Short circuit Trip AlarmSignalling switchLeft hand
side
Max. per
MPCB
1 116410J77MN-11S
1 116410J77MN-TA-11S
1 116410J77MN-T-11S
ContactsRated Operating
Current
AC15AC1
24 V240 V 240 V
NONCAAA
2- 325J77MN-20F
- 2325J77MN-02F
2- 6410J77MN-20S
- 26410J77MN-02S
Typ e
DescriptionMounting
Undervoltage ReleaseTrips the circuit-breaker when
the voltage is interrupted. Prevents the motor from being restarted accidentally when the
voltage is restored, suitable for
EMERGENCY STOP acc. to
VDE 0113
Shunt ReleaseTrips the circuit-breaker when
the release coil energized.
DescriptionTyp e
EnclosurePlastic enclose with rotary operating mechanism, lockable space for aux. contact + releaseJ77MN-PF-3R
Enclose with rotary operating mechanism yellow - red, lock space for aux. contact + releaseJ77MN-PFC-3R
Door-coupling rotaryThe door-coupling rotary operating mechanisms consist of
a knob, a coupling driver and an extension shaft (5 mm x
5 mm, lenght 330 mm). The door-coupling rotary operating
mechanisms are designed for degree of protection IP 65.
The door locking device prevents accidental opening of the
cubicle door in the ON position of the circuit-breaker. The
OFF position can be locked with up to 3 padlocks.
Link modulesMechanical and electrical connection between Motor Pro-
tection Circuit Breaker and Contactor. Up-to max. 32 A.
Electrical connection between Motor Protection Circuit
Breaker and Contactor.
place
Right hand
side
Right hand
side
Max. per
MPCB
124 V 50 Hz, 28 V 60 HzJ77MN-U-24
124 V 50 Hz, 28 V 60 HzJ77MN-S-24
Rated voltagesType
110 - 127 V 50 Hz, 120 V 60 HzJ77MN-U-110
220 - 230 V 50 Hz, 240 - 260 V 60 HzJ77MN-U-230
240 V 50 Hz, 277 V 60 HzJ77MN-U-240
380 - 400 V 50 Hz, 440 - 460 V 60 HzJ77MN-U-400
415 - 440 V 50 Hz, 460 - 480 V 60 HzJ77MN-U-415
110 - 127 V 50 Hz, 120 V 60 HzJ77MN-S-110
220 - 230 V 50 Hz, 240 - 260 V 60 HzJ77MN-S-230
240 V 50 Hz, 277 V 60 HzJ77MN-S-240
380 - 400 V 50 Hz, 440 - 460 V 60 HzJ77MN-S-400
415 - 440 V 50 Hz, 460 - 480 V 60 HzJ77MN-S-415
Mechanism black, with supporting
bracket
Mechanism; red/yellow, with supporting bracket
Mini Motor Contactor J7KNAJ77MN-VKA-3
Motor Contactor J7KNJ77MN-VKN-3
Motor Contactor J7KNGJ77MN-VKG-3
Up-to 32 AJ77MN-VD-3
Up-to 63 AJ77MN-VD-6
Up-to 100 AJ77MN-VD-9
J77MN-DC-B
J77MN-DC-RY
J77MN-VDG-6
switch gear
Low voltage
Motor Protection Circuit BreakerJ7MNI-3
Page 4
DescriptionTyp e
DIN-rail adaptorsFor mechanical fixing of circuit-breaker and contactor. With
two moveable DIN-rail clips for easy mounting & replacing.
For J7MN-3 and J7KN(G)-10 up-to
J7KN(G)-40
J77MN-HU-3
Can be connected to one 35W x 15H mm DIN-rail or two
35W x 7.5H mm DIN-rails.
For mechanical fixing of circuit-breaker and contactor. Can
be connected to one 35W x 15H mm DIN-rail or two 35W x
7.5H mm DIN-rails.
For J7MN-6 and J7KN(G)-24 up-to
J7KNG-40 and/or J7KN-62
For J7MN-9 and J7KN-50 up-to
J77MN-HU-6
J77MN-HU-9
J7KN-74
Scale cover sealablefor covering the current setting scale (1 bag with 10 units)J77MN-K
Push-in lugsfor screwing the circuit-breaker onto mounting plates. 2 units required (1 bag with 20 units)J77MN-L
Insulation barriersUp to 600 V acc.UL 489 for increased distances and clearances acc. to UL Type "E“ 4 pcs per
device (2 pcs on each side) (pack 2 units)
Insulated 3-Phase Busbar System
DescriptionVersionFor Units
(MPCB)
3-phase busbars
modular spacing = 45 mm
In = 64 A
*1
3-phase busbars
modular spacing = 54 mm
In = 64 A
*1
3-phase busbars
modular spacing = 54 mm
In = 120 A
*1
3-phase busbars
modular spacing = 63 mm
In = 120 A
*1
Shrouds for
unused terminals on the busbar system
Line side terminals
to be used with busbar systems J75-CPM-...6
In = 64 A
*1
Line side terminals
for 2 unitsJ7MN-3P
for 3 units1J75-CPM-3-45-6
J7MN-3R
for 4 units1J75-CPM-4-45-6
for 5 units
*2
for 2 unitsJ7MN-3P
for 3 units1J75-CPM-3-54-6
J7MN-3R
for 4 units1J75-CPM-4-54-6
for 5 units
*2
for 2 unitsJ7MN-6R1J75-CPM-2-54-12
for 3 units1J75-CPM-3-54-12
for 4 units
*2
for 2 unitsJ7MN-9R1J75-CPM-2-63-12
for 3 units1J75-CPM-3-63-12
for 4 units
*2
for 64 A version10J75-TA-63
for 120 A versionJ75-TA-120
IEC 60947 EN 60947
according to UL 508
IEC 60947 EN 60947
according to UL 508E
to be used with busbar systems J75-CPM-...12
In = 120 A
*1
The sum of all added currents per module must not exeed the above mentioned nominal currents!
*2
For more than 5 units (64 A) and 4 units (120 A) the system can be extended accordingly by installing an additional busbar
*1
Pack
pcs
1J75-CPM-2-45-6
1J75-CPM-5-45-6
1J75-CPM-2-54-6
1J75-CPM-5-54-6
1J75-CPM-4-54-12
1J75-CPM-4-63-12
1J75-BTC-25-IC
1J75-BTC-25-EC
1J75-BTC-50-E
J77MN-TB32
J77MN-TB100
Typ e
I-4Motor Protection Circuit Breaker J7MN
Page 5
■ Components for Fuseless Load Feeders, DIN-rail Mounting
Type of coordination „1“ 3 x 415 V 10 kA (other conditions on request)
Technical Data according to IEC/EN 60947-1, 60947-2, 60947-4-1 and VDE 0660
This table shows the rated ultimate short-circuit breaking capacity Icu
and the rated service short-circuit breaking capacity Ics of the J7MN
circuit-breakers with different operational voltages as a function of
the rated current In of the circuit-breakers. The circuit-breakers can
be fed at the top or bottom supply terminals without any reduction of
the rated data.
If the short-circuit current exceeds the rated short-circuit breaking
capacity of the circuit-breaker specified in the tables at the installation point, a back-up fuse is to be used. The maximum rated current
for the back-up fuse is specified in the tables. These fuses are only
suitable for the short-circuit-currents as indicated on the fuses.
Circuitbreaker
Rated
current In
up to AC 240V
*1
IcuIcsmax.
fuse
(gL/gG)
up to AC 400V
up to AC 415V*2
IcuIcsmax.
*3
*1
*3
fuse
(gL/gG)
up to AC 440V
up to AC 460V
*1
*2
IcuIcsmax.
fuse
(gL/gG)
up to AC 500V
up to AC 525V
IcuIcsmax.
*3
*1
*2
*3
fuse
(gL/gG)
up to AC 690V
*1
IcuIcsmax.
fuse
(gL/gG)
*3
Typ e AkAkAAkAkAAkAkAAkAkAAkAkAA
J7MN-3P 0.16 to 0.63100100--100100--100100--100100--100100--
1100100--100100--100100--100100--100100--
1.6100100--100100--100100--100100--3320
2.5100100--100100--100100--50100--3335
4100100--100100--10038501538503340
6100100--100100--5011501011403350
8100100--100100--151163108403363
10100100--50388015116368633363
13100100--5038801088065633363
175038--20151001088065803363
22403012515111008610065803363
26403012515111008610065803363
32302212515111006410054803363
J7MN-3R 0.16 to 1.0100100--100100--100100--100100--100100--
1.6100100--100100--100100--100100--100100--
2.5100100--100100--100100--100100--8835
4100100--100100--100100--100100--8840
6100100--100100--100100--100100--6650
8100100--100100--5038805038636663
10100100--100100--5038805038806663
13100100--100100--5038804232806663
17100100--5038100201580108804463
22100100--50381252015100108804463
26100100--50381252015100108804463
32100100--50381252015100108804463
J7MN-6R26100100--505012535271251291005580
32100100--505012535271251081005580
40100100--505016035271251081005580
50100100--505016035271251081005580
63100100--505016035271601081005580
J7MN-9R63100100--503816040301601291006580
75100100--503816040301608612554100
90100100--503816040301608612554125
100100100--503816040301608612554125
--No back-up fuse required
*1
10% overvoltage
*2
5% overvoltage
*3
Back up fuse required if short-circuit current at installation point > Icu
I-6Motor Protection Circuit Breaker J7MN
Page 7
Technical Data according to IEC/EN 60947-1, 60947-2, 60947-4-1 and VDE 0660
Main Circuit
Typ e J7MN-3PJ7MN-3RJ7MN-6RJ7MN-9R
Number of poles 3
Max. rated current Inmax (=max. rated operational current Ie)32 A32 A63 A100 A
Permissible ambient temperatureStorage/transport-50 to +80°C
Multiple of set current × IeMultiple of set current × Ie
IThe curve shows the mean operating current at an ambient temperature of 20°C starting from cold.
IIThe tripping characteristic of electromagnetic overcurrent releases (short-circuit releases)
The tripping characteristic of the inverse-time delayed overload releases apply for DC and AC with a frequency of 0 to 400 Hz.
t operating temperature, the tripping times of the thermal releases are reduced to approximately 25 %.
The characteristic shown here is a schematic representation of circuit-breakers for all ranges.
Current limiting characteristics and I²t characteristics are available on request.
I-8Motor Protection Circuit Breaker J7MN
Page 9
Permissible ratings of devices approved for North America
Circuit breakers J7MN as „Manual Motor Starter“
If used as „Manual Motor Starter“ the circuit breaker is always operated in combination with a short circuit device. For use with approbated fuses or circuit breakers according to UL489 or CSA22.2 No. 5
J7MN-3
Rated operational current Ie0.16 0.250.4 0.6311.62.5468101317222632 A
only. The sizes are selected according to National Electrical Code
(UL), or Canadian Electrical Code (CSA)
1
1
1
1
/
/
1
/
10
1
/
3
3
/
4
111/
8
1
1
/
/3 1/
6
3
1
/
/
2
4
1
/
111/
2
1235571/210151520 HP
355101015202030 HP
2
1
/21010 HP
/
4
3
111/
2
12233 5 71/271/2HP
2335 71/2 71/210 HP
2
1
/
/
2
2
111/
2
2
23355HP
22HP
Circuit breakers J7MN as "Combination Motor Controller Type E" and " Suitable for Group Installation"
Acc to UL508 demands a line-side 1 inch air and 2 inch creepage
distance for „Combination Motor Controller Type E“ is necessary.
Therefor circuitbreaker J7MN-3R is approved to UL 508 in combination with the Terminal block J7MN-TB32. Circuit-breakers J7MN-9R
J7MN-3R + J77MN-TB32
Rated operational current Ie0.16 0.250.4 0.6311.62.5468101317222632 A
Max. rated fuse or breaker500500 500 500 500500 500 500 500 500500 500 500 500500 500 A
are approved to UL 508 in combination with the insulation barriers
J7MN-TB100. According to CSA these terminal blocks can be omitted when the device is used as "Combination Motor Controller
Type E“.
1
1
1
1
/
/
1
/
10
1
/
3
3
/
4
111/
8
1
1
/
/3 1/
6
1
3
/
/
2
4
1
/
111/
2
1235571/210151520 HP
355101015202030 HP
2
/
4
3
111/
2
12233 5 71/271/2HP
2335 71/2 71/210 HP
2
1
/
/
2
2
111/
2
23355HP
22HP
2
switch gear
Low voltage
Motor Protection Circuit BreakerJ7MNI-9
Page 10
J7MN-6RJ7MN-9R + J77MN-TB100
Rated operational current Ie2632405063637590100 A
Max. short-circuit current240 V100 100100 100 100100100100100 kA
480 V505050505040404040 kA
600 V101010101010101010 kA
Motor load
1-phase
Motor load
3-phase
Max. rated fuse or breaker600 600 600 600600 1,000 1,000 1,000 1,000 A
Ratings of auxiliary switches and
alarm switches
Breaking capacityA600A300AC
115 V 23355 57
230 V557
230 V101015152025253040 HP
460V 202530405050607575 HP
600V25304050606075100100 HP
Combination Motor Controller Type E
Lateral auxiliary switch with
J77MN-xxS and signalling
switch J77MN-T
Q300R300DC
1
/2101515152020 HP
Transversal auxiliary switch
with J77MN-xxF
1
/21010 HP
Descriptions
Releases
Circuit-breakers J7MN are equipped with bimetallic-based, inversetime delayed overload releases and with instantaneous overcurrent
releases (electromagnetic short-circuit releases). The overload
releases can be set in accordance with the load current. The overcurrent releases are permanently set to a value 13 times the rated
current and thus enable trouble-free start-up of motors. The scale
cover can be sealed to prevent unauthorized adjustments to the set
current.
Operating mechanisms
Circuit-breakers J7MN-3P are actuated via a rocker operating mechanism and circuit-breakers J7MN-3R, J7MN-6R and J7MN-9R via a
rotary operating mechanism. An electrical signal can be output, at all
Circuit-breakers, via a signalling switch to indicate that the Circuitbreaker has tripped. All operating mechanisms can be locked in the
0 position with a padlock (shackle diameter 3.5 to 4.5 mm). The
J7MN Circuit-breakers fulfil the isolation characteristics specified in
IEC 60947-2.
Operating conditions
Circuit-breakers J7MN are suitable for use in any climate. They are
designed for operation in enclosed rooms under normal conditions
(e. g. no dust, corrosive vapours or harmful gases). Suitable enclosures must be provided for installation in dusty or damp rooms. Circuit-breakers J7MN can also be fed from below. In order to prevent
premature tripping due to phase failure sensitivity, the three conducting paths must always be uniformly loaded. The conducting paths
must be connected in series in the case of single-phase loads.
Short-circuit protection
The short-circuit releases of J7MN circuit-breakers disconnect the
faulty load feeder from the system in the event of a short circuit and
thus prevent any further damage from being caused. Circuit-breakers with a short-circuit breaking capacity of 50 kA or 100 kA at a voltage of 400 V AC are practically short-circuit-proof at this voltage, as
higher short-circuit currents are not usually encountered at the installation point. Back-up fuses are only necessary if the short-circuit current at the installation point exceeds the rated ultimate short-circuit
breaking capacity of the circuit-breakers.
Motor protection
The tripping characteristics of J7MN circuit-breakers are designed
mainly to protect three-phase induction motors. The circuit-breakers
are therefore also referred to as Manual Motor Starters. The current
of the motor to be protected is set with the aid of the scale.
Line protection
J7MN Circuit-breakers for motor protection are also suitable for line
protection. The J7MN Circuit-breakers fulfil the isolation conditions of
IEC 60 947-3 as well as the additional test conditions for circuitbreakers with isolation characteristics specified in IEC 60947-2. Taking IEC 60 204-1 into consideration, they can thus be implemented
as main and EMERGENCY STOP switches. Door-coupling rotary
operating mechanism do not fulfil the isolation characteristics.