Orion KU Installation And Operating Instructions Manual

Website : www.orion-instruments.com
Kaustubha Udyog (Orion Instruments)
S. No. 36/1/1, Sinhgad Road, Vadgaon Khurd, Pune 411 041 INDIA Tel.: +91-(0) 20-24393877 Telefax : +91-(0) 20-24393577 / 25460486
Email : pressure@vsnl.com / info@orion-instruments.com
Certificate No.: FM72815
INSTALLATION AND OPERATING INSTRUCTIONS
KU Pressure Switches
Construction:
KU series pressure switches are housed in pressed steel powder coated enclosure and are recommended for panel mounting or indoor service. The repeat accuracy is better than +/-1.5 % FSR. Pressure port is 1/4” BSPM standard.
Principle of Operation:
The pressure in the pressure capsule is converted into force by means of a reinforced rubber diaphragm and a calibrated piston, which is balanced by a compression spring from above. When the force generated by the pressure in the pressure capsule exceeds/falls beyond the balancing spring force, an electrical element is actuated through a bell crank lever mechanism for accurate switching.
Please use the pressure switch well within the pressure and also the electrical parameters
Mounting
The pressure switches can be mounted in any direction. a) Pressure switches can be mounted directly in case the mounting is rigid. b) For panel mounting, Please use M4 bolts of appropriate length through the mounting holes . If the equipment is subject to vibration,
please use rubber washers / pads between the panel and the switch.
Connect the pressure tubing to the pressure port. The pressure port size is generally 1/4" B.S.P. Male, unless specially ordered otherwise. Other sizes can be obtained via adaptors.
Electrical Connections
Please use electrical loads well within the limits specified for the microswitch.
Wiring:
Please refer figure 2. a) Remove the cover. b) Pass the cable through the cable
bush (usually provided with the switch) and connect the wiring as per the wiring diagram.
The wiring code is as per the details given below.
Terminal 1 : (C) Common Terminal 2 : (NC) Normally Closed Terminal 3 : (NO) Normally Open
Please disconnect supply before wiring the switch, or removing the wiring. The cover should not be removed, if the supply is on.
APPROX. DIMENSIONS IN
mm
inches
INSTALLATION DRAWING
Fig 1.1
(0.90)
23
Pressure Port
(3.26)
83
(0.35)
9
17.5
(0.68)
33.5
(1.31)
12
(0.47)
(0.94)
24
1/4" BSP(M)
Cable Entry
12.5
(0.49)
60.5
(2.38)
Ø5, Mtg. Holes, 3 Nos.
(0.19)
Set Screw
Differential Screw
(1.75)
44.5
(0.82)
21
97.5
(3.83)
Fig. 1.2
Z
2 3
1
Set Point Adjustment:
Ensure the supply is off, before setting the switch. Status of contacts can be checked with a multimeter / continuity tester.
A) For adjustable differential models
Please refer Figure 2
1) Decide the cut-in (lower) pressure P1 & the cut-out (upper) pressure P2. The differential will be (P2 – P1).
2) Remove the cover.
3) Set the cut-in point on the main-scale with the help of the set-screw.
4) Turn the differential screw to the extreme positive end.
5) Apply the desired cutout (higher) pressure to the pressure switch
6) Decrease the differential pressure setting by turning the differential screw till contacts changeover.
7) Some minor adjustment will be required to achieve the exact cutin (lower) / cutout (higher) point, which can be checked with the help of a proper pressure measurement device.
8) Replace the cover back in the position.
Operating Temperatures:
The operating condition temperature restrictions for the KU Switch are as follows:
o o
Ambient : -5 C to +60 C
o o
Operational (all models): -5 C to +80 C Note : Switches with temperature ranges beyond the ones specified above can be supplied on request.
o o
storage :-5 C to +60 C
Trouble Shooting Tips:
Generally no problems are observed if the pressure switch selection, wiring and the setpoint is proper. For a pressure switch selection procedure, please consult our sales office. For properly selected pressure switches, if following symptoms are observed, the likely causes and remedies are as stated below.
Symptom 1: Switch does not operate
1) Wiring may not me correct. Check electrical connections to the pressure switch, if they are as per wiring diagram.
2) Pressure does not reach the pressure port. a) Check if the entry to the pressure capsule is not blocked by frozen process or
scales or impurities in the process. i) If this is the case, try freeing the blocked path by a blunt tool in case of
scales or impurities.
ii) For frozen process, it is advisable to use chemical seals.
DO NOT OPEN THE PRESSURE CAPSULE IN ANY EVENT.
If the cause is none of the above mentioned probabilities, proceed as per the following steps.
b) Check the system pressure & set point of pressure switch. For use of
pressure switch for falling setpoints, system pressure has to be greater than cutin point. For use of pressure switch for rising setpoints, the system pressure may not be reaching / exceeding the cutout point. i) For adjustable differential models turn the differential screw to the extreme
negative end.
ii) Use 'T' connection & connect calibrated pressure gauge to the 'T'
connection as shown in the figure 4.
iii) Adjust the setpoint such that the system pressure is greater than the cut-
out point of the pressure switch.
iv) If the switch still does not operate, remove the pressure switch physically
from the system. There should be continuity between terminals 1 & 2. If no continuity is observed, the pressure switch should be returned to the factory.
Symptom 2: Short Wiring
Isolate the switch electrically. Check the continuity between terminals and the screws fitted to the body. If no continuity is observed in between any of the terminals and screws fitted to the body, check the short connection elsewhere in the circuit. If continuity is observed, the wires of the pressure switch have internally touched the body, and the switch should be returned to the factory.
Symptom 3: Leakage
In case leakage is observed, the pressure switch has to be returned to the factory without opening the pressure capsule. Check for the following likely causes and use a new switch taking proper precautions. a) System pressure is greater than working pressure : Use an overrange protector or a switch with appropriate maximum working
pressure.
b) Incompatible wetted parts : The working medium may not be compatible with wetted parts, which damages the sealing of the process
from working parts. Use a chemical seal for the pressure switch or use proper compatible wetted parts.
c) Excessive process temperature : Process temperature may exceed maximum allowable temperature, which in turn damages the
diaphragms. Use an impulse tubing of proper length for cooling the process temperature. There may be a pressure drop depending on length of the impulse tube used. Adjust the setpoint of the pressure switch accordingly.
Symptom 4: Chattering
1) Check the system pressure for surges. Chattering is observed where the system pressure is close to the cutin / cutout point and the surge pressure exceeds the on-off differential. Use a pressure switch with an adjustable differential or use surge dampers in your system.
2) If there is a relay in the circuit, check if the relay is properly plugged in. Chattering may be due to loose contacts.
Fig. 2
Front Cover
Main Body
Scale Plate Set Screw
Differential Screw
C - Terminal 1 NC - Terminal 2 NO - Terminal 3
Cable Bush
Fig. 3
Cover
Pressure Port
Fig. 4
'T' Connection
System Pressure
Calibrated
Pressure
Gauge
Loading...