Omron F3SJ-E0465P25, F3SJ-E0625P25, F3SJ-E0385P25, F3SJ-E0545P25, F3SJ-E0225P25 User Manual

...
Page 1
Safety Light Curtain
F3SJ-E P25 F3SJ-B
P25 Series
User's Manual
Cat. No. SCHG-732D
Page 2
Original instructions
Thank you for purchasing the F3SJ-E/B Series Safety Light Curtain (hereinafter referred to as the "F3SJ-E/B"). This is the instruction manual describing the use of F3SJ-E/B. Always heed the following points when using the F3SJ-E/B:
Be sure to have F3SJ-E/B be handled by a "Responsible Person" who is well aware of and familiar with the machine to be installed. The term "Responsible Person" used in this User's Manual means the person qualified, authorized and responsible to secure "safety" in each process of the design, installation, operation, maintenance services and disposition of the machine. It is assumed that F3SJ-E/B will be used properly according to the installation environment, performance and function of the machine. Responsible Person should conduct risk assessment on the machine and determine the suitability of this product before installation. Read this Manual thoroughly to understand and make good use of the descriptions before installing and operating the product. Keep this Manual at the place where the operator can refer to whenever necessary.
Page 3
Legislation and Standards
1. An F3SJ-E/B does not receive type approval provided by Article 44-2 of the Industrial Safety and Health Act of Japan. Therefore, the F3SJ-E/B cannot be used as a "safety system for pressing or shearing machines" prescribed in Article 42 of that law.
2. The F3SJ-E/B is electro-sensitive protective equipment (ESPE) in accordance with European Union (EU) Machinery Directive Index Annex V, Item 2.
3. EC Declaration of Conformity OMRON declares that the F3SJ-E/B is in conformity with the requirements of the following EC Directives:
Machinery Directive 2006/42/EC EMC Directive 2004/108/EC
4. The F3SJ-E/B is in conformity with the following standards:
(1)European standards
EN 61496-1 (Type 4 ESPE), CLC/TS 61496-2 (Type 4 AOPD), EN 61508-1 through -3 (SIL3), EN 61000-6-4, EN ISO 13849-1:2008 (Category 4, PL e)
(2)International standards
IEC 61496-1 (Type 4 ESPE), IEC 61496-2 (Type 4 AOPD), IEC 61508-1 through -3 (SIL3), ISO 13849-1: 2006 (Category 4, PL e)
(3)JIS standards
JIS B 9704-1 (Type 4 ESPE), JIS B 9704-2 (Type 4 AOPD)
(4)North American Standards:
UL 61496-1 (Type 4 ESPE), UL 61496-2 (Type 4 AOPD), UL 508, UL 1998, CAN/CSA C22.2 No.14, CAN/CSA C22.2 No.0.8
Introduction
5. The F3SJ-E/B received the approvals of EC Type-Examination in accordance with the EU Machinery
Directive, Type 4 ESPE and Type 4 AOPD from the EU accredited body,
6. The F3SJ-E/B received the certificates of UL listing for US and Canadian safety standards, Type 4 ESPE and Type 4 AOPD from the Third Party Assessment Body UL.
7. The F3SJ-E/B is designed according to the standards listed below. To make sure that the final system complies with the following standards and regulations, you are asked to design and use it in accordance with all other related standards, laws, and regulations. If you have any questions, consult with specialized organizations such as the body responsible for prescribing and/or enforcing machinery safety regulations in the location where the equipment is to be used.
•European Standards: EN415-4, EN692, EN693
•U.S. Occupational Safety and Health Standards: OSHA 29 CFR 1910.212
•U.S. Occupational Safety and Health Standards: OSHA 29 CFR 1910.217
•American National Standards: ANSI B11.1 to B11.19
•American National Standards: ANSI/RIA 15.06
•Canadian Standards Association CSA Z142, Z432, Z434
•SEMI Standards SEMI S2
•Japan Ministry of Health, Labour and Welfare "Guidelines for Comprehensive Safety Standards of Machinery", Standard Bureau's Notification No. 0731001 dated July 31, 2007.
* For date of effect for these standards, see Related Standards.
Related Standards p.130
TÜV SÜD
Product Service GmbH.
F3SJ-E/B
User’s Manual
E
i
Page 4
Introduction
Terms and Conditions Agreement
Read and understand this catalog.
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments.
Warranties.
(a) Exclusive Warranty. Omron's exclusive warranty is that the Products will be free from defects in materials and
workmanship for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT NON-
INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET
THE REQUIREMENTS OF THEIR INTENDED USE. Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omron's sole obligation hereunder shall be, at Omron's election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty, repair, indemnity or any other claims or expenses regarding the Products unless Omron's analysis confirms that the Products were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice, recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above warranty. See http://www.omron.com/global/
or contact your Omron representative for published information.
Limitation on Liability; Etc.
OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY. Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.
Suitability of Use.
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the combination of the Product in the Buyer's application or use of the Product. At Buyer's request, Omron will provide applicable third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine, system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product with respect to Buyer's application, product or system. Buyer shall take application responsibility in all cases. NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
Programmable Products.
Omron Companies shall not be responsible for the user's programming of a programmable Product, or any consequence thereof.
F3SJ-E/B
ii
User’s Manual
Page 5
Performance Data.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of Omron's test conditions, and the user must correlate it to actual application requirements. Actual performance is subject to the Omron's Warranty and Limitations of Liability.
Change in Specifications.
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice to change part numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers may be assigned to fix or establish key specifications for your application. Please consult with your Omron's representative at any time to confirm actual specifications of purchased Product.
Errors and Omissions.
Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical or proofreading errors or omissions.
Introduction
F3SJ-E/B
User’s Manual
E
iii
Page 6
Introduction
Precautions on Safety
Regarding the alert symbols and meanings used for the safe uses
In order to use the F3SJ-E/B safely, the precautions listed in this manual indicated by alert symbols and descriptions must be followed. Failure to follow all precautions and alerts may result in an unsafe use or operation. The following indications and symbols are used for the descriptions.
Indicates a potentially hazardous situation which, if not avoided, will result in minor or moderate injury, or may result in serious injury or death. Additionally there may be significant property damage.
Meanings of Alert Symbols
Indicates prohibited actions.
Indicates mandatory actions.
Indicates the risk of electric shock.
Alert Statements in this Manual
For users
The F3SJ-E/B must be installed, configured, and incorporated into a machine control system by a sufficiently trained and qualified person. An unqualified person may not be able to perform these operations properly, which may cause a person to go undetected, resulting in serious injury.
Read this manual thoroughly and understand the procedures of installation, operation check and maintenance.
For machines
iv
Do not use this sensor for machines that cannot be stopped by electrical control. For example, do not use it for a pressing machine that uses full-rotation clutch. Otherwise, the machine may not stop before a person reaches the hazardous part, resulting in serious injury.
F3SJ-E/B
User’s Manual
Page 7
For installation
Reflector
Position with retro-reflection
Position with detection zone bent at 90°
Reflector
Make sure to test the operation of the F3SJ-E/B after installation to verify that the F3SJ-E/B operates as intended. Make sure to stop the machine until the test is complete. Unintended function settings may cause a person to go undetected, resulting in serious injury.
Make sure to install the F3SJ-E/B at the safe distance from the hazardous part of the equipment. Otherwise, the machine may not stop before a person reaches the hazardous part, resulting in serious injury.
Install a protective structure so that the hazardous part of a machine can only be reached by a person that passes through the sensor's detection zone. Install the sensors so that part of the person is always present in the detection zone when working in a machine's hazardous zones, eliminating areas where the sensors do not reach. If a person is able step into the hazardous zone of a machine and remain behind the F3SJ-E/B's detection zone, configure the system with an interlock function that prevents the machine from being restarted. Failure to do so may result in serious injury.
Install the interlock reset switch in a location that provides a clear view of the entire hazardous zone and where it cannot be activated from within the hazardous zone.
Introduction
The F3SJ-E/B cannot protect a person from a projectile exiting the hazardous zone. Install protective cover(s) or fence(s).
Install the F3SJ-E/B so that it is not affected by a reflective surface. Failure to do so may hinder detection, resulting in serious injury. Details on installation distance from the reflective surface, see "Distance from Reflective Surfaces" on page 41.
When using more than one set of F3SJ-E/Bs, install them so that mutual interference does not occur, such as by configuring series connections or using physical barriers between adjacent sets.
Make sure that the F3SJ-E/B is securely mounted and its cables and connectors are properly secured.
Do not use the sensor system with mirrors in a retro-reflective configuration as shown below. Doing so may hinder detection. It is possible to use mirrors to "bend" the detection zone to a 90­degree angle.
F3SJ-E/B
User’s Manual
E
v
Page 8
Introduction
Perform an inspection for all F3SJ-E/B as described in "Chapter 5 Checklists".
Install muting sensors so that they can distinguish between the object that is being allowed to be passed through the detection zone and a person. If the muting function is activated by the detection of a person, it may result in serious injury.
Use independent two input devices for muting inputs.
The muting and override functions disable the safety functions of the device. You must ensure safety using other method when these functions are operating.
Install the switch that uses hold-to-run device such as a spring-return key switch and is installed in a location that provides a clear view of the entire hazardous zone and where it cannot be activated from within the hazardous zone. Make sure that nobody is in the hazardous zone before activating the override function.
For wiring
Connect the load between the output and 0 V line (PNP output). Connecting the load between the output and +24 V line will result in a dangerous condition because operation is reversed to "ON when blocked".
Do not short-circuit the output line to the +24 V line. Otherwise, the output is always ON. Also, the 0 V of the power supply must be grounded so that output does not turn ON due to grounding of the output line.
Configure the system by using the optimal number of safety outputs that satisfy the requirements of the necessary safety category.
Do not connect each line of F3SJ-E/B to a DC power supply of more than 24 VDC+20%. Also, do not connect to an AC power supply. Failure to do so may result in electric shock or breakdown of the device.
Make sure to perform wiring while the power supply is OFF.
Do not use the auxiliary output for safety applications. Human body may not be detected when F3SJ-B fails, resulting in serious injury.
vi
F3SJ-E/B
User’s Manual
Page 9
For the F3SJ-E/B to comply with IEC 61496-1 and UL 508, the DC power supply unit must satisfy all of the following conditions:
• Must be within the rated power voltage (24 VDC
• Must have tolerance against the total rated current of devices if it is connected to multiple
devices
• Must comply with EMC directives (industrial environment)
• Double or reinforced insulation must be applied between the primary and secondary circuits
• Automatic recovery of overcurrent protection characteristics
• Output holding time must be 20 ms or longer
• Must satisfy output characteristic requirements for class 2 circuit or limited voltage current
circuit defined by UL 508. Refer to p.83 for details.
• Must comply with laws and regulations, regarding EMC and electrical equipment safety, of the
country or region where the F3SJ-E/B is used (Ex: In EU, the power supply must comply with the EMC Directive and the Low Voltage Directive.)
Double or reinforced insulation from hazardous voltage must be applied to all input and output lines. Failure to do so may result in electric shock.
Extension of the cable must be within a specified length. If it isn't, safety function may not work properly, resulting in danger.
± 20%)
Introduction
Other
To use the F3SJ-E/B in PSDI mode (Reinitiation of cyclic operation by the protective equipment), you must configure an appropriate circuit between the F3SJ-E/B and the machine. For details about PSDI, refer to OSHA1910.217, IEC 61496-1, and other relevant standards and regulations.
Do not try to disassemble, repair, or modify this product. Doing so may cause the safety functions to stop working properly.
Do not use the F3SJ-E/B in environments where flammable or explosive gases are present. Doing so may result in explosion.
Perform daily and 6-month inspections for the F3SJ-E/B. Otherwise, the system may fail to work properly, resulting in serious injury.
Do not use radio equipment such as cellular phones, walkie-talkies, or transceivers near the F3SJ-E/B.
F3SJ-E/B
User’s Manual
E
vii
Page 10
Introduction
Precautions for Safe Use
Make sure to observe the following precautions that are necessary for ensuring safe use of the product. Do not install the F3SJ-E/B in the following types of environments:
- Areas exposed to intense interference light, such as direct sunlight
- Areas with high humidity where condensation is likely to occur
- Areas where oil mist or corrosive gases are present
- Areas exposed to vibration or shock levels higher than in the specification provisions
- Areas where the product may come into contact with water
- Areas with pollution degree 3 or harsher
- Areas where the product may get wet with oil that can solve adhesive
• Loads must satisfy both of the following conditions:
- Not short-circuited
- Not used with a current that is higher than the rating
• Do not drop the product.
• Install the emitter and receiver to the same vertical direction.
• Dispose of the product in accordance with the relevant rules and regulations of the country or area where the
product is used.
• Make sure to tighten the connectors of the cables securely.
• When replacing the cable connectors with other types of connectors, use connectors that provide a
protection grade of IP54 or higher.
• Be sure to route the input/output lines for the F3SJ-E/B separate from high-potential power lines or through
an exclusive conduit.
• To extend a cable length with a cable other than the dedicated cable, use a cable with the same or superior
specifictions.
• The cable extension length must be within the specified length (30 m max).
• In environments where foreign material such as spatter adheres to the F3SJ-E/B, attach a cover to protect
the F3SJ-E/B from the spatter.
• PC Setting Support Software "SD Manager" (F39-GWUM) and Setting Console (F39-MC21) are available
only for F3SJ-A series. Do not use these setting tools for F3SJ-E/B series.
viii
Precautions for Correct Use
Observe the precautions described below to prevent operation failure, malfunctions, or undesirable effects on product performance.
Storage conditions and installation environment
•Do not install, use, or store the F3SJ-E/B for a long time at a temperature or humidity out of the specified range.
•This is a class A product. In residential areas it may cause radio interference, in which case the Responsible Person may be required to take adequate measures to reduce interference.
•F3SJ-E/B can be used at altitudes up to 2,000 meters.
Wiring and installation
•Make sure to perform wiring while the power supply is OFF. Otherwise, the F3SJ-E/B may fail to
operate due to the diagnosis function.
•Do not short-circuit output lines to +24 V line. Otherwise a fault of F3SJ-E/B may occur.
F3SJ-E/B
User’s Manual
Page 11
When extending the communication line with a cable (twisted-pair wire) other than the dedicated cable
(F39-JD
•Properly perform the wiring after confirming the signal names of all the terminals.
•Be sure that there is nothing in the detection zone and the stable-state indicator is turned ON after power is turned ON.
•Do not operate the control system until 2 seconds or more after turning ON the power of the F3SJ-E/B.
•Be sure to route the F3SJ-E/B cable separate from high-potential power lines or through an exclusive
conduit.
•When using a commercially available switching regulator power supply, make sure to ground the FG
terminal (frame ground terminal).
•If the protective height is more than 1,105 mm, use intermediate brackets of specified quantities and
locations according to the dimensions. If the brackets described above are not used, ratings and performance cannot be met.
•Do not install the F3SJ-E/B close to a device that generates high-frequency noise. Otherwise, take sufficient blocking measures.

), use a cable with the same or superior specifications. Connect the shield to the 0V line.
Cable specification (extension cable) p.87
Cleaning
Do not use thinner, benzene, or acetone for cleaning, because they affect the product's resin parts and paint on the extrusion.
Introduction
Object detection
The F3SJ-E/B cannot detect transparent and/or translucent objects.
F3SJ-E/B
User’s Manual
E
ix
Page 12
Introduction
F3SJ-E/B
x
User’s Manual
Page 13

Contents

Legislation and Standards i Terms and Conditions Agreement ii Precautions on Safety iv Precautions for Safe Use viii Precautions for Correct Use viii
Chapter1 Overview and Specifications 1
Basic Configuration and Names 2 Model Overview 3
Easy Type 3 Basic Type 3
Internal (LED) Indicator Display Pattern 4
Easy Type 4 Basic Type 4
Introduction
Ratings/Specifications 6
Model/Current Consumption List 8
Chapter2 System Configuration and Functions 9
How to Select a Model/System 10
Selection Flowchart 10 Function List 10
Wiring Diagrams 11
Easy Type 11 Basic Type (Basic System) 12 Basic Type (Muting System) 15
Description of Functions 16
External Test Function 16 Self-test Function 17 Lockout Reset Function 18 Interlock Function 19 Auxiliary Output Function 20 External Device Monitoring Function 21
Muting Function 22 Override Function 34
Chapter3 Wiring/Installation 37
Installation Conditions 38
Detection Zone and Approach 38
F3SJ-E/B
User’s Manual
E
xi
Page 14
Introduction
Safety Distance 39 Distance from Reflective Surfaces 41 Mutual Interference Prevention 41
Series Connection 43
Connection Procedure 45
Dimensions 46
Difference between Easy Type and Basic Type 46 When Using Top/Bottom and Intermediate Brackets 47 When Using Intermediate Brackets Only (Free-Location Mounting) 51 When Using One-touch Brackets 55 When Using Replacement Brackets 60 When Using Contact Mount Brackets 63 When Using Spatter Protection Cover 66
Mounting 67
Mounting Method 67 Number of Brackets Required 67 Mounting Procedure 68
Wiring 82
Wiring Precautions 82 Power Supply Unit 83 Wiring Method (Easy Type) 84 Wiring Method (Basic Type) 84
Chapter4 Input/Output Circuit and Applications 89
Input/Output Circuit 90
Easy Type 90 Basic Type 91
Wiring Examples 92
Using F3SJ-E Only 92 Using F3SJ-B Only 93 Connecting a F3SJ-E to Various Controllers 96 Connecting a F3SJ-B to Two Muting Sensors 100 Connecting a F3SJ-B to Four Muting Sensors 101 Connecting a F3SJ-B to Various Controllers 102
xii
Using a reduced wiring connector for F3SJ-B 107
Chapter5 Checklists 109
Pre-Operation Checklists 110
Checklists 110
Maintenance Checklists 112
F3SJ-E/B
User’s Manual
Page 15
Checklists 112
Chapter6 Appendix 115
Troubleshooting 116
Lockout State 116 Warning View 116 Troubleshooting Methods 118
Muting Error Indication 121 Optional Accessories (Sold Separately) 122 Glossary 128 Related Standards 130
International Standards 130
European Standards 130
US Occupational Safety and Health Standards 130
US Standards 130
Canadian Standards 131
Introduction
SEMI Standards 131
JIS Standards 131
F3SJ-E/B
User’s Manual
E
xiii
Page 16
Introduction
xiv
F3SJ-E/B
User’s Manual
Page 17

Chapter1 Overview and Specifications

Basic Configuration and Names 2
Model Overview 3
Easy Type 3 Basic Type 3
Internal (LED) Indicator Display Pattern 4
Ratings/Specifications 6
Model/Current Consumption List 8
Chapter1 Overview and Specifications
F3SJ-E/B
User’s Manual
E
1
Page 18
Overview and Specifications
F3SJ-E
□□□□
P25
-
1 432
F3SJ-B□□□□
P25
-
1432

Basic Configuration and Names

Chapter1 Basic Configuration and Names
This section describes the system configuration and part names of the F3SJ-E/B. (The picture below is a F3SJ-B)
Beam center-line mark
Beam
Receiver
Indicator
Emitter
Connection cable (Black)
Connection cable (Gray)
Extension cable
Component Model Description
Emitter, receiver F3SJ-EP25- Select a type name based on the required protective height.
The model name can be understood as follows:
1: Protective height (mm) 2: Output type (P for PNP output type *1)
3. Detection capability (mm) 4: L for emitter, D for receiver, blank for a set of emitter and receiver. *1. A hyphen "-" is added instead of "P" for emitter.
Emitter, receiver F3SJ-BP25- Select a type name based on the required protective height.
The model name can be understood as follows:
1: Protective height (mm) 2: Output type (P for PNP output type *1)
3. Detection capability (mm) 4: L for emitter, D for receiver, blank for a set of emitter and receiver. *1. A hyphen "-" is added instead of "P" for emitter.
F3SJ-E/B
2
User’s Manual
To distinguish between the emitter and receiver, find the labels attached to the front of the F3SJ-E/B. The label on the emitter reads "EMITTER" and the label on the receiver reads "RECEIVER".
Page 19

Model Overview

Overview and Specifications
There are two sensor types: F3SJ-E and F3SJ-B as follows:

Easy Type

The model name is represented as F3SJ-EP25. The Easy Type can be easily used as it limits functions available as external test and lockout reset with less wiring (emitter: 5-wire, receiver: 6-wire)

Basic Type

The model name is represented as F3SJ-BP25. The Basic Type offers more functions than the Easy Type, allowing you to select a system (basic or muting) according to your application. Functions available for each system are as follows:
• Basic system
The default is set as basic system. Functions: external test, lockout reset, interlock, external device monitoring, auxiliary output and
series connection.
• Muting system
Muting system can be used by replacing the cap with Muting Key Cap (F39-CN10). Functions: external test, lockout reset, auxiliary output, muting, override and series connection.
Chapter1 Model Overview
For details on cap replacement, refer to "Upgrading F3SJ-B for muting system" on page 23.
F3SJ-E/B
User’s Manual
E
3
Page 20
Chapter1 Internal (LED) Indicator Display Pattern
Emitter
Receiver
6. Test indicator (Green)
5. Power indicator (Green)
4. Lockout indicator (Red)
3. ON/OFF-state indicator (Green/Red)
2. Stable-state indicator (Green)
1. Top-beam-state indicator (Blue)
10. Bottom-beam-state indicator (Blue)
4. Lockout indicator (Red)
3. ON/OFF-state indicator (Green/Red)
2. Stable-state indicator (Green)
1. Top-beam-state indicator (Blue)
10. Bottom-beam-state indicator (Blue)
7. Internal error indicator (Red)
6. Configuration indicator (Green)
5. Communication indicator (Green)
Emitter
Receiver
10. Bottom-beam-state indicator (Blue)
9. Muting input 2 indicator (Green)
8. Muting input 1 indicator (Green)
7. Muting error indicator (Green)
6. Test indicator (Green)
5. Power indicator (Green)
4. Lockout indicator (Red)
3. ON/OFF-state indicator (Green/Red)
2. Stable-state indicator (Green)
1. Top-beam-state indicator (Blue)
4. Lockout indicator (Red)
3. ON/OFF-state indicator (Green/Red)
2. Stable-state indicator (Green)
1. Top-beam-state indicator (Blue)
10. Bottom-beam-state indicator (Blue)
9. External device monitoring indicator (Green)
8. Interlock indicator (Yellow)
7. Internal error indicator (Red)
6. Configuration indicator (Green)
5. Communication indicator (Green)

Easy Type

Basic Type

Overview and Specifications

Internal (LED) Indicator Display Pattern

F3SJ-E/B
4
User’s Manual
Page 21
Overview and Specifications
Emitter
No. Internal indicator
1 Top-beam-state indicator TOP *1
2 Stable-state indicator STB 
3 ON/OFF-state indicator
4 Lockout indicator LOCKOUT 
5 Power indicator POWER 
6 Test indicator TEST 
7 Muting error indicator
8 Muting input 1 indicator MUTE1
9 Muting input 2 indicator MUTE2
10 Bottom-beam-state indicator BTM *1
*1. The Easy Type does not have muting/override and series connection functions.
ON OFF
MUTING ERROR
Easy Type
Receiver
No. Internal indicator
1 Top-beam-state indicator TOP *1
2 Stable-state indicator STB 
3 ON/OFF-state indicator
4 Lockout indicator LOCKOUT 
5 Communication indicator COM 
6 Configuration indicator CFG 
7 Internal error indicator INTERNAL 
8 Interlock indicator
External device monitoring
9
indicator
10 Bottom-beam-state indicator BTM *1
*1. The Easy Type does not have muting/override and series connection functions. *2.
It turns ON when there is an external device monitoring input regardless of the availability of the external device monitoring.
ON OFF
INT
-LK
EDM
Easy Type
Basic
Type
Turns ON when the top beam is receiving light.
Turns ON when incidence level is 170% or more of the output ON threshold.
Green: Turns ON when safety


Red: Turns ON when safety
Turns ON when the F3SJ-E/B enters a lockout on the receiver.
Turns ON while the power of the emitter is ON.
Turns ON when muting input 1 is ON under the muting system. Turns ON when muting input 2 is ON under the muting system. Turns ON when the bottom beam is receiving light.
Basic
Type
Turns ON when the top beam is receiving light.
Turns ON when incidence level is 170% or more of the output ON threshold. Green: Turns ON when safety
Red: Turns ON when safety
Turns ON when the F3SJ-E/B enters a lockout on the emitter.
Turns ON when communication between emitter and receiver is established.
Turns ON when the F3SJ-E/B is in interlock state. Turns ON when an input is given to external device monitoring input. *2 Turns ON when the bottom beam is receiving light.
ON Blinking
output is ON.
output is OFF.
ON Blinking
output is ON.
output is OFF.
Blinks during muting/override, or when cap error or connection error occurs.*1
Blinks when the safety output is turned OFF due to disturbance light or vibration.
Red: Blinks when the F3SJ-E/B
enters a lockout due to a safety output error.
Blinks when the F3SJ-E/B enters a lockout on the emitter. Blinks when the F3SJ-E/B enters a lockout due to power voltage/ noise. Blinks when external test is being performed. Blinks during a muting error.*1
For details, refer to Muting Error Indication in Chapter 6: Troubleshooting on page 121 .
Blinks during muting/override.*1
Blinks during muting/override, or when cap error or connection error occurs.*1
Blinks when the safety output is turned OFF due to disturbance light or vibration.
Red: Blinks when the F3SJ-E/B
enters a lockout due to a safety output error.
Blinks when the F3SJ-E/B enters a lockout on the receiver. Blinks when the F3SJ-E/B enters
lockout due to a communication error between receiver and emitter.
Blinks when the F3SJ-E/B enters lockout due to a model type error between receiver and emitter.
Blinks when the F3SJ-E/B enters a lockout due to an internal error. Blinks when the F3SJ-E/B enters a lockout due to a wiring error. Blinks when the F3SJ-E/B enters a lockout due to an external device monitoring error.
Blinks during muting/override.*1
Chapter1 Internal (LED) Indicator Display Pattern
E
F3SJ-E/B
User’s Manual
5
Page 22
Overview and Specifications

Ratings/Specifications

Chapter1 Ratings/Specifications
The model names of the F3SJ-E/B contain the 4 digits indicating the protective height (mm).
Model
Item
Detection capability
Beam gap 20 mm Number of beams 8 to 54 8 to 102 Protective height 185 to 1,105 mm 185 to 2,065 mm Lens diameter 5 mm Operating range 0.2 to 7 m
Response time
Startup waiting time 2 s max. Power supply voltage (Vs) SELV/PELV 24 VDC±20% (ripple p-p 10% max.)
Current consumption
Light source Infrared LED (870 nm wavelength)
Effective aperture angle (EAA)
Safety output (OSSD)
Auxiliary output
Output operation mode Safety output: ON when receiving light
Input voltage
Overvoltage category II (IEC 60664-1)
Indicator
Mutual interference prevention function Mutual interference prevention algorithm prevents interference in up to three sets.
Series connection function
Test function
Safety-related functions
Opaque objects 25 mm diameter
ON to OFF: 15 ms max. (Response time when used alone or in 2 or 3 connected) OFF to ON: 70 ms max. (Response time when used alone or in 2 or 3 connected)
Based on IEC 61496-2. Within ±2.5° for both emitter and receiver at an operating range of 3 meters or more.
Two PNP transistor outputs, Load current: 200 mA max., Residual voltage: 2 V max. (except for voltage drop due to cable extension), Leakage current: 1 mA max., Load inductance: 2.2 H max. *1 Maximum capacitive load: 1 µF *2
Test input and reset input are both:
ON voltage: Vs-3V to Vs *3 (sink current 3mA max.) OFF voltage: 0V to 1/2Vs, or open *3
External device monitoring input is:
ON voltage: Vs-3V to Vs *3 (sink current 5mA max.) OFF voltage: 0V to 1/2Vs, or open *3
Self-test (at power-on, and during operation) External test (light emission stop function by test input)
Easy Type Basic Type
F3SJ-EP25 F3SJ-BP25
Refer to "Model/Current Consumption List" on page 8.
One PNP transistor output Load current: 100 mA max. Residual voltage: 2 V max.(except for voltage drop due to cable extension) Leakage current: 1 mA max.
Safety output: On when receiving light Auxiliary output:
- Basic system Reverse output of safety output
- Muting system ON during muting/override
Test input, interlock selection input, reset input, and muting input are all:
ON voltage: Vs-3V to Vs *3 (sink current 3mA max.) OFF voltage: 0V to 1/2Vs, or open *3
External device monitoring input is:
ON voltage: Vs-3V to Vs *3 (sink current 5mA max.) OFF voltage: 0V to 1/2Vs, or open *3
Refer to "Internal (LED) Indicator Display Pattern" on page 4.
Number of connections: Up to three sets Total number of beams: Up to 192 Maximum connection cable length: 7 m
Interlock (basic system) External device monitoring (basic system) Muting (muting system) Override (muting system)
*1. The load inductance is the maximum value when the safety output frequently repeats ON and OFF. When you use the safety
output at 4 Hz or less, the usable load inductance becomes larger. *2. These values must be taken into consideration when connecting elements including a capacitive load such as a capacitor. *3. The Vs indicates a voltage value in your environment.
F3SJ-E/B
6
User’s Manual
Page 23
Overview and Specifications
Model
Item
Protection circuit Output short-circuit protection, and power supply reverse polarity protection
Ambient temperature During operation: -10 to 55°C (non-freezing), During storage: -25 to 70°C
Ambient humidity During operation: 35 to 85%RH (non-condensing), During storage: 35 to 95%RH
Ambient light intensity
Insulation resistance 20 MΩ or higher (500 VDC)
Dielectric strength 1,000 VAC, 50/60 Hz, 1 min
Degree of protection IP65 (IEC 60529)
Vibration resistance
Shock resistance Malfunction: 100 m/s
Pollution degree Pollution degree 3 (IEC 60664-1)
Connection method
Power cable
Series connection cable (F39-JBR2W)
Extension cable (F39-JDA, JDB)
Number of wires Emitter: 5 wires, receiver: 6 wires 8 wires
Cable diameter Dia. 6 mm
Allowable bending radius
Connection method
Number of wires 8 wires
Cable diameter Dia. 6 mm
Allowable bending radius
Connection method
Incandescent lamp: 3,000 lx max. on receiving surface. Sunlight: 10,000 lx max. on receiving surface.
Malfunction: 10 to 55 Hz, Multiple amplitude of 0.7 mm, 20 sweeps each in X, Y, and Z directions
Prewired cable, cable length 3 m
R5 mm
page 87.
Easy Type Basic Type
F3SJ-EP25 F3SJ-BP25
2
, 1,000 times each in X, Y, and Z directions
Prewired connector cable, cable length 0.3 m Connector type (M12, 8-pin) Connector: IP67 rated (when mated)
Prewired connector cable, cable length 0.2 m Connector type (M12, 8-pin) Connector: IP67 rated (when mated)
R5 mm
Connector method (M12, 8-pin) IP67 degree of protection for connector (fitting)
For details about twisted pair wires (single-ended cable) p.84, (double­ended cable) p.85
Refer to "<Extension cable>" on
For details about total extension cable length
Chapter1 Ratings/Specifications
Number of wires 8 wires
Cable diameter Dia. 6.6 mm
Allowable bending radius
Extension cable 30 m max.
Case: Aluminum
Material
Weight (packaged) F3SJ-EP25
Accessories CD (User's Manual), Instruction manual
Applicable standards
Safety-related characteristic data (EN 61508:2010)
Cap: ABS resin, PBT Optical cover: PMMA resin (acrylic) Cable: Oil resistant PVC
Weight (g) = (protective height) x 2.6 + 800
Refer to "Legislation and Standards" on page i.
See http://www.fa.omron.co.jp/safety_6en/
R36 mm
F3SJ-BP25 Weight (g) = (protective height) x 2.7 + 500
F3SJ-E/B
User’s Manual
E
7
Page 24
Overview and Specifications

Model/Current Consumption List

Easy Type
Chapter1 Ratings/Specifications
F3SJ-E0185P25 8 185 29.0 mA 38.0 mA
F3SJ-E0225P25 10 225 31.0 mA 38.0 mA
F3SJ-E0305P25 14 305 34.0 mA 40.0 mA
F3SJ-E0385P25 18 385 37.0 mA 41.0 mA
F3SJ-E0465P25 22 465 41.0 mA 42.0 mA
F3SJ-E0545P25 26 545 44.0 mA 43.0 mA
F3SJ-E0625P25 30 625 47.0 mA 44.0 mA
F3SJ-E0705P25 34 705 50.0 mA 45.0 mA
F3SJ-E0785P25 38 785 54.0 mA 46.0 mA
F3SJ-E0865P25 42 865 57.0 mA 47.0 mA
F3SJ-E0945P25 46 945 60.0 mA 48.0 mA
F3SJ-E1025P25 50 1025 63.0 mA 50.0 mA
F3SJ-E1105P25 54 1105 58.0 mA 51.0 mA
Model
Easy Type
(F3SJ-EP25)
Number of beams Protective height [mm]
Current consumption
Emitter Receiver
Basic Type
Model
Basic Type
(F3SJ-BP25)
F3SJ-B0185P25 8 185 41.0 mA 41.0 mA
F3SJ-B0225P25 10 225 43.0 mA 42.0 mA
F3SJ-B0305P25 14 305 46.0 mA 43.0 mA
F3SJ-B0385P25 18 385 49.0 mA 44.0 mA
F3SJ-B0465P25 22 465 52.0 mA 45.0 mA
F3SJ-B0545P25 26 545 55.0 mA 46.0 mA
F3SJ-B0625P25 30 625 58.0 mA 47.0 mA
F3SJ-B0705P25 34 705 62.0 mA 48.0 mA
F3SJ-B0785P25 38 785 65.0 mA 49.0 mA
F3SJ-B0865P25 42 865 68.0 mA 50.0 mA
F3SJ-B0945P25 46 945 71.0 mA 52.0 mA
F3SJ-B1025P25 50 1025 75.0 mA 53.0 mA
F3SJ-B1105P25 54 1105 69.0 mA 54.0 mA
F3SJ-B1185P25 58 1185 72.0 mA 55.0 mA
F3SJ-B1265P25 62 1265 75.0 mA 56.0 mA
F3SJ-B1345P25 66 1345 77.0 mA 57.0 mA
F3SJ-B1425P25 70 1425 80.0 mA 58.0 mA
F3SJ-B1505P25 74 1505 83.0 mA 59.0 mA
F3SJ-B1585P25 78 1585 85.0 mA 60.0 mA
F3SJ-B1665P25 82 1665 88.0 mA 61.0 mA
F3SJ-B1745P25 86 1745 91.0 mA 63.0 mA
F3SJ-B1825P25 90 1825 93.0 mA 64.0 mA
F3SJ-B1905P25 94 1905 96.0 mA 65.0 mA
F3SJ-B1985P25 98 1985 99.0 mA 66.0 mA
F3SJ-B2065P25 102 2065 101.0 mA 67.0 mA
Number of beams Protective height [mm]
Current consumption
Emitter Receiver
F3SJ-E/B
8
User’s Manual
Page 25
Chapter2 System Configuration and
Functions
How to Select a Model/System 10
Selection Flowchart 10 Function List 10
Wiring Diagrams 11
Easy Type 11 Basic Type (Basic System) 12 Basic Type (Muting System) 15
Description of Functions 16
External Test Function 16 Self-test Function 17 Lockout Reset Function 18 Interlock Function 19 Auxiliary Output Function 20 External Device Monitoring Function 21 Muting Function 22 Override Function 34

Chapter2 System Configuration and Functions

F3SJ-E/B
User’s Manual
E
9
Page 26
Chapter2 How to Select a Model/System
Do you use muting function?
Do you use interlock function? Do you use external device monitoring function? Do you use auxiliary output function? Do you use series connection?
Easy Type
Basic Type (Muting system)
Basic Type (Basic system)
NO NO
YES
YES
System Configuration and Functions

How to Select a Model/System

Selection Flowchart

The required system configuration depends on the functions to be used. Use the following flowchart to determine the model/system.

Function List

Function Easy Type
Self-test 
External test 
Interlock
External device monitoring
Auxiliary output 
Muting
Override
Series connection 
Basic Type
Basic system
Basic Type
Muting system
F3SJ-E/B
10
User’s Manual
Page 27
System Configuration and Functions
0V
Emitter
Receiver
0 V (Blue)
Test input (Black)
24 V (Brown)
24 V (Brown)
Safety
output 1 (Black)
Safety
output 2 (White)
0 V (Blue)
Power supply
+24 VDC
(Gray) Communication line (+)
(Pink) Communication line (-)
S1
*1
KM1
KM2
S1 : External test/lockout reset switch (connect to 0 V if a switch is not required) KM1, KM2 : Safety relay with force-guided contact (G7SA) or magnetic contactor
*1. Use a switch for small loads (input specifications: 24 V, 3 mA).

Wiring Diagrams

Easy Type

Minimum wiring required to check the operation of the F3SJ-E
Chapter2 Wiring Diagrams
Emitter
(Gray) Communication line (+)
(Pink) Communication line (-)
0 V (Blue)
24 V (Brown)
Test input (Black)
Open
Wiring when using test input line
Receiver
24 V (Brown)
Safety
output 1 (Black)
Open
0 V (Blue)
Safety
output 2 (White)
Open
+24 VDC
Power supply
0V
F3SJ-E/B
User’s Manual
E
11
Page 28
System Configuration and Functions
Open
Open
Open
Open
0 V
Shield
Not Used (Red)
0 V (Blue)
Interlock select input (White)
Test input (Black)
Reset input (Yellow)
24 V (Brown)
Emitter
Receiver
(Gray) Communication line (+)
(Pink) Communication line (-)
24 V (Brown)
External device
monitoring input (Red)
0 V (Blue)
Auxiliary output (Yellow)
Safety output 1 (Black)
Safety output 2 (White)
Shield
Open
Open
Open
Power supply
+24 VDC
F39-JDA-L F39-JDA-D
KM1
KM2
S
*1 *1
*2
1 S 2
S1 S2 KM1, KM2 K1
*1. Use a switch for small loads (input specifications: 24 V, 3 mA). *2. F3SJ operates even when K1 is not connected.
: External test switch (connect to 0 V if a switch is not required) : Interlock/lockout reset switch : Safety relay with force-guided contact (G7SA) or magnetic contactor : Load or PLC, etc. (for monitoring)
K1
KM1
KM2
0 V
Emitter
Receiver
(Grey) Communication line (+)
(Pink) Communication line (-)
Shield
Not Used (Red)
0 V (Blue)
Interlock select input (White)
Test input (Black)
Reset input (Yellow)
24 V (Brown)
24 V (Brown)
External device monitoring input (Red)
0 V (Blue)
Auxiliary output (Yellow)
Safety output 1 (Black)
Safety output 2 (White)
Shield
Power supply
+24 VDC
F39-JDA-L F39-JDA-D

Basic Type (Basic System)

Minimum wiring required to check the operation of the F3SJ-B
Chapter2 Wiring Diagrams
(Wiring for auto reset mode and deactivated external device monitoring)
Wiring when using manual reset mode and external device monitoring
12
F3SJ-E/B
User’s Manual
Page 29
System Configuration and Functions
S1 S2 KM1, KM2 K1
: External test switch (connect to 0 V if a switch is not required) : Lockout reset switch (connect to 24 V if a switch is not required) : Safety relay with force-guided contact (G7SA) or magnetic contactor : Load or PLC, etc. (for monitoring)
24 V (Brown)
External device monitoring input (Red)
0 V (Blue)
Auxiliary output (Yellow)
Safety output 1 (Black)
Safety output 2 (White)
Shield
Shield
Not Used (Red)
0 V(Blue)
Interlock select input (White)
Test input (Black)
Reset input (Yellow)
24 V (Brown)
KM1
KM2
S1 S2
K1 KM1 KM2
0 V
Emitter
Receiver
(Gray) Communication line (+)
(Pink) Communication line (-)
Power supply
+24 VDC
F39-JDA-L F39-JDA-D
*1 *1
*2
*1. Use a switch for small loads (input specifications: 24 V, 3 mA). *2. F3SJ operates even when K1 is not connected.
S
Wiring for auto reset mode and external device monitoring function
Chapter2 Wiring Diagrams
Wiring for manual reset mode and deactivated external device monitoring function
Emitter
F39-JDA-L F39-JDA-D
hield
0 V (Blue)
Not Used (Red)
S1 S2 KM1, KM2 K1
*1. Use a switch for small loads (input specifications: 24 V, 3 mA). *2. F3SJ operates even when K1 is not connected.
: External test switch (connect to 0 V if a switch is not required) : Interlock/lockout reset switch : Safety relay with force-guided contact (G7SA) or magnetic contactor : Load or PLC, etc. (for monitoring)
Test input (Black)
S1 S2
Interlock select input (White)
*1 *1
(Gray) Communication line (+)
24 V (Brown)
Reset input (Yellow)
(Pink) Communication line (-)
Receiver
24 V (Brown)
Auxiliary
output (Yellow)
Safety output 1 (Black)
K1 KM1 KM2
External device monitoring input (Red)
*2
Shield
0 V (Blue)
Safety output 2 (White)
+24 VDC
Power supply
0 V
F3SJ-E/B
User’s Manual
E
13
Page 30
System Configuration and Functions
S
Wiring for auto reset mode and deactivated external device monitoring function
Chapter2 Wiring Diagrams
hield
S1 S2 KM1, KM2 K1
*1. Use a switch for small loads (input specifications: 24 V, 3 mA). *2. F3SJ operates even when K1 is not connected.
Emitter
F39-JDA-L F39-JDA-D
(Gray) Communication line (+)
(Pink) Communication line (-)
0 V (Blue)
Not Used (Red)
: External test switch (connect to 0 V if a switch is not required) : Lockout reset switch (connect to 24 V if a switch is not required) : Safety relay with force-guided contact (G7SA) or magnetic contactor : Load or PLC, etc. (for monitoring)
Test input (Black)
S1 S2
Interlock select input (White)
*1 *1
24 V (Brown)
Reset input (Yellow)
24 V (Brown)
Receiver
0 V (Blue)
Auxiliary
output (Yellow)
Safety output 1 (Black)
Safety output 2 (White)
K1 KM1 KM2
External device monitoring input (Red)
*2
Shield
+24 VDC
Power supply
0 V
F3SJ-E/B
14
User’s Manual
Page 31

Basic Type (Muting System)

0V
Power supply
+24 VDC
Emitter
Receiver
(Gray) Communication line (+)
(Pink) Communication line (-)
Open
Open
Open
Open
Open
Open
Open
Open
Open
24 V (Brown)
External device
monitoring input (Red)
0 V (Blue)
Auxiliary
output (Yellow)
Safety
output 1 (Black)
Safety
output 2 (White)
Shield
Shield
0 V (Blue)
Muting input 1 (white)
Muting input 2 (Red)
Test input (Black)
Reset input (Yellow)
24 V (Brown)
F39-JDA-L F39-JDA-D
24 V (Brown)
External device monitoring input (Red)
*2
0 V (Blue)
Auxiliary output (Yellow)
Safety output 1 (Black)
Safety output 2 (White)
Shield
Test input (Black)
*1
Reset input (Yellow)
*1
24 V (Brown)
Shield
0 V (Blue)
(Gray) Communication line (+)
(Pink) Communication line (-)
S1 S2 A1 B1 KM1, KM2 K1
: External test switch
(connect to 0 V if a switch is not required)
: Lockout reset switch (connect to 24 V if a switch is not required) : Contact by muting sensor A1 : Contact by muting sensor B1 : Safety relay with force-guided contact (G7SA) or magnetic contactor :
Indicator or PLC, etc. (for monitoring)
S1
B1 A1
S2
K1 KM1
KM2
Emitter
Receiver
Muting input 1 (white)
Muting input 2 (Red)
*1.
Used as override input as well.
*2.
When muting system is used, connect it to 0 V as the external device monitoring function cannot be used.
*3. Use a switch for small loads (input specifications: 24 V, 3 mA). *4. F3SJ operates even when K1 is not connected.
F39-JDA-L F39-JDA-D
*3 *3
*4
Minimum wiring required to operate the F3SJ-B
(Wiring for auto reset mode)
System Configuration and Functions
Chapter2 Wiring Diagrams
Wiring for muting function
F3SJ-E/B
User’s Manual
E
15
Page 32
System Configuration and Functions
Test input
Safety output
ON
OFF
60 ms max.
140 ms max.
ON
OFF
Test input
Safety output
ON
OFF
ON
OFF
60 ms max.
140 ms max.
Test input
Safety output
ON
OFF
360 ms max.
140 ms max.
ON
OFF

Description of Functions

External Test Function

Easy Type
Chapter2 Description of Functions
Basic Type (basic system)
Basic Type (muting system)
This function stops the emission using an external signal. It can be used to verify that a safety system should properly stop (safety output turns OFF) when F3SJ-E/B is interrupted. To stop the emission, apply Vs-3 V to Vs to the emitter's test input line.
Easy Type
Basic Type (basic system)
Basic Type (muting system)
16
F3SJ-E/B
User’s Manual
Page 33

Self-test Function

Subsequently performs periodic test
Power supply
ON
OFF
Self test
ON
OFF
2 s max.
Easy Type
Basic Type (basic system)
Basic Type (muting system)
System Configuration and Functions
The F3SJ-E/B performs the self-test when power is turned ON (within 2 seconds) to check for errors. Also, it regularly performs the self-test (within a response time) while operating. This function cannot be cancelled.
If an error is found in the self-test, the F3SJ-E/B enters lockout state, keeps the safety output in the OFF state, and indicates the error at the same time.
Self-test details
The self-test detects the types of errors described below. Emitter
• Failure of emitter element or circuit
• CPU failure
• Disconnected or short-circuited cable
Receiver
• Abnormal external power supply voltage
• Failure of internal power supply circuit
• Failure of receiver element or detection circuit
• CPU failure
• Memory failure
• Incidence of disturbance light
• Failure of safety output circuit
• Disconnected or short-circuited cable
Chapter2 Description of Functions
Waveform of safety outputs
When the F3SJ-E/B is receiving light, the safety outputs cyclically turn OFF as shown below to test the output circuit. When this OFF signal is fed back, the output circuit is diagnosed as normal. If the output signal does not include an OFF pulse signal due to short-circuit, etc, the receiver diagnoses a failure in the output circuit or wiring, and it enters lockout state.
Approx. 15 to 30 ms
ON
Safety output 1
OFF
ON
Safety output 2
OFF
* An OFF pulse signal of safety output may extend to a maximum of about 100μs due to the effect of the connected load (mostly capacitive load).
Approx.
7.5 to 15 ms
Approx. 15 to 30 ms
Approx. 40 μs max. *
F3SJ-E/B
User’s Manual
E
17
Page 34
System Configuration and Functions

Lockout Reset Function

Easy Type
Basic Type (basic system)
Basic Type (muting system)
Chapter2 Description of Functions
When the cause of the lockout is removed, you can release the lockout by using either of the following methods. *1
•Cycle the power back ON
•Reset input Resetting methods differ as follows depending on the system used.
System Lockout reset
Easy Type
Basic Type (basic system) Manual reset
Basic Type (basic system) Auto reset
Basic Type (muting system)
Apply a voltage of Vs-3 V to Vs to the test input line (black) for 1 s or longer, and then open the input line or apply 0 V to 1/2 Vs again.
Apply a voltage of Vs-3 V to Vs to the reset input line (yellow) for 1 s or longer, and then open the input line or apply 0 V to 1/2 Vs again.
Open or apply 0 V to 1/2 Vs to the reset input line (yellow) for 1 s or longer, and then apply a voltage of Vs-3 V to Vs again.
*1. When there is an input wiring error at startup, a lockout reset does not work. Fix the wiring error
and then turn ON the power again.
18
F3SJ-E/B
User’s Manual
Page 35

Interlock Function

Safety output
ON
OFF
Interlock state
Reset input
ON
OFF
300 ms min.
Interlock Release
500 ms max.
Easy Type
Basic Type (basic system)
Basic Type (muting system)
System Configuration and Functions
The F3SJ-B turns the safety outputs OFF when its power is turned on or its beam is interrupted and holds this state until reset input is applied. This state is called "interlock". Two methods can be used to reset the interlock state: "auto reset" and "manual reset." "Auto reset" automatically turns safety outputs ON when the interrupting object is removed. "Manual reset" keeps safety outputs OFF until a reset signal is provided, if the interrupting object is removed.
Auto reset
When the interrupting object is removed from the detection zone, the safety outputs automatically turn ON. Auto reset is used on machines where a worker is not able to enter the area between the detection zone and the hazardous part of the machine.
- Wiring for auto reset mode and external device monitoring function p.13
- Wiring for auto reset mode and deactivated external device monitoring function p.14
Manual reset
When a reset input is given while no interrupting object exists in a detection zone, the safety outputs turn ON. This allows the machine to be manually reset using a reset switch after ensuring safety, preventing unexpected startup (EN 1037).
Chapter2 Description of Functions
There are two types of interlock as follows:
•The power is turned ON (start interlock).This is useful if you want to keep the machine stopped until start inspection is completed after the power is turned ON.
•The F3SJ-B is blocked (restart interlock). After the F3SJ-B is blocked and the machine stops, manual reset is effective when you want to restart the machine after an operator confirms a safe condition.
- Wiring when using manual reset mode and external device monitoring p.12
- Wiring for manual reset mode and deactivated external device monitoring function p.13
To re se t:
1. After applying a voltage of Vs-3 V to Vs for 300 ms or longer to the reset input line, set it to open or to
0 to 1/2 VsV.
Install the interlock reset switch in a location that provides a clear view of the entire hazardous zone and where it cannot be activated from within the hazardous zone.
F3SJ-E/B
User’s Manual
E
19
Page 36
System Configuration and Functions
Unblocked
/Blocked
Unblocked
Blocked
Safety output
Auxiliary output
ON
OFF
ON
OFF
15 ms
30 ms max. 30 ms max.
70 ms

Auxiliary Output Function

Easy Type
Basic Type (basic system)
Basic Type (muting system)
Chapter2 Description of Functions
The auxiliary output is used to monitor the status of the F3SJ-B. This output can be connected to a device such as programmable controller.
Do not use the auxiliary output for safety applications. Human body may not be detected when F3SJ-B fails, resulting in serious injury.
For details on operations when muting function is used, see the timing chart on page 24 .
20
F3SJ-E/B
User’s Manual
Page 37
System Configuration and Functions
Safety output
ON
OFF
External device monitoring input
ON
OFF
Unblocked
/Blocked
Unblocked
Blocked
Lockout
T = 0.3 s
0.3 s
Within 0.3 s

External Device Monitoring Function

Easy Type
Basic Type (basic system)
Basic Type (muting system)
The external device monitoring function cannot be used when the muting system is used. This function detects malfunctions, such as welding, in external relays (or contactors) that control the hazardous part of a machine. This function constantly monitors that a specified voltage is applied to the receiver's external device monitoring input line, and the system enters lockout state when an error occurs. The relay's operational delay can be up to 0.3 s without being evaluated as an error. For example, if the normally closed N.C. contact does not close within 0.3 s after the safety outputs turn from ON to OFF, and a specified voltage is not applied to the external device monitoring line , it is evaluated as an error and the system enters a lockout state. To utilize this function properly, use safety relays and contactors that have force guided or mechanically linked contact structure.
Wiring
Perform wiring so that a voltage of Vs-3 V to Vs is applied to the external device monitoring line via the external relay's normally closed N.C. contact. When external device monitoring is not being used, apply the auxiliary output to the external device monitoring input.
Wiring for external device monitoring function p.12
Timing chart
The sensor reads out a device monitoring input value a minimum of 0.5 s after the power of the F3SJ­B is turned ON. If the status of the safety outputs is changed back to the original status within the allowable delay time, the F3SJ-B will not enter the lockout state.
Chapter2 Description of Functions
F3SJ-E/B
User’s Manual
E
21
Page 38
System Configuration and Functions

Muting Function

Easy Type
Basic Type (basic system)
Basic Type (muting system)
Chapter2 Description of Functions
Muting function temporarily disables safety function of the F3SJ-B, keeping safety output ON even if beams are interrupted. This makes it possible to install safety light curtains for AGV passage, enabling both safety and productivity. When muting, the top-beam-state indicator (TOP), bottom-beam-state indicator (BTM) and external indicator (if wired) connected to the auxiliary output blink to notify people in the surrounding zone that the safety functions are disabled.
The muting and override functions disable the safety functions of the device. You must ensure safety using other method when these functions are operating.
Install muting sensors so that they can distinguish between the object that is being allowed to be passed through the detection zone and a person. If the muting function is activated by the detection of a person, it may result in serious injury.
22
F3SJ-E/B
User’s Manual
Page 39
System Configuration and Functions
Muting Key Cap Mode: F39-CN10 (Case color: Orange)
Cap (Case color: Black)
Upgrading F3SJ-B for muting system
Loosen two cap screws (M3 cross-shaped) of either an emitter or a receiver to remove the cap. Replace the Cap with a Muting Key Cap and then tighten it with two screws (M3 cross-shaped).
Chapter2 Description of Functions
- When mounting a Cap or Muting Key Cap, securely tighten the screw (M3 cross-shaped) with the recommended torque of 0.54 N•m. Failure to do so may cause the cap to come loose, leading to deterioration of the protective functions.
- Attaching/detaching of a Cap or Muting Key Cap may cause misalignment of rubber grommet in a connector assembly. Press the grommet to the bottom of the connector and attach the connector to the F3SJ-B again.
<Muting sensor>
The muting sensor is the sensor that is the trigger for temporarily disabling the safety functions of the F3SJ-B. You can use a photoelectric switch of transmission type or reflective type proximity switch, or limit switch. (Recommendation: OMRON E3Z series, E2E series (3-wire type), D4N series) Use a 3­wire type PNP output or N.O. type contact. Two-wire type sensor cannot be used.
<Muting lamp>
You may need a muting lamp depending on your application or as a result of a risk assessment. Before determining the use of the muting lamp, check laws and regulations of the country or region where the F3SJ-B is used and make sure of full compliance with them. The muting lamp can be connected to the auxiliary output.
<Internal indicators of the F3SJ-B>
Top-beam-state indicator
Bottom-beam-state indicator
Muting error indicator Blinks during a muting error.
Muting input 1 indicator Turns ON when an input is given to muting input 1.
Muting input 2 indicator Turns ON when an input is given to muting input 2.
Blinks during muting/override.
F3SJ-E/B
User’s Manual
E
23
Page 40
System Configuration and Functions
F3SJ-B Unblocked
/Blocked
Muting input 1
ON
OFF
Muting input 2
Muting state
Safety output
ON
OFF
Unblocked
Blocked
ON
OFF
Blinking
OFF
Auxiliary output
Enabled
Disabled
T2 max.
1 Hz Blinking
T3 max.
T3 max.
T1min to T1max
0.15 s max.
Using muting function
Turning muting inputs 1 and 2 ON sequentially enables muting function. When a muting lamp is required as a result of a risk assessment, connect a muting lamp to the auxiliary output line.
Chapter2 Description of Functions
If both of the following conditions are present for the F3SJ-B, muting is activated.
1. No interrupting object is found in the F3SJ-B's detection zone, and safety output is ON.
2. After muting input 1 is turned ON (connected to Vs-3 V to Vs), muting input 2 is turned ON (connected to Vs-3 V to Vs) within the muting input time limit of T1min to T1max (0.1 to 3 s).
Muting function can be enabled in up to 0.15 s after condition 2 is satisfied. When condition 1 is satisfied but time condition of 2 is not, a muting sequence error occurs and emitter's muting error indicator blinks. However, when there is a muting error, the F3SJ-B safety function operates and normal operation continues.
For muting error indication, see page 121 .
Muting error can be released by any of following conditions:
1. Correct muting initial condition continues for 0.1 s or longer. *1
2. Power cycle under muting input 1 and 2 OFF state.
*1. The correct initial muting condition is shown as follows.
• Safety output of the light curtain is ON.
• Muting input 1 and 2 are OFF.
<Start conditions>
<End conditions>
If either of the following conditions is satisfied, the muting state is released.
1. Muting input 1 or 2 turns OFF for T3 (0.1 s) or longer.
2. The muting continuation time exceeds the muting time limit of T2 (60 s).
F3SJ-E/B
24
User’s Manual
Page 41
System Configuration and Functions
Variable Variable name Valu e Description
1min
T
T
1max
T
2 Muting time limit
3
T
Muting state can be also released when the sensor enters lockout.
Muting input time limit value (minimum)
Muting input time limit value (maximum)
Maximum muting input pulse duration
0.1 s Minimum time difference between muting inputs 1 and 2. If the time difference between muting inputs 1 and 2 is smaller than this value, a muting error occurs.
3 s Maximum time difference between muting inputs 1 and 2.
If the time difference between muting inputs 1 and 2 is larger than this value, a muting error occurs.
60 s This is the muting function continuation time.
If muting state exceeds this time, the function is canceled.
0.1 s Maximum muting input time with allowable waveform cracks in muting input 1 and 2.
Installation standard for muting sensors
•Set the muting sensors so that they can detect all of the passing detection objects (palettes, automobiles, etc.). Do not install in a position so that only the front or rear end of the detection object is detected.
•Set the muting sensors so that they detect the objects even when they are loaded on palettes or other transport devices.
•Also, install the F3SJ-B and muting sensors so that each object passes through all muting sensors before the next object arrives at the first muting sensor. Also, install all F3SJ-Bs and muting sensors so that no person is able to accidentally enter the hazardous zone while the muting function is enabled.
•If objects' speeds can vary, the allocation of muting sensors must be taken into consideration.
•Install muting sensors so that they can distinguish between the object that is being allowed to be passed through the detection zone and a person.
Chapter2 Description of Functions
F3SJ-E/B
User’s Manual
E
25
Page 42
System Configuration and Functions
Workpiece
L
F3SJ-B
F3SJ-B
d1=D1
B1
Reflector
Reflector
A1
Hazardous zone
V
The crossover point of muting sensors A1 and B1 must be located within the hazardous zone
L: Length of workpiece d1: Maximum distance required for the muting sensor to keep the muting function enabled D1: Minimum distance required for the muting sensor to keep the muting function enabled
Workpiece
F3SJ-B
F3SJ-B
Hazardous zone
B1
Reflector
Reflector
A1
Installation example 1 of standard muting mode (Using two muting sensors)
This is an example of two retro-reflective type photoelectric sensors used as muting sensors installed in a cross pattern. Use two sensors when the length L of the workpieces are not constant or are insufficient.
1. Before a workpiece passes through
Chapter2 Description of Functions
The output state of muting sensors A1 and B1 are both OFF (contacts A1 and B1 are open due to muting output), and the safety function of the F3SJ-B is working. In this example where two muting sensors are used, the crossover point of muting sensors A1 and B1 is in the hazardous zone. This configuration prevents the muting function from being enabled by a person passing through the crossover point.
2. Muting function started working
When muting sensors A1 and B1 are turned ON in this order, the muting function is enabled. In this state, the safety function of F3SJ-B is disabled.
F3SJ-E/B
26
User’s Manual
Page 43
System Configuration and Functions
Workpiece
F3SJ-B
F3SJ-B
B1
Reflector
Reflector
A1
Hazardous zone
Workpiece
F3SJ-B
F3SJ-B
B1
Reflector
Reflector
A1
Hazardous zone
3. Muting function is working
The F3SJ-B is blocked but the safety function is disabled by the muting function, and safety outputs 1 and 2 are turned ON.
Chapter2 Description of Functions
4. The muting function is released
Muting sensor A1 is turned OFF, the muting function is released, and the safety function of the F3SJ-B is enabled.
<Installation distance>
The minimum distance, D1 [m], required for muting sensors to keep the muting function enabled is :
D1 < L . . . . . Formula (1)
L [m]: Length of a workpiece
The maximum distance, d1 [m], required for muting sensors to keep the muting function enabled is :
V x T1min < d1 < V x T1max . . . . . Formula (2)
V [m/s] : Approach speed of a workpiece T1min [s] : Muting input time limit value (minimum). It is set as 0.1 s. T1max [s] : Muting input time limit value (maximum). It is set as 3 s.
F3SJ-E/B
User’s Manual
E
27
Page 44
System Configuration and Functions
To enable the muting function, D1 and d1 must satisfy formulas (1) and (2), respectively. This distance must prevent the muting function from being enabled by a person passing through the muting sensors. Also, install the F3SJ-B and muting sensors so that each workpiece passes through all muting sensors before the next workpiece arrives at the first muting sensor.
Chapter2 Description of Functions
Using a photoelectric switch as a muting sensor
B1
Muting Input 2 (Red)
Muting Input 1 (White)
F3SJ-B
* Two-wire type muting sensor cannot be used.
Reflector
A1, B1: Retro-reflective photoelectric switch
- PNP Output
- ON when Interrupted
ReflectorA1
Using an N.O contact type switch as a muting sensor
Muting Input 2(Red)
Muting Input 1(White)
A1, B1: N.O. contact type switch
B1A1
+24 VDC
Power supply
0 V
<Timing chart>
<Wiring diagram>
T3 max.
T3 max.
T2 max.
1 Hz Blinking
Muting sensor A1
Muting sensor B1
Muting state
Auxiliary output
ON
OFF
ON
OFF
Enabled
Disabled
Blinking
OFF
T1min to T1max
0.15 s max.
28
F3SJ-B Unblocked
F3SJ-E/B
User’s Manual
Unblocked
/Blocked
Safety output
Variable Variable name Valu e Description
T1min
T1max
T2 Muting time limit 60 s
T3
Blocked
ON
OFF
Muting input time limit value (minimum)
Muting input time limit value (maximum)
Maximum muting input pulse duration
0.1 s
3 s
0.1 s
Minimum time difference between muting inputs 1 and 2. If the time difference between muting inputs 1 and 2 is smaller than this value, a muting error occurs.
Maximum time difference between muting inputs 1 and 2. If the time difference between muting inputs 1 and 2 is larger than this value, a muting error occurs.
This is the muting function continuation time. If muting state exceeds this time, the function is canceled.
Maximum muting input time with allowable waveform cracks in muting input 1 and 2.
Page 45
System Configuration and Functions
A1 F3SJ-B A2
Workpiece
Hazardous zone
B1 B2
Installation example 2 of standard muting mode (Using four muting sensors)
This installation example uses four through-beam type photoelectric sensors as muting sensors. The use of four muting sensors is useful when the length of the workpieces is constant or longer, and the entrance and exit have enough space. Muting can be performed from both directions in the arrangement as shown below.
1. Before a workpiece passes through
Hazardous zone
Chapter2 Description of Functions
A1B1F3SJ-B
Workpiece V
L
d2: Maximum distances required for the muting sensor to keep the muting function enabled D3: Minimum distance required for the muting sensor to keep the muting function enabled
F3SJ-B
d2 d2
D3
A2
WorkpieceV
B2
All muting sensors are turned OFF and the safety function of the F3SJ-B is working.
2. The muting sensor is blocked and the safety function of the F3SJ-B is disabled
When muting sensors A1 and B1 are turned ON in this order, the muting function is enabled. In this state, the safety function of F3SJ-B is disabled.
F3SJ-E/B
User’s Manual
E
29
Page 46
System Configuration and Functions
3. The muting sensor is blocked and the safety function of the F3SJ-B is disabled
Hazardous zone
A1 F3SJ-B A2
Chapter2 Description of Functions
Workpiece
B1 B2
Muting sensors A1 and B1 are turned OFF but A2 and B2 are ON, so the muting function is still working. Safety outputs 1 and 2 are turned ON.
4. The muting function is released
Hazardous zone
A1B1F3SJ-BB2A2
Workpiece
Muting sensor B2 is turned OFF, the muting function is released, and the safety function of the F3SJ-B is enabled.
<Installation distance>
The minimum distance, D3 [m], required for muting sensors to keep the muting function enabled is :
D3 < L . . . . . Formula (3)
L [m]: Length of a workpiece
30
The maximum distance, d2 [m], required for muting sensors to keep the muting function enabled is :
V x T1min < d2 < V x T1max . . . . . Formula (4)
V [m/s] : Approach speed of a workpiece T1min [s] : Muting input time limit value (minimum). It is set as 0.1 s. T1max [s] : Muting input time limit value (maximum). It is set as 3 s.
F3SJ-E/B
User’s Manual
Page 47
System Configuration and Functions
Moving direction
Workpiece Workpiece Workpiece Workpiece
Moving direction
+24 VDC
0 V
Power supply
A2A1 B2B1
Muting input 1 (White)
B2
A1 A2
B1
F3SJ-B
Using a photoelectric switch as a muting sensor
* Two-wire type muting sensor cannot be used.
Using an N.O. contact type switch as a muting sensor
A1, B1, A2, B2 : Retro-reflective photoelectric switch
- PNP Output
- ON when Interrupted
A1, A2, B1, B2: N.O. contact type switch
Muting input 2 (Red)
Muting input 1(White)
Muting input 2 (Red)
To enable the muting function, D3 and d2 must satisfy formulas (3) and (4), respectively. This distance must prevent the muting function from being enabled by a person passing through the muting sensors. Also, install the F3SJ-B and muting sensors so that each workpiece passes through all muting sensors before the next workpiece arrives at the first muting sensor.
<Wiring diagram>
Chapter2 Description of Functions
F3SJ-E/B
User’s Manual
E
31
Page 48
System Configuration and Functions
Muting sensor A2
Muting state
Enabled
Disabled
Safety output
ON
OFF
T2 max.
1Hz Blinking
Muting sensor B1
Unblocked
Blocked
Muting sensor B2
Muting sensor A1
Auxiliary output
Blinking
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
F3SJ-B Unblocked
/Blocked
T3 (0.1 s) max.
T3 (0.1 s) max.
T3 (0.1 s) max.
T3 (0.1 s) max.
T1min to T1max
0.15 s max.
F3SJ-B A2 B2 A1 B 1 A 1 B1 B2 A2 A1 B1 B2 A2
F3SJ-B F3SJ-B
D
Workpiece Workpiece Workpiece
(1) (1)
(1)
(2)
(3)
(1)
Reflected light
Direct light Light from other F3SJ-B
L
<Timing chart>
Chapter2 Description of Functions
32
F3SJ-E/B
User’s Manual
Variable Variable name Valu e Description
T1min
T1max
T2 Muting time limit 60 s
T3
<Reference: Preventing light interference of muting sensor>
When a photoelectric sensor is used as a muting sensor, light interference may cause a muting error of F3SJ-B. The cause and measures for light interference are shown as follows:
Muting input time limit value (minimum)
Muting input time limit value (maximum)
Maximum muting input pulse duration
0.1 s
3 s
0.1 s
(1) Interference between muting sensors
Minimum time difference between muting inputs 1 and 2. If the time difference between muting inputs 1 and 2 is smaller than this value, a muting error occurs.
Maximum time difference between muting inputs 1 and 2. If the time difference between muting inputs 1 and 2 is larger than this value, a muting error occurs.
This is the muting function continuation time. If muting state exceeds this time, the function is canceled.
Maximum muting input time with allowable waveform cracks in muting input 1 and 2.
Page 49
System Configuration and Functions
• Use sensors with mutual interference prevention (such as retro-reflective E3Z-R series)
• Use laser-type sensors (such as laser-type E3Z-LR series)
• Take distance from a sensor causing the interference
• Displace beams for each other to prevent interference (change installation height or place them
crosswise)
• Install a physical barrier
• Attach interference prevention filter (provided for E3Z series as accessories)
• Attach a slit to reduce light intensity (provided for E3Z series as accessories)
• Lower the sensitivity
• Reduce a distance between a workpiece and a muting sensor to prevent reflected light from a
workpiece
(2) Interference to a muting sensor from F3SJ-B
• Take distance (D) from a sensor causing the interference
• Displace beams for each other to prevent interference (change installation height or place them
crosswise)
• Install a physical barrier
• Arrange sensors in alternation
• Lower the sensitivity
(3) Interference to F3SJ-B from a muting sensor
• Use a red LED type sensor (such as retro-reflective E3Z-R series)
• Use laser-type sensors (such as laser-type E3Z-LR series)
• Take distance (D) from a sensor causing the interference
• Displace beams for each other to prevent interference (change installation height or place them
crosswise)
• Install a physical barrier
• Arrange sensors in alternation
• Attach a slit to reduce light intensity (provided for E3Z series as accessories)
Chapter2 Description of Functions
Mutual interference between a muting sensor and F3SJ-B in (2) and (3) above can be prevented by configuring D satisfying a formula shown below:
•If L = 0.2 to 3 m D = 0.26 m or larger
•If L = 3 m or larger D = L x tan5° = L x 0.088 m or larger
L : Distance between an emitter and a receiver of the F3SJ-B D : Distance between a muting sensor and a F3SJ-B
E
F3SJ-E/B
User’s Manual
33
Page 50
System Configuration and Functions
Workpiece
F3SJ-B
F3SJ-B
B1
Reflector
Reflector
A1

Override Function

Easy Type
Basic Type (basic system)
Basic Type (muting system)
Chapter2 Description of Functions
The override function turns the safety outputs ON when the muting start condition is not satisfied. If a workpiece stops while passing through the F3SJ-B, as shown below, causing a muting error, the normal state cannot be recovered unless the workpiece is removed from the muting sensors and the detection field of the F3SJ-B. However, the override function will mute the safety outputs of the F3SJ-B so that the conveyor can be restarted to move the workpiece out of the muting sensors and detection zone.
The override function can be enabled for up to 60 s.
The muting and override functions disable the safety function of the device. You must ensure safety using other method when these functions are operating.
Install the switch that uses hold-to-run device such as a spring-return key switch. Install the switch in a location that provides a clear view of the entire hazardous zone and where it cannot be activated from within the hazardous zone. Make sure that nobody is in the hazardous zone before activating the override function.
Override start conditions
If all of the following conditions are present in the F3SJ-B, the override function starts. The override function can be put into effect even when there is a muting error.
1. If either muting input 1 or 2 is ON (One or more muting sensors are turned ON by a workpiece)
2. The F3SJ-B is blocked and the output is OFF
3. Under the conditions of 1 and 2 shown above, the reset input changes from ON to OFF and the test
input changes from OFF to ON at the same time. The changing time of these two inputs must be 0.3 s max.
34
F3SJ-E/B
User’s Manual
Page 51
System Configuration and Functions
Muting input 2
Reset input
ON
OFF
Test input
Override state
Unblocked
/Blocked
Unblocked
Blocked
ON
OFF
ON
OFF
Enabled
Disabled
T1
T1 : Override Input Time Limit : 0.3 s T2 : Override Time Limit : 60 s
Muting input 1
ON
OFF
T2 max.
Safety output
ON
OFF
0.1 s max.
1 Hz Blinking
Auxiliary output
blinking
OFF
Override end conditions
When either of the following conditions is satisfied, the function is released.
•When 60 seconds has elapsed under the override status
•All muting sensors are turned OFF
•When the reset input is turns from OFF to ON and/or the test input turns from ON to OFF
Override state can be also released when the sensor enters lockout.
<Timing chart>
Chapter2 Description of Functions
F3SJ-E/B
User’s Manual
E
35
Page 52
System Configuration and Functions
Chapter2 Description of Functions
36
F3SJ-E/B
User’s Manual
Page 53

Chapter3 Wiring/Installation

Installation Conditions 38
Detection Zone and Approach 38 Safety Distance 39 Distance from Reflective Surfaces 41 Mutual Interference Prevention 41
Series Connection 43
Connection Procedure 45
Dimensions 46
Difference between Easy Type and Basic Type 46 When Using Top/Bottom and Intermediate Brackets 47 When Using Intermediate Brackets Only (Free-Location Mounting) 51 When Using One-touch Brackets 55 When Using Replacement Brackets 60 When Using Contact Mount Brackets 63 When Using Spatter Protection Cover 66
Mounting 67
Chapter3 Wiring/Installation
Mounting Method 67 Number of Brackets Required 67 Mounting Procedure 68
Wiring 82
Wiring Precautions 82 Power Supply Unit 83 Wiring Method (Easy Type) 84 Wiring Method (Basic Type) 84
E
F3SJ-E/B
User’s Manual
37
Page 54
Wiring/Installation
The hazardous zone of a machine can be reached only by passing through the sensor's detection zone.
While working, a person is inside the sensor's detection zone.
It is possible to reach the hazardous zone of a machine without passing through the sensor's detection zone.
A person is between the sensor's detection zone and the hazardous zone of a machine.

Installation Conditions

Detection Zone and Approach

Install a protective structure so that the hazardous part of a machine can only be reached by passing through the sensor's detection zone. Install the sensors so that part of the person is always present in the detection zone and no blind spot is generated when working in a machine's hazardous zones.
Chapter3 Installation Conditions
If a person is able to step into the hazardous zone of a machine and remain behind the F3SJ-E/B's detection zone, configure the system with an interlock function that prevents the machine from being restarted. Failure to do so may result in serious injury.
Do not use this sensor for machines that cannot be stopped by electrical control. For example, do not use it for a pressing machine that uses a full-rotation clutch. Otherwise, the machine may not stop before a person reaches the hazardous part, resulting in serious injury.
To use the F3SJ-E/B in PSDI mode (Reinitiation of cyclic operation by the protective equipment), you must configure an appropriate circuit between the F3SJ-E/B and the machine. For details about PSDI, refer to OSHA 1910.217, IEC 61496-1, and other relevant standards and regulations.
Install the interlock reset switch in a location that provides a clear view of the entire hazardous zone and where it cannot be activated from within the hazardous zone.
Do not use the F3SJ-E/B in environments where flammable or explosive gases are present. Doing so may cause an explosion.
The F3SJ-E/B cannot protect a person from a projectile exiting the hazardous zone. Install protective cover(s) or fence(s).
Make sure that the F3SJ-E/B is securely mounted and its cables and connectors are properly secured.
Correct installation
Incorrect installation
F3SJ-E/B
38
User’s Manual
Page 55
Wiring/Installation
Hazard
Safety distance (S)

Safety Distance

The safety distance is the distance that must be set between the F3SJ-E/B and a machine's hazardous part to stop the hazardous part before a person or object reaches it. The safety distance varies according to the standards of each country and the individual specifications of each machine. Always refer to relevant standards.
Make sure to secure the safety distance (S) between the F3SJ-E/B and the hazardous part. Otherwise, the machine may not stop before a person reaches the hazardous part, resulting in serious injury.
The response time of a machine is the time period from when the machine receives a stop signal to when the machine's hazardous part stops. Measure the response time on the actual system. Also, periodically check to make sure that the response time of the machine has not changed.
How to calculate the safety distance specified by International Standard ISO 13855
(European Standard EN ISO 13855) (Reference)
If a person approaches the detection zone of the F3SJ-E/B perpendicularly S = K x T + C . . . Formula (1)
•S: Safety distance
•K: Approach speed to the detection zone
•T: Total response time of the machine and F3SJ-E/B
•C: Additional distance calculated by the detection capability of the F3SJ-E/B
Chapter3 Installation Conditions
<System that has detection capability of 30 mm or less>
Use K = 2,000 mm/s and C = 8 x (d - 14 mm) in formula (1) for the calculation. S = 2,000 mm/s x (Tm + Ts) + 8 x (d - 14 mm)
•S = Safety distance (mm)
•Tm = Machine's response time (s)
•Ts = Response time of the F3SJ-E/B from ON to OFF (s)
•d = Detection capability of the F3SJ-E/B (mm)
[Calculation example] When Tm = 0.05 s, Ts = 0.015 s, and d = 25 mm: S = 2,000 mm/s x (0.05 s + 0.015 s) + 8 x (25 mm - 14 mm) = 218 mm If the result is less than 100 mm, use S = 100 mm. If the result exceeds 500 mm, use the following formula where K = 1,600 mm/s. S = 1,600 mm/s x (Tm + Ts) + 8 x (d - 14 mm) . . . Formula (2)
If the result of this formula (2) is less than 500 mm, use S = 500 mm.
F3SJ-E/B
User’s Manual
E
39
Page 56
Wiring/Installation
Hazard
Safety distance (S)
H
If a person approaches the detection zone of the F3SJ-E/B horizontally
Use K = 1,600 mm/s and C = (1200 - 0.4 x H) in formula (1) for calculation. Note that C must not be less than 850 mm. S = 1,600 mm/s x (Tm + Ts) + 1200 - 0.4 x H
•S = Safety distance (mm)
•Tm = Machine's response time (s)
•Ts = Response time of the F3SJ-E/B from ON to
Chapter3 Installation Conditions
OFF (s)
•H = Installation height of the F3SJ-E/B (mm)
Note that H must satisfy: 1000 >= H >= 15 (d - 50 mm)
Also, you must include a hazardous condition under which a person may go carelessly through under a detection zone if it exceeds 300 mm (200 mm for other purpose than industrial use) into risk assessment.
[Calculation example] When Tm = 0.05 s, Ts = 0.015 s, d = 25 mm, and H = 500 mm: S = 1,600 mm/s x (0.05 s + 0.015 s) + 1200 - 0.4 x 500 mm = 1,104 mm
How to calculate the safety distance specified by American Standard ANSI B11.19
(reference)
If a person approaches the detection zone of the F3SJ-E/B perpendicularly, calculate the safety distance as shown below. S = K x (Ts + Tc + Tr + Tbm) + Dpf
•S: Safety distance
•K: Approach speed to the detection zone (the value recommended by OSHA standard is 1,600 mm/s)
Approach speed K is not specified in the ANSI B.11.19 standard. To determine the value of K to apply, consider all factors, including the operator's physical ability.
•Ts = Machine's stopping time (s)
•Ts = Response time of the F3SJ-E/B from ON to OFF (s)
•Tc = Machine control circuit's maximum response time required to activate its brake (s)
•Tbm = Additional time (s)
If a machine has a brake monitor, "Tbm = Brake monitor setting time - (Ts + Tc)". If it has no brake monitor, we recommend using 20% or more of (Ts + Tc) as additional time.
•Dpf = Additional distance
According to ANSI's formula, Dpf is calculated as shown below: Dpf = 3.4 x (d - 7.0): Where d is the detection capability of the F3SJ-E/B (unit: mm)
40
[Calculation example] When K = 1,600 mm/s, Ts + Tc = 0.06 s, brake monitor setting time = 0.1 s, Tr = 0.015 s, and d = 25 mm: Tbm = 0.1 - 0.06 = 0.04 s Dpf = 3.4 x (25 - 7) = 61.2 mm S = 1,600 mm/s x (0.06 s + 0.015 s + 0.04 s) + 61.2 mm = 245.2 mm
F3SJ-E/B
User’s Manual
Page 57
Wiring/Installation
L
D
Detection zone
D
Emitter
Receiver
Reflective ceiling
Reflective floor
L
D
Emitter
Receiver
Reflective surface
Emitter Receiver Emitter Receiver

Distance from Reflective Surfaces

Install the sensor system so that it is not affected by reflection from a glossy surface. Failure to do so may hinder detection, resulting in serious injury.
Install the sensor system at distance D or further from highly reflective surfaces such as metallic walls, floors, ceilings, or workpieces, as shown below.
Chapter3 Installation Conditions
Distance between an emitter and a
receiver (operating range L)
0.2 to 3 m 0.13 m
More than 3 m L/2 x tan5° = L x 0.044 (m)
Allowable installation distance D

Mutual Interference Prevention

Mutual interference is prevented in up to three sets, using interference light detection and cycle shift algorithm. If four or more sets of F3SJ-E/Bs are installed, arrange them so that mutual interference does not occur. If two sets are installed near each other, reflection from the surface of the F3SJ-E/B may cause mutual interference. When mutual interference occurs, the safety outputs are turned OFF in a moment or the F3SJ-E/B enters lockout state. Combining countermeasures 1 to 3 shown below is effective.
1. Install a physical barrier between two sets
E
F3SJ-E/B
User’s Manual
41
Page 58
Wiring/Installation
Aligned horizontally
Aligned fore and aft
Aligned vertically
Receiver Emitter Emitter Receiver
Emitter Receiver
Receiver Emitter
Receiver Emitter
Emitter Receiver
Emitter
Receiver
Emitter
Receiver
Emitter Receiver
Emitter Receiver
D
L
D
2. Alternate the direction of emission between two sets (alternation)
Chapter3 Installation Conditions
If two sets of F3SJ-E/Bs are installed near each other, reflection from the surfaces may cause mutual interference.
3. Keep sufficient distance between the F3SJ-E/Bs so that mutual interference does not occur
Distance between emitter and
receiver (operating range L)
0.2 to 3 m 0.26 m
More than 3 m L x tan5° = L x 0.088 (m)
When using four or more sets, the installations shown below may cause mutual interference. When mutual interference occurs, the safety outputs are turned OFF in a moment or the F3SJ-E/B enters lockout state..
Emitter Receiver Emitter Receiver
Allowable installation distance D
Aligned horizontally
Aligned fore and aft
Emitter Receiver
Emitter Receiver
Aligned vertically
Emitter
Emitter
Receiver
Receiver
42
F3SJ-E/B
User’s Manual
Page 59
Wiring/Installation

Series Connection

Easy Type
Basic Type (basic system)
Basic Type (muting system)
Up to three sets of F3SJ-Bs can be series-connected. Series connection allows them to be used as a safety light curtain, requiring only one set to be wired to a controller and preventing mutual interference. If any one set of series-connected F3SJ-B is blocked, both of the safety outputs turn OFF. The indication LED for each F3SJ-B turns ON separately.
• Number of connections: Up to three sets
• Total number of beams: Up to 192 beams
• Connection cable length between two F3SJ-Bs in series connection: 7 m max.
Ex.: Configuring an U-shaped detection zone
Chapter3 Series Connection
The terms used in this document to describe each F3SJ-B in a series connection are shown below.
Secondary sensor 2 (3CH)
Secondary sensor 1 (2CH)
Primary sensor (1CH)
Easy Type cannot be series-connected.
E
F3SJ-E/B
User’s Manual
43
Page 60
Wiring/Installation
Properly connect an emitter to another emitter, and a receiver to another receiver, as shown below.
Chapter3 Series Connection
Secondary sensor 1 (Emitter)
Primary sensor (Emitter)
Do not series-connect an emitter and receiver. They will enter lockout state.
Do not face different models of emitters and receivers toward each other. They will enter lockout state or will be unable to detect objects.
Secondary sensor 1 (Receiver)
Primary sensor (Receiver)
Secondary sensor 1 (Emitter )
Primary sensor (Receiver)
Secondary sensor 1 (Receiver)
Primary sensor (Emitter)
Primary sensor 1 (Emitter)
Secondary sensor (Emitter)
Secondary sensor 1 (Receiver)
Primary sensor (Receiver)
If caps and series connection cables for extension are not connected properly, the F3SJ-B enters lockout (when power is
turned ON).
44
F3SJ-E/B
User’s Manual
Page 61
Wiring/Installation
1. 1.
1. 1.
2. 2.
2. 2.
3. 3.
3. 3.
Cap
Cap
F39-JBR2W
F39-JD
B
F39-JBR2W
F39-JD
B
Receiver’s
power supply
cable end
Emitter’s
power supply
cable end
Emitter’s
power supply
cable end
Receiver’s
power supply
cable end
<Secondary sensor>
<Primary sensor>

Connection Procedure

1. Remove the caps from the primary sensor. Loosen the screw (M3 cross-shaped) to remove the cap.
2. Use the F39-JBR2W series connection cable for extension to connect them.
3. When changing the connection distance between the F3SJ-Bs, connect a F39-JDB double-ended
connector cable (sold separately).
Chapter3 Series Connection
- When attaching a cable or cap, securely fasten the screws (M3 cross-shaped (2 for each), recommended torque:
- Attaching/detaching of a cap or a series-connection cable may cause misalignment of rubber grommet in a
0.54 N•m). Failure to do so may cause the cable/cap to come loose, leading to deterioration of the protective functions.
connector assembly. Press the grommet to the bottom of the connector and attach the connector F3SJ-B again.
F3SJ-E/B
User’s Manual
E
45
Page 62
Chapter3 Dimensions
3000
50
dia.6
M12 IP67 connector (plug)
dia.6
300
42.8
dia.15
[Unit: mm]
Wiring/Installation

Dimensions

Difference between Easy Type and Basic Type

The differences in appearance between F3SJ-E and F3SJ-B are the cable length and the shape of the cable end. Each cable shape is shown as follows.
Easy Type
Basic Type
46
F3SJ-E/B
User’s Manual
Page 63
Wiring/Installation
P (beam gap)
[ Unit : mm ]
13.4
22.5
34.5
B
A
5.5
30
19
6.5
dia.9
7.5
18.3
7
22
30
30
D
53
42
C (Protective height)
30
13
2
43
6.5
45
<M5 screw fixed> <M8 screw fixed>
Top/Bottom Bracket (F39-LJB1)
Top/Bottom Bracket (F39-LJB1)
Intermediate Bracket (F39-LJB2)
2
E
19
B
B
E
C
C
E
42
42
5.9 5.9
22 22
4-M5
2-M8
2-M5 2-M5
Dimensions A to E and P
Dimensions E
* Value E must be 700 mm or less when not using value E obtained from the calculation above.
AC+69 B C+42.2 C 4-digit number of the type name (protective height) DC-45 E Depends on the protective height. See the table below. P20
Protective height Number of Intermediate Brackets Dimensions E 0185 to 1105 0 ­1185 to 1345 1 C/2 max. 1425 to 2065 2 C/3 max.

When Using Top/Bottom and Intermediate Brackets

Backside mounting
Chapter3 Dimensions
Bracket mounting procedure (Mounting) p.67
- If the protective height is 1105 mm or more, use Intermediate Brackets of specified quantities and locations according to the dimensions. If the brackets described above are not used, ratings and performance cannot be met.
- When you use a sensor in a situation where the sensor is under a load, add an Intermediate Bracket.
E
F3SJ-E/B
User’s Manual
47
Page 64
Wiring/Installation
Dimensions A to E
Dimensions E
* Value E must be 700 mm or less when not using value E obtained from the calculation above.
AC+69 BC+42.2 C 4-digit number of the type name (protective height) DC-45 E Depends on the protective height. See the table below.
Protective height Number of Intermediate Brackets Dimensions E 0185 to 1105 0 ­1185 to 1345 1 C/2 max. 1425 to 2065 2 C/3 max.
Side mounting
Top/Bottom Bracket (F39-LJB1)
dia.9
18.3
30
30
19
6.5
7.5
46
30
34.5
4-M5
19
2-M8
Chapter3 Dimensions
Intermediate Bracket (F39-LJB2)
Top/Bottom Bracket (F39-LJB1)
7
22 22
B
B
53
42
5.5
34
42
12
A
E
13.4
D
C (Protective height)
22.5
42
2-M5 2-M5
16
C
42
E
B
C
E
5.9 5.9
<M5 screw fixed> <M8 screw fixed>
45
[ Unit : mm ]
F3SJ-E/B
48
User’s Manual
Bracket mounting procedure (Mounting) p.67
- If the protective height is more than 1105 mm, use Intermediate Brackets of specified quantities and locations according to the dimensions. If the brackets described above are not used, ratings and performance cannot be met.
- When you use a sensor in a situation where the sensor is under a load, add an Intermediate Bracket.
Page 65
Dimensions of Top/Bottom Brackets
Wiring/Installation
34.5
18.3
4.3
19
16
30
dia.9
7.5
6.5
2
Dimensions of Intermediate Brackets (backside mounting)
80
30
Chapter3 Dimensions
43
Material : Stainless
[ Unit : mm ]
45
15
7
5.5 42
53
8
(35.7)
(31.5)
Material : Zinc die-cast
[ Unit : mm ]
8
(13)
E
F3SJ-E/B
User’s Manual
49
Page 66
Chapter3 Dimensions
8
(46)
(16)
8
53
42
5.5
26
80 30
15
7
45
[ Unit : mm ]
Material : Zinc die-cast
Wiring/Installation
Dimensions of Intermediate Brackets (side mounting)
50
F3SJ-E/B
User’s Manual
Page 67
Wiring/Installation
[ Unit : mm ]
15
22
7
F
42
5.5
275 max 275 max
C (Protective height)
43
30 30
Intermediate Bracket (F39-LJB2)
Intermediate Bracket (F39-LJB2)
22
42
4-M5
42
F
C
Dimensions C and F
Dimensions F
C 4-digit number of the type name (protective height) F Depends on the protective height. See the table below.
Protective height Number of Intermediate Brackets Dimensions F 0185 to 0225 1 ­0305 to 1105 2 555 mm max. 1185 to 1585 3 555 mm max. 1665 to 2065 4 555 mm max.

When Using Intermediate Brackets Only (Free-Location Mounting)

Backside mounting
Chapter3 Dimensions
Bracket mounting procedure (Mounting) p.67
The alignment range of the Intermediate Bracket must be ±30°.
E
F3SJ-E/B
User’s Manual
51
Page 68
Chapter3 Dimensions
22
42
C
C
C
C
C/2
C/2
C/2
FF
FF
C
FFF
C/2
22
42 4242
C
FFF
22
42 4242 42
2-M5
6-M5
8-M5
275 max 275 max
275 max 275 max
275 max 275 max
• Mounting with one Intermediate Bracket • Mounting with three Intermediate Brackets • Mounting with four Intermediate Brackets
[Unit: mm]
Wiring/Installation
52
F3SJ-E/B
User’s Manual
Page 69
Side mounting
[ Unit : mm ]
42
275 max 275 max
275 max 275 max
5.5
7
3
F
C (Protective height)
C (Protective height)
45
37
33
16
30
42 42
F
Intermediate Bracket (F39-LJB2)
Intermediate Bracket (F39-LJB2)
Dimensions C and F
Dimensions F
C 4-digit number of the type name (protective height) F Depends on the protective height. See the table below.
Protective height Number of Intermediate Brackets Dimensions F 0185 to 0225 1 ­0305 to 1105 2 555 mm max. 1185 to 1585 3 555 mm max. 1665 to 2065 4 555 mm max.
Wiring/Installation
Chapter3 Dimensions
Bracket mounting procedure (Mounting) p.67
The alignment range of the Intermediate Bracket must be ±30°.
E
F3SJ-E/B
User’s Manual
53
Page 70
Chapter3 Dimensions
42
C
C
C
C
C/2
C/2
C/2
275 max 275 max
275 max 275 max
275 max 275 max
275 max 275 max
FF
FF
C
FFF
C/2
42 4242
C
FFF
42 4242 42
2-M5
6-M5
8-M5
• Mounting with one Intermediate Bracket • Mounting with three Intermediate Brackets • Mounting with four Intermediate Brackets
[Unit: mm]
Wiring/Installation
54
F3SJ-E/B
User’s Manual
Page 71

When Using One-touch Brackets

43
30
3030
F
C (Protective height)
15
275 max 275 max
[ Unit : mm ]
<M6 screw fixed> <M8 screw fixed>
C
C
32.1 32.1
2-M6
F
32.1 32.1
2-M8
F
One-touch Bracket (F39-LJB3-M6 or F39-LJB3-M8)
One-touch Bracket (F39-LJB3-M6 or F39-LJB3-M8)
Dimensions C and F
Dimensions F
C 4-digit number of the type name (protective height) F Depends on the protective height. See the table below.
Protective height Number of Intermediate Brackets Dimensions F 0185 to 1105 2 555 mm max. 1185 to 1585 3 555 mm max. 1665 to 2065 4 555 mm max.
Backside mounting
Wiring/Installation
Chapter3 Dimensions
Bracket mounting procedure (Mounting) p.67
The alignment range of the One-touch Bracket must be ±30°.
F3SJ-E/B
User’s Manual
E
55
Page 72
Chapter3 Dimensions
C
FF
FF
275 max275 max
275 max 32.1
3-M6
32.1 32.1
275 max
C/2
C/2
C
C
FF F 275 max275 max
FF
275 max
32.1
3-M8
32.1 32.1
275 max
C/2
C
FF F
275 max
32.1
4-M6
32.1 32.1
275 max
C
32.1
FF F
275 max
32.1
4-M8
32.1 32.1
275 max
C
32.1
• Mounting with three One-touch Brackets • Mounting with four One-touch Brackets
<M6 screw fixed> <M8 screw fixed> <M6 screw fixed> <M8 screw fixed>
[Unit: mm]
Wiring/Installation
56
F3SJ-E/B
User’s Manual
Page 73
Side mounting
[ Unit : mm ]
16
30
45
33
3
275 max 275 max
F
C (Protective height)
12
<M6 screw fixed> <M8 screw fixed>
C
C
32.1 32.1
2-M6
F
32.1 32.1
2-M8
F
One-touch Bracket (F39-LJB3-M6 or F39-LJB3-M8)
One-touch Bracket (F39-LJB3-M6 or F39-LJB3-M8)
Dimensions C and F
Dimensions F
C 4-digit number of the type name (protective height) F Depends on the protective height. See the table below.
Protective height Number of Intermediate Brackets Dimensions F
0185 to 1105 2 555 mm max. 1185 to 1585 3 555 mm max. 1665 to 2065 4 555 mm max.
Wiring/Installation
Chapter3 Dimensions
Bracket mounting procedure (Mounting) p.67
The alignment range of the One-touch Bracket must be ±30°.
E
F3SJ-E/B
User’s Manual
57
Page 74
Wiring/Installation
• Mounting with three One-touch Brackets • Mounting with four One-touch Brackets
Chapter3 Dimensions
275 max275 max
C/2
FF
C
32.1
3-M6
275 max 275 max
C/2
C
32.1
3-M8
FF
32.1 32.1
275 max 275 max
C/2
C
C
FF
32.1 32.1
275 max275 max
FFF
4-M6
32.1
C
32.1
FF F
32.1 32.1
275 max 275 max
4-M8
32.1
C
32.1
FF F
32.1 32.1
275 max 275 max
<M6 screw fixed> <M8 screw fixed> <M6 screw fixed> <M8 screw fixed>
[Unit: mm]
58
F3SJ-E/B
User’s Manual
Page 75
Wiring/Installation
22
1.5
8
dia.6.2
dia.13
Material : Stainless
22
1.5
8
dia.8.2
dia.17
Material : Stainless
80
(32.1) (32.1)
45
15
30
dia.22
dia.22
[ Unit : mm ]
30
53
8
(13)
(31.5)
(35.7)
Material : Zinc die-cast
45
15
30
8
(46)
(16)
Material : Zinc die-cast
80
(32.1) (32.1)
dia.22
dia.22
[ Unit : mm ]
26
53
Dimensions of One-touch M6 Bracket Dimensions of One-touch M8 Bracket
Dimensions of Intermediate Bracket + One-touch Bracket (backside mounting)
Dimensions of Intermediate Bracket + One-touch Bracket (side mounting)
Chapter3 Dimensions
F3SJ-E/B
User’s Manual
E
59
Page 76
Chapter3 Dimensions
19
4-M5
B
Replacement Bracket (F39-LJB4)
Replacement Bracket (F39-LJB4)
43
13
30 19
6.5
62
30
B
C (Protective height)
A
79.5
36.5
[ Unit : mm ]
Dimensions A to C
A C+159 BC+86 C 4-digit number of the type name (protective height)
Wiring/Installation

When Using Replacement Brackets

Backside mounting
Bracket mounting procedure (Mounting) p.67
If the protective height is more than 1105 mm, use Intermediate Brackets of the quantities and locations according to the dimensions described on page 47 "When Using Top/Bottom and Intermediate Brackets". If the brackets described above are not used, ratings and performance cannot be met.
60
F3SJ-E/B
User’s Manual
Page 77
Side mounting
[ Unit : mm ]
36.5
79.5
A
C (Protective height)
B
46
2
30
30
19
6.5
30
62
19
B
4-M5
Replacement Bracket (F39-LJB4)
Replacement Bracket (F39-LJB4)
Dimensions A to E and P
A C+159 BC+86 C 4-digit number of the type name (protective height)
Wiring/Installation
Chapter3 Dimensions
Bracket mounting procedure (Mounting) p.67
If the protective height is more than 1105 mm, use Intermediate Brackets of the quantities and locations according to the dimensions described on page 47 "When Using Top/Bottom and Intermediate Brackets". If the brackets described above are not used, ratings and performance cannot be met.
F3SJ-E/B
User’s Manual
E
61
Page 78
Chapter3 Dimensions
Material: Stainless [ Unit : mm ]
16
30
2
43
6.5
19
5.5
62
79.5
Wiring/Installation
Dimensions of replacement bracket
62
F3SJ-E/B
User’s Manual
Page 79

When Using Contact Mount Brackets

30
30
32
2
2
Contact Mount Bracket (F39-LJB5)
Contact Mount Bracket (F39-LJB5)
B
D
22.5
10.75
3.25
7
A
6.5
30
34.5
Dia. 9
19
30
P(beam gap)
C(Protective height)
C
B
3.25
2-M8
3.25
C
B
19
<M5 screw fixed> <M8 screw fixed>
4-M5
Dimensions A to D
AC+69 B C+47.5 C 4-digit number in the Model name (protective height) DC-45
Backside mounting
Wiring/Installation
Chapter3 Dimensions
- The protective height of the F3SJ-E/B series that supports the contact mount bracket is limited. Protective height allowed for mounting: 185 mm to 1,105 mm.
- Brackets of other models such as F39-LJB1 cannot be used simultaneously.
E
F3SJ-E/B
User’s Manual
63
Page 80
Wiring/Installation
Dimensions A to D
A C+69 B C+47.5 C 4-digit number in the Model name (protective height) DC - 45
Side mounting
Contact Mount Bracket (F39-LJB5)
Dia. 9
30
19
7
6.5
35
30
4-M5
19
2-M8
3.25
Chapter3 Dimensions
Contact Mount Bracket (F39-LJB5)
30
33
12
3.25
34.5
B
B
A
D
C
C
22.5
5
10.75 B
<M5 screw fixed> <M8 screw fixed>
3.25
64
F3SJ-E/B
User’s Manual
- The protective height of the F3SJ-E/B series that supports the contact mount bracket is limited. Protective height allowed for mounting: 185 mm to 1,105 mm.
- Brackets of other models such as F39-LJB1 cannot be used simultaneously.
Page 81
Dimensions of contact mount bracket
16 30
32
2
13.54
7.5
34.5
19
6.5
dia. 9
Material: Stainless
(Unit: mm)
Wiring/Installation
Chapter3 Dimensions
E
F3SJ-E/B
User’s Manual
65
Page 82
Chapter3 Dimensions
L = □□□□ - 21mm
Material: PC (Protection cover)
L
L
10
3232
10
[ Unit : mm ]
Wiring/Installation

When Using Spatter Protection Cover

Dimensions of Spatter Protection Cover F39-HB
Assembly Dimensions
32
35.5
[ Unit : mm ]
66
F3SJ-E/B
User’s Manual
Page 83

Mounting

Mounting Method

Mounting methods include use of Top/Bottom Brackets, Top/Bottom Brackets + Intermediate Brackets, Intermediate Brackets only (Free-Location Mounting) and use of One-touch Brackets. Any of these mounting methods allows the user to use the same bracket for the backside mounting and side mounting.
Wiring/Installation

Number of Brackets Required

The numbers of brackets required according to the protective heights of the sensor are as follows:
•When Using Top/Bottom Brackets Only --> p.68
•When Using Top/Bottom + Intermediate Brackets --> p.70
Protective height
0185 to 1105 2 0
1185 to 1345 2 1
1425 to 2065 2 2
Number of Top/
Bottom Brackets
• When Using Intermediate Brackets Only --> p.74
Protective height
0185 to 0225 1
0305 to 1105 2
1185 to 1585 3
1665 to 2065 4
Number of
Intermediate Brackets
• When Using One-touch Bracket --> p.77
Protective height
0185 to 1105 2
1185 to 1585 3
1665 to 2065 4
Number of One-touch
Brackets
Number of
Intermediate Brackets
Chapter3 Mounting
F3SJ-E/B
User’s Manual
E
67
Page 84
Chapter3 Mounting
Tighten securely
Hexagon socket head cap screws (M3 x 6)
Tighten lightly
Top/Bottom Mounting Bracket
Side mounting Backside mounting
Anti-rotation hexagon socket head cap screw (M3 x 8)
Anti-rotation hexagon socket head cap screw (M3 x 8)
Loosen Loosen
Tighten lightly
Figure 1
Tighten securely
Side mounting
Backside mounting
Tighten securely
Figure 2
Wiring/Installation

Mounting Procedure

Using Top/Bottom Bracket only
1. Attach Top/Bottom Brackets and tighten them using the included hexagon socket head cap screws (M3
x 6). Tighten the hexagon socket head cap screws (M3 x 6) with the torque at 0.54 N•m (recommended). (Figure 1) Loosen the hexagon socket head cap screws (M3 x 6), prepare brackets for backside or side mountings, and then lightly tighten them with the hexagon socket head cap screws (M3 x 6).
2. Adjust the Top/Bottom Brackets to the mounting position of the wall surface and then tighten them with
F3SJ-E/B
68
User’s Manual
screws. (Figure 2)
Screws to mount the brackets to the wall are not included.
Page 85
Wiring/Installation
Figure 3 Figure 4
Enlarged view
Side mounting
Backside mounting
Tighten securely
Tighten securely
Tighten securely
Hexagon socket head cap screw (M3 x 8)
Figure 5
3. Turn ON the sensor to perform beam alignment.
Move the emitter from side to side (Figure 3) to align it to a center position where the stable-state indicator (STB) is turned ON while checking the top beam state and bottom beam state with the top­beam-state indicator (TOP) and bottom-beam-state indicator (BTM). (Figure 4) Next, move the receiver from side to side (Figure 3) to align it to a center position where the stable­state indicator (STB) is turned ON. (Figure 4)
Emitter Receiver
TOP indicator
(Blue)
STB indicator
(Green)
BTM indicator
(Blue)
Chapter3 Mounting
EMITTER
- Confirm that there is no interrupting object in the detection zone before adjusting beams.
- If the stable-state indicator (STB) does not turn ON despite performing alignment, check if the mounting surfaces of the emitter/receiver are parallel, and if the mounting height of the emitter/receiver is appropriate. Using optional Laser Alignment Kit (F39-PTJ) makes alignment easier.
RECEIVER
4. Tighten the lightly tightened hexagon socket head cap screws (M3 x 6) of the Top/Bottom Brackets.
(Figure 5) Tighten the hexagon socket head cap screws (M3 x 6) with the torque at 0.54 N•m (recommended).
Tightening screws with a torque that considerably exceeds the recommended torque may cause failure.
Mounting is complete.
F3SJ-E/B
User’s Manual
E
69
Page 86
Chapter3 Mounting
Intermediate Bracket (1)
Hexagon socket head cap screw (M3 x 12)
Hexagon socket head cap screw (M3 x 18)
Loosen
Intermediate Bracket (2)
Intermediate Bracket (3)
Loosen
Backside mounting
Figure 6
Hexagon socket head cap screw (M3 x 18)
Hexagon socket head cap screw (M3 x 12)
Intermediate Bracket (1)
Loosen
Intermediate Bracket (2)
Intermediate Bracket (3)
Intermediate Bracket (1)
Loosen
Intermediate Bracket (2)
Change the direction of Intermediate Bracket (2) and insert it into Intermediate Bracket (3).
Intermediate Bracket (3)
Side mounting
Figure 7
Figure 8
Wiring/Installation
When Using Top/Bottom + Intermediate Brackets
1. Loosen the hexagon socket head cap screws (M3 x 18) of Intermediate Bracket (3) and change the
direction of Intermediate Bracket (2) according to its mounting direction. (Figure 6 and 7) Next, loosen the hexagon socket head cap screws (M3 x 12) of Intermediate Bracket (1) so that it can be mounted to the case of the sensor. For side mounting, the direction of Intermediate Bracket (2) that is inserted into Inermediate Bracket (3) can be left-right in reverse.
2. Mount the Intermediate Bracket to the case, and then lightly tighten the hexagon socket head cap
70
F3SJ-E/B
User’s Manual
screws (M3 x 12) of Intermediate Bracket (1). (Figure 8)
Side mountingBackside mounting
Intermediate Bracket (1) Intermediate Bracket (1)
Tighten lightly
Sensor is secured by Intermediate Brackets.
Optical surface
Intermediate Bracket (2)
Intermediate Bracket (3)
Optical surface
Intermediate Bracket (2)
Tighten lightly
Intermediate Bracket (3)
Sensor is secured by Intermediate Brackets.
Page 87
Wiring/Installation
Tighten securely
Hexagon socket head cap screws (M3 x 6)
Tighten lightly
Top/Bottom Mounting Bracket
Side mounting Backside mounting
Anti-rotation hexagon socket head cap screw (M3 x 8)
Anti-rotation hexagon socket head cap screw (M3 x 8)
Loosen Loosen
Tighten lightly
Figure 9
Figure 10
3. Attach a Top/Bottom Bracket and lightly tighten it using the included hexagon socket head cap screws
(M3x6). Tighten the hexagon socket head cap screws (M3 x 6) with the torque at 0.54 N•m (recommended). Loosen the hexagon socket head cap screws (M3 x 6), prepare brackets for backside or side mountings, and then lightly tighten them with the hexagon socket head cap screws (M3 x 6). (Figure 9)
Chapter3 Mounting
4. Position the Top/Bottom Brackets and the Intermediate Brackets to the mounting location on the wall
and tighten the hexagon socket head cap screws (M3 x 12). (Figure 10) Tighten the hexagon socket head cap screws (M3 x 12) with the torque at 0.54 N•m (recommended).
Backside mounting
Tighten securely
Tighten securely
Adjust to the mounting position
Side mounting
F3SJ-E/B
User’s Manual
E
71
Page 88
Chapter3 Mounting
Tighten the screws to secure the Intermediate Bracket (3) and the wall.
Tighten the screws to secure the Top/Bottom Brackets and the wall.
Figure 11
Emitter Receiver
TOP indicator
(Blue)
STB indicator
(Green)
BTM indicator
(Blue)
RECEIVER
EMITTER
Figure 12 Figure 13
Wiring/Installation
5.
Tighten the screws to mount to the wall by the order of Top/Bottom and Intermediate Brackets. (Figure 11)
Screws to mount the brackets to the wall are not included.
6. Turn ON the sensor to perform beam alignment.
Move the emitter from side to side ( indicator (STB) is turned ON while checking the top beam state and bottom beam state with the top­beam-state indicator (TOP) and bottom-beam-state indicator (BTM). ( Next, move the receiver from side to side to align it to a center position where the stable-state indicator (STB) is turned ON. (
Figure 13
)
Figure 12
) to align it to a center position where the stable-state
Figure 13
)
72
- Confirm that there is no interrupting object in the detection zone before adjusting beams.
- If the stable-state indicator (STB) does not turn ON despite performing alignment, check if the mounting surfaces of the emitter/receiver are parallel, and if the mounting height of the emitter/receiver is appropriate. Using optional Laser Alignment Kit (F39-PTJ) makes alignment easier.
F3SJ-E/B
User’s Manual
Page 89
Wiring/Installation
Enlarged view
Tighten securely
Hexagon socket head cap screw (M3 x 8)
Side mounting
Backside mounting
Tighten securely
Tighten securely
Enlarged view
Side mounting
Backside mounting
Tighten securely
Tighten securely
Hexagon socket head cap screw (M3 x 18)
Figure 14
7. Tighten the lightly tightened hexagon socket head cap screws (M3 x 6, M3 x 18) to prevent rotation of
the Top/Bottom Brackets and Intermediate Bracket. (Figure 14) Tighten the hexagon socket head cap screws (M3 x 6, M3 x 18) with the torque at 0.54 N•m (recommended).
Chapter3 Mounting
Tightening screws with a torque that considerably exceeds the recommended torque may cause failure.
Mounting is complete.
F3SJ-E/B
User’s Manual
E
73
Page 90
Chapter3 Mounting
Intermediate Bracket (1)
Hexagon socket head cap screw (M3 x 12)
Hexagon socket head cap screw (M3 x 18)
Loosen
Intermediate Bracket (2)
Intermediate Bracket (3)
Loosen
Backside mounting
Figure 15
Hexagon socket head cap screw (M3 x 18)
Hexagon socket head cap screw (M3 x 12)
Intermediate Bracket (1)
Loosen
Intermediate Bracket (2)
Intermediate Bracket (3)
Intermediate Bracket (1)
Loosen
Intermediate Bracket (2)
Change the direction of Intermediate Bracket (2) and insert it into Intermediate Bracket (3).
Intermediate Bracket (3)
Side mounting
Figure 16
Figure 17
Wiring/Installation
When using Intermediate Bracket (Free-Location Mounting)
1. Loosen the hexagon socket head cap screws (M3 x 18) of Intermediate Bracket (3) and change the
direction of Intermediate Bracket (2) according to its mounting direction. (Figure 15 and 16) Next, loosen the hexagon socket head cap screws (M3 x 12) of Intermediate Bracket (1) so that it can be mounted to the case of the sensor. For side mounting, the direction of Intermediate Bracket (2) that is inserted into Intermediate Bracket (3) can be left-right in reverse.
2. Mount the Intermediate Bracket to the case, and lightly tighten the hexagon socket head cap screws
74
F3SJ-E/B
User’s Manual
(M3 x 12) of Intermediate Bracket (1). (Figure 17)
Side mountingBackside mounting
Intermediate Bracket (1) Intermediate Bracket (1)
Tighten lightly
Sensor is secured by Intermediate Brackets.
Optical surface
Intermediate Bracket (2)
Intermediate Bracket (3)
Optical surface
Intermediate Bracket (2)
Tighten lightly
Intermediate Bracket (3)
Sensor is secured by Intermediate Brackets.
Page 91
3. Slide the Intermediate Brackets to the mounting position of the wall. (Figure 18)
Figure 18
Side mounting
Backside mounting
Tighten the screws to secure the Intermediate Brackets and the wall.
Tighten the screws to secure the Intermediate Brackets and the wall.
Figure 19
Figure 20
Wiring/Installation
Backside mounting
Adjust to the mounting position
Screws to mount the brackets to the wall are not included.
Side mounting
4. Tighten the screws that fix the Intermediate Bracket and the wall. (Figure 19)
Chapter3 Mounting
5. Tighten the hexagon socket head cap screw (M3 x 12) of Intermediate Bracket (1) with the tightening
torque at 0.54 N•m (recommended). (Figure 20)
Tighten securely
Hexagon socket head cap screw (M3 x 12)
Tightening screws with a torque that considerably exceeds the recommended torque may cause failure.
F3SJ-E/B
User’s Manual
E
75
Page 92
Chapter3 Mounting
Emitter
Receiver
TOP indicator
(Blue)
STB indicator
(Green)
BTM indicator
(Blue)
EMITTER
RECEIVER
Figure 21 Figure 22
Tighten securely
Enlarged view
Side mounting
Backside mounting
Tighten securely
Tighten securely
Hexagon socket head cap screw (M3 x 18)
Figure 23
Wiring/Installation
6. Turn ON the sensor to perform beam alignment.
Move the emitter from side to side (Figure 21) to align it to a center position where the stable-state indicator (STB) is turned ON while checking the top beam state and bottom beam state with the top­beam-state indicator (TOP) and bottom-beam-state indicator (BTM). (Figure 22) Next, move the receiver from side to side (Figure 21) to align it to a center position where the stable­state indicator (STB) is turned ON. (Figure 22)
- Confirm that there is no interrupting object in the detection zone before adjusting beams.
- If the stable-state indicator (STB) does not turn ON despite performing alignment, check if the mounting surfaces of the emitter/receiver are parallel, and if the mounting height of the emitter/receiver is appropriate. Using optional Laser Alignment Kit (F39-PTJ) makes alignment easier.
7. Tighten the lightly tightened the hexagon socket head cap screws (M3 x 18) of Intermediate Bracket (3)
to prevent rotation. (Figure 23) If there are three or more Intermediate Brackets, tighten the hexagon socket head cap screws (M3 x
18) from the order of top, bottom and middle brackets with a tightening torque at 0.54 N•m (recommended).
Tightening screws with a torque that considerably exceeds the recommended torque may cause failure.
76
Mounting is complete.
F3SJ-E/B
User’s Manual
Page 93
Wiring/Installation
Emitter Receiver Emitter Receiver
One-touch M6 Brackets (One-touch M8 Brackets)
Aluminum profile
<Position of the bracket to be mounted to the sensor><Side view of the aluminum profile to be mounted>
When using One-touch Bracket
<Precautions on mounting the sensor using One-touch Brackets>
When using two One-touch Brackets to mount a sensor, the combination of One-touch M6 Bracket (or One-touch M8 Bracket) and Intermediate Bracket at the both ends of the sensor must be positioned opposite each other. When using three or more Brackets, One-touch M6 Brackets (or One-touch M8 Brackets) and Intermediate Brackets at other positions than the both ends must be in the same orientation.
Chapter3 Mounting
(Good example 1) (Good example 2) (Bad example 1) (Bad example 2)
Mount One-touch M6 Brackets (or One-touch M8 Brackets) according to the mounting positions of the emitter and receiver. The positions of Intermediate Brackets mounted to the emitter and receiver must be aligned with each other.
F3SJ-E/B
User’s Manual
E
77
Page 94
Chapter3 Mounting
Intermediate Bracket (1)
Hexagon socket head cap screw (M3 x 12)
Hexagon socket head cap screw (M3 x 18)
Loosen
Intermediate Bracket (2)
Intermediate Bracket (3)
Loosen
Backside mounting
Figure 24
Hexagon socket head cap screw (M3 x 18)
Hexagon socket head cap screw (M3 x 12)
Intermediate Bracket (1)
Loosen
Intermediate Bracket (2)
Intermediate Bracket (3)
Intermediate Bracket (1)
Loosen
Intermediate Bracket (2)
Change the direction of Intermediate Bracket (2) and insert it into Intermediate Bracket (3).
Intermediate Bracket (3)
Side mounting
Figure 25
Figure 26
Wiring/Installation
1. Loosen the hexagon socket head cap screws (M3 x 18) of Intermediate Bracket (3) and change the
direction of Intermediate Bracket (2) according to its mounting direction. (Figure 24 and 25) Next, loosen the hexagon socket head cap screws (M3 x 12) of Intermediate Bracket (1) so that it can be mounted to the case of the sensor. For side mounting, the direction of Intermediate Bracket (2) that is inserted into Intermediate Bracket (3) can be right and left in reverse.
2. Mount the Intermediate Bracket to the case, and lightly tighten the hexagon socket head cap screw
78
F3SJ-E/B
User’s Manual
(M3 x 12) of Intermediate Bracket (1). (Figure 26)
Side mountingBackside mounting
Intermediate Bracket (1) Intermediate Bracket (1)
Tighten lightly
Sensor is secured by Intermediate Brackets.
Optical surface
Intermediate Bracket (2)
Intermediate Bracket (3)
Optical surface
Intermediate Bracket (2)
Tighten lightly
Intermediate Bracket (3)
Sensor is secured by Intermediate Brackets.
Page 95
Wiring/Installation
Figure 27
Tighten securely
Hexagon socket head cap screw (M3 x 12)
Insert Intermediate Bracket into One-touch M6 Bracket (One-touch M8 Bracket).
Figure 28
3. Mount One-touch M6 Brackets (or M8 Brackets) to the aluminum profile according to the position
where the sensor is mounted. The positions of One-touch M6 Brackets (or M8 Brackets) mounted to the emitter and receiver must be aligned with each other. To mount Brackets to the aluminum profile, insert a T-slide nut into the profile in advance with the recommended tightening torque of 11.0 N•m. The T-slide nut is user provided. Using the T-slide nut makes the mounting work easier.
One-touch M6 (M8) Bracket
T-slide nut (Optional)
4. The positions of Intermediate Brackets mounted to the emitter and receiver must be aligned with each
other. Tighten the hexagon socket head cap screws (M3 x 12) of Intermediate Bracket (1) to secure the sensor. (Figure 28) Insert the Intermediate Bracket, which has been mounted at the bottom of the sensor, into the One­touch M6 Bracket (or One-touch M8 Bracket) mounted to the aluminum profile. (Figure 28) Tighten the hexagon socket head cap screws(M3 x 12) with the tightening torque at 0.54 N•m (recommended).
Chapter3 Mounting
F3SJ-E/B
User’s Manual
E
79
Page 96
Wiring/Installation
Figure 29
Tapping position
Intermediate Bracket
One-touch M6 Bracket (One-touch M8 Bracket)
5. Slide the Intermediate Bracket mounted at the top of the sensor to insert it into the One-touch M6
Bracket (or One-touch M8 Bracket) mounted to the aluminum profile, and then tighten the hexagon socket head cap screws (M3 x 12) on Intermediate Bracket (1) to secure the sensor. (Figure 29) Tighten the hexagon socket head cap screws (M3 x 12) with the torque at 0.54 N•m (recommended).
Slide the Intermediate Bracket and insert it.
Tighten securely
Chapter3 Mounting
Hexagon socket head cap screw (M3 x 12)
Tap the Intermediate Bracket lightly with plastic hammer to the One-touch M6 Bracket (or One-touch M8 Bracket) to maintain stable mounting state. Do not tap areas other than indicated in the figure.
F3SJ-E/B
80
User’s Manual
Page 97
Wiring/Installation
TOP indicator
(Blue)
STB indicator
(Green)
BTM indicator
(Blue)
Emitter Receiver
EMITTER
RECEIVER
Figure 30 Figure 31
Tighten securely
Tighten securely
Tighten securely
Enlargement
Hexagon socket head cap screw (M3 x 18)
Figure 32
6. Turn ON the sensor to perform beam alignment.
Move the emitter from side to side (Figure 30) to align it to a center position where the stable-state indicator (STB) is turned ON while checking the top beam state and bottom beam state with the top­beam-state indicator (TOP) and bottom-beam-state indicator (BTM). (Figure 31) Next, move the receiver from side to side (Figure 30) to align it to a center position where the stable-
state indicator (STB) is turned ON. (Figure 31)
Chapter3 Mounting
- Confirm that there is no interrupting object in the detection zone before adjusting beams.
- If the stable-state indicator (STB) does not turn ON despite performing alignment, check if the mounting surfaces of the emitter/receiver are parallel, and if the mounting height of the emitter/receiver is appropriate. Using optional Laser Alignment Kit (F39-PTJ) makes alignment easier.
7.
Tighten two hexagon socket head cap screws (M3 x 18) on Intermediate Bracket (3) to prevent rotation. (Figure 32) Tighten the hexagon socket head cap screws (M3 x 18) with the torque at 0.54 N•m (recommended).
Securing the sensor with a torque that significantly exceeds the recommended value may result in failure.
Mounting is complete.
F3SJ-E/B
User’s Manual
E
81
Page 98
Wiring/Installation

Wiring

Wiring Precautions

Apply double or enhanced insulation from hazardous voltage to all input and output lines. Failure to do so may result in electric shock.
Chapter3 Wiring
Connect the load between the output and 0 V line (PNP output). Connecting the load between the output and +24 V line will result in a dangerous condition because operation is reversed to "ON when blocked".
Do not short-circuit the output line to the +24 V line. Otherwise, the output is always ON. Also, the 0 V of the power supply must be grounded so that output does not turn ON due to grounding of the output line.
Configure the system by using the optimal number of safety outputs that satisfy the requirements of the necessary safety category.
Do not connect each line of F3SJ-E/B to a DC power supply higher than 24 V+20%. Also, do not connect to an AC power supply. Failure to do so may result in electric shock or breakdown of the device.
F3SJ-E/B
Receiver
Brown
Black, White
Load
Blue
+24 V
F3SJ-E/B
Receiver
0 V
Brown
Black, White
Blue
+24 V
Load
0 V
82
F3SJ-E/B
User’s Manual
Page 99

Power Supply Unit

For the F3SJ-E/B to comply with IEC 61496-1 and UL 508, the DC power supply unit must satisfy all of the following conditions:
•Must be within the rated power voltage (24 VDC±20%)
•Must have tolerance against total rated current of devices if it is connected to multiple devices
•Must comply with EMC directives (industrial environment)
•Double or enhanced insulation must be applied between the primary and secondary circuits
•Automatic recovery of overcurrent protection characteristics
•Output holding time must be 20 ms or longer
•Must satisfy output characteristic requirements for class 2 circuit or limited voltage current circuit defined by UL 508 (Refer to remarks)
•Must comply with laws and regulations, regarding EMC and electrical equipment safety, of the country or region where the F3SJ-E/B is used (Ex: In EU, the power supply must comply to the EMC Directive and the Low Voltage Directive.)
Wiring/Installation
Chapter3 Wiring
(Remarks) To prevent a fire, the secondary circuit of the power supply must satisfy either of the following conditions in accordance with UL 508:
•As with secondary winding of isolation transformer, there must be a limited current voltage circuit to which isolated power supply provides power, and the "current is limited to 8 A max. (including short­circuit)" or "circuit protection such as a fuse is used to limit the current, which has a rating of 4.2 A max." (24 VDC power supply). Recommended power supply: OMRON S8VS (30 W, 60 W) These products are approved by UL listing (UL 508, class 2 power supply), CE marking compatible (EMC/Low Voltage Directive).
•Class 2 power supply unit complying with UL 1310, or a circuit using class 2 transformer complying with UL 1585 as a power supply.
F3SJ-E/B
User’s Manual
E
83
Page 100
Chapter3 Wiring
Insulated vinyl round cable dia. 6.6, shielded 8-wire (4-pair) (Cross section of conductor: 0.3mm
2
/insulator diameter: dia. 1.15mm)
dia.15
39.5
L
M12 IP67 connector
(Unit: mm)
Wiring/Installation

Wiring Method (Easy Type)

Directly wire the single-ended cable that is routed from the sensor.
<F3SJ cable> (The figure shown below is the cable for the emitter.)
Insulated vinyl round cord dia. 6 Emitter: 5-wire, Receiver: 6-wire (Cross section of conductor: 0.15mm
To extend the cable, the following specifications must be satisfied.
<Extension cable>
Refer to "<Extension cable>" on page 87.
2
/ Insulator diameter: 1mm)

Wiring Method (Basic Type)

Perform wiring according to the following procedure.
1. Connect an emitter cable (F39-JD-L, gray, sold separately) to the emitter's connection cable (gray).
2. Connect a receiver cable (F39-JD-D, black, sold separately) to the receiver's connection cable
(black).
3. Connect the 0 V line of the power supply directly to the protective earth (PE).
Single-ended connector cable (F39-JDA, sold separately)
F3SJ-E/B
84
User’s Manual
Set model
name
F39-JD3A F39-JD3A-L Gray cable F39-JD3A-D Black cable 3000
F39-JD7A F39-JD7A-L F39-JD7A-D 7000
F39-JD10A F39-JD10A-L F39-JD10A-D 10000
F39-JD15A F39-JD15A-L F39-JD15A-D 15000
F39-JD20A F39-JD20A-L F39-JD20A-D 20000
Emitter cable Receiver cable L (mm)
Loading...