire Minimum. Connect Leads To "Analog In" And "Ground" At Controller.
4.0"
3/4"
Mounting Plate
1/4" Hex Head Sheet Metal Screws
Mounting Plate
Gasket
Adhesive Backed Drill Guide Mounting Template
Duct Work
Drill 3/8” Hole In Ductwork For Probe
Temperature Sensor Resistance/Voltage Chart
Temp Resistance* Voltage
°
F Ohms @ Input*
-10.............93333 ........4.620
-5...............80531 ........4.550
0 ...............69822........4.474
5 ...............60552........4.390
10..............52500........4.297
15..............45902........4.200
20..............40147........4.095
25..............35165........3.982
30..............30805........3.862
35..............27140........3.737
40..............23874........3.605
*Chart Notes:
1. Use the resistance column to check the thermistor sensor while disconnected from the controllers (not powered).
2. Use the voltage column to check sensors while connected to powered controllers. Read voltage with meter set on DC volts. Place the "-"(minus) lead on GND terminal and the "+"(plus) lead on the sensor input terminal being investigated. If the voltage is above 5.08 VDC, the sensor or wiring is "open." If the voltage is less than 0.05 VDC, the sensor or wiring is shorted.
Temp Resistance* Voltage
F Ohms @ Input*°
45..............21094........3.470
50..............18655........3.330
52..............17799........3.275
54..............16956........3.217
56..............16164........3.160
58..............15385........3.100
60..............14681........3.042
62..............14014........2.985
64..............13382........2.927
66..............12758........2.867
68..............12191........2.810
Temp Resistance* Voltage
F Ohms @ Input*°
69..............11906 ........2.780
70..............11652 ........2.752
71..............11379 ........2.722
72..............11136 ........2.695
73..............10878........2.665
74..............10625........2.635
75..............10398........2.607
76..............10158........2.570
78..............9711 ..........2.520
80..............9302..........2.465
82..............8893..........2.407
Temp Resistance* Voltage
°
F Ohms @ Input*
84..............8514..........2.352
86..............8153..........2.297
88..............7805..........2.242
90..............7472..........2.187
95..............6716..........2.055
100............6047..........1.927
105............5453..........1.805
110............4923..........1.687
115............4449..........1.575
120............4030..........1.469
125............3656..........1.369
Notes:
1.)All Wiring To Be In Accordance With
Local And National Electrical Codes And Specifications.
FILENAME
G-DUCSENS1.CDR
DATE:
PAGE
1
07/13/15
DESCRIPTION:
OE230 & OE231
Duct Temperature Sensor
JOB NAME
DRAWN BY:
B. CREWS
Page 14
Gasketed Cover
Technical Specifications
Sensor Element:
Type III Thermistor 10k ohm @ 77ºF
Accuracy:
± 0.4º F between 40º F to 95º F
Range:
-30º F to 150º F
CAUTION! See Note3
3.00”
Cover Mounting Screw - Typ.
2.30”
2.70”
Closure Plug
CAUTION! See Note 2
0.21" Dia. x 0.73 Lg. Slot - Typ.
4.50”
3.00”
2.25”
1.13”
Sensor Tube
CAUTION! See Note 1
Front View Side View
Outside Air Sensor OE250
Mounting Tab & Screw - Typ.
Closure Plug
CAUTION! See Note 2
Back View
Mounting Tab & Screws - Typ.
Incorrect
See Note #1
Incorrect
Sensor Mounting
Postion
Correct
Temperature Sensor Resistance/Voltage Chart
Temp Resistance* Voltage
°
F Ohms @ Input*
-10.............93333 ........4.620
-5...............80531 ........4.550
0 ...............69822........4.474
5 ...............60552........4.390
10..............52500........4.297
15..............45902........4.200
20..............40147........4.095
25..............35165........3.982
30..............30805........3.862
35..............27140........3.737
40..............23874........3.605
Temp Resistance* Voltage
F Ohms @ Input*°
45..............21094........3.470
50..............18655........3.330
52..............17799........3.275
54..............16956........3.217
56..............16164........3.160
58..............15385........3.100
60..............14681........3.042
62..............14014........2.985
64..............13382........2.927
66..............12758........2.867
68..............12191........2.810
Temp Resistance* Voltage
F Ohms @ Input*°
69..............11906 ........2.780
70..............11652 ........2.752
71..............11379 ........2.722
72..............11136 ........2.695
73..............10878........2.665
74..............10625........2.635
75..............10398........2.607
76..............10158........2.570
78..............9711 ..........2.520
80..............9302..........2.465
82..............8893..........2.407
*Chart Notes:
1. Use the resistance column to check the thermistor sensor while disconnected from the controllers (not powered).
2. Use the voltage column to check sensors while connected to powered controllers. Read voltage with meter set on DC volts. Place the "-"(minus) lead on GND terminal and the "+"(plus) lead on the sensor input terminal being investigated. If the voltage is above 5.08 VDC, then the sensor or wiring is "open." If the voltage is less than 0.05 VDC, the sensor or wiring is shorted.
Notes:
1.)The Outside Air Sensor Must Be Mounted In A Vertical Position As Shown (Sensor Tube Pointing
Water Must Not Be
Down).
Allowed To Stand In Sensor Tube. Rainwater Will Damage Sensor.
Sensor Must Be Located Where It Will Not Be Affected By Direct Sunlight Or Heat Producing Equipment. If Possible Mount Under Roof Eave Or Similar Protected Location. If Sensor Is Not Located As Specified, Erroneous Outside Air
2.)Unused Conduit Opening(s) Must Have Closure Plugs Installed And Must Be Coated with Sealing Compound To Provide Raintight Seal. Water Can
Damage Sensor!
3.)Gasket Must Be Installed Under Cover
Plate To Provide Raintight Seal.
Rainwater Can Damage Sensor!
4.)All Wiring To Be In Accordance With Local And National Electrical Codes And Specifications.
Temperature Readings Will Result.
Temp Resistance* Voltage
°
F Ohms @ Input*
84..............8514..........2.352
86..............8153..........2.297
88..............7805..........2.242
90..............7472..........2.187
95..............6716..........2.055
100............6047..........1.927
105............5453..........1.805
110............4923..........1.687
115............4449..........1.575
120............4030..........1.469
FILENAME
G-OE250-OAS-PDWG.CDR
DATE:
PAGE
1
07/13/15
Outside Air Temperature Sensor
JOB NAME
DRAWN BY:
DESCRIPTION:
OE250
B. CREWS
Page 15
R
US CO
OE265-15-A
Description
The OE265-15-A E-BUS Horizontal Outdoor Air Temperature and Humidity is a combination Outdoor Air Temperature and Outdoor Air Humidity sensor that connects to the VCB-X Controller using an EBC E-BUS modular cable.
This sensor is used when both Outdoor Air Temperature and Humidity are needed for the VCB-X Controller to do Wetbulb or Dewpoint Economizer Control. It is also used if the VCB-X Controller is used in a Make Up Air application to initiate dehumidification based on an Outdoor Air Dewpoint Setpoint.
E-BUS Horizontal Outdoor
Air Temperature and Humidity Sensor
4.91
4.18
2.82
2.34
2.35
HINGED COVER
E-BUS CONNECTOR
FEMALE END
4321
3M
3.29
SENSING TUBE
36.00 APPROX.
FILTE
3M
4321
EBC-10F
"WATTMASTER EBUS" "WATTMASTER EBUS"
EBC-10F
3M
4321
120.00 APPROX.
E-B
NNECTOR EXTENSION CABLE WITH MALE ENDS PROVIDED WITH SENSOR
Mounting
A 10 foot EBC E-BUS cable (provided) plugs into the E-BUS Outdoor Air Temperature and Humidity Sensor's attached 3 foot cable and then attaches to an E-BUS Expansion port on the VCB-X Controller or into another available E-BUS Expansion port. The sensor should be mounted in the upright position as shown in an area that is protected from the elements and direct sunlight.
CAUTION: Be sure to mount the E-BUS Outdoor Air Temperature & Humidity Sensor in an area that is not exposed to direct sunlight. The shaded area under the HVAC unit rain hood is normally a good location. Unused conduit opening(s) must have closure plugs installed and must be coated with sealing compound to provide a rain-tight seal. Water can damage the sensor.
Technical Data OE265-15-A E-BUS Horizontal Outdoor Air Temperature
and Humidity Sensor
Sensor Element Digital Capacitive Sensing
Device
Sensor Reading Range
Ambient Tempera-
40F to 120F
RH = 0-100%
-40F to 180F
ture Limits
Three Year Warranty
Accuracy
RH +/-2%, Temp +/- .5F
Connection
Weight
WattMaster reserves the right to change specifications without notice
E-BUS
2.3 oz.
Form: Orion-OE265-15-A-EBUS-Horiz-OA-RH-Sensor-01A Page 1 of 1
Page 16
.
US CO
Description
The OE265-16 E-BUS Vertical Outdoor Air Temperature and Humidity is a combination Outdoor Air Temperature and Outdoor Air Humidity sensor that connects to the VCB-X Controller using an EBC E-BUS modular cable.
This sensor is used when both Outdoor Air Temperature and Humidity are needed for the VCB-X Controller to do Wetbulb or Dewpoint Economizer Control. It is also used if the VCB-X Controller is used in a Make Up Air application to initiate dehumidification based on an Outdoor Air Dewpoint Setpoint.
OE265-16
E-BUS Vertical Outdoor
Air Temperature and Humidity Sensor
FILTER
4.91
4.18
2.82
2.34
SENSING TUBE
2.35
HINGED COVER
3.29
Mounting
A 10 foot EBC E-BUS cable (provided) plugs into the E-BUS Outdoor Air Temperature and
E-BUS CONNECTOR
FEMALE END
Humidity Sensor's attached 3 foot cable and then attaches to
4321
an
3M
E-BUS Expansion port on the VCB-X Controller or into another available E-BUS Expansion port. The sensor should be mounted in the upright position as shown in an area that is protected from the
3M
4321
EBC-10F
"WATTMASTER EBUS" "WATTMASTER EBUS"
EBC-10F
elements and direct sunlight. CAUTION: Be sure to mount the
E-BUS Outdoor Air Temperature
E-B
NNECTOR EXTENSION CABLE WITH MALE ENDS PROVIDED WITH SENSOR
120.00 APPROX.
& Humidity Sensor in an area that is not exposed to direct sunlight. The shaded area under the HVAC unit rain hood is normally a good location. Unused conduit opening(s) must have closure plugs installed and must be coated with sealing compound to provide a rain-tight seal. Water can damage the sensor.
Technical Data OE265-16 E-BUS Vertical Outdoor Air Temperature
and Humidity Sensor
Sensor Element Digital Capacitive Sensing
Device
Sensor Reading Range
Ambient Tempera­ture Limits
40F to 120F
RH = 0-100%
-40F to 180F
Three Year Warranty
Accuracy
Connection
Weight
WattMaster reserves the right to change specifications without notice
RH +/-2%, Temp +/- .5F
Form: Orion-OE265-16-EBUS-Vert-OA-RH-Sensor-01B Page 1 of 1
36.00 APPROX
3M
4321
E-BUS
2.3 oz.
Page 17
R
US CO
OE265-17-A
E-BUS Return Air
Description
The OE265-17-A E-BUS Return Air Temperature and Humidity is a combination Return Air Temperature and Return Air Humidity sensor that connects to the VCB-X Controller using an EBC E-BUS modular cable.
This sensor is used when both Return Air Temperature and Return Air Humidity are needed for the VCB-X Controller. The Return Air Humidity Sensor can be used to initiate dehumidification based on an Indoor Humidity Setpoint.
Mounting
A 50 foot EBC E-BUS cable (provided) plugs into the E-BUS Return Air Temperature and Humidity Sensor's attached 3 foot cable and then attaches to an E-BUS Expansion port on the VCB-X Controller or into another available E-BUS Expansion port.
Temperature and Humidity Sensor
4.91
4.18
E-B
2.82
2.34
HINGED COVER
E-BUS CONNECTOR
FEMALE END
4321
3M
3M
4321
NNECTOR EXTENSION CABLE WITH MALE ENDS PROVIDED WITH SENSOR
"WATTMASTER EBUS" "WATTMASTER EBUS"
EBC-10F
50.00 FEET APPROX.
2.35
EBC-10F
3.29
36.00 APPROX.
3M
4321
ALL DIMENSIONS ARE IN INCHES UNLESS OTHERWISE NOTED.
FILTE
SENSING TUBE
Technical Data OE265-17-A E-BUS Return Air Temperature
and Humidity Sensor
Sensor Element Digital Capacitive Sensing
Device
Sensor Reading Range
Ambient
40F to 120F
RH = 0-100%
-40F to 180F Temperature Limits
Three Year Warranty
Form: ORION-OE265-17-A-EBUS-Return-RH-Sensor-01A Page 1 of 1
Accuracy
RH +/-2%, Temp +/- .5F
Connection
Weight
WattMaster reserves the right to change specifications without notice
E-BUS
2.3 oz.
Page 18
T op
V iew
Left
Side
V iew
Front
V iew
Installation Instructions:
1.) Place The Outside Air Humidity Sensor Where It Is To Be Mounted. See Note 1 Below For Important Mounting Information And Considerations. Mark The (4) Mounting Holes. Secure The Humidity Sensor By Using The Four #10 X 1.5" Self Tapping Screws Included With The Humidity Sensor.
Right
Side
V iew
6.70
INCORRECT
2.) Open The Cover by Moving the Latch to the Side And Install Your Conduit Connectors. The Cover Must Always Be Opened Before Attempting To Punch Out The Knockouts.
3.) Connect The Wires To The Corresponding Sensor Wire Leads Per The Wiring Diagram On Page 2 Of This Drawing. Insert the Wires Into the Sealant Filled Connectors Provided and Crimp. Lightly Tug on the Wire to Assure a Good Mechanical Connection
4.) Close The Cover by Pushing Down Until the Latch Snaps Into Place. Be Careful Not To Pinch The Sensor Wires When Closing The Housing Cover.
5.) Verify That You Are Getting A Humidity Reading On Your Control System. Please Note That It May Take Ten To Twenty Minutes For The Sensor Reading To Stabilize Upon Initial Power Up.
Notes:
1.) The Outside Air Humidity Sensor Must Be Mounted In A Vertical Position As Shown (Sensor Tube Pointing Down). Water Must
Not Be Allowed To Stand In Sensor Tube, it Will Cause Erroneous Sensor Readings. The Sensor will recover when it dries out. Sensor Must Be Located
Where It Will Not Be Affected By Direct Sunlight Or Heat Producing Equipment. If Possible Mount Under Roof Eave Or Similar Protected Location. If Sensor Is Not
Located As Specified, Erroneous Outside Air
Humidity Readings Will Result.
2.) Unused Conduit Opening(s) Must Not be Knocked Out to Prevent Dust
or Insects From Infiltrating the Sensor
Electrical Box.
3.) All Wiring To Be In Accordance With Local And National Electrical
Codes And Specifications.
G-OE265-13B-OAHUMID-1F.PDF
PAGE
1 of 2
CORRECT
FILE NAME
DATE: 08/25/11
Outside Air Humidity Sensor – 0-5 VDC
INCORRECT
Sensor Mounting Position
JOB NAME
DRAWN BY: B. CREWS
DESCRIPTION
OE265-13 BAPI
Page 19
0-5 VDC Output Wiring (24VAC Power)
CONNECT TO
24 VAC POWER
Be Sure To Observe
Polarity Or Serious
Damage To The
Board Could Result
Terminal
0-5VDC
LB101966
Label:
Not Used
BLK
RED
GND
WHT
0-5V
VACorDC
SENSOR TERMINAL BLOCK
Warning
Humidity Sensor
RH/Voltage Chart
RH Output % VDC
5 .......... 0.25
10 .......... 0.50
15 .......... 0.75
20 .......... 1.00
25 .......... 1.25
30 .......... 1.50
35 .......... 1.75
40 .......... 2.00
45 .......... 2.25
50 .......... 2.50
*Chart Notes:
1. First, be sure that +24VAC power is being supplied to the sensor. Second check the sensor output. Set the meter to DC volts and connect the meter between ground and the 0-5 VDC input terminal on the controller board or between the 0-5 VDC output on the sensor and its ground wire or you can measure voltage at the 0-5 VDC and GND terminals on the sensor located at the sensor installtion location. After measuring the voltage use an accurate humidity measurement device to determine RH (relative humidity) such as an aspirating psychrometer. Use the Output VDC column to read the Output Voltage corresponding with the RH percentage measured with the psychrometer. If the measured voltage is within 3% of what is listed for the corresponding RH, then the sensor is functioning properly.
Notes:
1.) All Wiring To Be In Accordance With Local And National Electrical Codes And Specifications.
RH Output % VDC
55 ........ 2.75
60 ........ 3.00
65 ........ 3.25
70 ........ 3.50
75 ........ 3.75
80 ........ 4.00
85 ........ 4.25
90 ........ 4.50
95 ........ 4.75
100 ........ 5.00
FILE NAME
G-OE265-13B-OAHUMID-1F.PDF
DATE: 08/25/11
PAGE
2 of 2
Outside Air Humidity Sensor – 0-5 VDC
JOB NAME
DRAWN BY: B. CREWS
DESCRIPTION
OE265-13 BAPI
Page 20
See Note #1
Mounting
Sensor to Duct
Top
View
Left Side View
Installation Instructions:
1.) Drill a 1" Diameter Hole In The Duct Wall In the Location Where The Humidity Sensor Is To Be Mounted. Insert The Probe Of The Return Air Humidity Sensor Through The Hole. See Note 1 Below For Important Mounting Information And Considerations. Mark The (4) Mounting Holes. Secure The Humidity Sensor By Using The Four #10 X 1.5" Self Tapping Screws Included With The Humidity Sensor.
2.) Open The Cover by Moving the Latch to the Side And Install Your Conduit Connectors. The Cover Must Always Be Opened Before Attempting To Punch Out The Knockouts.
3.) Connect The Wires To The Corresponding Sensor Wire Leads Per The Wiring Diagram On Page 2 Of This Drawing. Insert the Wires Into the Sealant Filled Connectors Provided and Crimp. Lightly Tug on the Wire to Assure a Good Mechanical Connection
4.) Close The Cover by Pushing Down Until the Latch Snaps Into Place. Be Careful Not To Pinch The Sensor Wires When
5.) Verify That You Are Getting A Humidity Reading On Your Control System. Please Note That It May Take Ten To Twenty Minutes For The Sensor Reading To Stabilize Upon Initial Power Up.
Front View
Closing Th e Housing Cover.
Right
Side
View
Notes:
1.) The Sensor Should Be Mounted so that the 6" Probe is in the Center of the Return Air Duct. It Should be Mounted Away from Fans, Elbows, Heating or Cooling Coils or Other Equipment that Could Affect the Measurement of Relative Humidity. Also, the Sensor Should be Mounted in an Area that Receives Adequate Air Flow for Proper Operation. The Sensor may be Mounted Horizontally or Vertically to the Return Air Duct. See the Sensor Mounting Diagram Above.
2.) Unused Conduit Opening(s) Must Not be Knocked Out to Prevent Dust or Insects From Infiltrating the Sensor Electrical Box.
3.) The Sensor Probe Gasket Must Be Installed Between the Back of the Sensor Box and the Duct to Provide an Airtight Seal.
4.) All Wiring To Be In Accordance With Local And National Electrical Codes And Specifications.
FILE NAME
G-OE265-14B-RAHUMID-1D.PDF
DATE: 08/28/07
PAGE
1 of 2
Return Air Humidity Sensor – 0-5 VDC
JOB NAME
DRAWN BY: B. CREWS
DESCRIPTION
OE265-14 BAPI
Page 21
0-5 VDC Output Wiring (24 VAC Power)
CONNECT TO
24 VAC POWER
Be Sure To Observe
Polarity Or Serious
Damage To The
Unit Could Result
Terminal
LB101966
0-5VDC
Label:
Not Used
BLK
RED
GND
WHT
0-5V
VACorDC
SENSOR TERMINAL BLOCK
Warning
Humidity Sensor
RH/Voltage Chart
RH Output % VDC
5 .......... 0.25
10 .......... 0.50
15 .......... 0.75
20 .......... 1.00
25 .......... 1.25
30 .......... 1.50
35 .......... 1.75
40 .......... 2.00
45 .......... 2.25
50 .......... 2.50
*Chart Notes:
1. First, be sure that +24VAC power is being supplied to the sensor. Second check the sensor output. Set the meter to DC volts and connect the meter between ground and the 0-5 VDC input terminal on the controller board or between the 0-5 VDC output on the sensor and its ground wire or you can measure voltage at the 0-5 VDC and GND terminals on the sensor located at the sensor installtion location. After measuring the voltage use an accurate humidity measurement device to determine RH (relative humidity) such as an aspirating psychrometer. Use the Output VDC column to read the Output Voltage corresponding with the RH percentage measured with the psychrometer. If the measured voltage is within 3% of what is listed for the corresponding RH, then the sensor is functioning properly.
Notes:
1.) All Wiring To Be In Accordance With Local And National Electrical Codes And Specifications.
RH Output % VDC
55 ........ 2.75
60 ........ 3.00
65 ........ 3.25
70 ........ 3.50
75 ........ 3.75
80 ........ 4.00
85 ........ 4.25
90 ........ 4.50
95 ........ 4.75
100 ........ 5.00
FILE NAME
G-OE265-14B-RAHUMID-1D.PDF
DATE: 08/28/07
PAGE
2 of 2
Return Air Humidity Sensor – 0-5 VDC
JOB NAME
DRAWN BY: B. CREWS
DESCRIPTION
OE265-14 BAPI
Page 22
Right Side View
Front View
Installation Instructions:
1.) Place The SpaceHumidity Sensor Where It Is To Be Mounted. See Note 1 Below For Important Mounting Information And Considerations.
2.) Remove The Humidity Sensor Cover By Screwing In The 2 Allen Screws That Secure It To The Base.
3.) Connect All Of The Wires From The Controller Board To The Corresponding Terminal Blocks Per The Wiring Diagram On Page 2 Of This Drawing.
4.) Secure The Cover Onto The Base Housing By Snapping The Cover Onto The Base And Backing Out The 2 Allen Screws.
5.) Verify That You Are Getting A Humidity Reading On Your Control System. Please Note That It May Take Ten To Twenty Minutes For The Sensor Reading To Stabilize Upon Initial Power Up.
Notes:
1.) The sensor is designed to be wall mounted in rooms where appearance is important. It may be mounted directly on dry wall or on any single gang electrical outlet box with no adapters required. Toggle bolts or other direct wall mount screws can be used where conduit is not required. It includes a detachable mounting plate. The cover is secured with tamper-resistant hex screws. The sensor should be mounted approximately five feet above the floor, on an interior wall, away from any heating or cooling generating devices, and out of the sun. Plug the wireway hole to prevent false readings by air drafts within the wall.
2.) All Wiring To Be In Accordance With Local And National Electrical Codes And Specifications.
FILE NAME
G-OE265-11-SPHUMID1D.PDF
DATE: 08/02/07
PAGE
1 of 2
Space Humidity Sensor – 0-5 VDC
JOB NAME
DRAWN BY: B. CREWS
DESCRIPTION
OE265-11
Page 23
0-5 VDC Output Wiring (24 VAC Power)
Be Sure To Observe
Polarity Or Serious
Damage To The
Board Could Result
Not Used
Not Used
0-5VDCTerminal
Gnd
Vin
Vo
Label: LB101969
Warning
Humidity Sensor
RH/Voltage Chart
RH Output % VDC
5 .......... 0.25
10 .......... 0.50
15 .......... 0.75
20 .......... 1.00
25 .......... 1.25
30 .......... 1.50
35 .......... 1.75
40 .......... 2.00
45 .......... 2.25
50 .......... 2.50
*Chart Notes:
1. First, be sure that +24VAC power is being supplied to the sensor. Second, set the meter to DC volts and connect the meter between ground and the 0-5 VDC input terminal on the controller board or between the 0-5 VDC output terminal on the sensor and its ground terminal. Use an accurate humidity measurement device to determine RH (relative humidity) such as an aspirating psychrometer. Use the Output VDC column to read the Output Voltage corresponding with the RH percentage measured with the psychrometer. If the measured voltage is within 3% of what is listed for the corresponding RH, then the sensor is functioning properly.
Notes:
1.) All Wiring To Be In Accordance With Local And National Electrical Codes And Specifications.
RH Output % VDC
55 ........ 2.75
60 ........ 3.00
65 ........ 3.25
70 ........ 3.50
75 ........ 3.75
80 ........ 4.00
85 ........ 4.25
90 ........ 4.50
95 ........ 4.75
100 ........ 5.00
FILE NAME
G-OE265-11-SPHUMID1D.PDF
DATE: 08/02/07
PAGE
2 of 2
Space Humidity Sensor – 0-5 VDC
JOB NAME
DRAWN BY: B. CREWS
DESCRIPTION
OE265-11
Page 24
Description
The OE265-06 Wall Mounted Humidistat is used with the HVAC unit controller to initiate dehumidification when the relative humidity in the space rises above the user adjustable setpoint. It is designed to be mounted on the wall in the space where sensing is required.
The Wall Mounted Humidistat is adjust­able for relative humidity between 10% to 90% with a differential relative humidity of 5%.
OE265-06 – Wall Mounted
Humidistat
2.88"
% Relative Humidity
40 60 80
20
1.63”
The electrical switch on the Humidstat is
3.31”
4.38”
a snap-acting SPDT type. The switch is rated at 8 Amps resistive load and 60 VA pilot duty load at 24 VAC.
The Humidistat is enclosed in a beige plastic housing with a removable cover. The cover face is of brushed bronze with relative humidity markings indicating relative humidity setpoints between 10%
Mounting Holes In Humidistat Base
to 90%. A removable dial is provided for the adjustment of the relative humidity setpoint. The Humidistat is also provided with a blank cover plate to facilitate tam­per proof installations. The external set­point cover plate is first removed and then the blank cover plate is installed. An Allen screw and 5/64” Allen wrench is also provided to complete the tamper proof hardware..
Six inch long color coded leads are provided on the back of the Humidistat base for wiring connections. A green grounding lead is provided for grounding requirements.
Mounting
The Humidistat can be mounted to a flush or surface switch box using the provided screws. It can also be mounted directly to the wall if your wiring codes allow for mounting of 24 Volt devices without a switch box. Mounting screws for direct wall mounting must be provided by others.
Technical Data
Humidity Sensing Element
Control Dial Settings 10 to 90% RH Location NEMA 1 Indoor Locations Only Differential 5% RH Housing Beige Plastic with Brushed Bronze Cover
Operating Humidity 5% to 95% RH Non-
Operating Temp
Three Year Warranty
Form: ORION-OE265-06-Humidistat-1C.doc Page 1 of 1
Nylon Ribbon Electrical Switch Snap acting SPDT Rated at 8 Amps
Connections 6” Long Color Coded Wire Leads with
condensing 40°F to 125°F
Weight 1 Lb.
WattMaster reserves the right to change specifications without notice
OE265-06 Wall Mounted Humidistat
Resistive Load. 60 VA Pilot Duty Load
Plate. Also includes Tamper Proof Cover Plate and Tamper Resistant Hardware
Ground Wire
Page 25
Description
The OE265-07 Duct Mounted Humidistat is used with the HVAC unit controller to initiate dehumidification mode when the relative humidity in the return air duct rises above the user adjust­able setpoint. The Duct Mounted Humidistat is designed to be mounted on the side of the HVAC unit return air duct.
The Duct Mounted Humidistat is adjustable for relative humidity setpoints between 15% to 95%. The Duct Mounted Humidistat has a relative humidity differential of 5%.
The electrical switch on the Duct Mounted Humidstat is of the snap-acting SPDT type. The switch is rated at 8 Amps resis­tive load and 345 VA pilot duty load at 120 VAC.
4.75”
OE265-07 – Duct Mounted
Humidistat
6.50”
0
2
0
1
% HUMIDITY
50
0
4
0
3
6
0
7
0
8
0
9
0
2.24"
1.25"
2.81"
The Humidistat is enclosed in a metal housing with a removable cover and duct mounting plate. The mounting base plate face is labeled with relative humidity markings indicating relative humidity setpoints between 15% to 95%. A dial knob is provided for the adjustment of the relative humidity setpoint. The dial knob can be locked at the setpoint position by tightening the dial lock screw to facilitate tamper proof installations.
Color coded wiring terminals are provided for wiring connections to the humidistat. A green grounding lead is provided for grounding requirements.
Mounting
The Duct Mounted Humidistat is designed to be mounted on the side of the HVAC unit return air duct. 4 screws are provided for mounting the humidistat to the return air duct. A mounting template is also provided to help lo­cate the mounting holes and the duct cut-out on the duct wall.
Technical Data
Humidity Sensing Element
Control Dial Settings 15 to 95% RH Location NEMA 1 Indoor Locations Only Differential 5% RH Housing Painted Metal Operating Humidity 5% to 95% RH Non-
Operating Temp
Three Year Warranty
Nylon Ribbon Electrical Switch Snap acting SPDT Rated at 8 Amps
Connections Color Coded Wire Terminals with Ground
condensing
40°F to 125°F
Weight 1.5 Lb.
WattMaster reserves the right to change specifications without notice
OE265-07 Duct Mounted Humidistat
Resistive Load. 345 VA Pilot Duty Load
Terminal
Form: ORION-OE265-07-Humidistat-1B.doc Page 1 of 1
Page 26
GasketedCover
CAUTION! SeeNote3
SensorWire LeadsInside WeatherProof Enclosure
AmbientLight SensorEye ThreadedInto WaterProof Enclosure
3.00”
Cover Mounting Screw-Typ.
2.30”
FrontView SideView
AmbientLightSensor OE259
MountingTab &Screw-Typ.
ClosurePlug
CAUTION! SeeNote2
2.70”
0.21"Dia.x0.73 Lg.Slot-Typ.
MountingTab &Screws-Typ.
ClosurePlug
CAUTION! SeeNote2
BackView
TheAmbientLightSensorIsAPhotoSensitiveResistorHousedInAWaterProofEnclosure. ItIsUsedInConjunctionWithTheOE310-21-LPLightingControllerToSenseThePresenceOrAbsence OfAmbientLightForTheControlOfLightingCircuitsConnectedToTheController.TheSensor HasAResistanceInExcessOf1MOhmsInDarknessAndRangesDownToLessThan1.5KOhmsIn BrightLight.TheSensorWireConnectionsAreNon-Polarized.SeeTheOE310-21-LPWiringDiagramFor CorrectWiringConnections.SeeNote1ForMountingLocationCautions.
Notes:
1.)TheAmbientLightSensorShould BeInstalledOutdoorsWhereItCan SenseTheAmbientLightLevel.Do NotMountInAShadyAreaOrNear AnyObstructionsThatWouldBlock TheSensorEye.TheAmbientLight SensorShouldBeMountedOnIts SideInAHorizontalPositionSo WaterWillNotPuddleAroundThe SensorEye.
2.)UnusedConduitOpening(s)Must
HaveClosurePlugsInstalledAndMust BeCoatedwithSealingCompoundTo ProvideRaintightSeal.WaterCan
DamageSensor!
CorrectMountingPosition IncorrectMountingPosition
3.)GasketMustBeInstalledUnderCover PlateToProvideRaintightSeal.
RainwaterCanDamageSensor!
4.)AllWiringToBeInAccordanceWith LocalAndNationalElectricalCodes AndSpecifications.
FILENAME
G-OE259-AmbLightSnsr1A.CDR
DATE: B.CREWS
PAGE
1
06/17/03
DESCRIPTION:
AmbientLightSensor
JOBNAME
DRAWNBY:
OE259
Page 27
Butt Splice Wire Leads To Extend Wires To Controller Terminals. Connect One Wire Lead To Return Water Temperature Or Supply Water Temperature Terminal At The Controller As Required By Intended Use. Secure Other Wire Lead To Ground Terminal At The Controller. See Note 3.
Secure Sensor Element And Thermal Mastic Strip To Pipe With Supplied Wire Tie. Be Sure To Tighten Wire Tie Snugly To Ensure Good Thermal Contact Between Pipe And Sensing Element.
Sensing Element (Supplied)
Install Sensing Element With Curved Face Touching Pipe Surface As Shown
Wire Tie (Supplied)
Supply Or Return Water Pipe. See Note1&2.
Important Note: For Accurate Temperature Readings It Is Necessary To Place Insulation Over The Sensor After Installation. This Prevents The Ambient Temperature From Affecting The Sensor. Insulation Should Cover The Sensor And Extend 6“ to 12” Beyond Each End Of The Sensor.
Temp Resistance* Voltage
F Ohms @ Input*
°
-10.............93333 ........4.620
-5...............80531 ........4.550
0 ...............69822........4.474
5 ...............60552........4.390
10..............52500........4.297
15..............45902........4.200
20..............40147........4.095
25..............35165........3.982
30..............30805........3.862
35..............27140........3.737
40..............23874........3.605
*Chart Notes:
1. Use the resistance column to check the thermistor sensor while disconnected from the controllers (not powered).
2. Use the voltage column to check sensors while connected to powered controllers. Read voltage with meter set on DC volts. Place the "-"(minus) lead on GND terminal and the "+"(plus) lead on the sensor input terminal being investigated. If the voltage is above 5.08 VDC, the sensor or wiring is "open." If the voltage is less than 0.05 VDC, the sensor or wiring is shorted.
Notes:
1.)Sensor Should Be Mounted At Location Along Pipe Length That Best Represents Desired Temperature Reading.
2.)Sensing Element Shown
Mounted To Top Of Pipe. The Sensor Element May Be Located
At Any Location Around Pipe.
3.)All Wiring To Be In Accordance
With Local And National Electrical Codes And Specifications.
Thermal Mastic
Place Between Pipe And Sensing Element. Pipe Should Be Clean And Smooth To Provide Proper Thermal Contact With Sensing Element.
Thermal Mastic Strip (Supplied)
Temperature Sensor Resistance/Voltage Chart
Temp Resistance* Voltage
F Ohms @ Input*°
45..............21094........3.470
50..............18655........3.330
52..............17799........3.275
54..............16956........3.217
56..............16164........3.160
58..............15385........3.100
60..............14681........3.042
62..............14014........2.985
64..............13382........2.927
66..............12758........2.867
68..............12191........2.810
Temp Resistance* Voltage
F Ohms @ Input*°
69..............11906 ........2.780
70..............11652 ........2.752
71..............11379 ........2.722
72..............11136 ........2.695
73..............10878........2.665
74..............10625........2.635
75..............10398........2.607
76..............10158........2.570
78..............9711 ..........2.520
80..............9302..........2.465
82..............8893..........2.407
FILENAME
G-OE233-W-TempSnsr1a.CDR
DATE: 01/03/05
PAGE
OE233 - Strap-On Temperature
1
Temp Resistance* Voltage
F Ohms @ Input*
°
84..............8514..........2.352
86..............8153..........2.297
88..............7805..........2.242
90..............7472..........2.187
95..............6716..........2.055
100............6047..........1.927
105............5453..........1.805
110............4923..........1.687
115............4449..........1.575
120............4030..........1.469
125............3656..........1.369
JOB NAME
CONTROLS
DRAWN BY:
DESCRIPTION:
B. CREWS
Sensor Kit Installation
Page 28
Static Pressure Pickup Tube OE290
Connect This End Of Tubing To “Hi” Port Of Pressure Sensor
1/4“ O.D. X 3/16” I.D. x 14” Long - Fire Rated Tubing Slide Over 1/4“ Barb Fitting Tubing Not To Exceed 250 Ft. Length. Do Not Splice Tubing.
1/8“ MPT Threaded Pipe
Thread Together
1/4“ Barb Fitting
3/4"
2-3/4“
1/4" Hex Head Sheet Metal Screws
Drill 5/16" Hole In Ductwork For Probe
Mounting Plate
Mounting Plate
Gasket
Adhesive Backed Drill Guide Mounting Template
Duct Work
4.0"
Caution!
In Order To Obtain Accurate Static Pressure Readings The Static pressure Pickup Probe Should Be Mounted Per The Following Recommendations:
1.)The Probe Should Be Mounted In a Straight Section Of Ductwork Approx. 2/3 The Length Of the Supply Duct, Downstream Of The HVAC Unit.
2.)The Probe Should Not Be Mounted Less Than 3 Duct Diameters Downstream Or Not Less Than 2 Duct Diameters Upstream Of Any Elbow or Takeoff.
See The Systems Installation And Operation Manual For Other Design Considerations And Recommendations Regarding Static Pressure Pickup Tube Location.
Notes:
1.)The Static Probe(OE290) Is Supplied With A 14“ Length Of Tubing For Connection To The Static Pressure Sensor. The Static Pressure Sensor (OE271) Is Designed To Be Mounted Adjacent To The Location Where The Static Pickup Tube Is Mounted And Wired Back To The Controller Board. The Static Pressure Sensor Can Also Be Mounted Close To The Controller Board And Tubing (By Others) Routed From The Sensor To The Static Pickup Probe. Be Sure Not To Kink The Tubing Between The Static Pickup Probe And The Static Pressure Sensor.
FILENAME
SPUTUBE1.CDR
DATE:
PAGE
1
05/21/00
Static Pressure Pickup Tube
JOB NAME
CONTROLS
DRAWN BY:
DESCRIPTION:
OE290
B. CREWS
Page 29
The OE230 Duct Sensor Threads Into The OE291 Stainless Steel Thermowell. The OE291 Thermowell Threads Into A 1/2” FPT Elbow or Tee in the Water Piping of the Water Coil at Which You wish to Measure the Water Temperature. The Pipe must be a minimum of 4” Diameter or an Extended Tee and Bushing Configuration Must be Used to Accommodate the Length of the Thermowell Assembly.
Leads Are Non-polarized. Butt Splice Leads To 24 Gauge Wire Minimum. Connect Leads To "Analog In" And "Ground" At Controller.
OE230 Temperature Sensor (Ordered Separately)
Caution!
The Duct Sensor Is Used For Sensing Entering Or Leaving Water Temperatures. Location Of The Sensors Is Very Important In Order To Obtain Accurate Temperature Readings. The Following Recommendations Should Be Followed:
Entering Water
When Used As A Supply Water Temperature Sensor The Sensor Should Be Mounted In The Supply Water Piping As Close To The Water Coil As Possible For Best Accuracy, Apply Insulation On The Outside Of The Piping Over The Sensor. This Will Help Thermal Gradients From Affecting The Sensor.
Leaving Water
When Used As A Leaving Water Temperature Sensor The Sensor Should Be Mounted In The Return Piping As Close To The Water Coil Outlet As Possible. For Best Accuracy, Apply Insulation On The Outside Of The Piping Over The Sensor. This Will Help Thermal Gradients From Affecting The Sensor.
See The Systems Installation And Operation Manual For Other Design Considerations And Recommendations Regarding Water Temperature
Using OE230 Temperature Sensor
1/8 -27 NPT External Thread"
1/8 -27 NPSM Internal Thread"
OE291 Stainless Steel Thermowell
5.13"
4.94
"
3.25"
1/2" NPT External Thread
0.5"
OE291 Thermowell Assembly
Temp Resistance* Voltage
F Ohms @ Input*
°
-10.............93333 ........4.620
-5...............80531 ........4.550
0 ...............69822........4.474
5 ...............60552........4.390
10..............52500........4.297
15..............45902........4.200
20..............40147........4.095
25..............35165........3.982
30..............30805........3.862
35..............27140........3.737
40..............23874........3.605
*Chart Notes:
1. Use the resistance column to check the thermistor sensor while disconnected from the controllers (not powered).
2. Use the voltage column to check sensors while connected to powered controllers. Read voltage with meter set on DC volts. Place the "-"(minus) lead on GND terminal and the "+"(plus) lead on the sensor input terminal being investigated. If the voltage is above 5.08 VDC, the sensor or wiring is "open." If the voltage is less than 0.05 VDC, the sensor or wiring is shorted.
Notes:
1.)All Wiring To Be In Accordance With Local And National Electrical Codes And Specifications.
Temperature Sensor Resistance/Voltage Chart
Temp Resistance* Voltage
F Ohms @ Input*°
45..............21094........3.470
50..............18655........3.330
52..............17799........3.275
54..............16956........3.217
56..............16164........3.160
58..............15385........3.100
60..............14681........3.042
62..............14014........2.985
64..............13382........2.927
66..............12758........2.867
68..............12191........2.810
Temp Resistance* Voltage
F Ohms @ Input*°
69..............11906 ........2.780
70..............11652 ........2.752
71..............11379 ........2.722
72..............11136 ........2.695
73..............10878........2.665
74..............10625........2.635
75..............10398........2.607
76..............10158........2.570
78..............9711 ..........2.520
80..............9302..........2.465
82..............8893..........2.407
FILENAME
G-OE291-T-Well.CDR
DATE:
PAGE
1
07/09/04
Water Temperature Sensor Thermowell
Temp Resistance* Voltage
F Ohms @ Input*
°
84..............8514..........2.352
86..............8153..........2.297
88..............7805..........2.242
90..............7472..........2.187
95..............6716..........2.055
100............6047..........1.927
105............5453..........1.805
110............4923..........1.687
115............4449..........1.575
120............4030..........1.469
125............3656..........1.369
JOB NAME
DRAWN BY:
DESCRIPTION:
B. CREWS
OE291
Page 30
OE271 - For
Applications
0-5” H O Pressure Range - 5 VDC Operation
2
Minimum Typical Maximum
Full Scale Output (Positive Pressure)
Null Offset
Span*
Non-Linearity
Hystereisis And Repeatability
Temperature Error
Null +10 To 40 C°°
Span +10 To 40 C°°
Stability (1 Year)
Supply Voltage (Vs)
Common Mode Pressure
Pressure Overload
Positive Pressure (Hi Side) Negative Pressure (Lo Side)
Burst Pressure
Positive Pressure (Hi Side) Negative Pressure (Lo Side)
*Span Is The Algebraic Difference Between End Points (Null OffsetAnd Full Scale Output)
3.92 VDC
0.17 VDC 0.2-0.3 VDC 0.33 VDC
3.59 VDC 3.91 VDC
4.75 VDC 5.0 VDC
Requiring 0-5” H O Pressure Range
3.95-4.05 VDC
3.65-3.85 VDC
±0.3 % Span ±0.5 % Span
±0.03 % Span
±1.0 % Span ±1.0 % Span
±0.5 % Span
Airflow Sensor
2
4.08 VDC
±0.05 % Span
±1.5 % Span ±1.5 % Span
8.0 VDC
15 PSI
25“ H O
2
15“ H O
2
50“ H O
2
25“ H O
2
1.29"
2.94"
0.15"
2.50"
2.20"
IN (Red)
GND
OUT
IN
UP
OE271
S.P. Sensor
(-)LO
Top View
12.0" APPROX.
OUT (Black)
GND (Green)
0.15" DIA.
0.60"
0.200" (3/16" Tubing Conn.)
0.125" (1/8" Tubing Conn.)
Warning!
The plastic housing on the sensor is electrically conductive. Avoid contact with any electrical components. It is acceptable to mount the sensor on grounded sheet metal such as ductwork, electrical panels, etc.
Warning!
Use extreme care when mounting the sensor to avoid damage to the plastic housing. Do not overtighten the mounting screws! Do not use mounting screws which are too large for the holes!
General Notes
Caution:
1.) The Airflow Sensor Should Be Mounted In A Vertical Position As Shown With Arrow Pointing Up. ( Tubing Connections Pointing Down). If This Mounting Position Is Not Possible In Your Application, It May Be Mounted In A Horizontal Position. When Mounted In A Horizontal Position Accuracy Will Be Affected By Approximately 2% Full Scale Null Shift Due To Diaphragm Gravity Effect Error.
Duct Static Pressure Sensor Applications Mounting Information
When The OE271 Is Used As A Duct
Pressure Sensor
Ductwork Near The Static Pressure Pickup Tube. If The Sensor Is Mounted In This Manner, Away From The Controller, The Modular Plug Must Be Cut Off And 3-conductor 24 Gauge Minimum Wire Must Be Butt Spliced Between The Sensor And The Modular Plug To Extend The Sensor Wire Length. Total Wire Length Should Not Exceed 100Ft. If Desired The Sensor May Also Be Located Near The Controller, With The Modular Plug On The Sensor Directly Connected To The Mating Controller Jack. When This Method Is Used Tubing Must Be Run From The Sensor To The Static Pressure Pickup Tube. Tubing Should Not Exceed 250 Ft. And Must Be Continuous Without Any Splices.
It May Be Mounted To The
0.35"
2.)All Wiring To Be In Accordance With Local And National Electrical Codes And Specifications.
VAV Pressure Independent Airflow Sensor Applications Mounting Information
Static
When The OE271 Is Used As An Airflow For VAV Applications It Should Be Mounted In The VAV Box Control Enclosure Near The Box Controller Board. The Modular Plug should be Connected To The VAV Controller Board Connection. Tubing Must Be Run From The Sensor to The Airflow Pickup Probe Tubing Connection.
G-OE271TRAN1.CDR
DATE:
PAGE
1
FILENAME
08/19/08
1.95"
Side View
Sensor
JOB NAME
DRAWN BY:
DESCRIPTION:
OE271
Pressure Sensor
0.55"
1.00"
B. CREWS
Page 31
OE274 - Velocity Pressure For P. I. VAV/Zone ControlSensor
0-1.5“ H O Pressure Range - 5 VDC Operation
2
Minimum Typical Maximum
Full Scale Output (Positive Pressure)
Null Offset
Span*
Non-Linearity
Hystereisis And Repeatability
3.92 VDC
3.95-4.05 VDC
0.17 VDC 0.2-0.3 VDC 0.33 VDC
3.59 VDC 3.91 VDC
3.65-3.85 VDC
±0.3 % Span ±0.5 % Span
±0.03 % Span
Temperature Error
Null +10 To 40 C°°
Span +10 To 40 C°°
Stability (1 Year)
Supply Voltage (Vs)
4.75 VDC 5.0 VDC
±1.0 % Span ±1.0 % Span
±0.5 % Span
Common Mode Pressure
Pressure Overload
Positive Pressure (Hi Side) Negative Pressure (Lo Side)
Burst Pressure
Positive Pressure (Hi Side) Negative Pressure (Lo Side)
*Span Is The Algebraic Difference Between End Points (Null Offset And Full Scale Output)
4.08 VDC
±0.05 % Span
±1.5 % Span ±1.5 % Span
±1 % Span
8.0 VDC
15 PSI
5“ H O
2
3“ H O
2
10“ H O
2
5“ H O
2
2.94"
1.29"
0.15"
2.50"
2.20"
IN (Red)
GND
OUT
IN
UP
OE274
P.I. Sensor
(-)LO
Top View
1.95"
12.0" APPROX.
OUT (Black)
GND (Green)
0.15" DIA.
0.60"
0.200" (3/16" Tubing Conn.)
0.125" (1/8" Tubing Conn.)
0.55"
Warning! Warning!
The plastic housing on the sensor is electrically conductive. Avoid contact with any electrical components. It is acceptable to mount the sensor on grounded sheet metal such as ductwork, electrical panels, etc.
Notes:
1.) The Velocity Pressure Sensor Should Be
Caution:
Mounted In A Vertical Position As Shown With Arrow Pointing Up. ( Tubing Connections Pointing Down). If This Mounting Position Is Not Possible In Your Application, It May Be Mounted In A Horizontal Position. When Mounted In A Horizontal Position Accuracy Will Be Affected By Approximately 2% Full Scale Null Shift Due To Diaphragm Gravity Effect Error.
2.)All Wiring To Be In Accordance With Local And National Electrical Codes And Specifications.
0.35"
Side View
Use extreme care when mounting the sensor to avoid damage to the plastic housing. Do not overtighten the mounting screws! Do not use mounting screws which are too large for the holes!
1.00"
FILENAME
PITRAN1.5.CDR
DATE:
PAGE
1
10/20/01
Pressure Independent Velocity Sensor
JOB NAME
CONTROLS
DRAWN BY:
DESCRIPTION:
OE274
B. THRALL
Page 32

Description
The OE258 Building Static Pressure Sen­sor is used to sense building pr essure in applications where monitoring of the building static pressure is required to in­sure the building maintains the proper air pressurization.
0.95
0.156 DIA. HOLE TYP. 2 PL.
MODEL 265
The OE258 Building Pressure Sensor case is molded from fire retardant glass filled polyester. The sensor utilizes a ten­sioned stainless steel diaphragm and in­sulated stainless steel electrode. This arrangement allows up to 10 PSI over­pressure without damage to the unit. T he sensor provides a 0.0 to 5.0 VDC output in response to a –0.25 to +0.25 inch WC pressure differential. Ac curacy is ± 1% of full scale of the sensor.
For easy wiring the OE258 Building Static Pressure Sensor has (3) 6- 32 screw ter­minal wiring connectors. The sensor has (2) ¼” barbed fittings provided for the connection of tubing to the high and low pressure ports.
The OE258 Static Pressure Sensor is designed to be mounted to a flat surf ace by means of the (2) 0.156 diam eter holes provided in the sensor casing. For accu­rate readings the sensor must be mounted in a vertical position.
2.74
HIGH
setra
LOW
-
0.95
+
1.89
3.16
+
+
1.64
Technical Data OE258 - Building Static
Pressure Sensor
Operating Pressure Range
Operating Temp Circuit 3 Wire Non-repeatability Accuracy
Three Year Warranty WattMaster reserves the right to change specifications without notice
Form: ORION-OE258-6-BuildingPressureSensor-1B.doc
-0.25” WC to +0.25” WC Pressure Differential
0°F to 150°F
± 1% of full scale
Power Input Signal Output Hysteresis
Weight 3 ounces
± 0.1% of full scale
± 0.05% of full scale
9-30 VDC
0 to 5 VDC
Page
1 of 1
Page 33
Description
The OE256-01 Wall Mounted CO2 Sensor is used in conjunction with the VCM-X Control­ler (OE332-23-VCM) to monitor and control
levels in the building environment.
CO
2
Some typical applications are:
Demand Ventilation Control Controlling ventilation in a building
where the occupancy varies frequently
Controlling ventilation based on CO
2
levels to ensure excess outside air is not causing energy waste
To ensure good air distribution
throughout building zones
The OE256-01 is used for monitoring room
levels and is designed for permanent
CO
2
wall mounting in the conditioned space. It connects to the VCM-X Controller by using a modular prefabricated cable with RJ-45 con­nectors. It can be daisy chained with the Ori­on Modular Room Temperature Sensor or Digital Room Temperature Sensor for appli­cations requiring both a room CO and room temperature sensor.
The OE256-01 CO
Sensor uses non-
2
dispersive infrared (NDIR) technology. The CO
Sensor’s accuracy is 50 ppm @1000
2
ppm or 2% of the measured value and has a measurement range of 0-2000 ppm.
sensor
2
OE256-01 Wall Mounted CO2 Sensor
Mounting
The OE256-01 CO2 Sensor utilizes a sub­base mounting plate with either terminal blocks or modular phone jack providing for quick and easy mounting and wiring. The wall-mounted sensor’s sub-base is compatible with standard junction boxes. A locking screw secures the assembly to the wall.
Technical Data OE256-01 – CO
Input Power 12-34 VDC Power Consumption 30 mW Maximum Average
1.25 W Peak Power
Operating Temperature Sample Method Diffusion Or Flow—through
Sensitivity Analog Output 0-5 VDC Communications I2C
One Year Warranty WattMaster reserves the right to change specifications without notice
14 to 122 F
50-100 ml/min
<20 ppm
Operating Humidity 5-95% RH Non-Condensing Measurement Range 0 to 2000 ppm
Resolution
Form: ORION-OE256-01-CO2Sensor-1C.doc Page 1 of 1
Sensor
2
1 ppm
Page 34
Description
The OE256-02 Duct Mounted CO2 Sensor is used in conjunction with the VCM-X Con­troller (OE332-23-VCMX) to monitor and control CO ment. It can be configured via its address switch to be either a Supply Air CO sor or Return Air CO
Some typical applications are:
levels in the building environ-
2
Sen-
Sensor as required.
2
2
Demand Control Ventilation
Controlling ventilation in a building
where the occupancy varies fre­quently
Controlling ventilation based on CO
levels to ensure excess outdoor air is not causing energy waste
2
To ensure good air distribution
throughout building zones
The OE256-02 is used for monitoring duct CO
levels and is designed for permanent
2
duct mounting in the Supply or Return Air duct. It utilizes an aspiration box to accu­rately capture CO Return Air duct. It connects to the VCM-X by using a modular prefabricated cable with RJ-45 connectors. It can be daisy chained with the Orion Modular Room Temperature Sensor or Digital Room Temperature Sen­sor for applications requiring both a room CO
sensor and room temperature sensor.
2
The OE256-02 CO2 Sensor uses non­dispersive infrared (NDIR) technology and has a measurement range of 0-2000 ppm.
levels in the Supply or
2
OE256-02 Duct Mounted CO2 Sensor
Mounting
The OE256-02 CO2 Sensor is housed in an aspiration box. The sensor has an integral mounting sub-base mounting plate with modular phone jacks for connecting it to the VCM-X and another Digital or Modular Room Temperature Sensor. A conduit clamp is provided to help seal the opening where the sensor cabling penetrates the aspiration box housing. The sensor and aspiration box assembly is mounted to the ductwork by first cutting a 1 piration tube. The aspiration tube is then inserted into the hole. The aspiration box sensor assembly is then secured to the ductwork by inserting (4) supplied sheet metal screws through (4) mounting holes in the aspiration box base and securing the assembly by screwing it to the ductwork using a manual or powered screw driver to tighten the screws.
Technical Data OE256-02 Duct Mounted CO
Input Power 12-34 VDC Power Consumption 30 mW Maximum Average
Operating Temperature Sample Method Flow-Through
Sensitivity Accuracy
One Year Warranty WattMaster reserves the right to change specifications without notice
Form: ORION-OE256-02-DuctMtdCO2Sensor-1A.doc Page 1 of 1
±50 ppm @ 1000 ppm or 2%
14° to 122° F
50-100 ml/min
<±20 ppm
measured value
Operating Humidity 5-95% RH Non-Condensing Measurement Range 0 to 2000 ppm
Resolution Communications I
1
/4” diameter hole in the duct wall for insertion of the as-
Sensor
2
1.25 W Peak Power
±1 ppm
2
C
Page 35
OE256-05 Wall Mounted E-BUS CO2 Sensor
Description
The Wall Mounted E-BUS CO2 Sensor (Orion Part No. OE256-05; AAON Part No. V09310) is used in con­junction with the VCB-X Controller (Orion Part No. OE335-23-VCB-X; AAON Part No. V04740) to monitor and control CO
levels in the building environment.
2
Some typical applications are:
Demand Ventilation Control Controlling ventilation in a building where the oc-
cupancy varies frequently
Controlling ventilation based on CO
levels to
2
ensure excess outside air is not causing energy waste
To ensure good air distribution throughout build-
ing zones
The OE256-05 is used for monitoring room CO and is designed for permanent wall mounting in the conditioned space. It connects to the VCB-X using an E-BUS cable. It can be daisy chained with the 217-02 E-BUS Digital Room Temperature Sensor for applica­tions requiring both a room CO
sensor and room
2
temperature sensor. The OE256-05 CO
red (NDIR) technology. The CO
Sensor uses non-dispersive infra-
2
Sensor’s accuracy is
2
50 ppm @1000 ppm or 2% of the measured value and has a measurement range of 0-2000 ppm.
levels
2
4.54
2.80
0.96
0.80
Mounting
The OE256-05 CO2 Sensor utilizes a sub-base mount­ing plate with either terminal blocks or E-BUS connec­tion, providing for quick and easy mounting and wiring. The wall-mounted sensor’s sub-base is compatible with standard junction boxes. A locking screw secures the assembly to the wall.
Technical Data OE256-05 – CO
Input Power 12-34 VDC Power Consumption 30 mW Maximum Average
1.25 W Peak Power
Operating Temperature Sample Method Diffusion Or Flow—through
Sensitivity Analog Output 0-5 VDC Communications E-BUS
One Year Warranty WattMaster reserves the right to change specifications without notice
14 to 122 F
50-100 ml/min
<20 ppm
Operating Humidity 5-95% RH Non-Condensing Measurement Range 0 to 2000 ppm
Resolution
Form: AAON-OE256-05—EBUS-CO2Sensor-1A.doc Page 1 of 1
Sensor
2
1 ppm
Page 36
)
p
Description
The E-BUS Duct Mounted E-BUS CO2 Sensor with Remote Pickup (Orion Part No. OE256-07; AAON Part No. V09320) is used in conjunction with the VCB-X Controller (Orion Part No. OE335­23-VCB-X; AAON Part No. V04740) to monitor and control Return Air CO environment.
Some typical applications are:
levels in the building
2
OE256-07 E-BUS Duct Mounted CO2 Sensor
with Remote Picku
4.12"
3.31"
2.81”
5.00"
4.06"
HINGED COVER
2.55”
BRASS BARB FITTINGS FOR
0.170 I.D. TUBING
Demand Control Ventilation Controlling ventilation in a building where
the occupancy varies frequently
Controlling ventilation based on CO
levels to ensure excess outdoor air is not causing energy waste
To ensure good air distribution throughout
building zones
The OE256-07 is used for monitoring duct CO levels and is designed for permanent mounting in the Return Air duct. It utilizes an aspiration box to accurately capture CO nects to the VCB-X by using an E-BUS cable with E-BUS connectors.
The OE256-07 CO infrared (NDIR) technology and has a measure­ment range of 0-2000 ppm.
Mounting
The OE256-07 CO2 Sensor is housed in an aspira­tion box. A conduit clamp is provided to help seal the opening where the sensor cabling penetrates the aspiration box housing. The sensor has a Jack E-BUS connector for connecting it to the provided EBC E-BUS cable. The EBC E-BUS Cable con­nects to the VCB-X Controller or E-BUS Hub or Adapter Board and then to the VCB-X Controller. The sensor and aspiration box assembly is mounted and secured to the ductwork with the (2) supplied sheet metal screws. The remote pickup tube assembly is mounted separately to the duct­work by first cutting a 1 ductwork wall. The remote pickup tube is then in­serted into the hole. The remote pickup tube is then secured to the ductwork by inserting (2) supplied sheet metal screws through the (2) mounting holes in the remote pickup tube mounting plate and securing the remote pickup tube assembly by screwing it to the ductwork using a manual or powered screw driver to tighten the screws. Using the supplied 10 ft. long tub­ing, connect the remote pickup tube to the aspiration box assembly, cutting the tubing to fit.
levels in the duct. It con-
2
Sensor uses non-dispersive
2
1
/4” diameter hole in the
2
13.00" APPROX.
2
3M
4321
E-BUS CONNECTOR EXTENSION CABLE WITH MALE ENDS (PROVIDED WITH SENSOR)
4321
3M
CO2 SENSOR, HOUSING AND CABLE ASSEMBLY
CO2 PICKUP TUBE (PROVIDED WITH SENSOR)
EBC-10F
0.170 I.D. TUBING (PROVIDED WITH SENSOR
FIRE RATED
SENSOR HOUSING
E-BUS CONNECTOR FEMALE END
8.25"
"WATTMASTER EBUS" "WATTMASTER EBUS"
120.00” APPROX.
120.00” APPROX.
EBC-10F
3M
4321
BRASS BARB FITTINGS FOR
0.170 I.D. TUBING
0.55”
Technical Data OE256-07 E-BUS Duct Mounted CO
Sensor
2
with Remote Pickup
Input Power 12-34 VDC Power Consumption 30 mW Maximum Average
1.25 W Peak Power
Operating Temperature
14 to 122F
Sample Method Flow-Through
50-100 ml/min Sensitivity Accuracy
50 ppm @ 1000 ppm or
<20 ppm
2% measured value
One Year Warranty WattMaster reserves the right to change specifications without notice
Form: AAON-OE256-07-EBUS-DUCT-CO2-1B.doc Page 1 of 1
Operating Humidity 5-95% RH Non-Condensing Measurement Range 0 to 2000 ppm
Resolution
1 ppm
Communications E-BUS
Page 37
OE275-01 – Suction Pressure Transduce
r
e
(For Units With Digital Compressor)
Description
The OE275-01 Suction Pressure Trans­ducer is used to monitor the suction line pressure of a DX coil when the HVAC unit is equipped with a digital compressor. The Suction Pressure transducer is used in applications requiring tight control of the suction pressure in order to maintain coil efficiency during varying coil load condi­tions. The Suction Pressure Transducer monitors the suction pressure at the coil and this information is used to load/unload or stage compressors to maintain the suc­tion pressure at the DX coil within a pre­determined optimum operating range.
The OE275-01 Suction Pressure Trans­ducer metal wetted parts are made from stainless steel and Haynes 214 alloy. The Suction Pressure Transducer is weather resistant. Connection to the pressure source is accomplished by screwing the 1/4” SAE female Schrader fitting on the Suction Pressure Transducer onto a 1/4” Schrader male valve fitting (by others) that is welded into the suction line. The Suction Line Transducer provides a 0.5 to 4.5 VDC output in response to a 0 to 250 PSIG pressure. Transducer accuracy is ± 0.25% of the full scale of the transducer.
Not Used
Common
(Black)
0.50
Transducer Cable
Assembly - 6 Ft. Length
Top View
0.63
1.06
Front View
+ Excitation (Red)
1.28
- Output (White)
2.18
1/4” SAE Femal Schrader Fitting
For easy wiring the OE275-01 Suction Pressure Transducer has a 3 pin Packard connector that connects to a 6 foot long
Suction Pressure Transducer
prefabricated cable. The cable is supplied with a 3 pin Packard Metripak 150 mating connector for attachment to the sensor on one end and has 3 color coded stripped wires on the other end for attachment to the digital compressor’s control board. The stripped wire ends can be spliced to other wires to extend the wiring length when re­quired.
Technical Data OE275-01- Suction
Pressure Transducer
Operating Pressure Range -0 to 250 PSI Gauge Power Input 5 VDC Operating Temp
Wetted Parts Construction Stainless Steel Electrical Cable Connection 3 Pin Packard Connector Sensor Construction Haynes 214 Alloy Electrical Cable Length 6 Feet Pressure Fitting Construction Stainless Steel Accuracy Pressure Fitting Size
-40°F to 185°F
1/4” SAE Female
Schrader Fitting
Weight 2.3 Ounces Response Time
Three Year Warranty
Form: ORION-OE275-01-SuctionPressureTransducer-1E.doc Page 1 of 1
Signal Output 0.5 to 4.5 VDC
± 0.25% of Full Scale
Hysteresis Non-repeatability
WattMaster reserves the right to change specifications without notice
± 0.1% of Full Scale ± 0.05% of Full Scale ± 0.05% of Full Scale
Page 38
e
OE275-03-A Suction Pressure Sensor Kit
Description
The OE275-03-A Suction Pressure Sensor Kit with E-BUS Adapter is comprised of the OE275­01 Suction Pressure Transducer, an E-BUS Adapter Board, and a 3 foot EBC E-BUS cable. It is required for any VCB-X application with DX Cooling that requires Dehumidification. The Suction Pressure Transducer is used to meas­ure suction pressure at the HVAC unit’s DX evaporator coil suction line. This suction line pressure is converted to saturated refrigerant temperature by the VCB-X Controller. This tem­perature is used by the VCB-X Controller to accurately control the compressors to provide optimum performance from the system during Dehumidification operation.
The Suction Pressure Transducer connects to the E-BUS Adapter Board’s V, SIG, and GND terminals through a cable. The cable is supplied with a 3-pin Packard mating connector for at­tachment to the sensor on one end and has 3 color-coded stripped wires on the other end. The stripped wire ends can be spliced to other wires to extend the wiring length when required. The EBC E-BUS Cable connects to the E-BUS Adapter Board. This cable must then connect to the VCB-X Controller directly or to a VCB-X Expansion Board connected to the VCB-X Con­troller.
The OE275-03-A Suction Pressure Transduc­er’s metal wetted parts are made from stainless steel and Haynes 214 alloy. The Suction Pres­sure Transducer is weather resistant. Connec­tion to the pressure source is accomplished by screwing the 1/4” SAE female Schrader fitting on the Suction Pressure Transducer onto a 1/4” Schrader male valve fitting (by others) that is welded into the suction line. The Suction Line Transducer provides a 0.5 to 4.5 VDC output in response to a 0 to 250 PSIG pressure. Trans­ducer accuracy is 0.25% of the full scale of the transducer.
With E-BUS Adapter Board
0.63
1.06
+ Excitation
(Red)
1.28
- Output (White)
2.18
1/4” SAE Femal Schrader Fitting
E-BUS Adapter Board
Not Used
Common
(Black)
Top View
0.50
EBC E-BUS Cable
Technical Data OE275-03-A Suction
Pressure Sensor Kit with E-BUS Adapter
Operating Pressure Range -0 to 250 PSI Gauge Power Input 5 VDC Operating Temp Wetted Parts Construction Stainless Steel Electrical Cable Connection 3 Pin Packard Connector Sensor Construction Haynes 214 Alloy Electrical Cable Length 3 Feet Pressure Fitting Construction Stainless Steel Accuracy Pressure Fitting Size 1/4” SAE Female
Weight 2.3 Ounces Response Time
Three Year Warranty
Form: ORION-OE275-03-A-SuctionPressureSensorKit-wE-BUS-Adapter-1B.doc Page 1 of 1
-40F to 185F
Schrader Fitting
Signal Output 0.5 to 4.5 VDC
0.25% of Full Scale
Hysteresis Non-repeatability
WattMaster reserves the right to change specifications without notice
0.1% of Full Scale 0.05% of Full Scale 0.05% of Full Scale
Loading...