Orion E-BUS User Manual

E-BUS Digital Room Sensor
Technical Guide
TABLE OF CONTENTS
OVERVIEW ....................................................................................................................................... 3
BASIC OPERATION .......................................................................................................................... 4
Sensor Operation .....................................................................................................................................................4
LED Operation .........................................................................................................................................................4
MOUNTING AND WIRING ................................................................................................................ 5
Environmental Requirements ...................................................................................................................................5
Important Wiring Considerations ..............................................................................................................................5
SENSOR OPERATION ...................................................................................................................... 6
Main Sensor Display Screens....................................................................................................6
Temperature and Humidity Status Screen ..........................................................................................................6
Outside Air Temperature Humidity Status Screen...............................................................................................6
Unit Information Screen ......................................................................................................................................6
Setpoint Adjust Screen ........................................................................................................ ...............................7
Operation Modes ................................................................................................................................................7
TROUBLESHOOTING ....................................................................................................................... 8
Temperature Sensor Testing ...................................................................................................................................9
APPENDIX ..................................................................................................................................... 10
Sensor Confi guration and Test Screens ................................................................................................................10
Connecting the Digital Room Sensor to the HVAC Unit Controller ........................................................................12
Connecting a Wall Mounted E-BUS CO
Connecting a Remote Sensor ................................................................................................................................14
Mounting Plate Dimensions ...................................................................................................................................15
Sensor to the HVAC Unit Controller ......................................................13
2
PART NUMBER CROSS REFERENCE TABLE
PART DESCRIPTION ORION
E-BUS LCD Digital Room Sensor Temp Only OE217-02 E-BUS LCD Room Sensor Temp & Humidity OE217-03 E-BUS Digital Room Sensor Temp & Humidity OE217-04 E-BUS CO Mounting Plate BK000081 Return Air Temperature Sensor OE231 VCB-X Controller OE335-26B-VCBX VCC-X Controller OE338-26B-VCCX
WattMaster Controls Inc. 8500 NW River Park Drive · Parkville, MO 64152 Toll Free Phone: 866-918-1100 PH: (816) 505-1100 · FAX: (816) 505-1101 · E-mail: mail@wattmaster.com Visit our web site at www.orioncontrols.com
Sensor (Wall-Mounted) OE256-05
2
www.orioncontrols.com
AAON® is a registered trademark of AAON, Inc., Tulsa, OK. WattMaster Controls, Inc. assumes no responsibility for errors or omissions. This document is subject to change without notice. Form: OR-EBUS-DRS-TGD-01G Copyright May 2015 WattMaster Controls, Inc.
E-BUS DIGITAL ROOM SENSOR
Overview
Overview
The OE217 series of E-BUS Digital Room Sensors are used to sense Space T emperature only or Space Temperature & Space Humidity. See Figures 1 & 2.
The OE217-02 model is the Space T emperature Sensor only model and the OE217-03 & OE217-04 models are a combination Space T empera­ture & Space Humidity Sensor model. The OE217-04 model includes an enclosure without LCD display, front LEDs, and buttons.
The sensors can be used with the VCB-X Controller (OE335-26B­VCBX) and VCC-X Controller (OE338-26B-VCCX) and connect to the controller using various lengths of EBC E-BUS cables connected between the controller and the sensor. The EBC E-BUS cables should not run in conduit with other AC line voltage wiring or with any conductors carrying highly inductive loads.
The OE217-02 & OE217-03 sensors provide the following useful functions:
• Provides 112 x 64 monochrome Graphical LCD display with LED backlight
• Displays the Current Space Temperature
• Displays Outdoor Air Temperature (if controller is confi gured with an OA Temperature Sensor)
• Displays the Current Space Humidity (OE217-03 Model Only)
• Displays Outdoor Air Relative Humidity (OE217-03 Model if controller is confi gured with an OA Humidity Sensor)
• Displays the Current Zone Setpoint Temperature
• Equipped with Push Buttons for changing the Zone Setpoint Temperature
• Equipped with an Override Button for forcing the VCB-X Controller or VCC-X Controller into Occupied Operation from Unoccupied Operation
• Provides graphics to indicate the Mode of Operation
• Provides LEDs to indicate Schedule Override, Button Push, and Alarms
• Can display Temperature reading from a Remote Temperature Sensor (see Figure 20, page 14 for instructions)
Figure 1: OE217-02 & OE217-03 E-BUS Digital Room Sensor
Figure 2: OE217-04 E-BUS Digital Room Sensor
Operator Interface 3
E-BUS DIGITAL ROOM SENSOR
Basic Operation
Sensor Operation
When power is fi rst applied to the OE217-02 E-BUS Digital Room Sensor, the sensor will display the Current Room Temperature and the current setting of the slide offset. The OE217-03 model will also display Relative Humidity.
NOTE: The sensor readings are not accurate until the controller
that the sensor is connected to is done calibrating.
The sensor has 4 buttons—
<Down>. You can also access certain functions by touching the area
below the <Display> and <Override> buttons. The sensor has 3 LEDs—one to indicate an Override, one to indicate an Alarm, and one to indicate that a button has been pressed. See Figure 3 for LED and Button Descriptions.
An icon for the current mode of operation will appear in the sensor display. The operation mode icons are a Snowfl ake for Cooling Mode, a Flame for Heating Mode, a Fan in motion for Vent Mode, and a Moon for Unoccupied Mode. When the unit is in Unoccupied Mode, the screen’s background will turn dark. See Figur e 9, page 7 for examples of operation modes.
<Display>, <Override>, <Up>, and
LED Operation
Refer to Figure 3 below for LED locations.
Alarm LED: The Alarm LED will blink when there is an alarm from the Controller.
Sense LED: The Sense LED will blink when the sensor gets a valid touch.
Override LED: The Override LED is inoperable when in Occupied Mode. In Unoccupied Mode, if you touch the Override LED will blink, indicating an override request. The Control­ler will respond by sending the unit into override. The Override LED will then stay on for the duration of the Override. Any time the Unit is in Override, you can request to cancel the override by touching the
<Override> button, and the Override LED will blink. The Unit will
then cancel the override. The Override LED will then turn off. Comm LED: The Comm LED located on the back of the sensor
blinks on whenever communications are sensed.
<Override> button, the
Sense
LED LCD Display
Override LED
OVERRIDE ALARM
Alarm LED
Up Button
Display Button
Display
Override
Override Button
Down Button
Cover Set Screw
Front View
Figure 3: E-BUS Digital Room Sensor Components
Comm LED (Not visible with back cover on)
E-BUS Cable Connection
Remote Thermistor Sensor Connector
MICROCHIP
256GP206
PIC24HJ
SHLD
-COM
GND
+12Vdc
Back View
4
Operator Interface
E-BUS DIGITAL ROOM SENSOR
Mounting and Wiring
Environmental Requirements
The E-BUS Digital Room Sensor needs to be installed in an environment that does not exceed a temperature greater than 150°F or less than -30°F and does not exceed 90% relative humidity levels (non-condensing).
Indoor Reading Range
The E-BUS Digital Room Sensor’s Indoor Reading Range is 40°F to 120°F and 0-100% RH (RH is available on the OE217-03 & OE217-04 models). Its temperature reading accuracy is +/- .5°F, and its RH read­ing accuracy is +/-2%. Its sensor element is the integral communicating digital sensing device or external T ype III Thermistor 10K Ohm @ 77°F .
Outdoor Reading Range
If your E-BUS Digital Room Sensor is set up to read an Outdoor Air Temperature Sensor, any outdoor air temperature below -40°F will not appear on the E-BUS Digital Room Sensor’s display.
Important Wiring Considerations
The E-BUS Digital Room Sensors connect to the VCB-X or VCC-X Controller using various lengths of EBC E-BUS cable connected between the controller and the sensor. The EBC E-BUS cables should not run in conduit with other AC line voltage wiring or with any conductors carrying highly inductive loads. See Figure 18, page 12 for wiring.
Mounting
CAUTION: Do not touch the front face of the sensor while you
are plugging in the modular sensor cable. Touching the front face of the sensor while plugging in the cable may prevent proper initial­ization and keep the buttons on the sensor from working properly.
The E-BUS Digital Room Sensor is designed to be mounted to a vertical 2” x 4” electrical box recessed in the wall. If the wall cannot be pen­etrated, a plastic surface mount box such as those made by Wiremold may be used to mount the sensor to the wall surface. The Sensor should be mounted at least 5 feet above the fl oor.
The Sensor is mounted by removing the front cover and fastening the housing base to the electrical box using the supplied (2) 6/32” x 1” machine screws. The modular cable is then plugged into the phone jack located on the circuit board that is mounted on the cover. The cover is then placed onto the housing base, and the Allen Screw on the bottom of the base is adjusted to hold the cover in place. A locking screw secures the sensor to the wall. See Figure 4 for E-BUS Digital Room Sensor dimensions.
Optional Mounting Plate
Included with the Digital Room Sensor is a mounting plate that can be used, if necessary, to cover the sensor sheet rock opening. This mounting plate screws onto the back of the housing base. The mounting plate is then mounted and covers the recessed space in the wall. A locking screw secures the sensor to the wall. See Figure 21, page 15 for dimensions.
TM
1.00
2.80
OVERRIDE ALARM
0.69
4.55”
Display
Front View
Override
Side View
Figure 4: E-BUS Digital Room Sensor Dimensions
1.87
Remote Thermistor Sensor Connector
1.81
MICROCHIP
256GP206
PIC24HJ
SHLD
-COM
GND
+12Vdc
Back View
0.81
0.49
Operator Interface
5
Loading...
+ 11 hidden pages