Solid-state Timer H3FA 3
■ Ratings
Note: 1. Permissible ripple: 20% max. (3% max. at 5, 6 V DC-operated models)
2. Supply voltage can be selected by short-circuiting (12 V DC) or opening (24 V DC) the specified terminals.
■ Characteristics
Note: 1. Add or subtract 10 ms to the ratings when using a timer with a rated time of 1 s.
2. Applicable to contact output models.
■ Life-test Curve (Reference Values)
Item H3FA-A/ H3FA-B
H3FA-AU/ H3FA-BU
H3FA-SA/ H3FA-SB
H3FA-SAU/ H3FA-SBU
Rated supply voltage 5 V DC, 6V DC, 12V DC, 24 V DC (See note 1.) 5/6 V DC (See note 1.)
12/24 V DC (See notes 1 and 2.)
Operating voltage range 5 V DC: 90% to 110% of rated supply voltage
6, 12, 24 V DC: 85% to 110% of rated supply voltage
5/6 V DC: 90% to 110% of rated supply voltage
12/24 V DC: 85% to 110% of rated supply voltage
Power consumption 5, 6 V DC: approx. 230 mW
12 V DC: approx. 270 mW
24 V DC: approx. 330 mW
5/6 V DC: approx. 80 mW
12 V DC: approx. 100 mW
24 V DC: approx. 240 mW
Control outputs Contact output: SPST-NO + SPST-NC,
3 A at 250 V AC with resistive load,
Minimum applied load: 10 mA at 5 V DC
(Failure level: P, reference value)
Solid-state output: 150 mA max. at 30 V DC
Residual voltage: 1.0 V max.
Ambient temperature Operating:
−10°C to 55°C (with no icing)
Storage:
−25°C to 65°C (with no icing)
Ambient humidity 35% to 85%
X
Mean X/Mean value × 100 ≤ 20 (%) max.
Where,
Accuracy of operating time ±0.5% FS max. (See note 1.)
Setting error 0 to 30 % FS max. (at 20°C , at rated voltage)
Reset time 10 ms max.
Influence of voltage ±1% FS max. (2% FS max. for 5, 6, 5/6 V DC-operated models)
Influence of temperature ±5% FS max. (See note 1.)
Insulation resistance 100 M
Ω min. (at 500 V DC)
Dielectric strength 1,500 V AC, 50/60 Hz for 1 min (between control output and operating circuit) (See note 2.)
1,000 V AC, 50/60 Hz for 1 min (between contacts not located next to each other) (See note 2.)
Vibration resistance Destruction: 10 to 55 Hz with 0.375-mm single amplitude in 3 directions for 1 hour each
Malfunction: 10 to 55 Hz with 0.25-mm single amplitude in 3 directions for 10 minutes each
Shock resistance
Destruction: 1,000 m/s
2
3 times each in 6 directions
Malfunction: 100 m/s
2
3 times each in 6 directions
Life expectancy Mechanical: 10,000,000 operations min. (under no load at 1,800 operations/h)
Electrical: 100,000 operations min. (3 A at 250 V AC, resistive load at 1,800 operations/h)
Approved safety standards UL508, CSA C22.2 No.14
Weight Contact output models: approx. 15 g
Solid-state output models: approx. 10 g
1,000
700
500
300
100
70
50
30
10
5
01234
Load current