Orion MODGAS II User Manual

r
FACTORY CONTROLS SYSTEM
MODGAS II Controlle
Installation &
Operations Manual
r
FACTORY CONTROLS SYSTEM
MODGAS II Controlle
For Modulating Gas Heating Applications
Installation &
Operations Manual
This document is subject to change without notice.
WattMaster Controls, Inc. or AAON Inc. do not assume responsibility
for errors or omissions herein.
AAON MODGAS Controller
Installation & Operations Manual - Form WM-MG2-IOM-01C
AAON is a registered trademark of AAON, Inc.
Copyright 2010 WattMaster Controls, Inc.
All rights reserved.
Section 1
Table of Contents
Component Overview....................................................... 1
MODGAS II Controller............................................................................................................... 1
Blink Codes for Status LED ........................................................................................................ 2
Supply Air Temperature Sensor .................................................................................................. 4
Component Wiring............................................................ 5
MODGAS II Controller............................................................................................................... 5
Board Inputs & Outputs ................................................... 7
Analog Inputs .............................................................................................................................. 7
Relay Outputs .............................................................................................................................. 7
Setting DIP Switches .......................................................8
Discharge Air Temperature ......................................................................................................... 8
Discharge Air Temperature Reset Limit...................................................................................... 8
Table of Figures
Figure 1-1: MODGAS II Controller Component Locations.................................................... 2
Table 1-1: Diagnostic LED Blink Codes ................................................................................. 2
Figure 1-2: MODGAS II Controller Dimensions.................................................................... 3
Figure 1-3: Supply Air Sensor Installation.............................................................................. 4
Figure 1-4: MODGAS II Controller Wiring............................................................................ 5
Figure 1-5: MODGAS II Controller DIP Switch Settings...................................................9
Overview & Wiring
MODGAS II Controller Section 1
Component Overview
MODGAS II Controller
The MODGAS II Controller is designed to modulate a gas valve to maintain a desired Discharge Air Temperature. It also controls the speed of the induced draft fan to maintain proper combustion in the heat exchanger. The controller can be used as a stand-alone unit or be connected to the AAON HVAC unit controller as an expansion board.
The MODGAS II Controller has the following inputs and outputs:
4 Inputs:
Supply Air Temperature Sensor HEAT EN Input (24VAC)
Discharge Air Temperature Reset Signal from a
control automation system (0-10VDC)
AUX Input (not used)
4 Outputs:
Fan Enable (relay) LO SPEED fan control (relay)
AUX Output (relay / not used*) Gas Valve Analog Output (0-20VDC)
* If using EPROM SS0056 V 2.20 or higher, the AUX Output Relay is functional. Once the MODGAS II Controller brings on heat, if the Supply Air Temperature rises 5˚F and the valve output has reached 90%, then the AUX Relay will activate to bring on a 2 modulate as needed to maintain the Heating Supply Air Setpoint. If the modulating valve falls below 30%, the AUX Relay will disable.
When used in a stand-alone application (not connected to an AAON HVAC unit controller board), the MODGAS II Controller will modulate the gas valve to maintain the DISCHARGE setpoint set by the DIP switch on the board. The MODGAS II Controller is activated by a 24VAC signal to the HEAT EN input.
When the MODGAS II Controller is connected to an AAON HVAC unit controller via the modular cable, the following information will be passed between the MODGAS II and the AAON HVAC unit controller.
nd
stage of fixed heat. The modulating valve is then able to
Heat activation command The offset for the Supply Air
Temperature Sensor.
Hi Limit Temperature Setpoint. Heating Discharge Setpoint. This replaces the
setpoint that is set with the Discharge Air Temperature DIP switch on the MODGAS II Controller.
If the communication is interrupted
between the MODGAS II Controller and the AAON HVAC unit controller, the MODGAS II Controller will revert to stand-alone operation.
Overview and Wiring 1-1
Section 1 MODGAS II Controller
Status LED
Modulating Gas
Controller Board
These Terminals
Not Used For
This Application
24 VAC Power Input Terminals (See Note 1 & 2)
Max. Power Consumption 1 Gas Valve =15VA 2 Gas Valves = 30VA
C6
I2C IN
POWER
TB3
TB2
R26
R26
R25
Analog Input
Terminals
YS101826PREV 1 MODULATING GAS BOARD
PJ1
R15
R
SHLD
POWER
T
C7
U5
D8
V4
24VAC
GND
P1
RV1
+VDC
VR1
R7
D1
P
WDOG
CX6
U6
U1
C4
552 Processor Board
Notes:
1.)24 VAC Must Be Connected So That All Ground Wires Remain Common.
2.)All Wiring To Be In Accordance With Local And National Electrical Codes And Specifications.
Discharge Setpoint
Reset Limit DIP Switch
RST IN
SAT
AUX IN
GND
HEAT EN
C1
C2
R8
D2
R9
R2
CX1
PHILIPS
PHILIPS
C2
YS101818
P1
552 PROCESSOR BOARD
DIP Switch
STATUS
RESET LIMIT
F
F
J01
ADD
R1R3R1
P
U2
C3
R1
1
CX5
C1
PAL Chip Pin 1
Relay Output
LEDs
Relay Output
Terminals
DISCHARGE SETPOINT
TB1
O
O
F
F
1
1 2 4 8 16 32 64 128
R4
CX2
U5
2 4 8 16 32 64 128
ADD
RAM
CX4
RAM Chip Pin 1
LO SPD
FAN
LOSPD
FAN
U4
CX3
V1 V3K3V2
K1
AUX
COM
AUX
EPROM
U3
C13
EPROM Chip Pin 1
K2
FT
SER.#:
GAS
VALVE
GND
TB4
VOUT
V5
Gas Valve Output Terminals
Heat Sink
Must Be Fastened
With Sheet Metal
Screws
To A Sheet Metal
Surface
D9
Figure 1-1: MODGAS II Controller Component Locations
Blink Codes for Status LED
The MODGAS II Controller uses an on-board LED to indicate various diagnostic conditions during power-up and operation. The LED is labeled “STATUS”. Starting with power up, the LED blink codes are as follows:
One Blink
Off for five seconds
Blinks 30 times
Blinks 3 times rapidly
Status code repeatedly blinks every ten seconds to indicate controller status:
Priority No. of Blinks Status
Lowest 1 Normal Operation
- 2 SAT Over High Limit
Highest 3 Bad SAT Sensor
Table 1-1: Diagnostic LED Blink Codes
Only the highest priority failure code will be shown. You must correct the highest priority alarm before other problems will be indicated.
1-2 Overview and Wiring
MODGAS II Controller Section 1
Figure 1-2: MODGAS II Controller Dimensions
Overview and Wiring 1-3
Section 1 MODGAS II Controller
Supply Air Temperature Sensor
The supply air temperature sensor should be located in the ductwork downstream of the unit supply air connection. Locate the sensor in the center of the widest part of the duct. Use the supplied template and a and mount securely to the duct using the supplied sheet metal screws. Be sure the gasket is compressed to provide an air tight seal. For best accuracy, apply insulation on the outside of the duct, over the sensor. This will help prevent thermal gradients from affecting the sensor.
5
/16" drill to make a hole for the sensor. Install the gasket over the probe
Figure 1-3: Supply Air Sensor Installation
1-4 Overview and Wiring
MODGAS II Controller Section 1
Component Wiring
MODGAS II Controller
Figure 1-4: MODGAS II Controller Wiring
The MODGAS II Controller wiring is straightforward but allows for flexibility to set the system up exactly as required for the specific application. All wiring should follow the minimum wire sizing information that follows.
Overview and Wiring 1-5
Section 1 MODGAS II Controller
Warning: Use extreme care not to damage any of the electronic components while
mounting the controller. Mark the holes and then remove the MODGAS II Controller before drilling. Do not allow metal shavings to fall onto the circuit boards.
The MODGAS II Controller requires the following electrical connections: 18 Gauge minimum unless otherwise noted.
-24VAC Supply Voltage.......................................................................................2 Conductors
-Supply Air Temperature Sensor ...................................................(24 Ga. Min.) 2 Conductors
-Heat Enable................................................................................... (24 Ga. Min.) 2 Conductors
Tip: After making all electrical connections, it is advised that you unplug all terminal blocks
on the MODGAS II Controller until you are ready to begin the checkout procedure. This may help to prevent damage if wiring errors occur elsewhere in the system during installation or start-up.
1-6 Overview and Wiring
MODGAS II Controller Section 1
Board Inputs & Outputs
Analog Inputs
Input #1 - Heat Enable Contact (HEAT EN)
This input is only required when the controller is used in stand-alone operation; it is not required when used as an expansion board to other unit controllers.The Heat Enable input is activated by a 24 VAC signal supplied from a building automation system to enable the MODGAS II Controller. The controller will not operate without 24 VAC being applied to this input terminal when used in a stand-alone configuration.
Input #2 - Supply Air Temperature Sensor (SAT)
The Supply Air Temperature Sensor is the control source. This sensor has to be installed for the unit to operate. The Supply Air Sensor is located in the discharge air stream and monitors discharge air temperature to maintain the discharge air temperature setpoint.
Input #3 - Reset Input (RST IN)
The Discharge Temperature Setpoint can be reset by supplying a 0-10 VDC signal to the RST IN low voltage terminal block. This reset signal is optional and need only be used if you require resetting of the discharge air temperature.
Relay Outputs
Relay #1 - Fan Enable (FAN)
This relay works in conjunction with the LO SPEED relay to control the speed of the induced draft blower motor. When the MODGAS II Controller has heat enabled, this relay closes to bring the induced draft blower on at high speed. The controller will activate the LO SPEED relay to reduce the induced draft blower speed as the gas valve modulates closed.
Relay #2 - Fan Low Speed (LO SPD)
Depending on the gas valve position, this relay will close to switch the induced draft blower to low speed. The controller automatically switches the blower to low speed as the gas valve modulates closed in order to maintain proper fuel to air ratios.
Relay #3 - AUX Output (AUX)
If using EPROM SS0056 V 2.20 or higher, the AUX Output Relay is functional. Once the MODGAS II Controller brings on heat, if the Supply Air Temperature rises 5˚F and the valve output has reached 90%, then the AUX Relay will activate to bring on a 2 stage of fixed heat. The modulating valve is then able to modulate as needed to maintain the Heating Supply Air Setpoint. If the modulating valve falls below 30%, the AUX Relay will disable.
Gas Valve Output (VOUT)
This output is designed to supply a 0-20 VDC output signal for control of the modulating gas valve. Up to two gas valves may be connected to this output if required by the application. Do Not Connect More Than Two Gas Valves.
nd
Overview and Wiring 1-7
Section 1 MODGAS II Controller
Setting DIP Switches
Discharge Air Temperature
This switch is only used when the controller is operated in stand-alone mode. The main unit controller will set the discharge setpoint when the MODGAS II is used as an expansion device.
The user can set the desired Discharge Air Temperature Setpoint using the DIP Switch labeled DISCHARGE SETPOINT. See Figure 1-5 for location and DIP Switch setting instructions. The MODGAS II Controller will allow the user to set a Discharge Air Temperature Setpoint between 4F and 200°F. If a value of less than 4F is set, the controller will default to a 40°F Discharge Air Temperature Setpoint, a value greater than 200°F will cause the unit to default to a 140°F Discharge Air Temperature Setpoint.
Discharge Air Temperature Reset Limit
The user can reset the Discharge Air Temperature Setpoint by supplying a 0-10VDC control signal to the Reset Input (RST IN) terminal on the MODGAS II Controller board. The reset range is determined by the RESET LIMIT DIP Switch. See Figure 1-5 for location and setting instructions. The controller will reset the Discharge Air Temperature
Setpoint from the value set on the DISCHARGE SETPOINT DIP Switch to the value set on the RESET LIMIT DIP Switch, as the Reset Input (RST IN)
signal is increased from 0Volts to 10Volts.
Example:
We want the Discharge Air Temperature Setpoint to increase from 70°F when the Reset Input signal is at 0 Volts to 130°F when the Reset Input signal is at 10 Volts.
Set the DISCHARGE SETPOINT DIP Switch to 70°F
Set the RESET LIMIT DIP Switch to 130°F
The discharge air temperature will now increase from 70°F to 130°F as the Reset Input voltage signal ramps from 0 Volts to 10 Volts.
1-8 Overview and Wiring
MODGAS II Controller Section 1
NOTE: It is possible to create a “reverse acting” control sequence by setting the
DISCHARGE SETPOINT DIP Switch to 130°F and the RESET LIMIT DIP Switch to 70°F. In this case the controller will maintain a 130°F discharge temperature when the Reset Input signal is at 0 Volts and will reduce it to 70°F when the Reset Input signal is at 10 Volts.
Reset Limit DIP Switch
YS101826PREV 1 MODULATING GAS BOARD
P1
RV1
RST IN
SAT
+VDC
PJ1
I2C IN
TB2
C6
POWER
TB3
VR1
R15
R
SHLD
POWER
T
R26
R26
R25
C7
U5
D8
V4
24VAC
GND
HEAT EN
C1
R8
R9
R7
D1
P
WDOG
R2
CX6
U6
U1
PHILIPS
PHILIPS
C2
C4
P1
MODGAS II Controller Board
64+32+16+8=120
Discharge Setpoint DIP Switch
AUX IN
GND
C2
D2
CX1
STATUS
J01
P
C3
C1
YS101818 552 PROCESSOR BOARD
DISCHARGE
RESET LIMIT
O
F
F
1 2 4 8
16 32 64
128
ADD
R1R3R1
U2
R1
1
CX5
SETPOINT
R4
CX2
U5
TB1
O
F
F
1
LO SPD
FAN
2 4 8 16 32 64
LOSPD
FAN
128
ADD
RAM
U4
CX4
CX3
AUX
EPROM
COM
AUX
V1 V3K3V2
K1
U3
All Rocker Switches Depressed
In the Direction Of The ADD Arrow
Are Added Together To Total The Setpoint
K2
FT
SER.#:
GAS
VALVE
GND
C13
TB4
D9
VOUT
V5
128+2=130
O
F
F
1 2
4 8 16
32
64
128
ADD
Typical DIP Switch
Detail View
ADD
DIP Switch Setting Shown
Is For A Setpoint Of 120
ADD
DIP Switch Setting Shown
Is For A Setpoint Of 130
Figure 1-5: MODGAS II Controller DIP Switch Settings
Overview and Wiring 1-9
Section 1 MODGAS II Controller
1-10 Overview and Wiring
Section 2
Table of Contents
Hand Held Service Tool LCD/Keypad Operations............ 1
Data Entry Functions................................................................................................................... 1
Menu Screens ..................................................................2
Main Menu Screen #1 ................................................................................................................. 2
View Status......................................................................2
MODGAS II Controller Status .................................................................................................... 2
Change Setpoints............................................................. 3
MODGAS II Controller Setpoints............................................................................................... 3
Summary Screen.............................................................. 5
MODGAS II Controller Summary .............................................................................................. 5
Programming
MODGAS II Controller Section 2
Hand Held Service Tool LCD/Keypad Operations
Initialization Screen
Initializing
Service Tool v1.22 Mod Heat Controller Wattmaster Controls
The screen shown above is displayed for a few seconds after the service tool is powered up. This screen displays the current version of the software installed in your service tool.
The remainder of this section will lead the user through the system menus and keypad operations.
Data Entry Functions
A - Abort
B - Backup
C - Clear
D - Negative
* - Decimal
# - Enter
Used to exit from screens or from data entry. Use this key to return to the Main Menu from any screen in the system.
The user can step backwards to previous screens or setpoints by pressing this key.
If a data entry mistake is made, press this key to clear the data entry field and start over.
If the user is entering a setpoint that is negative in value, press this key for the minus sign.
Use this key as the decimal point when entering decimal values.
This key is used to close a data entry field and advance to the next item or screen.
Programming 2-1
Section 2 MODGAS II Controller
Menu Screens
After initialization, you will be advanced to the Main Menu screen. All status and setpoint screens are accessed from this screen and additional menu screens are also accessed from this Main Menu screen.
Main Menu Screen #1
1) View Status
2) Change Setpoints
3) Summary Screen
View Status
MODGAS II Controller Status
Accessed from Main Menu Screen #1 – Menu Item #1
The following status screens will appear when this menu item is selected and the selected unit is a Modulating Gas Heat Controller. Step to each additional screen by pressing the “#” key. Press the “A” key to exit before all status screens have been viewed. If the unit doesn’t respond, the data on the screen will not be valid, although you can still step through the screens to get an idea of what is displayed on each status screen. Use the “B” key to step backwards through the Status Screens.
Note: The top line of every status screen displays the same message that identifies the type
of unit you accessed. (Mod-Heat Controller)
Status Screen #1
Mod-Heat Controller
No Signal To Run
Supply Air: xxx.x°F
Line 2 -
Line 3 -
No Signal To Run = A signal has not initiated controller operation.
W1 Signal Active = A signal has initiated controller operation.
Supply Air xxx.x°F = Supply Air Temperature in degrees Farenheit
2-2 Programming
MODGAS II Controller Section 2
Status Screen #2
Mod-Heat Controller
MAX Setpoint: xxx°F MIN Setpoint: xxx°F
Line 2 -
Line 3 -
Max Setpoint = This is the value from the RESET LIMIT DIP switch on the MODGAS II Controller. This is the value that the controller will use as the Discharge Temperature Setpoint when the RESET INPUT voltage signal is at 10 VDC.
NOTE: It is acceptable for this value to be less than the MIN Setpoint for reverse acting control schemes.
Min Setpoint = This is the value from the DISCHARGE SETPOINT Dip switch on the MODGAS II Controller. This is the value that the controller will use as the Discharge Temperature Setpoint when the RESET INPUT voltage signal is at 0 VDC or when the no reset signal is connected.
Change Setpoints
MODGAS II Controller Setpoints
Accessed from Main Menu Screen #1 – Menu Item #2
Setpoint Screen #1
Controller Setpoints Proportional. Kp: xx
Integral......Ki: xx
Setpoint Screen #2
Controller Setpoints
Derivative Kd.: xxx Unwind Signal..:xxx
Kp = the proportional constant value for the PID loop. This value affects the process stability of the PID loop. Ki = the Integral constant value of the PID loop. This value is used to eliminate positioning error on the PID loop.
Proportional Kp 1 20 70 Integral Ki 0 5 90
Kd = The derivative constant value of the PID loop. This value is used to change the anticipation function on the PID loop.
The Integral Unwind value accounts for non-linear effects and limitations in the valve.
Minimum Default Maximum
Derivative Kd 0 5 90 Unwind Signal 0 5 30
Programming 2-3
Minimum Default Maximum
Section 2 MODGAS II Controller
Setpoint Screen #3
Controller Setpoints
PID LOOP PERIOD
Seconds......: xxx s
This value represents the sampling interval of the PID loop. It indicates the time in seconds between calculations.
Minimum Default Maximum
PID LOOP Period 0 sec. 15 sec. 100 sec.
Setpoint Screens #4
Controller Setpoints
Switch To HI Speed
Fan Above Sig: xxx%
This is the percentage open of the modulating gas valve where the Hi-Speed fan is required for proper induced airflow in the heat exchanger.
Switch To HI Speed
Minimum Default Maximum
0% 40% 100%
Fan Above Sig
Setpoint Screens #5
Controller Setpoints
SUPPLY CUT-OFF
Temp. Above..: xxx°F
If the Supply Air Temperature ever exceeds this value, the MODGAS II Controller will immediately be disabled. In order for the MODGAS controller to be re-enabled (resume normal operation), the temperature must drop 10°F below this setpoint.
Temp Above
Setpoint Screens #6
Controller Setpoints
Sensor Calibration
SAT: xx.x° xx.x°
The Thermistor Type III sensor readings can be calibrated. Enter a Positive value to increase a reading and a Negative value to decrease a reading.
Supply Sensor SAT
Minimum Default Maximum
50°F 150°F
300°F
Minimum Default Maximum
-100.0° 0.0°F +100.0°F
2-4 Programming
MODGAS II Controller Section 2
Summary Screen
MODGAS II Controller Summary
Accessed from Main Menu Screen #1 – Menu Item #3
OFF SAT xxx SP xxx
VLV xxx % Fan OFF
BRN1 OFF
O xx.x N xx.x D xx.x
Line 1 -
Line 2-
Line 3 -
Line 4 -
OFF – ON = Indicates if unit is off or on.
SAT = Supply Air Temperature at unit discharge in degrees Fahrenheit.
SP = Setpoint Temperature currently being used by the controller in degrees Fahrenheit.
VLV xxx % = Percentage that valve is open.
FAN – Off – Lo Speed – High Speed = Indication of fan condition and speed.
BRN1 = Indicates the status of the burner. This value is either ON or OFF.
O = Old Error – The previous error calculation.
N = New Error – Difference between the setpoint and the current temperature.
D = Desired Position – The position the valve is driving towards.
Programming 2-5
Form: WM-MG2-IOM-01C Printed in the USA March 2010 All rights reserved
WattMaster Controls Inc. 8500 NW River Park Drive Parkville MO 64152
Phone (816) 505-1100
Copyright 2010
E-mail: mail@wattmaster.com
2425 So. Yukon Ave • Tulsa, OK 74107-2728
Ph: (918) 583-2266 • Fax: (918) 583-6094
Fax (816) 505-1101
AAON Part No. R02950
Loading...