Note: Not all combinations of current and voltage are available.
05:5 A
10:10 A
20:20 A
25:25 A
40:40 A
50:50 A
75:75 A
90:90 A
5. Termina l Ty pe
B:Screw terminals
6. Zero Cross Function
Blank:Equipped with zero cross function
(AC-output models only)
7. Certification
Blank:Models certified by UL and CSA
UTU:Certified by UL, CSA, and TÜV
Solid State Relays G3NA1
Ordering Information
■ List of Models
IsolationZero cross
function
PhototriacYesYes5 A at 24 to 240 VAC
Photocoupler100 to 120 VACG3NA-205B-UTU AC100-120
Phototriac10 A at 24 to 240 VAC
Photocoupler100 to 120 VACG3NA-210B-UTU AC100-120
Phototriac20 A at 24 to 240 VAC
Photocoupler100 to 120 VACG3NA-220B-UTU AC100-120
Phototriac40 A at 24 to 240 VAC
Photocoupler100 to 120 VACG3NA-240B-UTU AC100-120
Phototriac50 A at 24 to 240 VAC
Photocoupler100 to 120 VACG3NA-250B-UTU AC100-120
Phototriac75 A at 24 to 240 VAC
Photocoupler100 to 240 VACG3NA-275B-UTU AC100-240
Phototriac90 A at 24 to 240 VAC
Photocoupler100 to 240 VACG3NA-290B-UTU AC100-240
---10 A at 5 to 200 VDC5 to 24 VDCG3NA-D210B-UTU DC5-24
*All models are certified by UL, CSA, and TÜV.
Note: 1. The applicable output load depends on the ambient temperature. Refer to Load Current vs. Ambient Temperature in Engineering Data.
2. Loss time increases under 75 VAC. (Refer to page 13.) Confirm operation with the actual load.
IndicatorApplicable output load
(See note 1.)
(See note 2.)
(See note 2.)
(See note 2.)
(See note 2.)
(See note.)
(See note 2.)
(See note 2.)
10 A at 200 to 480 VAC5 to 24 VDCG3NA-410B-UTU DC5-24
25 A at 200 to 480 VAC5 to 24 VDCG3NA-425B-UTU DC5-24
50 A at 200 to 480 VAC5 to 24 VDCG3NA-450B-UTU DC5-24
75 A at 200 to 480 VAC
(See note 2.)
90 A at 200 to 480 VAC
(See note 2.)
Rated input voltageModel
5 to 24 VDCG3NA-205B-UTU DC5-24
200 to 240 VACG3NA-205B-UTU AC200-240
5 to 24 VDCG3NA-210B-UTU DC5-24
200 to 240 VACG3NA-210B-UTU AC200-240
5 to 24 VDCG3NA-220B-UTU DC5-24
200 to 240 VACG3NA-220B-UTU AC200-240
5 to 24 VDCG3NA-240B-UTU DC5-24
200 to 240 VACG3NA-240B-UTU AC200-240
5 to 24 VDCG3NA-250B-UTU DC5-24
200 to 240 VACG3NA-250B-UTU AC200-240
5 to 24 VDCG3NA-275B-UTU DC5-24
5 to 24 VDCG3NA-290B-UTU DC5-24
100 to 240 VACG3NA-410B-UTU AC100-240
100 to 240 VACG3NA-425B-UTU AC100-240
100 to 240 VACG3NA-450B-UTU AC100-240
5 to 24 VDCG3NA-475B-UTU DC5-24
100 to 240 VACG3NA-475B-UTU AC100-240
5 to 24 VDCG3NA-490B-UTU DC5-24
100 to 240 VACG3NA-490B-UTU AC100-240
Note: 1. The input impedance is measured at the maximum value of the rated supply voltage (for example, with the model rated at 100 to 120 VAC,
the input impedance is measured at 120 VAC).
2. With constant current input circuit system.
3. Refer to Temperature Characteristics (for Must Operate Voltage and Must Release Voltage) in Engineering Data for further details.
5 to 24 VDC4 to 32 VDC15 mA max. (See note 2.) 4 VDC max.1 VDC min.
100 to 240 VAC75 to 264 VAC72 k
(See note 1.)
Ω±20%75 VAC max. (See note 3.) 20 VAC min. (See note 3.)
Ω±20%150 VAC max. (See note 3.) 40 VAC min. (See note 3.)
Ω±20%75 VAC max.20 VAC min.
Ω±20%75 VAC max.20 VAC min.
Must operate voltageMust release voltage
Voltage level
Output
ModelApplicable load
Rated load voltage Load voltage rangeLoad current (See note 1.)Inrush current
With heat sink
(See note 2.)
G3NA-205B-UTU 24 to 240 VAC19 to 264 VAC0.1 to 5 A (at 40
G3NA-210B-UTU0.1 to 10 A (at 40
G3NA-410B-UTU 200 to 480 VAC180 to 528 VAC0.2 to 10 A (at 40
G3NA-220B-UTU 24 to 240 VAC19 to 264 VAC0.1 to 20 A (at 40
G3NA-425B-UTU 200 to 480 VAC180 to 528 VAC0.2 to 25 A (at 40
G3NA-240B-UTU 24 to 240 VAC19 to 264 VAC0.1 to 40 A (at 40
G3NA-250B-UTU 24 to 240 VAC19 to 264 VAC0.1 to 50 A (at 40
G3NA-450B-UTU 200 to 480 VAC180 to 528 VAC0.2 to 50 A (at 40
G3NA-275B-UTU 24 to 240 VAC19 to 264 VAC1 to 75 A (at 40
G3NA-475B-UTU 200 to 480 VAC180 to 528 VAC1 to 75 A (at 40
G3NA-290B-UTU 24 to 240 VAC19 to 264 VAC1 to 90 A (at 40
G3NA-490B-UTU 200 to 480 VAC180 to 528 VAC1 to 90 A (at 40
G3NA-D210B-UTU 5 to 200 VDC4 to 220 VDC0.1 to 10 A (at 40
Note: 1. The load current varies depending on the ambient temperature. Refer to Load Current vs. Ambient Temperature under Engineering Data.
2. When an OMRON Heat Sink (refer to Options) or a heat sink of the specified size is used.
°C)0.1 to 3 A (at 40°C)60 A (60 Hz, 1 cycle)
°C)0.1 to 4 A (at 40°C)150 A (60 Hz, 1 cycle)
°C)0.2 to 4 A (at 40°C)
°C)0.1 to 4 A (at 40°C)220 A (60 Hz, 1 cycle)
°C)0.2 to 4 A (at 40°C)
°C)0.1 to 6 A (at 40°C)440 A (60 Hz, 1 cycle)
°C)0.1 to 6 A (at 40°C)
°C)0.2 to 6 A (at 40°C)
°C)1 to 7 A (at 40°C)800 A (60 Hz, 1 cycle)
°C)1 to 7 A (at 40°C)800 A (60 Hz, 1 cycle)
°C)1 to 7 A (at 40°C)1,000 A (60 Hz, 1 cycle)
°C)1 to 7 A (at 40°C)1,000 A (60 Hz, 1 cycle)