OMRON E5CN-H, E5AN-H, E5EN-H User Manual

Page 1
SUB1 SUB2 SUB3
HA
OUT1
OUT2
STOP
CWM
MANU
E5CN-H
E5CN-H
E5CN-H
E5AN-H
E5AN-H
E5AN-H
E5EN-H
E5EN-H
E5EN-H
Digital Controllers
E5CN-H
PF
E5AN-H
A/M
HA
OUT1
OUT2
STOP
RSP
MANU
CMW
PV
SV
MV
Ir
SUB1
SUB2
HA
SUB3
RSP
STOPOUT1
CMWOUT2
E5EN-H
MANU
PV
SV
MV
PF
A/M
Ir
Cat. No. H157-E1-08
User's Manual
Advanced Type
Page 2
Page 3
E5CN-H E5AN-H E5EN-H Digital Controllers
User’s Manual
Advanced Type
Revised September 2022
Page 4
iv
Page 5

Preface

© OMRON, 2008-2022
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of OMRON.
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is con­stantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication.
The E5CN-H, E5AN-H, and E5EN-H are Digital Controllers. The main functions and characteristics of these Digital Controllers are as follows:
This manual describes the E5CN-H, E5AN-H, and E5EN-H. Read this manual thoroughly and be sure you understand it before attempting to use the Digital Controller and use the Digital Controller correctly according to the information provided. Keep this manual in a safe place for easy reference. Refer to the following manual for further information on communications: E5CN-H/E5AN-H/E5EN-H Digital Control- lers Communications Manual Advanced Type (Cat. No. H159).
• Use the universal inputs to input from thermocouples or temperature­resistance thermometers, or to input analog voltage or analog current inputs.
• Either standard or heating/cooling control can be performed.
• Both auto-tuning and self-tuning are supported.
• Event inputs can be used to switch banks, switch between RUN and STOP status, switch between automatic and manual operation, start/reset the simple program function, and perform other operations.
• Heater burnout detection, heater short (HS) alarms, and heater overcur­rent (OC) functions are supported. (Applicable to E5CN-H, E5AN-H, and E5EN-H models with heater burnout detection function.)
• Communications are supported. (Applicable to E5CN-H, E5AN-H, and E5EN-H models with communications.)
• User calibration of the sensor input is supported.
• User calibration of transfer output is supported. (Applicable to E5CN-H, E5AN-H, and E5EN-H models with transfer outputs.)
• Use position-proportional control. (Applicable to the E5AN-H and E5EN­H.)
• Use a remote SP input (Applicable to the E5AN-H and E5EN-H.)
• The structure is waterproof (IP66).
• Conforms to UL, CSA, and IEC safety standards and EMC Directive.
• The PV display color can be switched to make process status easy to understand at a glance.

Visual Aids

The following headings appear in the left column of the manual to help you locate different types of information.
Note Indicates information of particular interest for efficient and convenient opera-
tion of the product.
1,2,3... 1. Indicates lists of one sort or another, such as procedures, checklists, etc.
v
Page 6

Terms and Conditions Agreement

Warranty, Limitations of Liability

Warranties
● Exclusive Warranty Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron disclaims all other warranties, express or implied.
● Limitations OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT NON-INFRINGEMENT, MERCHANTABILITY OR FIT­NESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE PROD­UCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the Products or otherwise of any intel­lectual property right.
● Buyer Remedy Omron’s sole obligation hereunder shall be, at Omron’s election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty, repair, indemnity or any other claims or expenses regarding the Products unless Omron’s analysis confirms that the Products were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate modification. Return of any Products by Buyer must be approved in writing by Omron before ship­ment. Omron Companies shall not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or elec­tronic components, circuits, system assemblies or any other materials or sub­stances or environments. Any advice, recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above warranty.
Limitation on Liability; Etc
vi
See http://www.omron.com/global/ or contact your Omron representative for published information.
OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.
Page 7

Application Considerations

Suitability of Use Omron Companies shall not be responsible for conformity with any standards,
codes or regulations which apply to the combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will pro­vide applicable third party certification documents identifying ratings and limi­tations of use which apply to the Product. This information by itself is not sufficient for a complete determination of the suitability of the Product in com­bination with the end product, machine, system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the par­ticular Product with respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT(S) IS PROP­ERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
Programmable Products
Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence thereof.

Disclaimers

Performance Data Data presented in Omron Company websites, catalogs and other materials is
provided as a guide for the user in determining suitability and does not consti­tute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate it to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.
Change in Specifications
Errors and Omissions Information presented by Omron Companies has been checked and is
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice to change part numbers when published ratings or features are changed, or when significant construc­tion changes are made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers may be assigned to fix or establish key specifications for your application. Please con­sult with your Omron’s representative at any time to confirm actual specifica­tions of purchased Product.
believed to be accurate; however, no responsibility is assumed for clerical, typographical or proofreading errors or omissions.
vii
Page 8
Definition of Precautionary Information
The following notation is used in this manual to provide precautions required to ensure safe usage of the product.
The safety precautions that are provided are extremely important to safety. Always read and heed the information provided in all safety precautions.
The following notation is used.
Indicates a potentially hazardous situation which, if not
CAUTION
avoided, is likely to result in minor or moderate injury or in property damage.
Symbols
Symbol Meaning
General Caution
Indicates non-specific general cautions, warnings, and
Caution
dangers.
Electrical Shock Caution
Indicates possibility of electric shock under specific conditions.
Prohibition
Mandatory Caution
General Prohibition
Indicates non-specific general prohibitions.
General Caution
Indicates non-specific general cautions, warnings, and dangers.
viii
Page 9

Safety Precautions

Do not touch the terminals while power is being supplied. Doing so may occasionally result in minor injury due to electric shock.
Do not allow pieces of metal, wire clippings, or fine metallic shav­ings or filings from installation to enter the product. Doing so may occasionally result in electric shock, fire, or malfunction.
Do not use the product where subject to flammable or explosive gas. Otherwise, minor injury from explosion may occasionally occur.
Never disassemble, modify, or repair the product or touch any of the internal parts. Minor electric shock, fire, or malfunction may occasionally occur.
CAUTION - Risk of Fire and Electric Shock a) This product is UL listed as Open Type Process Control
Equipment. It must be mounted in an enclosure that does not allow fire to escape externally.
b) When using more than one shutoff switch, always turn OFF all
the shutoff switches to ensure that no power is being supplied
before servicing the product. c) Signal inputs are SELV, limited energy. (See note 1.) d) Caution: To reduce the risk of fire or electric shock, do not
interconnect the outputs of different Class 2 circuits. (See note
2.)
CAUTION
If the output relays are used past their life expectancy, contact fusing or burning may occasionally occur. Always consider the application conditions and use the output relays within their rated load and electrical life expectancy. The life expectancy of output relays varies considerably with the output load and switching conditions.
Note 1: An SELV circuit is one separated from the power supply with double
insulation or reinforced insulation, that does not exceed 30 V r.m.s.
and 42.4 V peak or 60 VDC.
Note 2: A class 2 power supply is one tested and certified by UL as having
the current and voltage of the secondary output restricted to specific
levels.
ix
Page 10
CAUTION
Tighten the terminal screws to between 0.74 and 0.90 N·m. Loose screws may occasionally result in fire.
Set the parameters of the product so that they are suitable for the system being controlled. If they are not suitable, unexpected operation may occasionally result in property damage or accidents.
A malfunction in the Digital Controller may occasionally make control operations impossible or prevent alarm outputs, resulting in property damage. To maintain safety in the event of malfunction of the Digital Controller, take appropriate safety measures, such as installing a monitoring device on a separate line.
When inserting the body of the Digital Controller into the case, confirm that the hooks on the top and bottom are securely engaged with the case. If the body of the Digital Controller is not inserted properly, faulty contact in the terminal section or reduced water resistance may occasionally result in fire or malfunction.
When connecting the Control Output Unit to the socket, press it in until there is no gap between the Control Output Unit and the socket. Otherwise contact faults in the connector pins may occa­sionally result in fire or malfunction.
x
Page 11
Security Measures
Anti-virus protection
Install the latest commercial-quality antivirus software on the computer connected to the control/monitor system and maintain to keep the software up-to-date.
Security measures to prevent unauthorized access
Take the following measures to prevent unauthorized access to our products.
• Install physical controls so that only authorized personnel can
access control/monitor systems and equipment.
• Reduce connections to control/monitor systems and equipment
via networks to prevent access from untrusted devices.
• Install firewalls to shut down unused communications ports and
limit communications hosts and isolate control/monitor systems
and equipment from the IT network.
• Use a virtual private network (VPN) for remote access to con-
trol/monitor systems and equipment.
• Scan virus to ensure safety of SD cards or other external stor-
ages before connecting them to control/monitor systems and
equipment.
Take adequate security measures against DDoS attacks (Distributed Denial of Service attacks), computer viruses and other technologically harmful programs, unauthorized access and other possible attacks before using this product.
Data input and output protection
Validate backups and ranges to cope with unintentional modification of input/output data to control/monitor systems and equipment.
• Checking the scope of data
• Checking validity of backups and preparing data for restore in
case of falsification and abnormalities
• Safety design, such as emergency shutdown, in case of data
tampering and abnormalities
Data recovery
Backup data and keep the data up-to-date periodically to prepare for data loss.
xi
Page 12

Precautions for Safe Use

Be sure to observe the following precautions to prevent operation failure, malfunction, or adverse affects on the performance and functions of the product. Not doing so may occasionally result in unexpected events.
1) The product is designed for indoor use only. Do not use the product outdoors or in any of the following locations.
• Places directly subject to heat radiated from heating equipment.
• Places subject to splashing liquid or oil atmosphere.
• Places subject to direct sunlight.
• Places subject to dust or corrosive gas (in particular, sulfide gas and ammonia gas).
• Places subject to intense temperature change.
• Places subject to icing and condensation.
• Places subject to vibration and large shocks.
2) Use and store the Digital Controller within the rated ambient temperature and humidity. Gang-mounting two or more Digital Controllers, or mounting Digital Controllers above each other may
cause heat to build up inside the Digital Controllers, which will shorten their service life. In such a case, use forced cooling by fans or other means of air ventilation to cool down the Digital Controllers.
3) To allow heat to escape, do not block the area around the product. Do not block the ventilation holes on the product.
4) Be sure to wire properly with correct polarity of terminals.
5) Use specified size (M3.5, width 7.2 mm or less) crimped terminals for wiring. To connect bare wires, use stranded or solid copper wires with a gage of AWG24 to AWG14 (equal to cross-sectional areas of 0.205
2
to 2.081 mm terminals can be inserted into a single terminal.
6) Do not wire the terminals which are not used.
7) To avoid inductive noise, keep the wiring for the Digital Controller's terminal block away from power cables carry high voltages or large currents. Also, do not wire power lines together with or parallel to Digital Controller wiring. Using shielded cables and using separate conduits or ducts is recommended. Attach a surge suppressor or noise filter to peripheral devices that generate noise (in particular, motors, transformers, solenoids, magnetic coils or other equipment that have an inductance component). When a noise filter is used at the power supply, first check the voltage or current, and attach the noise filter as close as possible to the Digital controller. Allow as much space as possible between the Digital Controller and devices that generate powerful high frequencies (high-frequency welders, high-frequency sewing machines, etc.) or surge.
8) Use this product within the rated load and power supply.
9) Make sure that the rated voltage is attained within two seconds of turning ON the power using a switch or relay contact. If the voltage is applied gradually, the power may not be reset or output malfunctions may occur.
10) Make sure that the Digital Controller has 30 minutes or more to warm up after turning ON the power before starting actual control operations to ensure the correct temperature display.
11) When using self-tuning, turn ON power for the load (e.g., heater) at the same time as or before supplying power to the Digital Controller. If power is turned ON for the Digital Controller before turning ON power for the load, self-tuning will not be performed properly and optimum control will not be achieved.
12) A switch or circuit breaker should be provided close to this unit. The switch or circuit breaker should be within easy reach of the operator, and must be marked as a disconnecting means for this unit.
13) Always turn OFF the power supply before pulling out the interior of the product, and never touch nor apply shock to the terminals or electronic components. When inserting the interior of the product, do not allow the electronic components to touch the case.
14) Do not use paint thinner or similar chemical to clean with. Use standard grade alcohol.
). (The stripping length is 5 to 6 mm.) Up to two wires of same size and type, or two crimp
xii
Page 13
15) Design system (control panel, etc.) considering the 2 second of delay that the controller’s output to be set after power ON.
16) The output may turn OFF when shifting to certain levels. Take this into consideration when performing control.
17) The number of EEPROM write operations is limited. Therefore, use RAM write mode when frequently overwriting data during communications or other operations.
18) Always touch a grounded piece of metal before touching the Digital Controller to discharge static electricity from your body.
19) Do not remove the terminal block. Doing so may result in failure or malfunction.
20) Control outputs that are voltage outputs are not isolated from the internal circuits. When using a grounded thermocouple, do not connect any of the control output terminals to ground. (Doing so may result in an unwanted circuit path, causing error in the measured temperature.)
21) When replacing the body of the Digital Controller, check the condition of the terminals. If corroded terminals are used, contact failure in the terminals may cause the temperature inside the Digital Controller to increase, possibly resulting in fire. If the terminals are corroded, replace the case as well.
22) Use suitable tools when taking the Digital Controller apart for disposal. Sharp parts inside the Digital Controller may cause injury.
23) Check the specifications of the Control Output Unit and assemble it correctly.
24) When mounting the Control Output Unit, read and follow all relevant information in the product catalogs and manuals.
25) When applying Lloyd's standards, install the Digital Controller according to the requirements given in Shipping Standards.
Service Life
Use the Digital Controller within the following temperature and humidity ranges: Temperature: −10 to 55°C (with no icing or condensation), Humidity: 25% to 85%
If the Controller is installed inside a control board, the ambient temperature must be kept to under 55°C, including the temperature around the Controller.
The service life of electronic devices like Digital Controllers is determined not only by the number of times the relay is switched but also by the service life of internal electronic components. Component service life is affected by the ambient temperature: the higher the temperature, the shorter the service life and, the lower the temperature, the longer the service life. Therefore, the service life can be extended by lowering the temperature of the Digital Controller.
When two or more Digital Controllers are mounted horizontally close to each other or vertically next to one another, the internal temperature will increase due to heat radiated by the Digital Controllers and the service life will decrease. In such a case, use forced cooling by fans or other means of air ventila­tion to cool down the Digital Controllers. When providing forced cooling, however, be careful not to cool down the terminals sections alone to avoid measurement errors.
Ambient Noise
To avoid inductive noise, keep the wiring for the Digital Controller's terminal block wiring away from power cables carrying high voltages or large currents. Also, do not wire power lines together with or parallel to Digital Controller wiring. Using shielded cables and using separate conduits or ducts is rec­ommended. Attach a surge suppressor or noise filter to peripheral devices that generate noise (in particular, motors, transformers, solenoids, magnetic coils or other equipment that have an inductance compo­nent). When a noise filter is used at the power supply, first check the voltage or current, and attach the noise filter as close as possible to the Digital Controller. Allow as much space as possible between the Digital Controller and devices that generate powerful high frequencies (high-frequency welders, high-frequency sewing machines, etc.) or surge.
xiii
Page 14
Ensuring Measurement Accuracy
When extending or connecting the thermocouple lead wire, be sure to use compensating wires that match the thermocouple types.
When extending or connecting the lead wire of the platinum resistance thermometer, be sure to use wires that have low resistance and keep the resistance of the three lead wires the same.
Mount the Digital Controller so that it is horizontally level.
If the measurement accuracy is low, check to see if input shift has been set correctly.
Waterproofing
The degree of protection is as shown below. Sections without any specification on their degree of pro­tection or those with IP0 are not waterproof.
Front panel: IP66 Rear case: IP20, Terminal section: IP00
xiv
Page 15

Precautions for Operation

1) It takes approximately two seconds for the outputs to turn ON from after the power supply is turned ON. Due consideration must be given to this time when incorporating Digital Controllers into a control panel or similar device.
2) Make sure that the Digital Controller has 30 minutes or more to warm up after turning ON the power before starting actual control operations to ensure the correct temperature display.
3) When executing self-tuning, turn ON power for the load (e.g., heater) at the same time as or before supplying power to the Digital Controller. If power is turned ON for the Digital Controller before turning ON power for the load, self-tuning will not be performed properly and optimum control will not be achieved. When starting operation after the Digital Controller has warmed up, turn OFF the power and then turn it ON again at the same time as turning ON power for the load. (Instead of turning the Digital Controller OFF and ON again, switching from STOP mode to RUN mode can also be used.)
4) Avoid using the Controller in places near a radio, television set, or wireless installing. The Controller may cause radio disturbance for these devices.

Shipping Standards

The E5N-H Digital Controllers comply with Lloyd's standards. When applying the standards, the following installation and wiring requirements must be met in the application.
Application Conditions
1) Installation Location
The E5N-H Digital Controllers comply with installation categories ENV1 and ENV2 of Lloyd's stan­dards. They must therefore be installed in a location equipped with air conditioning. They cannot be used on the bridge or decks, or in a location subject to strong vibration.
2) Wiring Conditions
Install the recommended ferrite core and wrap the line around it three turns for the applicable lines (e.g., power supply cable line and signal lines) of the models listed in the following table. (See illustra­tions.) Install the ferrite cores as close to the terminal block of the E5N-H as possible. (As a guide­line, the ferrite core should be within 10 cm of the terminal block.)
Lines Requiring Ferrite Cores
Model Signal line or power supply line onto which a ferrite core is installed
E5CN, E5CN-U, or E5CN-H Input power supply line
E5EN, E5AN, E5EN-H, or E5AN-H
Recommended Ferrite Core
Manufacturer Seiwa Electric Manufacturing Co., Ltd.
Model E04RA310190100
Input power supply line and I/O lines (control outputs 1 and 2, communica­tions, event inputs EV1, EV2, EV3, and EV4, transfer output, and external power supply (not provided on Advanced-type Digital Controllers (E5
N-H)))
xv
Page 16
Ferrite Core Connection Examples
A
B
+
+
−
+
−
−
+
−
●
B
●
V
DO NOT USE
DO NOT USE
DO NOT USE
mA
●
6
7
8
9
10
11
12
13
14
15
1
3
2
4
5
Input power supply
Auxiliary output 1
Auxiliary output 2
Control output 1
Auxiliary outputs (relay outputs)
Analog input
TC/Pt universal input
Power supply
AC/DC
3 turns
1
2
3
4
5
6
7
8
9
10
21
22
23
24
25
26
27
28
29
30
21
22
23
24
25
26
27
28
29
30
21
22
23
24
25
26
27
28
29
30
11
12
13
14
15
16
17
18
19
20
EV4
EV3
+
−
+
−
+
−
+
−
+
−
−
+
−
+
DO NOT USE
DO NOT USE
DO NOT USE
B
V
CT2
CT1
EV1
EV2
CT1/CT2
DO NOT USE
DO NOT USE
DO NOT USE
B
A
DO NOT USE
DO NOT USE
DO NOT USE
B (+) A (−)
DO NOT USE B (+) A (−)
11
12
13
21
22
11
12
13
21
22
RS-485RS-232C
SD
RD
SG
DO NOT USE
DO NOT USE
mA
Input power supply
Control output 1
Auxiliary output 3
Auxiliary output 2
Auxiliary output 1
Transfer output
4 to 20 mA DC (Load: 600 Ω max.)
Communications
Event Inputs*
Control Output 2
Control Output 2
External Power Supply
External power supply 12 VDC, 20 mA
Connected to communications or event inputs 1 and 2.
Connected to control output 2 or external power supply.
Power supply
Connected to control output 1.
Connected to event inputs 3 and 4.*
Connected to transfer output.
Analog input
TC/Pt universal input
AC/DC
3 turns
3 turns
3 turns
3 turns
3 turns
3 turns
* EV3 and EV4 are assigned to event inputs in Controllers with two event inputs.
1. E5CN/E5CN-H
2. E5AN/E5EN/E5AN-H/E5EN-H
xvi
Page 17

Preparations for Use

Be sure to thoroughly read and understand the manual provided with the product, and check the fol­lowing points.
Timing Check point Details
Purchasing the prod­uct
Setting the Unit Product installation loca-
Wiring Terminal wiring Do not subject the terminal screws to excessive stress (force) when
Operating environ­ment
Product appearance After purchase, check that the product and packaging are not dented or
Product model and speci­fications
tion
Power supply inputs Wire the power supply inputs correctly. Incorrect wiring will result in
Ambient temperature The ambient operating temperature for the product is −10 to 55°C (with
Vibration and shock Check whether the standards related to shock and vibration are satis-
Foreign particles Install the product in a location that is not subject to liquid or foreign
otherwise damaged. Damaged internal parts may prevent optimum control.
Make sure that the purchased product meets the required specifica­tions.
Provide sufficient space around the product for heat dissipation. Do not block the vents on the product.
tightening them. Make sure that there are no loose screws after tightening terminal
screws to the specified torque of 0.74 to 0.90 N·m.
Be sure to confirm the polarity for each terminal before wiring the termi­nal block and connectors.
damage to the internal circuits.
no condensation or icing). To extend the service life of the product, install it in a location with an ambient temperature as low as possible. In locations exposed to high temperatures, if necessary, cool the products using a fan or other cooling method.
fied at the installation environment. (Install the product in locations where the conductors will not be subject to vibration or shock.)
particles entering the product.
xvii
Page 18

Conventions Used in This Manual

Meanings of Abbreviations

The following abbreviations are used in parameter names, figures and in text explanations. These abbreviations mean the following:
Symbol Term
PV Process value
SP Set point
SV Set value
AT Auto-tuning
ST Self-tuning
HB Heater burnout
HS Heater short (See note 1.)
OC Heater overcurrent
LBA Loop burnout alarm
EU Engineering unit (See note 2.)
RSP Remote SP
LSP Local SP
Note: (1) A heater short indicates that the heater remains ON even when the control output from the Digital
Controller is OFF because the SSR has failed or for any other reason.
(2) “EU” stands for Engineering Unit. EU is used as the minimum unit for engineering units such as °C,
m, and g. The size of EU varies according to the input type. For example, when the input temperature setting range is –200 to +1300°C, 1 EU is 1°C, and when the input temperature setting range is –20.0 to +500.0°C, 1 EU is 0.1°C. For analog inputs, the size of EU varies according to the decimal point position of the scaling setting, and 1 EU becomes the minimum scaling unit.
xviii
Page 19

How to Read Display Symbols

ABCDEFG
H
IJKL
M
NO
P
Q
RS T U VWX Y Z
abcdefghijklm
nopqrstuvwxyz
The following tables show the correspondence between the symbols displayed on the displays and alphabet characters. The default is for 11-segment displays.
The Character Select parameter in the advanced function setting level can be turned OFF to display the following 7-segment characters.
ABCDEFGH I JKLM
NOPQRSTUVWXYZ
xix
Page 20
xx
Page 21

TABLE OF CONTENTS

SECTION 1
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1-1 Names of Parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1-2 I/O Configuration and Main Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1-3 Setting Level Configuration and Key Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
1-4 Communications Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
1-5 Isolation/Insulation Block Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
SECTION 2
Preparations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2-1 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
2-2 Wiring Terminals. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
2-3 Using the Support Software Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
2-4 Using Infrared Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
SECTION 3
Basic Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
3-1 Initial Setting Examples. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
3-2 Setting the Input Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
3-3 Selecting the Temperature Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
3-4 Selecting PID Control or ON/OFF Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
3-5 Setting Output Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
3-6 Setting the Set Point (SP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
3-7 Using ON/OFF Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57
3-8 Determining PID Constants (AT, ST, Manual Setup). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
3-9 Alarm Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
3-10 Using Heater Burnout, Heater Short, and Heater Overcurrent Alarms . . . . . . . . . . . . . . . . . 71
3-11 Setting the No. 3 Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
SECTION 4
Applications Operations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
4-1 Shifting Input Values. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
4-2 Alarm Hysteresis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
4-3 Setting Scaling Upper and Lower Limits for Analog Inputs . . . . . . . . . . . . . . . . . . . . . . . . . 92
4-4 Executing Heating/Cooling Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
4-5 Using Event Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
4-6 Setting the SP Upper and Lower Limit Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
4-7 Using the SP Ramp Function to Limit the SP Change Rate . . . . . . . . . . . . . . . . . . . . . . . . . 102
4-8 Moving to the Advanced Function Setting Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
4-9 Using the Key Protect Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .106
4-10 PV Change Color. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
4-11 Alarm Delays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
4-12 Loop Burnout Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
4-13 Performing Manual Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .118
xix
Page 22
TABLE OF CONTENTS
4-14 Using the Transfer Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
4-15 Using Banks and PID Sets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .128
4-16 Using the Simple Program Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
4-17 Output Adjustment Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
4-18 Using the Extraction of Square Root Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
4-19 Setting the Width of MV Variation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
4-20 Setting the PF Key . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
4-21 Counting Control Output ON/OFF Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
4-22 Displaying PV/SV Status. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
4-23 Using a Remote SP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154
4-24 Position-proportional Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .156
4-25 Logic Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
SECTION 5
Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167
5-1 Conventions Used in this Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 168
5-2 Protect Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169
5-3 Operation Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
5-4 Adjustment Level. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 188
5-5 Bank Setting Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 207
5-6 PID Setting Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 214
5-7 Monitor/Setting Item Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .218
5-8 Manual Control Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219
5-9 Initial Setting Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 221
5-10 Advanced Function Setting Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 240
5-11 Communications Setting Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 279
SECTION 6
CALIBRATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 281
6-1 Parameter Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 282
6-2 User Calibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 283
6-3 Thermocouple Calibration (Thermocouple/Resistance Thermometer Input) . . . . . . . . . . . . 283
6-4 Platinum Resistance Thermometer Calibration
(Thermocouple/Resistance Thermometer Input). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 287
6-5 Calibrating Analog Input (Analog Input) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 288
6-6 Calibrating the Transfer Output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 290
6-7 Checking Indication Accuracy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 292
Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 295
Index. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 341
Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 349
xx
Page 23

About this Manual:

!WARNING Failure to read and understand the information provided in this manual may result in per-
sonal injury or death, damage to the product, or product failure. Please read each section in its entirety and be sure you understand the information provided in the section and related sections before attempting any of the procedures or operations given.
This manual describes the E5CN/AN/EN-H Digital Controllers and includes the sections described below.
Please read this manual carefully and be sure you understand the information provided before attempting to set up or operate an E5CN/AN/EN-H Digital Controller.
• Overview
Section 1 introduces the features, components, and main specifications of the E5CN/AN/EN-H Digital Controllers.
•Setup
Section 2 describes the work required to prepare the E5CN/AN/EN-H Digital Controllers for operation, including installation and wiring.
• Basic Operations
Section 3 describes the basic operation of the E5CN/AN/EN-H Digital Controllers, including key oper­ations to set parameters and descriptions of display elements based on specific control examples.
Section 5 describes the individual parameters used to set up, control, and monitor operation.
• Operations for Applications
Section 4 describes scaling, the SP ramp function, and other special functions that can be used to make the most of the functionality of the E5CN/AN/EN-H Digital Controllers.
Section 5 describes the individual parameters used to setup, control, and monitor operation.
• User Calibration
Section 6 describes how the user can calibrate the E5CN/AN/EN-H Digital Controllers.
• Appendix
The Appendix provides information for easy reference, including lists of parameters and settings.
xxi
Page 24
xxii
Page 25
SECTION 1
Introduction
This section introduces the features, components, and main specifications of the E5CN-H, E5AN-H, and E5EN-H Digital Controllers.
1-1 Names of Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1-1-1 Front Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1-1-2 Explanation of Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1-1-3 Using the Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1-2 I/O Configuration and Main Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1-2-1 I/O Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1-2-2 Main Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1-3 Setting Level Configuration and Key Operations . . . . . . . . . . . . . . . . . . . . . . 11
1-3-1 Selecting Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
1-3-2 Saving Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
1-4 Communications Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
1-5 Isolation/Insulation Block Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
1
Page 26
Names of Parts Section 1-1

1-1 Names of Parts

1-1-1 Front Panel

E5CN-H
Temperature unit
No. 1 display
Operation indicators
No. 2 display
Level Key
E5AN-H
Mode Key
Temperature unit
Operation indicators
PF (Function (Auto/ Manual)) Key
Level Key
Down Key
Mode Key
Up Key
Down Key
No. 1 display
No. 2 display
No. 3 display
Up Key
Infrared Communications Light Receiver
Ir
2
Page 27
Names of Parts Section 1-1
Infrared Communications Light Receiver
No. 1 display
No. 2 display
Mode Key
Up Key
Level Key
Down Key
Temperature unit
Operation indicators
Operation indicators
No. 3 display
Ir
PF (Function (Auto/ Manual)) Key
E5EN-H

1-1-2 Explanation of Indicators

No. 1 Display Displays the process value or parameter name.
Lights for approximately one second during startup.
No. 2 Display Displays the set point, parameter operation read value, or the variable input
value.
Lights for approximately one second during startup.
The SP display will flash during auto-tuning.
No. 3 Display (E5AN/EN-H Only)
Operation Indicators
1,2,3... 1. SUB1 (Sub 1)
Displays MV (valve opening), soak time remain, or bank number.
Lights for approximately one second during startup.
Lights when the function set for the Auxiliary Output 1 Assignment param­eter is ON.
SUB2 (Sub 2) Lights when the function set for the Auxiliary Output 2 Assignment param­eter is ON.
SUB3 (Sub 3) Lights when the function set for the Auxiliary Output 3 Assignment param­eter is ON.
2. HA (Heater Burnout, Heater Short Alarm, Heater Overcurrent Detection Output Display) Lights when a heater burnout, heater short alarm, or heater overcurrent occurs.
3. OUT1 (Control Output 1) Lights when the control output function assigned to control output 1 turns ON. For a current output, however, OFF for a 0% output only. With position-proportional models, OUT1 lights when the "open" output turns ON.
3
Page 28
Names of Parts Section 1-1
OUT2 (Control Output 2) Lights when the control output function assigned to control output 2 turns ON. For a current output, however, OFF for a 0% output only. With position-proportional models, OUT2 lights when the "close" output turns ON.
4. STOP Lights when operation is stopped.
During operation, this indicator lights when operation is stopped by an event or by key input using the RUN/STOP function.
5. CMW (Communications Writing) Lights when communications writing is enabled and is not lit when it is dis­abled.
6. MANU (Manual Mode) Lights when the auto/manual mode is set to manual mode.
7. (Key) Lights when settings change protect is ON (i.e., when the U and D Keys are disabled by protected status.
8. RSP Lights when the SP Mode parameter is set to Remote SP Mode.
Temperature Unit The temperature unit is displayed when parameters are set to display a tem-
perature. The display is determined by the currently set value of the Tempera­ture Unit parameter. c indicates °C and f indicates °F.
This indicator flashes during ST operation. It is OFF when an analog input is set.
Ir Indicates whether infrared communications is enabled. Lights when communi-
cations is enabled. Not lit when infrared communications is disabled.
• Infrared Communications Light Receiver Used when infrared cable is used.

1-1-3 Using the Keys

This section describes the basic functions of the front panel keys.
PF (Function (Auto/ Manual)) Key (E5AN/EN-H Only)
O Key Press this key to move between setting levels. The setting level is selected in
M Key Press this key to change parameters within a setting level.
U Key Each press of this key increments the value displayed on the No. 2 display or
This is a function key. When it is pressed for at least 1 second, the function set in the PF Setting parameter will operate.
Example: When A-M (auto/manual) is selected in the PF Setting parameter (initial value: A-M), the key operates as an auto/manual switch, switching between Auto Mode and Manual Mode. If the key is pressed for more than 1 second (regardless of key release timing), the mode will switch.
the following order: operation level: adjustment level, initial setting level, com­munications setting level.
The parameters can be reversed by holding down the key (moving one per second in reverse order).
advances the setting. Holding the key down speeds up the incrementation.
D Key Each press of this key decrements values displayed on the No. 2 display or
reverses the setting. Holding the key down speeds up the incrementation.
4
Page 29
I/O Configuration and Main Functions Section 1-2
Temperature input or analog input
CT1 input
CT2 input
Event inputs 2 channels
Control section
Control output (heating)
Control output (cooling)
Alarm 2
HB alarm
Alarm 1
Control output 1
Control output 2
HS alarm
OC alarm
Input error
Program end output
Communications function
Heating/cooling
Auxiliary output 1
Auxiliary output 2
Alarm 3
O + M Keys Press these keys to change to the protect level. For details on operations
involving holding these keys down simultaneously, refer to 1-3 Setting Level
Configuration and Key Operations. For details on the protect level, refer to SECTION 5 Parameters.
O + U Keys O + D Keys
To restrict set value changes (in order to prevent accidental or incorrect oper­ations), these key operations require simultaneously pressing the O key along with U or D key. This applies only to the parameter for the password to move to protect level. (Refer to page 172.)

1-2 I/O Configuration and Main Functions

1-2-1 I/O Configuration

E5CN-H
Note Functions can be assigned individually for each output by changing the set
values for the Control Output 1 Assignment, the Control Output 2 Assignment, the Auxiliary Output 1 Assignment, and the Auxiliary Output 2 Assignment parameters in the advanced function setting level.
5
Page 30
I/O Configuration and Main Functions Section 1-2
1 2 3 4 5 6 7
E5CN-@@@M@-@-500
1 2 3 4
E53-@@@@
Model Number Structure
Model Number Legends
Controllers Option Units
1. Type
H: Advanced
2. Control Output 1
R: Relay output Q: Voltage output
(for driving SSR) C: Current output V: Linear voltage output
3. Auxiliary Outputs
2: Two outputs
4. Option 1
M: Option Unit can be mounted.
5. Power Supply Voltage
Blank: 100 to 240 VAC D: 24 VAC/VDC
6. Case Color
Blank: Black W: Silver
7. Terminal Cover
−500: With terminal cover
1. Applicable Controller
CN: E5CN-H or E5CN
2. Function 1
Blank: None Q: Control output 2 (voltage output for
driving SSR) P: Power supply for sensor C: Current output
3. Function 2
Blank: None H: Heater burnout/Heater short/
Heater overcurrent detection (CT1) HH: Heater burnout/Heater short/
Heater overcurrent detection (CT2) B: Two event inputs 03: RS-485 communications H03: Heater burnout/Heater short/
Heater overcurrent detection (CT1)
+ RS-485 communications HB: Heater burnout/Heater short/
Heater overcurrent detection (CT1)
+ Two event inputs HH03: Heater burnout/Heater short/
Heater overcurrent detection (CT2)
+ RS-485 communications H01: Heater burnout/Heater short/
Heater overcurrent detection (CT1)/
RS-232C communications F: Transfer output BF: Two event inputs/Transfer output
4. Version
N2: Available only to models released
after January 2008
6
Page 31
I/O Configuration and Main Functions Section 1-2
Temperature input or analog input
Control section
CT1 input
CT2 input
Event inputs 1 and 2 (2 channels)
Control output (heating)
Control output (cooling)
Alarm 3
Alarm 1
Alarm 2
HB alarm
HS alarm
Input error
Program end output
Communications function
Heating/cooling
Control output 1
Control output 2
Alarm output 1
Alarm output 2
Alarm output 3
OC alarm
Event inputs 3 and 4 (2 channels)
RSP input error
Remote SP input error
E5AN/EN-H
Note Functions can be assigned individually to each output by changing the set val-
ues for the Control Output 1 Assignment, Control Output 2 Assignment, Auxil­iary Output 1 Assignment, Auxiliary Output 2 Assignment, and Auxiliary Output 3 Assignment parameters in the advanced function setting level.
7
Page 32
I/O Configuration and Main Functions Section 1-2
1 2 3 4 5 6 7 8 9 10
11
E5AN/E5EN-@@@@@@@M@-@-500
1
E53-@
Model Number Structure
Model Number Legends
Controllers Option Units
1. Type
H: Advanced
2. Control Mode
Blank: Standard or heating/cooling control P: Position-proportional control
3. Control Output 1
A: Control Output Unit R: Relay output S: SSR output
4. Control Output 2
A: Control Output Unit R: Relay output S: SSR output
5. Auxiliary Outputs
2: Two outputs 3: Three outputs
6. Option 1
Blank: None H: Heater burnout/Heater short/
Heater overcurrent detection (CT1)
HH: Heater burnout/Heater short/
Heater overcurrent detection (CT2)
7. Option 2
B: Two event inputs BF: Event input + Transfer output
8. Option 3
M: Option Unit can be mounted.
9. Power Supply Voltage
Blank: 100 to 240 VAC D: 24 VAC/VDC
10. Case Color
Blank: Black W: Silver
11. Terminal Cover
-500: With Terminal Cover
1. Function
EN01: RS-232C
communications
EN02: RS-422
communications
EN03: RS-485
communications AKB: Event input
Output Units
E53-@@
1 2
1. Control Output
R: Relay output Q: Voltage output
(for driving SSR)
Q3: Voltage output
(for driving SSR) + 24 VDC (NPN)
Q4: Voltage output
(for driving SSR) + 24 VDC (PNP)
C3: Current output +
4 to 20 mA DC
C3D: Current output +
0 to 20 mA DC
V34: Linear voltage output +
0 to 10 VDC
V35: Linear voltage output +
0 to 5 VDC
2. Version
Blank: Available for
E5AN-H/E5EN-H and E5AK/E5EK.
N: Available only for
E5AN-H/E5EN-H.

1-2-2 Main Functions

Input Sensor Types • The following input sensors can be connected.:
8
This section introduces the main E5N-H functions. For details on particular functions and how to use them, refer to SECTION 3 Basic Operation and fol­lowing sections.
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, PLII Platinum resistance thermometer: Pt100, JPt100 Current input: 4 to 20 mA DC, 0 to 20 mA DC Voltage input: 1 to 5 VDC, 0 to 5 V DC, 0 to 10 V DC
Page 33
I/O Configuration and Main Functions Section 1-2
Control Outputs • A control output can be a relay output, voltage output (for driving SSR),
linear voltage output, SSR output, or current output, depending on the model.
• With the E5CN-H2, auxiliary output 2 is used as control output (cooling) when heating/cooling control is selected. (It is also possible to allocate a different output.) Therefore, use auxiliary output 1 if an auxiliary output is required while using heating/cooling control.
Alarms • Set the alarm type and alarm value or the alarm value upper and lower
limits.
• If necessary, a more comprehensive alarm function can be achieved by setting a standby sequence, alarm hysteresis, auxiliary output close in alarm/open in alarm, alarm latch, alarm ON delay, and alarm OFF delay.
• If the Input Error Output parameter is set to ON, the output assigned to alarm 1 function will turn ON when an input error occurs.
• If the Remote SP Input Error Output parameter is set to ON, the output assigned to the alarm 1 function will turn ON when an input error occurs.
Control Adjustment • Optimum PID constants can be set easily by performing AT (auto-tuning)
or ST (self-tuning).
Event Inputs • With the E53-CNBN2 for the E5CN-H (for two event inputs), the
E5AN/EN-HBM-500 for E5AN/EN-H (for two event inputs) or the E5AN/EN-HBM-500 with the E53-AKB for the E5AN/EN-H (for four event inputs), the following functions can be executed using event inputs: switching banks, switching RUN/STOP, switching between automatic and manual operation, starting/resetting the program, inverting direct/reverse operation, switching SP modes, 100% AT execute/cancel, 40% AT exe­cute/cancel, setting change enable/disable, communications writing enable/disable and canceling the alarm latch.
Heater Burnout, HS Alarm, and Heater Overcurrent
Communications Functions
Note (1) CompoWay/F is an integrated general-purpose serial communications
• With the E53-CNHN2 or E53-CNHHN2 for the E5CN-H, or the E5AN/EN-HH-500 or E5AN/EN-HHH-500, the heater burnout detection function, HS alarm function, and heater overcurrent detection function can be used.
• Communications functions utilizing CompoWay/F (See note 1.), SYSWAY (See note 2.), or Modbus (See note 3.) can be used.
RS-485 Interface Use the E53-CN03N2 for the E5CN-H, or the E53-EN03 for the E5AN/ EN-H.
RS-232C Interface Use the E53-CN01N2 for the E5CN-H, or the E53-EN01 for the E5AN/ EN-H.
RS-422 Interface Use the E53-EN02 for the E5AN/EN-H.
l developed by OMRON. It uses commands compliant with the
otoco
pr well-established FINS, together with a consistent frame format on OMRON Programmable Controllers to facilitate communications be­tween personal computers and components.
(2) SYSWAY communications do not support alarm 3.
(3) Modbus is a communications control method conforming to the RTU
Mode of Modbus Protocol. Modbus is a registered trademark of Schneider Electric.
9
Page 34
I/O Configuration and Main Functions Section 1-2
(4) The E5CN-H does not support the RS-422 interface.
Transfer Output A 4 to 20-mA transfer output can be used with the E53-CNFN2 for the
E5CN-H, or the E5AN/EN-HF-500.
Remote SP Inputs Remote SP inputs can be used with the E5AN-H and E5EN-H.
Infrared Communications When Support Software, such as CX-Thermo version 4.00 or later (EST2-2C-
MV4 or later), is used, the personal computer can be connected to the Digital Controller using infrared communications.
10
Page 35
Setting Level Configuration and Key Operations Section 1-3
Start in manual mode.
Press the O Key for at least 3 s while a-m is displayed. (a-m will flash after 1st second.)
25.0
100.0
c
a-m
25.0
100.0
c
Power ON
Manual Control Level
Manual mode
Operation Level
Press the O Key for at least 1 s.
Input password.
Press the O Key less than 1 s.
Press the O Key for at least 3 s. (Display will flash after 1st second.)
Control stops.
Press the O Key for less than 1 s.
Press the O+ M Keys for at least 1 s.
Press the O + M Keys for at least 3 s. (Display will flash after 1st second.)
Protect Level
Control in progress
Level change
Not displayed for some models
Control stopped
Start in automatic mode.
Adjustment Level
Initial Setting Level
Monitor/Setting Item Level
Advanced Function Setting Level
Calibration Level
Press the PF Key for at least 1 s.
Communica­tions Setting Level
Press the O Key less than 1 s.
Press the O Key less than 1 s.
Press the O Key for at least 1 s.
PID Setting Level
Bank Setting Level
Press the O Key less than 1 s.
Note: The time taken to
move to the protect level can be adjusted by changing the “Move to protect level time” setting.

1-3 Setting Level Configuration and Key Operations

Parameters are divided into groups, each called a level. Each of the set val­ues (setting items) in these levels is called a parameter. The parameters on the E5CN/AN/EN-H are divided into the following 9 levels.
When the power is turned ON, all of the display lights for approximately one second.
Note (1) Your can return to the operation level by executing a software reset.
(2) You cannot move to other levels by operating the keys on the front panel
from the calibration level. You must turn OFF the power supply.
(3) From the manual control level, key operations can be used to move to the
operation level only.
Protect level Can be set. ---
Operation level Can be set. ---
Adjustment level Can be set. ---
Bank setting level Can be set. ---
Level Control in progress Control stopped
11
Page 36
Setting Level Configuration and Key Operations Section 1-3
Level Control in progress Control stopped
PID setting level Can be set. ---
Manual control level Can be set. ---
Monitor/setting item level Can be set. ---
Initial setting level --- Can be set.
Advanced function setting level --- Can be set.
Calibration level --- Can be set.
Communications setting level --- Can be set.
Of these levels, the initial setting level, communications setting level, advanced function setting level, and calibration level can be used only when control is stopped. Control outputs are stopped when any of these four levels is selected.
(4) When the PF Setting is set to A-M in models with a PF Key (E5AN/EN-H)
(5) When the PF Setting is set to PFDP in models with a PF Key (E5AN/EN-
H)
Protect Level • To switch to the protect level from the operation level, the adjustment
level, bank setting level, or PID setting level, simultaneously hold down the O and M Keys for at least 3 seconds. (See note.) This level is for pre­venting unwanted or accidental modification of parameters. Protected lev­els will not be displayed, and so the parameters in that level cannot be modified.
Note The key pressing time can be changed in Move to Protect Level pa-
rameter (advanced function setting level).
Operation Level • The operation level is displayed when the power is turned ON. You can
move to the protect level, initial setting level, or adjustment level from this level.
• Normally, select this level during operation. While operation is in progress, items such as the PV and manipulated variable (MV) can be monitored, and the set points, alarm values, and alarm upper and lower limits can be monitored and changed.
Adjustment Level • To move to the adjustment level, press the O Key once (for less than 1 s).
• This level is for entering set values and offset values for control. In addi­tion to AT (auto-tuning), communications write enable/disable switching, hysteresis settings, SP settings, and input offset parameters, it includes HB alarm, HS alarm, OC alarm, and PID constants. From the adjustment level, it is possible to move to the bank setting level, initial setting level, or protect level.
Bank Setting Level • To move to the bank setting level from the adjustment level, press the O
Key once (for less than 1 s).
• This level is used to input parameters such as set points, alarm values, and PID set numbers. From the bank setting level, it is possible to move to the PID setting level, the initial setting level, or the protect level.
PID Setting Level • To move to the PID setting level from the bank setting level, press the O
Key once (for less than 1 s).
• This level is used to input parameters such as the PID values for each PID set, MV upper and lower limits, and automatic selection range upper and lower limits. From the PID setting level, it is possible to move to the opera­tion level, the initial setting level, or the protect level.
12
Page 37
Setting Level Configuration and Key Operations Section 1-3
Monitor/Setting Item Level • To switch to the monitor/setting item level, press the PF Key from the
operation level, adjustment level, bank setting level, or PID setting level. The contents set for monitor/setting items 1 to 5 can be displayed. You can move from the monitor/setting item level to the operation level or initial setting level. (E5AN/EN-H only.)
Manual Control Level • When the O Key is pressed for at least 3 seconds from the operation
level's auto/manual switching display, the manual control level will be dis­played. (The MANU indicator will light.)
• When the PF Setting is set to A-M (auto/manual) and the PF Key is pressed for more than one second from the operation level, adjustment level, bank setting level, or PID setting level the manual control level will be displayed. (E5AN/EN-H only.)
• This is the level for changing the MV in manual mode.
• To return to the operation level, press the O Key for at least one second. It is also possible to return to the operation level by pressing the PF Key for more than one second when the PF Setting is set to A-M.
Initial Setting Level • To move to the initial setting level from the operation level, the adjustment
level, bank setting level, PID setting level, or monitor/setting item level, press the O Key for at least 3 seconds. The PV display flashes after one second. This level is for specifying the input type and selecting the control method, control period, setting direct/reverse operation, setting the alarm types, etc. You can move to the advanced function setting level or commu­nications setting level from this level. To return to the operation level, press the O Key for at least one second. To move to the communications setting level, press the O Key for less than one second. (When moving from the initial setting level to the operation level, all the indicators will light.)
Note Pressing the O Key for at least 3 seconds in the operation level's
auto/manual switching display will move to the manual control level, and not the initial setting level.
Advanced Function Setting Level
Communications Setting Level
Calibration Level • To move to the calibration level, input the password (1201) from the
• To move to the advanced function setting level, set the Initial Setting/Com­munications Protect parameter in the protect level to 0 (the default) and then, in the initial setting level, input the password (−169).
• From the advanced function setting level, it is possible to move to the cali­bration level or to the initial setting level.
• This level is for setting the automatic display return time and standby sequence, and it is the level for moving to the user calibration and other functions.
• To move to the communications setting level from the initial setting level, press the O Key once (for less than 1 s). When using the communica­tions function, set the communications conditions in this level. Communi­cating with a personal computer (host computer) allows set points to be read and written, and manipulated variables (MV) to be monitored.
advanced function setting level. The calibration level is for offsetting error in the input circuit.
• You cannot move to other levels from the calibration level by operating the keys on the front panel. To cancel this level, turn the power OFF then back ON again.
13
Page 38
Communications Function Section 1-4
M
M
Moves in order after M key is pressed (if key is released within 1 s).
Parameter 1
Parameter 2
Parameter 3
After M key is pressed
Parameter 4
Hold down the M key during this interval.
While the M key is being held down, the parameter will move each second in reverse order.
Parameter 2
Parameter 3
After M key has been held down for 2 s.
After M key has been held down for 1 s.

1-3-1 Selecting Parameters

• Within each level, the parameter is changed in order (or in reverse order) each time the M Key is pressed. (In the calibration level, however, parameters cannot be changed in reverse order.) For details, refer to SECTION 5 Parameters.

1-3-2 Saving Settings

1-4 Communications Function

• If you press the M Key at the final parameter, the display returns to the top parameter for the current level.
• To change parameter settings, specify the setting using the U or D Key, and either leave the setting for at least two seconds or press the M Key. This saves the setting.
• When another level is selected after a setting has been changed, the con­tents of the parameter prior to the change is saved.
• When you turn the power OFF, you must first save the settings (by press­ing the M Key). The settings are sometimes not changed by merely pressing the U or D Keys.
The E5CN/AN/EN-H Digital Controllers are provided with a communications function that enables parameters to be checked and set from a host computer. If the communications function is required, use a model that has that function (E5CN-HM-500 with an E53-CN01N2 or E53-CN03N2, E5AN-H/EN­HM-500 with an E53-EN01, E53-EN02, or E53-EN03). For details on the communications function, see the separate Communications Manual Advanced Type. Use the following procedure to move to the communications setting level.
1,2,3... 1. Press the O Key for at least three seconds to move from the operation lev-
el to the initial setting level.
14
Page 39
Communications Function Section 1-4
M
M
M
M
M
M
M
psel
cwf
u-no
1
bps
9.6
len
7
sbit
2
prty
even
sdwt
20
Protocol Setting
Communications Unit No.
Communications Baud Rate
Communications Parity
Send Data Wait Time
Communications Data Length (See note.)
Communications Stop Bits (See note.)
2. Press the O Key for less than one second to move from the initial setting
level to the communications setting level.
3. Select the parameters as shown below by pressing the M Key.
4. Press the U or D Key to change the parameter setting.
Setting Communications Data
Parameter name Symbol Setting (monitor) value Selection symbols Default Unit
Protocol Setting psel CompoWay/F (SYSWAY),
Communications Unit No.
Communications Baud Rate
Communications Data Length
Communications Stop Bits
Communications Parity
Send Data Wait Time
Note The Protocol Setting parameter is displayed only when CompoWay/F commu-
nications are being used.
Match the communications specifications of the E5CN/AN/EN-H and the host computer. If a 1:N connection is being used, ensure that the communications specifications for all devices in the system (except the communications Unit No.) are the same.
Modbus
u-no 0 to 99 1 None
bps 1.2, 2.4, 4.8, 9.6, 19.2,
38.4, 57.6
len 7, 8 7 Bits
sbit 1, 2 2 Bits
prty None, Even, Odd none, even, odd Even None
sdwe 0 to 99 20 ms
cwf, mod CompoWay/F
1.2, 2.4, 4.8, 9.6, 19.2, 38.4.
57.6
(SYSWAY)
9.6 kbps
None
15
Page 40
Isolation/Insulation Block Diagrams Section 1-5

1-5 Isolation/Insulation Block Diagrams

This section provides the isolation/insulation block diagrams for the E5CN-H, E5AN-H, and E5EN-H.
E5CN-H
Transfer output
Temperature input, analog input, CT input, and voltage pulse output
E5AN-H and E5EN-H
Power supply
Power supply
Communications and event inputs
Linear current output and linear voltage output
Auxiliary outputs 1 and 2
: Reinforced insulation
Temperature input, analog input, CT input, potentiometer input, and remote SP input
Communications and event inputs
Voltage pulse output, linear current output, linear voltage output, and transfer output
Relay output
: Functional isolation
Relay output
Auxiliary output 1
Auxiliary output 2
16
: Reinforced insulation
: Functional isolation
Page 41
SECTION 2
Preparations
This section describes the work required to prepare the E5CN-H, E5AN-H, and E5EN-H Digital Controllers for operation, including installation and wiring.
2-1 Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
2-1-1 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
2-1-2 Panel Cutout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
2-1-3 Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
2-1-4 Removing the Digital Controller from the Case. . . . . . . . . . . . . . . . 23
2-2 Wiring Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
2-2-1 Terminal Arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
2-2-2 Precautions when Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
2-2-3 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
2-3 Using the Support Software Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
2-4 Using Infrared Communications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
17
Page 42
Installation Section 2-1
48 × 48
44.8 × 44.8
48.8
91
78
1.5
58
6
79.2
91 × 91
96 × 96
112
78
6
2
44
91
79.2
6
2
78
112
96
48

2-1 Installation

2-1-1 Dimensions

Unit: mm
E5CN-H
E5AN-H
E5EN-H
18
Page 43
Installation Section 2-1
60 min.
+1.0 0
Individual Mounting Group Mounting
(48 × number of Units − 2.5)
120 min.
+1.0 0
Individual Mounting Group Mounting (See note.)
(96 × number of Units − 3.5)

2-1-2 Panel Cutout

Unit: mm
E5CN-H
E5AN-H
Note Group mounting is not possible when an SSR output is used for
120 min.
control output 1 or 2 and an E53-C3N or E53-C3DN Output Unit is used. Mount at the intervals shown in the following diagram.
110 min.
19
Page 44
Installation Section 2-1
)
120 min.
60 min.
E5EN-H
Individual Mounting Group Mounting (See note.
(48 × number of Units − 2.5)
120 min.
Note Group mounting is not possible when an SSR output is used for
control output 1 or 2 and an E53-C3N or E53-C3DN Output Unit is used. Mount at the intervals shown in the following diagram.
+1.0 0
20
• Waterproofing is not possible when group mounting several Controllers.
• The recommended panel thickness is 1 to 5 mm for E5CN-H, and 1 to 8 mm for E5AN/E5EN-H.
• Units must not be group mounted vertically. In addition, group mounting is not possible when an SSR output is used for control output 1 or 2 and an E53-C3N or E53-C3DN Output Unit is used. (Observe the recommended mounting intervals.)
• When group mounting several Controllers, ensure that the surrounding temperature does not exceed the ambient operating temperature listed in the specifications.
Page 45
Installation Section 2-1
Adapter
Waterproof packing
Panel
E53-COV17 Terminal Cover

2-1-3 Mounting

E5CN-H
Mounting to the Panel
1,2,3... 1. For waterproof mounting, waterproof packing must be installed on the
Controller. Waterproofing is not possible when group mounting several Controllers. Waterproof packing is not necessary when there is no need for the waterproofing function.
2. Insert the E5CN-H into the mounting hole in the panel.
3. Push the adapter from the terminals up to the panel, and temporarily fasten the E5CN-H.
4. Tighten the two fastening screws on the adapter. Alternately tighten the two screws little by little to maintain a balance. Tighten the screws to a torque of 0.29 to 0.39 N·m.
21
Page 46
Installation Section 2-1
Mounting the Terminal Cover
Make sure that the "UP" mark is facing up, and then attach the E53-COV17 Terminal Cover to the holes on the top and bottom of the Digital Controller.
E5AN/EN-H
Mounting Bracket
Terminal Cover (E53-COV16)
Panel
Waterproof packing
Terminal Cover (E53-COV16)
E5AN-H
Mounting Bracket
Panel
22
Waterproof packing
E5EN-H
Page 47
Installation Section 2-1
Flat-blade screwdriver
(Unit: mm)
Tool insertion hole
(1)
(1)
(2)
(3)
2.0
0.4
Mounting to the Panel
1,2,3... 1. For waterproof mounting, waterproof packing must be installed on the
Controller. Waterproofing is not possible when group mounting several Controllers. Waterproof packing is not necessary when there is no need for the waterproofing function.
2. Insert the E5AN/E5EN-H into the square mounting hole in the panel (thick­ness: 1 to 8 mm). Attach the Mounting Brackets provided with the product to the mounting grooves on the top and bottom surfaces of the rear case.
3. Use a ratchet to alternately tighten the screws on the top and bottom Mounting Brackets little by little to maintain balance, until the ratchet turns freely.
Mounting the Terminal Cover
Slightly bend the E53-COV16 Terminal Cover to attach it to the terminal block as shown in the following diagram. The Terminal Cover cannot be attached in the opposite direction.
Slightly bend the E53-COV16 Terminal Cover in the direction shown by the arrows to attach it to the terminal block.
Enlarged Illustration of Terminal Section

2-1-4 Removing the Digital Controller from the Case

The body of the Digital Controller can be removed from the case to set Output Units or to perform maintenance. Check the specifications of the case and Digital Controller before removing the Digital Controller from the case.
E5CN-H
23
Page 48
Installation Section 2-1
Keep the PCBs parallel to each other and insert them into the rear case.
Bottom View of the E5CN-H
1,2,3... 1. Insert a flat-blade screwdriver into the two tool insertion holes (one on the
top and one on the bottom) to release the hooks.
2. Insert the flat-blade screwdriver in the gap between the front panel and rear case, and pull out the front panel slightly. Hold the top and bottom of the front panel and carefully pull it out toward you, without applying unnec­essary force.
3. When inserting the body of the Digital Controller into the case, make sure the PCBs are parallel to each other, make sure that the sealing rubber is in place, and press the E5CN-H all the way to the rear case. While pushing the E5CN-H into place, push down on the hooks on the top and bottom sur­faces of the rear case so that the hooks are securely locked in place. Be sure that electronic components do not come into contact with the case.
24
Page 49
Installation Section 2-1
E5AN/EN-H
Tool insertion hole
(1)
(2)
(3)
(1)
Tool insertion hole
(1)
(2)
(3)
(1)
Flat-blade screwdriver
(Unit: mm)
0.4 5.0
2.0
1,2,3... 1. Insert a flat-blade screwdriver into the two tool insertion holes (one on the
top and one on the bottom) to release the hooks.
2. Insert a flat-blade screwdriver in the gap between the front panel and rear case (two on the top and two on the bottom), and use it to pry and pull out the front panel slightly. Then, pull out on the front panel gripping both sides. Be sure not to impose excessive force on the panel.
25
Page 50
Installation Section 2-1
OUT1
OUT2
E5AN-H
OUT1
OUT2
E5EN-H
Gap between the Front Panel and Rear Case Four gaps, two on the top and two on the bottom
Top View of E5AN-H
Gap between the Front Panel and Rear Case Four gaps, two on the top and two on the bottom
Top View of E5EN-H
3. When inserting the body of the Digital Controller into the case, make sure the PCBs are parallel to each other, make sure that the sealing rubber is in place, and press the E5AN/EN-H toward the rear case until it snaps into position. While pressing the E5AN/EN-H into place, press down on the hooks on the top and bottom surfaces of the rear case so that the hooks securely lock in place. Make sure that electronic components do not come into contact with the case.
Keep the PCBs parallel to each other and insert them into the rear case.
Keep the PCBs parallel to each other and insert them into the rear case.
Bottom View of the E5AN-H
Bottom View of the E5EN-H
Mounting Output Units
Before Performing the Setup
Setting Procedure • Check the socket positions to be set using the following diagram.
• Confirm the type of Output Units that are to be set.
• For details on types of Output Units and the main specifications, refer to Output Units on page 32.
• For position-proportional models and models with SSR outputs, the Out­put Units are already set. This setting operation is not required.
• When setting the Output Units, draw out the body of the Controller from the case and insert the Output Units into the sockets for control output 1 and 2.
26
Page 51
Installation Section 2-1
OUT1
OUT2
Clamps
1,2,3... 1. While lifting the hooks securing the PCB on the front panel, remove the
PCB to which the sockets are attached.
Hooks securing PCB
E5AN-H
Hooks securing PCB
E5EN-H
2. Set the Output Unit for control output 1 in the OUT1 socket. Set the Output Unit for control output 2 in the OUT2 socket.
3. For the E5AN-H, use the enclosed clamps to secure the Output Units. Do not use clamps for the E5EN-H.
4. Set the PCB back in its original location, and make sure that the hooks se­curing the PCB are firmly in place.
Confirm that the hooks
Confirm that the hooks securing the PCB are firmly in place on the top and bottom.
E5AN-H
securing the PCB are firmly in place on the top and bottom.
E5EN-H
27
Page 52
Control output 1
A
B
B
Control output 1
V
DO NOT USE
DO NOT USE
DO NOT USE
mA
Auxiliary outputs (relay outputs)
Input power supply
Auxiliary outputs (relay outputs) 250 VAC, 3 A (resistive load)
• 100 to 240 VAC
• 24 VAC/VDC (no polarity)
Auxiliary output 2
Auxiliary output 1
6
7
8
9
10
11
12
13
14
15
1
3
2
4
5
A heater burnout alarm, heater short, heater overcurrent alarm, or input error is sent to the output to which the alarm 1 function is assigned.
RS-232C
CT1
CT1
CT1
11
12
13
14
15
Communications (RS-232) and CT
11
12
13
14
15
CT2
CT1
Control Output 2 and CT2
11
12
13
14
15
Control Output 2 and Transfer Output
11
12
13
14
15
EV1
EV2
Event Inputs
E53-CNBN2
E53-CNQHHN2
11
12
13
14
15
CT1
Control Output 2 and CT
E53-CNQHN2E53-CN03N2 E53-CNQ03N2 E53-CNH03N2 E53-CNHH03N2
E53-CNQFN2 E53-CN01N2 E53-CNH01N2 E53-CNQ01N2
E53-CNQBN2 E53-CNHBN2 E53-CNBFN2
SD
RS-232C
RD
SG
SD
RD
SG
RS-232C
11
12
13
14
15
Communications (RS-232)
SD
RD
SG
11
12
13
14
15
11
12
13
14
15
RS-485
Communications (RS-485) and CT
11
12
13
14
15
CT2
CT1
RS-485
Communications (RS-485) and CT2
Communications (RS-232) and Control Output 2
11
12
13
14
15
RS-485
Communications (RS-485) and Control Output 2
11
12
13
14
15
RS-485
Communications (RS-485)
11
12
13
14
15
EV1
EV2
Event Inputs and Control Output 2
11
12
13
14
15
EV1
EV2
Event Inputs and CT
11
12
13
14
15
EV1
EV2
Event Inputs and Transfer Output
Transfer output
DO NOT USE
DO NOT USE
DO NOT USE
DO NOT USE
DO NOT USE
DO NOT USE
DO NOT USE
DO NOT USE
DO NOT USE
DO NOT USE
DO NOT USE
B (+)
A (−)
B (+)
A (−)
B (+)
A (−)
B (+)
A (−)
Control output 2 12 VDC 21 mA
Control output 2 12 VDC 21 mA
Control output 2 12 VDC 21 mA
Control output 2 12 VDC 21 mA
Transfer output
Control output 2 12 VDC 21 mA
Control output 2 12 VDC 21 mA
Controllers
Option Units
Wiring Terminals Section 2-2

2-2 Wiring Terminals

Check the terminal arrangements for E5CN-H terminals 1 to 15 and E5AN/ EN-H terminals 1 to 30 as marked on the product label and on the side of the case.

2-2-1 Terminal Arrangement

E5CN-H
28
Note Wire all voltage input terminals correctly. The Controller may fail if
voltage input terminals are wired incorrectly.
Page 53
Wiring Terminals Section 2-2
Potentiometer
RDB
RDA
SG
SDB
SDA
4 to 20 mA DC (Load: 600 max.)
4 to 20 mA DC
1
2
3
4
5
6
7
8
9
10
21
22
23
24
25
26
27
28
29
30
21
22
23
24
25
26
27
28
29
30
11
12
13
14
15
16
17
18
19
20
100 to 240 VAC 24 VAC/VDC (no polarity)
Input power supply
Control output 1
B
V
mA
Control output 2
CT2
CT1
EV1
EV2
CT2
DO NOT USE
DO NOT USE
DO NOT USE
B
A
C
W
O
DO NOT USE
DO NOT USE
DO NOT USE
DO NOT USE
Event Inputs
*1
EV1
EV2
Event Inputs
Communications
B (+)
A ( )
DO NOT USE B (+)
*2
A ( )
11
12
13
21
22
E53-EN03 RS-485
11
12
13
21
22
E53-EN01 RS-232C
SD
RD
SG
DO NOT USE
DO NOT USE
11
12
13
21
22
E53-AKB
11
12
13
21
22
E53-EN02 RS-422
Control Output Unit Control outputs 1, 2 Refer to page 32
SSR Outputs 75 to 250 VAC, 1 A (resistive load)
Models with Position­proportional Control Relay output 250 VAC, 1 A (including inrush current)
Control outputs 1, 2
Relay output SPST-NO, 250 VAC, 3 A (resistive load)
Auxiliary outputs 1, 2, 3
A heater burnout alarm, SSR failure, heater overcurrent alarm, input error, or Remote SP Input Error is sent to the output to which the alarm 1 function is assigned.
Auxiliary output 3
14
15
16
1
2
3
4
5
6
7
8
9
10
21
22
23
24
25
26
27
28
29
30
EV4
EV3
+
+
+
+
Output unit
Output unit
Control Output Unit
1
2
3
4
5
6
7
8
9
10
SSR
SSR
SSR Outputs
1
2
3
4
5
6
7
8
9
10
Open
Closed
Models with Position­proportional Control
Event input*1/ Transfer output/ Remote SP
Remote SP input
DO NOT USE
Transfer output
Input power supply
Input power supply
Input power supply
Auxiliary output 2
Auxiliary output 1
Auxiliary output 2
Auxiliary output 1
Auxiliary output 2
Auxiliary output 1
Auxiliary output 2
Auxiliary output 1
Relay output SPDT, 250 VAC, 3 A (resistive load)
Auxiliary output 3
Option UnitsControllers
−
−
*2
*1 EV3 and EV4 are assigned to event inputs in Controllers with two event inputs.
E5AN/EN-H
Note Wire all voltage input terminals correctly. The Controller may fail if
voltage input terminals are wired incorrectly.
29
Page 54
Wiring Terminals Section 2-2
7.2 mm max.
7.2 mm max.

2-2-2 Precautions when Wiring

• Separate input leads and power lines in order to prevent external noise.
• Use AWG24 (cross-sectional area: 0.205 mm
2
tional area: 2.081 mm
) twisted-pair cable (stripping length: 5 to 6 mm).
2
) to AWG14 (cross-sec-
• Use crimp terminals when wiring the terminals.
• Use the suitable wiring material and crimp tools for crimp terminals.
• Tighten the terminal screws to a torque of 0.74 to 0.90 N·m.
• Use the following types of crimp terminals for M3.5 screws.
Note Do not remove the terminal block. Doing so will result in malfunction or failure.

2-2-3 Wiring

In the connection diagrams, the left side of the terminal numbers represents the inside of the Controller and the right side represents the outside.
Power supply • With the E5CN-H, connect to terminals 9 and 10; with the E5AN-H and
E5EN-H, connect pins 1 and 2. The following table shows the specifica­tions.
Input power supply E5CN-H E5AN/EN-H
100 to 240 VAC, 50/60 Hz 8.5 VA 12 VA
24 VAC, 50/60 Hz 5.5 VA 8.5 VA
24 VDC (no polarity) 3.5 W 5.5 W
• These models have reinforced insulation between the input power supply, the relay outputs, and other terminals.
Input • Make the connections as shown below, using terminals 3 to 5 for the
E5CN-H and pins 17 to 20 for the E5AN/EN-H, and matching the input types.
3
−
4
5
+
Thermocouple
17
18
−
19
20
+
Thermocouple
Do not use.
Platinum resistance thermometer
Do not use.
Do not use.
Platinum resistance thermometer
3
4
5
E5CN-H
Do not
17 17
use.
18
19
20
E5AN/EN-H
Do not
3
use.
−
4
V
5
+
Analog input
Do not use.
+
18
mA
19
−
Do not
20
use.
Analog input
+
mA
−
Do not use.
Do not use.
Do not use.
+
V
−
30
Note When wiring a voltage input, check the connected terminals care-
fully to make sure there are no mistakes. Incorrect wiring can cause the Unit to fail.
Page 55
Wiring Terminals Section 2-2
Control Output 1 • Outputs are sent from terminals 1 and 2 with the E5CN-H and from pins 3
and 4 with the E5AN/EN-H. The following diagrams show the available outputs and their internal equalizing circuits.
Relay
Relay
v
+
+
GND
1
L
2
−
E5CN-H
v
+
+
GND
3
L
4
−
3
4
E53-Q4 (PNP) E53-QN (PNP)
1
2
3
4
SSR
v
+
+
1
2
−
CurrentVoltage (for driving SSR)
v
+
3
4
GND
E53-Q3 (NPN) E53-V34N
E5AN/EN-H
1
VL
2
Linear voltage
+
L
−
+
L
−
V
E53-V35N
• The following table shows the specifications for each output type.
E5CN-H
Output type Specifications
Relay 250 VAC, 3 A (resistive load), electrical durability: 100,000
operations
Voltage (for driv­ing SSR)
Current DC 4 to 20 mA/DC 0 to 20 mA, resistive load: 600 Ω max.
Linear voltage 0 to 10 VDC, resistive load: 1 kΩ max.
PNP type, 12 VDC ±15%, 21 mA (with short-circuit protec­tion)
Resolution: Approx. 10,000
Resolution: Approx. 10,000
+
3
L
4
−
+
3
mA
4
−
E53-C3N E53-C3DN
L
E5AN/EN-H
Output type Specifications
SSR 75 to 250 VAC, 1 A (See note.)
Relay (Position-
250 VAC 1 A (including inrush current) proportional mod­els)
Note The SSR output (control output 1 or control output 2) ratings are as
follows:
• Rated load voltage: 75 to 250 VAC
• Rated load current: 1 A (resistance load) Use the load current within the derating curve.
• A zero cross function is not supported.
31
Page 56
Wiring Terminals Section 2-2
0
0.25
0.5
0.75
1
1.25
1.5
−100 10 20304050
Derating Curve for SSR
Output Models
Load current I (A) for
current output 1 or 2
Condition A
Condition B
Ambient temperature (°C)
55°C
45°C
25°C
Condition A: SSR output 100% ON Condition B: SSR output 50% ON, control cycle: 2 s
■ Output Units
Model Output Type Output
method
E53-RN Relay ON/OFF 250 VAC, 5 A (resistive load), Electrical life:
100,000 operations
E53-QN E53-Q3 E53-Q4
Voltage (PNP) Voltage (NPN) Voltage (PNP)
ON/OFF ON/OFF ON/OFF
PNP type, 12 VDC, 40 mA (with short-circuit protection)
NPN type, 24 VDC, 20 mA (with short-circuit protection)
PNP type, 24 VDC, 20 mA (with short-circuit protection)
E53-C3N E53-C3DN
4 to 20 mA 0 to 20 mA
Linear Linear
DC 4 to 20 mA, resistive load: 600 Ω max. Resolution: Approx. 10,000 DC 0 to 20 mA, resistive load: 600 Ω max. Resolution: Approx. 10,000
E53-V34N E53-V35N
0 to 10 V 0 to 5 V
Linear Linear
0 to 10 VDC, resistive load: 1 kΩ min. Resolution: Approx. 10,0000 to 5 VDC, resis­tive load: 1 kΩ min. Resolution: Approx. 10,000
Specifications
32
• The E5CN-H voltage output (for driving SSR) is not electrically isolated from the internal circuits. When using a grounding thermocouple, do not connect any of the control output terminals to the ground. (If a control out­put terminal is connected to the ground, errors will occur in the measured temperature as a result of leakage current.) E5AN/EN-H voltage outputs (for driving SSR), however, are functionally isolated from the internal cir­cuits.
• If high levels of noise or surge are imposed between the output terminals of an SSR output, short-circuit faults may occasionally occur. If the output becomes permanently shorted, there is the danger of fire due to overheat­ing of the heater. Design safety into the system, including measures to prevent excessive temperature rise and spreading of fire.
Page 57
Wiring Terminals Section 2-2
4
3
SSR output
Varistor
Load
Varistor
~
E5AN/EN-H
Relay
GND
Voltage (for driving SSR)
E5CN-H
or
+
v
L
+
−
+
v
L
+
−
+
−
L
V
+
−
L
mA
+
v
L
+
−
+
v
L
+
−
Voltage (for driving SSR)
GND
GND
GND
SSR
E53-Q4 (PNP) E53-QN (PNP)
E53-Q3 (NPN)
E53-V34N E53-V35N
E53-C3N E53-C3DN
14
15
11
12
5
6
5
6
5
6
5
6
5
6
5
6
• Take countermeasures such as installing a surge absorber. As an addi­tional safety measure, provide error detection in the control loop. (Use the Loop Burnout Alarm (LBA) and HS alarm that are provided for the E5N- H.)
Select a surge absorber that satisfies the following conditions.
Voltage used Varistor voltage Surge resistance
100 to 120 VAC 240 to 270 V 1,000 A min.
200 to 240 VAC 440 to 470 V
Control Output 2 • Outputs are sent from terminals 11, 12, 14, and 15 with the E5CN-H, and
from pins 5 and 6 with the E5AN/EN-H. The following diagrams show the available outputs and their internal equalizing circuits.
• The following table shows the specifications for each output type.
E5CN-H
Output type Specifications
Voltage (for driv­ing SSR)
PNP type, 12 VDC ±15%, 21 mA (with short-circuit protec­tion)
E5AN/EN-H
Output type Specifications
SSR 75 to 250 VAC 1 A (See note.)
proportional mod­els)
Note The SSR output (control output 1 or control output 2) ratings are as
Relay (Position-
250 VAC 1 A (including inrush current)
follows:
• Rated load voltage: 75 to 250 VAC
• Rated load current: 1 A (resistance load) Use the load current within the derating curve.
33
Page 58
Wiring Terminals Section 2-2
0
0.25
0.5
0.75
1
1.25
1.5
−100 10 20304050
Derating Curve for SSR
Output Models
Load current I (A) for
current output 1 or 2
Condition A
Condition B
Ambient temperature (°C)
55°C
45°C
25°C
Condition A: SSR output 100% ON Condition B: SSR output 50% ON, control cycle: 2 s
• A zero cross function is not supported.
■ Output Units
Model Output Type Output
method
E53-RN Relay ON/OFF 250 VAC, 5 A (resistive load), Electrical life:
100,000 operations
E53-QN E53-Q3 E53-Q4
Voltage (PNP) Voltage (NPN) Voltage (PNP)
ON/OFF ON/OFF ON/OFF
PNP type, 12 VDC, 40 mA (with short-circuit protection)
NPN type, 24 VDC, 20 mA (with short-circuit protection)
PNP type, 24 VDC, 20 mA (with short-circuit protection)
E53-C3N E53-C3DN
4 to 20 mA 0 to 20 mA
Linear Linear
DC 4 to 20 mA, resistive load: 600 Ω max. Resolution: Approx. 10,000 DC 0 to 20 mA, resistive load: 600 Ω max. Resolution: Approx. 10,000
E53-V34N E53-V35N
0 to 10 V 0 to 5 V
Linear Linear
0 to 10 VDC, resistive load: 1 kΩ min. Resolution: Approx. 10,0000 to 5 VDC, resistive load: 1 kΩ min. Resolution: Approx. 10,000
Specifications
34
• The E5CN-H voltage output (for driving SSR) is not electrically isolated from the internal circuits. When using a grounding thermocouple, do not connect any of the control output terminals to the ground. (If a control out­put terminal is connected to the ground, errors will occur in the measured temperature as a result of leakage current.) E5AN/EN-H voltage outputs (for driving SSR), however, are functionally isolated from the internal cir­cuits.
• Control output 2 of the E5CN-H is a voltage output (for driving SSR) only, and outputs across terminals 11(+) and 12(-), or 14(+) and 15(-).
• Control output 1 (voltage output for driving SSR) and control output 2 (voltage output for driving SSR) are not isolated.
• If high levels of noise or surge are imposed between the output terminals of an SSR output, short-circuit faults may occasionally occur. If the output becomes permanently shorted, there is the danger of fire due to overheat­ing of the heater. Design safety into the system, including measures to prevent excessive temperature rise and spreading of fire.
Page 59
Wiring Terminals Section 2-2
• Take countermeasures such as installing a surge absorber. As an addi­tional safety measure, provide error detection in the control loop. (Use the Loop Burnout Alarm (LBA) and HS alarm that are provided for the E5N- H.)
SSR output
5
Varistor
6
Select a surge absorber that satisfies the following conditions.
Voltage used Varistor voltage Surge resistance
100 to 120 VAC 240 to 270 V 1,000 A min.
200 to 240 VAC 440 to 470 V
Auxiliary Outputs 2, and 3 • On the E5CN-H2-500, auxiliary output 1 (SUB1) is output across ter-
minals 7 and 8, and auxiliary output 2 (SUB2) is output across terminals 6 and 8.
• On the E5AN/EN-H2-500, auxiliary output 1 (SUB1) is output across terminals 9 and 10, auxiliary output 2 (SUB2) is output across terminals 7 and 8.
• On the E5AN/EN-H3-500, auxiliary output 1 (SUB1) is output across terminals 9 and 10, auxiliary output 2 (SUB2) is output across terminals 7 and 8, and auxiliary output 3 (SUB3) is output across terminals 14, 15 and 16.
• When the Input Error Output parameter is set to ON, the output assigned to the alarm 1 function turns ON when an input error occurs.
• If the Remote SP Input Error Output parameter is set to ON, the output assigned to the alarm 1 function will turn ON when an RSP input error occurs.
• When the HB alarm, HS alarm, or heater overcurrent alarm is used with the E5CN-H (with E53-CNH/HHN2), alarms are output to the output assigned to the alarm 1 function.
• When the HB alarm, HS alarm, or heater overcurrent alarm is used with the E5AN-H/EN-H, alarms are output across terminals 9 and 10.
• On the E5CN-H, when heating/cooling control is used, auxiliary output 2 becomes control output (cooling).
• On the E5AN-H and E5EN-H, when heating/cooling control is used, con­trol output 2 becomes the control output (cooling).
• For models that have a heater burnout alarm, an OR of the alarm 1 func­tion and the HB alarm, HS alarm, or heater overcurrent alarm is output. If the alarm 1 function is to be used for HB alarm only, set the alarm 1 type to 0 (i.e., do not use alarm 1 function).
• The following diagrams show the internal equalizing circuits for auxiliary outputs 1, 2, and 3.
Varistor
Load
~
35
Page 60
Wiring Terminals Section 2-2
(
)
SUB3
SUB2
SUB2
SUB1
SUB1
E5CN-H
E5AN/EN-H
ALM1, 2, 3 can be output to auxiliary output 1, 2, 3 or changed with the advanced function setting level.
• The relay specifications are as follows:
E5N-H (SUB1, SUB2) SPST-NO, 250 VAC, 3 A
E5N-H (SUB3) SPDT, 250 VAC, 3 A
Event Inputs •The E5N-HB supports event inputs. When event inputs 1/2 are to
be used, connect to terminals 11 to 13, and when event inputs 3/4 are to be used, connect to terminals 23 to 25.
12
13
11
EV1
EV2
11
12
13
Two Event Inputs: E53-CN@B@N2 (for E5CN-H)
EV1
EV2
23
24
25
Two Event Inputs: E5AN/EN-H@B@M@-500 (for E5AN/EN-H)
EV3
EV4
23
24
25
EV3
EV4
Four Event Inputs: E5AN/EN-H@B@M@-500 with the E53-AKB
for the E5AN/EN-H
• Use event inputs under the following conditions:
• The outflow current is approximately 7 mA.
Contact inputON: 1 kΩ max., OFF: 100 kΩ min.
No-contact inputON: Residual voltage 1.5 V max.; OFF: Leakage current 0.1 mA
max.
36
Polarities during no-contact input are as follows:
−
11
12
13
Two Event Inputs:
E53-CN@B@N2
(for E5CN-H)
EV1
+
EV2
+
23
+
24
+
25
−
Two Event Inputs:
E5AN/EN-
H@B@M@-500
(for E5AN/EN-H)
EV3
EV4
11
12
13
Two Additional Event Inputs:
E53-AKB in E5AN/EN-
(for E5AN/EN-H)
+
EV1
+
EV2
−
H@B@M@-500
Page 61
Wiring Terminals Section 2-2
E53-CN@H@N2 (for E5CN-H)
15
14
CT
E53-CN@HH@N2
15
14
13
CT1
CT2
CT
E5AN/EN-H@@H@-500 E5AN/EN-H@@HH@-500
CT2
CT1
14
15
14
15
16
L
+
v
+
−
27
28
L
+
v
+
−
14
15
Current
Current
E53-CN@FN2
(for E5CN-H)
E5AN/EN-H@@F-500
29
30
+
−
4 to 20 mA
E5AN/EN-H
CT Inputs • When the HB alarm, HS alarm, or heater overcurrent alarm is to be used
with the E5CN-HM-500 with an E53-CNH/HHN2 Option Unit, con­nect a current transformer (CT) across terminals 14 and 15 or terminals 13 and 15 (no polarity).
• When the HB alarm, HS alarm, or heater overcurrent alarm is to be used with the E5AN/EN-HH-500 or E5AN/EN-HHH-500, connect a current transformer (CT) across terminals 14 and 15 or terminals 15 and 16 (no polarity).
Transfer Output • On the E5CN-HM-500 with an E53-CNFN2, the transfer output is
output across terminals 14 and 15.
• On the E5AN/EN-HF-500, transfer output is output across terminals 27 and 28.
Remote SP Input • The E5AN-H and E5EN-H support remote SP inputs. To use remote SP,
Output type Specifications
Current 4 to 20 mA DC, Load: 600 Ω max., Resolution: 10,000
Even with models that do not have a transfer output, control outputs 1 or 2 can be used as a simple transfer output if it is a current output or linear output. For details on the operation, refer to 4-14 Using the Transfer Output.
connect to terminals 29 and 30.
Remote SP inputs are not electrically isolated from the internal circuits. When using a grounding thermocouple, do not connect any of the remote SP input terminals to the ground. (If a remote SP input terminal is connected to the ground, errors will occur in the measured temperature as a result of leakage current.)
37
Page 62
Wiring Terminals Section 2-2
No.
1211A (−)
B (+)
A (−)
B (+)
RS-485
−
+
FG
No.
12
11
RS-485
E5CN-H (No. 1)
E5CN-H (No. 31)
RS-485
Host computer
Shield
Terminator (120 Ω, 1/2 W)
Abbreviation Abbreviation
A < B: [1] Mark A > B: [0] Space
RS-485
RS-485
RS-485
Host computer
Shield
Terminator (120 Ω, 1/2 W)
Abbreviation
A < B: [1] Mark A > B: [0] Space
−
+
FG
No.
22 21
No.
22
21 12 11
12
11
E5AN/EN-H (No. 31)
E5AN/EN-H (No. 1)
Abbreviation
A (−)
A (−)
A (−)
A (−)
B (+)
B (+)
B (+)
B (+)
Cross-sectional area of conductor AWG24: 0.205 mm
2
AWG14: 2.081 mm
2
Communications RS-485
• When communications are to be used with the E53-CN03N2 for the E5CN-H, or E53-EN03 for the E5AN/EN-H, connect communications cable across terminals 11 and 12 or 21 and 22.
11
B(+)
RS-485
A(−)
12
E53-CN@03N2 (for E5CN-H)
11
12
13
22
E53-EN03 (for E5AN/EN-H)
21
B(+)
A(−)
Do not use.
B(+) A(−)
RS-485
Specify both ends of the transmission path including the host computer as end nodes (that is, connect terminators to both ends). The minimum terminal resistance is 54 Ω.
Communications Unit Connection Diagram
E5CN-H
38
E5AN/EN-H
• The RS-485 connection can be either one-to-one or one-to-N. A maxi­mum of 32 Units (including the host computer) can be connected in one­to-N systems. The maximum total cable length is 500 m. Use AWG24
2
(cross-sectional area: 0.205 mm
2
2.081 mm
) shielded twisted-pair cable.
) to AWG14 (cross-sectional area:
Page 63
Wiring Terminals Section 2-2
SD
RD
SG
RS-232C
RD (RXD) SD (TXD) ER (DTR) SG
DR (DSR) RS (RTS)
CS (CTS)
3 4 5 6 7
2
8
11
No.
12 13
SD RD SG
1
FG
SD (TXD) RD (RXD)
RS (RTS) CS (CTS) DR (DSR) SG ER (DTR)
3 4 5 6 7
20
2
11
No.
12 13
SD RD SG
E53-CN@01N2 (for E5CN-H) E53-EN01 (for E5AN/EN-H)
Host computer RS-232C: 25-pin
E5@N-H
RS-232C
Host computer (DOS/V) RS-232C: 9-pin
E5@N-H
RS-232C
K L
SDB
SDA
M
SG
U
V
RS-422
E5AN/EN-H@M@-500 with an E53-EN02
RDB
RDA
RS-232C
• When communications are to be used with the E53-CN01N2 for the E5CN-H, or the E53-EN01 for the E5AN/EN-H, connect communications cable across terminals 11 to 13.
• A 1:1 connection is used. The maximum cable length is 15 m. To extend the transmission path, use the OMRON Z3R RS-232C Optical Interface.
2
• Use AWG24 (cross-sectional area: 0.205 mm
2
tional area: 2.081 mm
) shielded twisted-pair cable.
Cross-sectional area of conductor AWG24: 0.205 mm AWG14: 2.081 mm
) to AWG14 (cross-sec-
2
2
RS-422 (E5AN/EN-H Only)
• When communications are to be used with the E53-EN02 for the E5AN/ EN-H, connect Communications Cable across terminals 11 to 13 and 21 to 22.
39
Page 64
Using the Support Software Port Section 2-3
22
21
12
SDA
SDB
RDA
11 RDB
13 SG
RS-422
Shielded cable
RDA
RDB
SDA
SDB
SG
FG
RS-422
Host computer
22
21
12
SDA
SDB
RDA
11 RDB
13 SG
RS-422
Two Terminators (240 Ω, 1/2 W)
E5AN/EN-H (No.1)
E5AN/EN-H (No.31)
No.
No.
Cross-sectional area of conductor AWG24: 0.205 mm
2
AWG14: 2.081 mm
2
• A 1:1 or 1:N connection is used. When a 1:N connection is used, a maxi­mum of 32 nodes including the host computer can be connected.
2
• Use AWG24 (cross-sectional area: 0.205 mm
2
tional area: 2.081 mm
) shielded twisted-pair cable.
) to AWG14 (cross-sec-

2-3 Using the Support Software Port

Use the communications port for Support Software to connect the personal computer to the Digital Controller when using EST2-2C-MV4 CX-Thermo or a version of CX-Thermo higher than 4.00, or other Support Software. The E58­CIFQ1 USB-Serial Conversion Cable is required to make the connection.
For information concerning the models that can be used with CX-Thermo, contact your OMRON sales representative.
Procedure Use the following procedure to connect the Digital Controller to the personal
computer using the USB-Serial Conversion Cable. The USB-Serial Conver­sion Cable is used to communicate with the COM port of the personal com­puter. To perform communications using USB-Serial Conversion Cable, set the communications port (COM port) number to be used for the software to the COM port assigned to the Cable.
1,2,3... 1. Turn ON the power to the Digital Controller.
2. Connect the Cable.
Note If the Cable is connected when the power to the Digital Controller
Connect the personal computer’s USB port with the Support Software port on the Digital Controller using the Cable.
is OFF, power will be supplied from the personal computer and im­pose a load on the internal circuits of the Digital Controller.
40
Page 65
Using the Support Software Port Section 2-3
• Digital Controller Connection Method
E5CN-H
Communications port
Personal computer's USB port
E58-CIFQ1
Bottom view of E5CN-H
E5AN-HE5EN-H
for Support Software
Communications port for Support Software
Note Hold the connector when inserting or disconnecting the Cable.
3. Install the driver. Install the driver to enable the Cable to be used with the personal comput­er.
• Installation When the Cable is connected with the personal computer, the OS detects the product as a new device. At this time, install the driver using the instal­lation wizard. For details on installation methods, refer to the user’s man­ual for the E58-CIFQ1 USB-Serial Conversion Cable.
4. Setting Setup Tool Communications Conditions Set the communications port (COM port) number to be used for the CX­Thermo Setup Tool to the COM port number assigned to the USB-Serial Conversion Cable. Refer to the E58-CIFQ1 USB-Serial Conversion Cable Instruction Manual and Setup Manual for details on how to check the COM port assigned to the USB-Serial Conversion Cable. The communications conditions for Setup Tool COM ports are fixed as shown in the table below. Set the communications conditions for the CX­Thermo Setup Tool according to the following table.
Communications Unit No. 01
Communications baud rate 38.4 (kbps)
Communications data length 7 (bits)
Communications stop bits 2 (bits)
Communications parity Even
Communications port for Support Software
Bottom view of E5EN-H
Parameter Set value
Bottom view of E5AN-H
41
Page 66
Using Infrared Communications Section 2-4

2-4 Using Infrared Communications

When a Setup Tool, such as CX-Thermo version 4.00 or later (EST2-2C-MV4 or later), is used, the personal computer and Digital Controller can be con­nected using infrared communications. Using infrared communications enables the personal computer and Digital Controller to be connected from the front panel while ensuring a dust-tight and drip-tight structure. Use a USB­Infrared Conversion Cable, and connect it to the USB port at the personal computer. Infrared communications are supported only for the E5AN-H and E5EN-H. The infrared communications port and the Setup Tool port cannot be used at the same time.
For information concerning the models that can be used with the CX-Thermo, contact your OMRON sales representatives.
Procedure Use the following procedure to connect the Digital Controller to the personal
computer using the USB-Infrared Conversion Cable. The USB-Infrared Con­version Cable is used to communicate with the COM port on the personal computer. To perform communications using the USB-Infrared Conversion Cable, set the communications port (COM port) number to be used for the Setup Tool (such as CX-Thermo) to the COM port assigned to the Cable.
1,2,3... 1. Connecting the USB-Infrared Conversion Cable to the Personal Computer
Connect the USB-Infrared Conversion Cable to the USB port on the per­sonal computer.
2. Install the driver Install the driver to enable the USB-Infrared Conversion Cable to be used with the personal computer.
• Installation When the Cable is connected with the personal computer, the OS will detect is as a new device. At this time, install the driver using the installa­tion wizard. For details on installation methods, refer to the Instruction Sheet and Setup Manual for the E58-CIFIR USB-Infrared Conversion Cable.
3. Enabling Digital Controller Infrared Communications Mount the Digital Controller to the panel and wire it. Turn ON the power supply for the Digital Controller, go to the adjustment level, and set the In­frared Communications Use parameter to ON. When this parameter is set to ON, the Ir indicator on the front panel of the Digital Controller will light. This enables connecting to a personal computer using infrared communi­cations.
42
Lit when Infrared Communications Use parameter is set to ON.
E5EN-H Series E5AN-H Series
Page 67
Using Infrared Communications Section 2-4
Line on label
Insert up to the line
4. Connecting the USB-Infrared Conversion Cable to the Digital Controller Mount the enclosed adapter to the Digital Controller. Hold the USB-Infra­red Conversion Cable with the label side facing up, and insert the Cable into the adapter to the line specified on the label.
Mounting adapters
E5EN-H Series
E5AN-H Series
5. Setting the Setup Tool Communications Conditions Set the communications port (COM port) number to be used for the CX­Thermo Setup Tool to the COM port number assigned to the USB-Infrared Conversion Cable. Refer to the E58-CIFIR USB-Infrared Conversion Cable Instruction Sheet and Setup Manual for details on checking the COM port assigned to the USB-Infrared Conversion Cable. The communications conditions for infra­red COM ports are fixed as shown in the table below. Set the communica­tions conditions for the CX-Thermo Setup Tool according to the following table.
Parameter Set value
Communications Unit No. 01
Communications baud rate 38.4 (kbps)
Communications data length 7 (bits)
Communications stop bits 2 (bits)
Communications parity Even
6. Checking the Settings After completing all data transfers, be sure that the data is correct. Finally, remove the USB-Infrared Conversion Cable and mounting adapter from the Digital Controller and set the Infrared Communications Use parameter to OFF. Operation can now be started.
Turn ON the Infrared Communications Use parameter only when connect­ed to the Setting Tool through infrared communications. Leave it set to OFF during normal operation.
43
Page 68
Using Infrared Communications Section 2-4
44
Page 69
SECTION 3
Basic Operation
This section describes the basic operation of the E5CN-H, E5AN-H, and E5EN-H Digital Controllers, including key operations to set parameters and descriptions of display elements based on specific control examples.
3-1 Initial Setting Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
3-2 Setting the Input Type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
3-2-1 Input Type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
3-3 Selecting the Temperature Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
3-3-1 Temperature Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
3-4 Selecting PID Control or ON/OFF Control . . . . . . . . . . . . . . . . . . . . . . . . . . 51
3-5 Setting Output Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
3-5-1 Control Periods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
3-5-2 Direct and Reverse Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
3-5-3 Assigned Output Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
3-6 Setting the Set Point (SP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
3-6-1 Changing the SP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
3-7 Using ON/OFF Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
3-7-1 ON/OFF Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
3-7-2 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
3-8 Determining PID Constants (AT, ST, Manual Setup) . . . . . . . . . . . . . . . . . . 60
3-8-1 AT (Auto-tuning) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
3-8-2 ST (Self-tuning) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
3-8-3 RT (Robust Tuning) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
3-8-4 Manual Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
3-9 Alarm Outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
3-9-1 Alarm Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
3-9-2 Alarm Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
3-10 Using Heater Burnout, Heater Short, and Heater Overcurrent Alarms. . . . . . 71
3-10-1 Heater Burnout, Heater Short,
and Heater Overcurrent Alarm Operations. . . . . . . . . . . . . . . . . . . . 71
3-10-2 Installing Current Transformers (CT). . . . . . . . . . . . . . . . . . . . . . . . 72
3-10-3 Calculating Detection Current Values . . . . . . . . . . . . . . . . . . . . . . . 73
3-10-4 Application Examples. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
3-10-5 Settings: HB Alarm. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
3-10-6 Settings: Heater Short Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
3-10-7 Settings: Heater Overcurrent Alarm . . . . . . . . . . . . . . . . . . . . . . . . . 80
3-11 Setting the No. 3 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
3-11-1 PV/SP Display Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
45
Page 70
Initial Setting Examples Section 3-1
25.0
0.0
C
in-t
0
cntl
pid
cntl
M
M
M
pid
in-l
0
in-h
100
Changing Parameters
A image means that there are parameters. Continue pressing the M key to change parameters until you reach the intended parameter.
Changing Numbers
Numeric data and selections in each screen can be changed by using the
U and D keys.
100.0
20.0
onof
pid
run stop
25.0
0.0
C
in-t
5
cntl
onof
alt1
2
25.0
100.0
C
r-s
run
al-1
20.0
C
M
M
M
M
M
M
Input type: 5 (K thermocouple,
−200.0°C to 1,300.0°C)
Control method: ON/OFF control Alarm type: 2 (upper limit) Alarm value 1: 20°C (deviation) Set point: 100°C
Setup Procedure
Power ON
Initial Setting Level
Set input specifications
Set control specifications
Set alarm type
Operation Level
Set alarm values
Start operation
Power ON
Operation Level
PV/SP
Press the O key for at least 3 s.
Control stops.
Initial Setting Level
Input Type: 5
Check that control method is ON/OFF control.
ON/OFF control:
PID control:
Check alarm type.
Check input type.
Alarm 1 Type: 2
Press the O key for at least 1 s.
Control starts.
Operation Level
Use the U and D keys to set the SP to 100°C.
PV/SP:
Confirm that control is running.
Running
Stopped:
Use the U and D keys to set the alarm value to 20°C.
Alarm Value 1:
Start operation.

3-1 Initial Setting Examples

Initial hardware setup, including the sensor input type, alarm types, control periods, and other settings is done using parameter displays. The O and M Keys are used to switch between parameters, and the amount of time that you press the keys determines which parameter you move to.
This section describes 3 typical examples.
Explanation of Examples
Example 1
46
Page 71
Initial Setting Examples Section 3-1
9
20
30.0
2
150.0
onof
pid
on
off
off
run stop
Input type: 9 (T thermocouple,
−200.0°C to 400.0°C)
Control method: PID control PID constants found using auto-tuning (AT). Alarm type: 2 upper limit Alarm value 1: 30°C Set point: 150°C
Setup Procedure
Power ON
Initial Setting Level
Set input specifications
Set control specifications
Set alarm type
Adjustment Level
AT execution
(When PID control is selected)
Operation Level
Set alarm value
Start operation
Power ON
25.0
0.0
C
in-t
9
cntl
pid
st
off
cp
20
alt1
2
25.0
150.0
C
at
off
25.0
150.0
C
r-s
run
al-1
30.0
C
at
at-1
at
off
26.0
150.0
C
25.0
150.0
C
M
M
M
M
M
M
M
M
Operation Level
PV/SP
Press the O key for at least 3 s.
Control stops.
Initial Setting Level
Use the U and D keys to select the input type.
Input Type:
Use the U and D keys to select PID control.
ON/OFF control:
Use the U and D keys to set ST to OFF.
To execute ST:
PID control:
To cancel ST:
Check the control period.
Control Period (Heat) (Unit: Seconds)
Check the alarm type.
Alarm 1 Type:
When ON, self-tuning operates.
It is recommended that 20 seconds be set for a relay output and 2 seconds for an SSR voltage output.
Press the O key for at least 1 s.
Operation Level
Use the U and D keys to set the SP to 150°C.
PV/SP:
Adjustment Level
Execute AT.
To execute 100%AT:
To cancel AT:
To execute 100% AT (auto-tuning), select at-2. To execute 40% AT, select at-1. To cancel AT, select off: (AT cancel).
Press the O key (for less than 1 s).
Press the O key (for less than 1 s).
Control starts.
Operation Level
Confirm that the set point is 150°C.
PV/SP
Confirm that control is running.
Running Stopped
Use the U and D keys to set the alarm value to 30°C.
Alarm Value 1
Start operation.
PV/SP after AT is stopped
The set point flashes during auto-tuning (AT) execution.
After AT is stopped
During AT execution
at-1
To execute 40%AT:
at-2
Example 2
47
Page 72
Initial Setting Examples Section 3-1
Example 3
Input type: 5 (K thermocouple,
−200.0°C to 1,300.0°C)
Control method: Floating control (default) SP ramp time unit: EU/min (default) Travel time: 45 s SP ramp set value: 10.0 EU (°C) Set point: 250°C
Setup Procedure
Power ON
Initial Setting Level
Set input
specifications
Set control
specifications
Set travel time
Operation Level
Initial Setting Level
Check input type.
Check that control method is floating control.
Use the
U and D
keys to set the travel time to 45.
Operation Level
Use the U and D keys to set the SP to 250.0°C.
Power ON
c
25.0
0.0
Press the O key for at least 3 s.
in-t
5
M
clfl
flot
M
mot
45
M
Press the O key for at least 1 s.
c
25.0
250.0
PV/SP
Control stops.
Input Type:
Floating control:
Close control:
Travel time:
5
Control starts.
PV/SP:
250.0
flot
clos
45
Adjustment Level
Set SP ramp
Start operation
Adjustment Level
U and D
Use the keys to set the SP ramp set value to
10.0°C.
Operation Level
Confirm that control is running.
Press the O key (for less than 1 s).
at
off
M
sprt
10.0
10.0
Press the O key (for less than 1 s).
c
25.0
250.0
M
r-5
run
M
Start operation.
SP ramp set value:
PV/SP:
250.0
Running
Stopped
run
stop
48
Page 73
Setting the Input Type Section 3-2
C
25.0
0.0
in-t
5
Input Type
in-t
6

3-2 Setting the Input Type

The Controller supports 3 input types: platinum resistance thermometer, ther­mocouple, and analog inputs. Set the input type that matches the sensor that is used.

3-2-1 Input Type

The following example shows how to set a K thermocouple for −20.0 to
500.0°C.
Operating Procedure
Operation Level
1. Press the O Key for at least three seconds to move from the operation
level to the initial setting level.
Initial Setting Level
List of Input Types
Input type Specifications Set value Input temperature setting range
Platinum resistance thermometer
Thermocouple K
Pt100 0 −200.0 to 850.0 (°C)/−300.0 to 1,500.0 (°F)
JPt100 3 −199.9 to 500.0 (°C)/−199.9 to 900.0 (°F)
J7−100.0 to 850.0 (°C)/−100.0 to 1,500.0 (°F)
T9−200.0 to 400.0 (°C)/−300.0 to 700.0 (°F)
E11−200.0 to 600.0 (°C)/−300.0 to 1,100.0 (°F) L12−100.0 to 850.0 (°C)/−100.0 to 1,500.0 (°F) U13−200.0 to 400.0 (°C)/−300.0 to 700.0 (°F)
N15−200.0 to 1,300.0 (°C)/−200.0 to 2,300.0 (°F) R 16 0.0 to 1,700.0 (°C)/0.0 to 3,000.0 (°F) S 17 0.0 to 1,700.0 (°C)/0.0 to 3,000.0 (°F)
B 1 W 19 0.0 to 2,300.0 (°C)/0.0 to 3,200.0 (°F) PLII 20 0.0 to 1,300.0 (°C)/0.0 to 2,300.0 (°F) K21−50.00 to 200.00 (°C)/−50.00 to 200.00 (°F) J22−50.00 to 200.00 (°C)/−50.00 to 200.00 (°F) T23−50.00 to 200.00 (°C)/−50.00 to 200.00 (°F)
2. Press the U Key to enter the set value of the desired sensor.
When you use a K thermocouple (−20.0 to 500.0°C), enter 6 as the set value.
Hint: The key operation is saved two seconds after the change, or by press-
ing the O or M Key.
1 −199.9 to 500.0 (°C)/−199.9 to 900.0 (°F) 2 0.0 to 100.0 (°C)/0.0 to 210.0 (°F)
4 0.0 to 100.0 (°C)/0.0 to 210.0 (°F) 5 −200.0 to 1,300.0 (°C)/−300.0 to 2,300.0 (°F) 6 −20.0 to 500.0 (°C)/0.0 to 900.0 (°F)
8 −20.0 to 400.0 (°C)/0.0 to 750.0 (°F)
10 −199.9 to 400.0 (°C)/−199.9 to 700.0 (°F)
14 −199.9 to 400.0 (°C)/−199.9 to 700.0 (°F)
8 100.0 to 1,800.0 (°C)/300.0 to 3,200.0 (°F)
49
Page 74
Setting the Input Type Section 3-2
Input type Specifications Set value Input temperature setting range
Platinum resistance thermometer
Current input 4 to 20 mA 25 Either of the following ranges, by scaling:
Voltage input 1 to 5 V 27
Pt100 24 −50.0 to 200.0 (°C)/−50.0 to 200.0 (°F)
0 to 20 mA 26
0 to 5 V 28
0 to 10 V 29
−19999 to 32400
−1999.9 to 3240.0
−199.99 to 324.00
−19.999 to 32.400
• The default is 5.
• If a platinum resistance thermometer is mistakenly connected while a set­ting for other than a platinum resistance thermometer is in effect, S.ERR will be displayed. To clear the S.ERR display, check the wiring and then
turn the power OFF and back ON.
50
Page 75
Selecting the Temperature Unit Section 3-3
C
30.0
0.0
in-t
5
Input Type
d-u
c
Temperature Unit

3-3 Selecting the Temperature Unit

3-3-1 Temperature Unit

• Either °C or °F can be selected as the temperature unit.
• Set the temperature unit in the Temperature Unit parameter of the initial setting level. The default is c (°C).
Operating Procedure The following example shows how to select °C as the temperature unit.
Operation Level
Initial Setting Level
1. Press the O Key for at least three seconds to move from the operation
level to the initial setting level.
2. Select the Temperature Unit parameter by pressing the M Key.
Press the U or D Key to select either °C or °F.
c: °C f: °F
3. To return to the operation level, press the O Key for at least one second.

3-4 Selecting PID Control or ON/OFF Control

Two control methods are supported: 2-PID control and ON/OFF control. Switching between 2-PID control and ON/OFF control is executed by means of the PID ON/OFF parameter in the initial setting level. When this parameter is set to pid, 2-PID control is selected, and when set to onoff, ON/OFF con­trol, is selected. The default is pid. ON/OFF control is not displayed for posi- tion-proportional models.
2-PID Control PID control is set by AT (auto-tuning), ST (self-tuning), or manual setting.
For PID control, set the PID constants in the Proportional Band (P), Integral Time (I), and Derivative Time (D) parameters.
ON/OFF Control In ON/OFF control, the control output is turned ON when the process value is
lower than the current set point, and the control output is turned OFF when the process value is higher than the current set point (reverse operation).
51
Page 76
Setting Output Specifications Section 3-5
cp
c-cp
Control Period (Heating)
Control Period (Cooling)
100%
0%
100%
0%
Manipulated variable Manipulated variable
Low temperature
Set Value High
temperature
Low temperature
Set Value High
temperature
Direct operation Reverse operation

3-5 Setting Output Specifications

The following table shows the parameters related to outputs. Each of the parameters is described in detail following the table.
(

3-5-1 Control Periods

Parameter Standard
models
cp Control Period (Heating)
c-cp Control Period (Cooling)
orev Direct/Reverse Operation 
out1 Control Output 1 Assignment
out2 Control Output 2 Assignment
sub1 Auxiliary Output 1 Assignment 
sub2 Auxiliary Output 2 Assignment 
sub3 Auxiliary Output 3 Assignment
: Supported)
• Set the output periods (control periods). Though a shorter period provides better control performance, it is recommended that the control period be set to 20 seconds or longer for a relay output to preserve the service life of the relay. After the settings have been made in the initial setup, readjust the control period, as required, by means such as trial operation.
• Set the control periods in the Control Period (Heating) and Control Period (Cooling) parameters in the initial setting level. The default is 20 seconds.
• The Control Period (Cooling) parameter is used only for heating/cooling control.
• When the control output is used as a current output or linear voltage out­put, the Control Period settings cannot be used.
• The control period can be set for standard models only.
Position-
proportional
models

3-5-2 Direct and Reverse Operation

• Direct operation increases the manipulated variable whenever the pro-
52
cess value increases. Reverse operation decreases the manipulated vari­able whenever the process value increases.
Page 77
Setting Output Specifications Section 3-5
C
30.0
0.0
in-t
5
Input Type
d-u
c
Temperature Unit
cp
20
Control Period (Heating)
orev
or-r
Direct/Reverse Operation
C
30.0
0.0
PV/SP
For example, when the process value (PV) is lower than the set point (SP) in a heating control system, the manipulated variable increases according to the difference between the PV and SP. Accordingly, reverse operation is used in a heating control system. Direct operation is used in a cooling con­trol system, in which the operation is the opposite of a heating control sys­tem.
• Direct/reverse operation is set in the Direct/Reverse Operation parameter in the initial setting level. The default is or-r (reverse operation).
Operating Procedure In this example, the input type, temperature unit, direct/reverse operation, and
control period (heat) parameters are checked.
Input type = s (K thermocouple) Temperature unit = c (°C) Direct/reverse operation = or-r (reverse operation) Control period (heat) = 20 (seconds)
Operation Level
Initial Setting Level
Operation Level
1. Press the O Key for at least three seconds to move from the operation
level to the initial setting level.
2. The input type is displayed. When the input type is being set for the first
time, s (K thermocouple) is set. To select a different sensor, press the U or D Key.
3. Select the Temperature Unit parameter by pressing the M Key. The de-
fault is c (°C). To select f (°F), press the U Key.
4. Select the Control Period (Heating) parameter by pressing the M Key.
The default is 20.
5. Select the Direct/Reverse Operation parameter by pressing the M Key. The default is or-r (reverse operation). To select or-d (direct opera- tion), press the U Key.
6. To return to the operation level, press the O Key for at least one second.

3-5-3 Assigned Output Functions

• Function assignments can be changed by changing the settings for con­trol and auxiliary output assignments.
• The default function assignments for each output are shown below.
Parameter name Symbol Initial status
Control Output 1 Assignment out1 Control output (heating) Control Output 2 Assignment out2 Not assigned. Auxiliary Output 1 Assignment sub1 Alarm 1
53
Page 78
Setting Output Specifications Section 3-5
C
25.0
100.0
PV/SP
in-t
5
Input Type
5-hc
stnd
Standard or Heating/Cooling
Parameter name Symbol Initial status
Auxiliary Output 2 Assignment sub2 Alarm 2
Auxiliary Output 3 Assignment (E5AN/EN-H only)
sub3 Alarm 3
• Each output is automatically initialized as shown below by changing the control mode.
Example: E5CN-H
Parameter name Symbol Without control output 2 With control output 2
Standard Heating/cooling Standard Heating/cooling
Control Output 1 Assignment
Control Output 2 Assignment
Auxiliary Output 1 Assignment
Auxiliary Output 2 Assignment
out1 Control output
(heating)
out2 Not assigned.
(See note 1.)
sub1 Alarm 1
(See note 2.)
sub2 Alarm 2 Control output
Control output (heating)
Not assigned. (See note 1.)
Alarm 1 (See note 2.)
(cooling)
Control output (heating)
Not assigned. Control output
Alarm 1 (See note 2.)
Alarm 2 Alarm 2
Control output (heating)
(cooling)
Alarm 1 (See note 2.)
Note (1) There is no control output 2 and no parameter assignment is displayed
for that output.
(2) The Auxiliary Output 1 Assignment parameter becomes the program end
output unless the Program Pattern parameter is set to OFF.
■ Alarms
It will be specified in this section when an alarm must be assigned, i.e., when an alarm must be set for the Control Output 1 or 2 Assignment parameters, or for the Auxiliary Output 1 or 3 Assignment parameters. For example, if alarm 1 is set for the Control Output 1 Assignment parameter, then alarm 1 has been assigned.
Assigning a work bit to either control output 1 or 2 or to auxiliary output 1 to 3 is also considered to be the same as assigning an alarm. For example, if work bit 1 is set for the Auxiliary Output 1 Assignment parameter, then alarms 1 to 3 have been assigned.
Operating Procedure This procedure sets the following control and auxiliary output assignments.
Control output 1: Control output (heating); Control output 2: Control output (cooling); Auxiliary output 1: Alarm 1; Auxiliary output 2: Alarm 2
Operation Level
1. Press the O Key for at least three seconds to move from the operation
level to the initial setting level.
Initial Setting Level
2. Select the Standard or Heating/Cooling parameter by pressing the M
Key.
Initial Setting Level
54
Page 79
Setting Output Specifications Section 3-5
5-hc
h-c
amov
0
Move to Ad- vanced Function Setting Level
init
off
Parameter Initialization
out1
o
Control Output 1 Assignment
out1
o
out2
c-o
Control Output 2 Assignment
out2
c-o
sub1
alm1
Auxiliary Output 1 Assignment
sub1
alm1
sub2
alm2
Auxiliary Output 2 Assignment
sub2
alm2
Initial Setting Level
Advanced Function Setting Level
Advanced Function Setting Level
Advanced Function Setting Level
3. Press the U Key to set the parameter to h-c.
Note The following output assignments do not need to be set because they
are set automatically by changing the control mode, but they are shown here as a reference for checking the assignments for each out­put.
4. Select the Move to Advanced Function Setting Level parameter by press-
ing the M Key. (For details on moving between levels, refer to 4-8 Mov- ing to the Advanced Function Setting Level.)
5. Press the D Key to enter the password (“−169”), and move from the initial
setting level to the advanced function setting level.
6. Select the Control Output 1 Assignment parameter by pressing the M
Key.
7. Press the U or D Key to set o. (The default is o.)
8. Select the Control Output 2 Assignment parameter by pressing the M Key.
Advanced Function Setting Level
Advanced Function Setting Level
9. Press the U or D Key to set c-o. (When h-c is selected for the Standard or Heating/Cooling parameter, the setting will be c-o.)
10. Select the Auxiliary Output 1 Assignment parameter by pressing the M Key.
11. Press the U or D Key to set alm1. (The default is alm1.)
12. Select the Auxiliary Output 2 Assignment parameter by pressing the M Key.
13. Press the U or D Key to set alm2. (The default is alm2.)
55
Page 80
Setting the Set Point (SP) Section 3-6
in-t
5
Input Type
C
25.0
100.0
PV/SP
C
20.0
0.0
C
20.0
0.0
50.0
Initial Setting Level
Operation Level
Auxiliary Output Opening or Closing in Alarm
14. Press the O Key for at least one second to move from the advanced function setting level to the initial setting level.
15. Press the O Key for at least one second to move from the initial setting level to the operation level.
• When “close in alarm” is set, the status of the auxiliary output is output unchanged. When “open in alarm” is set, the status of the auxiliary output function is reversed before being output.
• Each auxiliary output can be set independently.
• These settings are made in the Auxiliary Output 1 to 3 Open in Alarm parameters (advanced function setting level).
• The default is n-o: Close in Alarm.
• When “open in alarm” is set for the alarm 1 output, the open in alarm sta­tus is also applied to heater burnout, HS alarm, heater overcurrent, and input error outputs.
Auxiliary output functions 1 to 3
Close in Alarm ON ON Lit
OFF OFF Not lit
Open in Alarm ON OFF Lit
OFF ON Not lit
Auxiliary
output
Indicators
(SUB1 to SUB3)
• The alarm output will turn OFF (i.e., the relay contacts will open) when power is interrupted and for about two seconds after the power is turned ON regardless of the setting of the Auxiliary Output 1 to 3 Open in Alarm parameter.

3-6 Setting the Set Point (SP)

Operation Level
Operation Level

3-6-1 Changing the SP

The operation level is displayed when the power is turned ON. The process value (PV) is at the top of the display, and the set point (SP) is at the bottom.
For Controllers that support a No. 3 display (E5AN/E5EN-H), the contents set in the PV/SP Display Screen Selection parameter (advanced function setting level) are displayed below the PV and SP. The MV is displayed as the default. For details, refer to 3-11 Setting the No. 3 Display.
• The set point cannot be changed when the Operation/Adjustment Protect parameter is set to 3. For details, refer to 4-9 Using the Key Protect Level.
56
Page 81
Using ON/OFF Control Section 3-7
C
30.0
0.0
d.bnk
0
Display Bank Selection
d.bnk
3
3.lsp
0.0
C
Bank 3 SP 1
3.lsp
200.0
C
Bank 3 SP 1
• To change the set point, select the bank number in the Display Bank Selection parameter in the bank setting level, and press the U or D Key in the SP parameter (in the bank setting level) for each bank to set the desired set value. The new set point will be selected two seconds after the new value has been specified.
• If the SP parameter is changed in the operation level, the change will be reflected in the set point for the current bank.
• The bank function can be used to change eight set points. For details, refer to Banks on page 128.
Operating Procedure In this example, the set point in bank 3 is changed from 0°C to 200°C.
Operation Level
Bank Setting Level
1. Normally, the Process Value/Set Point parameter is displayed. The set
point is 0.0°C.
2. The current bank number will be displayed.
Press the O Key to move the bank setting level.
3. Press the U or D Key to set 3.
4. Select the Bank 3 SP parameter by pressing the M Key.
5. Press the U and D Keys to set 200.0.

3-7 Using ON/OFF Control

3-7-1 ON/OFF Control

In ON/OFF control, the control output turns OFF when the temperature being controlled reaches the preset set point. When the manipulated variable turns OFF, the temperature begins to fall and the control turns ON again. This oper­ation is repeated over a certain temperature range. At this time, how much the temperature must fall before control turns ON again is determined by the Hys­teresis (Heating) parameter. Also, what direction the manipulated variable must be adjusted in response to an increase or decrease in the process value is determined by the Direct/Reverse Operation parameter.
• Switching between 2-PID control and ON/OFF control is performed using the PID ON/OFF parameter in the initial setting level. When this parame­ter is set to pid, 2-PID control is selected, and when it is set to onof, ON/ OFF control is selected. The default is pid.
• ON/OFF control can be set for standard models only.
57
Page 82
Using ON/OFF Control Section 3-7
PV
ON
OFF
Reverse operation
Hysteresis (heating)
Set point
C
25.0
100.0
PV
Hysteresis • With ON/OFF control, hysteresis is used to stabilize operation when
switching between ON and OFF. The control output (heating) and control output (cooling) functions are set in the Hysteresis (Heating) and Hystere­sis (Cooling) parameters, respectively.
• In standard control (heating or cooling control), the setting of the Hystere­sis (Heating) parameter in the adjustment level is used as the hysteresis regardless of whether the control type is heating control or cooling con­trol.
Three-position Control

3-7-2 Settings

• In heating/cooling control, a dead band (an area where both control out­puts are 0) can be set to either the heating or cooling side. This makes it possible to use 3-position control.
Reverse operation
Dead band
Hysteresis (heating) Hysteresis (cooling)
ON
Heating side
OFF
Set point
Cooling side
PV
Parameters
Symbol Parameter: level Application
s-hc cntl orev c-db hys chys
Standard or Heating/Cooling: Initial setting level PID ON/OFF: Initial setting level Direct/Reverse Operation: Initial setting level Dead Band: Adjustment level Hysteresis (Heating): Adjustment level Hysteresis (Cooling): Adjustment level
Specifying control method Specifying control method Specifying control method Heating/cooling control ON/OFF control ON/OFF control
To execute ON/OFF control, set the Set Point, PID ON/OFF, and Hysteresis parameters.
Setting the PID ON/OFF Parameter
Operating Procedure The following example shows how to change the PID ON/OFF parameter to
onof in the initial setting level.
Operation Level
1. Press the O Key for at least three seconds to move from the operation
level to the initial setting level.
58
Page 83
Using ON/OFF Control Section 3-7
in-t
5
Input Type
cntl
pid
PID•ON/OFF
cntl
onoff
PID•ON/OFF
C
25.0
100.0
PV/SP
C
25.0
200.0
C
25.0
200.0
PV/SP
1.adj
Adjustment Level Display
hys
1.0
Hysteresis (Heating)
C
hys
2.0
C
Initial Setting Level
2. The Input Type parameter is displayed in the initial setting level.
3. Select the PID ON/OFF parameter by pressing the M Key.
4. Use the U and D Keys to set onof.
5. To return to the operation level, press the O Key for at least one second.
Next, set the set point value.
Setting the SP
Operating Procedure In this example, the set point is set to 200.0. The set value (i.e., the SP) is
shown at the bottom of the display.
Operation Level
1. Select the Process Value/Set Point parameter in the operation level.
2. Use the U and D Keys to set the SP. (In this example, it is set to 200.0.) The new set value can be saved by pressing the M Key, or it will go into effect after two seconds have elapsed. (The new set point will be reflected in the current bank.)
Next, set the hysteresis.
Setting the Hysteresis
Operating Procedure Set the hysteresis to 2.0°C.
Operation Level
Adjustment Level
1. Press the O Key to move from the operation level to the adjustment level.
2. The Adjustment Level Display parameter will be displayed in the adjust­ment level.
3. Select the Hysteresis (Heating) parameter by pressing the M Key.
4. Press the U and D Keys to set the hysteresis (2.0 in this example). Ei­ther press the M Key or wait for at least two seconds after setting the hys­teresis value to confirm the setting.
5. To return to the operation level, press the O Key.
59
Page 84
Determining PID Constants (AT, ST, Manual Setup) Section 3-8
at
∗
233.0
C
∗
.p
(0
∗
.d
40.0
PID Setting Level
PID* Proportional Band
PID* Integral Time
PID* Derivative Time
(∗: 1 to 8)
y
C
25.0
100.0
C
25.0
100.0
PV/SP
AT execution in progress
No. 2 display

3-8 Determining PID Constants (AT, ST, Manual Setup)

3-8-1 AT (Auto-tuning)

• When AT is executed, the optimum PID constants for the set point at that time are set automatically. A method (called the limit cycle method) for forcibly changing the manipulated variable and finding the characteristics of the control object is employed.
• Either 40% AT or 100% AT can be selected depending on the width of MV variation in the limit cycle. In the AT Execute/Cancel parameter, specify at-2 (100% AT) or at-1 (40% AT). To cancel AT, specify off (AT can­cel).
• Only 100% AT can be executed for heating and cooling control or for float­ing control for position-proportional models.
• AT cannot be executed when control has stopped or during ON/OFF con­trol.
• The results of AT are reflected in the Proportional Band (P), Integral Time (I), and Derivative Time (D) parameters for the PID set at the time AT exe­cution starts. For details on PID sets, refer to PID Sets on page 128.
Note If ST (self-tuning) parameter is set to ON in the initial setting level, ST is exe-
cuted the first time operation is started and whenever the set point is changed. This may cause the PID constants that were calculated by AT to be overwritten with new values. To retain the PID constants that were calculated by AT, turn OFF the ST parameter.
AT Operations AT is started when either at-2 (100% AT) or at-1 (40% AT) is specified for
Related parameter: ST (Self-tuning) (initial setting level)
the AT Execute/Cancel parameter. During execution, the AT Execute/Cancel parameter on the No. 1 display flashes. When AT ends, the AT Execute/Can­cel parameter turns OFF, and the No. 1 display stops flashing.
AT Execute/Cancel
at
off
100% AT execution in progress
If you move to the operation level during AT execution, the No. 2 display flashes to indicate that AT is being executed.
Only the Communications Writing, RUN/STOP, AT Execution/Cancel, and Pro­gram Start parameters can be changed during AT execution. Other parame­ters cannot be changed.
AT Calculated Gain
The AT Calculated Gain parameter sets the gain for when PID values are cal­culated using AT. When emphasizing response, decrease the set value. When emphasizing stability, increase the set value.
at
at-2
No. 1 displa
60
Page 85
Determining PID Constants (AT, ST, Manual Setup) Section 3-8
SP
PV
AT started
AT ended
Time
Limit Cycle MV Amplitude 40%
Deviation ≥ 10% FS
Deviation: 10% FS
Time
Deviation < 10% FS
SP
PV
AT started AT ended
Limit Cycle MV Amplitude 40%
Deviation: 10% FS
SP
PV
AT started AT ended
Time
Limit Cycle MV Amplitude 100%
at
off
AT Execute/ Cancel
at
at-2
at
off
AT Hysteresis
The AT Hysteresis parameter sets the hysteresis when switching ON and OFF for the limit cycle operation during auto-tuning.
Limit Cycle MV Amplitude
The Limit Cycle MV Amplitude parameter sets the MV amplitude for limit cycle operation during auto-tuning.
Note Disabled for 100% AT.
■ 40% AT
The width of MV variation in the limit cycle can be changed in the Limit Cycle MV Amplitude parameter, but the AT execution time may be longer than for 100% AT. The limit cycle timing varies according to whether the deviation (DV) at the start of auto-tuning execution is less than 10% FS.
■ 100% AT
Operation will be as shown in the following diagram, regardless of the devia­tion (DV) at the start of AT execution. To shorten the AT execution time, select 100% AT.
Note The Limit Cycle MV Amplitude parameter is disabled.
Operating Procedure This procedure executes 100%AT.
Adjustment Level
1. Press the O Key to move from the operation level to the adjustment level.
Press the M Key to select the AT Execute/Cancel parameter.
2. Press the U Key to select at-2. The No. 1 display for AT Execute/Cancel
will flash during AT execution.
3. off will be displayed when AT ends.
61
Page 86
Determining PID Constants (AT, ST, Manual Setup) Section 3-8
C
25.0
0.0
PV
st
in-t
5
Input Type
st
on
ST
C
25.0
100.0
PV
Operation Level
4. To return to the operation level, press the O Key.

3-8-2 ST (Self-tuning)

ST (self-tuning) is a function that finds PID constants by using step response tuning (SRT) when Digital Controller operation begins or when the set point is changed.
Once the PID constants have been calculated, ST is not executed when the next control operation is started as long as the set point remains unchanged.
ST (self-tuning) is enabled when the ST parameter is set to ON in the initial setting level.
When the ST function is in operation, be sure to turn the power supply of the load connected to the control output ON simultaneously with or before starting Controller operation.
When executing self-tuning, turn ON power for the load (e.g., heater) at the same time as or before supplying power to the Digital Controller. If power is turned ON for the Digital Controller before turning ON power for the load, self­tuning will not be performed properly and optimum control will not be achieved. ST can be set for standard models only.
Operating Procedure This procedure executes self-tuning (ST).
Initial Setting Level
Operation Level
1. Press the O Key for at least three seconds to move from the operation
level to the initial setting level.
2. Select the ST parameter by pressing the M Key.
3. Press the U Key to select on. ON is the default.
4. To return to the operation level, press the O Key for at least one second.
The temperature display flashes during self-tuning (ST) execution.
Note PID Constants
When control characteristics are already known, PID constants can be set directly to adjust control. PID constants are set in the Proportional Band (P), Integral Time (I), and Derivative Time (D) parameters, according to the Dis­play PID Selection parameter setting in the PID setting level. Changing the Proportional Band (P), Integral Time (I), or Derivative Time (D) parameter set­tings in the adjustment level changes the settings in these parameters in the current PID set.
62
Page 87
Determining PID Constants (AT, ST, Manual Setup) Section 3-8
Bank 0 PID set number = 1
Bank 1 PID set number = 2
Bank 0
Bank 1 Bank 0
Bank 1
Bank 0 PID set number = 1 Bank 0 PID set number = 1
SP=200
SP=200
SP=100
SP=100
Startup Conditions Self-tuning by step response tuning (SRT) is started when the following condi-
tions are met after program execution is started and the set point is changed.
At start of operation When set point is changed
1. The set point at the start of operation differs from the set point when the pre­vious SRT was executed. (See note 1.)
2. The difference between the tempera­ture at the start of operation and the set point is greater both of the following: (Present proportional band × 1.27 + 4°C) and the ST stable range.
3. The temperature at the start of opera­tion is lower than the set point during reverse operation, and is larger than the set point during direct operation.
4. There is no reset from input errors.
Note (1) The previous SRT-implemented set point is the set point that was used for
calculating the PID constants for the previous SRT.
(2) In this state, the measurement point is within the ST stable range.
(3) In this state, the change width of the PV every 60 seconds is within the
ST stable range or less.
In the following instances, PID constants are not changed by self-tuning (ST) for the present set point.
1. When the PID constants have been changed manually with ST set to ON.
2. When auto-tuning (AT) has been executed.
3. When the PID set has been changed during SRT.
4. When the PID set for the current bank is set to 0 (PID set automatic selec­tion).
In addition, the following diagrams show the difference between setting a dif­ferent PID set for each bank and setting the same PID set. For details on bank settings, refer to 4-15 Using Banks and PID Sets.
1. The new set point differs from the set point used when the previous SRT was executed. (See note 1.)
2. The set point change width is greater both of the following: (Present propor­tional band × 1.27 + 4°C) and the ST stable range.
3. During reverse operation, the new set point is larger than the set point before the change; and during direct opera­tion, the new set point is smaller than the set point before the change.
4. The temperature is stable. (See note
2.) (Equilibrium with the output amount at 0% when the power is turned ON is also all right.) (See note 3.)
1,2,3... 1. When operation starts, ST is executed for each bank and the PID con-
stants are saved for each PID set. Stable control is thus enabled, because ST is not executed when the bank is changed or when the next operation starts.
2. ST is executed each time the bank is changed, and PID constants are saved for the same PID set. Therefore ST is executed each time the bank is changed and when the next operation starts.
63
Page 88
Determining PID Constants (AT, ST, Manual Setup) Section 3-8
C
st-b
1%0
ST Stable Range
C
st-b
2*0
rt
ST Stable Range
Operating Procedure The ST stable range determines the condition under which ST (self-tuning)
functions. This procedure sets the ST stable range to 20°C.
Advanced Function Setting Level
1. Select the ST Stable Range parameter by pressing the M Key in the ad-
vanced function setting level.
2. Use the U Key to set the parameter to 20°C.

3-8-3 RT (Robust Tuning)

• When AT or ST is executed with RT selected, PID constants are automat­ically set that make it hard for control performance to degenerate even when the characteristics of the controlled object are changed.
• RT can be set in the advanced function setting level when PID control has been set.
• The RT mode cannot be selected while an analog input is set.
• Selecting the RT mode in the following cases will help to prevent hunting from occurring.
• When the set temperature is not constant and is changed in a wide
• When there are large variations in ambient temperatures due to factors
• When there are large variations in ambient wind conditions and air flow
• When heater characteristics change depending on the temperature
• When an actuator with disproportional I/O, such as a phase-control-
• When a rapidly heating heater is used
• When the control object or sensor has much loss time
• When hunting occurs in normal mode for any reason
• PID constants are initialized to the factory settings by switching to RT
• When the RT mode is selected, the derivative time setting unit be-
range
such as seasonal changes or differences between day and night tem­peratures
type power regulator, is used
mode.
comes the second.
RT Features • Even when hunting occurs for PID constants when AT or ST is executed
in normal mode, it is less likely to occur when AT or ST is executed in RT mode.
64
Page 89
Determining PID Constants (AT, ST, Manual Setup) Section 3-8
Temperature Temperature
Much hunting occurs.
Set value Set value
Start of control Start of control
Time Time
Hunting is reduced.
C
25.0
100.0
PV/SP
in-t
5
Input Type
amov
0
Move to Ad- vanced Function Setting Level
init
off
Parameter Initialization
rt
off
RT
• When the temperature (PV) falls short of the set point for the PID con­stants when using AT or ST in normal mode, executing AT or ST in RT mode tends to improve performance.
Temperature Temperature
Set value
Start of control Start of control
• When the manipulated variable (MV) is saturated, the amount of over­shooting may be somewhat higher in comparison to PID control based on AT or ST in normal mode.
Operating Procedure This procedure selects RT mode.
Operation Level
Initial Setting Level
Initial Setting Level
1. Press the O Key for at least three seconds to move from the operation
level to the initial setting level.
2. Select the Move to Advanced Function Setting Level parameter by press-
ing the M Key.
3. Use the D Key to enter “−169” (the password).
Time Time
Set value
Advanced Function Setting Level
Advanced Function Setting Level
4. Press the M Key to select rt.
It is possible to move to the advanced function setting level by pressing the M Key or leaving the setting for at least two seconds.
65
Page 90
Determining PID Constants (AT, ST, Manual Setup) Section 3-8
rt
on
in-t
5
Input Type
C
25.0
100.0
PV/SP
d.pid
1
Display PID Selection
d.pid
2
2.p
8.0
C
Proportional Band
2.p
10.0
C
2.i
233.0
Integral Time
2.i
250.0
2.d
40.0
Derivative Time
5. Press the U Key to select on. off is the default.
Initial Setting Level
Operation Level
6. To return to the initial setting level, press the O Key for at least one sec-
ond.
7. To return to the operation level, press the O Key for at least one second.

3-8-4 Manual Setup

PID constants can be manually and individually set in the Proportional Band (P), Integral Time (I), and Derivative Time (D) parameters, according to the Display PID Selection parameter set in the PID setting level. Changing the Proportional Band (P), Integral Time (I), or Derivative Time (D) parameter set­tings in the adjustment level changes the settings in the current PID set. For details on PID sets, refer to PID Sets on page 128.
Operating Procedure In this example, the PID 2 Proportional Band parameter is set to 10.0, the PID
2 Integral Time parameter to 250, and the PID 2 Derivative Time parameter to
45.
PID Setting Level
1. Press the O Key to move from the operation level to the PID setting level.
2. Use the U and D Keys to set 2.
3. Press the M Key to select the PID 2 Proportional Band parameter.
4. Use the U and D Keys to set 10.0.
5. Press the M Key to select the PID 2 Integral Time parameter.
6. Use the U and D Keys to set 250.0.
7. Press the M Key to select the PID 2 Derivative Time parameter.
66
Page 91
Alarm Outputs Section 3-9
2.d
45.0
X
ON OFF
SP
8. Use the U and D Keys to set 45.0.
9. To return to the operation level, press the O Key.
Note If ST (self-tuning) parameter is set to ON in the initial setting level, ST is exe-
cuted the first time operation is started and whenever the set point is changed. This may cause the manually set PID constants to be overwritten with new values. To retain the manually set PID constants, turn OFF the ST parameter.
Related parameter: ST (Self-tuning) (initial setting level)
Note Proportional Action
When PID constants I (integral time) and D (derivative time) are set to 0, con­trol is executed according to proportional action. As the default, the center value of the proportional band becomes the set point. Related parameter: Manual reset value (adjustment level)

3-9 Alarm Outputs

3-9-1 Alarm Types

• Alarm outputs are determined by a combination of Alarm Type, Alarm Value, and Alarm Hysteresis alarm output conditions. For details, refer to 4-2 Alarm Hysteresis.
• This section describes the Alarm Type, Alarm Value, Upper-limit Alarm and Lower-limit Alarm parameters.
Set value Alarm type Alarm output operation
When alarm value X
is positive
0 Alarm function OFF Output OFF
1 Upper- and lower-limit See note 2.
2 (See note
Upper-limit
1.)
3 Lower-limit
4 (See note
1.)
5 (See note
1.)
Upper- and lower-limit range
Upper- and lower-limit with standby sequence
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
LH
SP
X
SP
X
SP
LH
SP
LH
SP
See note 5.
When alarm value X
is negative
X
ON OFF
SP
ON OFF
X
SP
See note 3.
See note 4.
6 Upper-limit with standby
sequence
7 Lower-limit with standby
sequence
ON OFF
X
ON OFF
SP
X
SP
ON OFF
X
SP
67
Page 92
Alarm Outputs Section 3-9
X
ON OFF
0
ON OFF
X
0
X
ON OFF
0
X
ON OFF
0
ON OFF
X
0
X
ON OFF
0
X
ON OFF
0
ON OFF
X
0
LH
H < 0, L > 0
|H| < |L|
SP
LH
H > 0, L < 0
|H| > |L|
SP
LH
H < 0, L < 0
SP
LH
H < 0, L > 0
|H| ≥ |L|
SP
LH
H > 0, L < 0
|H| ≤ |L|
SP
Case 1 Case 2 Case 3 (Always ON)
0
Set value Alarm type Alarm output operation
8 Absolute-value upper-
limit
When alarm value X
is positive
ON OFF
X
0
When alarm value X
is negative
9 Absolute-value lower-limit
ON OFF
X
0
10 Absolute-value upper-
limit with standby sequence
11 Absolute-value lower-limit
with standby sequence
ON OFF
X
0
12 LBA (alarm 1 type only) ---
13 PV change rate alarm ---
14 Remote SP absolute
value upper limit (See note 6.)
15 Remote SP absolute
value lower limit (See note 6.)
ON OFF
X
0
Note (1) With set values 1, 4, and 5, the upper- and lower-limit values can be set
independently for each alarm type, and are expressed as “L” and “H.”
(2) Set value: 1 (Upper- and lower-limit alarm)
(3) Set value: 4 (Lower limit range)
Case 1 Case 2 Case 3 (Always OFF)
LH
H < 0, L > 0
|H| < |L|
SP
HL
SP
H > 0, L < 0
|H| > |L|
SP
LLH
SP
H
SP
H < 0, L <
LH
H < 0, L > 0
|H| ≥ |L|
H > 0, L < 0
|H| ≤ |L|
(4) Set value: 5 (Upper- and lower-limit with standby sequence)
• For the lower-limit alarms in cases 1 and 2 above, the alarm is always OFF if upper- and lower-limit hysteresis overlaps.
• In case 3, the alarm is always OFF.
(5) Set value: 5 (Upper- and lower-limit with standby sequence)
• The alarm is always OFF if upper- and lower-limit hysteresis overlaps.
(6) Displayed when remote SP input is used.
• Set the alarm type independently for each alarm in the Alarm 1 to 3 Type parameters in the initial setting level. The default is 2 (Upper-limit alarm).
68
Page 93
Alarm Outputs Section 3-9
∗
.a1l
∗
.a1h
∗
.a2l
∗
.a2h
∗
.a-1
∗
.a-2
∗
.a3l
∗
.a3h
∗
.a-3
Bank* Alarm Value Lower Limit
Alarm Value Upper Limit Value
Alarm Value
(∗: 0 to 7)
(
∗
: 0 to 7)
(
∗
: 0 to 7)
in-t
5
Input Type
alt1
2
Alarm 1 Type
C
25.0
100.0
PV/SP
d.bnk
0
Display Bank Selection
d.bnk
1

3-9-2 Alarm Values

• Alarm values are indicated by “X” in the table on the previous page. When the upper and lower limits are set independently, “H” is displayed for upper limit values, and “L” is displayed for lower limit values.
• To set the alarm upper and lower limits for deviation, set the upper and lower limits in the Alarm 1 to 3 Upper Limit and Alarm 1 to 3 Lower Limit parameters.
• Alarm values can be set for each bank. Select the bank number in the Display Bank Selection parameter in the bank setting level, and set the Alarm Value, Alarm Value Upper Limit (1 to 3), and Alarm Value Lower Limit (1 to 3) parameters for that bank.
• When the Alarm Value, Alarm Value Upper Limit, and Alarm Value Lower Limit parameters in the operation level are changed, the changes will be reflected in those parameters for the current bank.
Operating Procedure This procedure sets alarm 1 for bank number 1 as an upper-limit alarm. The
related parameters and settings are shown below. The alarm is output when the set point exceeds 10°C. (In this example, the temperature unit is °C.)
Alarm 1 type = 2 (Upper-limit alarm) Bank 1 Alarm value 1 = 10
Initial Setting Level
Bank Setting Level
1. Press the O Key for at least three seconds to move from the operation
level to the initial setting level.
2. Select the Alarm 1 Type parameter by pressing the M Key. Confirm that
the set value is 2. The default value is 2 (Upper-limit alarm).
3. To return to the operation level, press the O Key for at least one second.
4. Press the O Key to move to the bank setting level.
5. Use the U and D Keys to set 1.
69
Page 94
Alarm Outputs Section 3-9
1.a-1
0.0
C
Bank 1 Alarm Value 1
1.a-1
10.0
C
6. Press the M Key to select the Bank 1 Alarm Value 1 parameter.
7. Use the U Key to set 10.0.
PV Change Rate Alarm The change width can be found for PV input values in any set period. Differ-
ences with previous values in each set period are calculated, and an alarm is output if the result exceeds the alarm value. The PV rate of change calculation period can be set in units of 60 ms.
If a positive value is set for the alarm value, the PV will operate as a change rate alarm in the rising direction. If a negative value is set, the PV will operate as a change rate alarm in the falling direction.
Precaution
If a shorter PV rate of change calculation period is set, outputs set for the PV change rate alarm function may repeatedly turn ON and OFF for a short period of time. It is therefore recommended that the PV change rate alarm be used with the alarm latch turned ON.
PV
SP Alarms When Remote SP Is Used
Time
Alarm value
0
ON
Alarm function
Parameter name Setting range Unit Default
PV Rate of Change Calculation Period
OFF
1 to 999 Sampling cycle 17
OFF
PV change width for PV rate of change calculation period
ON
(= 17 × 60 ms = 1,020 ms)
RSP Absolute Upper Limit and RSP Absolute Lower Limit parameters were added for the E5AN-H and E5EN-H (with remote SP input). These parame­ters are used for a remote SP regardless of whether the SP mode is set to Remote SP or Local SP Mode.
70
Page 95

Using Heater Burnout, Heater Short, and Heater Overcurrent Alarms Section 3-10

3-10 Using Heater Burnout, Heater Short, and Heater
Overcurrent Alarms
3-10-1 Heater Burnout, Heater Short, and Heater Overcurrent Alarm
Operations
• Heater burnout detection and heater overcurrent detection are executed by measuring heater current while the control output (heating) is ON, and heater short detection is executed by measuring heater current while it is OFF. For details, refer to the following table. (Heater burnout detection, heater short detection, and heater overcurrent detection cannot be used with the control output for cooling.)
• These settings can be made for standard models only.
Control output (heating) status Power to heater HB alarm
Control output
(heating)
ON Lit Yes (Normal) (See note 1.) OFF --- ---
OFF Not lit Yes (HS alarm) --- ON ---
ON Lit Normal --- --- OFF
Operation
indicator
No (Heater burnout) ON --- ---
No (Normal) (See note 2.) --- OFF ---
Heater overcurrent status (See note 3.)
ON
Control output (heating)
OFF
output
--- --- ON
Ton
(See note 3.)
HS alarm
output
Tof f
(See note 4.)
Heater overcurrent
Note (1) In the above diagram, power is considered to be ON (normal) if the heater
current is greater than the heater burnout detection current during the Ton interval. If the heater is burned out, the measured current decreases and falls below the heater burnout detection value. The output is then activat­ed as the heater burnout alarm.
(2) In the above diagram, power is considered to be OFF (normal) if the leak-
age current is less than the HS alarm current during the Toff interval. If the SSR output is short-circuited, the measured current increases be­yond the HS alarm value. The output is then activated as the HS alarm.
(3) In the above diagram, it is regarded as normal when the heater current is
less than the heater overcurrent detection current during the Ton period. Current is increased when excessive current flows to the heater, causing the heater overcurrent detection value to be exceeded and an OC (heater overcurrent) alarm to be output.
(4) Heater burnout and heater overcurrent are not detected if the control out-
put (heating) ON time (Ton) is 100 ms or less.
(5) HS alarms are not detected if the control output (heating) OFF time (Toff)
is 100 ms or less.
alarm output
71
Page 96
Using Heater Burnout, Heater Short, and Heater Overcurrent Alarms Section 3-10
CT
Load
Load (such as a heater)
AC line
Product To CT input
• For Controllers with heater burnout, HS, and heater overcurrent alarms, an OR output is established between the ALM 1 function and the alarms. If the ALM1 function is to be used for the heater burnout, HS, and heater overcurrent alarms only, set 0 as the alarm 1 type (i.e., do not use ALM1).
• Turn the heater power ON simultaneously or before turning ON the E5N-H power. If the heater power is turned ON after turning ON the E5AN-H power, the HB alarm will be activated.
• Control is continued even when the heater burnout, HS, or heater over­current alarm is active.
• The rated current value may sometimes differ slightly from the actual cur­rent flowing to the heater. Use the Heater Current 1 Value Monitor, Heater Current 2 Value Monitor, Leakage Current 1 Monitor, and Leakage Current 2 Monitor parameters to check the actual current being used.
• If there is little difference between the current in normal and abnormal states, detection may become unstable. To stabilize detection, set a cur­rent value difference of at least 1.0 A for heaters of less than 10.0 A, and at least 2.5 A for heaters of 10.0 A or more. If the heater current is too low, loop the load line several times through a CT, as shown in the diagram below. Looping it through once will double the detection current.
Load line
CT

3-10-2 Installing Current Transformers (CT)

• This function can be used with E5N-H models that have the HB alarm, HS alarm, and OC alarm. For the E5CN-H, connect the CT in advance to terminals 14 and 15 (CT1), or 13 and 15 (CT2). For the E5AN-H/EN-H, connect the CT in advance to terminals 14 and 15 (CT1) or 15 and 16 (CT2). Then pass the heater power line through the CT's hole. For specifications, models and dimensions of current transformers that can be used with this Controller, see Appendix Current Transformer (CT) on page 298.
Single-phase Heaters For single-phase heaters, install the CT in the position shown in the following
diagram.
Three-phase Heaters (E5N-HHH 3-phase Heater Detection Models)
When a 3-phase power supply is used, regardless of the types of connecting lines, two current transformers (CTs) are required to detect heater burnout, HS, and OC.
72
■ Delta connecting lines: Refer to the following diagram for CT installation
positions.
Note Heater voltage fluctuations are not considered here, so be take that
into account when setting the detection current.
Page 97
Using Heater Burnout, Heater Short, and Heater Overcurrent Alarms Section 3-10
CT
Load
Load
To CT input
Load
Load (such as a heater)
AC line
AC line
Product
To CT input
Product
Heater Burnout Detection 1/2 set value =
Normal current value + Burnout current value
2
HS Alarm 1/2 set value =
Leakage current value (output OFF) + HS current value
2
Heater overcurrent 1/2 set value =
Normal current value + Overcurrent value
2
■ Star connecting lines: Refer to the following diagram for CT installation
positions.
Note Heater voltage fluctuations are not considered here, so be take that
into account when setting the detection current.
Load
Load (such as a heater)
Load
AC line
Product To CT input
Load
CT
Product To CT input
■ V connecting lines: Refer to the following diagram for CT installation
CT
positions.
Note Heater voltage fluctuations are not considered here, so be take that
into account when setting the detection current.
Product To CT input
AC line
Product To CT input
CT
Load
Load (such as a heater)
Load
CT

3-10-3 Calculating Detection Current Values

• Calculate the set value using the following equation:
• To set the current for heater burnout when two or more heaters are con­nected through the CT, use the value from when the heater with the small­est current burns out. If all of the heaters have the same current, use the value from when any one of them burns out.
73
Page 98
Using Heater Burnout, Heater Short, and Heater Overcurrent Alarms Section 3-10
CT
0 A
200 V
CT
5 A→
←5 A
200 V
Normal
AC line
Load Load
AC line
Product To CT input
Product To CT input
Burnout
Load (such as a heater)
Burnout
Heater burnout detection current =
(Normal current) + (Heater burnout current)
2
=
5 + 0
2
= 2.5 [A]
10 A
10 A
CT
15 A→
←15 A
200 V
CT
200 V
Normal
Product To CT input
Product To CT input
Burnout
Load LoadLoad
Load LoadLoad
Burn­out
• Make sure that the following conditions are satisfied: Heater with a current of less than 10.0 A: (Current value at normal operation) − (Current value at heater burnout) ≥ 1A When the difference is less than 1 A, detection is unstable. Heater with a current of 10.0 A or more: (Current value at normal operation) − (Current value at heater burnout) ≥
2.5 A When the difference is less than 2.5 A, detection is unstable.
• The setting range is 0.1 to 49.9 A. Heater burnout, HS, and heater over­current are not detected when the set value is 0.0 or 50.0. When the set value is 0.0, the heater burnout alarm is always OFF, the HS alarm is always ON, and the heater overcurrent alarm is always ON. When the set value is 50.0, the heater burnout alarm is always ON, the HS alarm is always OFF, and the heater overcurrent alarm is always OFF.
• Set the total current value for normal heater operation to 50 A or less. When a current value of 55.0 A is exceeded, ffff is displayed in the Heater Current 1 (or 2) Value Monitor and Leakage Current 1 (or 2) Moni­tor parameters.

3-10-4 Application Examples

Single-phase Heaters Example: Using a 200-VAC, 1-kW Heater
The heater power supply provides 5 A when the current is normal, and 0 A when there is a burnout, so the heater burnout detection current is calculated as follows:
Example: Using Three 200-VAC, 1-kW Heaters
74
The heater power supply provides 15 A when the current is normal, and 10 A when there is a burnout, so the heater burnout detection current is calculated as follows:
Page 99
Using Heater Burnout, Heater Short, and Heater Overcurrent Alarms Section 3-10
Heater burnout detection current =
(Normal current) + (Heater burnout current)
2
=
15 + 10
2
= 12.5 [A]
CT
Load
Load
200 V
200 V
17.3 A→
17.3 A→
17.3 A→
200 V
Normal
Product To CT input
Product To CT input
Load
CT
CT
Load
Load
200 V
200 V
15 A→
15 A→
200 V
CT
CT
Load
Load
200 V
200 V
10 A→
17.3 A→
10 A→
200 V
BurnoutBurnout
Burnout
Load
Load
Product To CT input
Product To CT input
Product To CT input
Product To CT input
Current when there is a burnout = 10 A × √3 ×
(√3/2) = 15 A
Current when there is a burnout = 10 A × √3 ×
(1/√3) = 10 A
Burnout
Three-phase Heaters Delta Connecting Lines
Example: Using Three 200-VAC, 2-kW Heaters
The current when each phase is normal is 17.3 A (≈ √3 × 10 A).
The heater burnout current when there is a burnout at the load line is as fol­lows:
(Heater burnout detection current) = (17.3 + 15) / 2 ≈ 16.1 [A]
The heater burnout current when there is a burnout at the load is as follows:
(Heater burnout detection current) = (17.3 + 10) / 2 ≈ 13.65 [A]
To enable detection in either case, use 16.1 A as the heater burnout detection current.
75
Page 100
Using Heater Burnout, Heater Short, and Heater Overcurrent Alarms Section 3-10
p
CT
CT
200 V
200 V
5 A→
5 A→
200 V
Load
Load
CT
CT
200 V
200 V
5 A→
5 A→
200 V
Load
Load
Burnout
Burnout
Load (such as a heater) Load (such as a heater)
Load
Load
Product To CT input
Product To CT input
Product To CT input
Burnout
Current when there is a burnout = 10 A × (1/√3)
× (√3/2) = 5 A
Current when there is a burnout = 10 A × (1/√3)
× (√3/2) = 5 A
Product To CT input
Star Connecting Lines
Example: Using Three 200-VAC, 2-kW Heaters
Normal
5.8 A→
Load
200 V
200 V
5.8 A→
Load
Load (such as a heater)
Load
200 V
Product To CT input
5.8 A→
Product To CT in
CT
CT
ut
The current when each phase is normal is 5.8 A (≈ 10 A × (1 /√3)).
76
The heater burnout detection current for this connecting line is 5.4 A (= (5.8 +
5) / 2).
Loading...