Omron H3CR-A8, H3CR-A8S, H3CR-A8E, H3CR-F, H3CR-FN User Manual

...
Solid-state Timer H3CR 1
Solid-state Timer
H3CR
DIN 48 × 48-mm Multifunctional Timer Series
• Conforms to EN61812-1 and IEC60664-1 4 kV/2 for Low Voltage, and EMC Directives.
• Approved by UL and CSA.
• Six-language instruction manual provided.
Broad Line-up of H3CR Series
Contents
Solid-state Timer
H3CR-A........................................................................................................................................... 2
H3CR-F........................................................................................................................................... 24
H3CR-G .......................................................................................................................................... 30
H3CR-H .......................................................................................................................................... 37
Common to ALL Timers
Operation ........................................................................................................................................ 45
Accessories..................................................................................................................................... 47
Safety Precautions.......................................................................................................................... 51
H3CR
Multifunctional Timer Twin Timer Star-delta Timer Power OFF-delay Timer
H3CR-GH3CR-F
Note: H3CR-AS, H3CR-A8S: Transistor output models
11-pin model
8-pin model
11-pin model
8-pin model
8-pin model
8-pin model
11-pin model
H3CR-A
H3CR-A H3CR-AS H3CR-AP H3CR-A8 H3CR-A8S H3CR-A8E
8-pin with instantaneous contact output model
H3CR-F H3CR-FN H3CR-F-300 H3CR-FN-300 H3CR-F8 H3CR-F8N H3CR-F8-300 H3CR-F8N-300
H3CR-G8L H3CR-G8EL
H3CR-HRL H3CR-H8L H3CR-H8RL
H3CR-H
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. Refer to Warranty and Application Considerations (page 52), and Safety Precautions (page 22, 44, 51).
2 Solid-state Multi-functional Timer H3CR-A
Solid-state Multi-functional Timer
H3CR-A
DIN 48 × 48-mm State-of-the-art Multifunctional Timer
• A wider power supply range reduces the number of timer mod­els kept in stock.
• A wide range of applications through six or four operating modes.
• Reduced power consumption. (Except for H3CR-A8E)
• Enables easy sequence checks through instantaneous outputs for a zero set value at any time range.
• Length, when panel-mounted with a Socket, of 80 mm or less.
• Time Setting Rings enable consistent settings and limit the set­ting range.
• Panel Covers enable various panel designs.
• PNP input models available.
• Rich variety of inputs: Start, reset, and gate functions (11-pin models and -AP models)
Model Number Structure
Model Number Legend
Note: This model number legend includes combinations that are not available. Before ordering, please check the List of Models on page 3 for avail-
ability.
1. Number of Pins
None: 11-pin models 8: 8-pin models
2. Input Type for 11-pin Models
None: No-voltage input (NPN type) P: Voltage input (PNP type)
3. Output
None: Relay output (DPDT) S: Transistor output (NPN/PNP universal use) E: Relay output (SPDT) with instantaneous relay output (SPDT)
4. Suffix
300: Dual mode models (signal ON/OFF-delay and one-shot) 301: Double time scale (range) models (0.1 s to 600 h)
5. Supply Voltage
100-240AC/100-125DC: 100 to 240 VAC/100 to 125 VDC 24-48AC/12-48DC: 24 to 48 VAC/12 to 48 VDC 24-48AC/DC: 24 to 48 VAC/VDC (Only for H3CR-A8E)
H3CR-A@ @ @ - @ @
123 45
Solid-state Multi-functional Timer H3CR-A 3
Ordering Information
List of Models
11-pin Models
8-pin Models
Supply voltage
Note: 1. Specify both the model number and supply voltage when ordering.
Example: H3CR-A 100-240AC/100-125DC
2. The operating modes are as follows A: ON-delay D: Signal OFF-delay B: Flicker OFF start E: Interval B2: Flicker ON start G: Signal ON/OFF-delay C: Signal ON/OFF-delay J: One-shot
Output Supply voltage Input type Time range Operating mode
(See note 2)
Model
(See note 1.)
Contact 100 to 240 VAC (50/60 Hz)/
100 to 125 VDC
No-voltage input 0.05 s to 300 h Six multi-modes: A, B,
B2, C, D, E
H3CR-A
24 to 48 VAC (50/60 Hz)/ 12 to 48 VDC
100 to 240 VAC (50/60 Hz)/ 100 to 125 VDC
Dual-modes: G, J H3CR-A-300
24 to 48 VAC (50/60 Hz)/ 12 to 48 VDC
100 to 240 VAC (50/60 Hz)/ 100 to 125 VDC
Voltage input Six multi-modes: A, B,
B2, C, D, E
H3CR-AP
24 to 48 VAC (50/60 Hz)/ 12 to 48 VDC
100 to 240 VAC (50/60 Hz)/ 100 to 125 VDC
No-voltage input 0.1 s to 600 h H3CR-A-301
24 to 48 VAC (50/60 Hz)/ 12 to 48 VDC
Transistor (Photocoupler)
24 to 48 VAC (50/60 Hz)/ 12 to 48 VDC
0.05 s to 300 h H3CR-AS
Output Supply voltage Input type Time range Operating mode
(See note 2)
Model
(See note 1.)
Contact 100 to 240 VAC (50/60 Hz)/
100 to 125 VDC
No-input available 0.05 s to 300 h Four multi-modes: A,
B2, E, J (Power supply start)
H3CR-A8
24 to 48 VAC (50/60 Hz)/ 12 to 48 VDC
100 to 240 VAC (50/60 Hz)/ 100 to 125 VDC
0.1 s to 600 h H3CR-A8-301
24 to 48 VAC (50/60 Hz)/ 12 to 48 VDC
Transistor (Photocoupler)
24 to 48 VAC (50/60 Hz)/ 12 to 48 VDC
0.05 s to 300 h H3CR-A8S
Time-limit contact and instantaneous contact
100 to 240 VAC (50/60 Hz)/ 100 to 125 VDC
H3CR-A8E
24 to 48 VAC/VDC (50/60 Hz)
4 Solid-state Multi-functional Timer H3CR-A
Accessories (Order Separately)
Note: 1. Y92A-48G is a finger safe terminal cover which is attached to the P3G-08 or P3GA-11 Socket.
2. The Time Setting Ring and Panel Cover are sold together.
3. Hold-down Clips are sold in sets of two.
Specifications
General
*The internal circuits are optically isolated from the output. This enables universal application as NPN or PNP transistor.
Name/specifications Models
Flush Mounting Adapter Y92F-30
Y92F-73
Y92F-74
Mounting Track 50 cm (l)
× 7.3 mm (t) PFP-50N
1 m (l)
× 7.3 mm (t) PFP-100N
1 m (l)
× 16 mm (t) PFP-100N2
End Plate PFP-M
Spacer PFP-S
Protective Cover Y92A-48B
Track Mounting/ Front Connecting Socket
8-pin P2CF-08
8-pin, finger safe type P2CF-08-E
11-pin P2CF-11
11-pin, finger safe type P2CF-11-E
Back Connecting Socket 8-pin P3G-08
8-pin, finger safe type P3G-08 with Y92A-48G (See note 1)
11-pin P3GA-11
11-pin, finger safe type P3GA-11 with Y92A-48G (See note 1)
Time Setting Ring Setting a specific time Y92S-27
Limiting the setting range Y92S-28
Panel Cover (See note 2) Light gray (5Y7/1) Y92P-48GL
Black (N1.5) Y92P-48GB
Medium gray (5Y5/1) Y92P-48GM
Hold-down Clip (See note 3) For PL08 and PL11 Sockets Y92H-7
For PF085A Socket Y92H-8
Item H3CR-A/-AS H3CR-AP H3CR-A8/-A8S H3CR-A8E
Operating mode A: ON-delay
B: Flicker OFF start B2: Flicker ON start C: Signal ON/OFF-delay D: Signal OFF-delay E: Interval G: Signal ON/OFF-delay (Only for H3CR-A-300) J: One-shot (Only for H3CR-A-300)
A: ON-delay (power supply start) B2: Flicker ON start (power supply start) E: Interval (power supply start) J: One-shot (power supply start)
Pin type 11-pin 8-pin
Input type No-voltage input Voltage input ---
Time-limit output type H3CR-A/-A8/-AP: Relay output (DPDT)
H3CR-AS/-A8S: Transistor output (NPN/PNP universal)*
Relay output (SPDT)
Instantaneous output type --- Relay output (SPDT)
Mounting method DIN track mounting, surface mounting, and flush mounting
Approved standards UL508, CSA C22.2 No.14, NK, Lloyds
Conforms to EN61812-1 and IEC60664-1 (VDE0110) 4kV/2. Output category according to EN60947-5-1 for Timers with Contact Outputs. Output category according to EN60947-5-2 for Timers with Transistor Outputs.
Solid-state Multi-functional Timer H3CR-A 5
Time Ranges
Note: When the time setting knob is turned below “0” until the point where the time setting knob stops, the output will operate instantaneously at
all time range settings.
Standard (0.05-s to 300-h) Models
Double (0.1-s to 600-h) Models
Ratings
Note: 1. DC ripple rate: 20% max. if the power supply incorporates a single-phase, full-wave rectifier.
2. Do not use an inverter output as the power supply. Refer to Power Supplies in Safety Precautions for All Timers on page 51 for details.
3. Models with 24-to-48-VAC or 12-to-48-VDC power supply have inrush current. Caution is thus required when turning ON and OFF power
to the Timer with a non-contact output from a device such as a sensor. (Models with an inrush current of approximately 50 mA and a 24­VDC power supply are available (the H3CR-A-302 and H3CR-A8-302).)
4. The values are for when the terminals 2 and 7 and terminals 10 and 6 are short-circuited, and include the consumption current of the input circuit.
5. Refer to Power Supplies in Safety Precautions for All Timers on page 51 when using the Timer together with a 2-wire AC proximity sensor.
Time unit s (sec) min (min) h (hrs)
×10 h (10 h)
Full scale setting
1.2 0.05 to 1.2 0.12 to 1.2 1.2 to 12
3 0.3 to 3 3 to 30
12 1.2 to 12 12 to 120
30 3 to 30 30 to 300
Time unit s (sec) min (min) h (hrs) ×10 h (10 h)
Full scale setting
2.4 0.1 to 2.4 0.24 to 2.4 2.4 to 24
6 0.6 to 6 6 to 60
24 2.4 to 24 24 to 240
60 6 to 60 60 to 600
Rated supply voltage (See notes 1, 2, and 5.) 100 to 240 VAC (50/60 Hz)/100 to 125 VDC, 24 to 48 VAC (50/60 Hz)/12 to 48 VDC (24 to 48 VAC/VDC for H3CR-
A8E) (See note3.)
Operating voltage range 85% to 110% of rated supply voltage (90% to 110% at 12 VDC)
Powe r r es et Minimum power-opening time: 0.1 s
Input No-voltage Input
ON impedance: 1 k max. ON residual voltage: 1 V max. OFF impedance: 100 k
min.
Voltage Input Max. permissible capacitance between inputs lines (terminals 6 and 7): 1,200 pF Load connectable in parallel with inputs (terminals 6 and 7).
100 to 240 VAC/100 to 125 VDC
High (logic) level: 85 to 264 VAC/85 to 137.5 VDC Low (logic) level: 0 to 10 VAC/0 to 10 VDC
24 to 48 VAC/12 to 48 VDC
High (logic) level: 20.4 to 52.8 VAC/10.8 to 52.8 VDC Low (logic) level: 0 to 2.4 VAC/0 to 1.2 VDC
Power consumption H3CR-A/-A8
100 to 240 VAC/100 to 125 VDC
(When at 240 VAC, 60 Hz)
Relay ON: approx. 2.0 VA (1.6 W) Relay OFF: approx. 1.3 VA (1.1 W)
24 to 48 VAC/12 to 48 VDC
(When at 24 VDC)
Relay ON: approx. 0.8 W Relay OFF: approx. 0.2 W
H3CR-AP (See note 3)
100 to 240 VAC/100 to 125 VDC
(When at 240 VAC, 60 Hz)
Relay ON: approx. 2.5 VA (2.2 W) (See note 4.) Relay OFF: approx. 1.8 VA (1.7 W) (See note 4.)
24 to 48 VAC/12 to 48 VDC
(When at 24 VDC)
Relay ON: approx. 0.9 W (See note 4.) Relay OFF: approx. 0.3 W (See note 4.)
H3CR-A8E
100 to 240 VAC/100 to 125 VDC
(When at 240 VAC, 60 Hz)
Relay ON/OFF: approx. 2 VA (0.9 W)
24 to 48 VAC/VDC
(When at 24 VDC)
Relay ON/OFF: approx. 0.9 W
H3CR-AS/-A8S
24 to 48 VAC/12 to 48 VDC
(When at 24 VDC)
Output ON: 0.3 W Output OFF: 0.2 W
Control outputs Time limit contacts: 5 A at 250 VAC/30 VDC, 0.15 A at 125 VDC, resistive load (cos
φ = 1)
Transistor output: Open collector (NPN/PNP), 100 mA max. at 30 VDC max.,
residual voltage: 2 V max.
Instantaneous contact: 5 A at 250 VAC/30 VDC, 0.15 A at 125 VDC, resistive load (cos
φ = 1)
6 Solid-state Multi-functional Timer H3CR-A
Characteristics
Note: 1. The value is ±5% FS +100 ms to 0 ms max. when the C, D, or G mode signal of the H3CR-AP is OFF.
2. Refer to the Life-test Curve.
Accuracy of operating time
±0.2% FS max. (±0.2%±10 ms max. in a range of 1.2 s)
Setting error
±5% FS ±50 ms (See note 1)
Reset time Min. power-opening time: 0.1 s max.
Min. pulse width: 0.05 s (H3CR-A/-AS)
Reset voltage 10% max. of rated supply voltage
Influence of voltage
±0.2% FS max. (±0.2%±10 ms max. in a range of 1.2 s)
Influence of temperature
±1% FS max. (±1%±10 ms max. in a range of 1.2 s)
Insulation resistance 100 M
min. (at 500 VDC)
Dielectric strength 2,000 VAC (1,000 VAC for H3CR-A@S), 50/60 Hz for 1 min (between current-carrying metal parts and exposed non-
current-carrying metal parts) 2,000 VAC (1,000 VAC for H3CR-A@S), 50/60 Hz for 1 min (between control output terminals and operating circuit) 2,000 VAC, 50/60 Hz for 1 min (between contacts of different polarities) 1,000 VAC, 50/60 Hz for 1 min (between contacts not located next to each other) 2,000 VAC, 50/60 Hz for 1 min (between input and control output terminals and operation circuit) for H3CR-AP
Impulse withstand voltage
3 kV (between power terminals) for 100 to 240 VAC/100 to 125 VDC, 1 kV for 24 to 48 VAC/12 to 48 VDC
4.5 kV (between current-carrying terminal and exposed non-current-carrying metal parts) for 100 to 240 VAC/100 to 125 VDC, 1.5 kV for 24 to 48 VAC/12 to 48 VDC and 24 to 48 VAC/VDC
Noise immunity
±1.5 kV (between power terminals) and ±600 V (between no-voltage input terminals), square-wave noise by noise
simulator (pulse width: 100 ns/1
µs, 1-ns rise)
Static immunity Malfunction: 8 kV
Destruction: 15 kV
Vibration resistance Destruction: 10 to 55 Hz with 0.75-mm single amplitude each in 3 directions for 2 hours each
Malfunction: 10 to 55 Hz with 0.5-mm single amplitude each in 3 directions for 10 minutes each
Shock resistance
Destruction: 1,000 m/s
2
3 times each in 6 directions
Malfunction: 100 m/s
2
3 times each in 6 directions
Ambient temperature Operating:
10°C to 55°C (with no icing)
Storage:
25°C to 65°C (with no icing)
Ambient humidity Operating: 35% to 85%
Life expectancy Mechanical: 20,000,000 operations min. (under no load at 1,800 operations/h)
Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 1,800 operations/h) (See note 2)
EMC (EMI) EN61812-1
Emission Enclosure: EN55011 Group 1 class A Emission AC Mains: EN55011 Group 1 class A (EMS) EN61812-1 Immunity ESD: IEC61000-4-2: 6 kV contact discharge (level 3)
8 kV air discharge (level 3) Immunity RF-interference from AM Radio Waves: IEC61000-4-3: 10 V/m (80 MHz to 1 GHz) (level 3) Immunity RF-interference from Pulse-modulated Radio Waves:IEC61000-4-3: 10 V/m (900
±5 MHz) (level 3)
Immunity Conducted Disturbance: IEC61000-4-6: 10 V (0.15 to 80 MHz) (level 3) Immunity Burst: IEC61000-4-4: 2 kV power-line (level 3)
2 kV I/O signal-line (level 4) Immunity Surge: IEC61000-4-5: 1 kV line to line (level 3)
2 kV line to ground (level 3)
Case color Light gray (Munsell 5Y7/1)
Degree of protection IP40 (panel surface)
Weight Approx. 90 g
Solid-state Multi-functional Timer H3CR-A 7
Life-test Curve
10,000
5,000
1,000
500
100
Load current (A)
30 VDC L/R = 7 ms
250 VAC (cosφ = 0.4)
Switching operations (x 10
3
)
250 VAC/30 VDC (cosφ = 1)
Reference: A maximum current of 0.15 A can be switched at 125 VDC (cosφ = 1)
and a maximum current of 0.1 A can be switched if L/R is 7 ms. In both cases, a life of 100,000 operations can be expected. The minimum applicable load is 10 mA (100 mA for H3CR-A8E) at 5 VDC (failure level: P).
8 Solid-state Multi-functional Timer H3CR-A
Connections
Block Diagrams
H3CR-A/AS
AC (DC) input
Output circuit
Reset input, start input, and gate input
Input circuit
Power supply circuit
Oscillation circuit
Counting circuit
Zero setting detection circuit
Time range/ unit selectors
Operating mode selector
Indicator circuit
Power-ON indicator
Output-ON indicator
H3CR-AP
AC (DC) input
Output circuit
Start
Input circuit
Power supply circuit
Zero setting detection circuit
Oscillation circuit
Counting circuit
Time range/ unit selectors
Operating mode selector
Indicator circuit
Power-ON indicator
Output-ON indicator
Solid-state Multi-functional Timer H3CR-A 9
I/O Functions
Note: H3CR-AP incorporates start input only.
H3CR-A8/A8S
AC (DC) input
Output circuit
Power supply circuit
Zero setting detection circuit
Oscillation circuit
Counting circuit
Time range/ unit selectors
Operating mode selector
Indicator circuit
Power-ON indicator
Output-ON indicator
H3CR-A8E
AC (DC) input
Output circuit
Power supply circuit
Zero setting detection circuit
Oscillation circuit
Counting circuit
Time range/ unit selectors
Operating mode selector
Indicator circuit
Power-ON indicator
Output-ON indicator
Instantaneous output circuit
Inputs (for -A/
-AS models)
Start Starts time-measurement.
Reset Interrupts time-measurement and resets time-measurement value. No time-measurement is made and
control output is OFF while the reset input is ON.
Gate Prohibits time-measurement.
Outputs Control output Outputs are turned ON according to designated output mode when preset value is reached.
10 Solid-state Multi-functional Timer H3CR-A
Terminal Arrangement
Note: The delayed contact of conventional Timers was indicated as
The contact symbol of the H3CR-A is indicated as because its operating mode is six multi-modes (four multi-modes for the H3CR-A8).
11-pin Models
Note: Terminals 1, 3, 4, and 8 are empty. Terminals 2, 5, 6, 7, and 10
are the same as for the H3CR-A.
Note: 1. Terminal 5 is empty.
2. Separate power supplies can be used for the Timer and in-
puts.
8-pin Models
Note: Terminals 1, 3, 4, and 5 are empty. Terminals 2 and 7 are the
same as for the H3CR-A8.
H3CR-A/-A-300/-A-301 (Contact Output)
Reset input
Start input
Gate input
Power supply
H3CR-AS (Transistor Output)
Power supply
Reset input
Start input
Gate input
Power supply
Start input
H3CR-AP (Contact Output)
H3CR-A8/-A8-301 (Contact Output)
Power supply
H3CR-A8S (Transistor Output)
Power supply
H3CR-A8E (Contact Output)
Power supply
Solid-state Multi-functional Timer H3CR-A 11
Input Connections
H3CR-A/-AS
5 6 7
2
+
5 6 7
2
+
5 6 7
2
The inputs of the H3CR-A/-AS are no-voltage (short-circuit or open) inputs.
No-voltage Input Signal Levels
No-contact Input Contact Input No-contact Input
No-voltage Inputs
Sensor
Timer
Gate Start Reset
Operates with transistor ON
Timer
Operates with relay ON
Gate Start Reset
Input (0 V)
Sensor
Timer
Operates with transistor ON
Gate Start Reset
Input (0 V)
(Connection to NPN open collector output sensor.)
12 to 24 VDC (sensor power supply)
DC power supply
Input (0 V)
No-contact input
1. Short-circuit level Transistor ON Residual voltage: 1 V max. Impedance when ON: 1 k max.
2. Open level Transistor OFF Impedance when OFF: 100 k min.
Contact input
Use contacts which can adequate­ly switch 0.1 mA at 5 V
(Connection to a voltage
output sensor.)
12 to 24 VDC (sensor power supply)
DC power supply
12 Solid-state Multi-functional Timer H3CR-A
H3CR-AP
6
10
7
6
10
7
22
6
10
7
2
+
+
The start input of the H3CR-AP is voltage input. (Voltage imposition or open)
Voltage Input Signal Levels
No-contact Input No-contact Input Contact Input
Sensor
Timer
Start
Operates with PNP transistor ON
Operates with NPN transistor ON
Timer
Sensor
Timer
Operates with relay ON
Voltage Inputs
Input 0V
Start
Input 0V
Start
Input 0V
AC power supply
DC power supply
(Connection to PNP open collector output sensor)
12 to 24 VDC (sensor power supply)
DC power supply
Powe r supply (+)
Powe r supply ()
(Connection to NPN open collector output sensor)
12 to 24 VDC (sensor power supply)
DC power supply
Powe r supply (+)
Powe r supply ()
Note: The input circuit is isolated from the
power supply circuit. Thus, an NPN transistor can be connected.
Powe r supply (+)
Powe r supply ()
Note: Refer to the signal levels in the fol-
lowing table and be aware of the minimum applicable load of the relay.
No-contact input
1. Transistor ON Residual voltage: 1 V max. The voltage between terminals 6 and 7 must be 10.8 VDC min.
2. Transistor OFF Leakage current: 0.01 mA max. The voltage between terminals 6 and 7 must be 1.2 VDC max.
Contact input
Use contacts that can adequately switch 0.1 mA at each oper­ating voltage. The voltage between terminals 6 and 7 with contacts ON or OFF must satisfy the specified value.
Contacts ON 100-to-240-VAC and 100-to-125-VDC models: 85 to 264 VAC or 85 to 137.5 VDC 24-to-48-VAC and 12-to-48-VDC models: 20.4 to 52.8 VAC or
10.8 to 52.8 VDC
Contacts OFF 100-to-240-VAC and 100-to-125-VDC models: 0 to 10 VAC or 0 to 10 VDC 24-to-48-VAC and 12-to-48-VDC models: 0 to 2.4 VAC or 0 to
1.2 VDC
Solid-state Multi-functional Timer H3CR-A 13
Operation
Timing Chart
Note: 1. The minimum power-opening time (“Rt”) is 0.1 s.
2. The minimum input pulse width (for start, reset) is 0.05 s.
3. The letter “t” in the timing charts stands for the set time and “t–a” means that the period is less than the time set.
4. Power supply start in mode J is also possible for H3CR-A8/-A8E/-A8S/-A8-301 models.
5. Refer to page 19 for application examples.
H3CR-A/-AS/-AP*
*H3CR-AP model incorporates start input only.
Operating
mode
Timing chart
A: ON-delay
B: Flicker OFF start
B2: Flicker ON start
C: Signal ON/ OFF­delay
t t
t
Powe r
Start
Reset
Output relay (NC)
Power indicator
Powe r
Output
Basic operation
Output relay (NO) (Output indicator)
Start
(See note)
Note: Start input is invalid while the
Timer is in operation.
t t t t
Basic operation
Powe r
Output
Powe r
Power indicator
Start
Reset
Output relay (NC)
Output relay (NO) (Output indicator)
Start
(See note)
Note: Start input is invalid while
the Timer is in operation.
t
t
t t
Basic operation
Powe r
Output
Powe r
Start
Reset
Power indicator
Output relay (NC)
Output relay (NO) (Output indicator)
Start
(See note)
Note: Start input is invalid while the
Timer is in operation.
tttt
Basic operation
Powe r
Output
Powe r
Start
Reset
Output relay (NC)
Power indicator
Output relay (NO) (Output indicator)
Start
(See note)
Note: Start input is valid and re-
triggerable while the Timer is in operation.
14 Solid-state Multi-functional Timer H3CR-A
Gate Signal Input
D: Signal OFF­delay
E: Interval
G: Signal ON/ OFF­delay
J: One-shot out­put
Operating
mode
Timing chart
t
Basic operation
Powe r
Output
Output relay (NC)
Power indicator
Powe r
Start
Reset
Output relay (NO) (Output indicator)
Start
(See note)
Note: Start input is valid and
re-triggerable while the Timer is in operation.
t
Powe r
Start
Reset
Output relay (NC)
Power indicator
Powe r
Output
Output relay (NO) (Output indicator)
Basic operation
Start
(See note)
Note: Start input is valid and
re-triggerable while the Timer is in opera­tion.
tttt
Basic operation
Powe r
Output
Powe r
Start
Reset
Output relay (NC)
Power indicator
Output relay (NO) (Output indicator)
Start
(See note)
Note: Start input is valid and re-triggera-
ble while the Timer is in operation.
t
Basic operation
Output
Powe r
Powe r
Start
Reset
Output relay (NC)
Power indicator
Output relay (NO) (Output indicator)
1±0.6 s (Fixed)
1±0.6 s (Fixed)
Start
(See note)
1±0.6 s (Fixed)
Note: Start input is valid and re-
triggerable while the Timer is in operation.
t1 t2
Powe r
Start
Gate
Reset
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
Output relay
Note: 1. This timing chart indicates the gate input in op-
erating mode A (ON-delay operation).
2. The set time is the sum of t
1 and t2.
3. H3CR-AP model incorporates start input only.
Solid-state Multi-functional Timer H3CR-A 15
H3CR-A8/-A8S
Note: 1. The minimum power-opening time (“Rt”) is 0.1 s.
2. The letter “t” in the timing charts stands for the set time and “t–a” means that the period is less than the time set.
Operating
mode
Timing chart
A: ON-delay
B
2
:
Flicker ON start
E: Interval
J: One-shot out­put
t
Powe r
Output
Basic operation
Powe r
Output relay (NC)
Output relay (NO) (output indicator)
Powe r indicator
t t t t
Powe r
Powe r
Output
Basic operation
Output relay (NC)
Output relay (NO) (output indicator)
Powe r indicator
t
Powe r
Output
Basic operation
Powe r
Output relay (NC)
Output relay (NO) (output indicator)
Powe r indicator
t
Powe r
Powe r
Output
Basic operation
Output relay (NC)
Output relay (NO) (output indicator)
Powe r indicator
1±0.6 s (Fixed)
1±0.6 s (Fixed)
1±0.6 s (Fixed)
16 Solid-state Multi-functional Timer H3CR-A
H3CR-A8E
Note: 1. The minimum power-opening time (“Rt”) is 0.1 s.
2. The letter “t” in the timing charts stands for the set time and “t–a” means that the period is less than the time set.
Operating
mode
Timing chart
A: ON-delay
B
2
:
Flicker ON start
E: Interval
J: One-shot out­put
t
Powe r
Power indicator
Powe r
Output
Basic operation
Output relay (NC)
Output relay (NO) (output indicator)
Instantaneous output relay (NC)
Instantaneous output relay (NO)
t ttt
Powe r
Power indicator
Powe r
Output
Basic operation
Output relay (NC)
Output relay (NO) (output indicator)
Instantaneous output relay (NC)
Instantaneous output relay (NO)
t
Powe r
Output
Basic operation
Powe r
Power indicator
Output relay (NC)
Output relay (NO) (output indicator)
Instantaneous output relay (NC)
Instantaneous output relay (NO)
t
Powe r
Power indicator
Powe r
Output
Basic operation
(Fixed) (Fixed)
Output relay (NC)
Output relay (NO) (output indicator)
Instantaneous output relay (NC)
Instantaneous output relay (NO)
1±0.6 s (Fixed)