Omron PRT1-SCU11, PROFIBUS DP GATEWAY OPERATION MANUAL

Page 1
Cat. No. W01E-EN-02
PRT1-SCU11
PROFIBUS-DP Gateway to Host Link/Compoway-F
OPERATION MANUAL
Page 2

PRT1-SCU11 PROFIBUS DP Gateway

Operation Manual
Revised September 19, 2005
Page 3
iv
Page 4
Notice:
OMRON products are manufactured for use by a trained operator and only for the purposes described in this manual.
The following conventions are used to classify and explain the precautions in this manual. Always heed the information provided with them.
!DANGER
!WARNING
!Caution
Indicates information that, if not heeded, is likely to result in serious injury or loss of life.
Indicates information that, if not heeded, could possibly result in serious injury or loss of life.
Indicates information that, if not heeded, could possibly result in minor or relatively serious injury, damage to the product or faulty operation.
OMRON Product References
All OMRON products are capitalized in this manual. The first letter of the word when it refers to an OMRON product, regardless of whether it appears in the proper name of the prod­uct.
The abbreviation and is abbreviated as Wd in the documentation.
The abbreviation
Ch
appears in some displays and on some OMRON products. It often means
PLC
means Programmable Logic Controller.
Visual Aids
The following headings appear in the left column of the manual to help you locate different types of information.
Unit
is also capitalized
word
Note Indicates information of particular interest for efficient and convenient opera-
tion of the product.
1, 2, 3...Indicates various lists such as procedures, checklists etc.
v
Page 5
Trademarks and Copyrights
r f
PROFIBUS, PROFIBUS FMS, PROFIBUS DP, and PROFIBUS PA are trademarks of PROFIBUS International.
Microsoft, Windows, Windows NT, Windows 2000, Windows XP, Windows Explorer and ActiveX are trademarks of Microsoft Corporation.
Other product names and company names in this manual are trademarks or registered trademarks of their respective companies.
The copyright of the PRT1-SCU11 PROFIBUS DP Gateway belongs to OMRON Corporation.
OMRON, 2005
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, o by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission o OMRON.
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is con­stantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication.
vi
Page 6
TABLE OF CONTENTS
About this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ix
PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xi
1 Intended Audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xii
2 General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xii
3 Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xii
4 Operating Environment Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xiii
5 Application Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .xiii
6 Conformance to EC Directives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xv
SECTION 1
Features and Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1-1 Overview of PROFIBUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1-2 PROFIBUS DP Network configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1-3 PROFIBUS DP Gateway . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1-4 Basic Operating Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
SECTION 2
Installation and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2-1 Unit Components. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
2-2 Installing the PRT1-SCU11 PROFIBUS DP Gateway . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
2-3 Wiring the RS-422A / RS-485 Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
2-4 Initial Setup Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
2-5 Setting up a PROFIBUS Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
2-6 Configuring the PROFIBUS DP network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
SECTION 3
Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
3-1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
3-2 PROFIBUS Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
3-3 Compoway-F Communication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
3-4 K-Format Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
3-5 Host Link Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
3-6 Memobus Communication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
3-7 PROFIBUS Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
3-8 Auxiliary RS-232C interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
vii
Page 7
TABLE OF CONTENTS
SECTION 4
Troubleshooting and Maintenance . . . . . . . . . . . . . . . . . . . . 57
4-1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
4-2 Troubleshooting Using LED Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
4-3 Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
4-4 Replacing the Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Appendices
A Memory Mapping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .63
B Function Block Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Index. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
viii
Page 8

About this Manual

This manual describes the PRT1-SCU11 PROFIBUS DP Gateway, how to install it and how and oper­ate the Unit. The Unit version number on the side case of the housing indicates supported functional­ity. If no version number is shown, the version number is 1.0. The following table lists the functions supported per version number.
Unit name Unit Version Protocols supported
PRT1-SCU11 1.0 Compoway-F
2.0 Compoway-F
Unit version 2.0 includes the same functions as Unit version 1.0, in addition to new protocols sup­ported. Unit version 2.0 will eventually replace Unit version 1.0.
Note This manual describes the features and functions of Unit version 2.0.
Please read this manual carefully so that you understand the information provided before installing or using the PRT1-SCU11 PROFIBUS DP Gateway. Start with the precautions in the following section. They describe the operating environment and application safety measures which must be observed prior to and when using the PRT1-SCU11 PROFIBUS DP Gateway.
The sections of this manual are as follows:
Section 1
introduces the PRT1-SCU11 PROFIBUS DP Gateway.
Host Link
Host Link K-Format protocol Memobus
Section 2 Section 3 Section 4
The
describes the installation and setup of the PRT1-SCU11 PROFIBUS DP Gateway. describes operational aspects of the PRT1-SCU11 PROFIBUS DP Gateway. provides procedures for troubleshooting the PRT1-SCU11 PROFIBUS DP Gateway.
Appendices
contain information supplementary to the information in the main body of the man-
ual. They are referred to in the various sections as required.
Manual Products Contents Cat. No.
CS/CJ Series PROFIBUS DP Master Units Operation Manual
E5GN Temperature Controller User manual
E5EN Temperature Controller User manual
E5AN Temperature Controller User manual
E5CN Temperature Controller User manual
SYSMAC CS1/CJ1W-PRM21 Describes the Installation and Opera-
tion of the CS1/CJ1W-PRM21 PROFI­BUS DP Master Units and CX-Profibus Configurator.
E5GN Temperature Controller Describes the Installation and Opera-
tion of the E5GN Temperature Control­ler.
E5EN Temperature Controller Describes the Installation and Opera-
tion of the E5EN Temperature Control­ler.
E5AN Temperature Controller Describes the Installation and Opera-
tion of the E5AN Temperature Control­ler.
E5CN Temperature Controller Describes the Installation and Opera-
tion of the E5CN Digital Temperature Controller.
W409-E2-
H101-E1-
H111-E1-
H112-E1-
H129-E1-
@
@
@
@
@
ix
Page 9
Manual Products Contents Cat. No.
E5@N Communication Func­tions User manual
E5ZN Temperature Controller User manual
E5AR/E5ER Digital Controller Users Manual
E5@K Communication Func­tions User manual
R88A-MCW151-E / R88A­MCW151-DRT-E Motion Con­trol Option Board Operation Manual
VARISPEED F7 Vector Control Frequency Inverter User’s Manual
E5AN/E5EN/E5CN/E5GN Tem­perature Controllers
E5ZN Temperature Controller Describes the Installation and Opera-
E5AR/E5ER Digital Controller Describes the Installation and Opera-
E5AK/E5EK Process Controllers Describes the Installation and Opera-
R88A-MCW151-E / R88A­MCW151-DRT-E Motion Control Option Board
OMRON-Yaskawa VARISPEED F7 Inverter
Describes the Compoway-F Communi­cation Functions for the E5AN/E5EN/ E5CN/E5GN Temperature Controllers.
tion of the E5ZN Temperature Control­ler.
tion of the E5AR/E5ER Digital Control­lers.
tion of the E5AK/E5EK Intelligent Digi­tal Controller.
Describes the Installation and Opera­tion of the R88A-MCW151-E / R88A­MCW151-DRT-E Motion Control Option Board.
Describes the Installation and Opera­tion of the OMRON-Yaskawa VARISPEED F7 Inverter.
H102-E1­H130-E1-
H113-E1-
Z182-E1-
H083-E1­H085-E1-
I203-E2-
YEG-TOE­S616-55.1­OY
@
@ @
@
@
@ @
!WARNING
x
Failure to read and understand the information provided in this manual may result in per­sonal injury or death, damage to the product, or product failure. Please read each section in its entirety and be sure you understand the information provided in the section and related sections before attempting any of the procedures or operations given.
Page 10

PRECAUTIONS

This section provides general precautions for using the PRT1-SCU11 PROFIBUS DP Gateway modules, Programmable Controllers and related devices.
The information contained in this section is important for the safe and reliable operation of the PRT1-SCU11 PROFIBUS DP Gateway. You must read this section and understand the information contained before attempting to set up or operate a PROFIBUS DP Gateway system.
1 Intended Audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xii
2 General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xii
3 Safety Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xii
4 Operating Environment Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xiii
5 Application Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xiii
6 Conformance to EC Directives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xv
6-1 Applicable Directives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xv
6-2 Concepts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xv
6-3 Conformance to EC Directives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xv
xi
Page 11
Intended Audience

1 Intended Audience

This manual is intended for the following personnel, who must also have a knowledge of electrical systems (an electrical engineer or the equivalent).
• Personnel in charge of installing FA systems.
• Personnel in charge of designing FA systems.
• Personnel in charge of managing FA systems and facilities.

2 General Precautions

The user must operate the product according to the performance specifica­tions described in the operation manuals.
Before using the product under conditions which are not described in the manual or applying the product to nuclear control systems, railroad systems, aviation systems, vehicles, combustion systems, medical equipment, amuse­ment machines, safety equipment, and other systems, machines, and equip­ment that may have a serious influence on lives and property if used improperly, consult your OMRON representative.
Make sure that the ratings and performance characteristics of the product are sufficient for the systems, machines, and equipment, and be sure to provide the systems, machines, and equipment with double safety mechanisms.
This manual provides information for programming and operating OMRON PROFIBUS DP Gateway. Be sure to read this manual before attempting to use the Unit and keep this manual close at hand for reference during opera­tion.
1
!WARNING
It is extremely important that the Unit is used for its specified purpose and under the specified conditions, especially in applications that can directly or indirectly affect human life. You must consult your OMRON representative before using it in a system in the above-mentioned applications.

3 Safety Precautions

!WARNING
!WARNING
!WARNING
Do not attempt to take any Unit apart while the power is being supplied. Doing so may result in electric shock.
Never touch any of the terminals while power is being supplied. Doing so may result in serious electrical shock or electrocution.
Do not attempt to disassemble, repair, or modify any of the Units. Any attempt to do so may result in malfunction, fire, or electric shock.
xii
Page 12
Operating Environment Precautions

4 Operating Environment Precautions

4
!Caution
!Caution
Do not operate the Unit in the following places:
• Locations subject to direct sunlight.
• Locations subject to temperatures or humidities outside the range speci­fied in the specifications.
• Locations subject to condensation as the result of severe changes in tem­perature.
• Locations subject to corrosive or flammable gases.
• Locations subject to dust (especially iron dust) or salt.
• Locations subject to exposure to water, oil, or chemicals.
• Locations subject to shock or vibration.
Provide proper shielding when installing in the following locations:
• Locations subject to static electricity or other sources of noise.
• Locations subject to strong electromagnetic fields.
• Locations subject to possible exposure to radiation.
• Locations near to power supply lines.
The operating environment of the PROFIBUS DP Gateway can have a large effect on the longevity and reliability of the system. Unsuitable operating envi­ronments can lead to malfunction, failure and other unforeseeable problems with the system. Ensure that the operating environment is within the specified conditions at installation time and remains that way during the life of the sys­tem. Follow all installation instructions and precautions provided in the opera­tion manuals.

5 Application Precautions

Observe the following precautions when using the PROFIBUS DP Gateway.
!WARNING
!Caution
Failure to abide by the following precautions could lead to serious or possibly fatal injury. Always heed these precautions.
• Always connect to a class-3 ground (100 Units.
Failure to abide by the following precautions could lead to faulty operation of the Unit or the system or could damage the Unit or Temperature Controllers and R88A-MCW151-E. Always heed these precautions.
• Install double safety mechanisms to ensure safety against incorrect sig­nals that may be produced by broken signal lines or momentary power interruptions.
• When adding a new device to the network, make sure that the baud rate is the same as other nodes.
or less) when installing the
xiii
Page 13
Application Precautions
5
• When adding a new Host Link or Compoway-F node to the network, make sure that the PROFIBUS DP Gateway is powered down, to prevent unex­pected results when starting up the new node.
• Use specified communications cables.
• Do not extend connection distances beyond the ranges given in the spec­ifications.
• Always turn OFF the power supply to the personal computer, Slaves, and Communications Units before attempting any of the following.
• Mounting or dismounting the PROFIBUS DP Gateway, Power Supply Units, I/O Units, CPU Units, or any other Units.
• Assembling a Unit.
• Setting DIP-switches or rotary switches.
• Connecting or wiring the cables.
• Connecting or disconnecting connectors.
• Be sure that all the mounting screws, terminal screws, Unit mounting screws, and cable connector screws are tightened to the torque specified in the relevant manuals. Incorrect tightening torque may result in malfunc­tion.
• Leave the label attached to the Unit when wiring. Removing the label may result in malfunction if foreign matter enters the Unit.
• Remove the label after the completion of wiring to ensure proper heat dis­sipation. Leaving the label attached may result in malfunction.
• Always use the power supply voltage specified in this manual.
• Double-check all the wiring and connection of terminal blocks and con­nectors before mounting the Units.
• Use crimp terminals for wiring. Do not connect bare stranded wires directly to terminals.
• Observe the following precautions when wiring the communications cable.
• Separate the communications cables from the power lines or high-ten­sion lines.
• Do not bend the communications cables.
• Do not pull on the communications cables.
• Do not place heavy objects on top of the communications cables.
• Be sure to wire communications cable inside ducts.
• Use appropriate communications cables.
• Take appropriate measures to ensure that the specified power with the rated voltage and frequency is supplied in places where the power supply is unstable. An incorrect power supply may result in malfunction.
• Install external breakers and take other safety measures against short-cir­cuits in external wiring. Insufficient safety measures against short-circuits may result in burning.
• Double-check all the wiring and switch settings before turning ON the power supply.
• When transporting or storing the product, cover the PCB’s with electrically conductive materials to prevent LSI’s and IC’s from being damaged by static electricity, and also keep the product within the specified storage temperature range.
xiv
Page 14
Conformance to EC Directives
• When transporting the Unit, use special packing boxes and protect it from being exposed to excessive vibration or impacts during transportation.
• Do not attempt to disassemble, repair, or modify any Units.

6 Conformance to EC Directives

6-1 Applicable Directives

•EMC Directives
• Low voltage directive

6-2 Concepts

OMRON units complying with EC Directives also conform to related product standards making them easier to incorporate in other units or machines. The actual products have been checked for conformity to product standards. Whether the products conform to the standards in the system used by the customer, however, must be checked by the customer.
Product related performance of OMRON units complying with EC Directives will vary depending on the configuration, wiring, and other conditions of the equipment or control panel in which OMRON devices are installed. The cus­tomer must, therefore, perform final checks to confirm that units and the over­all system conforms to product standards.
A Declaration of Conformity for the PROFIBUS DP Gateway can be requested at your nearest OMRON representative.
6

6-3 Conformance to EC Directives

PROFIBUS units should be installed as follows, for the complete configuration to meet the EC directives:
1,2,3...
1. The units are designed for installation inside control panels. All units must be installed within control panels.
2. Use reinforced insulation or double insulation for the DC power supplies used for the communications power supply, internal circuit power supply, and the I/O power supplies.
3. The PROFIBUS DP Gateway product meets the generic emission stan­dard. However as EMC performance can vary in the final installation, ad­ditional measures may be required to meet the standards. It should therefore be verified that the overall machine or device also meets the rel­evant standards. You must therefore confirm that EC directives are met for the overall machine or device, particularly for the radiated emission re­quirement (10 m).
xv
Page 15
Page 16
SECTION 1
Features and Specifications
This section provides an introductory overview of PROFIBUS, its functions and how to setup and configure a network. It also addresses the PRT1-SCU11 PROFIBUS DP Gateways and the Configurator, their features and specifications.
1-1 Overview of PROFIBUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1-1-1 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1-1-2 PROFIBUS Communication Protocol . . . . . . . . . . . . . . . . . . . . . . . 2
1-1-3 Device Types. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1-1-4 Bus Access Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1-1-5 Diagnostic functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1-1-6 Protection mechanisms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1-1-7 Network Operation Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1-2 PROFIBUS DP Network configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1-3 PROFIBUS DP Gateway. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1-3-1 PROFIBUS DP Gateway Features . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1-3-2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
1-4 Basic Operating Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
1-4-1 Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
1-4-2 Procedures Prior to Starting Communications . . . . . . . . . . . . . . . . . 15
1
Page 17
Overview of PROFIBUS
Section 1-1

1-1 Overview of PROFIBUS

1-1-1 Introduction

Standard EN50170 PROFIBUS (PROcess FIeldBUS) is an open fieldbus standard for a wide
range of applications in manufacturing, processing and building automation. The Standard, EN 50170 (the Euronorm for field communications), to which PROFIBUS adheres, guarantees vendor independence and transparency of operation. It enables devices of various manufacturers to intercommunicate without having to make any special interface adaptations.
The PROFIBUS family comprises three mutually compatible versions: PROFIBUS FMS, PROFIBUS DP and PROFIBUS PA.
PROFIBUS FMS FMS means Fieldbus Message Specification. This version is the general-pur-
pose solution for high-level extensive and complex communication tasks. Powerful services open up a wide range of applications and provide great flexibility.
PROFIBUS DP DP means Decentralized Periphery. PROFIBUS DP is optimized for high
speed and low-cost interfacing. It is specially designed for communication between automation control systems and distributed I/O at the device level.
PROFIBUS PA PA means Process Automation. It permits sensors and actuators to be con-
nected to one common bus even in areas where intrinsically safe products are required. It also permits data and power to be supplied over the bus using 2-wire technology according the international standard IEC 1158-2.
Uniform Bus Access Protocol
!Caution
PROFIBUS DP and PROFIBUS FMS use the same transmission technology and uniform bus access protocol. Consequently, both versions can be oper­ated simultaneously on the same bus. FMS field devices, however, cannot be controlled by DP masters and vice versa.
It is not possible to exchange one of these family members by another family member. This will cause faulty operation.
The rest of this section describes the PROFIBUS DP Protocol architecture.

1-1-2 PROFIBUS Communication Protocol

OSI reference model
ISO-7498
In general, the PROFIBUS communication protocol is based on the Open System Interconnection (OSI) reference model in accordance with the inter­national standard ISO-7498 (see the following illustration). The model defines 7 layers of communication functions, three of which - layers 1, 2, and 7 - are used in PROFIBUS.
• Layer 1, the Physical Layer of this model, defines the physical transmis­sion characteristics.
• Layer 2, the Data Link Layer of this model, defines the bus access proto­col. This protocol also includes data security and the handling of trans­mission protocols and telegrams.
• Layer 7, the Application Layer of this model, defines the application func­tions. This Layer is only applicable to PROFIBUS FMS.
2
Page 18
Overview of PROFIBUS
Section 1-1
DP-Profiles
User Interface Layer DP Basic Functions (7) Application Layer (6) Presentation Layer (5) Session Layer NOT DEFINED (4) Transport Layer (3) Network Layer (2) Data Link Layer Fieldbus Data Link (FDL) (1) Physical Layer RS-485 / Fibre Optics
OSI Layer 1, 2 and User Interface
PROFIBUS DP uses layers 1 and 2, and the user interface. Layers 3 to 7 are not defined for PROFIBUS DP. The user interface Layer defines the interface functions for specific application areas, i.e. the PROFIBUS DP basic functions and communication profiles.This streamlined architecture ensures fast and efficient data transmission. The application functions which are available to the user, as well as the system and device behaviour of the various PROFI­BUS DP device types, are specified in the user interface.
OSI Layer 1: Transmission Medium
RS-485 transmission technology or fibre optics are available for transmission. RS-485 transmission is the most frequently used transmission technology. Its application area includes all areas in which high transmission speed and sim­ple inexpensive installation are required. PROFIBUS modules are intercon­nected by single twisted-pair shielded copper wires.
RS-485 Technology The RS-485 transmission technology is very easy to handle. Installation of the
twisted pair cable does not require expert knowledge. The bus structure per­mits addition and removal of devices or step-by-step commissioning of the system without influencing the other devices. Later expansions have no effect on devices which are already in operation.
RS-485 Transmission Speed
Transmission speeds between 9.6 kbit/s and 12 Mbit/s can be selected as shown in the table below. One unique transmission speed must selected for all devices on the bus (master and slave devices) when the system is com­missioned
Baud rate (kbit/s) Distance / segment (m)
9.6 1200
19.2 1200
45.45 1200
93.75 1200
187.5 1000 500 400
1500 200 3000 100 6000 100
12000 100
Cable length The maximum cable length values depend on the transmission speed and are
based on type-A cable (see
Bus Cable Connector
on page 34). The length can be increased by the use of repeaters.However, it is not recommended to use more than three repeaters in series in a PROFIBUS network.
3
Page 19
Overview of PROFIBUS
Section 1-1

1-1-3 Device Types

PROFIBUS distinguishes between master devices and slave devices.
Master Devices Master devices determine the data communication on the bus. A Master can
send messages without an external request, as long as it holds the bus access right (the token). Masters are also referred to as active devices in the PROFIBUS standard.
There are two types of master devices:
Class 1 Master (DPM1) A PROFIBUS DP Class 1 Master (DPM1) device is a central controller, which
exchanges information with the decentralized devices (i.e. DP slaves) within a specified message cycle.
Class 2 Master (DPM2) PROFIBUS DP class 2 Master (DPM2) devices are programmers, configura-
tion devices or operator panels. They are used during commissioning, for con­figuration of the DP system, or for operation and monitoring purposes.
Slave Devices Slave devices are peripheral devices. Typical slave devices include input/out-
put devices, valves, drives, and measuring transmitters. They do not have bus access rights and they can only acknowledge received messages or send messages to the master when requested to do so. Slave devices are also called passive devices. The PRT1-SCU11 is a slave device.
Device Profile To enable the exchange of devices from different vendors, the user data has
to have the same format. The PROFIBUS DP protocol does not define the for­mat of user data, it is only responsible for the transmission of this data. The format of user data may be defined in so called profiles. Profiles can reduce engineering costs since the meaning of application-related parameters is specified precisely. Profiles have been defined for specific areas like drive technology, encoders, and for sensors / actuators.

1-1-4 Bus Access Protocol

OSI Layer 2: Bus Access Protocol
Medium Access Control The Medium Access Control (MAC) specifies the procedures which determine
Token Passing The token passing procedure guarantees that the bus access right (the token)
Polling Procedure The polling or master-slave procedure permits the master, currently in pos-
The PROFIBUS bus access protocol is implemented by OSI layer 2. This pro­tocol also includes data security and the handling of the transmission proto­cols and messages.
when a device is permitted to transmit data. A token passing procedure is used to handle the bus access between master devices, and a polling proce­dure is used to handle the communication between a master device and its assigned slave device(s).
is assigned to each master within a precisely defined time frame. The token message, a special message for passing access rights from one master to the next master, must be passed around the logical token ring - once to each master - within a specified target rotation time. Each master executes this pro­cedure automatically.
session of the token, to access its assigned slaves. The figure below shows a possible configuration The configuration shows three active devices (masters) and six passive devices (slaves).
The three masters form a logical token ring. When an active device receives the token message, it can perform its master role for a certain period of time. During this time it can communicate with all assigned slave devices in a mas­ter-slave communication relationship, and a DPM2 master can take the initia-
4
Page 20
Overview of PROFIBUS
tive to communicate with DPM1 master devices in a master-master communication relationship.
Multi-peer Communication In addition to logical peer-to-peer data transmission, PROFIBUS DP provides
multi-peer communication (broadcast and multicast).
Section 1-1
Broadcast Communication
Multicast Communication In the case of multicast communication a master device sends an un-
In the case of broadcast communication a master device sends an unac­knowledged message to all other devices (masters and slaves).
acknowledged message to a predetermined group of devices (masters and slaves).

1-1-5 Diagnostic functions

Extensive Diagnostics Extensive diagnostic functions defined in PROFIBUS DP enable the fast loca-
tion of error at slave devices. Diagnostic messages are transmitted over the bus and collected at the master. Three levels of diagnostic messages are defined:
Device Related Diagnostics
Module Related Diagnostics
Channel Related Diagnostics
• Messages concerning the general operational status of the whole device, e.g. over temperature, low voltage.
• Messages indicating that an error is present in a specific I/O range of a device, e.g. an 8-bit output module.
• Messages indicating an error at a given input or output, e.g. short circuit on Output 5.

1-1-6 Protection mechanisms

Monitoring Time PROFIBUS DP provides effective protection functions against parameteriza-
tion errors or failure of the transmission equipment. Time monitoring is pro­vided both at the master and the slave devices. The monitoring interval is specified when the system is configured.
Monitoring at the Master The PROFIBUS DP Master monitors data transmission of the slaves with the
Data-Control-Timer. A separate control timer is used for each slave. This timer expires if response data is not correctly transmitted by the slave within the monitoring interval. The user is informed when this happens. If the auto­matic error reaction (Auto-CLEAR) has been enabled, the PROFIBUS DP
5
Page 21
PROFIBUS DP Network configuration
master exits its OPERATE state, switches the outputs of all assigned slaves to the fail-safe status and changes to the CLEAR state.
Monitoring at the Slave Slave devices use a watchdog to detect failures of the master or the bus. If
data communication with the master does not occur within the set watchdog time interval, a slave automatically switches its outputs to the fail-safe mode.
Also, access protection is provided for the inputs and outputs of the slaves operating in multi-master systems. Only authorized masters can access their slaves.
Section 1-2

1-1-7 Network Operation Modes

PROFIBUS DP distinguishes four different network operation modes:
OFF-LINE Communication with all PROFIBUS DP participants (masters and slaves) is
stopped. The Master ceases to access the PROFIBUS network.
STOP Communication between the master and its slaves is stopped. Only communi-
cation between the master and other masters is still possible.
CLEAR The master tries to set parameters, check the configuration, and perform data
exchange with its associated slaves. Data exchange involves reading the inputs of the PROFIBUS DP slaves and writing zeros to the outputs of the slaves.
OPERATE The master exchanges data with its assigned slaves, inputs are read and out-
puts are written. Also, the master cyclically sends its local status to all its assigned PROFIBUS DP slaves (using a broadcast message).
Auto-CLEAR
Fail-safe State
If an error occurs during the data exchange phase of the master, the ‘Auto­CLEAR’ function determines the subsequent actions. If this function has been disabled, the master remains in the OPERATE mode. If the function has been enabled, the master automatically changes the network to the CLEAR mode, in which the outputs of the assigned PROFIBUS DP slaves are switched to zero, i.e. the ‘fail-safe’ state. The master continues to read the inputs of the slaves.

1-2 PROFIBUS DP Network configuration

In order to operate a PROFIBUS network, each master in the network needs to be configured. This process of PROFIBUS Master configuration involves:
• setting up the network topology, i.e. assigning the slave devices with which the master will be exchanging data,
• defining the parameterization data, which the master will send to each of the slave devices, before process data exchange can commence
• defining the configuration data, i.e. defining the process data, which will be exchanged,
• setting up the bus parameters, which define the baud rate and the bus timing parameters.
• downloading the configuration setup to the master device.
Configuration Technology The configuration process is usually facilitated by a special Computer based
program, often referred to as a Configurator. The Configurator requires spe­cial configuration files, defining the configuration options for each device, which is to participate in data exchange. The files must be provided by the manufacturer of the device.
6
Page 22
PROFIBUS DP Network configuration
Two types of configuration technology exist:
• Configuration technology based on FDT/DTM technology
• Configuration technology based on GSD-files
FDT/DTM Concept The FDT/DTM concept specifies the interfaces between the engineering sys-
tems called Field Device Tools (FDT), and the device-specific software com­ponents called Device Type Managers (DTM).
The FDT/DTM concept separates the device dependent functionality (which is in the DTM) from the application. It provides separate interfaces for device configuration, monitoring and maintenance solutions, which before largely depended on the manufacturer of the application. Because of this concept, FDT/DTM technology is not limited to PROFIBUS applications. In concept, any type of network can be configured and accessed, provided the appropri­ate DTM’s are available.
CX-Profibus is an example of a FDT container application. It is described in detail in the following sections.
GSD file Technology The older and most commonly used configuration technology is the based on
GSD files (General Slave Data file). A GSD file is a text file, containing the characteristic features and configuration options of a device. The device data base file of each device is loaded in the configurator and downloaded to the master device.
GSD files are usually supplied with a unit, or can be downloaded from the Internet, either from the manufacturer's site, or from the GSD library of the PROFIBUS Nutzer Organisation at http://www.profibus.com.
Section 1-2
GSD File Language The language used in the GSD file is indicated by the last letter of the file
extension, *.GS?: Default = GSD
English = GSE German = GSG Italian = GSI Portuguese = GSP Spanish = GSS The GSD files are prepared individually by the vendor for each type of device,
according to a fixed format. Some parameters are mandatory, some have a default value and some are optional. The device data base file is divided into three parts:
General Section • General specifications
This section contains the vendor name, the device name, hardware- and soft­ware release versions, device type and identification number, protocol specifi­cation and supported baud rates.
DP-master Section • DP master-related specifications
This section contains all parameters which only apply to DP master devices (e.g. maximum memory size for the master parameter set, maximum number of entries in the list of active devices, or the maximum number of slaves the master can handle).
DP-slave Section • DP slave-related specifications
This section contains all specification related to slaves (e.g. minimum time between two slave poll cycles, specification of the inputs and outputs, and consistency of the I/O data).
7
Page 23
PROFIBUS DP Gateway

1-3 PROFIBUS DP Gateway

1-3-1 PROFIBUS DP Gateway Features

Section 1-3
PRT1-SCU11 PROFIBUS DP Gateway
The PRT1-SCU11 is a standalone product, providing an interface between a PROFIBUS DP Master device and the following OMRON units.
Unit Description Protocol
supported
E5AN / E5CN /
OMRON single channel Temperature controllers. Compoway-F
E5EN / E5GN
E5ZN OMRON 2-channel Temperature controllers.
E5AR / E5ER OMRON 4-channel Temperature controllers.
E5__ / K3__ /
H8GN
OMRON instruments, supporting OMRON’s RS­485 based Compoway-F protocol.
E5AK / E5EK OMRON Intelligent Digital Controllers K-Format
protocol
R88A-MCW151-E Option board for W-series servo drives. Host Link
F7 Inverter OMRON-Yaskawa Varispeed F7 Inverter. Memobus
In addition to this functionality, an auxiliary RS-232C interface is provided on the Unit, to provide a direct connection to a Personal Computer. This direct connection links the Personal Computer directly to Compoway-F / K-Format / Memobus protocol, thus bypassing the PROFIBUS DP connection.
Note The PRT1-SCU11 supports only one of the possible protocols at a time. This
means that for example a mix of Compoway-F and Host Link devices is not supported.
Typical application setup A typical application setup for the PRT1-SCU11 is shown in the figure below.
The PRT1-SCU11 Unit interfaces between PROFIBUS DP and Host Link, Compoway-F, Memobus and the K-Format protocol.
IBM PS/2
Compoway-F network
(e.g.) E5ZN
PROFIBUS DP network
PRT1-SCU11 PROFIBUS DP Gateway
(e.g.) E5_N
(e.g.) E5ER
Host Link network
PRT1-SCU11 PROFIBUS DP Gateway
R88A­MCW151
PROFIBUS-DP Master
PRT1-SCU11 PROFIBUS DP Gateway
F7 Inverter
R88A­MCW151
Memobus network
F7 Inverter
PRT1-SCU11 PROFIBUS DP Gateway
K-Format network
E5EK
E5AK
8
Page 24
PROFIBUS DP Gateway
The PRT1-SCU11 is present on the PROFIBUS DP network as a slave unit. The interface of the PRT1-SCU11 is controlled by a Master unit on the net­work. This Master unit can be any PROFIBUS DP class 1 or class 2 master
Compoway-F Compoway-F is the OMRON proprietary serial communication bus system,
based on RS-485, to communicate with a range of OMRON Temperature Controllers.
K-Format The K-Format protocol is the OMRON proprietary serial communication bus
system, based on either RS-422A or RS-485, to communicate with OMRON’s E5AK/E5EK Intelligent Digital Controllers.
Host Link Host Link is the OMRON proprietary serial communication bus system, based
on RS-422A, to communicate with the OMRON/Yaskawa R88A-MCW151-E option board for W-series servo drives.
Memobus The Memobus protocol is the Omron-Yaskawa variation of the Modbus RTU
Protocol used to communicate over either RS-422A or RS-485 with Omron­Yaskawa F7 Inverters.
Section 1-3
IBM compatible Personal Computer
I/O Data The data exchanged over PROFIBUS DP are word sized, and represent
Fixed Communication Blocks
Free Communication Blocks
An IBM compatible Personal Computer is connected to the PRT1-SCU11 PROFIBUS DP Gateway via a RS-232C serial communication to the auxiliary port. Application programs running on the Personal Computer can communi­cate through the auxiliary port with Compoway-F, K-Format and Memobus components, thus bypassing the PROFIBUS DP interface. The Host Link pro­tocol is not supported by the Auxiliary port.
either fixed length communication blocks or Free Communication blocks. The PRT1-SCU11 PROFIBUS DP Gateway limits the total number of input words to 100 words, and the total number of output words to 100 words.
Fixed Communication Blocks are I/O modules with predefined parameter con­tent. These modules are to be used to send output and control data to a device and read status from a device. These I/O modules are defined in the PRT1-SCU11 and cannot be changed by the user. They are the most com­monly used and straight forward way to exchange data between a Master and one or more of the devices attached to the PRT1-SCU11.
In general there are at least two Fixed Communication Blocks defined for each device type or group of devices attached to a PRT1-SCU11. One block is always available for limited I/O data, e.g. setpoint and process value, and one block is available for extended I/O data transfer.
Free Communications Blocks, are predefined I/O modules, which allow the user to send any read, write or operate instruction to any attached Compo­way-F, K-Format or Memobus device without unit interference. The informa­tion in the Free Communication Block is used by the PRT1-SCU11 to assemble the correct message format.
Three types of Free Communication Blocks are defined, the types are Oper­ate, Read and Write.
• Operate: Execution of a special operation command, which is defined in a controller.
• Write: Execution of a write data command to any parameter defined in a controller.
• Read: Execution of a read data command of any parameter defined in a controller.
9
Page 25
PROFIBUS DP Gateway
Section 1-3
PROFIBUS I/O Data Exchange
Troubleshooting Functions
The PRT1-SCU11 PROFIBUS DP Gateway supports cyclic Master - Slave communications, i.e. data exchange mode. In data exchange mode the PRT1-SCU11:
• retrieves all data from the attached units (e.g. Compoway-F) according to the PROFIBUS configuration and stores this data in the PROFIBUS input buffer. All input data is obtained before the data is sent to the PROFIBUS Master as input data.
• writes all data from the PROFIBUS outputs to the attached units accord­ing to the PROFIBUS configuration, using the proper protocol. Only if the data received from the Master differs from the current value in the units, the new output data is sent.
• sends special operation commands.
• sends command data from Free Communication Blocks to the addressed unit, and returns the command response to the Master as PROFIBUS input data.
The PRT1-SCU11 is provided with a variety of troubleshooting functions for prompt recovery in case of errors:
• Extensive self-diagnostic function at startup.
• Diagnostics information is sent to the PROFIBUS Master unit in case:
• One or more units attached to the PRT1-SCU11 has a communication error.
• The PRT1-SCU11 has a system error.
• Diagnostics flags, indicating if units attached to the PRT1-SCU11 are functioning correctly. For Host Link there is a communication active bit that indicates to the Host Link Unit if the received PROFIBUS data is valid.

1-3-2 Specifications

General Specifications The PRT1-SCU11 is a Gateway between PROFIBUS DP and a range of
OMRON devices, supporting OMRON proprietary protocols. The Unit version number on the side case of the housing indicates supported protocols. If no version number is shown, the version number is 1.0. The following table lists the protocols supported per version number.
PROFIBUS DP Gateway Model
Note 1. Unit version 2.0 includes the same functions as Unit version 1.0, in addition
Model name Unit Version Protocol supported
PRT1-SCU11 1.0 Compoway-F
Host Link
2.0 Compoway-F Host Link K-Format Memobus
to new protocols supported, and it is backward compatible with Unit ver­sion 1.0. Unit version 2.0 will eventually replace Unit version 1.0.
2. This manual describes all features and functions of Unit version 2.0.
10
Page 26
PROFIBUS DP Gateway
PRT1-SCU11 PROFIBUS DP Gateway Specifications
Item Specification (Unit version 2.0)
Model PRT1-SCU11 Mounting position DIN rail mounted Power supply 24 Vdc +10% -15% (20.4 to 26.4 Vdc) Current consumption 85 mA (max), 75 mA typical at 24 Vdc Dimensions (W x H x D) 40 x 90 x 65 mm Weight 130g
Installation
Ambient temperatures Operating temperature: 0 to 55°C
Ambient operating humidity 10% to 90% (with no condensation) Vibration resistance Conforms to IEC60068-2-6, test Fc.
Shock resistance Conforms to IEC60068-2-27, test Ea.
Dielectric strength 600 VAC (between isolated circuits) Conformance to EMC and Electrical
safety standards
Environment
Settings, rotary switches 2 Slave address rotary switches, range: 0 ~ 99 (Decimal) Settings DIP-switches 4 DIP-switches on the front of the Unit:
Indicators 6 LED’s, indicating Unit status and PROFIBUS status:
PROFIBUS Connector 9-pin sub-D female connector (#4/40 UNC thread).
Front case
Number of GSD I/O Units 15. Number of GSD I/O modules 18, maximum number of modules represent 15 units and 1 read, 1 write
Number of I/O data supported by slave Unit
Number of diagnostics data supported by slave Unit
Extended diagnostics supported by the slave Unit
I/O units + data
Storage temperature: –20 to 75°C
10 to 55Hz, 0.25-mm amplitude, 55 to 300Hz, acceleration: 29.4 m/s in X, Y, and Z directions for 120 minutes each. (Total time: 12 linear sweeps x 10 minutes / sweep = 120 minutes)
196 m/s
EN61000-6-2: 2001 EN61000-6-4: 2001/CISPR11 EN61131-2: 2003, IDT
• Switch 1, Switch 2: Baud rate setting RS-422A / RS-485 communi-
• Switch 3: not used.
• Switch 4: auxiliary
Unit status: RUN (Green LED)
RS-422A/RS-485 protocol: FCOM (Green LED)
PROFIBUS status: COMM (Green LED)
and 1 operation Free Communication Block. Total sum of all modules must not exceed 18 modules, this includes a maximum of 15 physical units.
Up to 100 words input and 100 words output maximum.
Up to 7 bytes of diagnostics max. per attached unit. Diagnostic data is collected at the attached unit, and is part of the PROFIBUS input/output message.
The Unit reports system errors and communication errors in a PROFI­BUS extended diagnostic message, this message has a length of 7 bytes. After detection of a system error, the data exchange is stopped.
2
three times each in X, Y, and Z directions
cation interface.
Section 1-3
RS-232C interface function selector.
ERR (Red LED)
FERR (Red LED)
BF (Red LED)
2
11
Page 27
PROFIBUS DP Gateway
Protocol Specifications
Item Specification
Media types • RS-422A, galvanically isolated.
termination resistor Internal 220 Ohm resistor between receiver lines.
Connector 5-pin Phoenix connector Baud rates supported • 9.6 kbit/s
Protocol types supported via this port • Compoway-F
Device address range
Protocol port physical layer
Media type RS-232C, located behind cover marked “Peripheral”
Baud rates supported Baud rate used on Auxiliary port is the same as the baud rate used on
Protocol types supported via this port • Compoway-F
Auxiliary port
Applicable standards EN50170, Volume 2 Protocol type supported PROFIBUS DP PROFIBUS Unit type PROFIBUS DP slave PROFIBUS Media type RS-485, galvanically isolated PROFIBUS Connector 9-pin sub-D female connector (#4/40 UNC thread)
Unit device address range
Baud rates supported (Auto-detect) • 9.6 kbit/s
PROFIBUS DP interface
Section 1-3
• RS-485, galvanically isolated. Selection for RS-485 is made with Physical layer switch 1 (see
Switch Settings
ON: RS-485 OFF: RS-422A
Use of resistor can be enabled or disabled, using Physical layer switch 2 (see
2-1-3 Switch Settings
ON: Termination resistor enabled. OFF: Termination resistor disabled.
• 19.2 kbit/s
• 38.4 kbit/s Selection via DIP-switches 1 and 2. (See
• Host Link
•K-Format
• Memobus
).
).
2-1-3 Switch Settings
1 ~ 15, set through the slot number of the PROFIBUS module configu-
ration. Number 0 (zero) is reserved.
Use the CS1W-CN226 connection cable for connecting the PRT1­SCU11 with Thermotools
the main protocol port. Selection via DIP-switches 1 and 2. (See
•K-Format
• Memobus
Termination according to EN50170 provided by the cable connector
2-1-3 Switch Settings
0 ~ 99, set through rotary switches
Remote setting not supported.
• 19.2 kbit/s
• 45.45 kbit/s
• 93.75 kbit/s
• 187 kbit/s
• 500 kbit/s
• 1.5 Mbit/s
•3 Mbit/s
•6 Mbit/s
• 12 Mbit/s
2-1-3
).
).
12
Page 28
PROFIBUS DP Gateway
Item Specification
PROFIBUS services supported • Set_Prm
PROFIBUS services
Number of I/O data supported Up to 100 words input and 100 words output max. Number of diagnostics data supported 6 Bytes basic, and 9 bytes extended.
I/O Data
External Dimensions
Section 1-3
• Chk_Cfg
• Get_Cfg
• Slave_Diag
• Data_Exchange
• RD_Inp
• RD_Outp
• Global_Control - Sync / Unsync Freeze / Unfreeze/ Clear
90
PRT1-SCU11
PERIPHERAL
24 Vdc
BUS
40
1234
23 1 0
9
23 1 0
NODE ADDRESS
ON
RUN
ERR
4
COMM
5
6
78
BF
x10
x1
4
FCOM
5
6789
FERR
ON
57
1
2
R-
R+
FG
S-
S+
25
65
8
5
Units: mm
13
Page 29
Basic Operating Procedure

1-4 Basic Operating Procedure

1-4-1 Overview

The following diagram provides an overview of the installation procedures. For experienced installation engineers, this may provide sufficient informa­tion. For others, cross-references are made to various sections of this manual where more explicit information is given. When reading this manual online, the flow chart entries provide links to the sections containing detailed informa­tion.
Mount the PRT1-SCU11 on a DIN-rail, and wire the Unit. (See section
SCU11
Select a Device address using the two rotary switches on the front of the PRT1-SCU11 (See section
2-2-2 Mounting the PRT1-
)
2-1-3 Switch Settings
Section 1-4
)
Select a baud rate to be used on the RS-422A/RS-485 protocol network. Disable the auxiliary RS-232C port on the front. (See section
Connect the I/O Modules Units to the RS-422A/RS-485 network, and connect the PRT1-SCU11 to the PROFIBUS network (See section
RS-422A / RS-485 Devices
Power up the PRT1-SCU11. Configure the PROFIBUS Master,
using the Master Configuration tool (See section
PROFIBUS DP network
The PRT1-SCU11 starts exchanging I/O data between the RS-422A/RS-485 devices and the PROFIBUS Master.
Status is confirmed by the FCOM and COMM LED indicators.
(See section
2-1-3 Switch Settings
2-3 Wiring the
)
2-6 Configuring the
).
2-1-2 LED Indicators
)
).
14
Page 30
Basic Operating Procedure

1-4-2 Procedures Prior to Starting Communications

Use the following procedure to configure the Unit using CX-Profibus:
Section 1-4
1,2,3...
1. Wire the network, to connect the PRT1-SCU11 to the RS-422A / RS-485 devices.
2. Turn ON the PLC power supply and the power supply of the PRT1-SCU11.
3. In CX-Profibus, create a network and define the parameters and I/O con­figurations for the PRT1-SCU11 settings and the allocated modules. De­termine the baud rate and the bus parameter setup,
Configuring the PROFIBUS DP network
4. Download the network configuration to the PROFIBUS DP master. After downloading the configuration, CX-Profibus will restart the PROFIBUS DP master automatically.
5. After restarting the PRT1-SCU11 it will automatically start communication.
.
see section
2-6
15
Page 31
Page 32
SECTION 2
Installation and Wiring
This section describes the PRT1-SCU11 PROFIBUS DP Gateway and identifies its controls and indicators. It contains the procedures for installing the PROFIBUS DP Gateway and setting up the PROFIBUS network.
2-1 Unit Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
2-1-1 Nomenclature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
2-1-2 LED Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
2-1-3 Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
2-1-4 PROFIBUS Connector. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
2-1-5 RS-422A / RS-485 Connector. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
2-2 Installing the PRT1-SCU11 PROFIBUS DP Gateway . . . . . . . . . . . . . . . . . . 23
2-2-1 Handling Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
2-2-2 Mounting the PRT1-SCU11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
2-2-3 Wiring the Power Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
2-3 Wiring the RS-422A / RS-485 Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
2-3-1 Precautions When Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
2-3-2 2-Wire and 4-Wire Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
2-3-3 Connection for E5_N Compoway-F Communications . . . . . . . . . . . 24
2-3-4 Connection for E5ZN Compoway-F Communications. . . . . . . . . . . 25
2-3-5 Connection for E5AR/E5ER Compoway-F Communications . . . . . 26
2-3-6 Connection for R88A-MCW151-E Host Link Communications . . . 27
2-3-7 Connection for E5AK/E5EK K-Format Communication . . . . . . . . . 28
2-3-8 Connection for F7 Inverter Memobus Communication. . . . . . . . . . . 29
2-4 Initial Setup Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
2-4-1 Selecting a Node Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
2-5 Setting up a PROFIBUS Network. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
2-5-1 Network Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
2-5-2 Bus Termination. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
2-5-3 PROFIBUS Cable Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
2-5-4 Shielding Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
2-6 Configuring the PROFIBUS DP network . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
2-6-1 Configuring the Slave Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
2-6-2 Defining the I/O Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
2-6-3 Setting Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
17
Page 33
Unit Components

2-1 Unit Components

2-1-1 Nomenclature

The illustration below shows the DIP-switches, physical layer switches, auxil­iary RS-232C port (behind cover), the status LED indicators, the unit number selector switch, and a 9-pin female sub-D connector on the front side of the PRT1-SCU11. Each of these components is explained in the following sec­tions.
Power supply input
Peripheral port (behind cover)
PRT1-SCU11
PERIPHERAL
DIP switches
1234
23 1 0
9
78
23 1 0
NODE ADDRESS
24 Vdc
Section 2-1
PROFIBUS address rotary switches
ON
RUN
ERR
4
COMM
5
6
BF
x10
x1
4
FCOM
5
6789
FERR
ON
Unit LED indicators
1
RS-422A / RS485 switch
2
Termination switch

2-1-2 LED Indicators

R-
R+
PROFIBUS connector
BUS
FG
S-
S+
RS-422A / RS485 connector
The PRT1-SCU11 has six colored (red and green) LED’s to indicate the oper­ational mode, and status of the Unit, the status of the PROFIBUS interface and the status of the RS-422A / RS-485 interface.
PRT1-SCU11
PERIPHERAL
1234
23
1
0
9
23
1
0
NODE ADDRESS
ON
RUN
ERR
4
COMM
5
6
78
BF
x10
x1
4
FCOM
5
6789
FERR
Unit LED indicators
18
Page 34
Unit Components
S
Indicator Specifications
Indicator Color Status Description
RUN Green Not lit • Startup test failed, Unit not operational.
• Operation stopped due to a fatal error.
• Power is off.
Lit Initialization successful, Unit is in normal operation. ERR (unit error)
FCOM (RS-422A / RS-485
communication)
FERR (RS-422A / RS-485
communication) COMM (PROFIBUS communica-
tion)
BF (PROFIBUS Bus fail)
Red Not lit The PRT1-SCU11 is in normal operation (RUN LED is lit).
Flashing The Unit was not able to initialize normally due to a fatal error during
system startup.
Lit Fatal error during operation occurred.
Green Not lit No communication with any devices attached to the RS-422A / RS-485
network. This may be caused by:
• a communication failure (broken wire).
• a non initialized PROFIBUS DP interface.
• the PRT1-SCU11 is not able to exchange data with all configured devices.
Flashing Communication with the RS-422A / RS-485 network is performed
through the auxiliary port. The PROFIBUS DP interface is bypassed.
Lit RS-422A / RS-485 communication active, no errors.
Green Not lit No RS-422A / RS-485 network errors present. The PRT1-SCU11 is
exchanging data with all configured devices.
Lit A failure occurred in the RS-422A / RS-485 network communication.
Green Not lit The PRT1-SCU11 is not in Data_Exchange with the PROFIBUS DP
master. Flashing Auxiliary port ready, PROFIBUS DP interface is not active. Lit The PRT1-SCU11 is in Data_Exchange with the PROFIBUS DP mas-
ter.
Green Not lit No PROFIBUS DP communication errors, Set_Prm and Chk_Cfg mes-
sages have been accepted. Data_Exchange in progress. Flashing Either the Set_Prm or the Chk_Cfg message has been rejected by the
PRT1-SCU11. The Unit is not in Data Exchange with the PROFIBUS
DP master. Lit All communication with the PROFIBUS DP master is lost. The PRT1-
SCU11 is awaiting a new Set_Prm message.
Section 2-1

2-1-3 Switch Settings

Node address Two rotary switches on the front of the PRT1-SCU11, marked Address x10
ADDRES
23
1
4
0
5
6789
x 10
23
1
4
0
5
6789
x 1
1,2,3...
and x1, are provided to set the PROFIBUS DP device address of the Unit. The address can be set in the range of 00 through 99. The device address on the Unit must be the same as the address used in the master’s configuration.
The device address is used to identify individual slave devices on the PROFI­BUS DP network. The device address must be unique for each unit. Selecting a non-unique address for a unit will prevent the PROFIBUS DP network from starting or operating correctly.
In order to set the device address, perform the following steps.
1. Turn OFF the power supply before setting the device address.
2. Set the switch to the (new) device address. Use a small screwdriver to make the setting, taking care not to damage the rotary switch. The node address is factory-set to 0.
3. Turn ON the power again.
19
Page 35
Unit Components
Section 2-1
Note Always turn OFF the power to the Unit before changing the device address
setting. The Unit only reads the address setting during the initialization follow­ing a power-up, i.e. any changes after power up will have no effect.
Baud rate setting In order to select the baud rate used for communication over the RS-422A/
RS-485 network, two DIP-switches are available. Baud rate switches are part of the DIP-switch bank of 4 switches on the front-case of the Unit. Switch 1 and 2 are used to select the baud rate to be used for communication over the RS-422A / RS-485 network. The possible combinations are summarized below.
Communication Format Selection
DIP switches
PRT1-SCU11
1234
23
1
0
9
23
1
DIP-
Switch 1
ON
RUN
ERR
4
COMM
5
6
78
BF
x10
x1
4
FCOM
OFF OFF 9600 (default) OFF ON 19200 ON OFF 38400 ON ON Reserved for future use
DIP-
Switch 2
Baud rate
(bits/sec.)
Note The two DIP-switches for the baud rate are only read during power-up/restart
of the PRT1-SCU11. Changing them during operation has no effect.
DIP-Switch 3 allows the user to select the communication protocol on the RS­422A / RS-485 network, to be either Memobus or one of the other protocols.
DIP-
Switch 3
OFF Communication protocol on RS-422A / RS-485 is
• Compoway-F
• Host Link
•K-Format Note Selection of the protocol is made through I/O module selection in
the PROFIBUS Master configuration.
Note The communication format used is 7 data bits, 2 stop bits, 1 even
parity bit.
ON Communication protocol on RS-422A / RS-485 is Memobus.
Note The communication format used is 8 data bits, 1 stop bit, 1 even
parity bit.
Description
Note The communication format selection must be set prior to power-up. Changes
made during operation have no effect.
Auxiliary Port Selection DIP-Switch 4 allows the user to enable or disable the use of the RS-232C
Port, behind the cover next to the DIP-switches.
DIP-
Switch 4
OFF PROFIBUS to Compoway-F and Host Link is active. The RS-232C Auxil-
iary Port is inactive. Communication from PROFIBUS is rerouted to the RS-485/RS-422A
communication port.
ON PROFIBUS to Compoway-F and Host Link is inactive. The RS-232C Aux-
iliary Port is active. Communication from the Auxiliary Port is rerouted to the RS-485/RS-
422A communication port.
Description
Note DIP-Switch 4 can be changed during operation. The selected mode is
reflected through the LED Indicators.
20
Page 36
Unit Components
Section 2-1
Peripheral setting For the physical layer settings on the RS-422A / RS-485 network port, two
switches are provided on the front-case of the Unit, located close to the RS­422A / RS-485 network connector.
NODE ADDRESS
PERIPHERAL
24 Vdc
ON
1
RS-422A / RS485 switch
2
Termination switch
Switch 1 defines whether to use RS-422A or RS-485 as the physical layer on the RS-422A / RS-485 network.
Switch 1 Description
OFF RS-422A ON RS-485
Switch 2 enables or disables the termination resistor on the RS-422A / RS­485 receiver channel.
Switch 2 Description
OFF 220 Ohm Termination resistor disabled. ON 220 Ohm Termination resistor enabled.
The two switches are independent of the selected protocol. They can be changed during operation and take effect immediately.
Note 1. It is recommended to switch the power off before changing switches.
2. If the wrong combination is selected for this PRT1-SCU11 (e.g. Host Link and RS-485 or Compoway-F and RS-422A), the communication between the PRT1-SCU11 and the connected devices may not work. The Unit has no direct way of detecting this, apart from a possible time-out.

2-1-4 PROFIBUS Connector

The PROFIBUS connector on the font of the Unit is a 9-pin female sub-D con­nector, as recommended by the PROFIBUS standard EN50170.
Pin No. Signal Description
9
6
5
1
1 Shield Shield/protective ground 2-­3 B-line Receive/Transmit data - plus (B wire) 4 RTS Control signal for repeaters (direction control) (TTL) 5 DGND Data ground (reference potential for VP) 6 VP Supply voltage of the terminator resistance (5 Vdc) 7-­8 A-line Receive/Transmit data - minus (A wire) 9--
The signal RTS (TTL signal) is for the direction control of repeaters, which do not have a self-controlling capability.
21
Page 37
Unit Components
The signals DGND and VP are used to power the bus terminator located in the cable connector.
Note 1. The orientation of the sub-D connector allows the use of PROFIBUS con-
nectors with a 90° angle cable outlet, e.g ERNI, Delconec and Phoenix.
2. The 9-pin sub-D connector uses #4/40 UNC thread for mechanical fixation of the cable connector. Make sure that if non-standard PROFIBUS connec­tors are used, the same thread is used on the cable connector.
3. PROFIBUS DP Baud rate setting is accomplished through automatic de­tection, all the defined PROFIBUS DP baud rate values are supported.

2-1-5 RS-422A / RS-485 Connector

The RS-422A / RS-485 port is a dedicated RS-422A / RS-485 compliant inter­face, which is galvanically isolated. The PRT1-SCU11 has a switch on the front case, allowing the user to select either the RS-422A or the RS-485 phys­ical layer. The Unit also provides a switch to turn a 220 Ohm termination resis­tor ON or OFF The termination resistor is placed inside the Unit and between the two receiver lines of either RS-422A or RS-485.
Section 2-1
R­R+
FG
S-
S+
Pin No. Description
RS-422A (Switch1 OFF) RS-485 (Switch 1 ON)
R- RD- Receiver line A line Transmit/Receive line R+ RD+ Receiver line B line Transmit/Receive line
FG Frame Ground Frame Ground
S- SD- Transmission line A line Transmit/Receive line
S+ SD+ Transmission line B line Transmit/Receive line
Note In case Switch 1 is set to ON and RS-485 is selected, the A and B lines are
doubled on the S-/S+ connector pins, i.e. the signal on R- is the same signal as on S- and the signal on R+ is the same signal as on S+.
Address setting The communication through the RS-422A / RS-485 interface does not require
a separate address setting feature. All connected devices must have addresses selected in the range of 1 through 15. The address set on the device must match the slot number of the selected PROFIBUS I/O-module. Free Communication Blocks carry their own address as part of the message itself.
The default communication format used on the RS-422A / RS-485 interface depends on whether Memobus or one of the other protocols will be used, i.e. it depends on the setting of DIP-switch 3. The table below lists the default communication settings used.
Format Memobus
(DIP-Switch 3 ON)
Data length 8 bits 7 bits
Stop bit length 1 bits 2 bits
Error detection 1 bit, even parity 1 bit, even parity
Compoway-F / Host Link / K-Format
(DIP-switch 3 OFF)
22
Page 38
Installing the PRT1-SCU11 PROFIBUS DP Gateway
Section 2-2

2-2 Installing the PRT1-SCU11 PROFIBUS DP Gateway

2-2-1 Handling Precautions

When installing the PROFIBUS DP Gateway, observe the following handling precautions
• Always turn OFF the power supply to the Unit before mounting or dis­mounting the Unit or connecting or disconnecting cables.
• Provide separate conduits or ducts for the I/O lines to prevent noise from high-tension lines or power lines.
• Prevent foreign matters to enter the Unit when wiring. Failure to do so, may result in malfunction if foreign matter enters the Unit.

2-2-2 Mounting the PRT1-SCU11

The PRT1-SCU11 can be mounted directly on a DIN-rail.
Mounting Procedure Mount the PRT1-SCU11 to the DIN-rail using the following procedure.
!Caution
1,2,3...
Always turn OFF the power supply to the Unit before mounting or dismounting the Unit or connecting or disconnecting cables.
1. Pull the hook down on the bottom.
2. Latch the top hook onto the track
3. Push the Unit until the hook locks onto the track.
4. Push the hook back up to lock the Unit in place.
2) Insert onto track.
3) Push in on the Unit.
1) Pull down.
4) Lock

2-2-3 Wiring the Power Terminals

• Supply power to the Unit using the 2 pin power connector provided with the Unit.
• When wiring the power, observe the required polarity. Failure to do so can damage the Unit.
• Use a Phillips screw driver to tighten the connector screw, using a torque value between 0.25 and 0.3 N·m.
23
Page 39
Wiring the RS-422A / RS-485 Devices

2-3 Wiring the RS-422A / RS-485 Devices

2-3-1 Precautions When Wiring

• Always switch off the power to the Unit and to the RS-422A / RS-854 devices, before wiring.
• Make sure that no foreign objects enter the Unit when wiring. Failure to do so, may damage the Unit when power is applied.
• Use a Phillips screw driver to secure the network connector to the Unit after setting up the RS-422A / RS-485 network. Tighten the screws to a torque of 0.25 to 0.3 Nm.

2-3-2 2-Wire and 4-Wire Connections

The transmission circuits for 2-wire and 4-wire connections are different, as shown in the following diagram.
Section 2-3
Example of 4-Wire Connections
2/4-wire switch
PRT1-SCU11
R88A­MCW151-E
R88A­MCW151-E
Example of 2-Wire Connections
2/4-wire switch
E5ZNE5_N
Not connected
PRT1-SCU11
Note 1. Use a 2-wire transmission circuit to connect E5_N, E5ZN and E5_R Tem-
perature Controllers to the PRT1-SCU11. Use a 4-wire transmission circuit to connect the R88A-MCW151-E Motion Control option Board to the PRT1-SCU11. Use the same transmission circuit (2-wire or 4-wire) for all nodes.
2. Do not use 4-wire connections when the 2/4-wire switch on the PRT1­SCU11 is set to 2-wire.
3. Do not intermix Temperature Controllers, R88A-MCW151-E devices and F7-Inverter devices on one and the same transmission circuit.
4. In case the PRT1-SCU11 is on one of the ends of the transmission net­work, switch on the Termination Resistor - by setting Switch 2 to ON.

2-3-3 Connection for E5_N Compoway-F Communications

The E5AN / E5CN / E5EN / E5GN Temperature Controllers all use Compo­way-F communications over 2-wire RS-485.
• The RS-485 connection can be either one-to-one or one-to-N. Up to 15
E5_N units can be connected in a one-to-N system.
• The total cable length is 500 m max.
• Use a shielded twisted-pair cable with wires of a thickness of AWG24
2
(0.205 mm
24
) to AWG14 (2.081 mm2)
Page 40
Wiring the RS-422A / RS-485 Devices
The figure below shows the connection between one PRT1-SCU11 and 1 to 15 E5_N Temperature Controller units. Refer to the E5AN / E5CN / E5EN and E5GN User Manuals for more information on Wiring.
PRT1-SCU11 E5_N side
RS-485 RS-485
FG
R-
R+
Pin No.
AN/EN/CN GN
12 11
6 5
Section 2-3
Description
S- / R
S+ / R+
Shield
Shield
Terminator
220
(1/2 W)
E5_N side RS-485
End Node
AN/EN/CN GN
12 11
Use a 220 (1/2 W) terminator.
This way of communication also allows the use of other stand-alone Compo­way-F instruments, for example a K3GN Digital Panel Meter.
Note The E5AN / E5CN / E5EN and E5GN support baud rates of 9.6 and 19.2
kbits/sec. Ensure that the PRT1-SCU11 baud rate setting (DIP-switch 1 and
2) is set to the correct setting.

2-3-4 Connection for E5ZN Compoway-F Communications

The E5ZN Temperature Controllers use Compoway-F communications over 2­wire RS-485. Multiple E5ZN units can be connected together, using one RS­485 Terminal. The RS-485 connection is extended through the E5ZN sockets. However, these units all have unique RS-485 addresses.
The RS-485 connection can be either one-to-one or one-to-N. Up to 15 E5ZN units can be connected in a one-to-N system.
The figure below shows the connection between one PRT1-SCU11 and 1 to 15 E5ZN Temperature Controller units. Refer to the E5ZN User Manuals for more information on Wiring.
Pin No.
Description
6 5
S- / R
S+ / R+
Note The E5ZN supports baud rates of 9.6, 19.2 and 38.4 kbits/sec. Ensure that
the PRT1-SCU11 baud rate setting (DIP-switch 1 and 2) is set to the correct setting.
25
Page 41
Wiring the RS-422A / RS-485 Devices
PRT1-SCU11
RS-485
FG
R-
R+
Shield
Section 2-3
Terminator 220 (1/2 W)
(B)
23 24
(A)
E5ZN
(No.0,1,2)
(B)
23
(A)
24
E5ZN
(No.3,4,5)
(B)
23
(A)
24
E5ZN
(No.13,14,15)
Terminator 220 (1/2 W)

2-3-5 Connection for E5AR/E5ER Compoway-F Communications

The E5AR/E5ER Temperature Controllers all use Compoway-F communica­tions over 2-wire RS-485.
• The RS-485 connection can be either one-to-one or one-to-N. Up to 15
Temperature Controller units can be connected in a one-to-N system.
• The total cable length is 500 m max.
The figure below shows the connection between one PRT1-SCU11 and 1 to 15 E5AR/E5ER Temperature Controller Units. Refer to the E5AR/E5ER User Manuals for more information on Wiring.
PRT1-SCU11 E5ER / E5AR side
RS-485 RS-485
FG
R-
R+
Pin No.
E5ER E5AR
1 2
1 2
Description
R-
R+
26
Shield
Shield
Terminator
220
(1/2 W)
E5ER / E5AR side RS-485 End Node
Pin No.
E5ER E5AR
2
2
1
1
Use a 220 (1/2 W) terminator.
Description
R-
R+
Note The E5AR/E5ER supports baud rates of 9.6, 19.2 and 38.4 kbits/sec. Ensure
that the PRT1-SCU11 baud rate setting (DIP-switch 1 and 2) is set to the cor­rect setting.
Page 42
Wiring the RS-422A / RS-485 Devices
Section 2-3

2-3-6 Connection for R88A-MCW151-E Host Link Communications

The R88A-MCW151-E uses Host link communications over 4-wire RS-422A. The figure below shows the connection between one PRT1-SCU11 and 1 to 15 R88A-MCW151-E units.
PRT1-SCU11
RS­422A Inter­face
Phoenix Connector Switch SW1: OFF
Switch SW2: ON
Signal Pin
R- 1 R+ 2 FG 3 S- 4 S+ 5
R88A-MCW151-E unit
Pin Signal RS-
1 RD­2 RD+
422A Inter­face
3FG 4SD­5SD+
DIP switch SW2 Pin 1 OFF Pin 2 OFF Pin 3 OFF
RS-422A Port Connector
R88A-MCW151-E unit
Pin Signal RS-
422A
1 RD­2 RD+
Inter­face
3FG 4SD­5SD+
DIP switch SW2 Pin 1 OFF Pin 2 OFF Pin 3 ON
RS-422A Port Connector
Note 1. If the PRT1-SCU11 is connected on one end of the transmission circuit,
the termination resistor must be enabled on the Unit, by setting Switch 2 to ON.
2. The R88A-MCW151-E connected at one end of the transmission circuit, must also have its termination resistor enabled, by setting Pin 3 of DIP­switch SW2 to ON.
3. The R88A-MCW151-E supports baud rates of 9.6, 19.2 and 38.4 kbits/sec. Ensure that the PRT1-SCU11 baud rate setting (DIP-switch 1 and 2) is set to the correct setting.
27
Page 43
Wiring the RS-422A / RS-485 Devices

2-3-7 Connection for E5AK/E5EK K-Format Communication

The E5AK/E5EK Intelligent Digital Controllers use the K-Format communica­tions over either 4-wire RS-422A or 2-wire RS-485. Both are supported, through dedicated communication option units. Refer to the E5AK/E5EK User Manuals for more information on these dedicated communication units.
Section 2-3
RS-422A Connection to E5AK/E5EK
The RS-422A connection can be either one-to-one or one-to-N. Up to 15 E5AK/E5EK units can be connected in a one-to-N system.
The figure below shows the connection between one PRT1-SCU11 and 1 to 15 E5AK/E5EK Intelligent Digital Controller units. The table below shows the pin numbers used on the E5AK and E5EK units for connection of communica­tion signals. Refer to the E5AK/E5EK User Manuals for more information on Wiring.
PRT1-SCU11
RS-422 Interface
RS-422
R­R+
S­S+ FG
E5AK / E5EK (1)
(See table below)
RS-422
SDB SDA RDB RDA
Terminator
220 Ω, 1/2W
E5AK / E5EK (15)
(See table below)
RS-422
SDB SDA RDB RDA
RS-485 Connection to E5AK/E5EK
RS-422A Signal E5AK Pin number E5EK Pin number
SDB (Transmission line) 31 21 SDA (Transmission line) 32 22
RDB (Receiver line) 20 20 RDA (Receiver line) 19 19
The E5AK/E5EK Intelligent Digital Controllers can also communicate over RS-485, using the dedicated communication option for RS-485. Refer to the E5AK/E5EK User Manuals for more information on the RS-485 dedicated communication unit.
The RS-485 connection can be either one-to-one or one-to-N. Up to 15 E5AK/ E5EK units can be connected in a one-to-N system.
The figure below shows the connection between one PRT1-SCU11 and 1 to 15 E5AK/E5EK Intelligent Digital Controller units. Refer to the E5AK/E5EK User Manuals for more information on Wiring
28
Page 44
Wiring the RS-422A / RS-485 Devices
PRT1-SCU11
RS-485 Interface
RS-485
R-
R+
S­S+ FG
E5AK / E5EK (1)
(See table below)
RS-485
Terminator
220 , 1/2W
Section 2-3
E5AK / E5EK (15) (See table below)
RS-485
A (2) B (2) A (1) B (1)
RS-485 Signal E5AK Pin number E5EK Pin number
A (2) 32 22 B (2) 31 21 A (1) 19 19 B (1) 20 20
Note The E5AK/E5EK supports baud rates of 9.6, and 19.2 kbits/sec. Ensure that
the PRT1-SCU11 baud rate setting (DIP-switch 1 and 2) is set correctly.

2-3-8 Connection for F7 Inverter Memobus Communication

The F7 Inverter use the Memobus communications over either 4-wire RS­422A or 2-wire RS-485.
RS-422A Connection to F7 Inverter
The RS-422A connection can be either one-to-one or one-to-N. Up to 15 F7 Inverter units can be connected in a one-to-N system.
The figure below shows the connection between one PRT1-SCU11 and 1 to 15 F7 Inverter units. Refer to the F7 Inverter User Manual for more information on Wiring.
A (2) B (2) A (1) B (1)
PRT1-SCU11
RS-422 Interface
RS-422
R-
R+
S­S+ FG
F7 Inverter (1)
RS-422
S­S+ R­R+
Terminator
220 Ω, 1/2W
F7 Inverter (15)
RS-422
S­S+ R­R+
29
Page 45
Initial Setup Procedure
Section 2-4
RS-485 Connection to F7 Inverter
PRT1-SCU11
RS-485 Interface
The F7 Inverter can also communicate over RS-485. The RS-485 connection can be either one-to-one or one-to-N. Up to 15 F7 Inverter units can be con­nected in a one-to-N system.
The figure below shows the connection between one PRT1-SCU11 and 1 to 15 F7 Inverter units. Refer to the F7 Inverter User Manuals for more informa­tion on Wiring.
RS-485
R-
R+
S­S+ FG
F7 Inverter (1)
RS-485
S­S+ R­R+
F7 Inverter (15)
RS-485
S-
S+
R-
R+

2-4 Initial Setup Procedure

After mounting the PRT1-SCU11, the following Initial Setup Procedure must be applied to allow the Unit to start up properly and to be configured for oper­ation.
• A unique PROFIBUS node address must be selected, before the unit’s power supply is turned on, see section
• Select the required baud rate to be used on the RS-422A / RS-485 net­work, using DIP-switches 1 and 2. Select the protocol to be used, i.e. Memobus or one of the other protocols, using DIP-switch 3. Disable the Auxiliary port, using DIP-switch 4.
• Select the required physical layer, either RS-422A or RS-485, using switch number 1, directly over the RS-422A / RS-485 connector.
• Setup the PROFIBUS network, see section
Network
ration tool on the Personal Computer, and download the configuration to the master unit.
• Refer to the manuals of the connected devices, on how to set up the devices.
2-4-1 Selecting a Node Address
1,2,3...
1. Make sure that the power supply is turned OFF before setting the node ad­dress.
2. Set the switch to the desired node address, using a small screwdriver, and taking care not to damage the rotary switch. The default node address is
0. Make sure that the node address is unique on the PROFIBUS DP net­work, i.e. there must be no other unit with the same node address.
3. Turn ON the power supply of the Unit.
, configure the PROFIBUS Master unit using the master configu-

2-4-1 Selecting a Node Address

2-5 Setting up a PROFIBUS
.
30
Page 46
Setting up a PROFIBUS Network
Section 2-5

2-5 Setting up a PROFIBUS Network

2-5-1 Network Structure

Communication Medium The PROFIBUS standard defines the use of EIA RS-485 as the main commu-
nication transport medium. The PRT1-SCU11 is designed to interface directly to this type of medium. This section will discuss the setup of networks based on this medium.
Note The other communication medium specified for PROFIBUS is optical fibre.
The PRT1-SCU11 does not provide a direct interface to this type of medium. However, by using third party couplers an interface between EIA RS-485 and optical fibre networks can be made.
Linear Bus Topology PROFIBUS DP defines the use of the Linear Bus Network Topology. The Bus
must be terminated at both ends, and must not contain network branches. The total cable length of the bus depends on the cable and the selected baud rate. Also, RS-485 specifies a maximum of up to 32 devices - master and slave devices - per line segment. If more than 32 devices are to be connected, or if the total length of the segment must be extended beyond its maximum, repeaters must be used to link the separate segments.
Note Repeaters are devices which connect two segments. They do not have a
device address of their own, but they do count in the total number of devices in a segment.
Repeaters A maximum of up to three repeaters between two devices in a network can be
used, i.e. a network can consist of up to 4 segments. The maximum number of PROFIBUS devices in such a network is then 122. The figure below shows an example of a two-segment network.
OMRON SYSMAC CS1G PROGRAMMABLE CONTROLLER
Station 1
Termination
Station 2 Station 3 Station 31
Termination
Station 63 Station 33 Station 32
Termination
Repeater
Termination
Tree Topology The use of repeaters allows the extension of three or more Linear Bus seg-
ments into a Tree topology. In a tree topology more than three repeaters are allowed, provided that there are no more than three repeaters between any
31
Page 47
Setting up a PROFIBUS Network
two devices in the network. The following figure presents an example of a net­work with more than three segments and repeaters.
M / S
Segment 1
Max. 31 stations
Section 2-5
Segment 2
Max. 31 stations
M / S
Segment 3
Max. 28 stations
Segment 5
R
M / S
R
M / S
Segment 4
Max. 31 stations
M / S
R
R
Max. 30 stations
M / S
Master or slave station
R
Repeater
Termination
Max. total number of stations = 126
R
Segment 6
Max. 31 stations
M / S
Cable Type The PROFIBUS standard EN 50170 specifies Type A shielded, twisted- pair
cable as the recommended cable type for use in an RS-485 based PROFI­BUS network. This cable type has the following characteristics:
Characteristic Value
Impedance 135 - 165 ohms Capacitance per unit length < 30 pF/m Loop resistance 110 ohms/km Core diameter 0.64 mm Core cross section
0.34 mm
2
Maximum PROFIBUS Cable Length
32
Note The PROFIBUS standard EN 50170 also specifies a Type B cable with slightly
different cable characteristics. This Type B cable is no longer recommended for use.
The transmission speed defines the maximum advised cable distance or cable segment in metres before the use of a repeater is recommended. The cable lengths specified in the following table are based on PROFIBUS type A cable.
Baud rate
(kbit/s)
9.6 1200 500 400
19.2 1200 1500 200
45.45 1200 3000 100
93.75 1200 6000 100
187.5 1000 12000 100
Distance/segment
(m)
Baud rate
(kbit/s)
Distance/segment
(m)
Page 48
Setting up a PROFIBUS Network
k
A
Section 2-5
Note If the network must be extended beyond the range of the advised cable
length, the use of a fibre optic segment to cross the larger distance should be considered.
Stub Lines Passive Stub lines (branches from the main line) should be avoided for data
transmission speeds of more than 500 kbit/s. Except at end devices with ter­mination, it is recommended to always use plug connectors that permit two data cables to be connected directly to the plug. This method allows the bus connector to be plugged and unplugged at all times without interrupting data communication between other devices.

2-5-2 Bus Termination

Termination Resistors In order to minimize cable reflections and ensure a defined signal level on the
data lines, the data transfer cable must be terminated at both ends with a ter­minating resistor combination. The bus termination diagram is shown on the left.
The bus terminator connects the two data lines via a 220 ohm resistor which, in turn, is connected to VP 5Vdc and DGND via two 390 ohm resistors. Pow­ering the terminator resistor via VP 5V and DGND ensures a defined idle state potential on the data lines.
To ensure the correct functioning up to the highest baud rate, the bus cable must be terminated at both its ends.
A missing bus termination can cause errors during data transfer. Problems can also arise if too many bus terminators are fitted, since each bus termina­tor represents an electrical load and reduces the signal levels and thus the signal-to-noise ratio. Too many or missing bus terminators can also cause intermittent data transfer errors, particularly if the bus segment is operated close to the specified limits for maximum numbers of devices, maximum bus segment length and maximum data transfer rate.
B-Line
A-Line
DGND
VP
390 Ohm
220 Ohm
390 Ohm
Networ
Inductors In addition to the bus termination, additional precautions must be taken to
ensure proper operation at high baud rates, i.e. baud rates of 500 kbit/s and
B-Line
110 mH
Network
-Line 110 mH
higher. Due to the capacitive load of the device and the resulting cable reflec­tions, bus connectors must be provided with built-in series inductors, of 110 mH each, as shown in the figure on the left.
Installing the inductors applies to all devices on the network, and not only to the devices at both ends of the bus cable.
33
Page 49
Setting up a PROFIBUS Network
Section 2-5

2-5-3 PROFIBUS Cable Connector

Bus Cable Connector The plug connector to be used on the PRT1-SCU11 is a 9-pin male sub-D
type, preferably encased in metal and having a facility to connect the shield of the cable to the case or to pin 1. The cable should be connected to the receive / transmit lines, pin 3 (B-line) and pin 8 (A-line). The use of special PROFIBUS DP cable connectors, which are available from several manufacturers, is highly recommended. Various models are widely available, with or without the bus termination and inductors built-in. If provided in the connector, the Bus termination can often be enabled or disabled through a switch on the connector. The special PROFIBUS DP cable connectors often provide a convenient way of connecting the cables. The figure on the left, provides an example of such a bus cable connector. A standard 9-pin sub-D plug can only be used if the PRT1-SCU11 is not at the start or the end of a bus segment, or on a stub line at a baud rate of 500 kbit/ s or less.
To next station
From previous station
The two PROFIBUS data lines are designated A and B. There are no regula­tions on which cable core color should be connected to which of the two data terminals on each PROFIBUS device; the sole requirement is to ensure that the same core color is connected to the same terminal (A or B) for all devices throughout the entire system (across all devices and bus segments). The PROFIBUS Organization recommends the following rule for data line color codes: PROFIBUS cables in general will use the colors red and green for the data lines, with the following assignment:
Data cable wire A - green Data cable wire B - red
This rule applies to both the incoming and the outgoing data lines.

2-5-4 Shielding Precautions

Cable Shield Connection To ensure electro-magnetic compatibility (EMC), the shield of the cable should
be connected to the metal case of the plug connector.
Inside cabinet
Ground Rail
Outside cabinet
When entering the control cabinet in which the PRT1-SCU11 Unit is installed, the bus cable shield should be brought into physical contact with a grounding rail using a grounding clamp or similar device. The cable shield should con­tinue in the cabinet right up to the PROFIBUS device. Ensure that the Unit and the control cabinet in which it is mounted have the same ground potential by providing a large-area metallic contact to ground, e.g. galvanized steel to ensure a good electrical connection. Grounding rails should not be attached to painted surfaces. For further information regarding PROFIBUS network installation, please refer to “Installation Guideline for PROFIBUS DP/FMS” (PNO Order No. 2.112), which is available at every regional PROFIBUS Organization. The information covers:
• Commissioning of PROFIBUS equipment.
• Testing the PROFIBUS cable and bus connectors.
• Determining loop resistance.
• Testing for correct bus termination.
• Determining the segment length and cable route.
• Other test methods.
• Example of an equipment report in the PROFIBUS guideline.
34
Page 50
Configuring the PROFIBUS DP network
Section 2-6

2-6 Configuring the PROFIBUS DP network

Defining the Configuration After making the physical connections of the network, the PROFIBUS Master
unit has to be configured using the PROFIBUS Master’s configuration tool. OMRON provides a Personal Computer based configuration program, called CX-Profibus (only required for OMRON masters), as well as the required DTM’s for this purpose. It must be used to:
• Install new GSD-file
• Define the master(s).
• Assign slaves to their respective master(s).
• Assign slaves to groups for broadcast/multicast messages.
• Enter bus parameters, e.g. baud rate, target rotation time etc.
• Enable / Disable watchdog.
• Adjust watchdog settings
Refer to CS/CJ Series PROFIBUS DP Master Units Operation Manual
@
(W409-E2-
) for more information on CX-Profibus.
Downloading the Configuration
The configuration must be downloaded to the Master unit after configuring it at the Personal Computer. This can be accomplished by either connecting the serial COM port of the Personal Computer to the CS1/CJ1 PLC with a serial interface cable, or use an Ethernet connection between the Personal Com­puter and the CS1/CJ1 PLC via an Ethernet unit.

2-6-1 Configuring the Slave Devices

After adding each of the slave DTM’s to the network, configurations have to be selected for each of them. Setting up a configuration involves
• Selecting the proper I/O modules I/O Modules represent either a fixed number of setpoint and process parameters for each connected RS-422A / RS-485 device or a fixed size I/O slot which can be used to send user defined protocol data. One type of I/O slot needs to be selected for each connected RS-422A / RS-485 device.
• Setting up the device parameters Depending on the I/O module, device settings can be made, which will be transferred to the RS-422A / RS-485 device through the PRT1-SCU11. The PRT1-SCU11 itself will validate the settings and reject the data in case of faulty parameters.
• Selecting the group assignment, which defines the group of slave devices each slave belongs to and to allow sending Global-Control commands to this particular group.
All these settings will be downloaded to the Master unit, which will send the data to the individual slave devices over the PROFIBUS network.
Note The available I/O Modules are discussed in
SECTION 3 Operation
.
35
Page 51
Configuring the PROFIBUS DP network

2-6-2 Defining the I/O Configuration

Section 2-6
Opening the DTM Configuration User Interface
Adding/Inserting I/O Modules
In order to define the I/O configuration, the DTM Configuration User Interface must be opened. The next example uses CX-Profibus to define, edit and download an I/O configuration.
The figure below, shows the DTM User Interface for the PRT1-SCU11 PROFI­BUS DP slave device. The DTM Configuration User Interface displays two lists.
• The Available Modules list, which contains the I/O modules the user can select.
• The Configured Modules list, which contains all the I/O modules selected by the user.
To select the I/O modules, perform one of the following procedures.
• Select the I/O module that needs to be added in the Available Modules list, and double-click it with the left mouse button. If more than one mod­ule must be added, repeat this step for the other modules.
• Select the I/O module that needs to be added in the Available Modules list, and press either the Insert or Append button.
36
Note 1. When pressing the Insert button, the selected I/O module will be inserted
above the selected module in the Configured Modules list.
2. The selected I/O modules are sent to the slave device, in the same se­quence as selected in the user interface. The sequence determines the target Temperature Controller / R88A-MCW151-E for the I/O data. For ex­ample, the I/O data of the first selected Fixed Communication Block will be sent to the first temperature Controller
3. A mandatory I/O module sequence is sometimes indicated in the GSD file, by using non-PROFIBUS standard GSD file keywords (i.e. only interpreted
Page 52
Configuring the PROFIBUS DP network
by a specific configurator). The Generic Slave DTM does not check such keywords. In this case, refer to the manual of the specific device for details.
4. Also in this window are the maximum values, which can be set, and the to­tals of I/O data that actually have been set. If - while selecting I/O modules
- one of the maximum values is exceeded, a warning message will be dis­played.
Removing I/O Modules To remove I/O modules from the Configured Modules list, perform one of the
following procedures.
• Select the I/O module that needs to be removed from the Configured Modules list, and double-click it with the left mouse button. If more than one module must be added, repeat this step for the other modules.
• Select the I/O module that needs to be removed from the Configured Modules list, and press the Remove button.
Example For the PRT1-SCU11, the I/O modules for two E5ZN devices, and two E5_N
devices have been selected, see figure above. The E5ZN devices have Com­poway-F addresses 1 and 2, the E5_N devices have Compoway-F addresses 3 and 5. Address 4 is not used in this example.
Watchdog Settings Apart from the I/O module selection, the Configuration tab also contains the
settings for two other parameters.
1. Enable Watchdog Control This parameter will enable/disable the monitoring of the Master-Slave communication in the slave device. If enabled, the slave will stop I/O data exchange with the Master, if the Master has not sent any request message to the slave, within the configured Watchdog time. Furthermore, the slave will
• switch its outputs to a known state.
• signal its change of state in a diagnostics message, the next time the Master addresses the slave.
• request re-parameterization from the Master, before resuming I/O data exchange.
If disabled, the slave will remain in data exchange, even if the Master is not communicating, thus maintaining its outputs in the latest known state, based on the last I/O data exchange message.
2. Watchdog Interval This value is the watchdog time-out related to the Master-Slave communi­cation time out.
Section 2-6
Note Enabling the Watchdog Control is highly recommended for safe operation of
the network.
!Caution
In the current version of CX-Profibus, the watchdog value for each of the slave devices is overruled by the value determined by the Master DTM. Therefore, changing the value in the Generic Slave DTM has no effect.
37
Page 53
Configuring the PROFIBUS DP network
Section 2-6

2-6-3 Setting Parameters

The parameters are sent by the Master unit to the slave device prior to estab­lishing I/O data exchange. The slave device will reject incorrect parameters and not establish I/O data exchange, unless the parameters are changed.
In general there will be two types of parameters.
• Common Parameters The PRT1-SCU11 defines one Common parameter, which applies to the unit itself. This parameter - Fail Safe support - defines whether or not the unit will accept empty output messages or messages containing all zeros in case the PROFIBUS DP Master switches to Clear mode. Clear mode is often the indication of a failure on the network.
• Module Parameters Modular Parameters are parameters which are associated with the I/O modules selected. In the case of the PRT1-SCU11 these parameters define behaviour with respect to the devices attached to the PRT1­SCU11. They are discussed in the next section.
Example The Parameter tab of the PRT1-SCU11 is shown in the figure below. It lists
the parameters for the selected temperature controller the E5ZN-Extended 2 Channel 11WI/3WO. The parameter captions are listed in the left column and the options can be set in the right column. In order to change settings, double­click the required parameter row with the left mouse button. Depending on the parameter type, either a drop-down list will become available for selection or a value can be entered.
38
Page 54
SECTION 3
Operation
This section describes how to operate the PRT1-SCU11 in a network. It will discuss setting up a network, configuring all the connected devices and starting the network. Furthermore, it provides information the I/O data exchange performance and it also provides information on how to monitor a network, using the unit and monitoring the status of the Temperature Controller by using CX-Thermo (not shipped with the PRT1-SCU11).
3-1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
3-2 PROFIBUS Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
3-3 Compoway-F Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
3-3-1 Fixed Communication Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
3-3-2 Special Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
3-3-3 Compoway-F Parameter Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
3-3-4 Free Communication Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
3-4 K-Format Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
3-4-1 Fixed Communication Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
3-4-2 Operation Execute . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
3-4-3 K-Format Parameter Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
3-4-4 Free Communication Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
3-5 Host Link Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
3-6 Memobus Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
3-6-1 Fixed / Flexible Communication Blocks . . . . . . . . . . . . . . . . . . . . . 51
3-6-2 Memobus Parameter Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
3-7 PROFIBUS Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
3-8 Auxiliary RS-232C interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
39
Page 55
Introduction

3-1 Introduction

This section discusses the operational aspects of using the PRT1-SCU11 and the configuration software. The section has been setup, to follow the general process flow of setting up and configuring a network, downloading the config­uration, and operating the PROFIBUS network, the Compoway-F, K-Format, Host Link or Memobus network.
The PROFIBUS Master can communicate with the PRT1-SCU11 using fixed communication block and/or Free Communication blocks.
In case Error messages are displayed, while using CX-Profibus, refer to the appropriate manual for more information on errors.
Note 1. The maximum number of devices is 15.
2. The maximum of modules is 18. This number consists of 15 fixed commu­nication blocks, 1 write, 1 read and 1 operation Free Communication block.

3-2 PROFIBUS Communication

As mentioned in the previous section there are two ways of PROFIBUS com­munication. Communication with fixed communication blocks and Free Com­munication blocks.
Section 3-1
Fixed Communication Blocks
Example For an E5ZN connected to the PRT1-SCU11 a 2-channel basic fixed I/O block
Free Communication Blocks
Flexible Communication Blocks
Maximum PRT1-SCU11 PROFIBUS DP I/O Size
Fixed communication blocks are pre-defined blocks of data to be read/written from/to a device. Fixed communication blocks can not be changed. The most common data can be read/written using fixed communication blocks.
defines the data transfer of 1 Setpoint Value for each channel and 1 Process Value for each channel between the PROFIBUS Master unit and the E5ZN through the PRT1-SCU11.
Free communication blocks are sent directly to the device connected to the PRT1-SCU11. The PRT1-SCU11 does not interfere with the data contents of the block. This allows Free Communication blocks to be used to access data in a device which can not be accessed through fixed communication blocks. Free Communication Blocks can be used for Compoway-F and the K-Format protocol.
Flexible communication blocks are defined for the Memobus protocol and are a mix between the fixed blocks and the Free Communication blocks. The flex­ible communication blocks will contain 3 input words and 3 output words, for each of which a target register in the Varispeed F7 Inverter can be defined.
The maximum amount of PROFIBUS data the PRT1-SCU11 can handle is 100 words input data and 100 words100 output data. If more capacity is needed an extra PRT1-SCU11 is required to access additional devices.
Note As per PROFIBUS DP definition the I/O data words are sent in Big Endian for-
mat, i.e. the high byte is sent first.
40
Page 56
Compoway-F Communication
Section 3-3

3-3 Compoway-F Communication

3-3-1 Fixed Communication Blocks

Fixed communication blocks are pre-defined blocks, which define specific groups of I/O data words. Each device has at least one Fixed communication block for specific status and control words. In the next table an overview of all devices and their communication blocks is listed. In addition to the Input and Output words, a number of I/O modules also provide Special Operations words, which can be used to change the control status of a Temperature Con-
troller, for example from STOP to RUN.
Compoway-F
Device
type
- Empty slot (No device) - - 0 0 N/A E5_R E5_R-Basic 1 channel SV channel 1 PV-channel 1 1 1 1
Module name Output words Input words Total
E5_R-Basic 2 channels SV channel 1
E5_R-Basic 4 channels SV channel 1
E5_R-Extended 1 channel SV channel 1
E5_R-Extended 2 channel SV channel 1
E5_R-Extended 4 chan­nels
SV channel 2
SV channel 2 SV channel 3 SV channel 4
Special operation (See Note)
SV channel 2 Special operation
(See Note)
SV channel 1 SV channel 2 SV channel 3 SV channel 4 Special operation
(See Note)
PV channel 1 PV channel 2
PV channel 1 PV channel 2 PV channel 3 PV channel 4
PV channel 1 MV1 channel 1 MV2 channel 1 Status high word channel 1 Status low word channel 1 Operation execute
PV channel 1 MV1 channel 1 MV2 channel 1 Status high word channel 1 Status low word channel 1 PV channel 2 MV1 channel 2 MV2 channel 2 Status high word channel 2 Status low word channel 2 Operation execute
PV channel 1 MV1 channel 1 MV2 channel 1 Status high word channel 1 Status low word channel 1 PV channel 2 MV1 channel 2 MV2 channel 2 Status high word channel 2 Status low word channel 2 PV channel 3 MV1 channel 3 MV2 channel 3 Status high word channel 3 Status low word channel 3 PV channel 4 MV1 channel 4 MV2 channel 4 Status high word channel 4 Status low word channel 4 Operation execute
output
words
Tota l input
words
22 2
44 4
26 1
311 2
521 4
Number of
channels
41
Page 57
Compoway-F Communication
Compoway-F
Device
type
E5ZN E5ZN-Basic 2 channels SV channel 1
E5_N E5_N-Basic 1 channel SV channel 1 SV channel 1 1 1 1
Module name Output words Input words Total
SV channel 2
E5ZN-Extended 2 chan­nels
E5_N-Extended 1 channel SV channel 1
SV channel 1 SV channel 2 Special operation
(See Note)
Special operation (See Note)
PV channel 1 PV channel 2
PV channel 1 MV1 channel 1 MV2 channel 1 Status high word channel Status low word channel PV channel 2 MV1 channel 2 MV2 channel 2 Status high word channel 2 Status low word channel 2 Operation execute
PV channel 1 MV1 channel 1 MV2 channel 1 Status high word channel 1 Status low word channel 1 Operation execute
output
words
22 2
311 2
26 1
Section 3-3
Tota l input
words
Number of
channels
Note The Special operation word is explained in the section below.

3-3-2 Special Operation

Command Word The Special Operation word format is shown in the figure below. It contains
the Command Code, and the Channel Number. The Command Code speci­fies the action to be performed, the Channel Number specifies channel to which the action will apply. Both the Command Code and Channel Number coding are listed in the table below.
Special Operation Word
1514131211109876543210
Command Code
Channel Number
Since the Command Word will be part of the cyclic data exchange, a mecha­nism in the PRT1-SCU11 is used to send this word to the targeted device only when needed. The PRT1-SCU11 will transfer the command word to the target device up on a change of one or more of the bits in the contents of the Com­mand Word.
Response Word Once the command has been sent, the response from the device is placed in
the PROFIBUS input Operation Execute word. The format of the response is shown in the figure below. the Operation Execute word contains the Com­mand Code, the Channel Number as well as an Error Code bit. If the Error bit (bit 4) is set, an error has occurred in the communication with the targeted device.
42
Page 58
Compoway-F Communication
Section 3-3
Operation Execute Word
1514131211109876543210
Command Code
Error
Channel Number
An overview of all the Command Codes, Channel Numbers and Error Codes is given in the table below.
Bit group
name
Command code
Channel numbers
Error code, one bit
Binary
Value
0000 Clear command 0001 Run 0010 Stop 0011 AT Cancel 0100 AT Execute 0101 Auto 0110 Manual 0111-1111 Reserved 000 Channel 1 001 Channel 2 010 Channel 3 011 Channel 4 100-110 Not supported 111 All channels 0No error 1Error
• Not supported command number
• Not supported channel number
• Command execution failed
• Communication with Temperature Controller fails
Value description
Handshaking In order to prevent an overflow of commands being sent to one or more
devices, the user must implement a simple handshaking mechanism in the PROFIBUS DP Master unit.
• When no command is to be sent to a device, set the Special Operation Word in the PROFIBUS DP Master to 0. The PRT1-SCU11 will respond by setting the Operation Execute word to 0.
• When a command must be sent to a device, set the Command Code and the Channel Number. For another Special Operation command to be sent, the user must first wait for the Operation Execute word to change to a non-zero value, indicating the completion of the first Special operation command.
43
Page 59
Compoway-F Communication

3-3-3 Compoway-F Parameter Settings

For the Fixed Communication blocks the user can define behaviour of the PRT1-SCU11 on the Compoway-F communication in case the PROFIBUS communication fails.
Section 3-3
PROFIBUS Communication Fails
In case the PROFIBUS communication fails, there are two options for the PRT1-SCU11 to handle this, as defined by the a user.
• The PRT1-SCU11 can send a stop command to one or more of the devices, causing the control cycle to stop.
• The Temperature Controller can Hold the last received Setpoint Value.
This behavior can be selected in CX-Profibus when configuring the PROFI­BUS DP Master unit, see the example in the figure below.
This setting can be defined for every individual Temperature Controller and will be sent to the PRT1-SCU11 as part of the PROFIBUS DP Set_Prm mes­sage.

3-3-4 Free Communication Blocks

With Free Communication blocks it is possible to read data, write data or send an operation instruction directly from or to any parameter in a Compoway-F device. With Free Communication blocks, however, the commands have to be assembled by the PROFIBUS Master system. The user also has to provide a simple handshaking mechanism to prevent too many commands being sent. The PRT1-SCU11 uses the contents of the Free Communication block to assemble a Compoway-F mini-FINS command, which is sent to the device.
The Free Communications blocks can be selected as I/O modules from the GSD file. Three Free Communication blocks are defined for Compoway-F and can be used to configure the PRT1-SCU11.
1. Read for reading one parameter defined in the device.
2. Write for writing one parameter defined in the device.
3. Operation for executing any operation defined in device.
Note The Free Communication blocks do not require the user to make parameter
settings.
44
Page 60
Compoway-F Communication
Device
type
E5_N, E5ZN, E5_R
Module name Output words Input words Total
Free comms Read 4 WI / 5 WO
Free comms Write 2 WI / 7 WO
Free comms Operation 2 WI / 3 WO
Section 3-3
In the next table an overview is presented on how the Free Communication blocks are composed for several different device types.
Compoway-F
output
words
Device address (1 word) Command data (4 words)
Device address (1 word) Command data (4 words) Write data (2 words)
Device address (1 word) Command data (2 words)
Response code (2 words) Read data (2 words)
Response code (2 words) 7 2
Response code (2 words) 3 2
54
A Free Communication block always contains a device address (one word with a value in the range between 0000 (hex) and 0063(hex)) and a mini FINS command. The length of the mini FINS command depends on the command type (operation, write or read) to be executed.
Total
input
words
Operation Mini FINS Command
The Operation mini FINS command type consists of a command code MRC/ SRC, followed by an instruction code, the value of this instruction code is com­mand type dependent. The operation of a mini FINS command is defined as follows.
Device address Command code
MRC/SRC
2 bytes 2 bytes 2 bytes
Instruction code &
related information
The response of this command for a correct executing of the command is defined as:
Command code
MRC/SRC
2 bytes 2 bytes
Response
code
Refer to the operation manual of the targeted Compoway-F device for more commands and detailed information.
Example To stop control on channel 1 of the E5_R, with address 05, the contents of the
Fee Communication block must be set to 0005 3005 0101 (hex), or
• Device address: 0005 (hex)
• Command code: 3005 (hex)
• Instruction code: 0101 (hex).
Assuming there is no error, the response is four bytes: 3005 0000 (hex).
Read Mini FINS Command The Read mini FINS command consists of
• A device address number.
• A command code MRC/SRC.
• A variable area type, indicating the area within the device, from where the parameter must be read.
• A Read start address within the specified area.
• A Bit position within the parameter to be read.
• The Number of bits/bytes to read from the parameter area/location.
This format is shown below.
45
Page 61
Compoway-F Communication
Section 3-3
Device
address
2 bytes 2 bytes 1 byte 2 bytes 1 byte 2 bytes
Command
code
MRC/SRC
Variable
type
Read start
address
Bit position Number of
elements
The response of this command for a correct executing of the command is defined as:
Command code
MRC/SRC
2 bytes 2 bytes 4 bytes
Response
code
Data
Refer to the operation manual of the Compoway-F device for more detail regarding the read mini FINS command.
Note 1. The actual data to be written to the device consists of one double word. If
a CS1/CJ1 PLC is used to assemble the Write command, de data will be swapped before sending it over PROFIBUS, due to the communication for­mats of both Compoway-F and PROFIBUS. The PLC program must swap these words before the data can be transmitted.
2. For CX-Programmer 5.0 or higher OMRON provides function blocks to im­plement the assembly of the Free Communication Read command. When processing the response this function block will perform the word swapping automatically. Refer to
Appendix B Function Block Programming
for more
details.
Example Reading the internal setpoint from an E5ZN (device 2), channel 1 (start
address 2, 1 element to read) is done with the command: 0002 0101 C1 0002 00 0001(hex). The response is (no error occurred): 0101 0000 0000 0000 0000 0000(hex).
Write Mini FINS Command The Write mini FINS command consists of
• A device address number.
• A command code MRC/SRC.
• A variable area type, indicating the area within the device, to where the parameter must be written.
• A Read start address within the specified area.
• A Bit position within the parameter to be read.
• The Number of bits/bytes to read from the parameter area/location.
• The data to be written.
This format is shown below.
Device
address
2 bytes 2 bytes 1 byte 2 bytes 1 byte 2 bytes 4 bytes
Command
code
MRC/SRC
Variable
type
Write
start
address
Bit
position
Number
of
elements
Element1
The response of this command for a correct executing of the command is defined as:
Command code
MRC/SRC
2 bytes 2 bytes
Response
code
46
Page 62
Compoway-F Communication
Section 3-3
1. Refer to the operation manual of the Compoway-F device for more detail regarding the read mini FINS command. The actual data written to the Temperature Controller consists of one dou­ble word. Due to the communication formats of both Compoway-F and PROFIBUS, de data will end up as two swapped words in a CS1/CJ1 PLC, when the CS1/CJ1W-PRM21PROFIBUS Master is used. The PLC pro­gram must swap these words before the data can be sued.
2. For CX-Programmer 5.0 or higher OMRON provides function blocks to im­plement the assembly of the Free Communication Write command. When processing the response this function block will perform the word swapping automatically. Refer to
Appendix B Function Block Programming
for more
details.
Example Writing the lower limit of the setpoint an E5ZN (device 2), channel 1 is done
with the command: 0002 0102 C1 0003 00 0001 0000 0005(hex). The response is (no error occurred): 0102 0000(hex).
Free Communication Blocks
A write or operation command will be sent to the device when the command is changed from zero’s to the correct data. When the command data is set to zero, the response data will also be cleared. The read type command blocks are sent every Compoway-F cycle.
Broadcast Broadcasting can be used for operations and writes. If the device address is
set to 00FF(hex), a broadcast is sent to all devices using XX broadcast. The response code will be filled with a response to indicate that the command has been sent to the devices.
Note It is recommended to restrict the Free Communication blocks to the end of the
I/O configuration. Placing a Free Communication block in the middle of other modules is allowed, but it will influence the device number of other modules. The device number is affected due to the fact that the slot number is a repre­sentation of the device number.
Example Configuring 2 x E5ZN basic modules and a Free Communication write block:
If there is no device for a device address between two existing consecutive device addresses, the empty slot module must be used. The slot number rep­resents the device address.
Slot
number
1 E5ZN Basic 1 E5ZN Basic 1 2 E5ZN Basic 2 Free communication write
3 Free communication write
block
Recommended Not recommended
Module Device
number
block
-- E5ZN Basic 3
Module Device
number
--
Note The PROFIBUS Configuration for this slave is limited to 100 words input and
100 words output.
47
Page 63
K-Format Communication
Section 3-4

3-4 K-Format Communication

3-4-1 Fixed Communication Blocks

The K-Format protocol supports Fixed Communication blocks to allow easy configuration for a number of I/O parameters, supported by the E5AK / E5EK intelligent Digital Controllers. In the next table an overview of the Fixed Com­munication blocks is listed.
K-Format
Device
type
- Empty slot (No device) - - 0 0 N/A E5AK/
E5EK
Module name Output words Input words Total
E5_K-Basic 5WI/2WO SV channel 1
Operation Execute (See Note)
E5_K-Extended 5WI/4WO SV channel 1
Alarm value 1 Alarm Value 2 Operation Execute
(See Note)
PV channel 1 SV channel 1 Status A group Status B group Special Operation
PV channel 1 SV channel 1 Status A group Status B group Special Operation
output
words
Tot al
input
words
25 1
45 1
Number of
channels
Note The Special operation word is explained in the section below.

3-4-2 Operation Execute

The Operation Execute word can be used to Start or Stop a control cycle in the E5AK / E5EK Controller. The command options are shown below.
Command Value
(See Note)
Run 0000 Start Control cycle. Stop 0001 Stop Control Cycle.
Note Other values for Operation Execute are not supported.

3-4-3 K-Format Parameter Settings

For the Fixed Communication blocks the user can define behaviour of the PRT1-SCU11 on the K-Format communication in case the PROFIBUS com­munication fails.
PROFIBUS Communication Fails
In case the PROFIBUS communication fails, there are two options for the PRT1-SCU11 to handle this, as defined by the a user.
• The PRT1-SCU11 can send a stop command to the device, causing the control cycle to stop.
• The E5AK / E5EK can Hold the last received Setpoint Value.
Description
48
Page 64
K-Format Communication
This behavior can be selected in CX-Profibus when configuring the PROFI­BUS DP Master unit, see the example in the figure below.
This setting can be defined for every individual Temperature Controller and will be sent to the PRT1-SCU11 as part of the PROFIBUS DP Set_Prm mes­sage.

3-4-4 Free Communication Blocks

Section 3-4
Free Communication Block Format
For the K-Format protocol one Free Communication Block is available, which has however, a different format as compared to the Free Communication Block for Compoway-F. The one Free Communication block allows implemen­tation of Read, Write and special Operation type of commands.
The Free Communication block reserves 3 words of input data and 3 words of output data. The output format is shown below.
Device
address
1 byte 1 byte 1 byte 1 byte 2 byte
Reserved Command
type
Parameter Number/
Command code
Data
The table below lists the message parameters.
Message parameter Description
Device address The address number of the target device. Reserved A reserved byte, which will be ignored by the PRT1-SCU11 Command type A command type code
1 = Read command 2 = Write command 3 = Special command 4 ~ FF = Invalid command
Parameter Number / Command Code
Data Data to be written. The PRT1-SCU11 will ignore this part in
Refer to the E5AK / E5EK Operation Manual. In case the Command type is set to 1 or 2, use the Parameter
number to specify the parameter to be read or written. In case the Command type is set to 3, use the Command
code to define the Special Operation.
case of a Read command or a special operation command.
The input format is shown below.
49
Page 65
Host Link Communication
Section 3-5
Device
address
1 byte 1 byte 1 byte 1 byte 2 byte
End code Command
type
Parameter Number/
Command code
Data
The table below lists the message parameters.
Message
parameters
Device address The address number of the target device. End code Indicates failure or success of the command transmission.
If the End code is not equal to 0, the data part must be con­sidered invalid.
Command type A command type code
1 = Read command 2 = Write command 3 = Special command 4 ~ FF = Invalid command
This is the same as sent to the device via the output data.
Parameter Number / Command Code
Data Data read from or written to the E5AK / E5EK Controller.
Refer to the E5AK / E5EK Operation Manual. In case the Command type is set to 1 or 2, use the Parameter
number to specify the parameter to be read or written. In case the Command type is set to 3, use the Command
code to define the Special Operation.
Description

3-5 Host Link Communication

In the following table the fixed communication blocks for Host Link communi­cation are listed.
Host Link
Device type Module name Output words Input words Total
- Empty slot (No device) - - 0 0 R88A-MCW151-E “MCW151 Host Link 5 IW/5 OW” VR(5) (Status word)
VR(6) - VR(10)
“MCW151 Host Link 10 IW /10 OW” VR(10) (Status word)
VR(11) - VR(20)
“MCW151 Host Link 15 IW / 15 OW” VR(15) (Status word)
VR(16) - VR(30)
VR(0) - VR(4) 5 5
VR(0) - VR(9) 10 10
VR(0) - VR(14) 15 15
output
words
The required data on VR-memory address can be programmed in the R88A­MCW151-E. For more detailed information refer to the R88A-MCW151-E Operation Manual.
The status of the PROFIBUS communication can be checked by the R88A­MCW151-E through the R88A-MCW151-E status word (see figure below). This word is sent by the PRT1-SCU11 to the R88A-MCW151-E.In case PROFIBUS communication fails, the first bit of the status word will be set to
Tota l
input
words
50
Page 66
Memobus Communication
Section 3-6
OFF. If the PROFIBUS communication is active the same bit will be set to ON, regardless the number of I/O communication words.
R88A-MCW151-E Status Word
15 14 13 12 11 10 9 8
76543210
PROFIBUS Communication Active

3-6 Memobus Communication

3-6-1 Fixed / Flexible Communication Blocks

The Memobus protocol supports Fixed Communication blocks to allow easy configuration for a number of I/O parameters, supported by the E5AK / E5EK intelligent Digital Controllers. In the next table an overview of the Communica­tion blocks is listed.
Memobus
Device type Module name Output words Input words Total
- Empty slot (No device) - - 0 0 F7 Inverter Memobus Fixed 3WI/3WO
(Fixed)
Memobus 3WI/3WO (Flexible)
Command Register Frequency Register Voltage Register
(See Note 1) Register 1
Register 2 Register 3
(See Note 2)
Status Register Frequency Register Voltage Register
(See Note 1) Register 1
Register 2 Register 3
(See Note)
output
words
words
33
33
Total
input
Note 1. The addresses of these registers are fixed in the PROFIBUS parameter
message. They can not be changed by the user.
2. The user can define each of the addresses of the registers in the Input and Output area. This must be done upon configuring the PROFIBUS DP Mas­ter unit, see section
2-6 Configuring the PROFIBUS DP network
.
51
Page 67
Memobus Communication

3-6-2 Memobus Parameter Settings

During configuration of the PROFIBUS Master unit the user must set a num­ber of parameters, depending on the selected Communication block. De fig­ure below shows the selection options for a Fixed Communication Block.
Section 3-6
The parameter options are listed in the table below.
Parameter name Range
Device Address 00 ~ 1F Defines the Memobus address of the device to exchange the I/O
Read Status Register 0020 Address of the status register (Fixed). Read Frequency Register 0023 Address of the Actual Frequency register (Fixed). Read Voltage Register 0025 Address of the Actual Voltage register (Fixed). Write Command Register 0001 Address of the Command register (Fixed). Write Frequency Register 0002 Address of the Required Frequency register (Fixed).
Fixed Comm. Block
Write Voltage Register 0003 Address of the Required Voltage register (Fixed). Device Address 00 ~ 1F Defines the Memobus address of the device to exchange the I/O
Read Register Address One 0000 ~ FFFF Address of first register to read from. Read Register Address Two 0000 ~ FFFF Address of second register to read from. Read Register Address Three 0000 ~ FFFF Address of third register to read from Write Register Address One 0000 ~ FFFF Address of first register to write to. Write Register Address Two 0000 ~ FFFF Address of second register to write to.
Flexible Comm. Block
Write Register Address Three 0000 ~ FFFF Address of third register to write to.
(Hex)
data of this module with.
data of this module with.
Description
52
Page 68
PROFIBUS Diagnostics

3-7 PROFIBUS Diagnostics

The PRT1-SCU11 provides extended diagnostics over PROFIBUS to notify the PROFIBUS DP Master of the Unit’s status and the status of the RS-422A/ RS-485 communication. These extended diagnostics are sent to the Master unit via a PROFIBUS Diagnostics message. These messages are only sent up on occurrence of the error or status event.
A PROFIBUS Diagnostics message will contain 6 standard diagnostics bytes, followed by the Extended diagnostics bytes, in case any extended diagnostics data is available. The extended diagnostics bytes as produced by the PRT1­SCU11 are shown below.
Byte 1
Byte 2
Section 3-7
7654 3210
Block length (Bytes)
Including Header byte
Fixed to 00
76543 210
Device 01 Comm. error
Device 02 Comm. error
Device 03 Comm. error
Device 04 Comm. error
Device 05 Comm. error
Device 06 Comm. error
Device 07 Comm. error
Device 08 Comm. error
76543 210
Byte 3
Device 09 ~ 16 Comm. error
76543 210
Byte 4
Device 17 ~ 24 Comm. error
76543 210
Byte 5
Device 25 ~ 31 Comm. error
76543 210
Byte 6, Byte 7
Reserved
76543 210
Byte 8, Byte 9
Reserved
Note 1. Byte 1 in the figure above represents the 7th byte in a diagnostics mes-
sage. The first 6 bytes (not shown here) are standard diagnostics.
2. If a bit flag in byte 2 to 5 is ON, the corresponding device on the RS-422A/ RS-485 network is not responding or it has reported a communication er­ror.
53
Page 69
Auxiliary RS-232C interface
Section 3-8

3-8 Auxiliary RS-232C interface

The PRT1-SCU11 provides an RS-232C interface, behind a cover lid on the front of the Unit. This interface allows a user to connected an IBM compatible computer with a serial port and send and receive data to a Compoway-F, or K­Format device using the software package CX-Thermo.
Equally, when Memobus has been selected as the protocol, the RS-232C interface can be used to transfer commands from CX-Drive and the Varispeed F7 Inverter.
Using CX-Thermo Before using CX-Thermo DIP-switch 4 must be set on, a group of four DIP-
switches is located on the front of the PRT1-SCU11 Unit.
Note CX-Thermo is not shipped with the PRT1-SCU11.
!WARNING
Note The interface connection is not galvanically isolated.
When DIP-switch 4 is switched on, the PRT1-SCU11 will stop the data exchange with the PROFIBUS Master. The PROFIBUS DP interface will stay inactive until switch 4 is switch off.
When DIP-switch 4 is set on:
• The diagnostics indicates Slave Not_Ready.
• FERR LED is switched off.
• COMM LED starts flashing.
• FCOM start flashing.
• BF LED is switched off.
To connect with the PRT1-SCU11 use an auxiliary RS-232C compatible inter­face on an IBM compatible computer and a standard Omron RS-232C PLC cable e.g. (CS1W-CN226).
The baud rate settings are the same as used for the Compoway-F interface, as set through the associated DIP-switches.
54
Page 70
Auxiliary RS-232C interface
Section 3-8
To connect with the unit use the second button in the menu, starting from the left, see figure below.
When connected with CX-Thermo you can configure the required Tempera­ture Controller. For detailed information please use the ThermoTool online help and read the manual of the used Temperature Controller.
Note Make sure that the baud rate settings in CX-Thermo is the same as selected
on the PRT1-SCU11 with DIP-switch 1 and 2. It is required to use the follow­ing communication format:
• Data length: 7 bits
• Stop bit length: 2 bits
• Parity: even
55
Page 71
Page 72
SECTION 4
Troubleshooting and Maintenance
This section describes the troubleshooting procedures and maintenance operations needed to keep the PROFIBUS network optimally working.
4-1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
4-2 Troubleshooting Using LED Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
4-2-1 Unit Led Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
4-2-2 RS-422A / RS-485 Communication LED Indicators . . . . . . . . . . . . 58
4-2-3 PROFIBUS LED Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
4-3 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
4-3-1 Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
4-3-2 Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
4-4 Replacing the Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
4-4-1 Replacement Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
57
Page 73
Overview

4-1 Overview

The PRT1-SCU11 has several LED indicators, allowing the user to trouble­shoot and check the operation.
These LED indicators are:
• RUN, indicates normal operation.
• ERR, fatal error.
• FCOM, RS-422A / RS-485 communication.
• FERR, communication error on RS-422A / RS-485.
• COMM, communication with PROFIBUS Master.
• BF, all communication with the PROFIBUS Master has lost or configura­tion/parameter error occurs.
The LED’s can be categorized into 3 categories.
1. Unit LED indicators.
2. RS-422A / RS-485 Communication LED indicators.
3. PROFIBUS communication LED indicators.

4-2 Troubleshooting Using LED Indicators

Section 4-1

4-2-1 Unit Led Indicators

The Unit LED’s indicate the status of the PRT1-SCU11. These are the two highest LED’s. In the next table there is an overview of all possible LED states of the two Unit LED’s. A description of the error and a possible solution to solve the error.
Unit LED’s
RUN ERR Description Solution
Lit Not lit Normal operation -
Not lit Not lit • Initialization fails.
• No power connected to the Unit.
Not lit Blinks Initialization error during startup. Restart the module by switching the power off and on,
Not lit Lit Fatal error. Restart the module by switching the power off and on,
• Restart the module by switching the power off and on, if the problem remains replace the Unit.
• Switch power to the Unit.
if the problem remains replace the Unit.
if the problem remains replace the Unit.

4-2-2 RS-422A / RS-485 Communication LED Indicators

The Unit LED indicators show the status of the communication with Compo­way-F, Host Link, K-Format or Memobus over RS-422A / RS-485. These are the two LED’s in the middle. In the next table an overview of all possible LED states of the two LED indicators, a description of the error and a possible solutions to solve the error are presented.
58
Page 74
Troubleshooting Using LED Indicators
RS-422A / RS-485 LED’s
FCOM FERR Description Solution
Not lit Not lit • No communication over RS-422A /
RS-485. Probably a broken wire.
• Unit has not initialized.
• Not all devices configured in the PRT1­SCU11 are communicating.
• No power connected to the Unit.
• No PROFIBUS communication. Unit has not been initialized with a configu­ration and cannot proceed with RS­422A/ RS-485 communication.
Lit Not lit Communication with RS-422A / RS-485
devices fails, the Unit is unable to estab­lish communication with all devices.
Blinks Not lit Communication by auxiliary port selected. • End your ThemoTools session and switch DIP-
Not lit Lit No communication with RS-422A / RS-
485 network.
• Check all cables and connections.
• Switch the Unit off and on, make sure the network configuration has been downloaded.
• Check Compoway-F, Host Link, K-Format or Memobus addresses, baud rate settings. If baud rate settings are changed a restart must performed
• Switch power to the Unit. The hardware does not correspond with the configured network in the soft­ware.
-
switch 4 to off. Switch to the old baud rate settings if these ware changed, when baut rate settings are changed a restart must performed.
• Check Compoway-F, Host Link, K-Format or Memobus addresses, baud rate settings, when baut rate settings are changed a restart must per­formed.
• Check all cables and connections.
Section 4-2

4-2-3 PROFIBUS LED Indicators

The Unit LED indicators show the status of the communication with PROFI­BUS. These are the two lowest LED’s. In the next table an overview of all pos­sible LED states of the two PROFIBUS LED indicators, a description of the error and a possible solutions to solve the error are presented.
PROFIBUS LED
COMM BF Description Solution
Not lit Not lit No power connected to the Unit Switch power to the Unit Not lit Lit No communication with PROFIBUS Mas-
ter
Not lit Blinks The wrong module selected in the network
configuration
Blinks Not lit Compoway-F, K-Format or Memobus
communication through the auxiliary port
Lit Not lit Communication in progress -
• Check if the PROFIBUS Master is running
• Check all PROFIBUS cables and connections, ter­mination resistor.
• The hardware does not correspond with the config­ured network in the software,
• Check also the PROFIBUS addresses of the Unit
• End your ThemoTools / CX-Drive session and switch DIP-switch 4 to off. Switch to the old baud rate settings if these ware changed, when baut rate settings are changed a restart must performed
59
Page 75
Maintenance

4-3 Maintenance

4-3-1 Cleaning

Section 4-3
This section describes the routine cleaning and inspection recommended as regular maintenance.
Clean the PRT1-SCU11 regularly as described below in order to keep it in an optimum operating condition.
• Regularly wipe the Unit with a dry, soft cloth.
• If a spot cannot be removed with a dry cloth, dampen the cloth with a neu­tral cleaner, wring out the cloth and wipe the Unit.
!Caution
Never use volatile solvents such as paint thinner, benzine or chemical wipes. These substances could damage the surface of the Unit.

4-3-2 Inspection

Be sure to inspect the system periodically to keep it in optimum operating con­dition. In general, inspect the system once or twice a year, but more fre­quently if the system is used in high temperature or high humidity environments or dirty/dusty conditions.
Inspection Equipment Prepare the following equipment before inspecting the system.
Required Equipment
Phillips type screwdriver, multimeter, alcohol, and a clean cloth.
Optional Test Equipment
Depending on system conditions, a synchroscope, oscilloscope, thermometer or hygrometer (to measure humidity) might be needed.
Inspection Procedure Check the items in the following table and correct any that are below stan-
dard.
Item Standard Equipment
Environmental
conditions
Installation Are the units installed securely? No looseness ---
Ambient temperature 0° C to 55° C Thermometer
Ambient humidity 10% to 90% Hygrometer Dust/dirt accumulation None ---
Are the communications connec­tors fully inserted?
Are the external wiring screws tight?
Are the connecting cables undam­aged?
No looseness ---
No looseness ---
No damage ---
60
Page 76
Replacing the Unit

4-4 Replacing the Unit

4-4-1 Replacement Precautions

The PRT1-SCU11 is a network device. If the Unit is damaged, it will effect the entire Network, so always ensure repairs are undertaken immediately. It is recommended to have a spare PRT1-SCU11 on hand so that repairs may be conducted quickly.
Replacement Precautions Observe the following precautions when replacing the Unit.
• Always turn OFF the power before replacing the Unit.
• Ensure that the new Unit is not faulty.
• If a poor connection is suspected of causing the malfunction, clean the connectors using a clean, soft cloth and industrial-grade alcohol. Remove any lint or threads left from the cloth, and remount the Unit.
• When returning a faulty unit for repair, always attach a detailed fault report to the unit and return it to the nearest OMRON dealer.
Note 1. In order to prevent faulty operation be sure to turn off the power to all mas-
ter and slave devices before replacing the Unit.
2. When replacing the Unit, do not reconnect it to the Network before carrying out the procedures listed below.
Section 4-4
61
Page 77
Page 78
Appendix A
Memory Mapping

A-1 Memory Mapping for Compoway-F Devices

The table below lists the Mapping of individual parameters in the Basic and Extended on to the applicable Tem­perature Controller variable areas.
Parameter Read/
SV W 0102 C1:0003 C1:0003 C1:0103 C1:0003 C1:0103 C1:0203 C1:0303 PV R 0101 C0:0000 C0:0000 C0:0100 C0:0000 C0:0100 C0:0200 C0:0300
Basic block
SV W 0102 C1:0003 C1:0003 C1:0103 C1:0003 C1:0103 C1:0203 C1:0303 Special
Operation Command
PV R 0101 C0:0000 C0:0000 C0:0100 C0:0000 C0:0100 C0:0200 C0:0300 Status R 0101 C0:0001 C0:0001 C0:0101 C0:0001 C0:0101 C0:0201 C0:0301 MV1 R 0101 C0:0004 C0:0004 C0:0104 C0:0004 C0:0104 C0:0204 C0:0304 MV2 R 0101 C0:0005 C0:0005 C0:0105 C0:0005 C0:0105 C0:0205 C0:0305
Extended block
Special Operation Executed
Write
MRC/
SRC
W See table below
R See table below
E5_N E5ZN E5_R
Channel 1 Channel 2 Channel 1 Channel 2 Channel 3 Channel 4
The table below lists the command codes used by the PRT1-SCU11 to translate the Special Operation Com­mands to mini FINS messages.
Parameter (See Note)
Run / Stop 3005 01 00 / 01 00 / 01 10 / 11 00 / 01 10 / 11 20 / 21 30 / 31
AT Cancel/
Execute
Special Operation
Auto/
Manual
MRC/
SRC
3005 01 NA F0 / F1 F0 / F1 3005 03 00 / 01 00 / 01 10 / 11 01 and 0A 3005 03 NA F0 / F1
3005 09 NA 00 / 01 10 / 11 00 / 01 10 / 11 20 / 21 30 / 31 3005 09 NA F0 / F1 F0 / F1
Cmd
Code
E5_N E5ZN E5_R
Channel 1 Channel 2 Channel 1 Channel 2 Channel 3 Channel 4
Refer to E5AR/E5ER Digital Controller Users
@
)
Manual (Z182-E1-
for details
Note Each type of command lists two possible channel addressing methods: the first row specifies commands
for individual channels, the second row the command for all channels.
63
Page 79
Memory Mapping Appendix A

A-2 Parameter / Command Mapping for K-Format Devices

The table below lists the Mapping of individual parameters in the Basic and Extended blocks on to the E5AK/ E5EK Intelligent Digital Controller. Refer to the E5AK and E5EK Operation Manuals (H083-E1­for more information
Parameter Read/
Setpoint W 01 Special operation W -- Special Command is used to initiate Run or Stop.
PV monitor R 00 SP monitor R 01
Basic
Status A group R -- Special Command is used to read Status A/Status B. Status B group R
Operation Execute R -- Response to Special Operation is returned. Setpoint W 01 Special operation W -- Special Command is used to initiate Run or Stop.
Alarm Value 1 W 02 Alarm Value 2 W 03 PV monitor R 00 SP monitor R 01
Extended block
Status A group R -- Special Command is used to read Status A/Status B. Status B group R
Operation Execute R -- Response to Special Operation is returned.
.
Write
Parameter
Number
• 0000 = Run
• 0001 = Stop
• 0000 = Status group A
• 0001 = Status group B
• 0000 = Run
• 0001 = Stop
• 0000 = Status group A
• 0001 = Status group B
Remarks
@,
H085-E1-@)
64
Page 80
Memory Mapping Appendix A

A-3 Parameter / Command Mapping for Memobus Devices

The table below lists the Mapping of individual parameters in the Fixed and Flexible I/O blocks on to the OYMC Varispeed F7 Inverter. Refer to the F7 Inverter’s Operation Manual (YEG-TOE-S616-55.1-OY) for more infor­mation
Note Being able to write to the voltage register, a special firmware version - VSF108981 - for the Varispeed F7
.
Parameter Read/
Write
Command register W 0001 Frequency register W 0002 Voltage register W 0003 See Note Status register R 0020
Fixed block
Frequency register R 0023 Voltage register R 0025 Write register 1 W 0000 ~ FFFF The registers to read/write can be selected by the user Write register 2 W 0000 ~ FFFF Write register 3 W 0000 ~ FFFF Read register 1 R 0000 ~ FFFF Read register 2 R 0000 ~ FFFF
Flexible block
Read register 3 R 0000 ~ FFFF
Register Number
(Hex)
Remarks
when setting up the PROFIBUS I/O configuration. An invalid register address selection (i.e. non-existent or
read-only) will result in a Memobus error.
Inverter is required. Contact your supplier on how to obtain this firmware upgrade.
65
Page 81
Page 82
Appendix B
Function Block Programming

B-1 Introduction

In order to facilitate the data transfer to and from Temperature Controllers from a CS1/CJ1W-PRM21 PROFI­BUS DP Master via the PRT1-SCU11, OMRON provides a number of PLC Function Blocks. These function blocks can be used in the CS1/CJ1 PLC program to assemble the output data or extract the input data from the CS1/CJ1W-PRM21 PROFIBUS Master I/O data areas. This appendix describes these function blocks.
Note Function Blocks are only supported by CX-Programmer version 5.0 and higher.

B-2 Basic / Extended Function Blocks

A total of 10 function blocks are provided for the basic and extended I/O configuration blocks for the E5_N, E5ZN and E5_R Temperature controllers. The table below lists the specifics of these function blocks.
Item Description
Basic function Writes the SV/Operation command and reads the PV/MV/Status/Operation Executed word. Symbol
Start Trigger
Start Word
Profibus output data
Start Word
Profibus input data
SV Channel 1
SV Channel 2
SV Channel 3
SV Channel 4
Operation Command word
(BOOL) EN
(UINT) StratWordOutput
(UINT) StartWordInput
(WORD) SV_CH1
(WORD) SV_CH2
(WORD) SV_CH3
(WORD) SV_CH4
(WORD) Oper_Cmmnd
(WORD)
(WORD)
(WORD)
(WORD)
(WORD)
(WORD)
(WORD)
(WORD)
(WORD)
(WORD)
(WORD)
(WORD)
(WORD ) PV_CH1
(WORD ) MV1_CH1
(WORD ) MV2_CH1
(WORD ) Status_HW_CH1
(WORD ) Status_LW_CH1
(WORD ) PV_CH2
(WORD ) MV1_CH2
MV2_CH2
Status_HW_CH2
Status_LW_CH2
PV_CH3
MV1_CH3
MV2_CH3
Status_HW_CH3
Status_LW_CH3
PV_CH4
MV1_CH4
MV2_CH4
Status_HW_CH4
Status_LW_CH4
Operation_Exec
(BOOL)
ENO
PV Channel 1
MV1 Channel 1
MV2 Channel 1
Status High Word Channel 1
Status Low Word Channel 1
PV Channel 2
MV1 Channel 2
MV2 Channel 2
Status High Word Channel 2
Status Low Word Channel 2
PV Channel 3
MV1 Channel 3
MV2 Channel 3
Status High Word Channel 3
Status Low Word Channel 3
PV Channel 4
MV1 Channel 4
MV2 Channel 4
Status High Word Channel 4
Status Low Word Channel 4
Special Operation Executed Word
Note Only the function block for a 4 channel E5_R is shown. The other function blocks are limited
versions of this one.
67
Page 83
Item Description
File name PRT1_SCU11_E5_N_Basic_1CH.cxf
PRT1_SCU11_E5_N_Extended_1CH.cxf PRT1_SCU11_E5_R_Basic_1CH.cxf PRT1_SCU11_E5_R_Basic_2CH.cxf PRT1_SCU11_E5_R_Basic_4CH.cxf PRT1_SCU11_E5_R_Extended_1CH.cxf PRT1_SCU11_E5_R_Extended_2CH.cxf PRT1_SCU11_E5_R_Extended_4CH.cxf PRT1_SCU11_E5ZN_Basic_2CH.cxf PRT1_SCU11_E5ZN_Extended_2CH.cxf
Function description • Writes SV/Operation command to the CS1/CJ1W-PRM21 PROFIBUS Master I/O addresses
allocated to the targeted Temperature Controller.
• Reads PV/MV/Status/Operation Executed words from the CS1/CJ1W-PRM21 PROFIBUS Mas­ter I/O addresses allocated to the targeted Temperature Controller.
EN Input condition Connect EN to an OR between an upwardly differentiated condition for the start trigger and the
BUSY output from the Function Block.
Restrictions on Input variables
• Always use an upwardly differentiated condition for the EN.
• If the Input variables are out of range, the ENO flag will turn OFF and the Function Block will not be processed.
Application example
Start Trigger
Start Word Profibus output data
Start Word Profibus input data
Operation Command word
&3300
&3200
SV Channel 1
&100
SV Channel 2
#75
SV Channel 3
125
SV Channel 4
126
#0062
(BOOL) EN
(UINT) StratWordOutput
(UINT) StartWordInput
(WORD) SV_CH1
(WORD) SV_CH2
(WORD) SV_CH3
(WORD) SV_CH4
(WORD) Oper_Cmmnd
(WORD)
(WORD)
(WORD)
(WORD)
(WORD)
(WORD)
(WORD)
(WORD)
(WORD)
(WORD)
(WORD)
(WORD)
(WORD ) PV_CH1
(WORD ) MV1_CH1
(WORD ) MV2_CH1
(WORD ) Status_HW_CH1
(WORD ) Status_LW_CH1
(WORD ) PV_CH2
(WORD ) MV1_CH2
MV2_CH2
Status_HW_CH2
Status_LW_CH2
PV_CH3
MV1_CH3
MV2_CH3
Status_HW_CH3
Status_LW_CH3
PV_CH4
MV1_CH4
MV2_CH4
Status_HW_CH4
Status_LW_CH4
Operation_Exec
(BOOL)
ENO
PV Channel 1 1000
MV1 Channel 1 1001
MV2 Channel 1 1002
Status High Word Channel 1 1003
Status Low Word Channel 1 1004
PV Channel 2 1005
MV1 Channel 2 1006
MV2 Channel 2 1007
Status High Word Channel 2 1008
Status Low Word Channel 2 1009
PV Channel 3 1010
MV1 Channel 3 1011
MV2 Channel 3 1012
Status High Word Channel 3 1013
Status Low Word Channel 3 1014
PV Channel 4 1015
MV1 Channel 4 1016
MV2 Channel 4 1017
Status High Word Channel 4 1018 Status Low Word Channel 4 1019 Special Operation Executed Word 1020
Note Only the function block for a 4 channel E5_R is shown. The other function blocks are limited
versions of this one.
Page 84
Function Block Programming Appendix B
The table below lists the Input and Output variables for the basic / extended function blocks.
Name Variable name Data
type
EN EN BOOL 1 (ON): Function block started
Start Word PROFIBUS Out­put data
Start Word PROFIBUS Input data
SV values SV_CH1 WORD 0 SV Channel 1
Operation Com­mand
Input variables
ENO ENO BOOL 1 (ON): Function block processed normally
Process variables PV_CH1 WORD PV Channel 1
Output variables
StartWordOutput UINT 3000 Start Word of PROFIBUS Output data in
StartWordInput UINT 3010 Start Word of PROFIBUS Input data in PROFI-
SV_CH2 WORD 0 SV Channel 2 SV_CH3 WORD 0 SV Channel 3 SV_CH4 WORD 0 SV Channel 4 Oper_Cmmnd WORD 0 Special Operation Executed word
MV1_CH1 WORD MV1 Channel 1 MV2_CH1 WORD MV2 Channel 1 Status_HW_CH1 WORD Status High Word Channel 1 Status_LW_CH1 WORD Status Low Word Channel 1 PV_CH2 WORD PV Channel 2 MV1_CH2 WORD MV1 Channel 2 MV2_CH2 WORD MV2 Channel 2 Status_HW_CH2 WORD Status High Word Channel 2 Status_LW_CH2 WORD Status Low Word Channel 2 PV_CH3 WORD PV Channel 3 MV1_CH3 WORD MV1 Channel 3 MV2_CH3 WORD MV2 Channel 3 Status_HW_CH3 WORD Status High Word Channel 3 Status_LW_CH3 WORD Status Low Word Channel 3 PV_CH4 WORD PV Channel 4 MV1_CH4 WORD MV1 Channel 4 MV2_CH4 WORD MV2 Channel 4 Status_HW_CH4 WORD Status High Word Channel 4 Status_LW_CH4 WORD Status Low Word Channel 4 Operation_Exec WORD 0 Special Operation Executed word
Default Range Description
0 (OFF): Function block not started
PROFIBUS Master Output data area.
BUS Master Input data area.
0 (OFF): Function block not processed or ended in an error
Note The table lists all possible variables for the maximum size function block, i.e. the Extended block for the
E5_R. For other basic / extended function blocks subsets of variables apply.
69
Page 85
Function Block Programming Appendix B
A

B-3 Operate Function Block

The Operate Function Block facilitates the transmission of aN OPERATE command to a specific temperature Controller (refer to section tion block.
Item Description
Basic function Sends an Operation command to a specified Temperature Controller via PROFIBUS. Symbol
File name PRT1_SCU11_Operate.cxf Function description Sends an operation command to the CS1/CJ1W-PRM21 PROFIBUS Master I/O addresses allo-
Precautions
3-3-4 Free Communication Blocks
Start Trigger
Busy Flag
Related information to the
Start Word
Profibus output data
Start Word
Profibus input data
Unit No of TC
Command Code
operation command
(BOOL) EN
(UINT) StratWordOutput
(UINT) StartWordInput (UINT) UnitNo (UINT) CommandCode
(UINT) RelatedInformation
). The table below lists the specifics of this func-
(BOOL)
ENO
(WORD)
ResponseCode
(BOOL)
Busy
Response code from TC
Busy flag
cated to the targeted Temperature Controller, specified by the Unit No. The command is specified by the command code and related information.
Timechart
Start Trigger
Busy Flag (BUSY)
ON OFF
ON OFF
FB execution completed.
t normal end: Sending data has been completed.
EN Input condition Connect EN to an OR between an upwardly differentiated condition for the start trigger and the
BUSY output from the Function Block.
Restrictions on Input variables
• Always use an upwardly differentiated condition for the EN.
• If the Input variables are out of range, the ENO flag will turn OFF and the Function Block will not be processed.
Restrictions on Out­put variables
• This function block requires multiple cycles to process. Always connect an OR including the BUSY output variable to the EN input variable to ensure that the function block is processed to completion (see Symbol)
• Do not turn the BUSY output variable ON or OFF outside the function block.
Application example
Bit A
Bit B
Related information to the operation command
Start Word Profibus output data
Start Word Profibus input data
Unit No of TC
Command Code
&3200
&3300
#01
#10
&1
(BOOL) EN
(UINT) StratWordOutput (UINT) StartWordInput (UINT) UnitNo (UINT) CommandCode
(UINT) RelatedInformation
ResponseCode
(BOOL)
ENO
(WORD )
(BOOL)
Busy
Response code from TC Channel 2 Busy flag Bit B
70
Page 86
Function Block Programming Appendix B
The table below lists the Input and Output variables for the Operate function block.
Name Variable name Data
type
EN EN BOOL 1 (ON): Function block started.
Start Word
StartWordOutput UINT 3000 Start Word of PROFIBUS Output data in PROFIBUS Out­put data
Start Word
StartWordInput UINT 3010 Start Word of PROFIBUS Input data in PROFI­PROFIBUS Input data
Unit No of device UnitNo UINT 0 #0 - #63
Command code CommandCode UINT 0 Variable type in device. Information
RelatedInformation UINT 0 Specify the Write Start address. related to the operation com­mand
Input variables
ENO ENO BOOL 1 (ON): Function block processed normally
Result of execu-
ResponseCode WORD Outputs the error code when execution ended tion of the com­mand
Busy flag BUSY BOOL Automatically turns OFF when processing is
Output variables
Default Range Description
0 (OFF): Function block not started.
PROFIBUS Master Output data area.
BUS Master Input data area.
Unit number of device.
(0-99)
0 (OFF): Function block not processed or ended in an error.
in an error in the communications command level. Refer to section
tion Blocks
for more information.
3-3-4 Free Communica-
completed.

B-4 Read Function Block

The Read Function Block facilitates the transmission of a READ command to a specific temperature Controller (refer to section
Item Description
Basic function Reads data from a Temperature Controller’s variable area. Symbol
File name PRT1_SCU11_Read_Data.cxf Function description Sends a Read Data command to the CS1/CJ1W-PRM21 PROFIBUS Master I/O addresses allo-
3-3-4 Free Communication Blocks
Start Trigger
Busy Flag
Read Start address from TC
Start Word
Profibus output data
Start Word
Profibus input data
Unit No of TC
Variable Type
). The table below lists the specifics of this function block.
(BOOL) EN (UINT) StratWordOutput (UINT) StartWordInput (UINT) UnitNo (UINT) VarType (UINT) ReadStartAddress
ResponseCode
(BOOL)
ENO
(WORD)
(DWORD) DataRead
(BOOL)
Busy
Response code from TC
Data read from TC
Busy flag
cated to the targeted Temperature Controller, specified by the Unit No. The data to be read is spec­ified by the Variable Type and the Read Start Address.
71
Page 87
Function Block Programming Appendix B
A
Item Description
Precautions
Timechart
Start Trigger
ON OFF
Busy Flag (BUSY)
ON OFF
FB execution completed.
t normal end: Sending data has been completed.
EN Input condition Connect EN to an OR between an upwardly differentiated condition for the start trigger and the
BUSY output from the Function Block.
Restrictions on Input variables
• Always use an upwardly differentiated condition for the EN.
• If the Input variables are out of range, the ENO flag will turn OFF and the Function Block will not be processed.
Restrictions on Out­put variables
• This function block requires multiple cycles to process. Always connect an OR including the BUSY output variable to the EN input variable to ensure that the function block is processed to completion (see Symbol)
• Do not turn the BUSY output variable ON or OFF outside the function block.
Application example
it A
it B
Start Word Profibus output data
Start Word Profibus input data
Read Start address from TC
&3200
&3300
Unit No of TC
Variable Type
&1
#C0
#0100
(BOOL) EN (UINT) StratWordOutput (UINT) StartWordInput (UINT) UnitNo (UINT) VarType (UINT) ReadStartAddress
ResponseCode
(BOOL)
ENO
(WORD)
(DWORD) DataRead
(BOOL)
Busy
Response code from TC Channel 2 Data read from TC Channel 2 Busy flag Bit B
The table below lists the Input and Output variables for the Read function block.
Name Variable name Data
type
EN EN BOOL 1 (ON): Function block started.
Start Word
StartWordOutput UINT 3000 Start Word of PROFIBUS Output data in PROFIBUS Out­put data
Start Word
StartWordInput UINT 3010 Start Word of PROFIBUS Input data in PROFIBUS Input data
Unit No of device UnitNo UINT 0 #0 - #63
Variable Type VarType UINT 0 Variable type in device. Read Start
ReadStartAddress UINT 0 Specify the Read Start address. address from device
Input variables
Default Range Description
0 (OFF): Function block not started.
PROFIBUS Master Output data area.
PROFIBUS Master Input data area.
Unit number of device.
(0-99)
72
Page 88
Function Block Programming Appendix B
A
Name Variable name Data
Default Range Description
type
ENO ENO BOOL 1 (ON): Function block processed normally.
0 (OFF): Function block not processed or ended in an error.
Result of execu­tion of the com­mand
Data read from the device
ResponseCode WORD Outputs the error code when execution ended
in an error in the communications command level. Refer to section
tion Blocks
for more information.
3-3-4 Free Communica-
DataRead DWORD Data read from the device.
(See Note)
Busy flag BUSY BOOL Automatically turns OFF when processing is
Output variables
completed.
Note The function block ensures that Double Word sized data read from the Temperature Controller is cor-
rectly formatted, to match the DWORD data type as defined in the PLC.

B-5 Write Function Block

The Write Function Block facilitates the transmission of a WRITE command to a specific temperature Control­ler (refer to section
Item Description
Basic function Writes data to a Temperature Controller’s variable area. Symbol
File name PRT1_SCU11_Write_Data.cxf Function description Sends a Write Data command to the CS1/CJ1W-PRM21 PROFIBUS Master I/O addresses allo-
Precautions
3-3-4 Free Communication Blocks
Start Trigger
Busy Flag
Write Start address from TC
Start Word
Profibus output data
Start Word
Profibus input data
Unit No of TC
Variable Type
Data to be written
). The table below lists the specifics of this function block.
(BOOL) EN
(UINT) StratWordOutput
(UINT) StartWordInput (UINT) UnitNo (UINT) VarType
(UINT) WriteStartAddress (DWORD)
(BOOL)
ENO
(WORD)
ResponseCode
(BOOL)
Busy
Response code from TC
Busy flag
cated to the targeted Temperature Controller, specified by the Unit No. The data to be written and the location to write is to are specified by the DataWrite and the WordStartAddress variables.
Timechart
Start Trigger
Busy Flag (BUSY)
ON OFF
ON OFF
FB execution completed.
t normal end: Sending data has been completed.
EN Input condition Connect EN to an OR between an upwardly differentiated condition for the start trigger and the
BUSY output from the Function Block.
Restrictions on Input variables
• Always use an upwardly differentiated condition for the EN.
• If the Input variables are out of range, the ENO flag will turn OFF and the Function Block will not be processed.
73
Page 89
Function Block Programming Appendix B
Item Description
Restrictions on Out­put variables
Application example
• This function block requires multiple cycles to process. Always connect an OR including the BUSY output variable to the EN input variable to ensure that the function block is processed to completion (see Symbol)
• Do not turn the BUSY output variable ON or OFF outside the function block.
it A
it B
(BOOL) EN
&1
(UINT) StratWordOutput (UINT) StartWordInput (UINT) UnitNo (UINT) VarType
(UINT) WriteStartAddress (DWORD) DataWrite
Start Word Profibus output data
Start Word Profibus input data
Read Start address from TC
Data to be written
&3200
&3300
Unit No of TC
Variable Type
#C1
#0104
&99
ResponseCode
(BOOL)
ENO
(WORD)
(BOOL)
Busy
Response code from TC Channel 2 Busy flag Bit B
Response data is copied to channel 2 after Busy flag is OFF.
The table below lists the Input and Output variables for the Write function block.
Name Variable name Data
type
EN EN BOOL 1 (ON): Function block started.
Start Word
StartWordOutput UINT 3000 Start Word of PROFIBUS Output data in PROFIBUS Out­put data
Start Word
StartWordInput UINT 3010 Start Word of PROFIBUS Input data in PROFIBUS Input data
Unit No of device UnitNo UINT 0 #0 - #63
Variable Type VarType UINT 0 Variable type in device. Write Start
WriteStartAddress UINT 0 Start address of variable to which the data address from device
Data to be written DataWrite DWORD 0 Specify the data to be written.
Input variables
ENO ENO BOOL 1 (ON): Function block processed normally
Result of execu-
ResponseCode WORD Outputs the error code when execution ended tion of the com­mand
Busy flag BUSY BOOL Automatically turns OFF when processing is
Output variables
Default Range Description
0 (OFF): Function block not started.
PROFIBUS Master Output data area.
PROFIBUS Master Input data area.
Unit number of device.
(0-99)
must be written.
0 (OFF): Function block not processed or ended in an error.
in an error in the communications command level. Refer to section
tion Blocks
for more information.
3-3-4 Free Communica-
completed.
Note The function block ensures that Double Word sized data written to the Temperature Controller is cor-
rectly formatted.
74
Page 90

Index

Numbers
110 mH Inductor, 33 220 ohm resistor
, 24
2-wire 3-3-1 Using CX-Thermo
, 24, 27
4-wire
, 33
, 54
A
About
, ix
Manual
, 21
A-line Auto-CLEAR Auxiliary RS-323 interface
, 6
, 54
B
Basic Operating Procedure, 14 Baud rate BF B-line Broadcast Bus Access Protocol Bus fail Bus Termination Bus termination
, 12, 20, 22, 32, 54
, 19, 54, 58, 59
, 21
, 5, 47
, 2
, 19
, 33
, 33
C
Cable, 32, 34 Cable Length Cable length Cable shield connection Channel numbers Chk_Cfg Class 1 Class 1 Master Class 2 Class 2 Master Cleaning CLEAR COMM Command code Command word Common parameters Communication
Broadcast
, 32
, 3
, 34
, 43
, 19
, 4
, 4
, 4
, 4
, 60
, 5, 6
, 19, 54, 58, 59
, 43
, 42
, 38
, 5
Multicast
Multi-peer Communication fails Communication format Communication Medium Compoway-F Configuration Connector
Bus cable connector
DGND
RTS
VP CX-Profibus CX-Thermo
, 5
, 5
, 44, 48
, 22
, 31 , 9 , 6, 35
, 12, 21, 34
, 34
, 22
, 21
, 22
, 35, 36, 40, 44, 49
, 54, 55
D
Data length, 55 Data_Exchange Declaration of Confirmity Device profile Diagnostic Digital Panel Meter Dimensions DIN-rail DIP-switch DIP-switches Download configuration DTM Configuration
, 19
, xv
, 4
, 5, 13
, 25
, 13
, 23
, 20
, 18
, 35
, 36
E
E5AK/E5EK
Connection Wiring
RS-422 E5AR E5ER E5ZN Electro-magnetic compatibility EMC directive EN50170 Environment
, 19, 58
ERR Error code Extensive Diagnostics External Dimensions
, 28
, 28
, 28
, 8, 26
, 26
, 8, 25
, xv
, 2, 21
, 11
, 43
, 5
, 13
, 34
Page 91
Index
F
F7 Inverter
Connection Wiring
RS-422
RS-485 Fail-safe FCOM FDT/DTM
FDT Container application
FDT/DTM Concept FERR Fixed communication block Fixed communication blocks Flexible communication blocks Free communication block Free Communication Blocks Free communication blocks Front case
, 29
, 29
, 29 , 30
, 6
, 19, 54, 58, 59
, 7
, 19, 54, 58, 59
, 40, 41, 48, 51
, 40
, 40
, 9
, 40, 44
, 11
G-H
, 7
, 40
I/O Data I/O data I/O module IEC 1158-2 Inductor Inspection Inspection Equipment Inspection Procedure Installation ISO-7498
, 9
, 11, 13
, 35
, 2
, 33
, 60
, 60
, 60
, 11, 14
, 2
K
K3GN Digital Panel Meter, 25 K-Format
Fixed Communication blocks Free Communication blocks Operation Execute Parameters Wiring
RS-422A RS-485
, 28
, 48
, 48
, 28
, 48
, 49
Galvanically isolated, 54 Gateway
Compoway-F
Configuration
Free Communication Blocks
I/O Data
setup
, 8
Special operations
Troubleshooting
unit
, 8
Generic slave DTM
Configuring
I/O Configuration
Appending Inserting
, 34
Ground GSD File
DTM GSD file
DP-master
DP-slave
General Section
Language GSD File Language GSD-file Host Link
, 9
, 10
, 9
, 9
, 10
, 35
, 36
, 36
, 8
, 7, 36
, 7
, 7
, 7
, 7
, 7
, 7, 35
, 9, 10, 50
I
I/O configuration, 36
, 9
L-M
LED, 18, 58
BF
, 19, 54, 58, 59
, 19, 54, 58, 59
COMM
, 19, 58
ERR
, 19, 54, 58, 59
FCOM
, 19, 54, 58, 59
FERR RUN
, 19, 58
LED Indicators
Specifications LED indicators Low voltage directive
, 4
MAC Maintenance
Cleaning
Inspection Manual
About
Revision history
, 4
Master Master Devices Maximum amount of data Maximum number of devices Maximum number of modules MCW151 Memobus
Fixed Communication blocks
Flexible Communication blocks
, 19
, 18, 58
, xv
, 60
, 60
, 60
, ix
, 79
, 4
, 40
, 8, 9, 27
, 40
, 40
, 51
, 51
76
Page 92
Index
Parameters, 52 Wiring
RS-422A
RS-485 Module parameters Monitoring
Interval Master
Slave Mounting Mounting Procedure MRC/SRC Multicast Multi-peer
, 29
, 30
, 38
, 5
, 5
, 6
, 23
, 23
, 45
, 5
, 5
N
Network operation modes
Auto-CLEAR
CLEAR
Fail-safe State
OFF-LINE
OPERATE
STOP Network structure
Linear bus topology
Repeater
Tree topology Node address
, 23
Noise Not_Ready
, 6
, 6
, 6 , 6 , 6
, 6
, 31
, 31
, 31
, 31
, 19, 30
, 54
O-P
, 38
Module
, 55
Parity Pheripheral setting Polling Procedure Precautions
Application
, xii
General Operating Environment Safety
, xii
PROFIBUS
Diagnostics PROFIBUS-DP PROFIBUS-FMS PROFIBUS-PA
, 21
, 4
, 23
, xiii
, xiii
, 2
, 53
, 2
, 2
, 2
R
R88A-MCW151-E, 8, 9, 27
, 45
Read Read mini FINS command Receiver line Repeater Replacement Response word Rotary switch RS-232C RS-422 RS-422A RS-485
Cable Type RUN
, 22
, 3
, 61
, 42
, 19
, 9, 12, 18, 54
, 9, 22
, 27
, 3, 9, 22, 24, 25, 31
, 32
, 19, 58
, 45
OFF-LINE, 6 OMRON
Copyright notice OPERATE Operation Operation mini FINS command OSI
OSI reference model Parameters
, 45
ISO-7498
, 2, 3
Layer 1
, 2, 4
Layer 2
, 3
Layer 3
, 2
Layer 7
Medium Access Control
OSI Layer 1, 2 and User Interface
Polling Procedure
Token Passing
, 38
Common
, vi
, 6
, 2
, 4
, 4
, 4
, 2
, 38
, 45
, 3
S
Safety Precautions, xii Sending Free Communication Services Set_Prm Shielding shock resistance Slave Slave Devices Special Operation Special operations Specifications Status word STOP Stop bit Stub Lines
, 13
, 19
, 34
, 11
, 4
, 4
, 42
, 9, 41
, 10
, 50
, 6
, 55
, 33
, 47
77
Page 93
T
Temperature Controller, 26 Temperature Controllers Termination resister Termination Resistor Token Passing Trademarks Transmission Speed Transmission speed Troubleshooting
, 4
, vi
, 24
, 12
, 33
, 3
, 3
, 10
U
Unit replacement, 61
Precautions
Using CX-Thermo
, 61
, 54
V-W
vibration resistance, 11 Watchdog Wire A Wire B Wiring Write Write mini FINS command
, 37
, 34
, 34
, 34
, 45, 46
Index
, 46
78
Page 94

Revision History

A manual revision code appears as a suffix to the catalog number on the front cover of the manual.
Cat. No. W01E-EN-01
Revision code
The following table outlines the changes made to the manual during each revision. The page numbers of a revi­sion refer to the previous version.
Revision Code Date Revised Content
01 November 22, 2004 Initial version. 02 September 19, 2005 Changed manual title.
Corrected PROFIBUS DP naming to comply with PROFIBUS standards. Changed unit name reference to Host Link / Compoway-F to RS-422A/RS-485. Changed unit naming to more consistent name. Page ix: Added Unit version table. Page ix: Added E5_K and F7 Inverter manuals to table. Page 6: Removed bullets from list. Page 9: Added E5AK/E5EK and F7 Inverter to table. Page 9: Added text below table on Auxiliary port connection t o other protocols. Page 9: Added note on multiple protocol use. Page 9: Added a branches for Memobus and K-Format protocol to image. Page 9: Added description for Memobus and K-Format protocols. Page 10: Removed sentence on Special Operation. Page 10: Added paragraph on Fixed Communication blocks. Page 10: Added descriptions on Memobus and K-Format protocol. Page 11: Added text and version table to Specifications section. Page 11: Changed ‘modules’ to ‘units’ Page 11: Changed I/O words to bytes. Page 12: Reformatted specification table, added new protocols. Page 14: Improved flow chart. Page 19: Reformatted table. Page 19: Improved text of section 2-1-3. Page 20: Added paragraph on dip-switch 3. Page 20: Reformatted information on switches in to tables and notes. Page 21: Changed title of section 2-1-5. Page 21: Reformatted table on switches, to include switch dependencies. Page 21: Added Note to RS-422A/RS-485 table. Page 22: Renamed sections 2-2 and 2-2-2. Page 22: Reformatted communication formats in to table. Page 23: Added note on baud rates to end of section 2-3-3. Page 24: Added note on baud rates to end of section 2-3-4. Page 25: Renamed E5ZN terminals in figure. Page 25: Added note on baud rates to end of section 2-3-5. Page 26: Added section 2-3-7 and 2-3-8. Page 32: Added reference to CS1/CJ1 PROFIBUS Master manual. Page 32: Improved text of section 2-6-1. Page 35: Removed Note after example.
79
Page 95
Revision Code Date Revised Content
02 September 19, 2005 Page 38: Added paragraph on Flexible communication blocks.
Page 38: Reformatted paragraph on PROFIBUS I/O size. Page 40: Improved text and figures of section 3-3-2. Page 41: Inserted new section 3-3-1. Page 42: Improved text, reformatted table. Page 43: Improved text on mini-FINS commands. Page 44: Changed section 3-3-4 to 3-8, inserted new section 3-4. Page 47: Inserted new sections 3-6 and 3-7. Page 50, Renamed section 4.2.2. Page 55: Added Appendices A2 and A3. Removed Abbreviations section.
Loading...