functionsON start, Signal ON/OFF-delay, Signal OFF-delay, and Interval
Start, reset,TypeNo-voltage input—
gate inputs*ON impedance1 kΩ max.
Residual voltage 1 V max.
OFF impedance100 kΩ min.
ControlTypeTime limitDPDT contactNPN or PNP**SPDT contactSPDT contact
outputtransistor
Instantaneous————
Max. load5 A, 250 VAC100 mA, 30 VDC5 A, 250 VAC5 A, 250 VAC
(p.f. = 1)max. with 2 VDC(p.f. = 1)(p.f. = 1)
residual voltage
Min. load100 mA, 5 VDC—100 mA, 5 VDC100 mA, 5 VDC
Repeat accuracy±1% FS max. (1% ±10 ms in the 1.2 s range)±2% FS max.
Setting error±10% FS ±0.05 s max.
Resetting systemPower reset with minimum power opening time of 0.1 s
Resetting time0.1 s max.
IndicatorsPower (green LED), Output ON (orange LED)Power (green LED)
MaterialsPlastic case, knob
MountingDIN rail track
ConnectionsTerminal screws
Weight120 g (4.7 oz.)
ApprovalsUL/CSA/CE (EMC) (LV)
Operating ambient temperature-10° to 55°C (14° to 131°F)
Humidity35 to 85% RH
Vibration Mechanical durability10 to 55 Hz, 1.5 mm (0.06 in) double10 to 55 Hz with 0.75 mm (0.03 in) double
amplitude each in three directionsamplitude each in three directions
Malfunction durability10 to 55 Hz, 0.5 mm (0.02 in) double10 to 55 Hz with 0.5 mm (0.02 in) double
amplitude each in three directionsamplitude each in three directions
ShockMechanical durability30 G each in three directions100 G each in three directions
Malfunction durability10 G each in three directions10 G each in three directions
Variation due to voltage change±0.5% FS max., ±0.5% ±10 ms max. in the 1.2 s range±2% FS max.
Variation due to temperature change±2% FS max., ±0.2% ±10 ms max. in the 1.2 s range±5% FS max.
Insulation resistance100 MΩ min. at 500 VDC
Dielectric strength2,000 VAC, 50/60 Hz for 1 minute between current-carrying and non-current-carrying parts
2,000 VAC, 50/60 Hz for 1 minute between control output terminals and operating circuit
1,000 VAC, 50/60 Hz for 1 minute between contacts not located next to each other
Service lifeMechanical20 million operations minimum at 1,800 operations/hour
Electrical100,000 operations minimum at 5 A, 250 VAC (p.f. = 1)
H3DR
NOTE:
*H3DR-P has start input only; H3DR-M has no inputs.
**The internal circuits are optically isolated from the output, enabling application of either NPN or PNP transistor devices.
3
H3DRH3DR
Engineering Data
■ ELECTRICAL SERVICE LIFE
10,000
5,000
1,000
500
Electrical operations (thousands)
100
01 234 5
30 VDC L/R = 7 ms
250 VAC (p.f. = 0.4)
Load current (A)
250 VAC/30 VDC
(p.f. = 1)
Reference:
A maximum current of 0.15 A can be switched at 125 VDC
(p.f. = 1). Maximum current of 0.1 A can be switched if L/R is
7 ms. In both cases, a life of 100,000 operations can be
expected.
The minimum applicable load is 10 mA at 5 VDC.
Timing Charts
■ H3DR-M ON-DELAY ONLY TIMER
Note:The minimum reset time is 0.1 s and the minimum signal input delay is 0.05 s.
The letter "t" in the timing charts stands for the set time and "t–a" means that the period is less than the time set.
Output modeTiming chart
A: ON-delay
PowerON
(A1 and A2)OFF
Output relayON
(NC, 15 and 16)OFF
Output relayON
(NO, 15 and 18)OFF
Power indicatorON
OFF
■ H3DR-P MULTI-MODE TIMER WITH POWER-OFF RESET
Output modeTiming chart
A: ON-delay
Short-circuit start
input C1 and A2.
PowerON
(A1 and A2)OFF
StartON
(C1 and A2)OFF
Output relayON
(NC, 15 and 16)OFF
Output relayON
(NO, 15 and 18)OFF
output indicator
Power indicatorON
OFF
4
H3DR
H3DR-P TIMING CHARTS continued
Output modeTiming chart
B: Repeat cycle
signal OFF start
Short-circuit start
input C1 and A2.
PowerON
(A1 and A2)OFF
StartON
(C1 and A2)OFF
Output relayON
(NC, 15 and 16)OFF
Output relayON
(NO, 15 and 18)OFF
output indicator
H3DR
B2: Repeat cycle
signal ON start
Short-circuit start
input C1 and A2.
C: Signal ON/OFF
delay
Short-circuit start
input C1 and A2.
Power indicatorON
PowerON
(A1 and A2)OFF
StartON
(C1 and A2)OFF
Output relayON
(NC, 15 and 16)OFF
Output relayON
(NO, 15 and 18)OFF
output indicator
Power indicatorON
PowerON
(A1 and A2)OFF
StartON
(C1 and A2)OFF
OFF
OFF
Output relayON
(NC, 15 and 16)OFF
Output relayON
(NO, 15 and 18)OFF
output indicator
Power indicatorON
OFF
NOTE:The minimum reset time is 0.1 s and the minimum signal input delay is 0.05 s.
The letter "t" in the timing charts stands for the set time and "t–a" means that the period is less than the time set.
5
H3DRH3DR
H3DR-P TIMING CHARTS continued
Output modeTiming chart
D: Signal OFF-delay
Short-circuit start
input C1 and A2.
E: Interval
Short-circuit start
input C1 and A2.
PowerON
(A1 and A2)OFF
StartON
(C1 and A2)OFF
Output relayON
(NC, 15 and 16)OFF
Output relayON
(NO, 15 and 18)OFF
output indicator
Power indicatorON
PowerON
(A1 and A2)OFF
StartON
(C1 and A2)OFF
Output relayON
(NC, 15 and 16)OFF
Output relayON
(NO, 15 and 18)OFF
output indicator
Power indicatorON
OFF
OFF
■ H3DR-A❑ MULTI-MODE TIMER WITH EXTERNAL RESET AND GATE INPUTS
Output modeTiming chart
A: ON-delay
Short-circuit start
input C1 and A2.
B: Repeat cycle
signal OFF start
Short-circuit start
input C1 and A2.
PowerON
(A1 and A2)OFF
StartON
(C1 and A2)OFF
ResetON
(B1 and A2)OFF
Output (NC)ON
Output (NO)ON
output indicatorOFF
Power indicatorON
PowerON
(A1 and A2)OFF
StartON
(C1 and A2)OFF
ResetON
(B1 and A2)OFF
Output (NC)ON
Output (NO)ON
output indicatorOFF
Power indicatorON
OFF
OFF
OFF
OFF
6
H3DR
H3DR-A❑ TIMING CHARTS continued
Output modeTiming chart
B2: Repeat cycle
signal ON start
Short-circuit start
input C1 and A2.
C: Signal ON/OFF
delay
Short-circuit start
input C1 and A2.
PowerON
(A1 and A2)OFF
StartON
(C1 and A2)OFF
ResetON
(B1 and A2)OFF
Output (NC)ON
Output (NO)ON
output indicatorOFF
Power indicatorON
PowerON
(A1 and A2)OFF
StartON
(C1 and A2)OFF
ResetON
(B1 and A2)OFF
Output (NC)ON
Output (NO)ON
output indicatorOFF
Power indicatorON
OFF
OFF
OFF
OFF
H3DR
D: Signal OFF-delay
Short-circuit start
input C1 and A2.
E: Interval
Short-circuit start
input C1 and A2.
PowerON
(A1 and A2)OFF
StartON
(C1 and A2)OFF
ResetON
(B1 and A2)OFF
Output (NC)ON
Output (NO)ON
output indicatorOFF
Power indicatorON
PowerON
(A1 and A2)OFF
StartON
(C1 and A2)OFF
ResetON
(B1 and A2)OFF
Output (NC)ON
Output (NO)ON
output indicatorOFF
Power indicatorON
OFF
OFF
OFF
OFF
7
H3DRH3DR
H3DR-A❑ TIMING CHARTS continued
Gate signal input in mode A (ON-delay).
PowerON
(A1 and A2)OFF
StartON
(C1 and A2)OFF
GateON
(D1 and A2)OFF
ResetON
(B1 and A2)OFF
Output (NO)ON
output indicatorOFF
Dimensions
Unit: mm (inch)
■ TIMERS
H3DR-A❑H3DR-M
Note: The set time is the
sum of t1 and t2.
Wiring terminals accept M3 fork or a single wire.
54
H3DR-P
22.5
(0.89)
75
(2.95)
(2.13)
23.5
(0.93)
100 (3.94)
■ MOUNTING TRACK AND ACCESSORIES
PFP-100N, PFP-50N DIN Rail TrackPFP-M End PlatePFP-S Spacer
76.5 (3.01)
8
H3DR
Connections
■ TERMINAL ARRANGEMENT
PartInput terminal number (no voltage only)Power supply terminal numbersOutput terminal numbers
numberStartResetGateCOMAC (common), DC –AC (hot), DC +COMNCNO
H3DR-AC1B1D1A2A2A1151618
(Connection to NPN open collector output sensor)(Connection to a voltage output sensor)
12 to 24 VDC
sensor power supply
Sensor
+ DC power
– supply
Timer
Start/reset and
others
Input (0 V)
A
2
Timer
Start/reset and
others
Input (0 V)
A
2
Operates with relay ONOperates with transistor ON
12 to 24 VDC
sensor power supply
Sensor
Operates with transistor ON
+ DC power
– supply
Timer
Start/reset and
others
Input (0 V)
A
2
No-Voltage Input Signal Levels
No-contact inputContact input
Short-circuit levelOpen level
Transistor ONTransistor OFFUse contacts which can adequately
Residual voltage: 1 V max.Impedance when OFF: 100 kΩ min.switch 0.1 mA at 5 V
Impedance when ON: 1 kΩ max.
9
H3DRH3DR
Installation
■ POWER SUPPLIES
An AC power supply can be connected to the power input
terminals without regarding polarity. A DC power supply must
be connected to the power input terminals as designated
according to the polarity of the terminals.
A DC power supply can be connected if its ripple factor is 20%
or less and the mean voltage is within the rated operating
voltage range of the timer.
Connect the power supply voltage through a relay or switch in
such a way that the voltage reaches a fixed value at once or
the timer may not be reset or a timer error could result.
■ INPUT AND OUTPUT PRECAUTIONS
An appropriate input is applied to the input signal terminals of
the timer when the input terminal C1 and the common terminal
A2 for the input signal are short-circuited.
WARNING: Do not connect an input terminal to any terminal
other than the common terminal. Do not apply a voltage across
input and common terminals or the internal circuits of the timer
may be damaged.
For the power supply of an input device, use an isolating
transformer, of which the primary and secondary windings are
mutually isolated and the secondary winding is not grounded.
Use a commercial power supply with a sine-wave frequency of
50 or 60 Hz to supply 100 or 200 VAC.
When connecting a relay or a transistor as an external signal
input device, pay attention to the following points to prevent
short-circuiting due to a sneak current to the transformerless
power supply. If a relay or transistor is connected to two or
more timers, the input terminals of these timers must be wired
properly so that they will not be different in phase or the
terminals will be short-circuited to one another as shown below.
* Power supply terminal A2 is a common terminal for the input
signal (S) to the timer. Never use terminal A1 as the common
terminal for this purpose, otherwise the internal circuit of the
timer may be damaged.
** Do not connect a relay or any other load between these two
points, otherwise the internal circuit of the timer may be
damaged due to the high-tension voltage applied to the input
terminals.
■ ENVIRONMENT
When using the timer in an area with excess electrical noise,
separate the timer, wiring and the equipment which generates
the input signals as far as possible from the noise sources. It is
also recommended to shield the input signal wiring to prevent
electrical interference.
Organic solvents (such as paint thinner), as well as very acidic
or basic solutions can damage the outer casing of the timer.
10
H3DR
Operation
H3DR
■ SELECTING TIME RANGES
Scale range
display
Time unit
display
Be sure to turn power OFF before changing the time range.
Otherwise the timer will malfunction. Use a Phillips screwdriver
to select the time unit (seconds, minutes, hours or 10 hours)
and the time scale range two upper turn pots. Set the time
using the large central knob. On H3DR-A and H3DR-P timers,
a fine-tuning adjustment helps match the timing exactly to the
application.
Timing unitSeconds Minutes Hours10 hours
Setting0Instantaneous output
Timex 0.10.12 to 1.21.2 to 12
scalex 11.2 to 1212 to 120
CAUTION: Do not change the time unit, rated time, or
operating mode while the timer is in operation because a
malfunction could result.
Power ON indicator
Time setting knob
Operation
mode selector
Mode display
A: ON-delay
B: Repeat cycle, signal OFF start
B2: Repeat cycle, signal ON start
C: Signal ON/OFF-delay
D: Signal OFF-delay
E: Interval
Identification panel
for user notation
Time unit selector:
sec, min, hr, 10h
Output indicator
Fine-tuning
adjustment
Mounting
■ TRACK MOUNTING
MountingRemoval
Mount the H3DR timer as close to horizontal as possible.When removing the H3DR timer, pull out portion (C) with a flatTo mount the timer on DIN rail track, hook portion (A) of thetrack.
timer to the top edge of the track and then depress the timer in
the direction of (B).The H3DR can be mounted and removed easily by allowing a
blade screwdriver and remove the timer from the mounting
minimum distance of 30 mm (1.18 in) between the H3DR and
other equipment.
NOTE: ALL DIMENSIONS ARE IN MILLIMETERS. To convert millimeters into inches, divide by 25.4.
OMRON ELECTRONICS, INC.OMRON CANADA, INC.
One East Commerce Drive885 Milner Avenue
Schaumburg, IL 60173Scarborough, Ontario M1B 5V8
1-800-55-OMRON416-286-6465
Cat. No. GC TI811/97Specifications subject to change without notice.Printed in the U.S.A.
11
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.