OMRON NX-EIC Instruction Manual

NX-series EtherNet/IPTM Coupler Unit
EtherNet/IP master CJ-series CPU Unit or master from another manufacturer
Communications cable Ethernet cables
NX-series EtherNet/IP Coupler Unit NX-EIC202
Sysmac Studio Support Software
End Cover
NX Units *
EtherNet/IP port
EtherNet/IP Unit
Peripheral USB port
Network Configurator
Connection to peripheral USB port on EtherNet/IP Coupler Unit
Industrial Switching Hubs W4S1
EDS files
Sysmac is a trademark or registered trademark of OMRON Corporation in Japan and other countries for OMRON factory automation products. EtherCAT
is a registered trademark of Beckhoff Automation GmbH for their patented technology. EtherNet/IPTM is the trademarks of ODVA.
Other company names and product names in this document are the trademarks or registered trademarks of their respective companies.
NX-EIC
CSM_NX-EIC_DS_E_4_3
Connecting to open industrial network standard EtherNet/IP
Features
• Up to 63 NX-IO Units can be connected to one EtherNet/IP Coupler Unit. Standard and high-performance units can be mixed.*
• Each Coupler plus its I/O form just a single EtherCAT node on the network.
• I/O control and safety control can be integrated by connecting Units for safety.
• The IP address can be found on the label on the Unit, without using software.
• Slave configuration by Sysmac Studio can be done centrally via the controller, or on-the-spot using the Coupler's built-in USB port.
* Input per Coupler Unit: Maximum 504 bytes, Output per Coupler Unit: Maximum 504 bytes
System Configuration
System Configuration of Slave Terminals
Note: Do not make a loop connection in the communications path between Ethernet switches.
* Refer to Configuration Unit on page 8 for the NX Units that can be connected to the NX-series EtherNet/IP Coupler Unit.
1
NX-EIC
Ordering Information
Applicable standards
Refer to the OMRON website (www.ia.omron.com) or ask your OMRON representative for the most recent applicable standards for each model.
EtherNet/IP Coupler Unit
Product name Current consumption Maximum I/O power supply current Model
EtherNet/IP Coupler Unit
1.60 W or lower 10 A NX-EIC202
Automation Software Sysmac Studio
Please purchase a DVD and required number of licenses the first time you purchase the Sysmac Studio. DVDs and licenses are available individually. Each model of licenses does not include any DVD.
Product name Specifications Model
Sysmac Studio NX-I/O Edition is a limited license that
Sysmac Studio NX-I/O Edition Ver.1.@@
Sysmac Studio Standard Edition Ver.1.@@
*1. Model "SYSMAC-SE200D-64" runs on Windows 10 (64 bit). *2. The Sysmac Studio Standard Edition with license(s) (SYSMAC-SE@@@L) provides functions of the NX-I/O Edition (SYSMAC-NE001L). *3. With the Sysmac Studio Standard Edition with license(s) (SYSMAC-SE@@@L) version 1.10 or higher, you can use the setup functions for the
EtherNet/IP Coupler.
*4. Multi licenses are available for the Sysmac Studio (3, 10, 30, or 50 licenses).
provides selected functions required for EtherNet/IP Coupler settings. Because this product is a license only, you need the Sysmac Studio Standard Edition DVD media to install it.
The Sysmac Studio is the software that provides an integrated environment for setting, programming, debugging and maintenance of machine automation controllers including the NJ/NX-series CPU Units, NY­series Industrial PC, EtherCAT Slave, and the HMI.
Sysmac Studio runs on the following OS. Windows 7 (32-bit/64-bit version)/ Windows 8 (32-bit/64-bit version)/ Windows 8.1 (32-bit/64-bit version)/ Windows 10 (32-bit/64-bit version) *1
This software provides functions of the Vision Edition. Refer to your OMRON website for details such as supported models and functions.
Number of
licenses
1 license --- SYSMAC-NE001L
--­(Media only)
--­(Media only)
1 license *2 *3 *4 --- SYSMAC-SE201L
Media
Sysmac
Studio (32-bit)
DVD
Sysmac
Studio
(64-bit)
DVD
SYSMAC-SE200D
SYSMAC-SE200D-64
2
NX-EIC
Connecting Cable
Peripheral (USB) Port
Use a commercially available USB-certified cable. Specifications: USB 1.1 or 2.0 cable (A connector - B connector), 5.0 m max.
Recommended EtherNet/IP Communications Cables
For EtherNet/IP, required specification for the communications cables varies depending on the baud rate. For 100BASE-TX/10BASE-T, use a straight or cross STP (shielded twisted-pair) cable of category 5 or higher. For 1000BASE-T, use a straight or cross STP cable of category 5e or higher with double shielding (aluminum tape and braiding).
Cable with Connectors
Item Appearance
Cable with Connectors on Both Ends (RJ45/RJ45) Standard RJ45 plugs type *1 Wire Gauge and Number of Pairs: AWG26, 4-pair Cable Cable Sheath material: LSZH *2 Cable color: Yellow *3
Cable with Connectors on Both Ends (RJ45/RJ45) Rugged RJ45 plugs type *1 Wire Gauge and Number of Pairs: AWG22, 2-pair Cable Cable color: Light blue
Cable with Connectors on Both Ends (M12 Straight/M12 Straight) Shield Strengthening Connector cable *4 M12/Smartclick Connectors Wire Gauge and Number of Pairs: AWG22, 2-pair Cable Cable color: Black
Cable with Connectors on Both Ends (M12 Straight/RJ45) Shield Strengthening Connector cable *4 M12/Smartclick Connectors Rugged RJ45 plugs type Wire Gauge and Number of Pairs: AWG22, 2-pair Cable Cable color: Black
*1. Standard type cables length 0.2, 0.3, 0.5, 1, 1.5, 2, 3, 5, 7.5, 10, 15 and 20 m are available. Rugged type cables length 0.3, 0.5, 1, 2, 3, 5, 10
and 15 m are available. For details, refer to Cat.No.G019.
*2. The lineup features Low Smoke Zero Halogen cables for in-cabinet use and PUR cables for out-of-cabinet use. Although the LSZH cable is
single shielded, its communications and noise characteristics meet the standards. *3. Cables colors are available in blue, yellow, or Green. *4. For details, contact your OMRON representative.
Recommended
manufacturer
OMRON
OMRON
OMRON
OMRON
Cable length (m) Model
0.3 XS6W-6LSZH8SS30CM-Y
0.5 XS6W-6LSZH8SS50CM-Y
1 XS6W-6LSZH8SS100CM-Y
2 XS6W-6LSZH8SS200CM-Y
3 XS6W-6LSZH8SS300CM-Y
5 XS6W-6LSZH8SS500CM-Y
0.3 XS5W-T421-AMD-K
0.5 XS5W-T421-BMD-K
1 XS5W-T421-CMD-K
2 XS5W-T421-DMD-K
5 XS5W-T421-GMD-K
10 XS5W-T421-JMD-K
0.5 XS5W-T421-BM2-SS
1 XS5W-T421-CM2-SS
2 XS5W-T421-DM2-SS
3 XS5W-T421-EM2-SS
5 XS5W-T421-GM2-SS
10 XS5W-T421-JM2-SS
0.5 XS5W-T421-BMC-SS
1 XS5W-T421-CMC-SS
2 XS5W-T421-DMC-SS
3 XS5W-T421-EMC-SS
5 XS5W-T421-GMC-SS
10 XS5W-T421-JMC-SS
3
Cables / Connectors
Protrusions for removing the Unit
Unit hookup guide
Unit hookup guide
Protrusions for removing the Unit
Item Recommended manufacturer Model
Products for EtherNet/IP (100BASE-TX)
Products for EtherNet/IP (100BASE-TX)
*1. We recommend you to use above cable for EtherNet/IP and RJ45 Connector together. *2. We recommend you to use above cable for EtherNet/IP and RJ45 Assembly Connector together.
Wire Gauge and Number of Pairs: AWG24, 4-pair Cable
Wire Gauge and Number of Pairs: AWG22, 2-pair Cable
Cables
RJ45 Connectors Panduit Corporation MPS588-C *1
Cables
RJ45 Assembly Connector
Hitachi Cable, Ltd.
Kuramo Electric Co. KETH-SB *1
SWCC Showa Cable Systems Co. FAE-5004 *1
Kuramo Electric Co. KETH-PSB-OMR *2
JMACS Japan Co., Ltd. PNET/B *2
OMRON XS6G-T421-1 *2
NETSTAR-C5E SAB
× 4P CP *1
0.5
Optional Products
Product name Specification Model
Unit/Terminal Block Coding Pins
Product name
Terminal Block 8 A/B Provided 10 A NX-TBC082
Pins for 10 Units (30 terminal block pins and 30 Unit pins)
No. of terminals
Terminal number
indications
Specification
Ground terminal
mark
Terminal current
capacity
NX-AUX02
NX-EIC
Model
Accessories
End Cover (NX-END01)
One End Cover is provided together with the EtherNet/IP Coupler Unit.
4
NX-EIC
General Specification
Item Specification Enclosure Mounted in a panel Grounding method Ground to 100 Ω or less
Ambient operating temperature 0 to 55°C Ambient operating humidity 10% to 95% (with no condensation or icing) Atmosphere Must be free from corrosive gases. Ambient storage temperature 25 to 70°C (with no condensation or icing) Altitude 2,000 m max.
Operating environment
Applicable standards *2
*1. Refer to the NX-series Digital I/O Units User’s Manual (Cat. No. W521) for the vibration and shock resistance specifications of the Relay Output
Unit.
*2. Refer to the OMRON website (http://www.ia.omron.com/) or consult your OMRON representative for the most recent applicable standards for
each model.
Pollution degree Pollution degree 2 or less: Meets IEC 61010-2-201. Noise immunity Conforms to IEC 61000-4-4. 2 kV (power supply line) Overvoltage category Category II: Meets IEC 61010-2-201. EMC immunity level Zone B
Vibration resistance
Shock resistance Conforms to IEC 60068-2-27. 147 m/s2, 3 times each in X, Y, and Z directions *1
Conforms to IEC 60068-2-6. 5 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 Hz, acceleration of 9.8 m/s2, 100 min each in X, Y, and Z directions (10 sweeps of 10 min each = 100 min total) *1
cULus: Listed UL508, ANSI/ISA 12.12.01 EU: EN 61131-2, C-Tick or RCM, KC: KC Registration
EtherNet/IP Coupler Unit Specifications
Item Specification Model NX-EIC202 Number of connectable NX Units 63 Units max.*1
EtherNet/IP
Number of buffers (sockets):
• 8 message buffers for server
• No message buffers for client
• Shared buffers for UDP/IP messages and TCP/IP
Communications protocols
Modulation Baseband Link speed 100 Mbps Physical layer 100BASE-TX (IEEE 802.3) Number of connections 8 Received Packet Interval (RPI, refresh cycle) 4 to 1,000 ms Allowed communications bandwidth
addressing to the local node Topology Line, Tree, Star Ethernet Switch Layer 2 Ethernet switch
Transmission media
Transmission distance Distance between nodes: 100 m or less
NX bus I/O data size
EtherNet/IP I/O connection size
Refreshing methods Free-Run refreshing
Power supply voltage 24 VDC (20.4 to 28.8 VDC) NX Unit power supply capacity 10 W max. (Refer to Installation orientation and restrictions for details.)
Unit power supply *2
I/O power supply *2
NX Unit power consumption 1.60 W max. Current consumption from I/O power supply 10 mA max. (for 24 VDC)
*1. Refer to the NX-series Safety Control Unit User's Manual (Cat. No. Z930) for the number of Safety Control Units that can be connected. *2. Refer to the NX-series EtherNet/IP™Coupler Unit User’s Manual (Cat. No. W536) for procedures for designing the Unit power supply system
and I/O power supply system.
*3. Use a voltage that is appropriate for the I/O circuits of the NX Units and the connected external devices.
NX Unit power supply efficiency Isolation method No isolation between NX Unit power supply and Unit power supply terminals Current capacity of power
supply terminals Power supply voltage 5 to 24 VDC (4.5 to 28.8 VDC) *3 Maximum I/O power supply current Current capacity of power
supply terminals
UDP/IP and TCP/IP (Message Services)
1,000 pps
Category 5 or higher twisted-pair cable (Recommended cable: double-shielded cable with aluminum tape and braiding)
Input: 512 bytes max. (including input data, status, and unused areas) Output: 512 bytes max. (including output data and unused areas)
Input: 504 bytes max. (including input data, status, and unused areas) Output: 504 bytes max. (including output data and unused areas)
70%
4 A max.
10 A (Refer to Installation orientation and restrictions for details.)
10 A max.
messages
Maximum message size:
• Request: 492 bytes
• Response: 496 bytes
Maximum NX output data size:
• 490 bytes
Maximum NX input data size:
• 496 bytes
5
Item Specification
0 10 20 30 40 45 50 55 60
Ambient temperature [°C]
10
8
4
2
0
6
12
Unit power supply [W]
10 W output, 40°C
8.5 W output, 55°C
0 10 20 30 40 45 50 55 60
Ambient temperature [°C]
10
8
4
2
0
6
12
Unit power supply [W]
10 W output, 40 °C
6.0 W output, 55°C
0 10 20 30 40 45 50 55 60
Ambient temperature [°C]
10
8
4
2
0
6
12
°C
6 A current, 55°C
10 A current, 45
I/O power supply [A]
Dielectric strength 510 VAC for 1 min, leakage current: 5 mA max. (between isolated circuits) Insulation resistance 100 VDC, 20 MΩ min. (between isolated circuits)
Communications Connector For EtherNet/IP communications.
• RJ45 × 2 (shielded)
External connection terminals
Dimensions 46 × 100 × 71 mm (W×H×D) Weight 150 g max.
Screwless Clamping Terminal Block For Unit power supply, I/O power supply, and grounding. Removable.
Peripheral USB Port For Sysmac Studio connection.
• Physical layer: USB 2.0-compliant, B-type connector
• Transmission distance: 5 m max.
Installation orientation: 6 possible orientations Restrictions:
• Used in the upright installation orientation.
NX-EIC
Installation orientation and restrictions
• Used in any other orientation than the upright installation orientation.
6
Circuit layout
NX Unit power supply +
NX Unit power supply −
Terminal block
I/O power supply +
I/O power supply −
DIN Track contact plate
Peripheral USB port
IN communications connector
OUT communications connector
NX bus connector
UV
UV UG
UG
IOV
IOG
UNIT PWR LED
I/O PWR LED
Internal circuits
Non-isolated power supply circuits
IOV
UG
UV
IOG
UV
UG
A1
A8
B1
B8
Unit power supply
(24 VDC)
Through-wiring
for unwired
terminals.
I/O power supply
(5 to 24 VDC)
Ground to 100 Ω
or less.
NX-EIC
Item Specification
Terminal arrangement
Accessory End Cover (NX-END01): 1
7
Configuration Unit
Refer to the user's manuals for information on the NX Units that can be connected to the NX-series EtherNet/IP Coupler Unit.
EtherNet/IP Coupler Unit
Unit Model
EtherNet/IP Coupler Unit NX-EIC202
I/O Units
Unit
Digital Input Unit
Digital Output Unit
Digital Mixed I/O Unit −−−
Analog Input Unit
Analog Output Unit
Temperature Input Unit
Heater Burnout Detection Unit
2-point Units 4-point Units 8-point Units 16-point Units 32-point Units
NX-ID3317 NX-ID3343 NX-ID3417 NX-ID3443 NX-IA3117
NX-OD3121
NX-OC2633 NX-OC2733
NX-AD2603 NX-AD2604 NX-AD2608 NX-AD2203 NX-AD2204 NX-AD2208
NX-DA2603 NX-DA2605 NX-DA2203 NX-DA2205
NX-TS2101 NX-TS2102 NX-TS2104 NX-TS2201 NX-TS2202 NX-TS2204
NX-OD3153 NX-OD3256 NX-OD3257 NX-OD3268
NX-AD3603 NX-AD3604 NX-AD3608 NX-AD3203 NX-AD3204 NX-AD3208
NX-DA3603 NX-DA3605 NX-DA3203 NX-DA3205
NX-TS3101 NX-TS3102 NX-TS3104 NX-TS3201 NX-TS3202 NX-TS3204
NX-HB3101 NX-HB3201
Model
NX-ID4342 NX-ID4442
NX-OD4121 NX-OD4256 NX-OC4633
NX-AD4603 NX-AD4604 NX-AD4608 NX-AD4203 NX-AD4204 NX-AD4208
NX-ID5142-1 NX-ID5142-5 NX-ID5342 NX-ID5442
NX-OD5121 NX-OD5121-1 NX-OD5121-5 NX-OD5256 NX-OD5256-1 NX-OD5256-5
NX-MD6121-5 NX-MD6121-6 NX-MD6256-5
−−
−−−
−−−
−−−
NX-EIC
NX-ID6142-5 NX-ID6142-6
NX-OD6121-5 NX-OD6256-5
Temperature Control Units
Unit
Temperature Control Unit NX-TC2405, NX-TC2406, NX-TC2407, NX-TC2408 NX-TC3405, NX-TC3406, NX-TC3407, NX-TC3408
2CH 4CH
Model
Load Cell Input Unit
Unit Model
Load Cell Input Unit NX-RS1201
Position Interface Units
Unit
Incremental Encoder Input Unit NX-EC0112, NX-EC0122, NX-EC0132, NX-EC0142 NX-EC0212, NX-EC0222
SSI Input Unit NX-ECS112 NX-ECS212
Pulse Output Unit NX-PG0112, NX-PG0122
1CH 2CH
Model
Communications Interface Units IO-Link Master Unit
Unit Model
Communications Interface Unit
NX-CIF101, NX-CIF105, NX-CIF210
IO-Link Master Unit NX-ILM400
Unit Model
System Units Safety Control Units
Unit Model
Additional NX Unit Power Supply Unit NX-PD1000
Additional I/O Power Supply Unit NX-PF0630, NX-PF0730
I/O Power Supply Connection Unit
Shield Connection Unit NX-TBX01
NX-PC0010, NX-PC0020, NX-PC0030
Safety CPU Unit NX-SL3300 *1
Safety Input Unit NX-SIH400 *2, NX-SID800
Safety Output Unit NX-SOH200, NX-SOD400
*1. Safety CPU Unit Ver.1.1 or higher. *2. Safety Input Unit Ver.1.1 or higher.
Unit Model
8
NX-EIC
Version Information
Depending on the type and model of the Unit, some Units do not have all of the versions given in the corresponding versions. If a Unit does not have the specified version, support is provided by the oldest available version after the specified version. Refer to the user’s manuals for the specific Units for the relation between models and versions.
Connection to the NJ/NX-series CPU Unit or NY-series Industrial PC
NX-series CPU Unit or NY-series Industrial PC
EtherNet/IP Coupler Unit Corresponding unit version/version
Model Unit version
NX-EIC202
Ver.1.2 Ver.1.14 Ver.1.19 Ver.3.21 Ver.2.4 *
Ver.1.0 Not possible. Not possible. Not possible. Not possible.
Unit version of CPU Unit
or Industrial PC
Sysmac Studio version
* The CX-ConfiguratorFDT with version 2.2 or later can be used if it is connected to the peripheral USB port on the EtherNet/IP Coupler Unit.
NJ-series CPU Unit
EtherNet/IP Coupler Unit Corresponding unit version/version
Model Unit version
NX-EIC202
Ver.1.2 Ver.1.14 Ver.2.1 Ver.1.19 Ver.3.21 Ver.2.4 *
Ver.1.0 Not possible. Not possible. Not possible. Not possible. Not possible.
Unit version of CPU
Unit
* The CX-ConfiguratorFDT with version 2.2 or later can be used if it is connected to the peripheral USB port on the EtherNet/IP Coupler Unit.
Unit version of
CJ1W-EIP21
Network Configurator for
EtherNet/IP version
Sysmac Studio
version
Network
Configurator for
EtherNet/IP version
CX-ConfiguratorFDT
version
CX-
ConfiguratorFDT
version
Connection to CS/CJ/CP-series CPU Unit
CS1G/CS1H/CJ1H/CJ1M * CPU Units * Final order entry date for CJ1M:The end of March, 2021
EtherNet/IP Coupler Unit Corresponding unit version/version
Model Unit version
NX-EIC202
Unit version of CPU
Unit
Ver.1.2
Ver.1.0 Ver.1.00 *2 Ver.2.2
Ver.3.0 Ver.2.1 Ver.3.00
Unit version of
CS1W-EIP21/CJ1W-
EIP21
*1. The CX-ConfiguratorFDT with version 2.2 or later can be used if it is connected to the peripheral USB port on the EtherNet/IP Coupler Unit. *2. You can connect only to the peripheral USB port on the EtherNet/IP Coupler Unit. You cannot connect with any other path.
CJ2H-CPU6/CJ2M-CPU1/CP1H CPU Unit
EtherNet/IP Coupler Unit Corresponding unit version/version
Model Unit version
NX-EIC202
Unit version of CPU
Unit
Ver.1.2
Ver.1.0 Ver.1.00 *2 Ver.2.2
Ver.1.0 Ver.2.1 Ver.3.00
Unit version of
CJ1W-EIP21
*1. The CX-ConfiguratorFDT with version 2.2 or later can be used if it is connected to the peripheral USB port on the EtherNet/IP Coupler Unit. *2. You can connect only to the peripheral USB port on the EtherNet/IP Coupler Unit. You cannot connect with any other path.
CJ2H-CPU6-EIP CPU Unit
EtherNet/IP Coupler Unit Corresponding unit version/version
Model Unit version
NX-EIC202
Ver.1.2
Ver.1.0 Ver.1.00 *2 Ver.2.2
Unit version of CPU
Unit
Ver.1.5 Ver.2.1 Ver.3.00
*1. The CX-ConfiguratorFDT with version 2.2 or later can be used if it is connected to the peripheral USB port on the EtherNet/IP Coupler Unit. *2. You can connect only to the peripheral USB port on the EtherNet/IP Coupler Unit. You cannot connect with any other path.
Unit version of
CJ1W-EIP21
Network
Configurator for
EtherNet/IP version
Network
Configurator for
EtherNet/IP version
Network
Configurator for
EtherNet/IP version
NX-IO Configurator
version
Ver.1.00 Ver.2.4 *1
NX-IO Configurator
version
Ver.1.00 Ver.2.4 *1
NX-IO Configurator
version
Ver.1.00 Ver.2.4 *1
ConfiguratorFDT
version
ConfiguratorFDT
version
ConfiguratorFDT
version
CX-
CX-
CX-
CJ2M-CPU3 CPU Unit
EtherNet/IP Coupler Unit Corresponding unit version/version
Model Unit version
NX-EIC202
Unit version of CPU
Unit
Ver.1.2
Ver.1.0 Ver.1.00 *2 Ver.2.2
Ver.1.0 Ver.2.1 Ver.3.21
Unit version of
CJ1W-EIP21
Network
Configurator for
EtherNet/IP version
NX-IO Configurator
version
Ver.1.00 Ver.2.4 *1
*1. The CX-ConfiguratorFDT with version 2.2 or later can be used if it is connected to the peripheral USB port on the EtherNet/IP Coupler Unit. *2. You can connect only to the peripheral USB port on the EtherNet/IP Coupler Unit. You cannot connect with any other path.
CX-
ConfiguratorFDT
version
9
NX-EIC
Connection to the Sysmac Gateway
Sysmac Gateway
EtherNet/IP Coupler Unit Corresponding unit version/version
Model Unit version Sysmac Gateway version
NX-EIC202
*1. The CX-ConfiguratorFDT with version 2.2 or later can be used if it is connected to the peripheral USB port on the EtherNet/IP Coupler Unit. *2. You can connect only to the peripheral USB port on the EtherNet/IP Coupler Unit. You cannot connect with any other path.
Ver.1.2
Ver.1.0 Ver.1.00 *2 Ver.2.2
Ver.1.31 Ver.3.50
Network Configurator for
EtherNet/IP version
NX-IO Configurator
version
Ver.1.00 Ver.2.4 *1
CX-ConfiguratorFDT
version
10
NX-EIC
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
NX-EIC202
NET
(B) (D)
(E)
(C)
(F)
(C)
(G)
(A)
Eight-terminal Block
(A)
A1
A2
A3
A4
A5
A6
A7
A8
B1
B2
B3
B4
B5
B6
B7
B8
(B)
(C)
External Interface
EtherNet/IP Coupler Unit NX-EIC202
Letter Name Function
(A) NX bus connector
(B) Indicators The indicators show the current operating status of the Unit and the status of the power supply.
(C) Communications connectors These connectors are connected to the communications cables of the EtherNet/IP network.
(D) Peripheral USB port This port is used to connect to the Sysmac Studio.
(E) Terminal block The terminal block is used to connect to the power supply cables and ground wire.
(F) Rotary switches
(G) DIP switch
This connector is used to connect the EtherNet/IP Coupler Unit to the NX Unit on the right of the Coupler Unit.
The rotary switches are used to set the last octet of the IP address of the EtherNet/IP Coupler Unit as an EtherNet/IP Slave. The address is set in hexadecimal.
The DIP switch is used to set the default node address of the EtherNet/IP Coupler Unit as an EtherNet/IP slave.
Terminal Block
Symbol Name Function
(A) Terminal number indications
(B) Release holes Insert a flat-blade screwdriver into these holes to connect and remove the wires.
(C) Terminal holes The wires are inserted into these holes.
The terminal numbers (A1 to A8 and B1 to B8) are displayed. The terminal number indicators are the same regardless of the number of terminals on the terminal block, as shown above.
11
Applicable Wires
1.6 mm max. (Terminals other than ground terminals)
2.0 mm max. (Ground terminals)
2.4 mm max. (Terminals other than ground terminals)
2.7 mm max. (Ground terminals)
8 to 10 mm
Conductor length (stripping length)
Using Ferrules
If you use ferrules, attach the twisted wires to them. Observe the application instructions for your ferrules for the wire stripping length when attaching ferrules. Always use plated one-pin ferrules. Do not use unplated ferrules or two-pin ferrules.
The applicable ferrules, wires, and crimping tool are given in the following table.
Terminal types Manufacturer Ferrule model
AI0,34-8 0.34 (#22)
AI0,5-8
AI0,5-10
Terminals other than ground terminals
Phoenix Contact
AI0,75-8
AI0,75-10
AI1,0-8
AI1,0-10
AI1,5-8
AI1,5-10
Ground terminals
AI2,5-10 2.0 *1
H0.14/12 0.14 (#26)
H0.25/12 0.25 (#24)
H0.34/12 0.34 (#22)
H0.5/14
Terminals other than ground terminals
Weidmuller
H0.5/16
H0.75/14
H0.75/16
H1.0/14
H1.0/16
H1.5/14
H1.5/16
2
*1. Some AWG 14 wires exceed 2.0 mm
and cannot be used in the screwless clamping terminal block.
Applicable wire
2
(AWG))
(mm
0.5 (#20)
0.75 (#18)
1.0 (#18)
1.5 (#16)
0.5 (#20)
0.75 (#18)
1.0 (#18)
1.5 (#16)
Phoenix Contact (The figure in parentheses is the applicable wire size.) CRIMPFOX 6 (0.25 to 6 mm
Weidmueller (The figure in parentheses is the applicable wire size.) PZ6 Roto (0.14 to 6 mm
2
, AWG 26 to 10)
Crimping tool
2
, AWG 24 to 10)
NX-EIC
When you use any ferrules other than those in the above table, crimp them to the twisted wires so that the following processed dimensions are achieved.
Using Twisted Wires/Solid Wires
If you use the twisted wires or the solid wires, use the following table to determine the correct wire specifications.
Terminals
Twisted wires Solid wire
Classification Current capacity Plated Unplated Plated Unplated
2 A max.
All terminals except ground terminals
Greater than 2 A and 4 A or less
Greater than 4 A
Possible
Possible *1
Ground terminals --- Possible Possible
*1. Secure wires to the screwless clamping terminal block. Refer to the Securing Wires in the USER'S MANUAL for how to secure wires. *2. With the NX-TB@@@1 Terminal Block, use twisted wires to connect the ground terminal. Do not use a solid wire.
Wire type
Possible Possible Possible
Possible
Not Possible
*1
Not
Not Possible
Possible
Possible *2Possible
*2
Wire size
0.08 to 1.5 mm AWG28 to 16
2
2.0 mm
Conductor length (stripping length)
2
8 to 10 mm
9 to 10 mm
<Additional Information> If more than 2 A will flow on the wires, use plated wires or use ferrules.
12
NX-EIC
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
NX-EIC202
NET
48.1
80
71
65.2
104.5
100
1.5
1.5
0.55
46
Dimensions (Unit: mm)
EtherCAT Coupler Unit Only
With Cables Connected
*1
*2
100 to 120
5.8
*1. This dimension depends on the specifications of the commercially available USB-certified cable. Check the specifications of the USB cable
that is used.
*2. This is the dimension from the back of the Unit to the communications cables.
• 100 mm: When an MPS588-C Connector is used.
• 120 mm: When an XS6G-T421-1 Connector is used.
71
USB cable
Communications cable
13
End Cover
NX-EIC
12
1.5
100
1.5
71
Related Manuals
Man. No Model Manual Application Description
W536 NX-EIC@@@
NX-series EtherNet/IP Coupler Unit User’s Manual
Learning how to use an NX­series Ether-Net/IP Coupler Unit and EtherNet/IP Slave Terminals
Introduces the system, configuration methods, Unit hardware, setting methods, and functions of EtherNet/IP Slave Terminals that consist of an EtherNet/IP Coupler Unit and NX Units.
14
Terms and Conditions Agreement
Read and understand this catalog. Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments.
Warranties. (a) Exclusive Warranty. Omrons exclusive warranty is that the Products will be free from defects in materials and workmanship for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron disclaims all other warranties, express or implied. (b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omrons sole obligation hereunder shall be, at
Omrons election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or
replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty, repair, indemnity or any other claims or expenses regarding the Products unless Omrons analysis confirms that the Products were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice, recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above warranty. See http://www.omron.com/global/ or contact your Omron representative for published information.
Limitation on Liability; Etc. OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY. Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.
Suitability of Use. Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the combination of the Product in the Buyers application or use of the Product. At Buyers request, Omron will provide applicable third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine, system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product with respect to Buyers application, product or system. Buyer shall take application responsibility in all cases. NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
Programmable Products.
Omron Companies shall not be responsible for the users programming of a programmable Product, or any consequence
thereof. Performance Data.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of Omrons test conditions, and the user must correlate it to actual application requirements. Actual performance is subject to the Omrons Warranty and Limitations of Liability.
Change in Specifications. Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice to change part numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers may be assigned to fix or establish key specifications for your application. Please consult with your Omrons representative at any time to confirm actual specifications of purchased Product.
Errors and Omissions. Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical or proofreading errors or omissions.
2021.3
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
In the interest of product improvement, specifications are subject to change without notice.
(c)Copyright OMRON Corporation 2021 All Right Reserved.