Orion Digital Room User Manual

www.orioncontrols.com
Digital Room Sensor
Technical Guide
TABLE OF CONTENTS
OVERVIEW ....................................................................................................................................... 3
BASIC OPERATION .......................................................................................................................... 4
Sensor Operation .....................................................................................................................................................4
LED Operation .........................................................................................................................................................4
MOUNTING AND WIRING ................................................................................................................ 5
Indoor Reading Range ........................................................................................................................................5
Outdoor Reading Range .....................................................................................................................................5
Mounting ..................................................................................................................................................................5
SENSOR OPERATION ...................................................................................................................... 6
Main Sensor Display Screens....................................................................................................6
Temperature and Humidity Status Screen ..........................................................................................................6
Outside Air Temperature Humidity Status Screen...............................................................................................6
Unit Information Screen ......................................................................................................................................6
Setpoint Adjust Screen ........................................................................................................ ...............................6
TROUBLESHOOTING ....................................................................................................................... 7
Temperature Sensor Testing for OE217-00 .............................................................................................................7
APPENDIX ....................................................................................................................................... 8
Sensor Confi guration and Test Screens ..................................................................................................................8
Sensor Confi guration & Test Screen ...................................................................................................................8
Pixel Test Screen ................................................................................................................................................8
Sensor Info & LED Test Screen ..........................................................................................................................8
LCD Backlight Test Screens ...............................................................................................................................9
Thermistor Averaging Screen .............................................................................................................................9
Display Options - Temperature/Setpoint .............................................................................................................9
Connecting to VAV/Zone Controller & HVAC Unit Controller .................................................................................10
Connecting a Remote Sensor ................................................................................................................................ 11
Mounting Plate Dimensions ...................................................................................................................................12
PART NUMBER CROSS REFERENCE TABLE
PART DESCRIPTION ORION
Digital Room Sensor Temp Only OE217-00 Digital Room Sensor Temp & Humidity OE217-01 Mounting Plate BK000081 Space CO Duct Mounted CO Return Air Temperature Sensor OE231 VCM-X E-BUS Controller OE332-23E-VCMX
Sensor OE256-01
2
Sensor OE256-02
2
www.orioncontrols.com
WattMaster Controls Inc. 8500 NW River Park Drive · Parkville, MO 64152 Toll Free Phone: 866-918-1100 PH: (816) 505-1100 · FAX: (816) 505-1101 · E-mail: mail@wattmaster.com Visit our web site at www.orioncontrols.com
®
is a registered trademark of AAON, Inc., Tulsa, OK.
AAON WattMaster Controls, Inc. assumes no responsibility for errors or omissions. This document is subject to change without notice. Form: OR-DRS-TGD-01K Copyright May 2015 WattMaster Controls, Inc.
DIGITAL ROOM SENSOR
Overview
Overview
The OE217 series of Digital Room Sensors are used to sense Space T em­perature only or Space Temperature & Space Humidity. See Figure 1. The OE217-00 model is the Space T emperature Sensor only model and can be used with the VCM-X E-BUS Controller (OE332-23E-VCMX), RNE Controller (OE332-23E-RNE), SA E-BUS Controller (OE332-23E­VCMX-SA), and VAV/Zone Controller (OE324-02). The OE217-01 is a combination Space Temperature & Space Humidity Sensor model and can only be used with the VCM-X E-BUS, RNE, and SA-EBUS Controllers.
The sensor provides the following useful functions:
• Provides 112 x 64 monochrome Graphical LCD display with LED backlight
• Displays the Current Space Temperature or Cooling/Heating Setpoint on the Main Display Screen
• Displays Outdoor Air Temperature (if controller is confi gured with OA Temperature Sensor)
• Displays the Current Space Humidity (OE217-01 Model Only)
• Displays Outdoor Air Relative Humidity (OE217-01 Model if controller is confi gured with OA Humidity Sensor)
• Displays the Current Zone Setpoint Temperature
• Equipped with Push Buttons for changing the Zone Setpoint Temperature
• Equipped with an Override Button for forcing the VAV/Zone Controller or VCM-X / RNE / SA Controller into Occupied Operation from Unoccupied Operation
• Provides graphics to indicate the Mode of Operation
• Provides LEDs to indicate Schedule Override, Button Push, and Alarms
• Can display Temperature reading from a Remote Sensor (see Figure 19, page 11 for instructions)
• Can be used with the OE256-01 or OE256-02 CO2 Sensor (see notes in Figures 17 & 18, page 10 for instructions)
Both sensors connect to the controllers using various lengths of TSDRSC modular cables connected between the controller and the sensor. The TSDRSC modular cables should not run in conduit with other AC line voltage wiring or with any conductors carrying highly inductive loads.
Figure 1: Digital Room Sensor
Operator Interface 3
DIGITAL ROOM SENSOR
Basic Operation
Sensor Operation
When power is fi rst applied to the OE217-00 Digital Room Sensor, the sensor will display the Current Room T emperature or the Cooling/Heat­ing Setpoint and the current setting of the slide offset. The OE217-01 model will also display Relative Humidity.
NOTE: The sensor readings are not accurate until the controller
that the sensor is connected to is done calibrating.
The sensor has 4 buttons—
<Down>. You can also access certain functions by touching the area
below the <Display> and <Override> buttons. The sensor has 3 LEDs—one to indicate an Override, one to indicate an Alarm, and one to indicate that a button has been pressed. See Figure 2 for LED and Button Descriptions.
An icon for the current mode of operation will appear in the sensor display. The operation mode icons are a Snowfl ake for Cooling Mode, a Flame for Heating Mode, a Fan in motion for Vent Mode, and a Moon for Unoccupied Mode. When the unit is in Unoccupied Mode, the screen’s background will turn dark. See Figur e 8, page 6 for examples of operation modes.
<Display>, <Override>, <Up>, and
LED Operation
Refer to Figure 2 below for LED locations.
Alarm LED: The Alarm LED will blink when there is an alarm from the Controller.
Sense LED: The Sense LED will blink when the sensor gets a valid touch.
Override LED: The Override LED is inoperable when in Occupied Mode. In Unoccupied Mode, if you touch the Override LED will blink, indicating an override request. The Control­ler will respond by sending the unit into override. The Override LED will then stay on for the duration of the Override. Any time the Unit is in Override, you can request to cancel the override by touching the
<Override> button, and the Override LED will blink. The Unit will
then cancel the override. The Override LED will then turn off.
<Override> button, the
Figure 2: Digital Room Sensor Components
4
Operator Interface
DIGITAL ROOM SENSOR
Mounting and Wiring
Environmental Requirements
The Digital Room Sensor needs to be installed in an environment that does not exceed a temperature greater than 150°F or less than -30°F and does not exceed 90% relative humidity levels (non-condensing).
Indoor Reading Range
The Digital Room Sensor’s Indoor Reading Range is 40°F to 120°F and 0-100% RH (RH is available on the OE217-01 Model). Its temperature reading accuracy is +/- .5°F, and its RH reading accuracy is +/-2%. Its sensor element is the integral communicating digital sensing device or external Type III Thermistor 10K Ohm @ 77°F.
Outdoor Reading Range
If your Digital Room Sensor is set up to read an Outdoor Air T emperature Sensor, any outdoor air temperature below -40°F will not appear on the Digital Room Sensor’s display.
Important Wiring Considerations
The OE217-00 and OE217-01 Space Sensors connect to the VCM-X Controller, RNE, SA-E-BUS, or VA V/Zone Controller (OE217-00 only) using various lengths of TSDRSC modular cables connected between the controller and the sensor. The TSDRSC modular cables should not run in conduit with other AC line voltage wiring or with any conductors carrying highly inductive loads. See Figures 17 & 18, page 10 for wiring.
Mounting
CAUTION: Do not touch the front face of the sensor while you
are plugging in the modular sensor cable. Touching the front face of the sensor while plugging in the cable may prevent proper initial­ization and keep the buttons on the sensor from working properly.
The Digital Room Sensor is designed to be mounted to a vertical 2” x 4” electrical box recessed in the wall. If the wall cannot be penetrated, a plastic surface mount box such as those made by Wiremold used to mount the sensor to the wall surface.
The Sensor is mounted by removing the front cover and fastening the housing base to the electrical box using the supplied (2) 6/32” x 1” machine screws. The modular cable is then plugged into the phone jack located on the circuit board that is mounted on the cover. The cover is then placed onto the housing base, and the Allen Screw on the bottom of the base is adjusted to hold the cover in place. A locking screw secures the sensor to the wall. See Figure 3 for Digital Room Sensor dimensions.
Optional Mounting Plate
Included with the Digital Room Sensor is a mounting plate that can be used, if necessary, to cover the sensor sheet rock opening. This mounting plate screws onto the back of the housing base. The mounting plate is then mounted and covers the recessed space in the wall. A locking screw secures the sensor to the wall. See Figure 20, page 12 for dimensions.
TM
may be
Figure 3: Digital Room Sensor Dimensions
Operator Interface
5
DIGITAL ROOM SENSOR
Sensor Operation
Main Sensor Display Screens
There are 3 Main Sensor Display Screens. The fi rst screen displays the Current Room Temperature or Cooling/Heating Setpoint, Opera­tion Mode, Slide Offset, and RH (RH is available on the OE217-01 Model). The second screen displays the Outside Air Temperature and/ or Humidity if Outdoor Air Temperature and/or Outdoor Air Humidity is being monitored. The third screen displays the unit information for the controller that the Digital Room Sensor is connected to.
Temperature and Humidity Status Screen
The Main Display Screen dis- plays the current room tem­perature or Cooling/Heating Setpoint, the humidity in the room (RH is available on the OE217-01 Model), the current setting of the slide offset, and an icon for the current mode of
Figure 4: Main Display Screen
The different icons shown are a Snowfl ake for cooling mode, a Flame for heating mode, a Fan in motion for vent mode, and a Moon for unoccupied mode. When the unit is in unoccupied mode, the screen’s background will turn dark. Refer to Figure 8 for operation mode screen examples.
operation once the controller it is connected to is done calibrating.
Setpoint Adjust Screen
Touching <> or <> will dis- play the Setpoint Adjust Screen. You can adjust the cooling and heating setpoints from this screen based on the VCM-X controller or VAV/Zone controller slide off­set setpoint. For example, if the connected controller’s Max Slide
Figure 7: Setpoint Adjust Screen
NOTE: If the VCM-X Controller or VAV/Zone Controller’s slide
offset setpoint is set to Zero, this screen will not appear when you touch <> or <>.
Offset Setpoint is set for fi ve, you can adjust the setpoint up fi ve degrees and down fi ve degrees.
Cooling Mode with Snowfl ake Icon
Outside Air Temperature Humidity Status Screen
If the connected controller is receiving an outdoor air tempera­ture and/or humidity broadcast, touching <Display> will fi rst bring up the Outdoor Status Screen.
Figure 5: Outdoor Status Screen
Unit Information Screen
Touching <Display> again will bring up the Unit Information Screen which contains the con­troller’s address or ID number, screen ID, and software version of the controller connected to the sensor.
Figure 6: Unit Information Screen
Heating Mode with Flame Icon
Vent Mode with Fan in Motion Icon
Unoccupied Mode with Moon Icon
Figure 8: Operation Mode Screens
6
Operator Interface
DIGITAL ROOM SENSOR
Troubleshooting
Temperature – Resistance – Voltage for
Type III 10K Ohm Thermistor Sensors
Temp
(ºF)
-10 93333
-5 80531 0 69822 5 60552
10 52500 15 45902 20 40147 25 35165 30 30805 35 27140 40 23874 45 21094 50 18655 52 17799 54 16956 56 16164 58 15385 60 14681 62 14014 64 13382 66 12758 68 12191 69 11906 70 11652
Resistance
(Ohms)
Temperature – Resistance – Voltage for
Type III 10K Ohm Thermistor Sensors
Temp
(ºF)
71 11379 72 11136 73 10878 74 10625 75 10398 76 10158 78 9711 80 9302 82 8893 84 8514 86 8153 88 7805 90 7472
95 6716 100 6047 105 5453 110 4923 115 4449 120 4030 125 3656 130 3317 135 3015 140 2743 145 2502 150 2288
Table 1: Temperature/Resistance for Type III 10K Ohm Thermistor Sensors
Resistance
(Ohms)
T
9302
+
-
TSDRSC Cable
Disconnected
Sensor To The VAV/Zone or VCM-X Controller Modular Sensor Port
Figure 9: Temperature/Resistance Testing
Operator Interface
-
From
+
Digital Room Sensor
Back View
NOTE: ,
For This Test The Sensor Must Be Disconnected From Its TSDRSC Cable As Shown. The Meter Must Be Set To Measure Resistance in Ohms. Use To Determine If The Sensor Is Reading The Correct Resistance Value For The Ambient Temperature. This Resistance Value Should Match The Temperature Value Listed Next To The Resistance Value In The Table. The Temperature Should Be Measured With A Separate Accurate Temperature Measuring Device Located In The Area Where The Sensor Is Currently Located.
Test Points Labeled “Extern Therm” On Sensor Circuit Board
256GP206 PIC24HJ
MICROCHIP
Table 1
7
DIGITAL ROOM SENSOR
Appendix
Sensor Confi guration and Test Screens
To access the Sensor Con guration & Test Screens, you fi rst need to access the Unit Information Screen by touching <Display> while at the Main Display Screen.
NOTE: While in the Sensor Con guration & Test Screens, the
<Display> button functions as an exit key to return to the
previous screen or menu. After a few seconds, however , the sensor will automatically revert to the Main Display Screen. Refer to Figure 10 when reading the instructions that follow.
Figure 10: Digital Room Sensor Buttons
Pixel Test Screen
To select the first option— Pixelstouch <> while at the Sensor Configuration &
Test Screen (Figure 11). The Pixel T est Screen tests the pixels
of the LCD display, allowing you to make the screen white with black characters, black
Figure 12: Sensor Info & LED Test Screen
with white characters, or a black or white screen. To exit this screen, touch
Sensor Info & LED Test Screen
To select the second option—
Info & LEDS—touch <>
while at the Sensor Confi gura- tion & Test Screen (Figure 11). The Sensor Info & LED Test Screen shows the version of
software that the sensor is run-
Figure 13: Sensor Info & LED Test Screen
ning and allows you to test the
LEDs that are used on the con­troller. Touching <> will turn the LEDs on and touching <> will turn the LEDs off. To exit this screen, touch <Display>.
<Display>.
Sensor Confi guration & Test Screen
While the Unit Information Screen is being displayed, you can enter the Sensor Confi gura- tion & Test Screen options by touching simultaneously below
the <Display> and <Over-
ride> buttons. (See Figure 10
Figure 11: Sensor
which shows where to touch to
access this option.)
Confi guration & Test Screen
8
Operator Interface
DIGITAL ROOM SENSOR
Appendix
LCD Backlight Test Screens
Figure 14: Backlight Test & Confi guration Screen
Thermistor Averaging Screen
Figure 15: Temperature Averaging Screen
To select the third option— BACKLTtouch <Override> while at the Sensor Con guration & Test Screen (Figure 11). This option allows you to control when the LCD backlight turns on and off. You can confi gure the backlight to stay on at all times,
remain off at all times, or to come on when any button is touched on the sensor.
To exit this screen, touch
play>
.
To select the fourth and fi nal op- tion—THRM AVG—, while at the Sensor Con guration & Test Screen (Figure 1 1), touch simul- taneously below the and <Override> buttons. (See Figure 10 which shows where to touch to access this option.)
This option allows you to set the rate—from 1-15 seconds—at which the sensor takes a new temperature reading. Touch <> to increase the number of seconds and touch <> to decrease the number of seconds.
<Dis-
<Display>
Display Options - Temperature/Setpoint
To access the Display Options
DSPLY OPTIONS
UP = SETPOINT
DOWN = TEMP
TEMPERATURE
Figure 16: Address Screen
Screen, while at the Thermistor Averaging Screen, (Figure 15), touch the <Override> button.
This option allows you to set the main screen display. Touch <> to display the Cooling/Heating
Setpoint on the Main Display Screen. Touch <> to display the current room temperature on the Main Display Screen. The default is temperature.
If the Setpoint option is chosen, when the unit is in the Cooling Mode, the Cooling Setpoint will appear on the Main Display Screen. When the unit is in the Heating Mode, the Heating Set­point will appear on the Main Display Screen. When the unit is in Unoccupied Mode or Vent Mode, the setpoint that appears on the Main Display Screen will be half way between the Cooling and Heating Setpoint.
To exit this screen, touch
<Display>.
To exit this screen, touch <Dis-
.
play>
NOTE: The sensor takes the average of the last 10 readings based
on the number that is entered in this screen. For example, if you want a 3-second sample, the sensor will take the average of the last 10 readings every 3 seconds over a 30-second span. Therefore, if you have your sensor next to an outside doorway, you would want to enter a higher number for your sample to give a more accurate read­ing for the room temperature in case the outside door is opened often.
Operator Interface
9
DIGITAL ROOM SENSOR
Appendix
OE742/OE744 VAV/Zone Controller Actuator Package
NOTE: If Also Using An OE256-01
Or OE256-02 C Sensor,T Sensor Controller First Using A TSDRSC Cable Of The Length. The Digital Room Sensor Then Connects To The CO Sensor With Another TSDRSC Cable. Cable For Either One Or Both Cables Combined Cannot Exceed 160 Feet. See The
O
2
Connects To The VAV/Zone
Required
2
The Total Length Of
CO2Sensor Technical Guide
he CO
2
For Further Wiring Details.
OVERRIDE ALARM
Display
Override
OE217-00
Digital Room Sensor
Figure 17: Digital Room Sensor to VAV/Zone Controller Wiring
OE332-23E-VCMX
VCM-X E-BUS Controller
93C66
ACTUATOR
EEPROM
(-)LO
PAL
EPROM
EXPANSION D'STAT SPACE SENSOR
TSDRSC Cable
ADDRESS
OFF ON
AIR FLOW
SENSOR
485
VELOCITY
HI(VAV)
LOW(VVT)
WDOG
AIRFLOW
IN GND
MADEINUSA
OUT
WATTMASTERCONTROLSINC
DRV
STAT
POWER / COMM
REC
NOTE: If Also Using An OE256-01 Or OE256-02 CO Sensor, The CO Sensor Always Connects To The VCM-X Controller First Using A TSDRSC Cable Of The Required Length. The Digital Room Sensor Then Connects To The CO Sensor With Another TSDRSC Cable. The Total Length Of Cable For Either One Or Both Cables Combined Cannot Exceed 160 Feet. See The
CO2Sensor Technical Guide
Further Wiring Details.
22
2
For
OVERRIDE ALARM
Display
Override
OE217-00 Or OE217-01
Digital Room Sensor
RS-485 COMMUNICATION LOOP. WIRE “R”TO “R”, “T” TO “T” “SHLD” TO “SHLD”
RS-485 COMMUNICATION LOOP. WIRE “R”TO R”, T” TO “T” SHLD” TO SHLD”
www.aaon.com
www.orioncontrols.com
www.orioncontrols.com
VCM-X MODULAR E-BUS CONTROLLER
Orion No.:OE332-23E-VCMX-MOD-A
OE332-23-VCMX-AVCM-X CONTROLLER
AI1= SPC (SPACE TEMPERATURE SENSOR)
AI1= SPC (SPACE TEMPERATURE SENSOR)
= SAT(SUPPLY AIRTEMPERATURE SENSOR)
AI2
AI2
= SAT(SUPPLY AIRTEMPERATURE SENSOR)
= RAT(RETURN AIR TEMPERATURE SENSOR)
AI3
AI3
= RAT(RETURN AIR TEMPERATURE SENSOR)
= OAT(OUTDOOR AIR TEMPERATURE SENSOR)
AI4
= OAT(OUTDOOR AIR TEMPERATURE SENSOR)
AI4
= SUCTION PRESSURE SENSOR (FROM EXP. MODULE)
AI5
= SUCTION PRESSURE SENSOR
AI5
= SPACETEMPERATURE SENSOR SLIDE ADJUST
AI7
= SPACETEMPERATURE SENSOR SLIDE ADJUST
AI7
OR VOLTAGE RESETSOURCE
OR VOLTAGE RESETSOURCE
= ECONOMIZER (2-10 VDC OUTPUT)
A01
= ECONOMIZER (2-10 VDC OUTPUT)
A01
= SUPPLYFAN VFD (0-10 VDC OUTPUT)
A02
= SUPPLYFAN VFD (0-10 VDC OUTPUT)
A02
E-BUS
CONNECTOR
ANALOG INPUT
ANALOG INPUT
JUMPER
JUMPER
SETTINGS
SETTINGS
THERM
LEDNAME STATUS1 STATUS2
THERM
4-20mA
4-20mA
AI1
AI1
0-10V
NORMALOPERATION 0 1
0-10V
0-5V
0-5V
SATFAIL 1 2
THERM
THERM
OATFAIL 2 2
4-20mA
4-20mA
AI2
AI2
SPCFAIL 3 2
0-10V
0-10V
0-5V
0-5V
MODULEALARM 4 2
THERM
THERM
MECHCOOL FAIL 1 3
4-20mA
4-20mA
AI3
AI3
MECHHEAT FAIL 2 3
0-10V
0-10V
0-5V
0-5V
FANPROOF FAIL 3 3
THERM
THERM
DIRTYFILTER 4 3
4-20mA
4-20mA
AI4
EMERGENCYSHUTDOWN 5 3
AI4
0-10V
0-10V
0-5V
0-5V
LOWSAT 1 4
THERM
THERM
HIGHSAT 2 4
4-20mA
4-20mA
AI5
AI5
CONT.TEMP COOL FAIL 3 4
0-10V
0-10V
0-5V
CONT.TEMP HEAT FAIL 4 4
0-5V
THERM
PUSHBUTTON OVR 1 5
THERM
4-20mA
4-20mA
AI7
ZONEOVR 2 5
AI7
0-10V
0-10V
OUTPUTFORCE ACTIVE 0 6
0-5V
0-5V
ANALOG INPUTJUMPER SETTINGS
ANALOG INPUTJUMPER SETTINGS
MUSTBE SET AS SHOWN FOR
MUSTBE SET AS SHOWN FOR
PROPER OPERATION
PROPER OPERATION
STATIC
WattMaster Label
WattMaster Label
STATIC
#LB102073-01-A
PRESSURE
#LB102033-01
PRESSURE
Rev.: 1A
RELAYCONTACT RATING IS 1AMP MAX @ 24 VAC
LEDBL INKCODES
24 VAC POWER ONLY
WARNING!POLARITY MUST BE OBSERVED
WARNING!POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILLBE DAMAGED
OR THE CONTROLLER WILLBE DAMAGED
2
2
IC
IC
EXPANSION
EXPANSION
RELAYCONTACT RATING IS 1AMP MAX @ 24 VAC
RELAY COMMON
RELAY COMMON
RELAY2
RELAY2
RELAY3
RELAY3
RELAY4
RELAY4
RELAY5
RELAY5
AAON No.:
24 VAC POWER ONLY
TSDRSC Cable
FAN
FAN
V07150
2
2
IC DIGITAL
IC DIGITAL
SENSOR
SENSOR
POLARITY
OBSERVE
WARNING
Figure 18: Digital Room Sensor to VCM-X E-BUS Controller Wiring
10
Operator Interface
DIGITAL ROOM SENSOR
Appendix
Connecting a Remote Sensor
NOTE: The following directions are for the OE217-00 Space
Temperature Only E-BUS Digital Room Sensor. If you are using an OE217-01 Space T emperature and Humidity Model, please contact WattMaster T echnical Support for instructions.
Sometimes due to the requirements of a job, the sensor must be located outside the conditioned space due to special requirements such as hospital surgical room codes, security, or tampering considerations. In these cases, the Digital Room Sensor can be mounted in a different room and have a remote sensor connected to it. T ypically , this would be
a Return Air Duct Temperature Sensor. Usually, you will be using the OE231 Return Air Temperature Sensor , but you can also use any T ype III 10K Ohm Thermistor Sensor.
To connect a remote sensor to the Digital Room Sensor, you must fi rst remove the Digital Sensor’s back cover. Y ou will see a loop of wire hang­ing off of the sensor circuit board. See Figure 19. This is the external thermistor loop wire. Clip the external thermistor loop wire so that the sensor will read the remote temperature input. Be sure to cut the ends of the wire close to the circuit board so that the sensor loop wire ends won’t short between each other. The remote sensor then wires to the remote sensor terminal block on the back of the Digital Room Sensor. If using the W attMaster OE210 type Space Sensor as the remote sensor , you must clip off the yellow C1 capacitor from the back of the OE210. Be sure to cycle power to begin reading the remote sensor.
MICROCHIP
256GP206
PIC24HJ
Cut Wire Loop As Shown. Make Sure That The Wires Are Cut Close Enough To The Circuit Board So They Can’t Touch Each Other.
OE231 Return Air
Temperature Sensor
Return
Air Duct
OE217-00 Digital Room Sensor Back View
Mount Sensor In Return Air Duct As Shown. Route Wires To Digital Room Sensor Location And Connect To Terminal Block.
OE217-00 Digital Room Sensor Back View
Sensor Shown With
Back Cover Removed
MICROCHIP
256GP206
PIC24HJ
Sensor Shown With
Back Cover Removed
Figure 19: Attaching a Remote Sensor
Operator Interface
11
DIGITAL ROOM SENSOR
1.638
1.810
0.882
1.407
1.842
0.733
2.110
2.920
0.810
R0.220
3.275
0.060
0.160
5.037
3.278
3.766
4.153
Mounting Plate Dimensions
Optional Mounting Plate
Included with the Digital Room Sensor is a mounting plate that can be used, if necessary, to cover the sensor sheet rock opening. This mounting plate screws onto the back of the housing base. The mounting plate is then mounted and covers the recessed space in the wall. A locking screw secures the sensor to the wall. See Figure 20, below for dimensions.
Figure 20: BK000081 Mounting Plate Dimensions
12
Operator Interface
DIGITAL ROOM SENSOR
Notes
Operator Interface
13
DIGITAL ROOM SENSOR
Notes
14
Operator Interface
DIGITAL ROOM SENSOR
Notes
Operator Interface
15
Form: OR-DRS-TGD-01K Printed in the USA May 2015 All rights reserved. Copyright 2015 WattMaster Controls Inc. 8500 NW River Park Drive Parkville, MO  64152 Phone: 866-918-1100 www.orioncontrols.com Fax (816) 505-1101
Loading...