Circuit protectionOutput short-circuit protection, reverse polarity on supply
Operation modeLight ON and Dark ON, switch-selectable
Ambient light immunity
Ambient temperature
Ambient humidityOperating35% to 85% (with no condensation)
Dielectric strength1,000 VAC at 50/60 Hz for 1 minute
Vibration resistance10 to 55 Hz, 1.5-mm double amplitude or 300 m/s2(approx. 30G) for 2 hrs each in X, Y, and
Insulation resistance20 MΩ min. (at 500 VDC)
Shock resistance500 m/s2(approx. 50G) for 3 times each in X, Y, and Z axis
Enclosure ratingIEC IP50
Connection method2m cable
Material
Weight (with 2 m cable)Approx. 100 g
AccessoryMounting brackets (included)
Incandescen
tlamp
Sunlight10,000 ℓxmax.
Operating-- 2 5 °Cto55°C(--13°F to 131°F) with no icing
Storage-- 4 0 °Cto70°C(--40°F to 158°F) with no icing
CasePBT
CoverPolycarbonate
threshold indicator (red LED)
3,000 ℓxmax.
Z directions
3
Page 3
E3X-NH
Nomenclature
J E3X-NH11
Operation Indicator (orange)
Lit when output is ON.
Incident Level Indicators
(green, 8 levels)
Lit depending on the incident
light amount.
UP/DOWN Selector
Select UP for increasing the threshold value.
Select DOWN for decreasing the threshold
value.
Operation Mode Selector
Switchable between light-ON and
dark-ON modes.
Threshold Indicators
(red, 13 levels)
Indicates threshold level.
SET Button
For teaching or for fine threshold adjustment
Mode Selector
Switchable among TEACH, ADJ, and
RUN modes.
E3X-NH
Operation
J OUTPUT CIRCUITS
E3X-NH11 (NPN output)
Brown
Load
Photoelectric
sensor
main
circuit
Black
Orange
Blue
Control
output
Alarm output
Load
12 to 24 VDC
J OPERATION MODE
Light-ONDark-ON
Light received
Light not received
Operation indicator
(orange)
Output
transistor
Load (relay)Operate
ON
OFF
ON
OFF
Release
(Between brown and black)
PNP circuits
Photoelectric
sensor
main
circuit
Light received
Light not received
Operation indicator
(orange)
Output
transistor
Load (relay)Operate
ON
OFF
ON
OFF
Release
(Between brown and black)
Brown
Control output
Black
Alarm
output
Orange
Blue
12 to 24 VDC
Load
Load
4
Page 4
E3X-NH
E3X-NH
J SENSITIVITY SETTING AND ADJUSTMENT
Refer to the following to select the most suitable sensitivity setting method. We recommend that two-point teaching and manual-tuning be
tried first.
Using the Sensor at the
Maximum Sensitivity
Sensing Slight Differences
Sensitivity Setting
Without Objects
Application Examples
Detection of a passing object with
through-beam fibers.
Checking IC Tray Arrangements
E3X-NH
Sensitivity Setting
Application Examples
Detection of slight differences in
reflection.
Detection of translucent objects.
Detection of object surface irregu-
larities.
Color discrimination.
Detecting IC Chips on Film Sheet
E32-T16P
E3X-NH
Maximum Sensitivity SettingOne-point Teach ModeTwo-point Teach Mode
Fine-tuning, if required.
Film sheet
Application Examples
Detection of minute passing objects.
Detection of lead wires.
High-precision positioning.
Detecting Lead Frame Position
Lead frame
E32-D32
Fine-tuning on Production Lines
Reason
Marginal sensitivity adjustment is required considering the
differences in targets.
For high-precision positioning of electronic parts.
Detecting
Lead Frame Rises
E32-T24
E3X-NH
Detecting
Cassette Tape Cases
Ensuring reliable detection
without being influenced by
the difference in color or
mark.
E32-L25A
Sensitivity Adjustment (Fine-tuning)
Manual-tuning (Fine Sensitivity Adjustment)
E3X-NH
3.3 mm
Ideal Operation Under Frequently Changing
Environments
Reason
Dust sticking to the fiber tip.
Targets are slightly different from each other in color or
surface quality.
Detecting
Passing Chip Parts
E32-T16P
E3X-NH
Counting
Number Of Pills
Auto-tuning (Automatic Sensitivity Compensation)
5
Page 5
E3X-NH
E3X-NH
J SENSITIVITY SETTING (TEACHING)
The sensitivity of the E3X-NH is factory-set to maximum. When resetting the sensitivity of the E3X-NH to maximum after with/without-object teaching or positioning/no-object teaching, follow the steps described below.
Maximum Sensitivity Setting
1. Set the mode selector to TEACH.
Hold the SET button down for three seconds. Be sure that all
the threshold indicators (red) are lit. The built-in buzzer will
beep once when the threshold indicator is lit.
Two-point Teach Mode
1. Set the mode selector to TEACH.
Place the target object in the sensing area and press the
SET button once. Be sure that all the threshold indicators
(red) are lit. The built-in buzzer will beep once when the
threshold indicator is lit.
Press for 3 s min.
2. The sensitivity will be set when the built-in buzzer beeps
continuously and all the incident level indicators (green) are
lit.
3. Set the mode selector to RUN. Be sure that only the bottom
threshold indicator is lit.
Press once for 0.5 to 2.5 s
Through-beam Model
Light is
interrupted.
Diffuse Model
2. Remove the object and press the SET button.
If teaching is OK:
All the incident level indicators (green) will be lit. The built-in
buzzer will beep once.
Diffuse Model
Mark
Base
6
Press once for 0.5 to 2.5 s
Page 6
E3X-NH
E3X-NH
If teaching is not stable:
The threshold indicator (red) will flash. The built-in buzzer will
beep 3 times.
Change the position of the object and the sensing distance
that has been set and repeat the process.
Hold set button down
for 0.5 to 2.5 s
Through-beam Model
Light is received.
Diffuse Model
Mark
Base
Diffuse Model
One-point Teach Mode
1. Set the mode selector to TEACH.
Press the SET button once without a target object in the
sensing area. Be sure that all the threshold indicators (red)
are lit. The built-in buzzer will beep once when the threshold
indicators are lit.
Press once for 0.5 to 2.5 s
2. Set the mode selector to RUN. The threshold is set automatically.
3. Set the mode selector to RUN. Be sure that the middle
threshold indicator is lit. The threshold will be set to a 50%
value.
3. The Sensor will automatically compensate for environmental
changes.
7
Page 7
E3X-NH
J SENSITIVITY ADJUSTMENT (TUNING)
Manual-tuning
(Fine Sensitivity Adjustment)
Note: The auto-tuning function will be disabled if manual-tuning is
utilized.
1. After setting the sensitivity of the E3X-NH, select the adjustment direction with the UP/DOWN selector in the ADJ mode.
(2)
(1)
E3X-NH
Auto-tuning
(Automatic Sensitivity Compensation)
1. Set the mode selector to TEACH.
Press the SET button once without a target object in the
sensing area. Be sure that all the threshold indicators (red)
are lit. The built-in buzzer will beep once when the threshold
indicators are lit.
2. Press the SET button in ADJ mode. Be sure that the
threshold-level changes whenever the SET button is
pressed. If two threshold indicators are lit, the threshold will
automatically be set to a middle value equal to the target’s
sensed value.
3. Set the mode selector to RUN.
2. Set the mode selector to ADJ and press the SET button for
three seconds minimum. Be sure that the threshold indicator
(red) flashes. The built-in buzzer will beep continuously when
cycle is complete.
(2)
Press for 3 s min.
(1)
3. Set the mode selector to RUN. The threshold indicator (red)
will continue to flash while the the auto-tuning function is
enabled.
8
Page 8
E3X-NH
E3X-NH
J SENSITIVITY SETTING—THRESHOLD SETTING AND INDICATORS
Threshold
indicators
Level12345678910111213
Maximum Sensitivity Setting
•Use Through-beam Fibers for detection of opaque objects.
•Use the Diffuse Fibers for detection of objects with fixed background.
The threshold should be set to a level slightly higher than the Zero point when detecting objects that completely interrupt light.
Diffuse Sensor
The number of incident level indicators that are lit will depend on the location of the object. The bottom indicator of the threshold indicators
will always be lit.
Farther
Light
Closer
Target
Target
Threshold
Incident
level
indicator
Threshold
indicator
2-Point Teach Mode
•Ideal for the detection of object surface irregularities or minute objects.
•Ideal for the detection of objects against a background that reflects light irregularly.
Diffuse Sensor
1. Press the SET button with the target in the sensing area.
Then press the SET button without target in the sensing
area, as illustrated at the right.
Farther
Light
Closer
Fiber
head
Target
Light
Large
Small
Fiber
head
RUN/ADJ Mode
The number of the incident level indicators lit depends
on the position of the target. When using the
manual-tuning function, it is possible to adjust the
threshold in six levels. The default threshold is set to 7.
Farther
Target
Threshold
Light
Large
Light
Threshold
Small
2. Set the threshold to the middle value between the values
obtained with and without the target.
Closer
Incident
level
indicator
Threshold
indicator
9
Page 9
E3X-NH
E3X-NH
One-point Teach Mode
•Ideal if it is impossible to perform teaching with the target
fixed in the sensing area.
•Ideal for high-precision positioning.
•Ideal for detection of bright or dark objects.
Diffuse (Light-ON) Fiber Unit
1. Press the SET button without the target in the sensing
area.
Set the threshold to the value that is ±6% of the incident
level.
Farther
Threshold
Light
Closer
Note: If the target is not present at the time of teaching, the
threshold cannot be set to the position corresponding
to -6% of the incident level. The sensitivity will then be
set to maximum automatically when in RUN mode.
2. Detecting the first object in RUN/ADJ mode.
Farther
6%
6%
Threshold
Target
Incident level without a fixed background
or target.
The number of indicators lit depends on
the position of the target. The threshold
position of the target is set to 7.
Through-beam(Dark-ON)Fiber Unit
1. Press the SET button without target in the sensing area.
Set the threshold to the value that is ±6% of the incident
level.
Farther
Threshold
Light
Closer
6%
6%
Threshold
Incident level without a fixed
background or target.
2. Detecting the first object in RUN/ADJ mode.
Farther
Light
Closer
Target
6%
Threshold
Incident
level
indicator
Threshold
indicator
18%
Tuning
range
18%
The number of indicators lit depends on
the position of the target. The threshold
position of the target is set to 7.
Light
Closer
Threshold
6%
Incident
level
indicator
18%
18%
Threshold
indicator
Tuning
range
10
Page 10
E3X-NH
E3X-NH
J THRESHOLD LEVEL AND INDICATOR LEVELS
Setting the Initial Threshold
•To set the initial threshold, perform One-point teaching by pressing the SET button for a minimum of 3 seconds.
•As a result of target movement during operation, the middle value between the highest and lowest point on the incident scale will be
obtained. The E3X-NH will perform an auto-tuning function within a range of ±18% of this value.
Tuning
Farther
range
Light
Closer
Threshold Compensation
Farther
Light
Closer
Threshold
Initial threshold for
auto-tuning
Threshold compensation
Incident
level
indicator
(see note)
Time
Threshold
indicator
(The
threshold is
set to 7.)
Threshold
indicator
18%
18%
Note: The number of Incident-level
indicators lit depends on the
presence of the target.
•The sensor will perform an Automatic Threshold Compensation within the preset band.
•After the threshold has been compensated, the Threshold Indicator will flash, indicating the adjusted value.
•Threshold compensation occurs at 1, 3, 6, 10, 15, 22, and 30 minutes after turning on the E3X-NH. After the initial 30 minute time-
frame, Threshold Compensation is continually repeated, every 30-minutes.
•Alarm output will occur if the threshold compensation range is not within the tuning range. Perform sensitivity setting again if the alarm
signal turns ON.
11
Page 11
E3X-NH
Dimensions
Unit: mm (inch)
J AMPLIFIER
E3X-NHj1
E3X-NH
Cable: Polyvinyl chloride-covered cord
4-mm dia. (18/0.12 dia), 4 stranded conductors
Standard length: 2 m
Weight: Approx. 100 g
Two, 2.4 dia.
Operation indicator
Two, 3.2 -dia. holes
Threshold indicators
Incident level
indicators
(A) (see note)
Note: The mounting bracket can be at-
Mounting
bracket
Two, mounting holes
tached to this side.
12
Page 12
E3X-NH
Installation
E3X-NH
J CUTTING FIBER
Insert a fiber into the Fiber Cutter and determine the length of the
fiber to be cut.
Press down the Fiber Cutter in a single stroke to cut the fiber.
An insertion mark can be placed on the fiber to serve as a
reference when inserting the fiber into the Amplifier. Use the
following procedure.
Confirm through the Cutter hole that the fiber is inserted beyond
the insertion mark hole so that the insertion mark is properly
indicated, and then press firmly down on the Cutter.
(2)
(1)
Insert the fiber into the Amplifier up to the insertion mark. Proper
fiber performance will not be achieved unless the fiber is inserted
all the way to the insertion mark. (This method is applicable to
standard, 2.2-mm-diameter fibers only.)
J FIBER CONNECTION OR
DISCONNECTION PROCEDURES
The E3X-NH Amplifier has a lock button. Follow these steps to
connect or disconnect the fibers to (or from) the E3X-NH
Amplifier:
Note: The fiber must be locked or released in a temperature
range of --10°Cto40°C(14°F to 104°F).
Connection
Lock button
Fiber insertion mark
Fiber
1. After cutting the fibers (using the E39-F4 Fiber Cutter), place
an insertion mark on the fiber so that it can be correctly inserted into the Amplifier.
2. Insert the fiber into the Amplifier up to this insertion mark.
3. Press the lock button to lock the fiber in that position.
13
Page 13
E3X-NH
E3X-NH
Disconnection
1. Before pulling out the fiber, you MUST first press the lock
button to release (unlock) the fiber, or you may damage
the fiber.
2. Then, pull the fiber from the amplifier.
Protective cover
Unlocked
Locked
Procedure for Inserting the Fiber
If the portion from the tip to the insertion mark of the fiber is
not inserted into the Amplifier Unit, the sensing distance will
be reduced.
2.2-mm-dia. Fiber
Insert to the portion
from the tip to the
insertion mark of
each fiber into the
Amplifier Unit.
Fiber Unit
12.6 mm
Thin Fiber with the E39-F9 Attachment
The portion from the tip to
the insertion mark of each
fiber into the Amplifier Unit.
Fiber Unit
12.6 mm
Fiber with Fixed Length
The portion from the tip to
the insertion mark of each
fiber into the Amplifier Unit.
Amplifier Unit
Amplifier Unit
Amplifier Unit
J BENDING RADIUS
E39-F11 Sleeve Bender
The bending radius of the stainless tube should be as large as
possible. The smaller the bending radius becomes, the shorter
the sensing distance will be.
Insert the tip of the stainless tube to the Sleeve Bender and bend
the stainless tube slowly along the curve of the Sleeve Bender
(refer to the figure).
1.3 dia.
min.
10
1.2 dia.
max.
Stainless tube
10
R10
R5
Fiber tip position mark
Do not bend here.
R12.5
R7.5
90omax.
1.2 dia.
max.
J REFLECTOR
Observe the Following Precautions when Using the
Reflector (E39-R3)
Use detergent, etc., to remove any dust or oil from the surfaces
where tape is applied. Adhesive tape will not be attached
properly if oil or dust remains on the surface.
The E39-R3 cannot be used in places where it is exposed to oil
or chemicals.
12.6 mm
14
Page 14
E3X-NH
E3X-NH
J ATTACHMENT UNITS
Applications
E39-F10 Fiber Connector
Use the following procedure (refer to the figure) to connect fibers
via the Fiber Connector.
Splice
Retention unit
Retention unit
Fiber Unit
Each Fiber Unit should be as close as possible before they are
connected.
Sensing distance will be reduced by approximately 25% when
fibers are connected.
Only fibers with a 2.2-mm dia. can be connected. (Refer to page
NO TAG for applicable Fiber Units.)
Protective Spiral Tube
Insert a fiber to the Protective Spiral Tube from the head
connector side (threaded) of the tube.
Use the attached saddle to secure the end cap of the Protective
Spiral Tube. To secure the Protective Spiral Tube at a position
other than the end cap, apply tape to the tube so that the portion
becomes thicker in diameter.
Saddle
Tube
End cap
J AMPLIFIER UNITS
Mounting
1. Mount the front part (see #1) to the mounting bracket (attach-
ment)oronaDINrail.
2. Press the back part (see #2) onto the mounting bracket or
onto the DIN rail.
Note: DO NOT mount the back part on the mounting bracket or
the DIN rail first and then mount the front part on the mounting bracket on the DIN rail. This could decrease the mounting strength of the Amplifier Unit.
Protective spiral
tube
Fiber Unit
Push the fiber into the Protective Spiral Tube. The tube should be
straight so that the fiber is not twisted when inserted. Then turn
the end cap of the spiral tube.
Protective spiral
tube
Fiber Unit
Secure the Protective Spiral Tube on a suitable place with the
attached nut.
Mounting panel
tube
Hexagon clamping nut
Fiber Unit
Toothed washerProtective spiral
DIN Rail
(1)
Removal
You can remove the Amplifier in one easy step:
1. Press the Amplifier Unit in direction (A) and lift the fiber insertion part in direction (B) as shown here
(B)
DIN Rail
(A)
(2)
15
Page 15
E3X-NH
E3X-NH
When Side-Mounting
Washers
(6 dia. max.)
When side-mounting:
Attach the mounting bracket on the Amplifier first, and secure
the amplifier with M3 screws and washers. The diameter of
the washers should be a maximum of 6 mm.
Insert the fiber into the Amplifier up to the insertion mark. Proper
fiber performance will not be achieved unless the fiber is inserted
all the way to the insertion mark. (This method is applicable to
standard, 2.2-mm-diameter fibers only.)
Insertion mark
12.6
2.2-dia.
The cutting holes cannot be used twice. If the same hole is used
twice, the cutting face of the fiber will be rough and the sensing
distance will be reduced. Always use an unused hole.
Use either one of the two holes on the right (refer to the following
figure) to cut a thin fiber as follows:
1. An attachment is temporarily fitted to a thin fiber before
shipment.
Thin fiber attachment (E39-F9)
Temporarily fitted
2. Secure the attachment after adjusting the position of it in the
direction indicated by the arrow.
4. Finished state (proper cutting state)
Approx.
0.5 mm
Note: Insert the fiber in the direction indicated by the arrow.
Connection
Do not pull or press the Fiber Units. The Fiber Units have a
withstand force of 9.8 N (1 kgf) or 29.4 N (3 kgf) (pay utmost
attention because the fibers are thin).
Do not bend the Fiber Units beyond the permissible bending
radius.
Do not bend the edge of the Fiber Units (excluding the E32-TjR
and E32-DjR).
20 mm min.
Correct
Amplifier Unit
Incorrect
Do not apply excess force on the Fiber Units.
Fiber Unit
Nylon wireholder
Correct
Incorrect
The Fiber Head could be break by excessive vibration. To
prevent this, the following is effective:
Fiber Unit
20 mm min.
Metal holder
3. Insert the fiber into the E39-F4 to cut.
Cutter E39-F4
Two holes for
thin fiber
Three holes for
standard fiber
(2.2-mm dia.)
16
A one-turn loop can
absorb vibrations.
Tape
Turning the Power ON
When the power is turned ON, the operation indicator will be ON
momentarily. Note that this will not have an effect on performance
since no control output will be generated.
When the power is turned ON, the operation indicator will be ON
momentarily. Note that this will not have an effect on performance
since no control output will be generated.
Perform two-point teaching if two to three Fiber Units are closely
mounted together, at which time supply power only to the Unit in
teaching operation in turn or block the emitters of the Fiber Units
not in teaching operation.
Page 16
E3X-NH
Precautions
WARNING
!
The E3X-NH is not a safety component for ensuring the
safety of people as defined in EC Directive 91/368/EEC, or
as covered by separate European standards or by any other
regulations or standards.
E3X-NH
J SENSING A MINUTE OBJECT
This data sheet shows typical examples for detecting minute
objects. These typical examples are for reference use only,
because these example operations were tested on Units sampled
at random from a lot and the values described are average
values. Do not assume that all Units ensure such operations.
J AVOID DAMAGE TO THE E3X-NH
SENSOR
•Do not impose any voltage exceeding the rated voltage on
the E3X-NH.
•Do not impose 100 VAC or more on models that operate with
DC.
•When supplying power to the E3X-NH, make sure that the
polarity of the power is correct.
•Do not short-circuit the load connected to the E3X-NH.
•The load must be connected to the E3X-NH in operation.
J REFLECTOR
Precautions for Using the E39-R3 Reflector
Use detergent, etc., to remove any dust or oil from the surfaces
where tape is applied. Adhesive tape will not be attached
properly if oil or dust remains on the surface.
The E39-R3 cannot be used in places where it is exposed to oil
or chemicals.
J MUTUAL INTERFERENCE PROTECTION
Perform two-point teaching if two to three Fiber Units are closely
mounted together. The mutual interference feature will guard
against false triggering.
J EEPROM WRITING ERROR
Write errors may result at the time of teaching due to power
failure or static noise. If any of these occur, re-teach the
amplifier.
J WHEN THE POWER IS OFF
The moment power is turned off, the E3X-NH may output a pulse
signal which could affect the operation of the devices connected
to it. This will occur more often if power is supplied to the
E3X-NH from an external power supply, thus affecting the
connected timer or counter. We recommend using a separate
power supply to avoid a false signal.
For extending the cable, use wire with 0.3 mm
length of the cable should be a maximum of 100 m.
2
min. The total
J POWER SUPPLY
If a standard switching regulator is used as a power supply, the
frame ground (FG) terminal and the ground (G) terminal must be
grounded, or the Amplifier can malfunction due to the switching
noise of the power supply.
The supplied voltage must be within the rated voltage range.
Unregulated full- or half-wave rectifiers must not be used as
power supplies.
J WIRING
Never wire the Amplifier within the same conduit with power
lines. Doing so will cause induction between the lines, possibly
resulting in faulty operation or damage. Always wire the Amplifier
in a separate, dedicated conduit.
Power line
NOTE: DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters to inches divide by 25.4.
R
OMRON ELECTRONICS LLC
One East Commerce Drive
Schaumburg, IL 60173
1-800-55-OMRON
Cat. No. CEDSAX411/01Specifications subject to change without notice.Printed in U.S.A.
OMRON ON--LINE
Global -- http://www.omron.com
USA -- http://www.omron.com/oei
Canada -- http://www.omron.com/oci
OMRON CANADA, INC.
885 Milner Avenue
Scarborough, Ontario M1B 5V8
416-286-6465
17
17
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.