Optex SIP-4010, SIP-404, SIP-3020, SIP-3020CAMDN Installation

No. 59-1494-2 0911-01
2
INSTALLATION INSTRUCTIONS
INSTALLATION AND MAINTENANCE NOTES
Synthesized Intelligent PIR
Synthesized Intelligent PIR
REDWALL-V series
REDWALL-V series
FEATURES
* Intelligent PIR Detection System
- Detection of ambient temperature and illuminance for automatic sensitivity management
- Advanced detection algorithm
- Three dual pyro-elements with patented Double Conductive Shielding
* Anti-vandalism functions
- Anti-rotation function with 3-axis accelerometer
- Anti-masking function with photo-beam
- Reinforced polycarbonate housing
- Max. 4 m (13 ft.) installation height
* Independent sensitivity selector for near/far areas * Detection logic selector * Detection range selector * Independent N.C. and N.O. outputs * Adjustable alarm interval time
• SIP-3020CAM DN (EU), SIP-3020CAM DN (US) * High-quality camera image: Day (colour)/Night (B/W) * 480 TV lines * Varifocal lens 3-9 mm * Minimum illumination: Day (colour) 0.5 lx, Night (B/W): 0.03 lx
Warning Caution
Never repair or modify product
Nylon wire loop
When servicing, the sensor can be hooked onto the base using the nylon wire loop.
Caution Verify that the power is off before connecting the wiring.
ENGLISH FRANÇAIS DEUTSCH ITALIANO ESPAÑOL
REDWALL-V REDWATCH-V
: Synthesized Intelligent PIR
SIP-3020
• SIP-4010
• SIP-404
1
PARTS IDENTIFICATION
Base
Fixing screw for the base
Adjustment screws (two facing each other)
Main unit
Angle adjustment guide
: Synthesized Intelligent PIR
with D/N camera
SIP-3020CAM DN (EU)
• SIP-3020CAM DN (US)
Far area mirror
Masking plate for far area
Fixing rubber form
Window
Fixing rubber
form (*1) Masking plate for near area (*1)
Near area mirror
*1: Not used for the SIP-4010 and SIP-404.
SIP-3020CAM DN
Fixing screw for the cover
Cover
2-1
INSTALLATION HINTS
2.3-4.0 m (7.6-13 ft.)
Mount the detector so that the majority of traffi c fl ow is across the detection pattern.
Arrow marking
Fixing screw
Camera unit
- 1 -
3
INSTALLATION AND ANGLE ADJUSTMENT
3-1
Wall Mounting
Attach the paper template (an accessory) onto the wall,
(1)
and drill a 6-mm dia. mounting hole and a cabling hole. Insert the anchor bolt (an accessory) into the board mount hole.
Distance from the ground to the bottom of the template must be between 2.3 m (7.6 ft.) and 4 m (13 ft.).
Using an allen key, remove the main unit from the base.
(2)
4 Pull out.
2 Open.
3-2
Inside View of the Base
Main unit connector
Wall mounting hole
BNC terminal (SIP-3020CAM DN ONLY)
Wall mounting hole
Bushing of wiring hole
Base
Waterproof seal (Do not remove this seal.)
Wiring terminals
Bushing of wiring hole
Open wiring cap
1 Loosen the
xing screw for the base.
(3)
Drill through the bushing of the wiring hole, pass the cable through the hole, and secure the base to the wall.
(4)
Connect the cable to the terminal block (see Step 3-3).
(5)
Mount the main unit onto the base.
1 Insert and
secure here.
Nylon wire loop
3 Unplug
4 Tighten and
3 Close.
2 Connect the
connector.
Cautions>>
When mounting the main unit, take care not to trap the nylon wire loop. Also, take care not to get your fingers caught.
(6)
Check to see that the various settings and operations are correct.
Caution>>
When the red LED flashes after the power turns on, this signifies that the system is warming up. Wait for approximately 60 seconds.
the cable connector.
secure the xing screw for the base.
- 2 -
3-3
WIRING
BNC terminal (SIP-3020CAM DN ONLY)
POWER INPUT
TAMPER OUTPUT *1
ALARM OUTPUT (N.C.)
ALARM OUTPUT (N.O.)
*1: TAMPER terminals to be connected to a 24 hour supervisory loop.
Name Function
Trouble out is used for anti-masking signal. When
TROUBLE
OUTPUT
TAMPER OUTPUT
an object is placed close to the lens surface, for a period of more than 20 seconds (approx.), the IR anti-masking circuit will activate and generate a trouble signal.
It is detected when the cover is opened. It is detected when the main unit is removed from
its base. Anti-Rotation:
Damage sustained by the main unit is detected. When the system power switch is turned on while the cover is closed, the mounting position of the main unit itself will be determined and stored in memory after approximately 10 seconds. Then, if the main unit is impacted in a horizontal or vertical direction and if the position of the main unit has changed, damage sustained by the main unit will be detected. However, if you remove the cover while keeping the system power turned on, and if you close the cover again after correcting the position of the main unit, the new position of the main unit will be stored in memory after approximately 10 seconds.
TROUBLE OUTPUT
SPARE
D
Power wires should not exceed the following lengths.
SIP-3020CAM DN (EU) SIP-3020CAM DN (US)
WIRE SIZE
SIP-3020/SIP-4010/SIP-404
12V DC 14V DC 24V AC 12V DC
2
0.33 mm (AWG22)
0.52 mm (AWG20)
0.83 mm (AWG18)
4
DETECTION AREA SETTING
580
(1900)
2
910
(2990)
2
1450
(4760)
770
(2530)
1210
(3970)
1930
(6330)
1370
(4490)
2160
(7090)
3450
(11320)
You can adjust the detection area by 90 degrees in a horizontal direction and by 10 degrees in a vertical direction. Correct the vertical detection angle according to the mounting height of the sensor unit.
Applicable models
SIP-3020 SIP-4010 SIP-404 SIP-3020CAM DN
100
(330)
160
(520)
250
(820)
SIP-3020CAM
m (ft.)
Adjust the angle of the main unit in a horizontal direction so
(1)
that you can cover the desired detection area.
3 Rotate the main unit.
1 Loosen the xing screw for
the base.
2 Loosen the adjustment screw. 4 Tighten the adjustment screw slightly.
(2)
Adjust the angle of the main unit in a vertical direction so that you can cover the desired detection area.
Align the arrow of the main unit with the “Angle adjustment guide” of the adjustment screw. The main unit is usually adjusted within the width of this guide.
When mounted at a height of
2.3 meters (7.6ft.)
ENGLISH FRANÇAIS DEUTSCH ITALIANO ESPAÑOL
10°
10°
90°
90°
10°
10°
90°
Applicable models
90°
SIP-3020 SIP-4010 SIP-404 SIP-3020CAM DN
Cautions>>
To rotate the main unit counterclockwise, loosen the RHside adjustment screw. To rotate the main unit clockwise, loosen the LH-side adjustment screw. Otherwise, you may find it difficult to tighten or you may find that you cannot tighten the adjustment screw when you are securing the main unit.
When mounted at a height of 4.0 meters (13ft.)
Cautions>>
If the mounting wall is at an angle, the arrow of the main unit may exceed the top or bottom limit of “Angle adjustment guide”. Always check this using the area viewfinder or the walk tester. If the detection area is too high or too low, an object outside the detection area may be detected or incorrect object detection may occur.
(3)
Remove the cover.
Hooks
3 Slide the cover downward
and release the hooks.
1 Loosen two fi xing screws for
the cover and pull out the cover until it stops.
Cover
2 Hold the heads of both cover fi xing screws with your
hands, and pull down and remove the bottom section of the cover from the main unit.
Adjustment screw
To rotate the unit counterclockwise
Cautions>>
The cover is linked to the main unit by nylon wire loop so that the cover does not fall. Do not pull the cover using excessive force.
To rotate the unit clockwise
- 3 -
Mount the area viewfinder.
(4)
1
Put the red string round the main unit.
Red string to hold the main unit
Center circle of the lens
2
Insert and mount to the main unit.
Area viewfi nder AVF-1 (optional)
Inspection window
Mounting tips>>
Engage the convex section of the area viewfi nder fi xing
• arms with the notches of the main unit, and insert and mount the arms.
Determine the
3
detection direction
(see Step 5-
Area plate (an accessory)
* Peel off the
protection seal from both faces of the area plate.
4
Insert the area plate into the slot.
1).
Fixing arms
3 Locate the center circle of the area
plate on the center circle of the lens of the area viewfi nder, and check the detection area pattern on the area plate and the background image. * Each letter on the area plate
corresponds to each mirror number (see Step 8-2).
* You cannot observe mirror
numbers B1 to F1 and B6 to F6 (shown at right) of the SIP-3020 area plate through the inspection window. Check them using the walk tester.
Invisible area
Center circle of the lens
Center circle of the area plate
The detection area is inside the frame border.
Adjusting tips>>
If you experience any of the following, see Step 10.
Limit line of
detection area The sensor area is extended over the street where a person walks or a car drives.
Branches of a tree and grass move when the wind blows.
Notch
Mount the area plate so that an arrow of the plate
• center section faces upward and the letter surface can be seen. Insert the area plate into the top and bottom grooves of
• the area viewfi nder until the plate is stopped by the ribs.
SIP-3020 SIP-4010
Arrow marking
Fine adjust the main unit angle in vertical and horizontal
(5)
SIP-3020CAM DN
Grooves
Ribs
SIP-404
direction by observing the target area through the area viewfinder.
1 To change the direction of the inspection
window, rotate the area viewfi nder in a horizontal direction until it clicks and stops.
2 Move your face close to the viewfi nder
so that your eye comes within 5 mm of the inspection window (lens surface).
4010 (521204)4010 (521204)
404 (521205)404 (521205)
Convex section
Cautions>>
The area viewfi nder is a supporting tool for detection area adjustment.
After you have adjusted the detection area using the area viewfi nder, always check the area using the walk tester.
Never look directly into the sun through the area view fi nder.
After you have used the area viewfi nder, store it away from direct sunlight.
(6)
Securely tighten the adjustment screw that you have loosened.
(7)
Connect the walk tester (optional) to the sensor unit, and check that the detection area is correct.
(OPM-WT) (AWT-3)
For near area
For far area
Use at “REDWALL” position.
Power selector switch
REDWAVE
REDWAVE
PIR NEAR
PIR FAR
REDWAVE
REDWAVE
MICROWAVE
ALARM OUTPUT
CELL BATTERY
REDWAVE
POWER SUPPLY FROM
SENSOR REDWALL REDWIDE
POWER OFF
MEGARED
REDWALL
MEGARED
REDWIDE
FAR
MEGARED
NEAR
CONNECTION
MODE
POWER
SELECT
SELECT
SELECT
SWITCH
SWITCH
SWITCH
WALKTESTER
OPM-WT
For all areas
For near area
For far area
Use at “REDWALL” position.
Power selector switch
- 4 -
1 When the power selector switch is turned to “POWER
SUPPLY FROM SENSOR” position after plugging the cable into the walk tester connector, a continuous beeping sound will be heard.
2 When a pedestrian first enters the detection area, the
strong and weak beeps will sound alternately.
3 When the entirety of a pedestrian’s body is detected, the
strong beep will sound continuously.