Orion Digital Room User Manual

www.orioncontrols.com
Digital Room Sensor
Technical Guide
TABLE OF CONTENTS
OVERVIEW ....................................................................................................................................... 3
BASIC OPERATION .......................................................................................................................... 4
Sensor Operation .....................................................................................................................................................4
LED Operation .........................................................................................................................................................4
MOUNTING AND WIRING ................................................................................................................ 5
Indoor Reading Range ........................................................................................................................................5
Outdoor Reading Range .....................................................................................................................................5
Mounting ..................................................................................................................................................................5
SENSOR OPERATION ...................................................................................................................... 6
Main Sensor Display Screens....................................................................................................6
Temperature and Humidity Status Screen ..........................................................................................................6
Outside Air Temperature Humidity Status Screen...............................................................................................6
Unit Information Screen ......................................................................................................................................6
Setpoint Adjust Screen ........................................................................................................ ...............................6
TROUBLESHOOTING ....................................................................................................................... 7
Temperature Sensor Testing for OE217-00 .............................................................................................................7
APPENDIX ....................................................................................................................................... 8
Sensor Confi guration and Test Screens ..................................................................................................................8
Sensor Confi guration & Test Screen ...................................................................................................................8
Pixel Test Screen ................................................................................................................................................8
Sensor Info & LED Test Screen ..........................................................................................................................8
LCD Backlight Test Screens ...............................................................................................................................9
Thermistor Averaging Screen .............................................................................................................................9
Display Options - Temperature/Setpoint .............................................................................................................9
Connecting to VAV/Zone Controller & HVAC Unit Controller .................................................................................10
Connecting a Remote Sensor ................................................................................................................................ 11
Mounting Plate Dimensions ...................................................................................................................................12
PART NUMBER CROSS REFERENCE TABLE
PART DESCRIPTION ORION
Digital Room Sensor Temp Only OE217-00 Digital Room Sensor Temp & Humidity OE217-01 Mounting Plate BK000081 Space CO Duct Mounted CO Return Air Temperature Sensor OE231 VCM-X E-BUS Controller OE332-23E-VCMX
Sensor OE256-01
2
Sensor OE256-02
2
www.orioncontrols.com
WattMaster Controls Inc. 8500 NW River Park Drive · Parkville, MO 64152 Toll Free Phone: 866-918-1100 PH: (816) 505-1100 · FAX: (816) 505-1101 · E-mail: mail@wattmaster.com Visit our web site at www.orioncontrols.com
®
is a registered trademark of AAON, Inc., Tulsa, OK.
AAON WattMaster Controls, Inc. assumes no responsibility for errors or omissions. This document is subject to change without notice. Form: OR-DRS-TGD-01K Copyright May 2015 WattMaster Controls, Inc.
DIGITAL ROOM SENSOR
Overview
Overview
The OE217 series of Digital Room Sensors are used to sense Space T em­perature only or Space Temperature & Space Humidity. See Figure 1. The OE217-00 model is the Space T emperature Sensor only model and can be used with the VCM-X E-BUS Controller (OE332-23E-VCMX), RNE Controller (OE332-23E-RNE), SA E-BUS Controller (OE332-23E­VCMX-SA), and VAV/Zone Controller (OE324-02). The OE217-01 is a combination Space Temperature & Space Humidity Sensor model and can only be used with the VCM-X E-BUS, RNE, and SA-EBUS Controllers.
The sensor provides the following useful functions:
• Provides 112 x 64 monochrome Graphical LCD display with LED backlight
• Displays the Current Space Temperature or Cooling/Heating Setpoint on the Main Display Screen
• Displays Outdoor Air Temperature (if controller is confi gured with OA Temperature Sensor)
• Displays the Current Space Humidity (OE217-01 Model Only)
• Displays Outdoor Air Relative Humidity (OE217-01 Model if controller is confi gured with OA Humidity Sensor)
• Displays the Current Zone Setpoint Temperature
• Equipped with Push Buttons for changing the Zone Setpoint Temperature
• Equipped with an Override Button for forcing the VAV/Zone Controller or VCM-X / RNE / SA Controller into Occupied Operation from Unoccupied Operation
• Provides graphics to indicate the Mode of Operation
• Provides LEDs to indicate Schedule Override, Button Push, and Alarms
• Can display Temperature reading from a Remote Sensor (see Figure 19, page 11 for instructions)
• Can be used with the OE256-01 or OE256-02 CO2 Sensor (see notes in Figures 17 & 18, page 10 for instructions)
Both sensors connect to the controllers using various lengths of TSDRSC modular cables connected between the controller and the sensor. The TSDRSC modular cables should not run in conduit with other AC line voltage wiring or with any conductors carrying highly inductive loads.
Figure 1: Digital Room Sensor
Operator Interface 3
DIGITAL ROOM SENSOR
Basic Operation
Sensor Operation
When power is fi rst applied to the OE217-00 Digital Room Sensor, the sensor will display the Current Room T emperature or the Cooling/Heat­ing Setpoint and the current setting of the slide offset. The OE217-01 model will also display Relative Humidity.
NOTE: The sensor readings are not accurate until the controller
that the sensor is connected to is done calibrating.
The sensor has 4 buttons—
<Down>. You can also access certain functions by touching the area
below the <Display> and <Override> buttons. The sensor has 3 LEDs—one to indicate an Override, one to indicate an Alarm, and one to indicate that a button has been pressed. See Figure 2 for LED and Button Descriptions.
An icon for the current mode of operation will appear in the sensor display. The operation mode icons are a Snowfl ake for Cooling Mode, a Flame for Heating Mode, a Fan in motion for Vent Mode, and a Moon for Unoccupied Mode. When the unit is in Unoccupied Mode, the screen’s background will turn dark. See Figur e 8, page 6 for examples of operation modes.
<Display>, <Override>, <Up>, and
LED Operation
Refer to Figure 2 below for LED locations.
Alarm LED: The Alarm LED will blink when there is an alarm from the Controller.
Sense LED: The Sense LED will blink when the sensor gets a valid touch.
Override LED: The Override LED is inoperable when in Occupied Mode. In Unoccupied Mode, if you touch the Override LED will blink, indicating an override request. The Control­ler will respond by sending the unit into override. The Override LED will then stay on for the duration of the Override. Any time the Unit is in Override, you can request to cancel the override by touching the
<Override> button, and the Override LED will blink. The Unit will
then cancel the override. The Override LED will then turn off.
<Override> button, the
Figure 2: Digital Room Sensor Components
4
Operator Interface
DIGITAL ROOM SENSOR
Mounting and Wiring
Environmental Requirements
The Digital Room Sensor needs to be installed in an environment that does not exceed a temperature greater than 150°F or less than -30°F and does not exceed 90% relative humidity levels (non-condensing).
Indoor Reading Range
The Digital Room Sensor’s Indoor Reading Range is 40°F to 120°F and 0-100% RH (RH is available on the OE217-01 Model). Its temperature reading accuracy is +/- .5°F, and its RH reading accuracy is +/-2%. Its sensor element is the integral communicating digital sensing device or external Type III Thermistor 10K Ohm @ 77°F.
Outdoor Reading Range
If your Digital Room Sensor is set up to read an Outdoor Air T emperature Sensor, any outdoor air temperature below -40°F will not appear on the Digital Room Sensor’s display.
Important Wiring Considerations
The OE217-00 and OE217-01 Space Sensors connect to the VCM-X Controller, RNE, SA-E-BUS, or VA V/Zone Controller (OE217-00 only) using various lengths of TSDRSC modular cables connected between the controller and the sensor. The TSDRSC modular cables should not run in conduit with other AC line voltage wiring or with any conductors carrying highly inductive loads. See Figures 17 & 18, page 10 for wiring.
Mounting
CAUTION: Do not touch the front face of the sensor while you
are plugging in the modular sensor cable. Touching the front face of the sensor while plugging in the cable may prevent proper initial­ization and keep the buttons on the sensor from working properly.
The Digital Room Sensor is designed to be mounted to a vertical 2” x 4” electrical box recessed in the wall. If the wall cannot be penetrated, a plastic surface mount box such as those made by Wiremold used to mount the sensor to the wall surface.
The Sensor is mounted by removing the front cover and fastening the housing base to the electrical box using the supplied (2) 6/32” x 1” machine screws. The modular cable is then plugged into the phone jack located on the circuit board that is mounted on the cover. The cover is then placed onto the housing base, and the Allen Screw on the bottom of the base is adjusted to hold the cover in place. A locking screw secures the sensor to the wall. See Figure 3 for Digital Room Sensor dimensions.
Optional Mounting Plate
Included with the Digital Room Sensor is a mounting plate that can be used, if necessary, to cover the sensor sheet rock opening. This mounting plate screws onto the back of the housing base. The mounting plate is then mounted and covers the recessed space in the wall. A locking screw secures the sensor to the wall. See Figure 20, page 12 for dimensions.
TM
may be
Figure 3: Digital Room Sensor Dimensions
Operator Interface
5
Loading...
+ 11 hidden pages