Omron H3CR-A8, H3CR-A8S, H3CR-A8E, H3CR-F, H3CR-FN User Manual

...
Solid-state Timer H3CR 1
Solid-state Timer
H3CR
DIN 48 × 48-mm Multifunctional Timer Series
• Conforms to EN61812-1 and IEC60664-1 4 kV/2 for Low Voltage, and EMC Directives.
• Approved by UL and CSA.
• Six-language instruction manual provided.
Broad Line-up of H3CR Series
Contents
Solid-state Timer
H3CR-A........................................................................................................................................... 2
H3CR-F........................................................................................................................................... 24
H3CR-G .......................................................................................................................................... 30
H3CR-H .......................................................................................................................................... 37
Common to ALL Timers
Operation ........................................................................................................................................ 45
Accessories..................................................................................................................................... 47
Safety Precautions.......................................................................................................................... 51
H3CR
Multifunctional Timer Twin Timer Star-delta Timer Power OFF-delay Timer
H3CR-GH3CR-F
Note: H3CR-AS, H3CR-A8S: Transistor output models
11-pin model
8-pin model
11-pin model
8-pin model
8-pin model
8-pin model
11-pin model
H3CR-A
H3CR-A H3CR-AS H3CR-AP H3CR-A8 H3CR-A8S H3CR-A8E
8-pin with instantaneous contact output model
H3CR-F H3CR-FN H3CR-F-300 H3CR-FN-300 H3CR-F8 H3CR-F8N H3CR-F8-300 H3CR-F8N-300
H3CR-G8L H3CR-G8EL
H3CR-HRL H3CR-H8L H3CR-H8RL
H3CR-H
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. Refer to Warranty and Application Considerations (page 52), and Safety Precautions (page 22, 44, 51).
2 Solid-state Multi-functional Timer H3CR-A
Solid-state Multi-functional Timer
H3CR-A
DIN 48 × 48-mm State-of-the-art Multifunctional Timer
• A wider power supply range reduces the number of timer mod­els kept in stock.
• A wide range of applications through six or four operating modes.
• Reduced power consumption. (Except for H3CR-A8E)
• Enables easy sequence checks through instantaneous outputs for a zero set value at any time range.
• Length, when panel-mounted with a Socket, of 80 mm or less.
• Time Setting Rings enable consistent settings and limit the set­ting range.
• Panel Covers enable various panel designs.
• PNP input models available.
• Rich variety of inputs: Start, reset, and gate functions (11-pin models and -AP models)
Model Number Structure
Model Number Legend
Note: This model number legend includes combinations that are not available. Before ordering, please check the List of Models on page 3 for avail-
ability.
1. Number of Pins
None: 11-pin models 8: 8-pin models
2. Input Type for 11-pin Models
None: No-voltage input (NPN type) P: Voltage input (PNP type)
3. Output
None: Relay output (DPDT) S: Transistor output (NPN/PNP universal use) E: Relay output (SPDT) with instantaneous relay output (SPDT)
4. Suffix
300: Dual mode models (signal ON/OFF-delay and one-shot) 301: Double time scale (range) models (0.1 s to 600 h)
5. Supply Voltage
100-240AC/100-125DC: 100 to 240 VAC/100 to 125 VDC 24-48AC/12-48DC: 24 to 48 VAC/12 to 48 VDC 24-48AC/DC: 24 to 48 VAC/VDC (Only for H3CR-A8E)
H3CR-A@ @ @ - @ @
123 45
Solid-state Multi-functional Timer H3CR-A 3
Ordering Information
List of Models
11-pin Models
8-pin Models
Supply voltage
Note: 1. Specify both the model number and supply voltage when ordering.
Example: H3CR-A 100-240AC/100-125DC
2. The operating modes are as follows A: ON-delay D: Signal OFF-delay B: Flicker OFF start E: Interval B2: Flicker ON start G: Signal ON/OFF-delay C: Signal ON/OFF-delay J: One-shot
Output Supply voltage Input type Time range Operating mode
(See note 2)
Model
(See note 1.)
Contact 100 to 240 VAC (50/60 Hz)/
100 to 125 VDC
No-voltage input 0.05 s to 300 h Six multi-modes: A, B,
B2, C, D, E
H3CR-A
24 to 48 VAC (50/60 Hz)/ 12 to 48 VDC
100 to 240 VAC (50/60 Hz)/ 100 to 125 VDC
Dual-modes: G, J H3CR-A-300
24 to 48 VAC (50/60 Hz)/ 12 to 48 VDC
100 to 240 VAC (50/60 Hz)/ 100 to 125 VDC
Voltage input Six multi-modes: A, B,
B2, C, D, E
H3CR-AP
24 to 48 VAC (50/60 Hz)/ 12 to 48 VDC
100 to 240 VAC (50/60 Hz)/ 100 to 125 VDC
No-voltage input 0.1 s to 600 h H3CR-A-301
24 to 48 VAC (50/60 Hz)/ 12 to 48 VDC
Transistor (Photocoupler)
24 to 48 VAC (50/60 Hz)/ 12 to 48 VDC
0.05 s to 300 h H3CR-AS
Output Supply voltage Input type Time range Operating mode
(See note 2)
Model
(See note 1.)
Contact 100 to 240 VAC (50/60 Hz)/
100 to 125 VDC
No-input available 0.05 s to 300 h Four multi-modes: A,
B2, E, J (Power supply start)
H3CR-A8
24 to 48 VAC (50/60 Hz)/ 12 to 48 VDC
100 to 240 VAC (50/60 Hz)/ 100 to 125 VDC
0.1 s to 600 h H3CR-A8-301
24 to 48 VAC (50/60 Hz)/ 12 to 48 VDC
Transistor (Photocoupler)
24 to 48 VAC (50/60 Hz)/ 12 to 48 VDC
0.05 s to 300 h H3CR-A8S
Time-limit contact and instantaneous contact
100 to 240 VAC (50/60 Hz)/ 100 to 125 VDC
H3CR-A8E
24 to 48 VAC/VDC (50/60 Hz)
4 Solid-state Multi-functional Timer H3CR-A
Accessories (Order Separately)
Note: 1. Y92A-48G is a finger safe terminal cover which is attached to the P3G-08 or P3GA-11 Socket.
2. The Time Setting Ring and Panel Cover are sold together.
3. Hold-down Clips are sold in sets of two.
Specifications
General
*The internal circuits are optically isolated from the output. This enables universal application as NPN or PNP transistor.
Name/specifications Models
Flush Mounting Adapter Y92F-30
Y92F-73
Y92F-74
Mounting Track 50 cm (l)
× 7.3 mm (t) PFP-50N
1 m (l)
× 7.3 mm (t) PFP-100N
1 m (l)
× 16 mm (t) PFP-100N2
End Plate PFP-M
Spacer PFP-S
Protective Cover Y92A-48B
Track Mounting/ Front Connecting Socket
8-pin P2CF-08
8-pin, finger safe type P2CF-08-E
11-pin P2CF-11
11-pin, finger safe type P2CF-11-E
Back Connecting Socket 8-pin P3G-08
8-pin, finger safe type P3G-08 with Y92A-48G (See note 1)
11-pin P3GA-11
11-pin, finger safe type P3GA-11 with Y92A-48G (See note 1)
Time Setting Ring Setting a specific time Y92S-27
Limiting the setting range Y92S-28
Panel Cover (See note 2) Light gray (5Y7/1) Y92P-48GL
Black (N1.5) Y92P-48GB
Medium gray (5Y5/1) Y92P-48GM
Hold-down Clip (See note 3) For PL08 and PL11 Sockets Y92H-7
For PF085A Socket Y92H-8
Item H3CR-A/-AS H3CR-AP H3CR-A8/-A8S H3CR-A8E
Operating mode A: ON-delay
B: Flicker OFF start B2: Flicker ON start C: Signal ON/OFF-delay D: Signal OFF-delay E: Interval G: Signal ON/OFF-delay (Only for H3CR-A-300) J: One-shot (Only for H3CR-A-300)
A: ON-delay (power supply start) B2: Flicker ON start (power supply start) E: Interval (power supply start) J: One-shot (power supply start)
Pin type 11-pin 8-pin
Input type No-voltage input Voltage input ---
Time-limit output type H3CR-A/-A8/-AP: Relay output (DPDT)
H3CR-AS/-A8S: Transistor output (NPN/PNP universal)*
Relay output (SPDT)
Instantaneous output type --- Relay output (SPDT)
Mounting method DIN track mounting, surface mounting, and flush mounting
Approved standards UL508, CSA C22.2 No.14, NK, Lloyds
Conforms to EN61812-1 and IEC60664-1 (VDE0110) 4kV/2. Output category according to EN60947-5-1 for Timers with Contact Outputs. Output category according to EN60947-5-2 for Timers with Transistor Outputs.
Solid-state Multi-functional Timer H3CR-A 5
Time Ranges
Note: When the time setting knob is turned below “0” until the point where the time setting knob stops, the output will operate instantaneously at
all time range settings.
Standard (0.05-s to 300-h) Models
Double (0.1-s to 600-h) Models
Ratings
Note: 1. DC ripple rate: 20% max. if the power supply incorporates a single-phase, full-wave rectifier.
2. Do not use an inverter output as the power supply. Refer to Power Supplies in Safety Precautions for All Timers on page 51 for details.
3. Models with 24-to-48-VAC or 12-to-48-VDC power supply have inrush current. Caution is thus required when turning ON and OFF power
to the Timer with a non-contact output from a device such as a sensor. (Models with an inrush current of approximately 50 mA and a 24­VDC power supply are available (the H3CR-A-302 and H3CR-A8-302).)
4. The values are for when the terminals 2 and 7 and terminals 10 and 6 are short-circuited, and include the consumption current of the input circuit.
5. Refer to Power Supplies in Safety Precautions for All Timers on page 51 when using the Timer together with a 2-wire AC proximity sensor.
Time unit s (sec) min (min) h (hrs)
×10 h (10 h)
Full scale setting
1.2 0.05 to 1.2 0.12 to 1.2 1.2 to 12
3 0.3 to 3 3 to 30
12 1.2 to 12 12 to 120
30 3 to 30 30 to 300
Time unit s (sec) min (min) h (hrs) ×10 h (10 h)
Full scale setting
2.4 0.1 to 2.4 0.24 to 2.4 2.4 to 24
6 0.6 to 6 6 to 60
24 2.4 to 24 24 to 240
60 6 to 60 60 to 600
Rated supply voltage (See notes 1, 2, and 5.) 100 to 240 VAC (50/60 Hz)/100 to 125 VDC, 24 to 48 VAC (50/60 Hz)/12 to 48 VDC (24 to 48 VAC/VDC for H3CR-
A8E) (See note3.)
Operating voltage range 85% to 110% of rated supply voltage (90% to 110% at 12 VDC)
Powe r r es et Minimum power-opening time: 0.1 s
Input No-voltage Input
ON impedance: 1 k max. ON residual voltage: 1 V max. OFF impedance: 100 k
min.
Voltage Input Max. permissible capacitance between inputs lines (terminals 6 and 7): 1,200 pF Load connectable in parallel with inputs (terminals 6 and 7).
100 to 240 VAC/100 to 125 VDC
High (logic) level: 85 to 264 VAC/85 to 137.5 VDC Low (logic) level: 0 to 10 VAC/0 to 10 VDC
24 to 48 VAC/12 to 48 VDC
High (logic) level: 20.4 to 52.8 VAC/10.8 to 52.8 VDC Low (logic) level: 0 to 2.4 VAC/0 to 1.2 VDC
Power consumption H3CR-A/-A8
100 to 240 VAC/100 to 125 VDC
(When at 240 VAC, 60 Hz)
Relay ON: approx. 2.0 VA (1.6 W) Relay OFF: approx. 1.3 VA (1.1 W)
24 to 48 VAC/12 to 48 VDC
(When at 24 VDC)
Relay ON: approx. 0.8 W Relay OFF: approx. 0.2 W
H3CR-AP (See note 3)
100 to 240 VAC/100 to 125 VDC
(When at 240 VAC, 60 Hz)
Relay ON: approx. 2.5 VA (2.2 W) (See note 4.) Relay OFF: approx. 1.8 VA (1.7 W) (See note 4.)
24 to 48 VAC/12 to 48 VDC
(When at 24 VDC)
Relay ON: approx. 0.9 W (See note 4.) Relay OFF: approx. 0.3 W (See note 4.)
H3CR-A8E
100 to 240 VAC/100 to 125 VDC
(When at 240 VAC, 60 Hz)
Relay ON/OFF: approx. 2 VA (0.9 W)
24 to 48 VAC/VDC
(When at 24 VDC)
Relay ON/OFF: approx. 0.9 W
H3CR-AS/-A8S
24 to 48 VAC/12 to 48 VDC
(When at 24 VDC)
Output ON: 0.3 W Output OFF: 0.2 W
Control outputs Time limit contacts: 5 A at 250 VAC/30 VDC, 0.15 A at 125 VDC, resistive load (cos
φ = 1)
Transistor output: Open collector (NPN/PNP), 100 mA max. at 30 VDC max.,
residual voltage: 2 V max.
Instantaneous contact: 5 A at 250 VAC/30 VDC, 0.15 A at 125 VDC, resistive load (cos
φ = 1)
6 Solid-state Multi-functional Timer H3CR-A
Characteristics
Note: 1. The value is ±5% FS +100 ms to 0 ms max. when the C, D, or G mode signal of the H3CR-AP is OFF.
2. Refer to the Life-test Curve.
Accuracy of operating time
±0.2% FS max. (±0.2%±10 ms max. in a range of 1.2 s)
Setting error
±5% FS ±50 ms (See note 1)
Reset time Min. power-opening time: 0.1 s max.
Min. pulse width: 0.05 s (H3CR-A/-AS)
Reset voltage 10% max. of rated supply voltage
Influence of voltage
±0.2% FS max. (±0.2%±10 ms max. in a range of 1.2 s)
Influence of temperature
±1% FS max. (±1%±10 ms max. in a range of 1.2 s)
Insulation resistance 100 M
min. (at 500 VDC)
Dielectric strength 2,000 VAC (1,000 VAC for H3CR-A@S), 50/60 Hz for 1 min (between current-carrying metal parts and exposed non-
current-carrying metal parts) 2,000 VAC (1,000 VAC for H3CR-A@S), 50/60 Hz for 1 min (between control output terminals and operating circuit) 2,000 VAC, 50/60 Hz for 1 min (between contacts of different polarities) 1,000 VAC, 50/60 Hz for 1 min (between contacts not located next to each other) 2,000 VAC, 50/60 Hz for 1 min (between input and control output terminals and operation circuit) for H3CR-AP
Impulse withstand voltage
3 kV (between power terminals) for 100 to 240 VAC/100 to 125 VDC, 1 kV for 24 to 48 VAC/12 to 48 VDC
4.5 kV (between current-carrying terminal and exposed non-current-carrying metal parts) for 100 to 240 VAC/100 to 125 VDC, 1.5 kV for 24 to 48 VAC/12 to 48 VDC and 24 to 48 VAC/VDC
Noise immunity
±1.5 kV (between power terminals) and ±600 V (between no-voltage input terminals), square-wave noise by noise
simulator (pulse width: 100 ns/1
µs, 1-ns rise)
Static immunity Malfunction: 8 kV
Destruction: 15 kV
Vibration resistance Destruction: 10 to 55 Hz with 0.75-mm single amplitude each in 3 directions for 2 hours each
Malfunction: 10 to 55 Hz with 0.5-mm single amplitude each in 3 directions for 10 minutes each
Shock resistance
Destruction: 1,000 m/s
2
3 times each in 6 directions
Malfunction: 100 m/s
2
3 times each in 6 directions
Ambient temperature Operating:
10°C to 55°C (with no icing)
Storage:
25°C to 65°C (with no icing)
Ambient humidity Operating: 35% to 85%
Life expectancy Mechanical: 20,000,000 operations min. (under no load at 1,800 operations/h)
Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 1,800 operations/h) (See note 2)
EMC (EMI) EN61812-1
Emission Enclosure: EN55011 Group 1 class A Emission AC Mains: EN55011 Group 1 class A (EMS) EN61812-1 Immunity ESD: IEC61000-4-2: 6 kV contact discharge (level 3)
8 kV air discharge (level 3) Immunity RF-interference from AM Radio Waves: IEC61000-4-3: 10 V/m (80 MHz to 1 GHz) (level 3) Immunity RF-interference from Pulse-modulated Radio Waves:IEC61000-4-3: 10 V/m (900
±5 MHz) (level 3)
Immunity Conducted Disturbance: IEC61000-4-6: 10 V (0.15 to 80 MHz) (level 3) Immunity Burst: IEC61000-4-4: 2 kV power-line (level 3)
2 kV I/O signal-line (level 4) Immunity Surge: IEC61000-4-5: 1 kV line to line (level 3)
2 kV line to ground (level 3)
Case color Light gray (Munsell 5Y7/1)
Degree of protection IP40 (panel surface)
Weight Approx. 90 g
Solid-state Multi-functional Timer H3CR-A 7
Life-test Curve
10,000
5,000
1,000
500
100
Load current (A)
30 VDC L/R = 7 ms
250 VAC (cosφ = 0.4)
Switching operations (x 10
3
)
250 VAC/30 VDC (cosφ = 1)
Reference: A maximum current of 0.15 A can be switched at 125 VDC (cosφ = 1)
and a maximum current of 0.1 A can be switched if L/R is 7 ms. In both cases, a life of 100,000 operations can be expected. The minimum applicable load is 10 mA (100 mA for H3CR-A8E) at 5 VDC (failure level: P).
8 Solid-state Multi-functional Timer H3CR-A
Connections
Block Diagrams
H3CR-A/AS
AC (DC) input
Output circuit
Reset input, start input, and gate input
Input circuit
Power supply circuit
Oscillation circuit
Counting circuit
Zero setting detection circuit
Time range/ unit selectors
Operating mode selector
Indicator circuit
Power-ON indicator
Output-ON indicator
H3CR-AP
AC (DC) input
Output circuit
Start
Input circuit
Power supply circuit
Zero setting detection circuit
Oscillation circuit
Counting circuit
Time range/ unit selectors
Operating mode selector
Indicator circuit
Power-ON indicator
Output-ON indicator
Solid-state Multi-functional Timer H3CR-A 9
I/O Functions
Note: H3CR-AP incorporates start input only.
H3CR-A8/A8S
AC (DC) input
Output circuit
Power supply circuit
Zero setting detection circuit
Oscillation circuit
Counting circuit
Time range/ unit selectors
Operating mode selector
Indicator circuit
Power-ON indicator
Output-ON indicator
H3CR-A8E
AC (DC) input
Output circuit
Power supply circuit
Zero setting detection circuit
Oscillation circuit
Counting circuit
Time range/ unit selectors
Operating mode selector
Indicator circuit
Power-ON indicator
Output-ON indicator
Instantaneous output circuit
Inputs (for -A/
-AS models)
Start Starts time-measurement.
Reset Interrupts time-measurement and resets time-measurement value. No time-measurement is made and
control output is OFF while the reset input is ON.
Gate Prohibits time-measurement.
Outputs Control output Outputs are turned ON according to designated output mode when preset value is reached.
10 Solid-state Multi-functional Timer H3CR-A
Terminal Arrangement
Note: The delayed contact of conventional Timers was indicated as
The contact symbol of the H3CR-A is indicated as because its operating mode is six multi-modes (four multi-modes for the H3CR-A8).
11-pin Models
Note: Terminals 1, 3, 4, and 8 are empty. Terminals 2, 5, 6, 7, and 10
are the same as for the H3CR-A.
Note: 1. Terminal 5 is empty.
2. Separate power supplies can be used for the Timer and in-
puts.
8-pin Models
Note: Terminals 1, 3, 4, and 5 are empty. Terminals 2 and 7 are the
same as for the H3CR-A8.
H3CR-A/-A-300/-A-301 (Contact Output)
Reset input
Start input
Gate input
Power supply
H3CR-AS (Transistor Output)
Power supply
Reset input
Start input
Gate input
Power supply
Start input
H3CR-AP (Contact Output)
H3CR-A8/-A8-301 (Contact Output)
Power supply
H3CR-A8S (Transistor Output)
Power supply
H3CR-A8E (Contact Output)
Power supply
Solid-state Multi-functional Timer H3CR-A 11
Input Connections
H3CR-A/-AS
5 6 7
2
+
5 6 7
2
+
5 6 7
2
The inputs of the H3CR-A/-AS are no-voltage (short-circuit or open) inputs.
No-voltage Input Signal Levels
No-contact Input Contact Input No-contact Input
No-voltage Inputs
Sensor
Timer
Gate Start Reset
Operates with transistor ON
Timer
Operates with relay ON
Gate Start Reset
Input (0 V)
Sensor
Timer
Operates with transistor ON
Gate Start Reset
Input (0 V)
(Connection to NPN open collector output sensor.)
12 to 24 VDC (sensor power supply)
DC power supply
Input (0 V)
No-contact input
1. Short-circuit level Transistor ON Residual voltage: 1 V max. Impedance when ON: 1 k max.
2. Open level Transistor OFF Impedance when OFF: 100 k min.
Contact input
Use contacts which can adequate­ly switch 0.1 mA at 5 V
(Connection to a voltage
output sensor.)
12 to 24 VDC (sensor power supply)
DC power supply
12 Solid-state Multi-functional Timer H3CR-A
H3CR-AP
6
10
7
6
10
7
22
6
10
7
2
+
+
The start input of the H3CR-AP is voltage input. (Voltage imposition or open)
Voltage Input Signal Levels
No-contact Input No-contact Input Contact Input
Sensor
Timer
Start
Operates with PNP transistor ON
Operates with NPN transistor ON
Timer
Sensor
Timer
Operates with relay ON
Voltage Inputs
Input 0V
Start
Input 0V
Start
Input 0V
AC power supply
DC power supply
(Connection to PNP open collector output sensor)
12 to 24 VDC (sensor power supply)
DC power supply
Powe r supply (+)
Powe r supply ()
(Connection to NPN open collector output sensor)
12 to 24 VDC (sensor power supply)
DC power supply
Powe r supply (+)
Powe r supply ()
Note: The input circuit is isolated from the
power supply circuit. Thus, an NPN transistor can be connected.
Powe r supply (+)
Powe r supply ()
Note: Refer to the signal levels in the fol-
lowing table and be aware of the minimum applicable load of the relay.
No-contact input
1. Transistor ON Residual voltage: 1 V max. The voltage between terminals 6 and 7 must be 10.8 VDC min.
2. Transistor OFF Leakage current: 0.01 mA max. The voltage between terminals 6 and 7 must be 1.2 VDC max.
Contact input
Use contacts that can adequately switch 0.1 mA at each oper­ating voltage. The voltage between terminals 6 and 7 with contacts ON or OFF must satisfy the specified value.
Contacts ON 100-to-240-VAC and 100-to-125-VDC models: 85 to 264 VAC or 85 to 137.5 VDC 24-to-48-VAC and 12-to-48-VDC models: 20.4 to 52.8 VAC or
10.8 to 52.8 VDC
Contacts OFF 100-to-240-VAC and 100-to-125-VDC models: 0 to 10 VAC or 0 to 10 VDC 24-to-48-VAC and 12-to-48-VDC models: 0 to 2.4 VAC or 0 to
1.2 VDC
Solid-state Multi-functional Timer H3CR-A 13
Operation
Timing Chart
Note: 1. The minimum power-opening time (“Rt”) is 0.1 s.
2. The minimum input pulse width (for start, reset) is 0.05 s.
3. The letter “t” in the timing charts stands for the set time and “t–a” means that the period is less than the time set.
4. Power supply start in mode J is also possible for H3CR-A8/-A8E/-A8S/-A8-301 models.
5. Refer to page 19 for application examples.
H3CR-A/-AS/-AP*
*H3CR-AP model incorporates start input only.
Operating
mode
Timing chart
A: ON-delay
B: Flicker OFF start
B2: Flicker ON start
C: Signal ON/ OFF­delay
t t
t
Powe r
Start
Reset
Output relay (NC)
Power indicator
Powe r
Output
Basic operation
Output relay (NO) (Output indicator)
Start
(See note)
Note: Start input is invalid while the
Timer is in operation.
t t t t
Basic operation
Powe r
Output
Powe r
Power indicator
Start
Reset
Output relay (NC)
Output relay (NO) (Output indicator)
Start
(See note)
Note: Start input is invalid while
the Timer is in operation.
t
t
t t
Basic operation
Powe r
Output
Powe r
Start
Reset
Power indicator
Output relay (NC)
Output relay (NO) (Output indicator)
Start
(See note)
Note: Start input is invalid while the
Timer is in operation.
tttt
Basic operation
Powe r
Output
Powe r
Start
Reset
Output relay (NC)
Power indicator
Output relay (NO) (Output indicator)
Start
(See note)
Note: Start input is valid and re-
triggerable while the Timer is in operation.
14 Solid-state Multi-functional Timer H3CR-A
Gate Signal Input
D: Signal OFF­delay
E: Interval
G: Signal ON/ OFF­delay
J: One-shot out­put
Operating
mode
Timing chart
t
Basic operation
Powe r
Output
Output relay (NC)
Power indicator
Powe r
Start
Reset
Output relay (NO) (Output indicator)
Start
(See note)
Note: Start input is valid and
re-triggerable while the Timer is in operation.
t
Powe r
Start
Reset
Output relay (NC)
Power indicator
Powe r
Output
Output relay (NO) (Output indicator)
Basic operation
Start
(See note)
Note: Start input is valid and
re-triggerable while the Timer is in opera­tion.
tttt
Basic operation
Powe r
Output
Powe r
Start
Reset
Output relay (NC)
Power indicator
Output relay (NO) (Output indicator)
Start
(See note)
Note: Start input is valid and re-triggera-
ble while the Timer is in operation.
t
Basic operation
Output
Powe r
Powe r
Start
Reset
Output relay (NC)
Power indicator
Output relay (NO) (Output indicator)
1±0.6 s (Fixed)
1±0.6 s (Fixed)
Start
(See note)
1±0.6 s (Fixed)
Note: Start input is valid and re-
triggerable while the Timer is in operation.
t1 t2
Powe r
Start
Gate
Reset
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
Output relay
Note: 1. This timing chart indicates the gate input in op-
erating mode A (ON-delay operation).
2. The set time is the sum of t
1 and t2.
3. H3CR-AP model incorporates start input only.
Solid-state Multi-functional Timer H3CR-A 15
H3CR-A8/-A8S
Note: 1. The minimum power-opening time (“Rt”) is 0.1 s.
2. The letter “t” in the timing charts stands for the set time and “t–a” means that the period is less than the time set.
Operating
mode
Timing chart
A: ON-delay
B
2
:
Flicker ON start
E: Interval
J: One-shot out­put
t
Powe r
Output
Basic operation
Powe r
Output relay (NC)
Output relay (NO) (output indicator)
Powe r indicator
t t t t
Powe r
Powe r
Output
Basic operation
Output relay (NC)
Output relay (NO) (output indicator)
Powe r indicator
t
Powe r
Output
Basic operation
Powe r
Output relay (NC)
Output relay (NO) (output indicator)
Powe r indicator
t
Powe r
Powe r
Output
Basic operation
Output relay (NC)
Output relay (NO) (output indicator)
Powe r indicator
1±0.6 s (Fixed)
1±0.6 s (Fixed)
1±0.6 s (Fixed)
16 Solid-state Multi-functional Timer H3CR-A
H3CR-A8E
Note: 1. The minimum power-opening time (“Rt”) is 0.1 s.
2. The letter “t” in the timing charts stands for the set time and “t–a” means that the period is less than the time set.
Operating
mode
Timing chart
A: ON-delay
B
2
:
Flicker ON start
E: Interval
J: One-shot out­put
t
Powe r
Power indicator
Powe r
Output
Basic operation
Output relay (NC)
Output relay (NO) (output indicator)
Instantaneous output relay (NC)
Instantaneous output relay (NO)
t ttt
Powe r
Power indicator
Powe r
Output
Basic operation
Output relay (NC)
Output relay (NO) (output indicator)
Instantaneous output relay (NC)
Instantaneous output relay (NO)
t
Powe r
Output
Basic operation
Powe r
Power indicator
Output relay (NC)
Output relay (NO) (output indicator)
Instantaneous output relay (NC)
Instantaneous output relay (NO)
t
Powe r
Power indicator
Powe r
Output
Basic operation
(Fixed) (Fixed)
Output relay (NC)
Output relay (NO) (output indicator)
Instantaneous output relay (NC)
Instantaneous output relay (NO)
1±0.6 s (Fixed)
Solid-state Multi-functional Timer H3CR-A 17
Nomenclature
Operating mode display window
Scale range display windows
Time unit display window
Power indicator (green) (Flashes when Timer operates; lit when Timer stops operating)
Output indicator (orange) (Lit when output)
Time range selector (select one from 1.2, 3, 12, and 30 at full scale; with the H3CR-A@-301, select from 2.4, 6, 24, or 60 at full scale.)
Time setting knob (set time)
Time unit selector (select one from sec, min, hrs, and 10h)
Operating mode selector
Select a mode from: A, B, B2, C, D, and E (H3CR-A, -AP, and -AS) A, B2, E and J (H3CR-A8, -A8S, and -A8E) G and J (H3CR-A-300)
18 Solid-state Multi-functional Timer H3CR-A
Dimensions
Note: All units are in millimeters unless otherwise indicated.
48
48
66.6
52.3
15
6
44.8 × 44.8
0.7
48
66.6
48
15
6
52.3
0.7
44.8 × 44.8
11 pins
39 dia.
8 pins
39 dia.
H3CR-A H3CR-AP H3CR-AS
H3CR-A8 H3CR-A8S H3CR-A8E
50
16.5
50
Dimensions with Set Ring
Panel cover
42 dia.
Time Setting Ring
100.8*
98.5
2.3
*
89.9* 87.6
2.3
*
80
15
15
75
81.5
81.5
*These dimensions vary with the kind of DIN track (reference value).
H3CR-A8
@
Y92F-30
P3GA-11
Y92F-30
P3G-08
H3CR-A H3CR-AS H3CR-AP
P2CF-11
P2CF-11-E
P2CF-08
P2CF-08-E
H3CR-A H3CR-AS H3CR-AP + Adapter
(When Y92A-48G mounted)
H3CR-A8@ + Adapter
(When Y92A-48G mounted)
Dimensions with Front Connecting Socket P2CF-08-@/P2CF-11-
@
Dimensions with Back Connecting Socket P3G-08/P3GA-11
Solid-state Multi-functional Timer H3CR-A 19
Application Examples (H3CR-A)
A Mode: ON-delay
ON-delay operation (A mode) is a basic mode.
1. Power-ON Start/Power-OFF Reset
The Power-ON start/Power-OFF reset operation is a standard oper­ating method.
2. Signal Start/Signal Reset
The Signal start/Signal reset operation is useful for remote control of the Timer.
3. Control of Integrated Time with Gate Signal
With a gate signal, the Power-ON start operation and Signal start operation can be controlled (the operation can be interrupted).
B/B2 Mode: Flicker
The flicker operation in the B and B2 modes can be effectively applied to lamp or buzzer (ON and OFF) alarms or the monitoring of an intermittent operation with a display.
1. Power-ON Start/Power-OFF Reset (in B Mode)
t
Power (2 and 10)
Start (2 and 6)
Power indicator
Flashing
Lit
Externally short-circuited
Control output: NC (8 and 11)
NC (1 and 4)
Control output: NO (9 and 11)
NO (1 and 3)
Power supply
t
Reset (2 and 7)
Power (2 and 10)
Start (2 and 6)
Power indicator
Flashing Lit
Reset (2 and 7)
Lit
(Power continuously supplied)
Start signal (remote control possible) Reset signal (remote control possible)
Control output: NC (8 and 11)
NC (1 and 4)
Control output: NO (9 and 11)
NO (1 and 3)
Power supply
t
1
t
2
Power (2 and 10)
Start (2 and 6)
Power indicator
Flashing Lit
Gate (2 and 5)
t
1
+ t2: set time
Control output: NC (8 and 11)
NC (1 and 4)
Control output: NO (9 and 11)
NO (1 and 3)
Gate signal (The operation is interrupted with the gate signal if the Timer detects an abnormal signal.)
Externally short-circuited
Power supply
Power (2 and 10)
Start (2 and 6)
Power indicator
Flashing
Externally short-circuited
Control output: NC (8 and 11)
NC (1 and 4)
Power supply
Control output: NO (9 and 11)
NO (1 and 3)
20 Solid-state Multi-functional Timer H3CR-A
2. Signal Start/Signal Reset (in B Mode)
If there is an abnormal signal, flashing starts. When the abnormal condition is restored, a reset signal stops the display flashing.
C Mode: Signal ON/OFF-delay
The Signal ON-/OFF-delay operation (C mode) is useful for the con­trol of distribution of products on a production line into boxes by the specified number or time.
1. Power-ON Start/Instantaneous Operation/ Time-limit Reset
A set of these functions is useful for the operation of a machine for a specified period when power is ON.
2. Signal-ON-OFF Start/Instantaneous Operation/Time-limit Reset
D Mode: Signal OFF-delay
Signal OFF-delay operation (D mode) can be effectively used to keep a load operating for a certain period. For example, this function enables the cooling fan for a lamp or heater to operate for a certain period after the lamp or heater is switched OFF.
1. Power-ON Start/Instantaneous Operation/ Time-limit Reset
Power (2 and 10)
Start (2 and 6)
Power indicator
Reset (2 and 7)
Lit Flashing Lit
(
Power continuously supplied
)
Start signal Reset signal
Control output: NC (8 and 11)
NC (1 and 4)
Control output: NO (9 and 11)
NO (1 and 3)
Power supply
tt
Power (2 and 10)
Start (2 and 6)
Externally short-circuited
Control output: NC (8 and 11)
NC (1 and 4)
Control output: NO (9 and 11)
NO (1 and 3)
Power supply
Power (2 and 10)
Start (2 and 6)
Power indicator
Lit
Lit
Lit
Lit
(Power continuously supplied)
Flashing
Flashing
Flashing
Control output: NC (8 and 11)
NC (1 and 4)
Control output: NO (9 and 11)
NO (1 and 3)
Start signal (The operation starts with the signal ON or OFF)
Power supply
Power (2 and 10)
Start (2 and 6)
Power indicator
Lit Flashing
Lit
Start signal (NC to NO)
Control output: NC (8 and 11)
NC (1 and 4)
Control output: NO (9 and 11)
NO (1 and 3)
Power supply
Solid-state Multi-functional Timer H3CR-A 21
2. Signal Start/Instantaneous Operation/ Time-limit Reset
E Mode: Interval
1. Power-ON Start/Instantaneous Operation/ Time-limit Reset
This function is useful for the operation of a machine for a specified period after power is ON.
2. Signal Start/Instantaneous Operation/ Time-limit Reset
This function is useful for the repetitive control such as the filling of liquid for a specified period after each Signal start input.
Lit
Power (2 and 10)
Start (2 and 6)
Power indicator
Flashing Lit
Start signal (NO to NC to NO)
(Power continuously supplied)
Control output: NC (8 and 11)
NC (1 and 4)
Control output: NO (9 and 11)
NO (1 and 3)
Power supply
Power (2 and 10)
Start (2 and 6)
Externally short-circuited
Control output: NC (8 and 11)
NC (1 and 4)
Control output: NO (9 and 11)
NO (1 and 3)
Power supply
t t
Power (2 and 10)
Start (2 and 6)
Start signal
(Power continuously supplied)
Control output: NC (8 and 11)
NC (1 and 4)
Control output: NO (9 and 11)
NO (1 and 3)
Power supply
22 Solid-state Multi-functional Timer H3CR-A
Safety Precautions (H3CR-A)
Note: The undermentioned is common for all H3CR-A models.
Power Supplies
For the power supply of an input device of the H3CR-A@/-A@S/-AP, use an isolating transformer with the primary and secondary wind­ings mutually isolated and the secondary winding not grounded.
The H3CR-A@/-A@S/AP’s power supply terminal 2 is a common ter­minal for input signals to the Timer. Do not disconnect the wires on terminal 2, otherwise the internal circuitry of the Timer will be dam­aged.
Make sure that the voltage is applied within the specified range, oth­erwise the internal elements of the Timer may be damaged.
Input/Output
Relationship between Input and Power Supply Circuits (except for H3CR-A8E)
The H3CR-A (except for H3CR-A8E) uses transformerless power supply. When connecting a relay or transistor as an external signal input device, pay attention to the following points to prevent short-cir­cuiting due to a sneak current to the transformerless power supply. If a relay or transistor is connected to two or more Timers, the input ter­minals of those Timers must be wired properly so that they will not differ in phase, otherwise the terminals will be short-circuited to one another.
It is impossible to provide two independent power switches as shown below regardless of whether or not the Timers are different in phase.
S,G, R
5, 6, 7
2
10
2
H3CR-A
Power supply
Isolation transformer is required.
Input device
Input terminal
Correct
H3CR-A
Power supply
Input
terminal
Input device
10
2
2
Incorrect
Isolation
transformer
S,G, R
5, 6, 7
5, 6, 7 G, S, R
10
2
H3CR-A
Input terminal
Power supply
H3CR-A
Power supply
Incorrect
Correct
Short-circuit current
Contact or transistor for external input signal
Input terminal
Input terminal
Input terminal
Input terminal
Power supply
Input terminal
Input terminal
Solid-state Multi-functional Timer H3CR-A 23
Relationship between Input and Power Supply Circuits (H3CR-A@/-A@S)
An appropriate input is applied to the input signal terminals of the H3CR-A@/-A@S when one of the input terminals is short-circuited with the common terminal (terminal 2) for the input signals. Never use terminal 10 as the common terminal for this purpose, otherwise the internal circuit of the Timer will be damaged.
Do not connect a relay or any other load between input terminals, otherwise the internal circuit of the Timer will be damaged due to the high-tension voltage applied to the input terminals.
Relationship between Input and Power Supply Circuits (H3CR-AP)
Since the input circuit and the power supply circuit are configured independently, the input circuit can be turned ON or OFF irrespective of the ON/OFF state of the power supply. It must be noted that a voltage equivalent to the power supply voltage is applied to the input circuit.
If a relay or transistor is connected to two or more Timers, the input terminals of those Timers must be wired properly so that they will not be different in phase or the terminals will be short-circuited to one another (refer to the figures below).
Common to All H3CR-A Models
With the H3CR-AP, input wires must be as short as possible. If the floating capacity of wires exceeds 1,200 pF (approx. 10 m for cables with 120 pF/m), the operation will be affected. Pay particular atten­tion when using shielded cables.
The H3CR-A@S transistor output is isolated from the internal cir­cuitry by a photocoupler. Therefore, either NPN or PNP output is possible.
10
2
5, 6, 7 G, S, R
H3CR-A
Input terminal
Incorrect
AC or DC power supply
5, 6, 7 G, S, R
10
2
Input terminal
Correct
H3CR-A
AC or DC power supply
10
2
5, 6, 7 G, S, R
Ry
H3CR-A
Input terminal
AC or DC power supply
Input contact
Input circuit
H3CR-AP
AC/DC power supply
Power supply circuit
10
6
7
2
10
6
7
2
Incorrect
H3CR-AP
Power supply
H3CR-AP
Short-circuit current
Contact or transistor for external input signal
10
6
7
2
10
6
7
2
Correct
Power supply
H3CR-AP
H3CR-AP
Short-circuit current
Contact or transistor for external input signal
24 Solid-state Twin Timers H3CR-F
Solid-state Twin Timers
H3CR-F
DIN 48 × 48-mm Twin Timers
• Wide power supply ranges of 100 to 240 VAC and 48 to 125 VDC respectively.
• ON- and OFF-times can be set independently and so combina­tions of long ON- or OFF-time and short OFF- or ON-time set­tings are possible.
• Fourteen time ranges from 0.05 s to 30 h or from 1.2 s to 300 h depending on the model to be used.
• Models with a flicker ON start or flicker OFF start are available.
• Easy sequence checks through instantaneous outputs for a zero set value at any time range.
• Length, when panel-mounted with a Socket, of 80 mm or less.
• 11-pin and 8-pin models are available.
Model Number Structure
Model Number Legend
Ordering Information
List of Models
H3CR - F @ @ - @ @
1 23 54
1. Classification
F: Twin timers
2. Configuration
3. Twin Timer Mode
4. Time Range
None: 11-pin socket 8: 8-pin socket
None: Flicker OFF start N: Flicker ON start
5. Supply Voltage
None: 0.05 s to 30 h models 300: 1.2 s to 300 h models
100-240AC: 100 to 240 VAC 24AC/DC: 24 VAC/VDC 12DC: 12 VDC 48-125DC: 48 to 125 VDC
Operating
modes
Supply volt age
0.05 s to 30 h models 1.2 s to 300 h models
11-pin models 8-pin models 11-pin models 8-pin models
Flicker O FF start
100 to 240 VAC H3CR-F 100-240AC H3CR-F8 100-240AC H3CR-F-300 100-240AC H3CR-F8-300 100-240AC
24 VAC/DC H3CR-F 24AC/DC H3CR-F8 24AC/DC H3CR-F-300 24AC/DC H3CR-F8-300 24AC/DC
12 VDC H3CR-F 12DC H3CR-F8 12DC H3CR-F-300 12DC H3CR-F8-300 12DC
48 to 125 VDC H3CR-F 48-125DC H3CR-F8 48-125DC H3CR-F-300 48-125DC H3CR-F8-300 48-125DC
Flicker ON start 100 to 240 VAC H3CR-FN 100-240AC H3CR-F8N 100-240AC H3CR-FN-300 100-240AC H3CR-F8N-300 100-240AC
24 VAC/DC H3CR-FN 24AC/DC H3CR-F8N 24AC/DC H3CR-FN-300 24AC/DC H3CR-F8N-300 24AC/DC
12 VDC H3CR-FN 12DC H3CR-F8N 12DC H3CR-FN-300 12DC H3CR-F8N-300 12DC
48 to 125 VDC H3CR-FN 48-125DC H3CR-F8N 48-125DC H3CR-FN-300 48-125DC H3CR-F8N-300 48-125DC
Note: Specify both the model number and supply voltage when ordering.
Example: H3CR-F 100-240AC
Supply voltage
Solid-state Twin Timers H3CR-F 25
Accessories (Order Separately)
Note: 1. Y92A-48G is a finger safe terminal cover which is attached to the P3G-08 or P3GA-11 Socket.
2. Hold-down Clips are sold in sets of two.
Specifications
General
Time Ranges
0.05 s to 30 h Models
Note: Instantaneous output is available at any time range. To obtain instantaneous output, set to below 0.
1.2 s to 300 h Models
Note: Instantaneous output is available at any time range. To obtain instantaneous output, set to below 0.
Name/specifications Models
Flush Mounting Adapter Y92F-30
Y92F-73
Y92F-74
Mounting Track 50 cm (l)
× 7.3 mm (t) PFP-50N
1 m (l)
× 7.3 mm (t) PFP-100N
1 m (l)
× 16 mm (t) PFP-100N2
End Plate PFP-M
Spacer PFP-S
Protective Cover Y92A-48B
Track Mounting/ Front Connecting Socket
8-pin P2CF-08
8-pin, finger safe type P2CF-08-E
11-pin P2CF-11
11-pin, finger safe type P2CF-11-E
Back Connecting Socket 8-pin P3G-08
8-pin, finger safe type P3G-08 with Y92A-48G (See note 1)
11-pin P3GA-11
11-pin, finger safe type P3GA-11 with Y92A-48G (See note 1)
Hold-down Clip (See note 2) For PL08 and PL11 Sockets Y92H-7
For PF085A Socket Y92H-8
Item H3CR-F H3CR-F8 H3CR-FN H3CR-F8N
Operating mode Flicker OFF start Flicker ON start
Pin type 11-pin 8-pin 11-pin 8-pin
Operating/Reset method Time-limit operation/Time-limit reset or self-reset
Output type Relay output (DPDT)
Mounting method DIN track mounting, surface mounting, and flush mounting
Approved standards UL508, CSA C22.2 No.14, NK, Lloyds
Conforms to EN61812-1 and IEC60664-1 (VDE0110) 4kV/2. Output category according to EN60947-5-1.
Time unit s (sec) ×10 s (10 s) min (min) h (hrs)
Setting 1.2 0.05 to 1.2 1.2 to 12 0.12 to 1.2
3 0.3 to 3 3 to 30 0.3 to 3
12 1.2 to 12 12 to 120 1.2 to 12
30 3 to 30 30 to 300 3 to 30
Time unit ×10 s (10 s) ×10 min (10 min) h (hrs) ×10 h (10 h)
Setting 1.2 1.2 to 12 1.2 to 12 0.12 to 1.2 1.2 to 12
3 3 to 30 3 to 30 0.3 to 3 3 to 30
12 12 to 120 12 to 120 1.2 to 12 12 to 120
30 30 to 300 30 to 300 3 to 30 30 to 300
26 Solid-state Twin Timers H3CR-F
Ratings
Note: 1. A power supply with a ripple of 20% max. (single-phase power supply with full-wave rectification) can be used with each DC Model.
2. Do not use an inverter output as the power supply. Refer to Power Supplies in Safety Precautions for All Timers on page 51 for details.
3. Refer to Power Supplies in Safety Precautions for All Timers on page 51 when using the Timer together with a 2-wire AC proximity sensor.
Characteristics
Note: Refer to the Life-test Curve.
Rated supply voltage (See notes 1, 2, and 3.) 100 to 240 VAC (50/60 Hz),12 VDC, 24 VAC/DC (50/60 Hz), 48 to 125 VDC
Operating voltage range 85% to 110% of rated supply voltage; 90% to 110% with 12-VDC models
Power rese t Minimum power-opening time: 0.1 s
Power consumption 100 to 240 VAC: approx. 10 VA (2.1 W) at 240 VAC
24 VAC/VDC: approx. 2 VA (1.7 W) at 24 VAC
approx. 1 W at 24 VDC 48 to 125 VDC: approx. 1.5 W at 125 VDC 12 VDC: approx. 1 W at 12 VDC
Control outputs Contact output: 5 A at 250 VAC/30 VDC, resistive load (cos
φ = 1)
Accuracy of operating time
±0.2% FS max. (±0.2% FS ±10 ms max. in ranges of 1.2 and 3 s)
Setting error
±5% FS ±50 ms max.
Reset time 0.1 s max.
Reset voltage 10% max. of rated voltage
Influence of voltage
±0.2% FS max. (±0.2% FS ±10 ms max. in ranges of 1.2 and 3 s)
Influence of temperature
±1% FS max. (±1% FS ±10 ms max. in ranges of 1.2 and 3s)
Insulation resistance 100 M
min. (at 500 VDC)
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min (between current-carrying metal par ts and exposed non-current-carrying metal parts)
2,000 VAC, 50/60 Hz for 1 min (between control output terminals and operating circuit) 2,000 VAC, 50/60 Hz for 1 min (between contacts of different polarities) 1,000 VAC, 50/60 Hz for 1 min (between contacts not located next to each other)
Impulse withstand volt­age
3 kV (between power terminals) for 100 to 240 VAC, 48 to 125 VDC 1 kV for 12 VDC, 24 VAC/DC
4.5 kV (between current-carrying terminal and exposed non-current-carrying metal parts) for 100 to 240 VAC, 48 to 125 VDC
1.5 kV for 12 VDC, 24 VAC/DC
Noise immunity
±1.5 kV (between power terminals), square-wave noise by noise simulator (pulse width: 100 ns/1 µs, 1-ns rise) ±400 V for 12 VDC
Static immunity Malfunction: 8 kV
Destruction: 15 kV
Vibration resistance Destruction: 10 to 55 Hz with 0.75-mm single amplitude for 2 hrs each in three directions
Malfunction: 10 to 55 Hz with 0.5-mm single amplitude for 10 min each in three directions
Shock resistance
Destruction: 980 m/s
2
three times each in six directions
Malfunction: 98 m/s
2
three times each in six directions
Ambient temperature Operating:
10°C to 55°C (with no icing)
Storage:
25°C to 65°C (with no icing)
Ambient humidity Operating: 35% to 85%
Life expectancy Mechanical: 20 million operations min. (under no load at 1,800 operations/h)
Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 1,800 operations/h) (See note)
EMC (EMI) EN61812-1
Emission Enclosure: EN55011 Group 1 class A Emission AC Mains: EN55011 Group 1 class A (EMS) EN61812-1 Immunity ESD: IEC61000-4-2: 6 kV contact discharge (level 3)
8 kV air discharge (level 3) Immunity RF-interference from AM Radio Waves: IEC61000-4-3: 10 V/m (80 MHz to 1 GHz) (level 3) Immunity RF-interference from Pulse-modulated Radio Waves: IEC61000-4-3: 10 V/m (900
±5 MHz) (level 3)
Immunity Conducted Disturbance: IEC61000-4-6: 10 V (0.15 to 80 MHz) (level 3) Immunity Burst: IEC61000-4-4: 2 kV power-line (level 3)
2 kV I/O signal-line (level 4) Immunity Surge: IEC61000-4-5: 1 kV line to line (level 3)
2 kV line to ground (level 3)
Case color Light Gray (Munsell 5Y7/1)
Degree of protection IP40 (panel surface)
Weight Approx. 100 g
Solid-state Twin Timers H3CR-F 27
Life-test Curve
Connections
Block Diagrams
I/O Functions
Terminal Arrangement
10,000
5,000
1,000
500
100
Load current (A)
30 VDC L/R = 7 ms
250 VAC (cosφ = 0.4)
Switching operations (x 10
3
)
250 VAC/30 VDC (cosφ = 1)
Reference: A maximum current of 0.15 A can be switched at 125 VDC (cosφ = 1)
and a maximum current of 0.1 A can be switched if L/R is 7 ms. In both cases, a life of 100,000 operations can be expected. The minimum applicable load is 10 mA at 5 VDC (failure level: P).
ON indicator OFF indicator
One-chip microcomputer
ROM
RAM
Clock
AC (DC) input
Power supply circuit
Indicator circuit
Zero setting detection circuit
Time range/unit selectors
Output circuit
Inputs ---
Outputs Control output Outputs are turned ON/OFF according to the time set by the ON- and OFF-time setting knob.
(+)(~)
Power supply
Power supply
H3CR-F8 H3CR-F8 NH3CR-F8-300 H3CR-F8N-300
H3CR-F H3CR-FN H3CR-F-300 H3CR-FN-300
Note: Leave terminals 5, 6, and 7 open.
Do not use them as relay terminals.
28 Solid-state Twin Timers H3CR-F
Operation
Timing Chart
tON: ON set time t
OFF
: OFF set time
Note: 1. The reset time requires a minimum of 0.1 s.
2. When power is supplied in flicker ON start mode, the OFF indicator lights momentarily. This, however, has no effect on the performance
of the Timer.
Nomenclature
Operating mode Timing chart
Flicker OFF start
Flicker ON start
t
OFF
t
ON
t
OFF
t
ON
t
OFF
t
OFF
ON OFF
Powe r
0.1 s min.
Lit Not lit
Lit Not lit
ON OFF
ON OFF
ON indicator
OFF indicator
Output NO
Output NC
t
ON
t
OFF
t
ON
t
OFF
t
ON
t
OFF
Powe r
ON OFF
0.1 s min.
Lit
Not lit
Lit
Not lit
ON OFF
ON OFF
ON indicator
OFF indicator
Output NO
Output NC
OFF-time unit display window
ON-time unit display window
OFF indicator (green) Lit when the output is OFF.
ON indicator (orange) Lit when the output is ON.
Scale range display windows
Time range selector (select one from 1.2, 3, 12, and 30 at full scale) For both ON-time and OFF-time.
OFF-time unit selector (select one from sec. 10 s, min., and hrs, or from 10 s, 10 min, hrs, and 10 h)
ON-time setting knob (with orange pointer) For ON-time setting
OFF-time setting knob (with green pointer) For OFF-time setting
ON-time unit selector (select one from sec, 10 s, min, and hrs, or from 10 s, 10 min, hrs, and 10 h)
Solid-state Twin Timers H3CR-F 29
Dimensions
Note: All units are in millimeters unless otherwise indicated.
66.6
0.7
17.4
52.3
6
5.7
R1.3
44.8 × 44.8
48
48
66.6
0.7
17.4
52.3
6
5.7
R1.3
44.8 × 44.8
48
48
37 dia.
14 dia.
37 dia.
14 dia.
11 pins
8 pins
H3CR-F H3CR-FN H3CR-F-300 H3CR-FN-300
H3CR-F8 H3CR-F8N H3CR-F8-300 H3CR-F8N-300
103.2* 100.9
2.3
*
92.3* 90.0
2.3
*
80
17.4
17.4 75
81.5
81.5
*These dimensions vary with the kind of DIN track (reference value).
Y92F-30
P3GA-11
Y92F-30
P3G-08
Dimensions with Front Connecting Socket P2CF-08-@/P2CF-11-@
H3CR-F H3CR-FN
P2CF-11
P2CF-11-E
H3CR-F8 H3CR-F8N
P2CF-08
P2CF-08-E
Dimensions with Back Connecting Socket P3G-08/P3GA-11
H3CR-F
H3CR-FN
H3CR-F8
H3CR-F8N
(When Y92A-48G mounted)
(When Y92A-48G mounted)
30 Solid-state Star-delta Timer H3CR-G
Solid-state Star-delta Timer
H3CR-G
DIN 48 × 48-mm Star-delta Timer
• A wide star-time range (up to 120 seconds) and star-delta trans­fer time range (up to 0.5 seconds).
Model Number Structure
Model Number Legend
Ordering Information
List of Models
Outputs Supply voltage 8-pin models
Time-limit contact 100 to 120 VAC H3CR-G8L 100-120AC
200 to 240 VAC H3CR-G8L 200-240AC
Time-limit contact and instantaneous contact 100 to 120 VAC H3CR-G8EL 100-120AC
200 to 240 VAC H3CR-G8EL 200-240AC
H3CR - G 8 @ L @
1 2 3 4 5
1. Classification
G: Star-delta timer
2. Configuration
8: 8-pin socket
3. Outputs
4. Dimensions
L: Long-body model
5. Supply Voltage
100-120AC: 100 to 120 VA
C
200-240AC: 200 to 240 VA
C
None: Star-delta operation contact E: Star-delta operation contact and instantaneous contact
Note: Specify both the model number and supply voltage when ordering.
Example: H3CR-G8L 100-120AC
Supply voltage
Solid-state Star-delta Timer H3CR-G 31
Accessories (Order Separately)
Note: 1. Y92A-48G is a finger safe terminal cover which is attached to the P3G-08 Socket.
2. The Time Setting Ring and Panel Cover are sold together.
3. Hold-down Clips are sold in sets of two.
Specifications
General
Time Ranges
Name/specifications Models
Flush Mounting Adapter Y92F-30
Y92F-70
Y92F-71
Mounting Track 50 cm (l)
× 7.3 mm (t) PFP-50N
1 m (l)
× 7.3 mm (t) PFP-100N
1 m (l)
× 16 mm (t) PFP-100N2
End Plate PFP-M
Spacer PFP-S
Protective Cover Y92A-48B
Track Mounting/ Front Connecting Socket
8-pin P2CF-08
8-pin, finger safe type P2CF-08-E
Back Connecting Socket 8-pin P3G-08
8-pin, finger safe type P3G-08 with Y92A-48G (See note 1)
Time Setting Ring Setting a specific time Y92S-27
Limiting the setting range Y92S-28
Panel Cover (See note 2) Light gray (5Y7/1) Y92P-48GL
Black (N1.5) Y92P-48GB
Medium gray (5Y5/1) Y92P-48GM
Hold-down Clip (See note 3) For PL08 and PL11 Sockets Y92H-1
For PF085A Socket Y92H-2
Item H3CR-G8L H3CR-G8EL
Functions Star-delta timer Star-delta timer with instantaneous output
Pin type 8-pin
Operating/Reset method Time-limit operation/Self-reset
Output type Time-limit: SPST-NO (star operation circuit)
SPST-NO (delta operation circuit)
Time-limit: SPST-NO (star operation circuit)
SPST-NO (delta operation circuit)
Instantaneous: SPST-NO
Mounting method DIN track mounting, surface mounting, and flush mounting
Approved standards UL508, CSA C22.2 No.14, NK, Lloyds
Conforms to EN61812-1 and IEC60664-1 (VDE0110) 4kV/2. Output category according to EN60947-5-1.
Time unit Star operation time ranges
Full scale setting 6 0.5 to 6 s
12 1 to 12 s
60 5 to 60 s
120 10 to 120 s
Star-delta transfer time Programmable at 0.05 s, 0.1 s, 0.25 s or 0.5 s
32 Solid-state Star-delta Timer H3CR-G
Ratings
Note: 1. Do not use an inverter output as the power supply. Refer to Power Supplies in Safety Precautions for All Timers on page 51 for details.
2. Refer to Power Supplies in Safety Precautions for All Timers on page 51 when using the Timer together with a 2-wire AC proximity sensor.
Characteristics
Note: Refer to the Life-test Curve.
Rated supply voltage (See notes 1 and 2.) 100 to 120 VAC (50/60 Hz), 200 to 240 VAC (50/60 Hz)
Operating voltage range 85% to 110% of rated supply voltage
Power reset Minimum power-opening time: 0.5 s
Power consumption 100 to 120 VAC: approx. 6 VA (2.6 W) at 120 VAC
200 to 240 VAC: approx. 12 VA (3.0 W) at 240 VAC
Control outputs Contact output: 5 A at 250 VAC/30 VDC, resistive load (cos
φ = 1)
Accuracy of operating time
±0.2% FS max.
Setting error
±5% FS ±50 ms max.
Accuracy of Star-delta transfer time
±25% FS + 5 ms max.
Reset voltage 10% max. of rated voltage
Influence of voltage
±0.2% FS max.
Influence of temperature
±1% FS max.
Insulation resistance 100 M
min. (at 500 VDC)
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min (between current-carrying metal parts and exposed non-current-carrying metal parts)
2,000 VAC, 50/60 Hz for 1 min (between control output terminals and operating circuit) 2,000 VAC, 50/60 Hz for 1 min (between contacts of different polarities) 1,000 VAC, 50/60 Hz for 1 min (between contacts not located next to each other)
Impulse withstand volt­age
3 kV (between power terminals)
4.5 kV (between current-carrying terminal and exposed non-current-carrying metal parts)
Noise immunity
±1.5 kV (between power terminals), square-wave noise by noise simulator (pulse width: 100 ns/1 µs, 1-ns rise)
Static immunity Malfunction: 8 kV
Destruction: 15 kV
Vibration resistance Destruction: 10 to 55 Hz with 0.75-mm single amplitude for 2 hrs each in three directions
Malfunction: 10 to 55 Hz with 0.5-mm single amplitude for 10 min each in three directions
Shock resistance
Destruction: 980 m/s
2
three times each in six directions
Malfunction: 294 m/s
2
three times each in six directions
Ambient temperature Operating:
10°C to 55°C (with no icing)
Storage:
25°C to 65°C (with no icing)
Ambient humidity Operating: 35% to 85%
Life expectancy Mechanical: 20 million operations min. (under no load at 1,800 operations/h)
Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 1,800 operations/h) (See note)
EMC (EMI) EN61812-1
Emission Enclosure: EN55011 Group 1 class A Emission AC Mains: EN55011 Group 1 class A (EMS) EN61812-1 Immunity ESD: IEC61000-4-2: 6 kV contact discharge (level 3)
8 kV air discharge (level 3) Immunity RF-interference from AM Radio Waves: IEC61000-4-3: 10 V/m (80 MHz to 1 GHz) (level 3) Immunity RF-interference from Pulse-modulated Radio Waves: IEC61000-4-3: 10 V/m (900
±5 MHz) (level 3)
Immunity Conducted Disturbance: IEC61000-4-6: 10 V (0.15 to 80 MHz) (level 3) Immunity Burst: IEC61000-4-4: 2 kV power-line (level 3)
2 kV I/O signal-line (level 4) Immunity Surge: IEC61000-4-5: 1 kV line to line (level 3)
2 kV line to ground (level 3)
Case color Light Gray (Munsell 5Y7/1)
Degree of protection IP40 (panel surface)
Weight H3CR-G8L: approx. 110 g; H3CR-G8EL: approx. 130 g
Solid-state Star-delta Timer H3CR-G 33
Life-test Curve
Connections
Block Diagrams
10,000
5,000
1,000
500
100
Load current (A)
30 VDC L/R = 7 ms
250 VAC (cosφ = 0.4)
Switching operations (× 10
3
)
250 VAC/30 VDC (cosφ = 1)
Reference: A maximum current of 0.15 A can be switched at 125 VDC (cosφ = 1)
and a maximum current of 0.1 A can be switched if L/R is 7 ms. In both cases, a life of 100,000 operations can be expected. The minimum applicable load is 10 mA at 5 VDC (failure level: P).
H3CR-G8L
AC input
Star operation
Delta operation
Powe r supply circuit
Star operation time oscillation circuit
Star operation time counting circuit
Star operation time range selector
Star-delta transfer time selector
Star-delta transfer time oscillation circuit
Star-delta
transfer time
counting
circuit
Output circuit
Indicator circuit
Star operation indicator
Delta operation indicator
34 Solid-state Star-delta Timer H3CR-G
I/O Functions
Terminal Arrangement
H3CR-G8EL
Star operation
Delta operation
AC input
Powe r supply circuit
Star operation time oscillation circuit
Star operation time range selector
Star operation time counting circuit
Star-delta transfer time selector
Star-delta transfer time oscillation circuit
Star-delta transfer time counting circuit
Output circuit
Indicator circuit
Instantaneous output circuit
Star operation indicator
Delta operation indicator
Inputs ---
Outputs Control output If the time reaches the value set with the time setting knob, the star operation output will be turned OFF
and there will be delta operation output after the set star-delta transfer time has elapsed.
H3CR-G8L H3CR-G8EL
Instantaneous contact
Delta operation contact
Star operation contact
Note: Leave terminals 1, 3, and 4 open.
Do not use them as relay terminals.
Delta operation contact
Star operation contact
Note: Leave terminal 4 open. Do not use
them as relay terminals.
Solid-state Star-delta Timer H3CR-G 35
Operation
Timing Chart
t1: Star operation time setting t2: Star-delta transfer time
Nomenclature
Model Timing chart
H3CR-G8L/-G8EL
t1
t2
0.5 s min.
Power (2 7)
Star operation indicator
Delta operation indicator
ON OFF
Lit Not lit
ON OFF
ON OFF
ON OFF
Lit Not lit
Instantaneous output (1 3) (-E models)
Star operation output (8 5)
Delta operation output (8 6)
Star-delta transfer time display window
Star operation indicator (green)
Delta operation indicator (orange)
Scale range display windows
Star operation time range selector (select one from 6, 12, 60, and 120 at full scale)
Time unit display (sec is fixed)
Time setting knob (for setting star operation time)
Star-delta transfer time selector (select one from 0.05 s, 0.1 s,
0.25 s, and 0.5 s)
36 Solid-state Star-delta Timer H3CR-G
Dimensions
Note: All units are in millimeters unless otherwise indicated.
15
6
(78.0)
63.7
44.8 × 44.8
0.7
48
48
39 dia.
8 pins
50
16.5
50
Dimensions with Set Ring
Time setting ringPanel cover
42 dia.
101.3*
99
2.3
*
15
86.4
92.9
Y92F-30
P3G-08
H3CR-G8@L
*These dimensions vary with the kind of DIN track (reference value).
Dimensions with Front Connecting Socket P2CF-08-@
P2CF-08
P2CF-08-E
Dimensions with Back Connecting Socket P3G-08
H3CR­G8@L
(When Y92A-48G mounted)
Solid-state Power OFF-delay Timer H3CR-H 37
Solid-state Power OFF-delay Timer
H3CR-H
DIN 48 × 48-mm Power OFF-delay Timer
• Long power OFF-delay times; S-series: up to 12 seconds, M-series: up to 12 minutes.
• Models with forced-reset input are available.
• 11-pin and 8-pin models are available.
Model Number Structure
Model Number Legend
Note: This model number legend includes combinations that are not available. Before ordering, please check the List of Models on page 37 for
availability.
List of Models
Input Output Supply voltage S-series M-series
11-pin models 8-pin models 11-pin models 8-pin models
With­out reset input
DPDT 100 to 120 VAC --- H3CR-H8L 100-120AC S --- H3CR-H8L 100-120AC M
200 to 240 VAC H3CR-H8L 200-240AC S H3CR-H8L 200-240AC M
24 VAC/DC H3CR-H8L 24AC/DC S H3CR-H8L 24AC/DC M
48 VDC H3CR-H8L 48DC S H3CR-H8L 48DC M
100 to 125 VDC H3CR-H8L 100-125DC S H3CR-H8L 100-125DC M
With reset input
100 to 120 VAC H3CR-HRL 100-120AC S --- H3CR-HRL 100-120AC M ---
200 to 240 VAC H3CR-HRL 200-240AC S H3CR-HRL 200-240AC M
24 VAC/DC H3CR-HRL 24AC/DC S H3CR-HRL 24AC/DC M
48 VDC H3CR-HRL 48DC S H3CR-HRL 48DC M
100 to 125 VDC H3CR-HRL 100-125DC S H3CR-HRL 100-125DC M
SPDT 100 to 120 VAC --- H3CR-H8RL 100-120AC S ---
H3CR-H8RL 100-120AC M
200 to 240 VAC H3CR-H8RL 200-240AC S
H3CR-H8RL 200-240AC M
24 VAC/DC H3CR-H8RL 24AC/DC S H3CR-H8RL 24AC/DC M
48 VDC H3CR-H8RL 48DC S H3CR-H8RL 48DC M
100 to 125 VDC H3CR-H8RL 100-125DC S
H3CR-H8RL 100-125DC M
H3CR - H @ @ L @ @
1 2 3 4 5 6
1. Classification
H: Power OFF-delay timer
2. Configuration
3. Input
4. Dimensions
L: Long-body model
None: 11-pin socket 8: 8-pin socket
None: Without reset input R: With reset input
5. Supply Voltage
6. Time Range
S: 0.05 to 12 s M: 0.05 to 12 min
100-120AC: 100 to 120 VAC 200-240AC: 200 to 240 VAC 48DC: 48 VDC 100-125DC: 100 to 125 VDC
Note: Specify the model number, supply voltage, and time range (S or M) when ordering.
Example: H3CR-H8L 100-120AC
S
Supply voltage
Time range
38 Solid-state Power OFF-delay Timer H3CR-H
Accessories (Order Separately)
Note: 1. Y92A-48G is a finger safe terminal cover which is attached to the P3G-08 or P3GA-11 Socket.
2. Hold-down Clips are sold in sets of two.
Specifications
General
Time Ranges
Note: 1. If the above minimum power ON time is not secured, the H3CR may not operate. Be sure to secure the above minimum power ON time.
2. Do not use the Timer with a repeat period of less than 3 s. Doing so may result in abnormal heating or burning. Refer to Safety Precautions
(H3CR-H) on page 44 for details.
Name/specifications Models
Flush Mounting Adapter Y92F-30
Y92F-70
Y92F-71
Mounting Track 50 cm (l)
× 7.3 mm (t) PFP-50N
1 m (l)
× 7.3 mm (t) PFP-100N
1 m (l)
× 16 mm (t) PFP-100N2
End Plate PFP-M
Spacer PFP-S
Protective Cover Y92A-48B
Track Mounting/ Front Connecting Socket
8-pin P2CF-08
8-pin, finger safe type P2CF-08-E
11-pin P2CF-11
11-pin, finger safe type P2CF-11-E
Back Connecting Socket 8-pin P3G-08
8-pin, finger safe type P3G-08 with Y92A-48G (See note 1)
11-pin P3GA-11
11-pin, finger safe type P3GA-11 with Y92A-48G (See note 1)
Hold-down Clip (See note 2) For PL08 and PL11 Sockets Y92H-1
For PF085A Socket Y92H-2
Item H3CR-H8L H3CR-H8RL H3CR-HRL
Operating/Reset method Instantaneous operation/Time-limit
reset
Instantaneous operation/Time-limit reset/Forced reset
Pin type 8-pin 11-pin
Input type --- No-voltage
Output type Relay output (DPDT) Relay output (SPDT) Relay output (DPDT)
Mounting method DIN track mounting, surface mounting, and flush mounting
Approved standards UL508, CSA C22.2 No.14, NK, Lloyds
Conforms to EN61812-1 and IEC60664-1 (VDE0110) 4kV/2. Output category according to EN60947-5-1.
Time unit S-series M-series
s (sec) min (min)
Setting 0.6 0.05 to 0.6
1.2 0.12 to 1.2
6 0.6 to 6
12 1.2 to 12
Min. power ON time 0.1 s min. 2 s min.
Time-up operation repeat period 3 s min.
Forced-reset repeat period 3 s min.
Solid-state Power OFF-delay Timer H3CR-H 39Solid-state Power OFF-delay Timer H3CR-H 39
Ratings
Note: 1. A power supply with a ripple of 20% max. (single-phase power supply with full-wave rectification) can be used with each DC Model.
2. Do not use an inverter output as the power supply. Refer to Power Supplies in Safety Precautions for All Timers on page 51 for details.
3. For contact input, use contacts which can adequately switch 1 mA at 5 V.
Characteristics
Note: Refer to the Life-test Curve.
Rated supply voltage (See notes 1 and 2.) 100 to 120 VAC (50/60 Hz), 200 to 240 VAC (50/60 Hz), 24 VAC/VDC (50/60 Hz), 48 VDC,
100 to 125 VDC
Operating voltage range 85% to 110% of rated supply voltage
No-voltage input (See note 3.) ON-impedance: 1 k
max.
ON residual voltage: 1 V max. OFF impedance: 500 k
min.
Power consumption 100 to 120 VAC: approx. 0.23 VA (0.22 W) at 120 VAC
200 to 240 VAC: approx. 0.35 VA (0.3 W) at 240 VAC 24 VAC/DC: approx. 0.17 VA (0.15 W) at 24 VAC
approx. 0.1 W at 24 VDC 48 VDC: approx. 0.18 W at 48 VDC 100 to 125 VDC: approx. 0.5 W at 125 VDC
Control outputs Contact output: 5 A at 250 VAC/30 VDC, resistive load (cos
φ = 1)
Accuracy of operating time
±0.2% FS max. (±0.2% FS ±10 ms max. in ranges of 0.6 and 1.2 s)
Setting error
±5% FS ±50 ms max.
Operation start voltage 30% max. of rated voltage
Influence of voltage
±0.2% FS max. (±0.2% FS ±10 ms max. in ranges of 0.6 and 1.2 s)
Influence of temperature
±1% FS max. (±1% FS ±10 ms max. in ranges of 0.6 and 1.2 s)
Insulation resistance 100 M
min. (at 500 VDC)
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min (between current-carrying metal parts and exposed non-current-carrying metal parts)
2,000 VAC, 50/60 Hz for 1 min (between control output terminals and operating circuit) 2,000 VAC, 50/60 Hz for 1 min (between contacts of different polarities) 1,000 VAC, 50/60 Hz for 1 min (between contacts not located next to each other)
Impulse withstand voltage
3 kV (between power terminals) for 100 to 120 VAC, 200 to 240 VAC, 100 to 125 VDC; 1 kV for 24 VAC/DC, 48 VDC
4.5 kV (between current-carrying terminal and exposed non-current-carrying metal parts) for 100 to 120 VAC, 200 to 240 VAC, 100 to 125 VDC;
1.5 kV for 24 VAC/DC, 48 VDC
Noise immunity
±1.5 kV (between power terminals) and ±600 V (between input terminals), square-wave noise by noise simulator
(pulse width: 100 ns/1
µs, 1-ns rise); ±1 kV (between power terminals) for 48 VDC
Static immunity Malfunction: 8 kV, Destruction:15 kV
Vibration resistance Destruction: 10 to 55 Hz with 0.75-mm single amplitude for 2 hrs each in three directions
Malfunction: 10 to 55 Hz with 0.5-mm single amplitude for 10 min each in three directions
Shock resistance
Destruction: 980 m/s
2
three times each in six directions
Malfunction: 98 m/s
2
three times each in six directions
Ambient temperature Operating:
10°C to 55°C (with no icing),
Storage:
25°C to 65°C (with no icing)
Ambient humidity Operating: 35% to 85%
Life expectancy Mechanical: 10 million operations min. (under no load at 1,200 operations/h)
Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 1,200 operations/h) (See note)
EMC (EMI) EN61812-1
Emission Enclosure: EN55011 Group 1 class A Emission AC Mains: EN55011 Group 1 class A (EMS) EN61812-1 Immunity ESD: IEC61000-4-2: 6 kV contact discharge (level 3)
8 kV air discharge (level 3) Immunity RF-interference from AM Radio Waves: IEC61000-4-3: 10 V/m (80 MHz to 1 GHz) (level 3) Immunity RF-interference from Pulse-modulated Radio Waves: IEC61000-4-3: 10 V/m (900
±5 MHz) (level 3)
Immunity Conducted Disturbance: IEC61000-4-6: 10 V (0.15 to 80 MHz) (level 3) Immunity Burst: IEC61000-4-4: 2 kV power-line (level 3)
2 kV I/O signal-line (level 4) Immunity Surge: IEC61000-4-5: 1 kV line to line (level 3)
2 kV line to ground (level 3)
Case color Light Gray (Munsell 5Y7/1)
Degree of protection IP40 (panel surface)
Weight Approx. 120 g
40 Solid-state Power OFF-delay Timer H3CR-H
Life-test Curve
Connections
Block Diagrams
I/O Functions
10,000
5,000
1,000
500
100
Load current (A)
30 VDC L/R = 7 ms
250 VAC (cosφ = 0.4)
Switching operations (× 10
3
)
250 VAC/30 VDC (cosφ = 1)
Reference: A maximum current of 0.15 A can be switched at 125 VDC (cosφ = 1)
and a maximum current of 0.1 A can be switched if L/R is 7 ms. In both cases, a life of 100,000 operations can be expected. The minimum applicable load is 10 mA at 5 VDC for H3CR-H8L/-HRL and 100 mA at 5 VDC for H3CR-H8RL (failure level: P).
Without Reset Input (H3CR-H8L)
LCD
AC (DC) input
Power supply circuit
Power failure detection circuit
Oscillation circuit
Time range/ unit selector
Counting circuit
Output circuit
Indicator circuit
Output indicator
With Reset Input (H3CR-H8RL/-HRL)
LCD
Input circuit
AC (DC) input
Reset input
Power supply circuit
Power failure detection circuit
Oscillation circuit
Time range/ unit selector
Counting circuit
Output circuit
Indicator circuit
Output indicator
Inputs Reset Turns off the control output and resets the elapsed time.
Outputs Control output Operates instantaneously when the power is turned on and time-limit resets when the set time is up
after the power is turned off.
Solid-state Power OFF-delay Timer H3CR-H 41Solid-state Power OFF-delay Timer H3CR-H 41
Terminal Arrangement
Note: DC models, including 24 VAC/DC models, have polarity.
8-pin Models
Without Reset Input (H3CR-H8L) With Reset Input (H3CR-H8RL)
11-pin Model
With Reset Input (H3CR-HRL)
Power supply
Power supply
Reset input
Power supply
Reset input
Note: Leave terminal 3 open. Do not use
them as relay terminals.
Note: Leave terminal 6 open. Do not use
them as relay terminals.
42 Solid-state Power OFF-delay Timer H3CR-H
Operation
Timing Chart
t: Set time Rt: Minimum power ON time (S-series: 0.1 s min.; M-series: 2 s min.)
If the power ON time is less than this value, the Timer may not operate (i.e., output may not turn ON).
Note: If the power is turned ON until the set time is up, the timer will be retriggered.
Model Timing chart
H3CR-H8L
H3CR-H8RL
H3CR-HRL
Rt
t
Rt
t
ON
OFF
Output (1 3)
Lit Not lit
Output (1 4)
Output (8 6)
Output (8 5)
Powe r (See note)
Output indicator
tt
Rt
Rt
Lit Not lit
ON
OFF
Output (8
6)
Reset input
ON (Short-circuited) OFF (Open)
0.05 s min.
0.05 s min.
Output (8 5)
Powe r (See note)
Output indicator
Rt
t
Rt
t
ON
OFF
Output (1 3)
Lit Not lit
Output (1 4)
Output (11 9)
Output (11 8)
Reset input
0.05 s min.
Powe r (See note)
Output indicator
0.05 s min.
Solid-state Power OFF-delay Timer H3CR-H 43Solid-state Power OFF-delay Timer H3CR-H 43
Nomenclature
Dimensions
Note: All units are in millimeters unless otherwise indicated.
Output indicator (red)
Scale range display windows
Time range selector (select one from 0.6, 1.2, 6, and 12 at full scale)
Time unit display S-series: sec M-series: min
Time setting knob (for setting power OFF-delay time)
15
78.0
6
63.7 0.7
44.8
× 44.8
48
48
15
78.0
6
63.7
0.7
44.8 × 44.8
48
48
H3CR-HRL
39 dia.
39 dia.
8 pins
11 pins
H3CR-H8L H3CR-H8RL
112.2* 109.9
2.3
*
15
91.4
101.3*
99
2.3
*
15
86.4
92.9
92.9
H3CR-HRL
*
These dimensions vary with the kind of DIN track (reference value).
Y92F-30
P3G-08
H3CR-H8@L
Y92F-30
P3GA-11
H3CR-HRL
Dimensions with Front Connecting Socket P2CF-08-@/P2CF-11-@
P2CF-08
P2CF-08-E
P2CF-11
P2CF-11-E
H3CR­H8@L
(When Y92A-48G mounted)
(When Y92A-48G mounted)
Dimensions with Back Connecting Socket P3G-08/P3GA-11
44 Solid-state Power OFF-delay Timer H3CR-H
Safety Precautions (H3CR-H)
Note: The undermentioned is common for all H3CR-H models.
Power Supplies
The H3CR-H has a large inrush current; provide sufficient power supply capacity. If the power supply capacity is too small, there may be delays in turning ON the output.
With the H3CR-H@RL, for the power supply of an input device, use an isolating transformer, of which the primary and secondary wind­ings are mutually isolated and the secondary winding is not grounded.
Input/Output (H3CR-H@RL)
An appropriate input is applied to the input signal terminal of the Timer when the input terminal for the input signal is short-circuited. Do not attempt to connect any input terminal to any terminal other than the input terminal or to apply voltage across other than the specified input terminals or the internal circuits of the Timer may be damaged.
The H3CR-H@RL uses transformerless power supply. When con­necting a relay or transistor as an external signal input device, pay attention to the following points to prevent short-circuiting due to a sneak current to the transformerless power supply.
If input is made simultaneously from one input contact or a transistor to the H3CR-H and a Timer whose common input terminals are used as power terminals, such as the H3CR-A, a short-circuit current will be generated. Either input through isolated contacts, or isolate the power supply for one of the Timers.
Wiring
The H3CR-H has a high impedance circuit. Therefore, the H3CR-H may not be reset if the H3CR-H is influenced by inductive voltage. In order to eliminate any influence of inductive voltage, the wires con­nected to the H3CR-H must be as short as possible and should not be installed alongside power lines. If the H3CR-H is influenced by inductive voltage that is 30% or more of the rated voltage, connect a CR filter with a capacitance of approximately 0.1
µF and a resistance
of approximately 120
or a bleeder resistor between the power sup-
ply terminals. If there is any residual voltage due to current leakage, connect a bleeder resistor between the power supply terminals.
Operation
An interval of 3 s minimum is required to turn on the H3CR-H after the H3CR-H is turned off. If the H3CR-H is turned on and off repeat­edly with an interval of shorter than 3 s, abnormal heating or burning may occur in internal elements.
After the forced reset function of the H3CR-H is activated, an interval of 3 s minimum is required to activate the forced reset function again. If the forced reset function is activated repeatedly with an interval of shorter than 3 s, the internal parts of the H3CR-H may deteriorate and the H3CR-H may malfunction.
If it is required that the output be turned on repeatedly with an inter­val of shorter than 3 s, consider use of the H3CR-A in mode D (signal OFF-delay).
Others
If the H3CR-H is dropped or experiences some other kind of shock, because a latching relay is used for output, contacts may be reversed or go into a neutral state. If the H3CR-H is dropped, reconfirm correct operation.
10
2
4*, 7
1*, 5
7*
2*
Correct
Input terminal
H3CR-H@RL
Power supply
Isolation transformer is required.
In
p
ut device
*
:H3CR-H8RL
H3CR-H@RL
Power
supply
Input
terminal
Input device
4*, 7
10, 7*
2, 2*
1*, 5
Incorrect
Isolation
transformer
*
:H3CR-H8R
L
10 7*
22*
10
2
R.S. 7
6G.5
4*
51*
7
H3CR-H@RL
Short-circuit current
*: H3CR-H8RL
H3CR-A
Powe r
3 s min.
Output state 1
Output state 2
Powe r
3 s min.
Output
3 s min.
Reset input
Solid-state Timer H3CR (Common) 45
Operation (Common)
Note: The undermentioned is common for all H3CR models.
Basic Setting
Setting of Selectors
The selectors can be turned clockwise and counterclockwise to select the desired time unit, time range, or operating mode. Each selector has a snap mechanism that secures the selector at a given position. Set the selector at a position at which it is secured. Do not set it midway between two securing positions or a malfunction could result from improper setting.
Selection of Operating Mode
• H3CR-A Multifunctional Timer
Turn the operating mode selector with a screwdriver until the desired operating mode (H3CR-A/AP/AS: A, B, B2, C, D, or E, H3CR-A8/ A8S/A8E: A, B2, E or J, H3CR-A-300: G or J) appears in the display window located above the selector.
Selection of Time Unit and Time Range
• H3CR-A Multifunctional Timer
The desired time unit (sec, min, hrs, or 10h) is displayed in the window below the time setting knob by turning the time unit selector located at the lower right corner of the front panel. A time range (1.2, 3, 12, or 30/2.4, 6, 24, or 60 for H3CR-A@-301) is selected with the time range selector at the lower left corner of the front panel, and the selected time range appears (in the window at the lower right part) within the plastic frame of the time setting knob.
• H3CR-F Twin Timers
A time range (0 to 1.2, 0 to 3, 0 to 12, or 0 to 30) is selected for ON­and OFF-time using the time range selector at the lower left corner of the front panel, and the selected time range appears within the plastic frame of the time setting knob (= scale range display windows).
For ON-time, the desired time unit (sec, 10 s, min, and hrs, or 10 s, 10 min, hrs, and 10 h) is indicated in the ON-time unit display window at the lower right corner of the front panel and can be changed by turning the ON-time unit selector located below the ON-time unit display window.
For OFF-time, the desired time unit (sec, 10 s, min, and hrs, or 10 s, 10 min, hrs, and 10 h) is indicated in the OFF-time unit display window at the upper right corner of the front panel and can be changed by turning the OFF-time unit selector located below the OFF-time unit display window.
(i.e., H3CR-A)
Operating mode selector
Operating mode display window
Groove for screwdriver
Time unit selector
Time unit display window
Time setting knob
Time range selector
Scale range display window
Time range selector
ON-time unit selector
OFF-time unit selector
46 Solid-state Timer H3CR (Common)
• H3CR-G Star-delta Timers
A star operation time range (0 to 6, 0 to 12, 0 to 60, or 0 to 120 seconds) is selected with the star operation time range selector at the lower left corner of the front panel.
The time required for switching (0.05, 0.1, 0.25, or 0.5 second) from the star operation to the delta operation of the H3CR-G can be selected with the star-delta transfer time selector at the lower right corner of the front panel.
• H3CR-H Power OFF-delay Timers
A time range (0 to 0.6, 0 to 1.2, 0 to 6, and 0 to 12) is selected with the time range selector at the lower left corner of the front panel. No time unit selector is available. When ordering the H3CR-H, specify S (for the second unit) or M (for the minute unit) for your H3CR-H.
Setting of Time
Use the time setting knob to set the desired time.
Using the Time Setting Ring for H3CR-A/-G
Setting a Specific Time
Mount the Panel Cover on the Timer, set the desired time with the time setting knob, and place Time Setting Ring A onto the time setting knob so that the time setting notch of Time Setting Ring A is in the center of the reset lock position of the Panel Cover.
Limiting the Setting Range
Example: To set a range of 10 and 20 s. Mount the Panel Cover on the Timer, set the time setting knob to 10 s (the lower limit of the setting range), and place Time Setting Ring C onto the time setting knob so that the stopper of Time Setting Ring C is on the right edge of the reset lock position of the Panel cover. Next, set the time setting knob to 20 s (the upper limit of the setting range), place Time Setting Ring B onto the time setting knob so that the stopper of Time Setting Ring B is on the left edge of the reset lock position of the Panel Cover.
Star operation time range selector
Star-delta transfer time selector
Time range selector
Reset lock position
Time Setting Ring A Panel cover
Example: To set the time to 10 s.
Time setting notch
Setting position
Time setting notch
Stopper
Reset lock position
Panel cover
Range
Time Setting Ring B
Time Setting Ring C
Solid-state Timer H3CR (Common) 47
Accessories (Order Separately) (Common)
Note: The undermentioned is common for all H3CR models.
Note: All units are in millimeters unless otherwise indicated.
Flush Mounting Adaptor
45
+0.6
0
(N)
45
+0.6
0
58 52
42 48
Y92F-30
Panel Cutout
0.5 R max.
Panel
Note: The adapters for two or more timers mounted in a vertical line are different in
orientation from those mounted in a horizontal line.
N can be obtained as follows (n: the number of H3CR models arranged side by side) Without a Cover: N = (48n - 2.5)
+1
/-0 With the Protective Cover: N = (51n - 5.5)+1/-0 With the Panel Cover: N = (50n - 4.5)+1/-0
P3G Back Connecting Socket
88
58
45±0.15
43±0.2
58
45±0.2
50
+0.2
-0
56
68
76±0.2
45
+0.5
0
55
+0.5
0
45±0.15
52.3 (63.7)
52.3 (63.7)
Y92F-70/-73
Y92F-71/-74
Panel
Panel
Panel Cutout
Adapter mounting hole Two, 4.5 dia.
52 to 53
65 to 66
R0.5 max.
R0.5 max.
Note: The mounting panel thickness
should be 1 to 3.2 mm.
Note: The mounting panel thickness
should be 1 to 3.2 mm.
P3G Back Connecting Socket
P3G Back Connecting Socket
Note: The value shown in
parentheses is for the Y92F-70.
(See note.)
Note: The value shown in
parentheses is for the Y92F-71.
(See note.)
48 Solid-state Timer H3CR (Common)
Track Mounting/Front Connecting Socket
Track Mounting/Front Connecting Socket
7.8
34.5
35.4
4
40±0.2
40±0.2
7.8
4
35.4
20.3
19
3
1.3
54.5
70 max.
50 max.
20.3 max.
P2CF-08-E (Finger Safe Terminal Type) Conforming to VDE0106/P100
Surface Mounting Holes
Two, 4.5 dia. or two, M4
50 max.
70 max.
21.5 max.
P2CF-08
Eight, M3.5 × 7.5 sems
Two, 4.5 dia. holes
Terminal Arrangement/ Internal Connections (Top View)
Two, 4.5 dia. holes
Eight, M3.5 × 7.5 sems
40±0.2
7.8
34.5
35.4
4
7.8
4
40±0.2
35.4
30
54.5
3
1.2
Surface Mounting Holes
Two, 4.5 dia. or two, M4
70 max.
50 max.
31.2 max.
P2CF-11-E (Finger Safe Terminal Type) Conforming to VDE0106/P100
70 max.
50 max.
31.2 max.
P2CF-11
Eleven, M3.5 × 7.5 sems
Terminal Arrangement/ Internal Connections (Top View)
Two, 4.5 dia. holes
Eleven, M3.5 × 7.5 sems
Solid-state Timer H3CR (Common) 49
Back Connecting Socket
Mounting Track
45
45
4.9
17
45
45
25.6
4.5
16.3
6.2
34
47.7 × 47.7
48 × 48
47.4
16.5
24.6
27.6
27 dia.
P3GA-11
27 dia.
Finger Safe Terminal Cover
Conforming to VDE0106/P100
Y92A-48G
Twelve, 6.4 dia. holes
P3G-08
Terminal Arrangement/ Internal Connections (Bottom View)
Terminal Arrangement/ Internal Connections (Bottom View)
(Attachment for P3G-08/P3GA-11 Socket)
4.5
15 25 25 25 25
10 10
7.3±0.15
35±0.3
27±0.15
1
4.5
15 25 25 25 25 15
10 10
35±0.3
27
24
16
29.2
11.5
1,000
PFP-100N2PFP-100N, PFP-50N
1,000 (500) (See note)
Note: The value shown in parentheses are for the
PFP-50N.
15 (5) (See note)
50
11.5
10
6.2
1.8
1
35.5 35.3
1.8
1.3
4.8
5
16
12
44.3
34.8
16.5
10
End Plate
PFP-M
M4 x 8 pan head screw
Spacer
PFP-S
50 Solid-state Timer H3CR (Common)
Protective Cover Y92A-48B
The protective cover protects the front panel, particularly the time setting section, against dust, dirt, and water. It also prevents the set value from being altered due to accidental contact with the time setting knob.
Note: 1. The Y92A-48B Protective Cover is made of a hard plastic
and therefore it must be removed to change the timer set value.
2. The Protective Cover cannot be mounted if the Panel Cover (sold separately) is used on the Timer.
Hold-down Clip
Hold-down clips are sold in sets of two.
Time Setting Ring/Panel Cover for H3CR-A/-G
There are three types of Panel Covers (Y92P-48GL, Y92P-48GB, and Y92P-48GM), all of which are available in three colors. Use the most suitable type of Panel Cover with the design of the scaling plate according to the application. When setting a given time for the Timer, use of the Y92S-27 or Y92S-28 Time Setting Ring facilitates the time setting operation and minimizes possible setting errors by operators.
The Y92F-73 or Y92-F-74 Flush Mounting Adapter or the Protective Cover cannot be used.
The Time Setting Ring and Panel Cover should be used as a pair.
Y92A-48B
Y92H-7/-1 For PL08 and PL11 Sockets
Y92H-8/-2 For PF085A Socket
Setting a specific time
Time Setting Ring A (Y92S-27) and Panel Cover (Y92P-48GL, -48GB, or -48GM)
Limiting the setting range
Time Setting Ring B or C (Y92S-28), and Panel Cover (Y92P-48GL, -48GB, or -48GM)
Y92S-27 Time Setting
Y92S-28 Time Setting
Y92S-28 Time Setting C
Y92P-48GL Light Gray
Y92P-48GB Black
Y92P-48GM Medium Gray
Solid-state Timer H3CR (Common) 51
Safety Precautions for All Timers
Note: The undermentioned is common for all H3CR models.
Precautions for Safe Use
Do not use the Timer in the following locations.
Locations with radical temperature changes.
Locations with high humidity that may result in condensation.
Locations with excessive vibration or shock.
Locations with corrosive gas or dust.
Locations where the Timer is exposed to sprayed water, oil, or
chemicals.
Organic solvents (such as paint thinner) as well as strong acid or alkali solutions will damage the outer casing of the Timer.
If the Timer is used in an area with excessive electronic noise, be sure to separate the Timer, wires, and input device as far as possible from the noise sources. Furthermore, it is recommended that the input signal wiring be shielded to prevent electronic interference.
Using a surge absorber is recommended if surge voltages occur.
Pay the utmost attention not to make mistakes in polarity when wiring the Timer.
The H3CR Series uses a transformerless power supply. Do not
touch the input terminals while the supply voltage is applied, otherwise an electric shock may be received.
Precautions for Correct Use
Changing the Setting
Do not change the time unit, time range, or operation mode while the Timer is in operation, otherwise the Timer may malfunction.
The time unit and time range can be set with the respective selectors turned clockwise or counterclockwise.
The selectors are of notched so that they will snap when they are properly set. Do not set the selectors midway between notches, otherwise the Timer may break or malfunction.
Do not use H3CR-A models (except for H3CR-A@S) in flicker mode, or H3CR-F models at the lowest selector setting. Doing so may result in damage to contacts.
Power Supplies
A DC power supply can be connected if its ripple factor is 20% or less and the mean voltage is within the rated operating voltage range of the Timer.
An AC power supply can be connected to the power input terminals without regard to polarity. A DC power supply must be connected to the power input terminals as designated according to the polarity of the terminals.
Make sure that the voltage is applied within the specified range, otherwise the internal elements of the Timer may be damaged.
Connect the power supply voltage through a relay or switch in such a way that the voltage reaches a fixed value at once, otherwise the Timer may not be reset or a timer error may result.
Be aware that the operating voltage will rise by 5% if the rated voltage is applied to the Timer continuously while the ambient temperature is close to the maximum permissible ambient temperature.
The power supply circuit of any H3CR-A model (except for H3CR­A@S), H3CR-F 100-to-240-VAC model, and H3CR-G model is a switching circuit. If the power line connected to the power supply circuit has a transformer with high inductance, a counter­electromotive voltage will be induced by the inductance. To suppress the voltage, apply a CR filter to the power supply line.
Precautions for EN61812-1 Conformance
The H3CR Series as a built-in timer conforms to EN61812-1 provided that the following conditions are satisfied.
Make sure that no voltage is applied to any terminals before dismounting the Timer from the Socket.
The output section of the H3CR is provided only with basic isolation.
The H3CR itself is designed under the following conditions:
Overvoltage category III
Pollution degree 2
Isolation
Operation parts: Reinforced isolation
With clearance of 5.5 mm and creepage distance of 5.5 mm at
230 VAC
Output: Basic isolation (See note)
With clearance of 3 mm and creepage distance of 3 mm at
230 VAC
Note: The 11-pin model ensures basic isolation by itself and also
ensures basic isolation with the 11-pin model mounted to the OMRON P2CF-11-@ or P3GA-11 Socket.
Connect the two output contacts different in polarity to the loads so that they will be the same in potential.
Others
If the Timer is mounted to a control board, dismount the Timer from the control board or short-circuit the control board circuitry before carrying out a voltage withstand test between the electric circuitry and non-charged metal part of the Timer. This protects the internal circuitry of the Timer from damage.
In the interest of product improvement, specifications are subject to change without notice.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Cat. No. L084-E1-06A
OMRON Corporation
Industrial Automation Company
Control Devices Division H.Q. Analog Controller Division
Shiokoji Horikawa, Shimogyo-ku, Kyoto, 600-8530 Japan Tel: (81)75-344-7080/Fax: (81)75-344-7189
Printed in Japan 1106-0.3M (0696) (C)
Warranty and Application Considerations
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS, OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted. IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE
PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's application or use of the products.
Take all necessary steps to determine the suitability of the product for the systems, machines, and equipment with which it will be used.
Know and observe all prohibitions of use applicable to this product. NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT
ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.