Omron G9SB-2002-A, G9SB-200-B, G9SB-2002-C, G9SB-200-D, G9SB-3010 Datasheet

...
1
G9SB Safety Relay Unit
Ultra Slim Safety Relay Unit
Models of width 17.5 mm (smallest Unit in the
world as of January 2001) available with 2 or 3 poles. Models of width 22.5 mm with 3 poles also available.
DIN track mounting possible.
Ordering Information
Model Num ber Legen d:
1. Function
None: Emergency stop
2. Contac t Con figuratio n (S a fet y O utp u t)
2: DPST-NO 3: 3PST-NO
3. Contact Configuration (OFF-delay Output)
0: None
4. Contact Configuration (Auxiliary Output)
0: None 1: SPST-NC
5. Input Configur a tio n
None: 1-channel or 2-channel input possible 0: None (direct breaking) 2: 2-chan ne l input
6. Miscellaneous
A: Auto-reset, inverse input B: Auto-reset, + common input C: Manual-reset, inverse input D: Manual-reset, + common input
Main contacts Auxi liary
contact
Number of input
channels
Reset mode Input type Rated
voltage
Model Category
DPST-NO None 2 channels Auto-reset Inverse 24 VAC/VDC G9SB-2002-A 4
1 channel or 2 channels
+ common G9SB-200-B
2 channe ls Ma nu a l -r e se t Inverse G9SB-2 0 02 - C 1 channel or 2
channels
+ common G9SB-200-D
3PST-NO SPST-NC None (direct
breaking)
Auto-re s et -- - 24 VDC G9SB-30 10 3
2 channe ls Invers e 24 VAC /VDC G9SB- 30 12 - A 4 1 channel or 2
channels
+ common G9SB-301-B
2 channe ls Ma nu a l -r e se t Inverse G9SB-3 0 12 - C 1 channel or 2
channels
+ common G9SB-301-D
G9SB-
@@@@@ @
1 2 3 4 5 6
2
G9SB
G9SB
Specifications
Ratings
Power Input
Inputs
Note Indicates the current between terminals A1 and A2.
Contacts
Characteristics
Note: 1. The contact resistance was measured with 1 A at 5 VDC using the voltage-drop method.
2. The bounce time is not included in the figure for operating time.
3. The response time is the time it takes for the main contact to open after the input is turned OFF.
4. The insulation resistance was measured with 500 VDC at the same places that the dielectric strength was checked.
Item G9SB-200
@-@
G9SB-3010 G9SB-301@-
@
Power supply volta ge 24 VAC/VDC: 24 VAC, 50/60 Hz, or 24VDC
24 VDC: 24 VDC
Operati ng voltage range
85% to 110% of rated power supply voltage
Power consumption 1.4 VA/1.4 W max. 1.7 W max. 1.7 VA/1.7 W max.
Item G9SB-200@-
@
G9SB-3010 G9SB-301@-
@
Input current 25 mA max. 60 mA max. (See note.) 30 mA max.
Item G9SB-200@-
@
G9SB-3010 G9SB-301@-
@
Resistive loa d (cos Φ=1)
Rated load 250 VAC, 5 A Rated carry current 5 A
Item G9SB-200
@-@
G9SB-3010 G9SB-301@-
@
Contact resistance (See note 1.) 100 m Operating time (See note 2.) 30 ms max. Response time (See notes 2 and 3.) 10 ms max. Insulation resistance (See note 4.) 100 M
min. (at 500 VDC)
Dielectric strength
Between differ­ent outputs
2,500 VA C, 50/60 Hz for 1 min
Between inpu ts and outputs
Between powe r inputs and out­puts
Vibration resistanc e 10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double ampli tude) Shock re s ist a nc e Destru ct i on
300 m/s
2
Malfunction
100 m/s
2
Durability Mechanical 5,000,000 op era tions min. ( at approx. 7,200 op er ations/hr)
Electrical 100,000 operations min. (at approx. 1,800 operations/hr) Error rate, p-level (reference value) 5 VDC, 1 mA Ambient operating temperature -25 to 55
°C (with no icing or condensation)
Ambient operating humidity 35% to 85% RH Terminal tightening torque 0.5 N·m Weight Approx. 115 g Approx. 135 g Approx. 120 g Approved standards (pending) EN954-1, EN60204-1, UL508, CSA C22.2 No. 14 EMC (pending) EMI: EN55011 group 1 class A
EMS: EN50082-2
3
G9SB
G9SB
Application Examples
G9SB-2002-A (24 VAC/VDC) or G9SB-3012-A (24 VAC/VDC) with 2-channel Limit Switch Input/Auto-reset
Note External connections and timing charts for G9SB-200-B/301-B models are the same as those for G9SB-2002-A/3012-A models.
G9SB-2002-C (24 VAC/VDC) or G9SB-3012-C (24 VAC/VDC) with 2-channel Emergency Stop Switch Input/Manual-reset
Note External connections and timing charts for G9SB-200-D/301-D models are the same as those f or G9SB-2002-C/3012-D models.
KM1
KM2
M
11
KM1 KM2
12
23
24
S2
S1
KM1
KM2
K1
K2
K1
K1
K2
K2 K1
a
a
+
-
K2
TH
SA
A1 A2
T11 T12 T31 T32
13 23
33㧕㧔41
14 24
34㧕㧔42
T21
T22
㧖㧖
㧖㧖
Open
Control circuit
Feedback loop
Timing Cha rt
Limit switches S1 and S2
K1 and K2 (NC)
K1 and K2 (NO)
KM1 and KM2 (NO)
S1: Safety limit swi tch with positive
opening mechanism (D4D or
D4B) S2: Limit switch KM1 and KM2: Magnetic Contactor (LC1D) M: 3-phase motor
Note Only the G9SB-3012-A
model has terminals 33-34 and 41-42.
KM1 and KM2 (NC)
KM1
KM2
M
S2
KM1 KM2
21
22
S1
11
12
KM1
KM2
K1
K2
K1
K1
K2
K2 K1
a
a
+
-
K2
TH
SA
A1 A2
T11
T12 T31 T32
13 23
33㧕㧔41
14 24
34
㧖㧖
㧖㧖
42
T21
T22
Control circuit
Feedback loop
Timing Chart
Emergency stop switch S1
K1 and K2 (NC)
K1 and K2 (NO)
KM1 and KM2 (NC)
KM1 and KM2 (NO)
S1: Emergency stop switch with
positive opening mechanism
(A165E, A22E) S2: Reset switc h KM1 and KM2: Magnetic Contactor (LC1D) M: 3-phase motor
Note Only the G9SB-3012-C model
has terminals 33-34 and 41-
42.
Reset switch S2
Note Output turns ON with the ris-
ing edge of reset switch S2, but wil l not ope r ate if t her e i s a short breakdown in S2 .
4
G9SB
G9SB
G9SB-200-D (24 VAC/VDC) or G9SB-301-D (24 VAC/VDC) with 2-channel Safet y Area Sensor /Manual-reset
G9SB-3010 (24 VDC) with 2-channel Limit Switch Input/Auto-reset
KM1
KM2
S1
KM1 KM2
㧱㧝
2
KM1
KM2
M
K1
K2
K1
K1
K2
K2 K1
a
a
+
-
K2
TH
SA
A1 A2
T11 T12 T31 T32
13
41
33
1424㧔34㧕㧔42㧕
T21
T22
23
㧖㧖
㧖㧖
Emitter Receiver
F3S-A
Shield
Red
Red/black
Shield
Feedback loop
Purple
Pink
Gray/black
Gray
Blue
Brown
Gray/black
White
Black
Gray
Blue
Brown
Control circuit
Timing Cha rt
F3S-A: Safety Area Sensor S1: Reset switc h KM1 and KM2: Magnetic Contactor (LC1D) M: 3-phase motor E1 and E2: 24-VDC power supply (S82K)
Note Output tu rns ON wit h t he ri si ng edg e of re-
set switch S1, but will not operate if there is a short breakdown in S1.
Note: 1. Connect E1 to
model other than the F3S-A.
2. Only the G9SB­301-D model has terminals 33-34 and 41-
42.
Open
Open
Open
Open
F3S-A: Incident
Interrupted
K1 and K2 (NC)
K1 and K2 (NO) KM1 and KM2 (NC)
KM1 and KM2 (NO)
Reset switch S1
KM1
KM2
M
KM1 KM2
11
12
23
24
S2
S1
KM1
KM2
K1
K2
K1
K1
K2
K2 K1
a
a
+
-
K2
TH
SA
A1 A2
T31 T32
13
23 33
41
14 24 34 42
Open
Control circuit
Feedback loop
Timing Chart
Limit switches S1 and S2 K1 and K2 (NC)
K1 and K2 (NO)
KM1 and KM2 (NC)
KM1 and KM2 (NO)
S1: Safety limit switch with positive
opening mechanism (D4D or D4B)
S2: Li mit s wit c h KM1 and KM2: Magnetic Contactor (LC1D) M: 3-phase motor
5
G9SB
G9SB
Dimensions
G9SB-200@-
@
G9SB-3010
G9SB-301-
@
13 23
T31
T11 T12
A1
T21 T22
A2
14 24
T32
13 23 33
41
T31
A1
42
T32
A2
14 24 34
PWR
K1 K2
PWR
K1 K2
83
18
2.5
68 48
2 5 10
2.6
100 max.
18 max. (Average: 17.5)
112 max.
Terminal Arrangement
G9SB-200
@-@
G9SB-3010
(green) (orange) (orange)
(green) (orange)
(orange)
83
18
2.5
68 48
3 5 15
2.6
13 23 33 T11 T12 T31
T21 T22 T32
14 24 34
41 A1
A2 42
PWR
K1 K2
100 max.
23 max. (Average: 22.5)
112 max.
Terminal Arrangement
G9SB-200
@-@
(green) (orange) (orange)
6
G9SB
G9SB
Installation
Internal connections
Note: 1. For 1-channel input with G9SB-
@@@
-B/D models, short terminals T12 and T22. It is not possible to wire G9SB-
@@@
2-A/C models for 1-channel input.
2. Only G9SB-301
@-@
models have terminals 33-34 and
41-42.
K1
K2
K1
K1
K2
K2 K1
a
a
+
-
K2
TH
SA
A1 A2
T31 T32
13
23 33
41
14 24 34 42
K1
K2
K1
K1
K2
K2 K1
a
a
+
-
K2
TH
SA
A1 A2
T11 T12 T31 T32
13
㧔41㧕
㧔33㧕
1424㧔34㧕㧔42㧕
T21
T22
23
㧖㧖
㧖㧖
K1
K2
K1
K1
K2
K2 K1
a
a
+
-
K2
TH
SA
A1 A2
T11
T12 T31
T32
13
23
㧔33㧕㧔41㧕
14 24
㧔34㧕
㧖㧖
㧖㧖
㧔42㧕
T21
T22
G9SB-2002-A/C (24 VAC/VDC) G9SB-3012-A/C (24 VAC/VDC)
Control circuit
G9SB-200-B/D (24 VAC/V DC) G9SB-301-B/D (24 VAC/V DC)
Control circuit
G9SB-3010 (24 VDC)
Control circuit
7
G9SB
G9SB
Precautions
Wiring
Turn OFF the G9SB before wiring. Do not touch the terminals of the G9SB while the power is turned ON, because the terminals are charged and may cause an electric shock.
Use the following to wire the G9SB. Stranded wire: 0.2 to 2.5 mm
2
Solid wire: 0.2 to 2.5 mm
2
Tighten each screw to a torqu e of 0.5 to 0.6 N·m, or the G9SB may malfunction or generate heat.
Extern al inputs c o nnected to T11 an d T12 or T21 and T22 of the G9SB must be no-voltage contact inp uts.
Applicable Safety Category
All G9SB Relays me et the requi rements of Safety Catego ry 4 of the EN954-1 standards when they are used as shown in the examples provided by OMRON. R elays may not meet the stan­dards in some operating conditions. The G9SB-3010 can be applie d to Safety Cate go ry 3 of th e E N954-1 us ing double break­ing.
The applicable safety category is determined from the whole safety control system. Make sure that the whole safety control syste m me et s E N954-1 requ irements.
Mounting Multiple Units
When mounting multiple Units close to each other, the rated cur­rent will be 3 A. Do not apply a current higher than 3 A.
Conne cting Inputs
If using multiple G9SB models, inputs cannot be made using the same switch. This is also true for other input terminals.
Earth Sh ort
A positi ve thermis tor is built int o the G9SB circuits, so you can detect e arth shor t breakdowns and breakdown shorts be tween channel 1 and channel 2. (Detection of breakdown shorts between channel 1 and channel 2 is supported for G9SB-2002-
@
/
3012-
@
models only.)
Note In order t o det e ct ear t h s hort b rea kdo wns , conne ct t he mi -
nus side of the power supply to ground.
T11 T12 T11 T12
G9SB
G9SB
8
G9SB
G9SB
In the interest of product improvement, specifi cations are subject to change without noti ce.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Cat. No. J130-E1-1
OMRON Corporation
Industrial Automation Company
Industrial Devices and Components Div ision H.Q. Industrial Control Components Department
Shiokoji Horikawa, Shimogyo-ku Kyoto, 600-8530 Japan
Tel: (81)75-344-7119/Fax: (81)75-344-7149
Printed in Japan 0301-2M (0301) (A)