Omron G9SE-221-T, G9SE-201, G9SE-401 User Manual

(1) Handle with care
Do not drop G9SE to the ground or expose to excessive vibration or
mechanical shocks. G9SE may be damaged
and may not function properly.
(2) Adhesion of solvent such as alcohol, thinner, trichloroethane or gasoline on the product should be
avoided. Such solvents make the marking on G9SE illegible and cause deterioration of parts. (3) Conditions of storage Do not store in such conditions stated below.
1) In direct sunlight
2) At ambient temperatures out of the range of -10 to 55
3) At relative humidity out of the range of 25% to 85% or under such temperature change that causes
condensation.
4) At atmospheric pressure out of the range 86 to 106 kPa.
5) In corrosive or combustible gases
6) With vibration or mechanical shocks out of the rated values.
7) Under splashing of water, oil, chemicals
8) In the atmosphere containing dust, saline or metal powder. G9SE may be damaged and may not function properly. (4) At least 50 mm
above top face of G9SE and below bottom face of G9SE
should be available to apply rated
current to outputs of G9SE and for enough ventilation.
(5) Mounting multiple units   When mounting multiple units close to each other, the rated current will be 3 A. Do not apply a current higher than 3 A. If the output current is 3 A or more, make sure that there is a minimum distance of 10mm each between all adjacent G9SE units.
(6) DIN rail mounting
Mount G9SE to DIN rails with attachments (TYPE PFP-M, not incorporated to this product), not to drop out of rails by vibration etc.
especially when the length of DIN railing is short compared to the widths of G9SE.
(7) Wire correctly according to 8 Wiring.
(8) Use cables with length less than 100 m to connect to Safety Inputs, Feed-back/Reset inputs, respectively. (9) G9SE may malfunction due to electro-magnetic disturbances. Be sure to connect the negative terminal of DC power supply to ground. When using a DC power supply with light curtains, use DC power supply which has no interruption by a power failure of 20 ms. (10)This is a class A product. In residential areas it may cause radio interference, in which case the user may be required to take adequate measures to reduce interference.
(11) Do NOT mix AC load and DC load to be switched in the following terminals.
   - G9SE-201 : between 13-14 terminal and 23-24 terminal
   - G9SE-401 : between 13-14 terminal and 23-24 terminal, 33-34 terminal and 43-44 terminal
   - G9SE-221-T : between 13-14 terminal and 23-24 terminal, 37-38 terminal and 47-48 terminal
(12)
Start entire system after more than 2s have passed since applying supply voltage to G9SE.
(13) Set the time duration of OFF-delay (Type
G9SE-221-T
)
1) Set the time duration of OFF-delay to an appropriate value that does not cause the loss of safety function of system.
2)
Set both of the two O-delay Time Preset Switches, one each
on the front and back, to the same value.
When setting the
dierent value, it is detected as a fault.
After setting, make sure G9SE operating time is correct
.
(14) To determine safety distance to hazards, take into account the
delay of Safety outputs caused by the following time:
1) Response time
2) Preset o-delay time and accuracy of o-delay time (15) Before G9SE outputs become in ON-state, non-regular self­ diagnosis for Safety output circuit may be executed. On this occasion, the operating noise of internal relays occurs. (16) In the place subjected to strong vibration or shock, mount G9SE to a mounting surface with screws and the screw mounting attachment. Otherwise, G9SE may not function properly due to vibration or mechanical shocks out of the rated values caused by sympathetic vibration of G9SE and the mounting parts, and so on.
Appearance and Explanation of Each Parts
3
Ratings and Specications
4
G9SE-201 G9SE-401 G9SE-221-T
Contact output 250 VAC 5 A 30 VDC 5 A (resistance load)
AC15: 240 VAC 2 A DC13: 24 VDC 1.5 A
Switching specication for Inductive load (IEC/EN60947-5-1)
Ratings
Specications and performance
Operating time (OFF to ON state) (See Note2)
100 ms Max. (See Note3)
3 W max.
Type G9SE-221-T
4 W max.
4 W max.
300 m/s
2
Ambient humidity
Surround Air Temperature
Mechanical shock resistance (See Note7)
Vibration resistance (See Note7)
25% to 85%RH
-10 to 55 (No freezing or condensation)
Frequency:10 to 55 to 10 Hz Amplitude:0.35 mm half amplitude (0.7 mm double amplitude)
15 ms Max.
1
Rated supply voltage 24 VDC
-15% to 10% of rated supply voltage
SuitabilityforUse
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the combination of the Product in the Buyer’ s application or use of the Product. At Buyer’ s request, Omron will provide applicable third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine, system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product with respect to Buyer’ s application, product or system. Buyer shall take application responsibility in all cases. NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PNP transistor output Load current100 mA DC max.
G9SE-201 G9SE-401 G9SE-221-T
Contact resistance (See Note5)
100 mΩ Max.
Maximum cable length 100 m Max. Reset input time
250 ms Min.
Accuracy of OFF-delay time
Within plus or minus 10% of the set value (See Note4)
Impulse withstand voltage (IEC/EN 60947-5-1)
Insulation resistance 100 MΩ Min.
5,000,000 operations Min.
Mechanical durability
50,000 operations Min.
Minimum applicable load
Pollution degree 2 Over voltage category (IEC/EN60664-1) Safety output: Class Ⅲ, the others: Class
Degree of protection
IP20
Weight
approx. 150 g approx.180 g approx.180 g
Note: (1) Power consumption of loads not included .
(2) This does not include the bounce time of internal relay in the G9SE. (3) This is in normal operation. When executing
non-regular self-diagnosis for Safety output circuit,
G9SE operating time become 500 ms max.. (4) This is initial value using the voltage-drop method with 1A at 5VDC. (5) Use an 8A fuse that conforms to IEC 60127 as a short-circuit protection device. This fuse is not included with the G9SE. (6) Condition: G9SE is mounted to
mounting surface with screw and the screw mounting attachment.
In the case of DIN rail mounting, mount DIN rail with G9SE to the place without big vibration. (Amplitude guideline: Less than 0.15 mm half amplitude (0.3 mm double amplitude))
Conditional short-circuit current (IEC/EN60947-5-1)
100 A (See Note6)
Preset Switches (only applies to Type G9SE-221-T)
Change the value of the preset switches only when G9SE is disconnected from power supply.
Function Presets OFF-delay time (duplicate) (*1)
Name OFF-delayed time preset switch
Value For Type G9SE-221-T05
0(default setting value)/0.1/0.2/0.3/0.4/0.5/0.6/0.7/0.8/1.0/1.5/2.0/2.5/3.0/4.0/5.0(s)(*2)
For Type G9SE-221-T30
0(default setting value)/1/2/4/5/6/7/8/9/10/12/14/16/20/25/30(s)(*2)
(*1)
Set both of the two O-delay Time Preset Switches, one each on the front and back, to the same value.
When setting the dierent value, it is detected as a fault. (*2)
See following illustration for setting position of O-delay Time Preset Switch. Make sure that the direction of cutting
edge of preset switch is correctly pointed to the o-delay time value which must be set.
ex.1) 0 second o-delay setting
ex.2) 1.5 second o-delay setting
OFF-DELAY
0
5.0
4.0
3.0
2.0
1.5
1.0
0.8
0.7
0.6
0.5
0.4
0.3
0.1
0.2
2.5
OFF-DELAY
0
5.0
4.0
3.0
2.0
1.5
1.0
0.8
0.7
0.6
0.5
0.4
0.3
0.1
0.2
2.5
cutting edge
LED Indicators
Marking
Color Name Function
PWR Green
Power supply Indicator
Lightsupwhilepowerissupplied. Blinkscorrespondingtotheoccurringerror
IN1 Orange
Safety Input #1 indicator
LightsupwhilehighsignalisinputtoT12 BlinkswhenerrorrelatingtoSafetyinput#1occurs.
IN2
OUT OUT1
LightsupwhileSafetyoutputs(13-14,23-24,33-34,43-44)areinON-state. BlinkswhenanerrorrelatingtoSafetyoutputoccurs.
OUT2
Lightsupwhileoff-delayedSafetyoutputs(37-38,47-48)areinON-state. BlinkswhenanerrorrelatingtoSafetyoff-delayedsolid-stateoutputoccurs.
Input current
ON voltage
Type G9SE-401 Type G9SE-221-T
Type G9SE-201
Reset/Feedback Input
Safety Outputs (Instantaneous)
Safety Outputs (OFF-delay)
OFF-delay time preset switch
Power Supply
Safety Input1
Safety Input2
Auxiliary output
Precautions for Correct Use
6 kV
24 VDC 4 mA
Inputs
OFF voltage OFF current
11 VDC Min.
5 mA Min.
5 VDC Max.
1 mA Max.
Electrical durability Contact outputs
Insulation specication
Dielectric strength
1,500 VAC
Destruction
Malfunction
100 m/s
2
22.5
124
109
4
111.6
4
3
6.6
3
17.5
Type G9SE-201
Type G9SE-401
Type G9SE-221-T
5.6
5.6
R2.3
11.4
9.9
71 73.5
Mounting holes
133 ±0.3
Two, 4.2 dia. or M4
Screw mounting attachment
Insert
(1) Use G9SE within an enclosure with IP54 protection or higher of IEC/EN60529. (2) When ready for wiring, the power source should be disconnected rst. Further, at operating this unit, do not touch the terminals in order to prevent an electrical shock. (3) Do not apply any excessive voltage or current to the input or output circuit the G9SE. Doing so may result in damage to the G9SE or cause a re. (4) Incorrect wiring may lead to loss of safety function. Wire conductors correctly and verify the operation of G9SE before commissioning the system in which G9SE is incorporated. (5) Do not apply DC voltages exceeding the rated voltages, or AC voltages to G9SE. (6) Use DC supply satisfying requirements below to prevent electric shock.
- DC power supply with double or reinforced insulation, for example, according to IED/EN60950 or EN50178 or a transformer according to IEC/EN61558.
- DC supply satises the requirement for class 2 circuits or limited voltage/current circuit stated in UL 508.
(7) The lifetime of G9SE depends on the conditions of switching of its outputs. Be sure to conduct its test operation under actual operating conditions in advance and use it within appropriate switching cycles. Apply protection circuitry against back electromotive force in case connecting inductive loads to safety outputs. (8) Do not operate the G9SE with ammable or explosive gas. An arc with operation and the heat of relay will cause a re or an explosion. (9) Do not
drop G9SE to the ground or ,
dismantle, repair, modify G9SE,
otherwise an electric shock may occur or
the G9SE may malfunction
. It may lead to loss of its safety functions. (10) Use protective device (Fuse etc.) for short-circuit protection and ground fault protection, otherwise a re may occur or the G9SE may malfunction. (11)
Auxiliary monitoring outputs are NOT safety outputs.
Do not use auxiliary outputs as any safety output.
Such incorrect use causes loss of safety function of G9SE and its relevant system. (12) After installation of G9SE, qualied personnel should conrm the installation, and should conduct test operations and maintenance. The qualied personnel should be qualied and authorized to secure the safety on each phases of design, installation, running, maintenance and disposal of system. (13) A person in charge, who is familiar to the machine in which G9SE is to be installed, should conduct and verify the installation.
Type G9SE-201 Type G9SE-221-T
Type G9SE-401
4022078-4 A
Original instructions
Safety Relay Unit
USER'S MANUAL
English
Thank you for purchasing G9SE Safety Relay Unit. Please read and understand this manual before using the products.
Keep this manual ready to use whenever needed. Only qualied person trained in professional electrical technique should handle G9SE.
Please consult your OMRON representative if you have any questions or comments.
EC Declaration of Conformity
OMRON declares that G9SE series are in conformity with the requirements of the following EC Directives:
- EMC Directive: 2004/108/EC
- Machinery Directive: 2006/42/EC
G9SE series are designed and manufactured in accordance with the following standards:
- EN ISO13849-1: 2008 PL e Category 4
- IEC/EN 60947-5-1, - IEC/EN 62061 SIL3,
- EN81-1 - EN81-2
- UL508 - CAN/CSA C22.2 No.14
Standards
Precaution for Safe Use
WARNING
Indicates a potentially hazardous situation which, if not avoided, will result in minor or moderate injury, or may result in serious injury or death. Additionally there may be signicant property damage.
Meanings of Signal Words The following signal words are used in this manual.
Indicates prohibited actions
Meaning of Alert Symbols The following alert symbols are used in this manual.
Indicates mandatory actions
Alert Statements
Serious injury may possibly occur due to breakdown of safety outputs. Do not connect loads beyond the rated value tothe safety outputs.
Serious injury may possibly occur due to loss of required safety functions. Wire G9SE properly so that supply voltages or voltages for loads do NOT touch the safety inputs accidentally or unintentionally.
WARNING
Seriousinjurymaypossiblyoccurduetolossofsafetyfunctions. Useappropriatedevicesreferringtotheinformationshownbelow.
Controlling Devices Emergency stop switch
Door interlocking switch Limit switch Safety Sensor
Relay with forcibly guided contacts
Contactor
Other devices
Requirements Use approved devices with Direct Opening Mechanism complying with IEC/EN 60947-5-1 Use approved devices with Direct Opening Mechanism complying with IEC/EN 60947-5-1 and capable of switching micro loads of 24VDC, 5mA. Use approved devices complying with the relevant product standards, regulations and rules in the country where it is used. Use approved devices with forcibly guided contacts complying with EN 50205. For feedback purpose use devices with contacts capable of switching micro loads of 24VDC, 5mA. Use contactors with forcibly guided mechanism to input the signal to Feedback/Reset input of G9SE through the NC contact of the contactor. For feedback purpose use devices with contacts capable of switching micro loads of 24VDC, 5mA. Failure to open contacts of a contactor cannot be detected by monitoring its auxiliary NC contact without forcibly guided mechanism. Evaluate whether devices used are appropriate to satisfy the requirements of safety category level.
Precautions for Safe Use
(14) Perform daily and 6-month inspections for the G9SE. Otherwise, the system may fail to work properly, resulting in serious injury. Turn OFF the signal to Safety input and make sure G9SE operates without fault by checking the state of the LED indicator in inspection. (15)
Conformity to requirements of performance level is determined as an entire system.
It is recommended to consult a certication body regarding assessment of conformity to the required safety level. (16) OMRON shall not be responsible for conformity with any safety standards regarding to customer's entire system.
(17) Dispose of the Units according to local ordinances as they apply.
Internal Connection
2
● Type G9SE-201
● Type G9SE-01
● Type G9SE-221-T
A1A2T11 T12 T32 T33
13 23
Safety Outputs (instanta
neous)
37 47
14 24 38 48
T21 T22
Reset/
Feedback
Input
Safety Input 1
Power supply circuit
Safety Input 2
T31
X1
Auxiliary Output
Safety Outputs
(OFF-
delay)
A1A2T11 T12 T32 T33
13 23
Safety Outputs
(instanta
neous)
33 43
14 24 34 44
T21 T22
Reset/
Feedback
Input
Safety Input 1
Power supply circuit
Safety Input 2
T31
X1
Auxiliary Output
A1
A2
T11 T12 T32 T33
13 23
Safety Outputs
(instanta
neous)
14 24
T21 T22
Reset/
Feedback
Input
Safety Input 1
Power supply circuit
Safety Input 2
T31
X1
Auxiliary
Output
Dimensions
Orange
Orange
Orange
Safety Input #2 indicator Safety Output indicator OFF-delayed Safety Output indicator
LightsupwhilehighsignalisinputtoT22 BlinkswhenerrorrelatingtoSafetyinput#2occurs.
cutting edge
Power input
Outputs
Item
Operating voltage range
Rated power consumption (See Note1)
Safety output OFF-delayed Safety output
Auxiliary output
Response time (ON to OFF state) (See Note2)
Note: Specications subject to change without notice.
OMRON Corporation (Manufacturer)
Shiokoji Horikawa, Shimogyo-ku, Kyoto, 600-8530 JAPAN
RegionalHeadquarters
OMRONEUROPEB.V.(ImporterinEU)
Wegalaan 67-69, 2132 JD Hoofddorp The Netherlands Tel: (31)2356-81-300/Fax: (31)2356-81-388
Contact:www.ia.omron.com
OMRONASIAPACIFICPTE.LTD.
No. 438A Alexandra Road # 05-05/08 (Lobby 2), Alexandra Technopark, Singapore 119967 Tel: (65) 6835-3011/Fax: (65) 6835-2711
OMRON(CHINA)CO.,LTD.
Room 2211, Bank of China Tower, 200 Yin Cheng Zhong Road, PuDong New Area, Shanghai, 200120, China Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200
OMRONSCIENTIFICTECHNOLOGIESINC.
6550 Dumbarton Circle Fremont CA 94555 U.S.A Tel: (1) 510-608-3400/Fax: (1) 510-744-1442
[mm]
Type G9SE-221-TType G9SE-221-T
Between input and output Between dierent poles of output Between input and output Between dierent poles of output
2,200 VDC
6 kV (between 13-14/23-24 and 33-34/43-44(37-38/47-48)) 4 kV (between 13-14 and 23-24,
between 33-34(37-38) and 43-44(47-48))
LED indicator
Wiring
Recommended driver: Type XW4Z-00B manufactured by Omron Type SZF0-0.4mmx2.5mm manufactured by Phoenix contact
8
- Insulated ferrule: AWG24 to AWG16 (0.25 to 1.5 mm2)
- Crimp height(H): 2.0 mm max Width(W): 2.7 mm max. Conductor length: 8 to 10 mm When using the twin type ferrule, use equal-sized wires and preferred insulated ferrule. The twin type ferrule should not be above the adjoining release hole.
How to insert solid wire and insulated ferrule
The wire should be pushed into the terminal block straight. No need to use the driver. After inserting, make sure wire is fastened on to terminal block.
How to release wire
Use the following minus drive to release wire from terminal block. And
When releasing wire, the power source should be disconnected rst.
1. Push the driver lightly into the taper of release hole.
2. Pull out the wire while the driver is pushed into release hole.
3. Pull out the driver.
Terminal block may be damaged.
1. Not push the driver into the release hole straight.
2. Not push the driver into the release hole by force of 30N and over.
3. Not tip or twist the driver pushed into release hole.
Precautions for Correct wiring
Fault Detection
When G9SE detects a fault, LED indicators blink to show the information of the fault.
When PWR indicator blinks, check and take needed measures referring to the following table. And then apply supply voltage to G9SE.
7
PWR
1) Failures involving the wiring of Safety input 1
1) Failures involving the wiring of Safety input 2
1) Supply voltage outside the rated value.
Expected causes of
the faults
Checking points and
measures to take
1) Check the wiring to T11 and T12.
When using stranded wire, insulated ferrule should be used. Use below insulated ferrule. But do not use ferrule terminals if G9SE is used as UL Listing. Insert the strand or solid wire directly into the holes on the terminal block.
Recommended insulated ferrule: manufactured by Phoenix contact
Type
Single
AI 0,34-8TQ AI 0,5-10WH AI 0,75-10WH
AI 1-10RD AI 1.5-10BK
Twin
AI TWIN2x0.75-10WH
Wire size
Cross section(mm
2
) AWG
0,34 0,5
0,75 1,0
1,5
2 x 0.75
22 20
18
18 16
Type G9SE-221-T Guard lock safety door switch (Mechanical Lock) 2-channel Safety limit switch inputs / Manual reset
A1
A2
T11 T12 T32 T33
13 23
14 24
T21 T22
T31
X1
24V
PLC etc.
M
KM2
KM1
S1
S3
M
:Safety limit switch
:Contactor :3-phase motor
Device
Guard lock safety
door switch S2
Operation command
KM1,KM2 N.C. contact
KM1,KM2 N.O. contact
Reset switch S3
Timing chart
37
47
38 48
KM1 KM2
KM2
KM1
S2
KM1,KM2
:Guard lock safety door switch (Mechanical Lock) :Reset switch
S3
Safety limit switch S1
14
Motor controller
Motor controller
(Operation command)
OFF-delay time
Rotation of motor
Blink
2)
Failures of the parts of the circuits
of Safety input 1.
2)
Failures of the parts of the circuits
of Safety input 2.
2) Replace with a new product.
H
W
Release hole
Wire
Front
φ2.5mm
2.5mm
Side
0.4mm
812°
Driver
Performance level and safety category (EN ISO13849-1)
Type G9SE can construct the condition conforming to PL=e and category 4 requested by EN ISO13849-1 European standard. This category class is recognized and based on the circuits we made, so we would like you to conform the category class with G9SE at your application once. Category is judged by the condition of the whole control system.
In order to category 4EN ISO13849-1
1) Input the signals to both of the Safety inputs (T11-T12 and T21-T22)
2) Input a signal to the Safety inputs (T11-T12 and T21-T22) through switches with Direct Opening Mechanism. When using limit switches, at least one of them must have Direct Opening Mechanism.
And wiring must be done in a way that a short circuit between the wires of safety input can be excluded.
3) When connecting Safety sensor with G9SE, use TYPE 4 safety sensor.
4) Input the signal through a NC contact of the contactor to Feedback/Reset input (T31-T32 for manual reset or T31-T33 for auto reset).(Refer to '5.Examples of Application')
5) Be sure to connect
the negative terminal of DC power supply
to ground.
6) Use two safety outputs (e.g. 13-14 and 23-24) for the system construction.
6
To set Safety outputs in ON state, HIGH state signals must be input to both of Safety input 1 and Safety input 2. Otherwise Safety outputs cannot be inON state.
To set Safety outputs in ON state, ON state signal must be input to T33. Otherwise Safety outputs cannot be in ON state.
To set Safety outputs in ON state, the signal input to T32 must change from OFF state to ON state, and then to OFF state.
Otherwise Safety outputs cannot
be in ON state.
Turns ON/OFF according to the state of safety inputs, Feedback/Reset inputs. During o-delay state, safety outputs are not able to turn ON.
O-delayed safety outputs. (See Note1) O-delay time is set by o-delay preset switch. When the delay time is set to zero, these outputs can be used as non-delay outputs.
Outputs a signal of the same logic as Safety outputs
Wiring of inputs and outputs
Signal Name
Safety input 1
Power supply input
Terminal Name
T11,
T12
A1, A2
Safety input 2
T21,
T22
Reset/ Feedback input
T31,
T32,
T33
WiringDescription of operation
1-channel
Safety input
2-channel
Safety input
Auto reset
Manual reset
Safety output
13-14,
O­delayed Safety output
Auxiliary output
X1
Keep these outputs Open when NOT used.
Keep these outputs Open when NOT used.
Keep these outputs Open when NOT used.
The input terminals for power supply. Connect the power source to the A1 and A2 terminals.
Connect the power supply plus to the A1 terminal. Connect the power supply minus to the A2 terminal.
Feedback loop
Feedback loop
T11 T12 T21 T22
+24V
T11 T12 T21 T22
T11 T12 T21 T22
KM
+24V
T31 T33T32
KM
+24V
T31 T33T32
Reset Switch
23-24, 33-34, 43-44,
37-38, 47-48
Connecting Safety Sensors and G9SE
640µsMax.
In many case, Safety Sensor outputs include the o-shot pulse for its self test. The following condition of test pulse is applicable as safety inputs for G9SE.
- O-shot pulse width of the sensor, during the ON-state : 640 μs
(1) When the inputs of G9SE-221-T are restored during o-delay time, G9SE-221-T will operate as below. Depending on the reset mode.
- Auto reset mode: Outputs turn o after o-delay time, then immediately turens on.
- Manual reset mode: Outputs turn o after o-delay time, then turn on when reset input is given.
IN1 IN2
OUT OUT1
OUT2
Blink
Blink
Blink
Blink
The all indicators Blink
Blink
Safety inputs: ON-state
Light
Light
Safety inputs: OFF-state
Light Light
Blink
LED indicator
PWR
IN1 IN2
OUT
OUT1
OUT2
Use the following to wire to G9SE.
- Solid wire: AWG24 to AWG16 (0.25 to 1.5 mm
2
)
- Stranded wire: AWG24 to AWG16 (0.25 to 1.5 mm2) Strip the cover of wire no longer than 8 to 10 mm
Blink
Blink
L
Safety sensor
OSSD1 OSSD2
S2
OPEN
S4
S1
KM2
KM1
Guard
Stop signal
Lock release signal
S4
:Lock release switch
Lock release signal
Lock release switch S4
Stop signal
Guard closed opened
Guard can be opened.
●TerminalarrangementandLEDindicators
T33
T32
T31
X1
24
14
T21
23
T22
13
T12
T11
A1
A2
Type G9SE-401 Type G9SE-221-TType G9SE-201
PWR
IN1
IN2
OUT
PWR
IN1
IN2
OUT
PWR
IN1
IN2 OUT1
OUT2
T33
T32
T31
X1
44
34
T21
43
T22
33
T12
T11
A1
A2
24
14
23
13
T33
T32
T31
X1
48
38
T21
47
T22
37
T12
T11
A1
A2
24
14
23
13
5
Examples of application
Type G9SE-201 2-channel emergency stop switch input / Manual reset
A1
A2
T11 T12 T32 T33
13 23
Safety Output (Instant
aneous)
14 24
T21 T22
Reset/
Feedback
Input
Safety Input1
Power
supply
circuit
Safety Input2
T31
X1
Auxiliary
output
KM1 KM2
24V
PLC etc.
S1
KM2
KM1
Feedback loop
S2
M
KM2
KM1
S1
KM1,KM2 M
:Emergency stop switch
S2 :Reset switch
:Contactor :3-phase motor
Device
Note1 : This example is corresponding to category 4
Emergency stop switch S1
KM1,KM2 NC contact
KM1,KM2 NO contact
Reset switch S2
Timing chart
Type G9SE-401 2-channel safety sensor / Auto reset
A1
A2
T11 T12 T32 T33
13 23
Safety
Output (Instant aneous)
14 24
T21 T22
Reset/
Feedback
Input
Safety Input1
Power
supply
circuit
Safety Input2
T31
X1
Auxiliary
output
KM1 KM2
24V
PLC etc.
KM4
KM3
Feedback loop
M1
KM2
KM1
KM1KM4 M1,M2
Safety sensor
:Contactor :3-phase motor
Device
Note1 : This example is corresponding to category 4
Safety sesor outputs
KM1KM4 NC contact KM1KM4 NO contact
Timing chart
33 43
34 44
KM3 KM4
M2
KM4
KM3
KM2
KM1
NC
NC
Safety sensor
ReceiverEmitter
OSSD1
OSSD2
Reset/
Feedback
Input
Safety Input1
Power supply circuit
Safety Input2
Auxiliary
output
Safety Output (Instant aneous)
Safety Output
(OFF-
delay)
Feedback loop
Note1 : This example is corresponding to category 4
The all indicators Light o
up
up
o o
1) Check the wiring to T21 and T22.
2) Replace with a new product.
2)
Failures of the parts of the circuits
of Feedback/Reset input.
1)
Failures involving the wiring of
Feedback/Reset input.
1)
Check the wiring to T31, T32, and T33
2) Replace with a new product.
1) Replace with a new product.
1)
Failures of the parts or relays of the circuits of instantaneous Safety Output.
1) Mismatch
of the two O-delay
Time Preset Switches.
2)
Failures of the parts or relays of the circuits of OFF-delay Safety Output.
1) Check
both of the two O-delay Time
Preset Switches.
2) Replace with a new product.
1) Check the supply voltage to G9SE.
1) By excessive electro-magnetic disturbance.
2) Failures of the parts of internal circuits
2) Replace with a new product.
1) Check the disturbance level around G9SE and its related system.
When indicators other than PWR indicator blink while PWR indicator lights up, check and take needed measures referring to the following table. After removing the fault, turn both safety inputs to OFF state.
Light
up
Safety inputs: ON-state
Light
o
Light
o
Expected causes of
the faults
Checking points and
measures to take
1) Mismatch
between Safety input 1 and Safety input 2. (OFF timing)
1)
Check the wiring from safety input devices
to G9SE.
Or check the inputs sequence of
safety input devices.
Loading...