Optex SL-200QDP User Manual

-1-
INSTALLATION INSTRUCTIONS
No.59-1881-3 131115UL
No.59-1881-3
PHOTOELECTRIC DETECTOR
• Quad high power beams
• Double modulated beam
- Slim body design
- Easy-to-see vivid interior color for optical alignment
- IP65*1 waterproof structure
• 4 channel beam frequency selector
• Alignment level indicator
• Viewfinder with 2X magnification
• Various options (refer to page 20)
( HU-3*1, ABC-4*1, BC-4*1, CBR-4, PSC-4*1, BAU-4*1 )
• UL/c-UL Listed
• Beam interruption adjustment function
• D.Q. circuit (environmental disqualification)
• Tamper function
• Beam power control selector
• Alarm memory
• Sound assist function
-
Optical alignment
- Beam reception status
- Walk test
[ SL-QDM only ]
• Auto Transmit Power Control (A.T.P.C*2) to optimize the beam power
• Integrated Alignment Status Communication (I.A.S.C*2) to communicate the transmitter and receiver
• Re-transmitting circuit function
• Solar Battery Unit SBU-4*1 (option)
PHOTOELECTRIC DETECTOR
A photoelectric detector consists of an infrared light source that generates IR(Infrared) beams, and an IR receiver that detects the IR beams. The transmitter and receiver are installed on opposite sides of the area to be monitored. The receiver detects when the IR beams are physically interrupted by an intruder, and sends an alarm signal to be a control panel.
FEATURES
INTRODUCTION
1-1 BEFORE YOUR OPERATION .......................2
1-2 PRECAUTIONS
.......................................................
2
1-3 PARTS IDENTIFICATION
.....................................
3 INSTALLATION
2-1 SEPARATING................................................. 4
2-2 WIRING.......................................................... 4
2-3 TERMINAL .....................................................5
2-4 WIRING DIAGRAM ........................................ 5
2-5 WIRING DISTANCE BETWEEN POWER
SUPPLY AND DETECTOR ............................ 6
2-6 WALL MOUNTING.........................................6
2-7 POLE MOUNTING ......................................... 8
2-8 MOUNTING IN THE BEAM TOWER..............9
2-9
INSTALLATION EXAMPLE AT PARTICULAR CASE
... 9 FUNCTION SETTING
3-1 DIP SWITCH ................................................. 10
3-2 BEAM POWER CONTROL SELECTOR....... 10
1
2
3
4
6
7
8
9
CONTENTS
3-3 FUNCTION.................................................... 11
OPTICAL ALIGNMENT 4-1 OPTICAL ALIGNMENT FOR UPPER AND
LOWER BEAM.............................................. 15
4-2 OPERATION CHECK.................................... 17
TROUBLESHOOTING
5-1 TROUBLESHOOTING .................................. 17
OPTIONAL SETTING
6-1 HEATER UNIT HU-3 (OPTION) .................... 18
6-2 SOLAR BATTERY UNIT SBU-4 (OPTION)... 18 DIMENSIONS
7-1 DIMENSIONS ............................................... 19
SPECIFICATIONS
8-1 SPECIFICATIONS......................................... 19
OPTIONS
9-1 OPTIONS ...................................................... 20
Detection range
SL-200QDM
SL-350QDM
SL-650QDM
SL-200QDP
SL-350QDP
SL-650QDP
Advanced Standard
5
Transmitter
Receiver
Smart Line series
Smart Line series
60m/200ft.
100m/350ft.
200m/650ft.
*1 not evaluated by UL *2 not require any additional tool
-2-
1-2
PRECAUTIONS
This symbol indicates prohibition.
This symbol indicates recommendation.
Receiver
Transmitter (different model)
Receiver (different model)
Transmitter
At least 1 m (3.3 ft.)
Warning
Caution
Read this instruction manual carefully prior to installation.
After reading, store this manual carefully in an easily accessible place for reference.
This manual uses the following warning indications for correct use of the product, harm to you or other people and damage to your assets, which
are described below. Be sure to understand the description before reading the rest of this manual.
INTRODUCTION
1
1-1
BEFORE YOUR OPERATION
Failure to follow the instructions provided with this indication and improper handling may cause death or serious injury.
Failure to follow the instructions provided with this indication and improper handling may cause injury and/or property damage.
This symbol indicates prohibition. The specific prohibited action is provided in and/or around the figure.
This symbol requires an action or gives an instruction.
Do not install the unit on an unstable surface.
Do not install the pole in a location where sufficient stability can not be ensured.
Do not install the unit in a location where trees, leaves, or other objects that may swing in the wind and block the beam.
Do not install the receiver in a location where it is exposed to direct sunlight.
Install the unit at a height where an object can be detected without fail.
Do not allow the infrared beam from a different model to reach the receiver.
Install the unit at least 1 m (3.3 ft.) away from the wall or fence that may be running parallel to the beam.
The pole size should be 34 - 48 mm ( 1.34 - 1.89 inch).
Warning
Caution
Do not use the product for purposes other than the detection of moving objects such as people and vehicles. Do not use the product to activate a shutter, etc., which may cause an accident.
Do not touch the unit base or power terminals of the product with a wet hand (do not touch when the product is wet with rain, etc.). It may cause electric shock.
Never attempt to disassemble or repair the product. It may cause fire or damage to the devices.
Do not exceed the voltage or current rating specified for any of the terminals during installation, doing so may cause fire or damage to the devices.
Do not pour water over the product with a bucket, hose, etc. The water may enter, which may cause damage to the devices.
Clean and check the product periodically for safe use. If any problem is found, do not attempt to use the product as it is and have the product repaired by a professional engineer or electrician.
[Receiver]
Transmitter
Receiver
For UL/c-UL installations ;
Reference to UL681, Standard for Installation and Classification of Burglar and Holdup Alarm System.
Reference to CAN/ULC-S302, ULC Standard for Installation and Classification of Burglar Alarm Systems for Financial and Commercial Premises.
Safes and Vaults, & CAN/ULC-S310, ULC Standards for Installation and Classification of Residential Burglar Alarm.
Conduit is required for all Outdoor Use Application with Conduit Bracket Kit, Model CBR-4, employing appropriate wiring methods.
Products to be installed within the protected premises.
-3-
<Transmitter>
U-brackets: 4
Pole brackets: 4
4×20 self tapping for wall mounting: 4
M4×30 screws for pole mounting (with rubber washer): 8
Beam blocking plate: 2
(attached on the back of the cover)
3×6 self tapping for pole bracket: 4
FUNCTION SETTING SECTION >>
ACCESSORIES >>
SL-QDM
SL-QDP
<Receiver>
<Transmitter> <Receiver>
Banding bands: 4
1-3
PARTS IDENTIFICATION
Cover
Main unit
Chassis
Cover lock screw
View finder
Terminals
Cut bush for wiring
Main unit base Mounting screw holes
Pole mounting screw holes
Pole mounting screw holes
Wall mounting screw holes
Vertical alignment dial
Vertical alignment dial
Horizontal alignment dial
Optical lens
I.A.S.C lens
[QDM only]
Horizontal alignment dial
Viewfinder
Beam blocking plate
T R
T
R
Upper/Lower beam selection button
Upper/Lower beam selection button
Upper/Lower beam selection button
Monitor jack (+)
Monitor jack (-)
Power indicator LED
Upper beam indicator LED
Lower beam indicator LED
Power indicator LED
Upper beam indicator LED Lower beam
indicator LED
Power supply selector
Sound assist switch Beam power control selector
Dip switch
Alignment level indicator LED
Upper/Lower beam selection button
Power supply selector
Sound assist switch
Dip switch
Alignment level indicator LED
Beam power control selector
Dip switch
Sound assist switch
Dip switch
Alignment level indicator LED
Optical lens
Tamper lock plate
Tamper button
Power indicator LED
Alarm memory indicator LED
Alarm indicator LED
Upper beam indicator LED Lower beam indicator LED
Power indicator LED
Alarm memory indicator LED
Alarm indicator LED
Upper beam indicator LED Lower beam indicator LED
Monitor jack (+)
Monitor jack (-)
Monitor jack (+)
Monitor jack (-)
Beam power control selector
-4-
2-1
SEPARATING
INSTALLATION
2
1
Remove the cover.
2
1
2
Remove the main unit from the chassis.
Pull the upper part of main unit, and raise it to remove.
Turn the optical unit 90 degrees and loosen the screws (both sides).
Do not place the main unit where it allows to incident direct sunlight to its optical lens during installation. Doing so may cause damage to the product.
Caution
3
4
1
2
5
6
2-2
WIRING
1
Cut off the cut bush according to the cable size.
2
5
3
4
1
Preparing the cut bush
Cut the wiring grommet required according to the wire diameter. Use the lidded grommet for the wiring hole not to be used. (I.D. : Internal diameter)
Refer to "TERMINAL" on Page 5 to make connections to the
terminals and refer to “OPTI­CAL ALIGNMENT” on Page 15 to make alignment for the maximum level of light reception.
Pass the cable through the cut bush.
Connect to the terminalsCut the excess portion of the banding band.Tighten the cable with the banding band.
2
Threading the wire
Do not exceed the voltage or current rating specified for any of the terminals during installation, doing so may cause fire or damage to the product.
Caution
Pull
Loosen the cover lock screw.
2
Twist it lightly.
1
3
A coin (Not included)
I.D. 10mm (0.39 inch) I.D. 8mm (0.31 inch) I.D.
6mm (0.24 inch)
I.D. 4mm (0.16 inch)
I.D. 7mm (0.28 inch) I.D. 6mm (0.24 inch) I.D. 4mm (0.16 inch)
-5-
2-4
WIRING DIAGRAM
<Receiver>
<Transmitter>
(1) + (2)
­(3) (4) (5) (6) (7)
(8) (9)
<Receiver>
<Transmitter>
SL-QDM SL-QDP
1
1 Set
POWER
CONTROL PANEL
ALARM
N.C.
(1)
(1)(2) (1)(2) (8)(9)
(1) (2)(1) (2) (8)(9)
(1)(2) (2) (8) (9)
(1) (1)(2) (2) (1) (2)(8) (9) (1) (2) (8) (9)
Transmitter Receiver
3
2 Sets in the line
POWER
TransmitterReceiverTransmitter Receiver
Connect the power supply in parallel. Connect the units serially for a normally closed alarm output and in parallel for a normally open output (the figure below shows an example for a normally closed alarm output).
Connect the power supply in parallel. Connect the units serially for a normally closed alarm output and in parallel for a normally open output (the figure below shows an example for a normally closed alarm output).
Connect the power supplies in parallel.
CONTROL PANEL
2
2 Sets Stacking
POWER
Transmitter Receiver
Ch1 Ch1
Ch3 Ch3
POWER INPUT
10.5-30VDC [ Normal ]
3.6VDC [ SBU-4 ]
*
POWER INPUT
10.5-30VDC [ Normal ]
3.6VDC [ SBU-4 ]
*
SPARE
ALARM INPUT
LOW BATTERY INPUT
(using with SBU-4)
*
TAMPER OUTPUT (N.C.)**
(1) + (2)
­(3) (4) (5) N.O. (6) N.C. (7) COM. (8) COM. (9) N.C. (
10
) N.O.
(
11
)
(
12
)
(
13
)
(
14
)
SPARE
D.Q.
OUTPUT
/ LOW BATTERY OUTPUT* **
ALARM OUTPUT**
TAMPER OUTPUT** (N.C.)
ALARM MEMORY INPUT
LOW BATTERY INPUT
(using with SBU-4)*
(1) + (2)
­(3) (4)
(5) (6)
POWER INPUT
10.5-30VDC
SPARE
(1) + (2)
­(3) (4) (5) N.O. (6) N.C. (7) COM. (8) COM. (9) N.C. (
10
) N.O.
(
11
)
(
12
)
(
13
)
(
14
)
POWER INPUT
10.5-30VDC
SPARE
D.Q.
OUTPUT
ALARM OUTPUT**
TAMPER OUTPUT** (N.C.)
ALARM MEMORY INPUT
SPARE
2-3
TERMINAL
TAMPER OUTPUT (N.C.)**
Note>>
Connect POWER INPUT - terminal(2) when wiring LOW BATTERY INPUT* terminal(7) of the transmitter, ALARM MEMORY INPUT terminal(11) and LOW BATTERY INPUT terminal(12) of the receiver.
*
SBU-4 and its low battery input/output function not evaluated by UL ** All outputs are power-limited.
ALARM
N.C.
ALARM
N.C.
*1 CONTROL PANEL = UL/c-UL listed burglar alarm control panel *2 POWER = power limited output
*2
*2
*1
*2
*1
CONTROL PANEL
*1
-6-
2
Pull the waterproof packing (x2) marked as "" at the
center of the chassis.
3
Mount the chassis to the wall.
4×20 self tapping (with rubber washer)
Side wall
Distance from the side wall: at least 1m
If two detectors are installed, the distance between the upper and lower detector should be at least 20 mm.
4
Put the waterproof packing back in place.
2-6
WALL MOUNTING
- Ensure that the wiring distance from the power supply is within the range shown in the table below.
- When using two or more units on one wire, the maximum length is obtained by dividing the wire length listed below by the number of units used.
2-5
WIRING DISTANCE BETWEEN POWER SUPPLY AND DETECTOR
Note>>
UL/c-UL requires to be connected to a UL/c-UL Listed burglar alarm power limited power supply of providing a nominal input of 12 VDC (10.5 to 30 VDC) 30 mA (SL-200/350/650 QDM) or 22 mA (SL-200/350/650 QDP), and battery standby time of 4 hours.
Wiring method shall be in accordance with the National Electrical Code (ANSI / NFPA 70), Canadian Electrical Code, Part 1 (CSA C22.1) Safety Standard for Electrical Installations, local codes, and the authorities having jurisdiction.
Pitch: 83.5 mm For connection to gang electric box
1
Open the wiring guide on the back of the chassis using pliers as shown.
<After the cutting>
[ Upper ] [ Lower ]
MODEL
WIRE SIZE
12 VDC 24 VDC
2,100 m
(7,000 ft.)
3,300 m
(10,000 ft.)
5,300 m
(17,000 ft.)
8,300 m
(27,000 ft.)
0.33 mm
2
(AWG22)
0.52 mm
2
(AWG20)
0.83 mm
2
(AWG18)
1.31 mm
2
(AWG16)
SL-200QDM / SL-200QDP /
SL-350QDM / SL-350QDP /
SL-650QDM SL-650QDP
600 m
(2,000 ft.)
900 m
(3,000 ft.)
1,500 m
(4,900 ft.)
2,500 m (8,000 ft.)
Note>>
Install the unit vertically at a height where an object can be detected without fail. In case to be stacked, be careful to cover the detection area totally.