Slim Relay
G2RV
The World's First Industrial Slim Relay
• Large plug-in terminals for reliable connection.
• LED indicator and mechanical flag to check operation.
• Transparent housing enables checking relay condition.
• Slim outline to save space.
• Push-in terminals and accessories for easy wiring.
Model Number Structure
■ Model Number Legend
G2RV-SL @ @ @ - @
1234 5
1. Auxiliary Type Designation
SL: Slim relay and socket combination
2. Wire Connection
7: Screw terminals
5: Push-in terminals
3. Relay LED
0: Without LED
Note: LED indicator available on socket.
4. Relay Pushbutton
0: Without pushbutton
5. Input Voltage
Ordering Information
■ List of Models
Classification Enclosure rating Input voltage Type of connection Contact form
SPDT
Plug-in terminals General-purpose Unsealed AC/DC Screw terminals G2RV-SL700
Push-in terminals G2RV-SL500
Relay and Socket Combinations
Input voltage Screw terminals Push-in terminals
12 VDC G2RV-SL700-12 VDC G2RV-SL500-12 VDC
24 VDC G2RV-SL700-24 VDC G2RV-SL500-24 VDC
24 VAC/DC G2RV-SL700-24 VAC/DC G2RV-SL500-24 VAC/DC
48 VAC/DC G2RV-SL700-48 VAC/DC G2RV-SL500-48 VAC/DC
110 VAC G2RV-SL700-110 VAC G2RV-SL500-110 VAC
230 VAC G2RV-SL700-230 VAC G2RV-SL500-230 VAC
Slim Relay G2RV 1

Specifications
■ Input Ratings
Rated voltage Rated current
AC DC % of rated voltage AC (VA)
50 Hz 60 Hz
12 VDC --- --- 27.2 mA 80% 10% --- 300 mW ±10%
24 VDC --- --- 13.3 mA --- 300 mW
24 VAC/DC 21.1 mA 22.5 mA 13.0 mA 0.5 VA 300 mW
48 VAC/DC 8.5 mA 9.0 mA 5.2 mA 0.4 VA 250 mW
110 VAC 7.1 mA 7.5 mA --- 0.8 VA ---
230 VAC 7.3 mA 7.9 mA --- 1.7 VA ---
*1) Rated currents are measured at 23 degrees Celsius (ambient)
■ Contact Ratings
Number of poles 1 pole
Load Resistive load
Rated load 6 A at 250 VAC;
Rated carry current 6 A
Max. switching voltage 400 VAC, 125 VDC
Max. switching current 6 A
Max. switching power 1,500 VA
Failure rate (reference value) 10mA at 5VDC (P level)
Note: P level: λ60 = 0.1 x 10-6/operation
*1
(cosφ = 1)
6 A at 30 VDC
180 W
Must operate
voltage
Must release
voltage
Inductive load
(cosφ = 0.4, L/R = 7 ms)
2.5 A at 250 VAC;
2 A at 30 VDC
500 VA
60 W
Power consumption Input voltage
Approx.
DC (mW)
Approx.
% of rated voltage
■ Characteristics
Item 1 pole
Contact resistance 100 mΩ max.
Operate (set) time 20 ms max.
Release time 40 ms max.
Max. operating frequency Mechanical: 18,000 operations/hr
Insulation resistance 1,000 MΩ min. (at 500 VDC)
Dielectric strength 4,000 VAC, 50/60 Hz for 1 min between coil and contacts*;
Vibration resistance Destruction: 10 to 55 to 10 Hz, 0.50 mm single amplitude (1.0 mm double amplitude)
Shock resistance
Endurance Mechanical: 5,000,000 operations min.
Ambient temperature Operating: –40°C to 55°C (with no icing or condensation)
Ambient humidity Operating: 5% to 85%
Weight Approx. 35 g
Overvoltage category III
Pollution degree 2
Contact material AgSnIn
Creepage distance 7.0 mm
Clearance distance 5.5 mm
Note: Values in the above table are the initial values.
Electrical: 1,800 operations/hr (under rated load)
1,000 VAC, 50/60 Hz for 1 min between contacts of same polarity
Malfunction: 10 to 55 to 10 Hz, 0.50 mm single amplitude (1.0 mm double amplitude)
Destruction: 1,000 m/s
Malfunction: 200 m/s2 when energized; 100 m/s2 when not energized
Electrical : 100,000 Typical; NO 70,000 operations min. ; NC 50,000 operations min.
2
2 Slim Relay G2RV

■ Approved Standards
UL 508 (File No. E41643)
Model Contact form Coil ratings Contact ratings Operations
G2RV-SL Series SPDT 12 to 48 VDC
24 to 230 VAC
IEC/VDE (EN 61810)
Contact form Coil ratings Contact ratings Operations
1 pole 12, 24 VDC
24, 48 VAC/DC
110, 230 VAC
250 VAC 6 A (Resistive Load)
30 VDC 6 A (Resistive Load)
400 VAC 2 A (Resistive Load)
250 VAC 6 A (Resistive Load)
30 VDC 6 A (Resistive Load)
400 VAC 2 A (Resistive Load)
50,000
50,000
6,000
6,000
Slim Relay G2RV 3

Engineering Data
■ Endurance
1000
operations)
3
100
30VDC inductive load
(L/R=7ms)
Endurance (x 10
10
02 4
30VDC resistive load
250VAC inductive load
(cos ϕ = 0.4)
250VAC resistive load
6
Switching capacity of DC resistive load
10,0
1,0
DC Breaking Current (A)
0,1
20 60 100 140 180 220
Switching voltage (VDC)
Switching current (A)
Typical Operating and Release Time
Model number Operating time (typical) Release time (typical)
G2RV-SL7@@/5@@ DC12 5 ~ 7 ms 5 ~ 8 ms
G2RV-SL7@@/5@@ DC24 5 ~ 7 ms 6 ~ 9 ms
G2RV-SL7@@/5@@ AC/DC24 5 ~ 7 ms 17 ~ 22 ms
G2RV-SL7@@/5@@ AC/DC48 5 ~ 7 ms 22 ~ 30 ms
G2RV-SL7@@/5@@ AC110 12 ~ 15 ms 22 ~ 30 ms
G2RV-SL7@@/5@@ AC230 12 ~ 15 ms 22 ~ 30 ms
Accessories
■ PLC Interface (for G2RV-SL700 series only)
List of Models
Model number Description Connection
P2RVC-8-O-F PLC Output Interface for 8x
G2RV-SL700-series
PNP - type
Specifications Electrical schematic P2RVC-8-O-F
Input Rated voltage 30 VAC/VDC max.
Current capacity 0.5 A per channel
2.0 A total current, power supply
terminal
Characteristics Ambient
temperature
Overvoltage
category
Pollution degree 2
Operating: 0 to 55°C
Storage: −20 to 85°C
III
Ribbon cable connector
10 Pole, IEC603/1
4 Slim Relay G2RV