Omron F3SP-U4P-TGR Operation Manual

F3SP-U4P-TGR
Safety Control Unit Safety Level 4
USER´S MANUAL
F3SP-U4P-TGR User's manual
Cat No E05-EN-01
F3SP-U4P-TGR
Safety control units,
Type 4,
For use with 1 or 2 pairs of safety light
curtains
USER'S MANUAL
F3SP-U4P-TGR User's manual
The device conforms with the EC requirements in compliance with the following standards:
-Low Voltage Directive 73/23/EEC
-EMC Directive 89/336/EEC
-Machinery Directive 98/37/EC
-IEC 61496-1: 1997
-IEC 61496-2 ed.2 IEC 2001 (CDV draft 8)
-DIN V VDE 0801: 1990 and
-amendement A1: 1994
-EN 61000-4-2,-3,-4,-5,-6
-EN 55022: 1994
-DIN EN 60204-1: 1993
-EN 50178: 1997
MANUFACTURER: TECHNO-GR s.r.l. via Torino, 13/15 10046 Poirino (TO) - ITALY Tel. +39 011 9452041 FAX +39 011 9452090
Version 3.0 date 12/06/03
3
F3SP-U4P-TGR User's manual
INDEX
1 BEFORE USING THE DEVICE. ......................................................5
1.1 GENERAL INSTRUCTIONS .............................................................................5
1.2 ROUTINE MAINTENANCE...............................................................................5
1.3 PRECAUTION OF SAFETY..............................................................................5
2 GENERAL INFORMATION .............................................................6
3 OPERATION....................................................................................8
4 PRECAUTIONS AND INSTALLATION CRITERIA. .......................9
4.1 CALCULATION OF THE MINIMUM INSTALLATION DISTANCE.....................9
5 CONNECTIONS............................................................................ 10
5.1 TERMINAL BLOCK ASSIGNMENT. ...............................................................10
5.2 PINOUT TOP VIEW ........................................................................................11
5.3 WIRING EXAMPLE.........................................................................................12
6 ALIGNMENT PROCEDURE......................................................... 16
7 OPERATING PROCEDURES. ..................................................... 17
7.1 DIP-SWITCHES CONFIGURATION...............................................................17
7.2 MUTING FUNCTION. .....................................................................................18
7.2.1 DESCRIPTION................................................................................................ 18
7.2.2 INSTALLATION CRITERIA ........................................................................... 18
7.3 OVERRIDE. ....................................................................................................22
7.4 STARTING THE OVERRIDE FUNCTION.......................................................22
7.5 MUTING RESTRICTIONS (MUTING FUNCTION)................................................23
8 LED DIAGNOSTIC ....................................................................... 24
9 FINAL CHECKS. .......................................................................... 25
10 ROUTINE MAINTENANCE. ......................................................... 25
11 GENERAL INFORMATION AND USEFUL DATA. ..................... 26
11.1 OMRON LIGHT CURTAINS TO BE USED WITH THE F3SP-U4P-TGR .......26
12 TECHNICAL DATA. ..................................................................... 27
13 OVERALL DIMENSIONS. ............................................................ 28
4
F3SP-U4P-TGR User's manual

1 BEFORE USING THE DEVICE.

1.1 GENERAL INSTRUCTIONS
Read this manual and the safety light curtain(s) (SLC) manual carefully and completely. Make sure the user information provided is understood before attempting to operate the light curtain. Keep the manual in a secure and convenient location and confirm information if necessary. To guarantee correct installation, carefully follow the instructions of this manual.
Do not touch non-insulated cables, unless they have been disconnected from the power supply.
Make sure that the cables connected to the control unit are not taut and that they do not hinder the movement of persons or objects.
The control unit does not contain parts subject to maintenance. Do not open the control unit for any reason, and in case of failure, send it to our laboratories, indicating the fault and the operation period.
A qualified person, as determined by local regulations, must confirm that installation, inspection, and maintenance have been implemented correctly.
Failure to do so may result in lethal or serious injury.
1.2 ROUTINE MAINTENANCE.
Please refer to sec. 10 and the safety light curtain instruction manual. OMRON Europe and TECHNO-GR refuses to accept any responsibility for damage to persons or objects due to the incorrect use / installation of the device.

1.3 PRECAUTION OF SAFETY

The following symbols are used for highlighting items in order to ensure safe and proper use of the F3SP-U4P-TGR. Highlighted items are critical for safe operation and must be heeded at all times.
NOTICE
WARNING
5
F3SP-U4P-TGR User's manual

2 GENERAL INFORMATION

The safety control unit F3SP-U4P-TGR has been designed to be used with the dedicated light curtains. (Please refer to sec.11) It cannot be connected to other light curtains.
The system conforms with the requirements for safety devices of type 4 in compliance with the international standards stated e.g. IEC 61496-1. However, the safety system category depends on the light curtain’s type as follows: Type 4 light curtain : Safety system category 4 (EN954-1) Type 2 light curtain : Safety system category 2 (EN954-1)
This safety device is made up of a control unit protected by a plastic housing so that it can be installed on a DIN/OMEGA rail; it has 32 removable screw terminals to which it is possible to connect from 1 to 2 pairs of light curtains.
This control unit has the double ‘muting’ function. This function makes it possible to obtain a “temporarily automatic suspension” of one or both safety light curtains in order to allow, for instance, the objects passage without stopping the machine. The ‘override’ function enables system, to keep the output relays closed even with intruded rays to enable material transport after a system shutdown. Both muting and override functions represent a system that require additional precautions to limit the reduction of the safety level. This precautions have to be considered carefully. The muting and override function is available by simply connecting the F39-A11 muting lamp (or similar yellow bulb type lamp for 24VDC / 3W to 5W) supplied separately.
The presence of a limb or an object interrupting a beam causes the opening of the safety outputs and the consequent stopping of the connected machine. It is necessary for the safety sensors to be connected in the right position in such a way that there isn’t any possibility to climb over or defeat the system. Do not install the control unit in the corrosive, flammable or explosive gas. Do not use the cellular phone or transceivers near the control unit.
6
F3SP-U4P-TGR User's manual
The unit has been designed in accordance to the following standards:
IEC 61496-1: 1997. Safety of machinery: electro-sensitive
protective devices
- General requirements and test.
FDIS IEC 61496-2: 1997. Safety of machinery: electro-sensitive
protective devices
- Particular requirements for system using active opto-electronic devices.
7
F3SP-U4P-TGR User's manual
3 OPERATION.
The electronic control system of the device is made up of a microprocessor. By means of the suitable hardware, it continuously control and check the connected photocells. No interference among the safety sensors is possible as they are controlled sequentially; it will be thus possible to install one or two adjacent safety sensors. When one or more beams are interrupted, the electronic system opens the outputs. The SLC have been triggered are displayed by LEDs on the housing. The control-unit can work in two different modes (please refer to par. 7 page
17) which he can carry out the following operations:
The two external buttons that have to be connected are for:
TEST : This is used to check if the whole system works effectively. By pressing the TEST button (opening of the contact), this simulates the interruption of one or more safety sensors. This operation makes the machine stop, so the system checks can be made according to the established time and modes. If pressed after a failure detection of the unit (see the table error code), reset of the system is required.
RESET button: It is used to start the system, also for manual reset condition after relay triggering or after an error which can be reset (see table related to the error codes).
Two different operating modes are available:
1. Automatic reset: The system will start automatically after the beam intrusion have been removed.
2. Manual reset: The system will remain in safe off condition until the RESET button have been pressed. This manual reset allows to start the system only on a wanted action of the user.
During the unit working, no operation set by the user interface involves functions which can influence the system safety.
8
F3SP-U4P-TGR User's manual

4 PRECAUTIONS AND INSTALLATION CRITERIA.

The safety products used must be suitable for the required application, other influences must also be taken into account such as room temperature, electromagnetic interference, intense light sources etc. Please refer to the manual for specification or contact the manufacturer for details.

4.1 CALCULATION OF THE MINIMUM INSTALLATION DISTANCE.

The safety distance ‘S’ must be sufficient to guarantee that the hazardous area cannot be reached by the operator up to the moment in which the hazardous movement stops. Please refer to EN999 or corresponding C­standards and the safety light curtain’s instruction manual;
The EN 999 uses this general formula
S = ( K x T ) + C
S = safety distance. T = T1 + T2 +T3 whereas T1 = machine response time in seconds. T2 = light curtains response time in seconds. T3 = controller response time in seconds. K = speed of the body approaching the hazardous area. C = additional distance calculated or defined based on the optical resolution of the
light curtain.
9