Large Setting Dial and Moving Pointers Ideal for Easy Operation and Monitoring
• Incorporating an easy-to-see large setting dial with moving pointers.
• Wide time-setting range of 0.2 s to 60 h (available through three time-range model types)
• Wide AC power supply range (100 to 240 VAC)
• IP65 watertight and dust-tight front panel.
• Approved by UL and CSA.
• Conforms to EN61812-1 and IEC60664-1 4 kV for Low Voltage, and EMC Directives.
• Conforms to EMC standards.
• Six-language instruction manual provided.
• Programmable contact enables the building of a self-holding relay circuit as well as built-in instantaneous contact. (-NS)
• Memory retention (-NSR)
• Finger protection terminal block
• Enables easy sequence checks through instantaneous outputs for a zero set value at any time range.
Model Number Legend
H3AM - NS
12-3
1. Resetting System
None: Self-resetting R: Electric resetting
-
2. Time Range
A: 0.5 s to 30 h B: 1 s to 60 h C: 0.2 s to 12 h
3. Accessory
None: Without accessory 300: Waterproof Packing (Y92S-35) provided
Ordering Information
List of Models
Rated supply
voltage
100 to 240 VAC
Note: The operation of the instantaneous contacts differs for the self-resetting and electric resetting systems. Refer to Timing Charts on page 5
for details.
Resetting
system
(See note.)
Self-resetting DPDT contact output
Electric resetting
Control output Time range
(Time-limit output SPDT and switchable SPDT (time-limit
DPDT contact output (Time-limit output SPDT and instantaneous output SPDT)
instantaneous))
0.5 s to 30 h (30 s, 3 min, 30 min, 3 h, 30 h)
H3AM-NS-A H3AM-NS-B H3AM-NS-C
H3AM-NSR-A H3AM-NSR-B H3AM-NSR-C
1 s to 60 h (60 s, 6 min,
60 min, 6 h, 60 h)
0.2 s to 12 h (12 s, 120 s, 12 min, 120 min, 12 h)
Mechatronic Analog Timer H3AM 1
Accessory (Order Separately)
Item Model
Waterproof Packing Y92S-35 (See note.)
Note: Supplied with H3AM-NS@-@-300 models.
Specifications
General
Operating mode ON-delay
Screw tightening torque 0.98 N·m (10 kgf) max.
Input type Voltage input
Output type Relay: DPDT
Mounting method Flush/Panel mounting, no restriction on mounting angle.
Approved standards UL 508, CSA C22.2 No. 14
Time Ranges
Conforms to EN61812-1, IEC60664-1 4 kV/2, VDE0106/P100 Output category according to IEC60947-5-1
Model Full scale on
H3AM-@@@-A 3 --- 0.5 to 30 s 0.05 to 3 min 0.5 to 30 min 0.05 to 3 h 0.5 to 30 h
H3AM-@@@-B 6 --- 1 to 60 s 0.1 to 6 min 1 to 60 min 0.1 to 6 h 1 to 60 h
H3AM-@@@-C 12 0.2 to12 s 2 to 120 s 0.2 to 12 min 2 to 120 min 0.2 to 12 h ---
Note: Instantaneous output is obtained by turning the time setting knob below "0" until the time setting knob stops.
dial
s 10 s min 10 min h (hour) 10 h (hour)
Set time unit
Ratings
Rated supply voltage 100 to 240 VAC (50/60 Hz)
Operating voltage range 85% to 110% of rated supply voltage
Power reset (-NS) Minimum power-opening time: 0.5 s
Reset input time (-NSR) Minimum input time: 0.5 s
Reset voltage range (-NSR) H level: 85 to 264 VAC
Power consumption Approx. 9 VA (Approx. 5 W)
Control output Contact output: 5 A at 250 VAC, resistive load (cos
Ambient temperature Operating: –10
Ambient humidity Operating: 35% to 85%
Note: The minimum applicable load:
H3AM-NS: 10 mA at 5 VDC (failure level: P, reference value) H3AM-NSR: 100 mA at 5 VDC (failure level: P, reference value)
L level: 0 to 10 VAC
Storage: –25
°C to 55°C (with no icing) °C to 65°C (with no icing)
φ = 1)
2 Mechatronic Analog Timer H3AM
Characteristics
Accuracy of operating time
Setting error
Reset time Power reset: 0.5 s max.
Influence of voltage
Influence of temperature
Insulation resistance 100 M
Dielectric strength 2,000 VAC (50/60 Hz) for 1 min between exposed non-current-carrying metal parts and current-carrying metal parts
Impulse withstand voltage 3 kV between power terminals
Noise immunity
Static immunity Malfunction: 8 kV
Vibration resistance Destruction: 10 to 55 Hz, 0.75-mm single amplitude for 2 cycles each in 3 directions (8 min per cycle)
Shock resistance
Life expectancy Mechanical: 5,000,000 times min. (under no load at 1,800 times/h)
Motor life expectancy 20,000 h
EMC (EMI): EN61812-1
Enclosure rating IP65 (front panel only) (See note.) IP20 (terminal section)
Weight Approx. 350 g
Note: A separately sold waterproof packing (Y92S-35) is necessary to ensure IP65 waterproofing between the Timer and installation panel.
The H3AM-NS@-@-300 model with waterproof packing is available.
±0.7% FS max.
±2% FS max.
Reset input time: 0.5 s max.
±1% FS max.
±2% FS max.
max. (at 500 VDC)
2,000 VAC (50/60 Hz) for 1 min between the operating circuit and control output terminals 1,000 VAC (50/60 Hz) for 1 min between the operating power supply circuit and reset input circuit (H3AM-NSR only) 1,000 VAC (50/60 Hz) for 1 min between contacts not located next to each other 2,000 VAC (50/60 Hz) for 1 min between contacts of opposite poles
4.5 kV between exposed non-current-carrying metal parts and current-carrying metal parts
±1.5 kV (between power terminals) square-wave noise by a noise simulator
(pulse width: 100 ns/1
Destruction: 15 kV
Malfunction: 10 to 55 Hz, 0.5-mm single amplitude for 2 cycles each in 3 directions (8 min per cycle)
Destruction: 300 m/s Malfunction: 150 m/s
Electrical: 100,000 times min. (5-A at 250 VAC, resistive load at 1,800 times/h)
Emission Enclosure: EN55011 class A Emission AC Mains: EN55011 class A (EMS): EN61812-1 Immunity ESD: IEC61000-4-2: 6 kV contact discharge
Immunity RF-interference: IEC61000-4-3: 10 V/m (Amplitude-modulated, 80 MHz to 1 GHz)
Immunity Power Frequency Magnetic Fields: IEC61000-4-8: 30 A/m (50 Hz) Immunity Conducted Disturbance: IEC61000-4-6: 10 V (0.15 to 80 MHz) Immunity Burst: IEC61000-4-4: 2 kV power-line
Immunity Surge: IEC61000-4-5: 1 kV line to line
µs, 1-ns rise)
2
3 times each in 6 directions
2
(100 m/s2 in the front/back direction) 3 times each in 6 directions
8 kV air discharge
10 V/m (Pulse-modulated, 900 MHz
2 kV I/O signal-line
2 kV line to ground
±5 MHz)
Mechatronic Analog Timer H3AM 3