All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or
by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of
OMRON.
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without
notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no responsibility
for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in
this publication.
SYSMAC CP Series
CP1E-E@@D@-@
CP1E-N@@D@-@
CP1E-NA@@D@-@
CP1E CPU Unit Hardware
User’s Manual
Revised June 2010
Introduction
Thank you for purchasing a SYSMAC CP-series CP1E Programmable Controller.
This manual contains information required to use the CP1E. Read this manual completely and be sure
you understand the contents before attempting to use the CP1E.
Intended Audience
This manual is intended for the following personnel, who must also have knowledge of electrical systems (an electrical engineer or the equivalent).
• Personnel in charge of installing FA systems
• Personnel in charge of designing FA systems
• Personnel in charge of managing FA systems and facilities
Applicable Products
CP-series CP1E CPU Units
• Basic Models CP1E-ED-
A basic model of CPU Unit that support basic control applications using instructions such as
basic, movement, arithmetic, and comparison instructions.
• Application Models CP1E-N/NAD-
An application model of CPU Unit that supports connections to Programmable Terminals, inverters, and servo drives.
The CP Series is centered around the CP1H, CP1L, and CP1E CPU Units and is designed with the
same basic architecture as the CS and CJ Series.
Always use CP-series Expansion Units and CP-series Expansion I/O Units when expanding I/O
capacity. I/O words are allocated in the same way as for the CPM1A/CPM2A PLCs, i.e., using fixed
areas for inputs and outputs.
CP1E CPU Unit Hardware User’s Manual(W479)
1
CP1E CPU Unit Manuals
Information on the CP1E CPU Units is provided in the following manuals.
Refer to the appropriate manual for the information that is required.
This Manual
Mounting and
1
Setting Hardware
2
Wiring
Connecting
3
Online to the PLC
4
Software Setup
CP1E CPU Unit Hardware
User’s Manual(Cat. No. W479)
· Names and specifications of the parts of all Units
· Basic system configuration for each CPU Unit
· Connection methods for Expansion I/O Units
and Expansion Units
· Wiring methods for the power supply
· Wiring methods between external I/O devices
and Expansion I/O Units or Expansion Units
Connecting Cables for CX-Programmer
Support Software
CP1E CPU Unit Software
User’s Manual(Cat. No. W480)
Procedures for connecting the
CX-Programmer Support Software
Software setting methods for the CPU
Units (PLC Setup)
CP1E CPU Unit Instructions
Reference Manual(Cat. No. W483)
5
Creating the Program
Checking and
6
Debugging Operation
Maintenance and
7
Troubleshooting
2
Error codes and remedies if a problem occurs
· Program types and basic information
· CPU Unit operation
· Internal memory
· Built-in CPU functions
· Settings
· Checking I/O wiring, setting the Auxiliary Area
settings, and performing trial operation
· Monitoring and debugging with the
CX-Programmer
CP1E CPU Unit Hardware User’s Manual(W479)
Detailed information on
programming instructions
Manual Configuration
The CP1E CPU manuals are organized in the sections listed in the following tables. Refer to the appropriate section in the manuals as required.
CP1E CPU Unit Hardware User’s Manual (Cat. No. W479)
(This Manual)
Section Contents
Section 1 Overview and Specifications
Section 2 Basic System Configuration and Devices
Section 3 Part Names and Functions This section describes the part names and functions of the CPU Unit,
Section 4 Programming DeviceThis section describes the features of the CX-Programmer used for pro-
Section 5 Installation and WiringThis section describes how to install and wire CP1E Units.
Section 6 Troubleshooting This section describes how to troubleshoot problems that may occur
Section 7 Maintenance and Inspection
Section 8 Using Expansion Units
and Expansion I/O Units
AppendicesThe appendices provide information on dimensions, wiring diagrams,
This section gives an overview of the CP1E, describes its features, and
provides its specifications.
This section describes the basic system configuration and unit models
of the CP1E.
Expansion I/O Units, and Expansion Units in a CP1E PLC .
gramming and debugging PLCs, as well as how to connect the PLC with
the Programming Device by USB.
with a CP1E PLC, including the error indications provided by the CP1E
Units.
This section describes periodic inspections, the service life of the Battery, and how to replace the Battery.
This section describes application methods for Expansion Units.
and wiring serial communications for the CP1E.
CP1E CPU Unit Software User’s Manual (Cat. No. W480)
Section Contents
Section 1 Overview This section gives an overview of the CP1E, describes its application
procedures.
Section 2 CPU Unit Memory This section describes the types of internal memory in a CP1E CPU
Unit and the data that is stored.
Section 3 CPU Unit OperationThis section describes the operation of a CP1E CPU Unit.
Section 4 Programming Concepts This section provides basic information on designing ladder programs
for a CP1E CPU Unit.
Section 5 I/O MemoryThis section describes the types of I/O memory areas in a CP1E CPU
Unit and the details.
Section 6 I/O Allocation This section describes I/O allocation used to exchange data between
the CP1E CPU Unit and other units.
Section 7 PLC SetupThis section describes the PLC Setup, which are used to perform basic
settings for a CP1E CPU Unit.
Section 8 Overview and Allocation
of Built-in Functions
Section 9 Quick-response Inputs This section describes the quick-response inputs that can be used to
Section 10 Interrupts This section describes the interrupts that can be used with CP1E PLCs,
This section lists the built-in functions and describes the overall application flow and the allocation of the functions.
read signals that are shorter than the cycle time.
including input interrupts and scheduled interrupts.
CP1E CPU Unit Hardware User’s Manual(W479)
3
Section Contents
Section 11 High-speed Counters This section describes the high-speed counter inputs, high-speed
counter interrupts, and the frequency measurement function.
Section 12 Pulse Outputs This section describes positioning functions such as trapezoidal control,
jogging, and origin searches.
Section 13 PWM Outputs This section describes the variable-duty-factor pulse (PWM) outputs.
Section 14 Serial Communications This section describes communications with Programmable Terminals
(PTs) without using communications programming, no-protocol communications with general components, and connections with a ModbusRTU Easy Master, Serial PLC Link, and host computer.
Section 15 Analog I/O FunctionThis section describes the built-in analog function for NA-type CPU
Units.
Section 16 Built-in Functions This section describes PID temperature control, clock functions, DM
backup functions, security functions.
Section 17 Ethernet Option BoardThis section gives an overview of the Ethernet Option Board, describes
its setting methods, I/O memory allocations, troubleshooting, how to
connect the CX-Programmer, and how to install an Ethernet network.
Section 18 Operating the Programming Device
AppendicesThe appendices provide lists of programming instructions, the Auxiliary
This section describes basic functions of the CX-Programmer, such as
using the CX-Programmer to write ladder programs to control the CP1E
CPU Unit, to transfer the programs to the CP1E CPU Unit, and to debug
the programs.
Area, cycle time response performance, PLC performance at power
interruption.
CP1E CPU Unit Instructions Reference Manual (Cat. No. W483)
Section Contents
Section 1 Summary of Instructions This section provides a summary of instructions used with a CP1E CPU
Unit.
Section 2 InstructionThis section describes the functions, operands and sample programs of
the instructions that are supported by a CP1E CPU Unit.
Section 3 Instruction Execution
Times and Number of Steps
Section 4 Monitoring and Computing the Cycle Time
AppendicesThe appendices provide a list of instructions by Mnemonic and ASCII
This section provides the execution times for all instructions used with a
CP1E CPU Unit.
This section describes how to monitor and calculate the cycle time of a
CP1E CPU Unit that can be used in the programs.
code table for the CP1E CPU Unit.
4
CP1E CPU Unit Hardware User’s Manual(W479)
Manual Structure
Page Structure and Icons
The following page structure and icons are used in this manual.
Level 2 heading
Level 3 heading
Step in a procedure
Indicates a step in a
procedure.
Special Information
(See below.)
Icons are used to indicate
precautions and
additional information.
5-2Installation
5-2-1 Installation Location
DIN Track Installation
1
Use a screwdriver to pull down the DIN Track mounting pins from the back of the Units to release
them, and mount the Units to the DIN Track.
Fit the back of the Units onto the DIN Track by catching the top of the Units on the Track and then
2
pressing in at the bottom of the Units, as shown below.
Press in all of the DIN Track mounting pins to securely lock the Units in place.
3
DIN Track mounting pins
5 Installation and wiring
Level 1 heading
Level 2 heading
Level 3 heading
Gives the current
headings.
5-2 Installation
DIN Track mounting pins
Release
DIN Track
5
5-2-1 Installation Location
Page tab
Gives the number
of the section.
Manual name
This illustration is provided only as a sample and may not literally appear in this manual.
Special Information
Special information in this manual is classified as follows:
Precautions for Safe Use
Precautions on what to do and what not to do to ensure using the product safely.
Precautions for Correct Use
Precautions on what to do and what not to do to ensure proper operation and performance.
Additional Information
Additional information to increase understanding or make operation easier.
Precautions for Correct Use
Tighten terminal block screws and cable screws to the following torques.
M4: 1.2 N·m
M3: 0.5 N·m
CP1E CPU Unit Hardware User’s Manual(W479)
5 - 3
CP1E CPU Unit Hardware User’s Manual(W479)
5
Terminology and Notation
Ter mDescription
E-type CPU UnitA basic model of CPU Unit that support basic control applications using instructions such
as basic, movement, arithmetic, and comparison instructions.
Basic models of CPU Units are called “E-type CPU Units” in this manual.
N-type CPU UnitAn application model of CPU Unit that supports connections to Programmable Terminals,
inverters, and servo drives.
Application models of CPU Units are called “N-type CPU Units” in this manual.
NA-Type CPU UnitAn application model of CPU Unit that supports built-in analog and connections to Pro-
grammable Terminals, inverters, and servo drives.
Application models of CPU Units with built-in analog are called “NA-type CPU Units” in
this manual.
CX-ProgrammerA programming device that applies for programming and debugging PLCs.
The CX-Programmer includes the Micro PLC Edition CX-Programmer (CX-One Lite), the
CX-Programmer (CX-One) and the CX-Programmer for CP1E.
This manual describes the unique applications and functions of the Micro PLC Edition
CX-Programmer version 9.03 or higher/CX-Programmer for CP1E.
“CX-Programmer” refers to the Micro PLC Edition CX-Programmer version 9.03 or
higher/CX-Programmer for CP1E in this manual.
Note E20/30/40 and N20/30/40 CPU Units are supported by CX-Programmer version 8.2
or higher. E10/14, N14/60 and NA20 CPU Units are supported by CX-Programmer
version 9.03 or higher.
Please read and understand this manual before using the product. Please consult your OMRON representative
if you have any questions or comments.
Warranty and Limitations of Liability
WARRANTY
OMRON’s exclusive warranty is that the products are free from defects in materials and workmanship for a
period of one year (or other period if specified) from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NONINFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE
PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR
INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which
liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS
REGARDING THE PRODUCTS UNLESS OMRON’S ANALYSIS CONFIRMS THAT THE PRODUCTS
WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO
CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
12
CP1E CPU Unit Hardware User’s Manual(W479)
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the
combination of products in the customer’s application or use of the products.
At the customer’s request, OMRON will provide applicable third party certification documents identifying
ratings and limitations of use that apply to the products. This information by itself is not sufficient for a
complete determination of the suitability of the products in combination with the end product, machine,
system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not
intended to be an exhaustive list of all possible uses of the products, nor is it intended to imply that the uses
listed may be suitable for the products:
• Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or
uses not described in this manual.
• Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical
equipment, amusement machines, vehicles, safety equipment, and installations subject to separate
industry or government regulations.
• Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR
PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO
ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND INSTALLED
FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user’s programming of a programmable product, or any
consequence thereof.
CP1E CPU Unit Hardware User’s Manual(W479)
13
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other
reasons.
It is our practice to change model numbers when published ratings or features are changed, or when
significant construction changes are made. However, some specifications of the products may be changed
without any notice. When in doubt, special model numbers may be assigned to fix or establish key
specifications for your application on your request. Please consult with your OMRON representative at any
time to confirm actual specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when
tolerances are shown.
PERFORMANCE DATA
Performance data given in this manual is provided as a guide for the user in determining suitability and does
not constitute a warranty. It may represent the result of OMRON’s test conditions, and the users must
correlate it to actual application requirements. Actual performance is subject to the OMRON Warranty and
Limitations of Liability.
ERRORS AND OMISSIONS
The information in this manual has been carefully checked and is believed to be accurate; however, no
responsibility is assumed for clerical, typographical, or proofreading errors, or omissions.
14
CP1E CPU Unit Hardware User’s Manual(W479)
Safety Precautions
Definition of Precautionary Information
The following notation is used in this manual to provide precautions required to ensure safe usage of a
CP-series PLC. The safety precautions that are provided are extremely important to safety. Always read
and heed the information provided in all safety precautions.
Indicates an imminently hazardous situation which,
WARNING
Caution
Precautions for Safe Use
Indicates precautions on what to do and what not to do to ensure using the product safely.
Precautions for Correct Use
Indicates precautions on what to do and what not to do to ensure proper operation
and performance.
if not avoided, will result in death or serious injury.
Additionally, there may be severe property damage.
Indicates a potentially hazardous situation which,
if not avoided, may result in minor or moderate
injury, or property damage.
Symbols
The triangle symbol indicates precautions (including
warnings). The specific operation is shown in the triangle
and explained in text. This example indicates a precaution for electric shock.
The circle and slash symbol indicates operations that you
must not do. The specific operation is shown in the circle
and explained in text.
The filled circle symbol indicates operations that you
must do. The specific operation is shown in the circle and
explained in text. This example shows a general precaution for something that you must do.
The triangle symbol indicates precautions (including
warnings). The specific operation is shown in the triangle
and explained in text. This example indicates a general
precaution.
The triangle symbol indicates precautions (including
warnings). The specific operation is shown in the triangle
and explained in text. This example indicates a precaution for hot surfaces.
CP1E CPU Unit Hardware User’s Manual(W479)
15
WARNING
Do not attempt to take any Unit apart while the power is being supplied.
Doing so may result in electric shock.
Do not touch any of the terminals or terminal blocks while the power is being
supplied.
Doing so may result in electric shock.
Provide safety measures in external circuits (i.e., not in the Programmable Controller), including the following items, to ensure safety in the system if an
abnormality occurs due to malfunction of the PLC or another external factor
affecting the PLC operation.
Not doing so may result in serious accidents.
• Emergency stop circuits, interlock circuits, limit circuits, and similar safety measures must be provided in external control circuits.
• The PLC will turn OFF all outputs when its self-diagnosis function detects any error
or when a severe failure alarm (FALS) instruction is executed. Unexpected operation, however, may still occur for errors in the I/O control section, errors in I/O memory, and errors that cannot be detected by the self-diagnosis function. As a
countermeasure for all these errors, external safety measures must be provided to
ensure safety in the system.
• The PLC outputs may remain ON or OFF due to deposition or burning of the output
relays or destruction of the output transistors. As a countermeasure for such problems, external safety measures must be provided to ensure safety in the system.
• When the 24-VDC output (service power supply to the PLC) is overloaded or shortcircuited, the voltage may drop and result in the outputs being turned OFF. As a
countermeasure for such problems, external safety measures must be provided to
ensure safety in the system.
Fail-safe measures must be taken by the customer to ensure safety in the event
of incorrect, missing, or abnormal signals caused by broken signal lines,
momentary power interruptions, or other causes.
Serious accidents may result from abnormal operation if proper measures are not
provided.
16
Do not apply the voltage/current outside the specified range to this unit.
It may cause a malfunction or fire.
CP1E CPU Unit Hardware User’s Manual(W479)
CautionCaution
Be sure to sufficiently confirm the safety at the destination when you transfer
the program or I/O memory or perform procedures to change the I/O memory.
Devices connected to PLC outputs may incorrectly operate regardless of the operating mode of the CPU Unit.
With an E-type CPU Unit or with an N/NA-type CPU Unit without a Battery, the contents of the DM Area (D) * , Holding Area (H), the Counter Present Values (C), the
status of Counter Completion Flags (C), and the status of bits in the Auxiliary Area (A)
related to clock functions may be unstable when the power supply is turned ON.
*This does not apply to areas backed up to EEPROM using the DM backup function.
If the DM backup function is being used, be sure to use one of the following methods
for initialization.
1. Clearing All Areas to All Zeros
Select the Clear Held Memory (HR/DM/CNT) to Zero Check Box in the Startup Data Read Area in the PLC Setup.
2. Clearing Specific Areas to All Zeros or Initializing to Specific Values
Make the settings from a ladder program.
If the data is not initialized, the unit or device may operate unexpectedly because of
unstable data.
Execute online edit only after confirming that no adverse effects will be caused
by extending the cycle time.
Otherwise, the input signals may not be readable.
Tighten the screws on the terminal block of the AC power supply section to the
torque specified in the user’s manual.
The loose screws may result in burning or malfunction.
Do not touch the power supply section when power is being supplied or immediately after the power supply is turned OFF.
The power supply section and I/O terminal blocks will be hot and you may be burned.
CP1E CPU Unit Hardware User’s Manual(W479)
17
Caution
Pay careful attention to the polarities (+/-) when wiring the DC power supply.
A wrong connection may cause malfunction of the system.
When connecting the PLC to a computer or other peripheral device, either
ground the 0-V side of the external power supply or do not ground the external
power supply at all.
Otherwise the external power supply may be shorted depending on the connection
methods of the peripheral device. DO NOT ground the 24 V-side of the external
power supply, as shown in the following diagram.
Non-insulated DC
power supply
FG
24V
0V
FG
0V
CPU Unit
USB cable or other
communications
cable
Peripheral device
FG
(e.g., personal computer)
0V
FG
The DM Area (D), Holding Area (H), Counter Completion Flags (C), and Counter
Present Values (C) will be held by the Battery if a Battery is mounted in a CP1EN/NAD- CPU Unit. When the battery voltage is low, however, I/O memory
areas that are held (including the DM, Holding, and Counter Areas) will be unstable.
The unit or device may operate unexpectedly because of unstable data.
Use the Battery Error Flag or other measures to stop outputs if external outputs are performed from a ladder program based on the contents of the DM
Area or other I/O memory areas.
Sufficiently check safety if I/O bit status or present values are monitored in the
Ladder Section Pane or present values are monitored in the Watch Pane.
If bits are set, reset, force-set, or force-reset by inadvertently pressing a shortcut key,
devices connected to PLC outputs may operate incorrectly regardless of the operating mode.
Program so that the memory area of the start address is not exceeded when
using a word address or symbol for the offset.
For example, write the program so that processing is executed only when the indirect
specification does not cause the final address to exceed the memory area by using
an input comparison instruction or other instruction.
If an indirect specification causes the address to exceed the area of the start address,
the system will access data in other area, and unexpected operation may occur.
18
CP1E CPU Unit Hardware User’s Manual(W479)
Caution
Set the temperature range according to the type of temperature sensor connected to the Unit.
Temperature data will not be converted correctly if the temperature range does not
match the sensor.
Do not set the temperature range to any values other than those for which temperature ranges are given in the following table.
An incorrect setting may cause operating errors.
CP1E CPU Unit Hardware User’s Manual(W479)
19
Precautions for Safe Use
Observe the following precautions when using a CP-series PLC.
Power Supply
• Always use the power supply voltages specified in the user’s manuals. An incorrect voltage may
result in malfunction or burning.
• Take appropriate measures to ensure that the specified power with the rated voltage and frequency is supplied. Be particularly careful in places where the power supply is unstable. An incorrect power supply may result in malfunction.
• Double-check all wiring and switch settings before turning ON the power supply. Incorrect wiring
may result in burning.
• Always turn OFF the power supply to the PLC before attempting any of the following. Not turning
OFF the power supply may result in malfunction or electric shock.
• Mounting or dismounting Expansion Units or Expansion I/O Units
• Mounting or dismounting Option Boards
• Setting rotary switches
• Connecting cables or wiring the system
• Connecting or disconnecting the connectors
Installation
• Before touching a Unit, be sure to first touch a grounded metallic object in order to discharge any
static build-up. Not doing so may result in malfunction or damage.
• Be sure that the terminal blocks, connectors, Option Boards, and other items with locking devices
are properly locked into place. Improper locking may result in malfunction.
Wiring
• Wire correctly according to specified procedures in this manual.
• Always use the following size wire when connecting I/O terminals: AWG22 to AWG18 (0.32 to
0.82 mm
• Install external breakers and take other safety measures against short-circuiting in external wiring.
Insufficient safety measures against short-circuiting may result in burning.
• Always connect to a ground of 100 Ω or less when installing the Units. Not connecting to a ground
of 100 Ω or less may result in electric shock.
• Leave the label attached to the top of the Unit when wiring to prevent the entry of foreign matter.
Removing the label may result in malfunction if foreign matter enters the Unit.
• Remove the label after the completion of wiring to ensure proper heat dissipation. Leaving the
label attached may result in malfunction.
• Use crimp terminals for wiring. Do not connect bare stranded wires directly to terminals. Connection of bare stranded wires may result in burning.
• Do not apply voltages to the input terminals in excess of the rated input voltage. Excess voltages
may result in burning.
• Do not apply voltages or connect loads to the output terminals in excess of the maximum switching capacity. Excess voltage or loads may result in burning.
• Disconnect the functional ground terminal when performing withstand voltage tests. Not disconnecting the functional ground terminal may result in burning.
2
).
20
CP1E CPU Unit Hardware User’s Manual(W479)
• Be sure that all the PLC terminal screws and cable connector screws are tightened to the torque
specified in the relevant manuals. The tightening torque for the terminals on the CP1WCIF11/CIF12 terminal block is 0.28 N·m Incorrect tightening torque may result in malfunction.
• The following devices can be connected to pin 6 (+5V) on the built-in RS-232C port on the CPU
Unit or the RS-232C Option Board (CP1W-CIF01) mounted to the CPU Unit. Do not connect pin 6
to any other device.
• RS-422A CJ1W-CIF11 Conversion Adapter
• RS-232C / RS-422A NT-AL001 Conversion Adapter
• NV3W-M20L Programmable Terminal
• Use the cables that are specified in the manual for each device. External devices or the CPU Unit
may be damaged if a commercially available RS-232C computer cable is used.
• Do not pull on the cables or bend the cables beyond their natural limit. Doing either of these may
break the cables.
• Do not place objects on top of the cables or other wiring lines. Doing so may break the cables.
Handling
• To initialize the DM Area, back up the initial contents for the DM Area to backup memory using
one of the following methods.
• Set the number of words of the DM Area to be backed up starting with D0 in the Number of CH
of DM for backup Box in the Startup Data Read Area.
• Include programming to back up specified words in the DM Area to built-in EEPROM by turning
ON A751.15 (DM Backup Save Start Bit).
• Check the ladder program for proper execution before actually running it on the Unit. Not checking
the program may result in an unexpected operation.
• The ladder program and parameter area data in the CP1E CPU Units are backed up in the built-in
EEPROM backup memory. The BKUP indicator will light on the front of the CPU Unit when the
backup operation is in progress. Do not turn OFF the power supply to the CPU Unit when the
BKUP indicator is lit. The data will not be backed up if power is turned OFF and a memory error
will occur the next time the power supply is turned ON.
• With a CP1E CPU Unit, data memory can be backed up to the built-in EEPROM backup memory.
The BKUP indicator will light on the front of the CPU Unit when backup is in progress. Do not turn
OFF the power supply to the CPU Unit when the BKUP indicator is lit. If the power is turned OFF
during a backup, the data will not be backed up and will not be transferred to the DM Area in RAM
the next time the power supply is turned ON.
• Before replacing the battery, supply power to the CPU Unit for at least 30 minutes and then complete battery replacement within 5 minutes. Memory data may be corrupted if this precaution is
not observed.
• The equipment may operate unexpectedly if inappropriate parameters are set. Even if the appropriate parameters are set, confirm that equipment will not be adversely affected before transferring the parameters to the CPU Unit.
• After replacing the CPU Unit, make sure that the required data for the DM Area, Holding Area, and
other memory areas has been transferred to the new CPU Unit before restarting operation.
• Do not attempt to disassemble, repair, or modify any Units. Any attempt to do so may result in malfunction, fire, or electric shock.
• Confirm that no adverse effect will occur in the system before attempting any of the following. Not
doing so may result in an unexpected operation.
• Changing the operating mode of the PLC (including the setting of the startup operating mode).
• Force-setting/force-resetting any bit in memory.
• Changing the present value of any word or any set value in memory.
• When replacing parts, be sure to confirm that the rating of a new part is correct. Not doing so may
result in malfunction or burning.
CP1E CPU Unit Hardware User’s Manual(W479)
21
• Do not touch the Expansion I/O Unit Connecting Cable while the power is being supplied in order
to prevent malfunction due to static electricity.
• Do not turn OFF the power supply to the Unit while data is being transferred.
• When transporting or storing Units or Board, static electricity can destroy LSIs or ICs. Cover the
PCBs with a conductive material and maintain the specified storage temperature.
• Do not touch circuit boards or the components mounted to them with your bare hands. There are
sharp leads and other parts on the boards that may cause injury if handled improperly.
• Double-check the pin numbers when assembling and wiring the connectors.
• Never short-circuit the positive and negative terminals of a battery or charge, disassemble, heat,
or incinerate the battery. Do not subject the battery to strong shocks or deform the battery by
applying pressure. Doing any of these may result in leakage, rupture, heat generation, or ignition
of the battery. Dispose of any battery that has been dropped on the floor or otherwise subjected to
excessive shock. Batteries that have been subjected to shock may leak if they are used.
• Dispose of the product and batteries according to local ordinances as they apply.
• UL standards require that only an experienced engineer can replace the battery. Make sure that
an experienced engineer is in charge of battery replacement. Follow the procedure for battery
replacement given in this manual.
• The following precaution must be displayed on all products that contain a lithium primary battery
(containing at least 6 ppb of perchlorate) and that will be exported to or transported through the
State of California in the USA.
Perchlorate Material - special handling may apply. See
http://www.dtsc.ca.gov/hazardouswaste/perchlorate
A CP1W-BAT01 or CJ1W-BAT01 lithium primary battery (containing at least 6 ppb of perchlorate)
can be mounted in a CP1E-N/NAD- CPU Unit. Display the precaution given above on your
product’s packaging box or shipping box if the product contains a CP1W-BAT01 or CJ1W-BAT01
Battery and is exported to or through the State of California in the USA.
• This product is EMC compliant when assembled in a complete PLC system. Refer to the applicable manual for grounding, cable selection, and any other conditions for EMC compliance.
• This is a Class A product for use in industrial environments. In residential environments it may
cause radio interference, in which case the user may be required to take adequate measures to
reduce interference.
External Circuits
• Always configure the external circuits to turn ON power to the PLC before turning ON power to the
control system. If the PLC power supply is turned ON after the control power supply, temporary
errors may result in control system signals because the output terminals on DC Output Units and
other Units will momentarily turn ON when power is turned ON to the PLC.
• Fail-safe measures must be taken by the customer to ensure safety in the event that outputs from
output terminals remain ON as a result of internal circuit failures, which can occur in relays, transistors, and other elements.
• If the I/O Hold Bit is turned ON, the outputs from the PLC will not be turned OFF and will maintain
their previous status when the PLC is switched from RUN or MONITOR mode to PROGRAM
mode. Make sure that the external loads will not produce dangerous conditions when this occurs.
(When operation stops for a fatal error, including those produced with the FALS instruction, all outputs from PLC will be turned OFF and only the internal output status in the CPU Unit will be maintained.)
22
CP1E CPU Unit Hardware User’s Manual(W479)
Operating Environment Precautions
Perform installation following the instructions in this manual
Follow the instructions in this manual to correctly perform installation.
Do not operate the control system in the following locations
• Locations subject to direct sunlight
• Locations subject to temperatures or humidity outside the range specified in the specifications
• Locations subject to condensation as the result of severe changes in temperature
• Locations subject to corrosive or flammable gases
• Locations subject to dust (especially iron dust) or salts
• Locations subject to exposure to water, oil, or chemicals
• Locations subject to shock or vibration
Take countermeasures in the following locations
• Locations subject to static electricity or other forms of noise
• Locations subject to strong electromagnetic fields
• Locations subject to possible exposure to radioactivity
• Locations close to power supplies
CP1E CPU Unit Hardware User’s Manual(W479)
23
Regulations and Standards
Conformance to EC Directives
Applicable Directives
• EMC Directives
• Low Voltage Directive
Concepts
EMC Directives
OMRON devices are electrical components that are designed to be built into equipment and manufacturing systems. OMRON devices that comply with EMC Directives also conform to the related
EMC standards*, so that they can be more easily built into other devices or the overall machine.
Whether the products conform to the standards in the system used by the customer, however, must
be checked by the customer.
EMC-related performance of the OMRON devices that comply with EC Directives will vary depending on the configuration, wiring, and other conditions of the equipment or control panel on which the
OMRON devices are installed. The customer must, therefore, perform the final check to confirm that
devices and the overall machine conform to EMC standards.
* The applicable EMC (Electromagnetic Compatibility) standard is EN61131-2.
Low Voltage Directive
Always ensure that devices operating at voltages of 50 to 1,000 VAC and 75 to 1,500 VDC meet the
required safety standards for the PLC (EN 61131-2).
Conformance to EC Directives
The CP1E PLCs comply with EC Directives. To ensure that the machine or device in which the
CP1E PLC is used complies with EC Directives, the PLC must be installed as follows:
• The CP-series PLC must be installed within a control panel.
• CP-series PLCs complying with EC Directives also conform to EN61131-2. Radiated emission
characteristics (10-m regulations) may vary depending on the configuration of the control panel
used, other devices connected to the control panel, wiring, and other conditions. You must therefore confirm that the overall machine or equipment complies with EC Directives.
• A SYSMAC CP-series PLC is a class A product (for an industrial environment). In residential
areas it may cause radio interference, in which case the user may be required to take adequate
measures to reduce interference.
Trademarks
SYSMAC is a registered trademark for Programmable Controllers made by OMRON Corporation.
CX-One is a registered trademark for Programming Software made by OMRON Corporation.
Windows is a registered trademark of Microsoft Corporation.
Other system names and product names in this document are the trademarks or registered trademarks
of their respective companies.
24
CP1E CPU Unit Hardware User’s Manual(W479)
Related Manuals
The following manuals are related to the CP1E. Use them together with this manual.
Manual nameCat. No. Model numbersApplicationContents
SYSMAC CP Series
CP1E CPU Unit Hardware User’s Manual
(this manual)
SYSMAC CP Series
CP1E CPU Unit Software User’s Manual
SYSMAC CP Series
CP1E CPU Unit Instructions Reference Manual
CS/CJ/CP/NSJ Series
Communications Commands Reference Manual
SYSMAC CP Series
CP1L/CP1E CPU Unit
Introduction Manual
To learn the hardware specifications
of the CP1E PLCs
Use this manual together with the CP1E CPU Unit Software User’s
Manual (Cat. No. W480) and Instructions Reference Manual (Cat. No.
W483).
To learn the software
specifications of the
CP1E PLCs
Use this manual together with the CP1E CPU Unit Hardware User’s
Manual (Cat. No. W479) and Instructions Reference Manual (Cat. No.
W483).
To learn programming instructions in
detail
To learn communications commands for
CS/CJ/CP/NSJseries Controllers in
detail
Note This manual describes commands addressed to CPU Units. It
does not cover commands addressed to other Units or ports (e.g.,
serial communications ports on CPU Units, communications ports
on Serial Communications Units/Boards, and other Communications Units).
To learn the basic
setup methods of the
CP1L/CP1E PLCs
Describes the following information for CP1E
PLCs.
• Overview and features
• Basic system configuration
• Part names and functions
• Installation and settings
• Troubleshooting
Describes the following information for CP1E
PLCs.
• CPU Unit operation
• Internal memory
• Programming
• Settings
• CPU Unit built-in functions
• Interrupts
• High-speed counter inputs
• Pulse outputs
• Serial communications
• Analog I/O function
• Other functions
Describes each programming instruction in
detail.
When programming, use this manual together
with the CP1E CPU Unit Software User’s Manual (Cat. No. W480).
Describes
1) C-mode commands and
2) FINS commands in detail.
Read this manual for details on C-mode and
FINS commands addressed to CPU Units.
Describes the following information for
CP1L/CP1E PLCs.
• Basic configuration and component names
• Mounting and wiring
• Programming, data transfer, and debugging
using the CX-Programmer
• Application program examples
CP1E CPU Unit Hardware User’s Manual(W479)
25
26
CP1E CPU Unit Hardware User’s Manual(W479)
1
\
Overview and Specifications
This section gives an overview of the CP1E, describes its features, and provides its
specifications.
The SYSMAC CP1E Programmable Controller is a package-type PLC made by OMRON that is
designed for easy application. The CP1E includes E-type CPU Units (basic models) for standard control operations using basic, movement, arithmetic, and comparison instructions, and N/NA-type CPU
Units (application models) that supports connections to Programmable Terminals, Inverters, and Servo
Drives.
Basic Models
(E-type CPU Units)
CPU Unit with
10,14 or 20 I/O
Points
Appearance
CPU Unit with 30 or 40 I/O
Points
CP1E Application Models
N-type CPU Units
CPU Unit with
14 or 20 I/O
Points
CPU Unit with
30,40 or 60
I/O Points
NA-type CPU
Units
CPU Unit with
20 I/O Points
Program capacity2K steps8K steps
DM Area capacity2K words
Of these 1,500 words can be written to the built-in
EEPROM.
Mounting Expansion I/O Units and
Expansion Units
Model with transistor outputs
Pulse outputsNot supported.Supported (Model with transistor outputs only)
Built-in serial communications port
Built-in AnalogNot available.Not available.Available
Option BoardNot supported.Not supported. Supported (for one port)
Connection port
for Programming
Device
ClockNot provided.Provided
Using a BatteryCannot be used.Can be used (sold separately).
Backup time of
built-in capacitor
Battery-free operation
Not possible.3 Units maximumNot possible.3 Units maximum
Available (CPU Unit with 10 I/O points only)Available
Not provided.RS-232C port provided
USB portUSB port
50 hours at 25°C40 hours at 25°C
Always battery-free operation.
Only data in the built-in EEPROM will be retained
if power is interrupted for longer than 50 hours.
8K words
Of these 7,000 words can be written to the built-in
EEPROM.
Battery-free operation if no battery is attached.
Only data in the built-in EEPROM will be retained
if power is interrupted for longer than 40 hours.
1-2
CP1E CPU Unit Hardware User’s Manual(W479)
Precautions for Correct UsePrecautions for Correct Use
For CP1E CPU Units, the following I/O memory area will be unstable after a power interruption.
• DM Area (D) (excluding words backed up to the EEPROM using the DM function)
• Holding Area (H)
• Counter Present Values and Completion Flags (C)
• Auxiliary Area related to clock functions(A)
Mount the CP1W-BAT01 Battery (sold separately) to an N/NA-type CPU Unit if data in the above
areas need to be retained after a power interruption. A Battery cannot be mounted to an E-type
CPU Unit.
1-1-2Features
System Configuration
1 Overview and Specifications
1-1 CP1E Overview
1
1-1-2 Features
CX-Programmer
Commercially
available USB
cable
USB port
Peripheral USB port
Analog adjuster
CP1E CPU Unit (An N-type CPU Unit with 40 I/O Points is shown here.)
CP1W-BAT01 Battery (sold separately)
(Can be mounted only to N/NA-type CPU Units.)
Built-in RS-232C port
One slot for an
Option Board
Option Board
One RS-232C portOne RS-422A/485 port
RS-232C Option
Board CP1W-CIF01
(Note) The following Option Boards cannot be used.
RS-422A/485 Option
Board CP1W-CIF11/12
·CP1W-DAM01 LCD Option Board
·CP1W-CIF41 Ethernet Option Board version 1.0
Power supply and input terminals
Expansion Units (Can be mounted to E30/40, N30/40/60 or NA20 CPU Units)
COM 01 03 05 0 7 09 11
NC 00 02 04 06 08 10
CH
IN
CH
00 01 02 03
04 05 06 07
08 09 10 11
OUT
CH
00 01 02 03 04 05 06 07
CH
NC 00 01 02 04 05 07
NC COM COM COM 03 COM 06
EXP
COM 01 03 05 0 7 09 11
NC 00 02 04 06 08 10
CH
IN
CH
00 01 02 03
04 05 06 07
08 09 10 11
OUT
CH
00 01 02 03 04 05 06 07
CH
NC 00 01 02 04 05 07
NC COM COM COM 03 COM 06
EXP
COM 01 03 05 0 7 09 11
NC 00 02 04 06 08 10
CH
IN
CH
00 01 02 03
04 05 06 07
08 09 10 11
OUT
CH
00 01 02 03 04 05 06 07
CH
NC 00 01 02 04 05 07
NC COM COM COM 03 COM 06
Output terminal block
IP ADDRESS:
SUBNET MASK:
COMMERR
10BASE-T
100BASE-TX
One Ethernet port
Ethernet Option Board
CP1W-CIF41 version 2.0
EXP
Programming, Setting, and Monitoring with the CX-Programmer
The CX-Programmer is used as the Programming Device for the CP1E.
Easy Connection with Computers Using Commercially Available
USB Cables
The CX-Programmer is connected using a commercially available USB cable between the computer’s
USB port and the built-in peripheral USB port of the CP1E.
CP1E CPU Unit Hardware User’s Manual(W479)
1-3
1 Overview and Specifications
With E30/40, N30/40/60 or NA20 CPU Units, Add I/O by Connecting
Expansion I/O Units
A total of up to three of the following Expansion I/O Units can be connected to an E30/40, N30/40/60 or
NA20 CPU Unit. (The total of three Units must also include Expansion Units.)
24-input/16-output Unit, 32-output Unit, 12-input/8-output Unit, 16-output Unit, 8-input Unit, or 8-output Unit
With E30/40, N30/40/60 or NA20 CPU Units, Add Analog I/O or
Temperature Inputs by Connecting Expansion Units
With an E30/40, N30/40/60 or NA20 CPU Unit, a total of up to three of the following Expansion Units
can be connected. (The total of three Units must also include Expansion I/O Units.)
Analog I/O Unit, Analog Input Unit, Analog Output Unit, Temperature Sensor Units, CompoBus/S I/O
Link Unit
Quick-response Inputs
By setting a built-in input to quick-response input operation, inputs with signal widths as small as 50 µs
can be read with certainty regardless of the cycle time.
Up to six quick-response inputs can be used.
Quick-response signal to
photomicrosensor or other device
Built-in input
Input bit
Input bit
Note The user setting in the PLC Setup determines if each input is a quick-response input, normal input, interrupt
input, or high-speed counter input.
Cycle time
ON for one scan
in the next cycle
Cycle time
Can read ON signals
shorter than this time.
I/O refresh
1-4
CP1E CPU Unit Hardware User’s Manual(W479)
1 Overview and Specifications
Input Interrupts
An interrupt task can be started when a built-in input turns ON or turns OFF .
Up to six interrupt inputs can be used.
Interrupt input
Built-in input
Interrupt occurs
Note The user setting in the PLC Setup determines if each input is a quick-response input, normal input, interrupt
input, or high-speed counter input.
Interrupt task
Ladder program
END
1-1 CP1E Overview
1
1-1-2 Features
Complete High-speed Counter Functionality
A high-speed counter input can be used by connecting a rotary encoder to a built-in input. A CP1E CPU
Unit is equipped with more than one high-speed counter input, making it possible to control devices for
multiple axes with a single PLC.
Note The user setting in the PLC Setup determines if each input is a quick-response input, normal input, interrupt
input, or high-speed counter input.
• High-speed counters can be used for high-speed processing, using either target value comparison or
range comparison with the counter’s PV to create interrupts.
An interrupt task can be started when the count reaches a specified value or falls within a specified
range.
• High-speed counter input frequency (speed) can be measured.
The input pulse frequency can be measured using the PRV instruction (counter 0 only).
CP1E CPU Unit Hardware User’s Manual(W479)
1-5
1 Overview and Specifications
Versatile Pulse Control for Transistor Output CPU Units
Fixed duty ratio pulse outputs can be output from the CPU Unit’s built-in outputs and used to perform
positioning or speed control with a servomotor or a stepping motor that accepts pulse inputs.
Two pulse outputs at 100 kHz are provided as standard features.
Stepping Motor
Servomotor
(Functions can be assigned.) (See note.)
Note The instruction used to control each output determines whether it is used as a normal output, pulse output,
or PWM output.
16 Built-in Outputs
Two pulse outputs
100 kHz
Positioning is possible with Trapezoidal Acceleration and Deceleration
Trapezoidal acceleration and deceleration can be used for positioning using the PULSE OUTPUT
(PLS2) instruction.
Jogging Can Be Performed
Jogging can be performed by executing the SPED or ACC instruction.
Origin Searches and Origin Returns Can Be Performed Using the ORIGIN
SEARCH Instruction
An accurate origin search combining all I/O signals can be executed with a single instruction. It is
also possible to move directly to an established origin using the ORIGIN SEARCH (ORG) instruction.
1-6
PWM Outputs for Transistor Output CPU Units
Lighting and power control can be performed by outputting variable duty ratio pulse (PWM) output signals from the CPU Unit’s built-in outputs.
Built-in RS-232C Port for N/NA-type CPU Units
The N/NA-type CPU Units have one built-in RS-232C port as a standard feature.
CP1E CPU Unit Hardware User’s Manual(W479)
1 Overview and Specifications
Mounting Serial Option Boards to N30/40/60 or NA20 CPU Units
One Serial Communications Option Board with one RS-232C port or one RS-422A/485 port can be
added to an N30/40/60 or NA20 CPU Unit. With the serial communications port, it is easy to connect to
general components, such as barcode readers, and other components such as PTs, other CP-series
PLCs, and Inverters.
1-1 CP1E Overview
NS-series PT, Barcode Reader, etc.
RS-232C
Built-in RS-232C
port
1
1-1-2 Features
RS-422A/485 Option Board
with the CP1W-CIF11/12 mounted
RS-422A
Modbus-RTU Easy Master Function
Example: Inverter
Serial PLC Links
CP1E, CP1H
CP1L, CJ1M
Built-in Analog for NA-type CPU Units
The NA-type CPU Units have analog functionality, with 2 analog voltage/current inputs and 1 analog
voltage/current output built in.
2 analog inputs
0 to 5V, 1 to 5V
0 to 10V, -10V to 10V
050607 09
02
01
I IN0
11
AG
10
V IN1
08
COM0
COM1
V IN0
04
NC
IOUT0
05 07
NC VOUT0
COM0
06
COM
03
L2/NL1
COM
01
03
00
04
POWER
PRPHL
02
RUN
INH
BKUP
+
-
00
COM COM COM
I IN1
Inverter, etc
• A range of applications is at a resolution of 6,000.
• Application is also possible for process-control sensor input or inverter control without using Expan-
sion I/O Units.
0 to 20mA, 4 to 20mA
1 analog output
0 to 5V, 1 to 5V
0 to 10V, -10V to 10V
0 to 20mA, 4 to 20mA
CP1E CPU Unit Hardware User’s Manual(W479)
1-7
1 Overview and Specifications
1-2Basic Operating Procedure
In general, use the following procedure.
1. Setting Devices and Hardware
Connect the CPU Unit, Expansion I/O Units, and Expansion Units.
Set the DIP switches on the Option Board and Expansion Units as required.
Refer to Section 3 Part Names and Functions and Section 5 Installation and Wiring in the CP1E CPU Unit Hardware User’s Manual (Cat. No. W479).
2. Wiring
Wire the power supply, I/O, and communications.
Refer to Section 5 Installation and Wiring in the CP1E CPU Unit Hardware User’s Manual (Cat. No. W479).
3. Connecting Online to the PLC
Connect the personal computer online to the PLC.
Refer to Section 4 Programming Device in the CP1E CPU Unit Hardware User’s Manual (Cat. No. W479).
4. I/O Allocations
Allocations for built-in I/O on the CPU Unit are predetermined and memory is allocated automatically
to Expansion I/O Units and Expansion Units, so the user does not have to do anything.
Refer to Section 6 I/O Allocation in the CP1E CPU Unit Software User’s Manual (Cat. No. W480).
5. Software Setup
Make the PLC software settings.
With a CP1E CPU Unit, all you have to do is set the PLC Setup.
When using an E-type CPU Unit or when using an N/NA-type CPU Unit without a Battery, be sure to
consider selecting the Clear retained memory area (HR/DM/CNT) Check Box in the Startup Data Read Area in the PLC Settings.
Refer to 3-2-4 Initializing I/O Memory at Startup and Section 7 PLC Setup in the CP1E CPU Unit Software User’s Manual (Cat. No. W480).
6. Writing the Programs
Write the programs using the CX-Programmer.
Refer to Section 4 Programming Concepts in the CP1E CPU Unit Software User’s Manual (Cat. No. W480).
7. Checking Operation
Check the I/O wiring and the Auxiliary Area settings, and perform trial operation.
The CX-Programmer can be used for monitoring and debugging.
Refer to Section 8 Overview and Allocation of Built-in Functions in the CP1E CPU Unit Software User’s Manual (Cat. No. W480).
8. Basic Program Operation
Set the operating mode to RUN mode to start operation.
1-8
CP1E CPU Unit Hardware User’s Manual(W479)
1 Overview and Specifications
1-3Specifications
1-3-1General Specifications
The following table lists the general specifications of CP1E CPU Units.
ItemAC pow er supplyDC power supply
EnclosureMounted in a panel
Dimensions (H × D × W)
WeightCPU Unit with 10 I/O points (CP1E-E10D-): 300g max.
Electrical specifications
Application environment
Terminal blockFixed (not removable)
Terminal screw sizeM3
Applicable standardsConforms to EC Directives.
Grounding methodGround to 100Ω or less.
*1Total of 110 mm with mounting brackets.
*2Excluding cables.
*3Use the external power supply to power input devices. Do not use it to drive output devices.
*4This is the rated value for the maximum system configuration. Use the following formula to calculate power consumption for CPU Units with DC power.
Formula: DC power consumption = (5V current consumption × 5 V/70% (internal power efficiency) + 24V current consumption) × 1.1(current fluctuation factor)
The above calculation results show that a DC power supply with a greater capacity is required.
ModelCP1E-D-ACP1E-D-D
CPU Unit with 10 I/O points (CP1E-E10D-): 90mm
CPU Unit with 14 or 20 I/O points (CP1E-14D-/20D-): 90mm
CPU Unit with 30 I/O points (CP1E-30D-): 90mm
CPU Unit with 40 I/O points (CP1E-40D-): 90mm
CPU Unit with 60 I/O points (CP1E-N60D-): 90mm
CPU Unit with 20 I/O points and built-in analog (CP1E-NA20D-): 90mm
CPU Unit with 14 I/O points (CP1E-14D-): 360g max.
CPU Unit with 20 I/O points (CP1E-20D- ): 370g max.
CPU Unit with 30 I/O points (CP1E-30D- ): 600g max.
CPU Unit with 40 I/O points (CP1E-40D-): 660g max.
CPU Unit with 60 I/O points (CP1E-N60D-): 850g max.
Supply voltage100 to 240 VAC 50/60 Hz24 VDC
Operating voltage range85 to 264 VAC20.4 to 26.4 VDC
Power consumption15 VA/1 00 VAC m ax.
Inrush current
External power supply *
Insulation resistance20 MΩ min. (at 500 VDC) between the external AC ter-
Dielectric strength2,300 VAC 50/60Hz for 1 min between AC external and
Power interrupt time10 ms min.2 ms min.
Ambient operating temperature
Ambient humidity10% to 90%
AtmosphereNo corrosive gas.
Ambient storage temperature
Altitude2,000 m max.
Pollution degree2 or less: Conforms to JIS B3502 and IEC 61131-2.
Noise resistance2 kV on power supply line (Conforms to IEC61000-4-4.)
Overvoltage categoryCategory II: Conforms to JIS B3502 and IEC 61131-2.
EMC immunity levelZone B
Vibration resistanceConforms to JIS 60068-2-6.
Shock resistanceConforms to JIS 60068-2-27.
CPU Unit with 20 I/O points and built-in analog (CP1E-NA20D- ): 680g max.
(CP1E-E10D-A/14D-A/
25 VA/2 40 VAC m ax.
50 VA/1 00 VAC m ax.
70 VA/2 40 VAC m ax.
120 VAC, 20 A for 8 ms max. for cold start at room temperature
240 VAC, 40 A for 8 ms max. for cold start at room temperature
3
Not provided. (CP1E-E10D-A/14D-A/20D-A)
24 VDC, 300 mA (CP1E-NA20D-A/30D-A/
40D-A/N60D-A)
minals and GR terminals
GR terminals leakage current: 5 mA max.
0 to 55°C
-20 to 75°C (excluding battery)
5 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 Hz
Acceleration of 9.8 m/s
2
, 3 times in X, Y, and Z directions
147 m/s
20D-A)
(CP1E-NA20D-A/30D-
A/40D-A/N60D-A)
2
for 100 min in X, Y, and Z directions (10 sweeps of 10 min each = 100 min total)
N60D-D) *
24 VDC, 30A for 20 ms max. for cold start at room temperature
Not provided.
Except between DC primary current and DC secondary
current
Except between DC primary current and DC secondary
current
*1
×85mm*2 × 86mm
*1
× 85mm*2 × 130mm
4
1-3 Specifications
1
1-3-1 General Specifications
CP1E CPU Unit Hardware User’s Manual(W479)
1-9
1 Overview and Specifications
1-3-2Characteristics
The following table gives the characteristics of CP1E CPU Units.
ItemCP1E-ED-
Program capacity2K steps (8 KB) including the symbol table, comments,
Control methodStored program method
I/O control methodCyclic scan with immediate refreshing
Program languageLadder programs
InstructionsApproximately 200
Processing speedOverhead process-
Number of CP1W-series Expansion I/O
Units and Expansion Units connected
• Absolute coordinates: 8000 0000 to 7FFF FFFF
hex (-2147483647 to 2147483647)
Trapezoidal acceleration and deceleration (Cannot
perform S-curve acceleration and deceleration.)
Only target position can be changed.
output or 2 Hz to 32,000 Hz (in increments of 1 Hz)
with 1 output
Accuracy: +1%/-0% at 2 Hz to 10,000 Hz and
+5%/-0% at 10,000 Hz to 32,000 kHz
CP1E-ND-
CP1E-NAD-
1-10
CP1E CPU Unit Hardware User’s Manual(W479)
1 Overview and Specifications
ItemCP1E-ED-
Communica
tions
Number of tasks17
Maximum subroutine number128
Maximum jump number128
Scheduled interrupt tasks1 interrupt task
ClockClock function not included.
Memory backupBuilt-in EEPROMLadder programs and parameters are automatically saved to built-in EEPROM
CIO AreaInput Bits1,600 bits (100 words): CIO 0.00 to CIO 99.15 (CIO 00 to CIO 99)
Wor k A rea (W )1,600 bits (100 words): W0.00 to W99.15 (W0 to W99)
Holding Area (H)800 bits (50 words): H0.00 to H49.15 (H0 to H49)
Auxiliary Area (A)Read-only: 7,168 bits (448 words) (A0 to A447)
Temporary Area (TR) 16 bits: TR0 to TR15
Timer Area (T)256 timer numbers (T0 to T255 (separate from counters))
Counter Area (C)256 counter numbers (C0 to C255 (separate from timers))
Data Memory Area (D)2K words: D0 to D2047
Operating modesPROGRAM Mode: Program execution is stopped.
Built-in RS-232C portNo built-in RS-232C portInterface: Conforms to EIA RS-232C.
Serial option portOption Board cannot be mounted.1 port (Option Board can be mounted only to
Battery backup
*With CP1W-BAT01 Bat-
tery (optional)
Output Bits1,600 bits (100 words): CIO 100.00 to CIO 199.15 (CIO 100 to CIO 199)
Serial PLC Link Words1,440 bits (90 words) : CIO 200.00 to CIO 289.15 (CIO 200 to CIO 289)
The time of error occurrence displays 01-01-01
01:01:01 Sunday.
A section of the Data Memory Area can be saved to the built-in EEPROM.
Battery cannot be mounted.CP1W-BAT01 can be used.
Bits in this area maintain their ON/OFF status when operating mode is changed.
Read/write: 4,896 bits (306 words) (A448 to A753)
Of these, 1,500 words can be saved to the backup
memory (built-in EEPROM) using settings in the
Auxiliary Area.
MONITOR Mode: Programs are executed.
RUN Mode:Programs are executed.
Preparations can be executed prior to program execution in this mode.
Some operations, such as online editing, and changes to present values in I/O memory, are enabled in this mode.
This is the normal operating mode.
Half duplex
Start-stop
15 m max.
• Host Link
• 1:N NT Link
• No-protocol mode
• Serial PLC Links (master, slave)
• Modbus-RTU Easy Master
N30/40/60 and NA20 CPU Units.)
• One RS-232C port: CP1W-CIF01
•
One RS-422A/485 port (not isolated): CJ1W-CIF11
• One RS-422A/485 port (isolated): CP1W-CIF12
• One Ethernet port: CP1W-CIF41 version 2.0
Depends on Option Board.
Depends on Option Board.
• Host Link
• 1:N NT Link
• No-protocol mode
• Serial PLC Links (master, slave)
• Modbus-RTU Easy Master
Included.
Accuracy (monthly deviation):-4.5 min to -0.5 min
at ambient temperature of 55ºC
-2.0 min to +2.0 min at ambient temperature of 25ºC
-2.5 min to +1.5 min at ambient temperature of 0ºC
Maximum battery service life: 5 years
Backup Time
Guaranteed value (ambient temperature: 55ºC):
13,000 hours (approx. 1.5 years)
Effective value (ambient temperature: 25ºC):
43,000 hours (approx. 5 years)
8K words: D0 to D8191
Of these, 7,000 words can be saved to the backup
memory (built-in EEPROM) using settings in the
Auxiliary Area.
CP1E-ND-
CP1E-NAD-
1-3 Specifications
1
1-3-2 Characteristics
CP1E CPU Unit Hardware User’s Manual(W479)
1-11
1 Overview and Specifications
1-3-3Functional Specifications
The following table gives the functional specifications of CP1E CPU Units.
FunctionDescription
Cycle time
management
CPU Unit
built-in
functions
Expansion
I/O Units
and
Expansion
Units
Memory
management functions
Communications
InterruptScheduled interruptsTasks can be executed at a specified inter val (1.0 ms min., Unit: 0.1 ms).
Minimum cycle timeMakes the cycle time consistent.
Cycle time monitoringMonitors the cycle time.
InputsHigh-
OutputsPulse out-
Built-in analogAnalog inputConvert analog signal into digital value range from 0 to 6,000.
Functions supported by both
Expansion I/O Unit
and Expansion Unit
Expansion I/O Units Input response timesThe response time can be increased to reduce the effects of chattering and
Expansion UnitsUnit error detectionErrors in Expansion Units are detected.
Holding I/O memory when changing operating modesThe status of I/O memory can be held when the operating mode is changed.
Automatic backup to the backup memory
(built-in EEPROM)
Peripheral USB port Peripheral bus (toolbus)For communications with programming device (CX-Programmer).
Serial port (N/NA-type only)−
Host Link (SYSWAY) communicationsHost Link commands can be sent from a PT or a computer to read/write I/O
No-protocol communicationsI/O instructions for communications ports (TXD/RXD instructions) can be used
NT Link communicationsI/O memory in the PLC can be allocated and directly linked to various PT func-
Serial PLC LinksUp to 10 words of data per Unit can be shared between up to nine CPU Units
Modbus-RTU Easy Master functionModbus-RTU commands are sent by the Modbus-RTU Master function. Mod-
Input interrupts Interrupt tasks are processed when the built-in input turns ON or OFF.
High-speed counter interruptsThis function counts input pulses with the CPU Unit’s built-in high-speed
speed
counters
inputs
Interrupt inputsRelevant interrupt tasks are executed during the cycle when the CPU Unit
Quick-response inputsInputs can be read without being affected by cycle time.
Normal
inputs
puts (Models with
transistor
outputs
only )
PWM outputs (Models with transistor outputs only )
Normal
outputs
Analog outputConvert digital value range from 0 to 6,000 into analog signal.
I/O refreshing
Load OFF functionAll of the outputs on Expansion I/O Units and Expansion Units are turned OFF
High-speed pulse
inputs
Input pulse frequency measurement
I/O
refres
hing
Input response timesInput constants can be set for Basic I/O Units.
Pulse controlA pulse signal is output and positioning or speed control is performed with a
Origin positioningOrigin searches and origin returns.
Load OFF functionAll of the outputs on the CPU Unit’s I/O can be turned OFF when an error
Cyclic refreshingThe Expansion I/O Units and Expansion Units are cyclically refreshed.
Refreshing by IORFI/O refreshing by IORF instruction.
Cyclic
refreshing
Immediate
refreshing
High-speed pulses from devices such as a rotary encoder are counted. The
counted values are stored in the Auxiliary Area.Interrupt tasks can be executed
when target is reached or by range comparison.
The frequency of pulses input by the PRV instruction is measured.
built-in inputs turn ON or turn OFF.
Use the quick-response inputs to read signals shorter than the cycle time.
The CPU Unit’s built-in I/O are cyclically refreshed.
I/O refreshing by immediate refreshing instructions.
The response time can be increased to reduce the effects of chattering and
noise at input contacts. The response time can be decreased to enable detecting shorter input pulses.
servo driver that accepts a pulse input.
Continuous mode for speed control or independent mode for position control
can be used. There are functions for changing to positioning during speed control and for changing the target value during positioning.
Pulses for which the duty ratio (ratio between ON time and OFF time during
one pulse cycle) can be set are output.
occurs in RUN or MONITOR mode.
(0000 hex) when an error occurs in RUN or MONITOR mode.
noise at input contacts.
The response time can be decreased to enable detecting shorter input pulses.
The CPU Unit is notified that the Expansion Unit stopped due to an error.
The forced-set/reset status can be held when the operating mode is changed .
Automatic backup of ladder programs and parameter area to the backup mem-
ory (built-in EEPROM).
memory, and perform other operations for PLC.
for data transfer with peripheral devices such as bar code readers.
tions, including status control areas, status notification areas, touch switches,
lamps, memory tables, and other objects.
(one polling unit and eight polled units).
* A PT cannot be conneected.
bus slaves, such as inverters, can be easily controlled with serial communications.
counter and executes an interrupt task when the count reaches the preset
value or falls within a preset range (target value or zone comparison).
1-12
CP1E CPU Unit Hardware User’s Manual(W479)
1 Overview and Specifications
FunctionDescription
Powe r supply management
Debugging Online editingThe program can be changed during operation in MONITOR mode or PRO-
Self-diagnosis and
restoration
Maintenance
Security
functions
Memory protectionHolding Area data, DM Area data, Counter Completion Flags, and Counter
Number of power interruptions counterThe number of times power has been interrupted is counted.
Force-set/resetSpecified bits can be set or reset.
Differentiate monitoringON/OFF changes in specified bits can be monitored.
Storing the stop position at errorsThe location and task number where execution stopped for a program error is
Program checkThe programs can be checked for items such as no END instruction and
Error LogDetails and the time of occurance of error codes predefined by the CPU Unit
CPU error detectionCPU Unit WDT errors are detected.
User-defined failure diagnosisErrors can be generated for user-specified conditions:Non-fatal errors (FAL)
Load OFF functionThe built-in outputs, Expansion I/O Unit outputs, and Expansion Unit outputs
Non-fatal error
detection
Fatal Error Detection
Automatic online connection via networkThis function enables automatically connecting to the PLC online when the
Read protection using passwordThis function protects reading and displaying programs using passwords.
Write protection from FINS commandsThis function prohibits writing by using FINS commands sent over the network.
System FAL error detection
(User-defined non-fatal error)
Backup memory error detectionThis function detects when data in the backup memory (built-in EEPROM) that
PLC Setup error detectionThis function detects setting errors in the PLC Setup.
Option Board errorsThis function detects when the Option Board is malfunctioning or discon-
Battery error detection (N/NA-type
CPU Units only)
Built-in analog errors (NA-type CPU
Units only)
Memory error detectionThis function detects errors that occur in memory of the CPU Unit.
I/O bus error detectionThis function detects errors that occur during data transfer between the CPU
Detection of too many I/O pointsThis function detects when more than the maximum number of CP1W Expan-
Program error detectionThis function detects when there is an error in the program.
Instruction processing error
detection
Indirect DM addressing BCD
error
Illegal area access error detection
No END error detectionThis function detects an error when there is no END instruction at the end of
Task error detectionThe execution condition for an interrupt task was met but there is no interrupt
Differentiation overflow error
detection
Invalid instruction error detection
User program area overflow
error detection
Cycle time exceeded error detection
System FALS error detection
(user-defined fatal error)
Present Values are held even when power is turned OFF.
This function is valid only when an optional battery is mounted.
GRAM mode.
recorded.
FALS/FAL errors at startup.
are stored.
and fatal errors (FALS).
are turned OFF.
This function generates a non-fatal (FAL) error when the user-defined condi-
tions are met in program.
stores the ladder program is corrupted.
nected.
This function detects when the battery voltage is low or the batter y is discon-
nected.
* This function is valid only when a battery is mounted and the Do not detect
battery error Check Box is cleared in the PLC Setup.
This function detects built-in analog I/O errors.
Unit and another Unit.
sion I/O Units and Expansion Units are connected to the PLC.
See the following for details.
This function detects an error when the given data value is invalid when exe-
cuting an instruction, or execution of instruction between tasks was attempted.
This function detects an error when an indirect DM/EM address in BCD mode
is not BCD.
This function detects an error when an attempt is made to access an illegal
area with an instruction operand.
the program.
task with the specified number.
This function detects an error when too many differentiated instructions are
entered or deleted during online editing (131,072 times or more).
This function detects an error when an attempt is made to execute an instruc-
tion that is not defined in the system.
This function detects an error when instruction data is stored after the last
address in user program area.
This function monitors the cycle time (10 to 1,000 ms) and stops the operation
when the set value is exceeded.
This function generates a fatal (FALS) error when the user-defined conditions
are met in program.
CX-Programmer is directly connected by a serial connection (peripheral USB
port or serial port).
Read protection: Set a password using the CX-Programmer.
* Overwrite protection function not included.
1-3 Specifications
1
1-3-3 Functional Specifications
CP1E CPU Unit Hardware User’s Manual(W479)
1-13
1 Overview and Specifications
1-14
CP1E CPU Unit Hardware User’s Manual(W479)
2
Ü
Basic System Configuration and
Devices
This section describes the basic system configuration and device models of the CP1E.
This section describes the system configurations using E-type and N/NA-type CP1E CPU Units.
2-1-1Basic System Configuration Using an E-type CPU Unit
The system configuration when using a CP1E E-type CPU Unit is shown below.
Support Software
CX-Programmer
Personal computer
IBM PC/AT or equivalent
CP1E CPU UnitExpansion I/O UnitsExpansion Units
CP1E-E30D-A
CP1E-E40D-A
CP1E-E10D-
CP1E-E14D-A
CP1E-E20D-A
20 or 40 I/O Points
8 inputs
8 outputs
16 outputs
32 outputs
Up to 3 Units can be connected
When a two level layout is created by expansion and distance is required
CP1E CPU Unit
Analog I/O
Analog inputs
Analog outputs
Temperature sensors
CompoBus/S I/O Link Unit
Expansion Units and
Expansion I/O Units
DIN Track
I/O Connecting Cable
CP1W-CN811
Precautions for Correct UsePrecautions for Correct Use
For CP1E CPU Units, the following I/O memory area will be unstable after a power interruption.
• DM Area (D) (excluding words backed up to the EEPROM using the DM function)
• Holding Area (H)
• Counter Present Values and Completion Flags (C)
• Auxiliary Area related to clock functions(A)
Mount the CP1W-BAT01 Battery (sold separately) to an N/NA-type CPU Unit if data in the
above areas need to be retained after a power interruption. A Battery cannot be mounted to
an E-type CPU Unit.
2-2
CP1E CPU Unit Hardware User’s Manual(W479)
2 Basic System Configuration and Devices
2-1-2Basic System Configuration Using an N/NA-type CPU Unit
The system configuration when using a CP1E N/NA-type CPU Unit is shown below.
2-1-2 Basic System Configuration Using an N/NA-type CPU Unit
(NT Link/Host Link)
General component
(No-protocol mode)
CP-series PLC or
CJ1M PLC
(Serial PLC Link)
Up to 3 Units can be connected
Inverter
(Modbus-RTU)
Host computer
(Host Link)
CP1E-N14D-
CP1E-N20D-
RS-232C Option Board
CP1W-CIF01
COMM
When a two level layout is created by expansion and distance is required
CP1E CPU Unit
*Neither the CP1W-DAM01 LCD Option Board nor the CP1W-CIF41
Ethernet Option Board version 1.0 can be used.
RS-422A/485 Option Board
OrOr
CP1W-CIF11
CP1W-CIF12
COMM
Expansion Units and
Expansion I/O Units
Ethernet Option Board
CP1W-CIF41
(version 2.0 or higher)
IP ADDRESS:
SUBNET MASK:
COMMERR
10BASE-T
100BASE-TX
I/O Connecting Cable
CP1W-CN811
Precautions for Correct UsePrecautions for Correct Use
For CP1E CPU Units, the following I/O memory area will be unstable after a power interruption.
• DM Area (D) (excluding words backed up to the EEPROM using the DM function)
• Holding Area (H)
• Counter Present Values and Completion Flags (C)
• Auxiliary Area related to clock functions(A)
Mount the CP1W-BAT01 Battery (sold separately) to an N/NA-type CPU Unit if data in the
above areas need to be retained after a power interruption. A Battery cannot be mounted to
an E-type CPU Unit.
CP1E CPU Unit Hardware User’s Manual(W479)
2-3
2 Basic System Configuration and Devices
2-2CPU Units
This section describes the models of CP1E CPU Units.
2-2-1CPU Unit Models
The CP1E CPU Unit model numbers are configured as shown below.
Unit type
E: Basic model
N: Application model
NA: Application model with built-in analog
The following is a list of available CP1E CPU Unit models.
E-type CPU Units
Number of built-in I/O
points
Name and appearanceModel number
CPU Unit with 10 I/O Points CP1E-E10DR-A 1064AC power
CP1E-E10DT-ASinking tran-
CP1E-E10DT1-ASourcing
E
CP1E-E10DR-DDC power
CP1E-E10DT-DSinking tran-
CP1E-E10DT1-DSo urcing
CPU Unit with 14 I/O Points CP1E-E14DR-A 1486Relays0.16A0.07A 350g max.
Tot al
Number
of
inputs
Number
of
outputs
Power
supply
specifica-
tions
supply 100
to 240 VAC
supply
24VDC
Pro-
DM Area
Output type
Relays2K steps 2K words 0.08A0.04A 300g max.
sistor
transistor
Relays0.08A0.04A 280g max.
sistor
transistor
gram
capacity
capacity
Current
consumption
Weight
5 VDC 24 VDC
0.11A0.00A 280g max.
0.11A0.00A 280g max.
0.11A0.00A 260g max.
0.11A0.00A 260g max.
2-4
E
CP1E CPU Unit Hardware User’s Manual(W479)
2 Basic System Configuration and Devices
Number of built-in I/O
points
Name and appearanceModel number
CPU Unit with 20 I/O Points CP1E-E20DR-A 20128AC power
CPU Unit with 30 I/O Points CP1E-E30DR-A 3018120.17A0.07A540g max.
CPU Unit with 40 I/O Points CP1E-E40DR-A 4024160.17A0.09A650g max.
Tot al
Number
of
inputs
Number
of
outputs
Power
supply
specifica-
tions
supply 100
to 240 VAC
Pro-
DM Area
Output type
Relays2K steps 2K words 0.17A0.08A360g max.
gram
capacity
capacity
Current
consumption
Weight
5 VDC 24 VDC
2-2 CPU Units
2
2-2-1 CPU Unit Models
Note A battery cannot be mounted to an E-type CPU Unit.
N-type CPU Units
Number of built-in I/O
points
Name and appearanceModel number
CPU Unit with 14 I/O Points CP1E-N14DR-A 1486AC power
CP1E-N14DT-ASinking tran-
E
CPU Unit with 20 I/O Points CP1E-N20DR-A 20128AC power
CP1E-N14DT1-ASourcing
CP1E-N14DR-DDC power
CP1E-N14DT-DSinking tran-
CP1E-N14DT1-DSourcing
CP1E-N20DT-ASinking tran-
CP1E-N20DT1A
CP1E-N20DRD
CP1E-N20DT-DSinking tran-
CP1E-N20DT1D
Tot al
Number
of
inputs
Number
of
outputs
Power
supply
specifica-
tions
supply 100
to 240 VAC
supply
24VDC
supply 100
to 240 VAC
DC power
supply
24VDC
Current
Pro-
DM Area
Output type
Relays8K steps 8K words 0.17A0.07A360g max.
sistor
transistor
Relays0.17A0.07A350g max.
sistor
transistor
Relays0.18A0.08A370g max.
sistors
Sourcing
transistors
Relays0.18A0.08A360g max.
sistors
Sourcing
transistors
gram
capacity
capacity
consumption
Weight
5 VDC 24 VDC
0.22A0.02A340g max.
0.22A0.02A340g max.
0.22A0.02A320g max.
0.22A0.02A320g max.
0.23A0.02A340g max.
0.23A0.02A340g max.
0.23A0.02A330g max.
0.23A0.02A330g max.
CP1E CPU Unit Hardware User’s Manual(W479)
2-5
2 Basic System Configuration and Devices
Number of built-in I/O
points
Name and appearanceModel number
CPU Unit with 30 I/O Points CP1E-N30DR-A 301812AC power
CP1E-N30DT-ASinking tran-
CP1E-N30DT1-A
CP1E-N30DR-D
CP1E-N30DT-DSinking tran-
CP1E-N30DT1-D
CPU Unit with 40 I/O Points CP1E-N40DR-A 402416AC power
CP1E-N40DT-ASinking tran-
CP1E-N40DT1-A
CP1E-N40DR-D
CP1E-N40DT-DSinking tran-
CP1E-N40DT1-D
CPU Unit with 60 I/O Points CP1E-N60DR-A 603624AC power
CP1E-N60DT-ASinking tran-
E
CP1E-N60DT1-ASourcin g
CP1E-N60DR-DDC power
CP1E-N60DT-DSinking tran-
CP1E-N60DT1-DSourcing
Tot al
Number
of
inputs
Number
of
outputs
Power
supply
specifica-
tions
supply 100
to 240 VAC
DC power
supply
24VDC
supply 100
to 240 VAC
DC power
supply
24VDC
supply 100
to 240 VAC
supply
24VDC
Current
Pro-
DM Area
Output type
Relays8K steps 8K words 0.21A0.07A600g max.
sistors
Sourcing
transistors
Relays0.21A0.07A515g max.
sistors
Sourcing
transistors
Relays0.21A0.09A660g max.
sistors
Sourcing
transistors
Relays0.21A0.09A575g max.
sistors
Sourcing
transistors
Relays0.21A0.13A850g max.
sistor
transistor
Relays0.21A0.13A720g max.
sistor
transistor
gram
capacity
capacity
consumption
Weight
5 VDC 24 VDC
0.27A0.02A570g max.
0.27A0.02A570g max.
0.27A0.02A485g max.
0.27A0.02A485g max.
0.31A0.02A630g max.
0.31A0.02A630g max.
0.31A0.02A545g max.
0.31A0.02A545g max.
0.31A0.02A790g max.
0.31A0.02A790g max.
0.31A0.02A670g max.
0.31A0.02A670g max.
NA-type CPU Units
Name and appearanceModel number
CPU Unit with 20 I/O
Points and Built-in Analog
E
CP1E-NA20DR-A 2012821AC power
CP1E-NA20DT-DDC power
CP1E-NA20DT1-DSourcing
Number of built-in I/O
points
Number
Tot al
of
inputs
Number
of
outputs
Built-in
analog
AD DA
Power
supply
specifica-
tions
supply 100
to 240 VAC
supply
24VDC
Output
type
Relays8K steps
Sinking
transistor
transistor
Program
capacity
DM Area
capacity
8K words
Current
consumption
5
24
VDC
VDC
0.18A 0.11A
0.23A 0.09A
0.23A 0.09A
Weight
680g
max.
500g
max.
500g
max.
2-6
CP1E CPU Unit Hardware User’s Manual(W479)
2 Basic System Configuration and Devices
2-2-2Optional Products
Optional Products for CPU Units
Name and appearanceModel numberApplications
RS-232C Option BoardCP1W-CIF01Mounted in the option slot of an N30/40/60 or
COMM
NA20 CPU Unit and can be used as an RS232C port.
Current
consumption
5 VDC
24 VDC
Including in
CPU
2-2 CPU Units
Weight
−Including in
CPU
2
Non-isolated RS-422A/485
Option Board
COMM
Isolated RS-422A/485 Option
Board
COMM
Ethernet Option BoardCP1W-CIF41
IP ADDRESS:
SUBNET MASK:
COMMERR
10BASE-T
100BASE-TX
CP1W-CIF11Mounted in the option slot of an N30/40/60 or
NA20 CPU Unit and can be used as an RS422A/485 port.
Maximum transmission distance: 50 m
CP1W-CIF12Mounted in the option slot of an N30/40/60 or
NA20 CPU Unit and can be used as an RS422A/485 port.
Maximum transmission distance: 500 m
Mounted in the option slot of an N30/40/60 or
(version 2.0 or
higher)
NA20 CPU Unit and can be used as an Ether-
net port.
Maximum transmission distance: 100 m (dis-
tance between the hub and the node)
BatteryCP1W-BAT01Mounted in an N/NA-type CPU Unit.
Mount the Battery to an N/NA-type CPU Unit if
data in the following areas need to be
after a power interruption.
• DM Area (D) (excluding words backed up to
the EEPROM using the DM backup function)
• Holding Area (H)
• Counter Present Values and Completion
Flags (C)
• Auxiliary Area related to clock function (A)
A Battery cannot be mounted to an E-type
CPU Unit.
retained
Including in
CPU
Includ-
−
ing in
CPU
0.075A−30g
0.130A−23g
−−−
2-2-2 Optional Products
Note The CP1W-ME05M Memory Cassette, CP1W-DAM01 LCD Option Board, and CP1W-CIF41 Ethernet Option Board ver-
sion 1.0 cannot be used with the CP1E CPU Unit.
CP1E CPU Unit Hardware User’s Manual(W479)
2-7
2 Basic System Configuration and Devices
Installation and Wiring Products
Name and appearanceModel numberSpecifications and application
DIN TrackPFP-50NTrack length: 50 cm, Height: 7.3 mm
PFP-100NTrack length: 1 m, Height: 7.3 mm
PFP-100N2Track length: 1 m, Height: 16 mm
End PlatePFP-MStopper to prevent Units from moving on the DIN Track.
I/O Connecting CableCP1W-CN811Length: 800 mm
This cable is used if the connecting cable for the Expansion I/O
Unit or Expansion Unit is not long enough or for a vertical configuration.
Only one I/O Connecting Cable can be used in each PLC.
2-2-3Unit Versions of CPU Units
Unit Versions
A “unit version” has been introduced to manage CPU Units in the CP Series according to differences in
functionality accompanying Unit upgrades.
Notation of Unit Versions on Products
The unit version is given to the right of the lot number on the nameplate of the products for which
unit versions are being managed, as shown below.
Product nameplate
CP1E-N40DR-A
CPU UNIT
Lot No. 28705 0000 Ver.1.0
OMRON Corporation MADE IN CHINA
Lot No.
Unit version
(example for unit version 1.0)
CP1E CPU Unit
2-8
Confirming Unit Versions with Support Software
CX-Programmer can be used to confirm the unit version of the CP1E CPU Units.
Refer to 4-1 Applicable Programming Devices for CP1E for details on the CX-Programmer.
The CX-Programmer can be used to confirm the unit version using one of the following methods.
• Using the PLC Information
• Using the Unit Manufacturing Information
CP1E CPU Unit Hardware User’s Manual(W479)
2 Basic System Configuration and Devices
Unit Versions
Typ eModel numbersUnit version
CP1E CPU UnitsCP1E-ED-
Unit version 1.
CP1E-ND-
CP1E-NAD-
Unit Versions and Support Software
The relationship between the unit versions of CP1E CPU Units and versions of Support Software is
shown below.
Relationship between Unit Versions and Support Software
This section describes the connection of Expansion I/O Units or Expansion Units to a CP1E CPU Unit.
2-3-1Expandable CPU Units
• Expansion I/O Units and Expansion Units cannot be connected to E10/14/20 or N14/20 CPU Units.
• A total of up to three Expansion I/O Units and Expansion Units can be connected to an E30/40,
N30/40/60 or NA20 CPU Unit.
CP1E E10/14/20 or N14/20 CPU Unit
CP1E E30/40, N30/40/60 or NA20 CPU Unit
A total of up to three CP-series Expansion I/O Units
and Expansion Units can be connected.
CP-series Expansion Units and Expansion I/O
Units cannot be connected.
NCNCNC
COM
01 03 05 07 09 11 01 03 05 07 09 11
NC
00 02 04 06 08 10
CHCH
CH
IN
CH
CH
OUT
CH
CHCH
NC
00 01 02 04 05 07 00 02 04 05 07
NC
COM COM COM COM COM COM03 06 01 03 06
00 02 04 06 08 10
111009080706050403020100
111009080706050403020100
0706050403020100
0706050403020100
40EDR
NCNCNC
COM
01 03 05 07 09 11 01 03 05 07 09 11
NC
00 02 04 06 08 10
00 02 04 06 08 10
CHCH
CH
IN
OUT
EXP
111009080706050403020100
CH
111009080706050403020100
CH
0706050403020100
CH
0706050403020100
CHCH
NC
00 01 02 04 05 07 00 02 04 05 07
NC
COM COM COM COM COM COM03 06 01 03 06
40EDR
NCNCNC
COM
01 03 05 07 09 11 01 03 05 07 09 11
NC
00 02 04 06 08 10
00 02 04 06 08 10
CHCH
CH
IN
OUT
EXP
111009080706050403020100
CH
111009080706050403020100
CH
0706050403020100
CH
0706050403020100
CHCH
NC
00 01 02 04 05 07 00 02 04 05 07
NC
COM COM COM COM COM COM03 06 01 03 06
40EDR
EXP
2-3-2Connection Methods
Connection cables for the Expansion I/O Units and Expansion Units are used to connect the Units.
The length can be extended by using a CP1W-CN811 I/O Connecting Cable (length: 800 mm).
Leave approximately 10mm of space between the CPU Unit and the Exapansion I/O Units or Expan-
sion Units.
2-3-3Maximum Number of I/O Points for an Expansion I/O Unit or
Expansion Unit
Tot a l num b er
CPU Unit
Built-in I/O on CPU Unit
Total
Number
of inputs
of outputs
Number
Built-in
Analog
ADDATotal
of Expansion
I/O Units and
Expansion
Units that can
be connected
CP1E-20D-20128None None Not possible.20128
CP1E-30D-3018123 Units maxi-
CP1E-40D-4024161609664
0 to 5 V, 1 to 5 V, 0 to 10 V, -10 to 10 V, 0 to
20 mA, and 4 to 20 mA
1 analog output
NC
NC
Analog Input UnitCP1W-AD0414 analog inputs
IN
CH
VIN2
VIN4
I IN1I IN3
COM2
COM4NCAG
COM3
VIN1
VIN3COM1
I IN2
I IN4
1 to 5 V, 0 to 10 V, -10 to 10 V, 0 to 20 mA, 4
to 20 mA
Resolution: 1/6,000
0 to 5 V, 1 to 5 V, 0 to 10 V, -10 to 10 V, 0 to
20 mA, and 4 to 20 mA
Resolution: 1/6,000
Current
consumption
Weight
5V24V
0.083A0.110A250g
0.100A0.090A200g
Analog Output UnitCP1W-DA0212 analog outputs
0.040A0.095A200g
1 to 5 V, 0 to 10 V, -10 to 10 V, 0 to 20 mA,
and 4 to 20 mA
Resolution: 1/6,000
OUT
I OUT1I OUT3
VOUT1
CH
CP1W-DA0414 analog outputs
VOUT4
VOUT2
COM4NCAG
COM2
COM3
COM1
VOUT3
I OUT4
I OUT2
1 to 5 V, 0 to 10 V, -10 to 10 V, 0 to 20 mA,
0.080A0.124A200g
and 4 to 20 mA
Resolution: 1/6,000
Temperature Sensor UnitCP1W-TS001Thermocouple inputs K or J, 2 inputs0.040A0.059A250g
CP1W-TS002Thermocouple inputs K or J, 4 inputs0.040A0.059A250g
CP1W-TS101Platinum resistance thermometer inputs
0.054A0.073A250g
Pt100 or JPt100, 2 inputs
CP1W-TS102Platinum resistance thermometer inputs
0.054A0.073A250g
Pt100 or JPt100, 4 inputs
CompoBus/S I/O Link UnitCP1W-SRT21Can perform communications as a Compo-
0.029A−200g
Bus/S slave via 8 inputs and 8 outputs.
No.
S
COMM
ERR
SRT21
EXP
BD H NC(BS+)
BD L NC(BS-) NC
2-12
CP1E CPU Unit Hardware User’s Manual(W479)
2 Basic System Configuration and Devices
2-3-5Restrictions on System Configuration
The following restrictions apply to the CP-series Expansion Units and CP-series Expansion I/O Units
that can be connected to CP1E CPU Units.
Restriction on the Number of Connected Units
A total of up to three Expansion Units and Expansion I/O Units can be connected to an E30/40,
N30/40/60 or NA20 CPU Unit. Expansion Units and Expansion I/O Units cannot be connected to
E10/14/20 or N14/20 CPU Units.
Each CPU Unit can connect one device to pin 6 (+5V power supply) of the CP1W-CIF01 built-in
RS232C port. If one CPU Unit connects two devices, a total of up to two Expansion Units can be connected to the CPU Unit.
Restrictions on External Power Supply Capacity
2-3 Expansion I/O Unit or Expansion Unit
2
2-3-5 Restrictions on System Configuration
The following restrictions apply when using the CPU Unit’s external power supply.
AC-power-supply E30/40, N30/40/60 or NA20 CPU Unit
The power supply capacity is restricted for AC-power-supply E30/40, N30/40/60 or NA20 CPU Units.
It may not be possible to use the full 300 mA of the external power supply, though a CPU Unit can
connect any CP-series Expansion I/O Unit or Expansion Unit.
The entire 300 mA from the external power supply can be used if Expansion Units and Expansion
I/O Units are not connected.
Refer to 2-4-1 External Power Supply Capacity When Expansion I/O Units or Expansion Units areConnected for details.
AC-power-supply or DC-power-supply E10/14/20, N14/20 CPU Unit
There is no external power supply on AC-power-supply or DC-power-supply E10/14/20, N14/20
CPU Units.
Restrictions by ambient temperature
According to the ambient temperature, there are restrictions on power supply voltage and output
load current for the DC-power-supply CPU Units.
Refer to Output Specifications for Relay Outputs in 3-1-3 Common I/O Specifications and in 3-2-4 I/OSpecifications for details.
Restrictions on the Number of Simultaneously ON Points
Use CP1W-32ER/ET/ET1 32-point Output Units with the number of simultaneously ON less than 24
points (75%).
CP1E CPU Unit Hardware User’s Manual(W479)
2-13
2 Basic System Configuration and Devices
Mounting Restriction
When connecting CP-series Expansion Units or Expansion I/O Units to a CPU Unit with AC power,
provide a space of approximately 10 mm between the CPU Unit and the first Expansion Unit or
Expansion I/O Unit.
CP1E CPU Unit
10 mm
Expansion I/O Units or Expansion Units
If sufficient space cannot be provided between the CPU Unit and the first Expansion Unit or Expansion I/O Unit, use the PLC in an ambient temperature of 0 to 50°C.
2-14
CP1E CPU Unit Hardware User’s Manual(W479)
2 Basic System Configuration and Devices
2-4Unit Current Consumption and
2-4 Unit Current Consumption and External
External Power Supply Capacity
This section describes the current consumption and external power supply capacity of units used by the
CP1E.
2-4-1External Power Supply Capacity When Expansion I/O Units or
Expansion Units are Connected
Power of 24 VDC can be supplied to external devices from E30/40, N30/40/60 or NA20 CPU Units.
Calculate the usable capacity of external power supply according to the following example.
Calculation Examples of the Capacity Limit of External Power
Supply
CPU UnitExpansion Units
1st unit2nd unit3rd unit
CP1E-
40D-A
5V0.21A0.08A0.08A0.08A0.2A0.65A≤1.2A
24V0.09A0.124A0.124A0.124A−0.462A≤0.7A
Power
consumption
Usable capacity
of external
power supply
5 V×0.65 A=3.25 W
24 V×0.462 A=11.088 W
18.5 W (Total of usable power consumption) − 14.388 W= 4.162 W
4.162 W/24 V=0.173 A
CP1W-
DA041
CP1WDA041
CP1WDA041
Other
devices
using PLC
internal
power supply
NV3WMR20L
Tota lLimit
14.258 W ≤18.5 W
0.173A≤0.3A
Power Supply Capacity
2
2-4-1 External Power Supply Capacity When Expansion I/O Units or Expansion Units are Connected
Note 1 The current consumption of CP1W-CIF01/11 Option Boards is included in the CPU Unit’s current con-
sumption.
2 The current consumption of CP1W-CIF12 Option Boards is 0.075A (5 VDC).
3 The current consumption of CP1W-CIF41 Option Boards version 2.0 is 0.13A (5 VDC).
4 The current consumptions given in the following table must be added to the current consumption of the
CPU Unit if an Expansion Unit or Expansion I/O Unit is connected.
This section describes the names of the CPU Unit parts and provides the I/O specifications and terminal arrangements. Refer to A-1 Dimensions for the dimensions, A-2 Wiring Diagrams for the wiring dia-
grams.
3-1-1E10/14/20 or N14/20 CPU Units
Part Names and Functions
Input terminal block
Input indicators
Peripheral
USB port
Analog
adjusters
Operation indicators
Output terminals
NumberNameFunction
E-type CPU Unit
CP1E-E10D-
CP1E-E14/20DR-A
Power supply input terminals
Ground terminal
Input terminals
Output indicators
Output terminal
block
Battery
cover
N-type CPU Unit
CP1E-N14/20D-
Built-in RS-232C
communications
status indicator
Built-in
RS-232C port
Input terminal blockThis is the terminal block for inputs such as the power supply input and 24
VDC inputs.
Input indicators (yellow)Input status is displayed. An indicator will be ON when the input is ON.
Peripheral USB portUsed to connect to a personal computer for programming and monitoring
by the CX-Programmer for CP1E.
Analog adjustersBy turning an analog adjuster, it is possible to adjust the value of A642 or
A643 within a range of 0 to 255.
Operation indicatorsThe CPU Unit’s operating status can be confirmed with this indicator.
Refer to CPU Unit Status Indicators (Page 3-3).
Output terminalsLoads such as lamps, contactors, and solenoid valves can be connected.
Power supply input termi-
Power of 100 to 240 VAC or 24 VDC can be supplied.
nals
Ground terminal
Protective ground (): To prevent electric shock, ground to 100 Ω or less.
Input terminalsInput devices such as switches and sensors can be connected.
Output indicators (yellow) Output status is displayed. An indicator will be ON when the output is ON.
Output terminal blockThis is the terminal block for outputs such as relay outputs and transistor
outputs.
Battery cover for N-type
A Battery can be installed by opening the cover. (The Battery is optional).
CPU Units
Built-in RS-232C com-
munications status indi-
This indicator will be flashing when the built-in RS-232C port is in communication mode.
cator
Built-in RS-232C port for
N-type CPU Units
By connecting a PT, the controlled system can be monitored and data can
be collected.
3-2
CP1E CPU Unit Hardware User’s Manual(W479)
CPU Unit Status Indicators
IndicatorColorStatusDescription
POWERGreen
POWER
RUN
RUNGreen
ERR/ALM
INH
ERR/ALMRed
PRPHL
BKUP
INHYellow
PRPHLYellow
BKUPYellow
Lit
Not lit
Lit
Not lit
Lit
Flashing
Not lit
Lit
Not lit
Flashing
Not lit
Lit
Not lit
3 Part Names and Functions
: Not lit : Flashing : Lit
Power is ON.
Power is OFF.
The CP1E is executing a program in either RUN or MONITOR
mode.
Operation is stopped in PROGRAM mode or due to a fatal error.
A fatal error (including FALS execution) or a hardware error (WDT
error) has occurred.
CP1E operation will stop and all outputs will be turned OFF.
A non-fatal error has occurred (including FAL execution).
CP1E operation will continue.
Normal
The Output OFF Bit (A500.15) was turned ON.
All outputs will be turned OFF.
Normal
Communications (either sending or receiving) are in progress
through the peripheral USB port.
Other than the above.
The user programs, parameters, or specified DM Area words are
being written to the backup memory (built-in EEPROM).
Other than the above.
3-1 CPU Units
3
3-1-1 E10/14/20 or N14/20 CPU Units
Precautions for Safe Use
Do not turn OFF the power supply to the PLC when the BKUP indicator is lit. It indicates that
data is being written to the backup memory (built-in EEPROM).
If the power supply is turned OFF while the BKUP indicator is ON, data in the backup memory
(built-in EEPROM) may be destroyed.
CP1E CPU Unit Hardware User’s Manual(W479)
3-3
3 Part Names and Functions
Terminal Arrangements
Input Arrangement
AC Power Supply
CP1E-E10D-A
CIO 0
L1 L2/N
CP1E-14D-A
L1 L2/N
CP1E-20D-A
L1 L2/N
COM 010305
000204NC
CIO 0
COM 01030507NCNC
00020406NCNCNC
CIO 0
COM 010305070911
000204060810NC
L1,L2/N : Power supply terminal
: Protective ground terminal
COM : Common terminal
00 to 05 : Input terminal
NC : No connection
L1,L2/N : Power supply terminal
: Protective ground terminal
COM : Common terminal
00 to 07 : Input terminal
NC : No connection
L1,L2/N : Power supply terminal
: Protective ground terminal
COM : Common terminal
00 to 11 : Input terminal
NC : No connection
DC Power Supply
CP1E-E10D-D
CIO 0
+
-
COM 010305
000204NC
CP1E-N14D-D
CIO 0
+
-
COM 01030507NCNC
00020406NCNCNC
CP1E-N20D-D
CIO 0
+
-
COM 010305070911
000204060810NC
+,- : Power supply terminal
: Protective ground terminal
COM : Common terminal
00 to 05 : Input terminal
NC : No connection
+,- : Power supply terminal
: Protective ground terminal
COM : Common terminal
00 to 07 : Input terminal
NC : No connection
+,- : Power supply terminal
: Protective ground terminal
COM : Common terminal
00 to 11 : Input terminal
NC : No connection
3-4
CP1E CPU Unit Hardware User’s Manual(W479)
Output Arrangement
AC Power Supply and DC Power Supply
CP1E-E10D-
00010203
COM COM NC COM NC
CIO 100
CP1E-14D-
00010203
COM COM NC COM
CIO 100
0405NC
NC
COMNC
3 Part Names and Functions
COM : Common terminal
00 to 03 : Output terminal
NC : No connection
3-1 CPU Units
COM : Common terminal
00 to 05 : Output terminal
NC : No connection
CP1E-20D-
00010203
COM COM NC COM
CIO 100
040507
06
COMNC
COM : Common terminal
00 to 07 : Output terminal
NC : No connection
3
3-1-1 E10/14/20 or N14/20 CPU Units
CP1E CPU Unit Hardware User’s Manual(W479)
3-5
3 Part Names and Functions
3-1-2E30/40, N30/40/60 or NA20 CPU Units
Part Names and Functions
Input terminal
block
Input
indicators
Peripheral
USB port
Analog
adjusters
Operation
indicators
E-type CPU Unit
CP1E-E30/40DR-A
Power supply
input terminals
External power
supply
Input terminals
Output terminals
Ground
terminal
Expansion
I/O Unit
connector
Output
indicators
Output
terminal
block
Battery
cover
N/NA-type CPU Unit
CP1E-N30/40/60D-
CP1E-NA20D-
Built-in RS-232C communications
status indicator
Built-in RS-232C
port
NumberNameFunction
Input terminal blockThis is the terminal block for inputs such as the power supply input and
24-VDC inputs.
Input indicators (yellow)Input status is displayed. An indicator will be ON when the input is ON.
Peripheral USB portUsed to connect to a personal computer for programming and monitor-
ing by the CX-Programmer for CP1E.
Analog adjustersBy turning an analog adjuster, it is possible to adjust the value of A642
or A643 within a range of 0 to 255.
Operation indicatorsThe CPU Unit’s operating status can be confirmed with this indicator.
Refer to CPU Unit Status Indicators (Page 3-7).
Power supply input terminal Power of 100 to 240 VAC or 24 VDC can be supplied.
Input terminalsInput devices such as switches and sensors can be connected.
Ground terminal
Protective ground (): To prevent electric shock, ground to 100 Ω or
less.
Serial Option
Board slot
Analog input
terminals
Analog output
terminals
3-6
Functional ground (): If noise is a significant source of errors or if
electrical shock is a problem, connect to the protective ground terminal
and ground both with a ground of 100Ω or less (AC power supply only).
Expansion I/O Unit connector
CP-series Expansion I/O Units or Expansion Units such as Analog I/O
Units, and Temperature Sensors can be connected.
Refer to 5-2-4 Connecting Expansion I/O Units and Expansion Units.
Output indicators (yellow)Output status is displayed. An indicator will be ON when the output is
ON.
Output terminal blockThis is the terminal block for outputs such as relay outputs, transistor
outputs, and the external power supply output.
Output terminalsLoads such as lamps, contactors, and solenoid valves can be con-
nected.
External power supply ter-
minals
The external supply terminals output up to 300 mA max at 24 VDC.
They can be used as a service power supply for input devices (AC
power supply only).
Battery cover for N/NA-type
A Battery can be installed by opening the cover. (Battery is optional).
CPU Units
Built-in RS-232C communications status indicator
This indicator will be flashing when the built-in RS-232C port is in com-
munication mode.
CP1E CPU Unit Hardware User’s Manual(W479)
3 Part Names and Functions
NumberNameFunction
Option Board slot for N/NAtype CPU Units
Built-in RS-232C port for
N/NA-type CPU Units
Analog input terminalsAnalog output devices such as switches and sensors can be connected.
Analog output terminalsAnalog input device can be connected.
distance: 50 m) or CP1W-CIF12 RS-422A/485 Option Board
(Maximum transmission distance: 500 m)
• CP1W-CIF41 Ethernet Option Board version 2.0(Maximum
transmission distance: 100 m)
By connecting a PT, the controlled system can be monitored and data
can be collected.
CPU Unit Status Indicators
3-1 CPU Units
POWER
RUN
ERR/ALM
INH
PRPHL
BKUP
IndicatorColorStatusDescription
POWERGreen
Lit
Not lit
RUNGreen
Lit
Not lit
ERR/ALMRed
Lit
Flashing
Not lit
INHYellow
Lit
Not lit
PRPHLYellow
Flashing
Power is ON.
Power is OFF.
The CP1E is executing a program in either RUN or MONITOR mode.
Operation is stopped in PROGRAM mode or due to a fatal error.
A fatal error (including FALS execution) or a hardware error (WDT
error) has occurred.
CP1E operation will stop and all outputs will be turned OFF.
A non-fatal error has occurred (including FAL execution).
CP1E operation will continue.
Normal
The Output OFF Bit (A500.15) was turned ON.
All outputs will be turned OFF.
Normal
Communications (either sending or receiving) are in progress through
the peripheral USB port.
: Not lit : Flashing : Lit
3
3-1-2 E30/40, N30/40/60 or NA20 CPU Units
BKUPYellow
Precautions for Safe Use
Do not turn OFF the power supply to the PLC when the BKUP indicator is lit. It indicates that
data is being written to the backup memory (built-in EEPROM).
If the power supply is turned OFF while the BKUP indicator is ON, data in the backup memory
(built-in EEPROM) may be destroyed.
CP1E CPU Unit Hardware User’s Manual(W479)
Not lit
Lit
Not lit
Other than the above.
The user program, parameters, or specified DM Area words are being
written to the backup memory (built-in EEPROM).
Other than the above.
3-7
3 Part Names and Functions
Terminal Arrangements
Input Arrangement
AC Power Supply
CP1E-30D-A
CIO 0
L1 L2/N
CP1E-40D-A
L1 L2/N
CP1E-N60D-A
COMNC01 0305 070911
00 0204 060810
CIO 0CIO 1
COM 01 03 05
00 02 04
07 09 11
06 08 10
CIO 1
01 0305
00 0204
01 03 05
00 02 04
07 09
06 08 10
L1, L2/N : Power supply terminal
COM : Common terminal
00 to 11 : Input terminal
: Functional ground terminal
: Protective ground terminal
NC : No connection
V IN0, V IN1 : Analog voltage Input
11
I IN0, I IN1 : Analog current Input
COM0, COM1: Common terminal for analog
AG : Analog 0V
CIO 0CIO 1CIO 2
L1 L2/N
COM 01 03 05
00 02 04
CP1E-NA20DR-A
CIO 0
L1 L2/N
01 0305 070911
COM
00 0204 060810
DC Power Supply
CP1E-N30D-D
+
-
COM
01 0305 070911
NC
CP1E-N40D-D
+
NC
CP1E-N60D-D
00 0204 060810
CIO 0CIO 1
COM
-
01 03 05 07 09 11
02
0408
CIO 0CIO 1
07 09 11
06 08 10
0610
VIN1
06
04
07 09
06 08 10
COM1
NC
08
01 03 05
00 02 04
CIO 90CIO 91
I IN0 AG I IN1
COM0
VIN0
01 0305
00 0204
01 03 05 07 09 11
000002
11
10
01 03 05
00 02 04
07 09
06 08 10
11
+, - : Power supply terminal
COM : Common terminal
00 to 11 : Input terminal
NC : No connection
: Protective ground terminal
V IN0, V IN1 : Analog voltage Input
I IN0, I IN1 : Analog current Input
COM0, COM1: Common terminal for analog
AG : Analog 0V
3-8
+
COM
-
NC
CIO 0CIO 1CIO 2
CP1E-NA20D-D
+
-
COM
00NC02 04 0608 10
CIO 0CIO 90CIO 91
01 03 05 07 09 11
02
01 0305 070911
0610
0408
01 03 05 07 09 11
06
00000002
I IN0 AG I IN1
COM0
VIN0
04
VIN1
08
COM1
01 03 05 07 09 11
10
02
06
04
10
08
CP1E CPU Unit Hardware User’s Manual(W479)
Output Arrangement
AC Power Supply
CP1E-30D-A
00 01 02 04 05 07 00
+
-
COMCOMCOMCOMCOM
CIO 100CIO 101
CP1E-40D-A
+00010702 03 04 0600 01
-
CIO 100CIO 101
CP1E-N60D-A
+
00 01 02 04 05 07 00 02 04 05 07 00 02 04 05 07
COM COM COM 03 COM 06 COM 01 03 COM 06 COM 01 03 COM 06
−
CIO 100CIO 101CIO 102
CP1E-NA20DR-A
0306
COM COM05 07 COM
02
01 03
03 04 06
0205
3 Part Names and Functions
+,- : External supply terminal
COM : Common terminal
00 to 07 : Output terminal
VOUT0 : Analog voltage Output
I OUT0 : Analog current Output
COM0 : Common terminal for analog
COMCOMCOM
3-1 CPU Units
3
3-1-2 E30/40, N30/40/60 or NA20 CPU Units
00 01 02 04 05 07 NC
+
-
COMCOMCOMCOMNC
CIO 100CIO 190
0306
IOUT0
VOUT0
COM0
DC Power Supply
CP1E-N30D-D
NC
00
NC
COM COM COMCOMCOM
CIO 100CIO 101
CP1E-N40D-D
00
NC
COM COMCOMCOM07
NC
CIO 100CIO 101
CP1E-N60D-D
00
NC
COM COM 03 COM 06 COM 01 03 COM 06 COM 01 03 COM 06
COM
NC
CIO 100CIO 101CIO 102
CP1E-NA20D-D
00
NC
COM COM COMCOMNC
NC
CIO 100CIO 190
020104 05 07 00 02
030601
020103 04 06 00 01 03 04 06
05
01 02 04 05 07 00 02 04 05 07 00 02 04 05 07
020104 05 07 NC
0306
COM
VOUT0
03
02
IOUT0
COM0
COM
NC : No connection
COM : Common terminal
00 to 07 : Output terminal
VOUT0 : Analog voltage Output
I OUT0 : Analog current Output
COM0 : Common terminal for analog
05 07
CP1E CPU Unit Hardware User’s Manual(W479)
3-9
3 Part Names and Functions
3-1-3Common I/O Specifications
The following table gives the specifications that apply to the built-in I/O on a CP1E CPU Unit.
Specifications
ItemSpecification
Input type
Input bitsCIO 0.00 to CIO 0.01
Input voltage24 VDC, +10%, -15%
Applicable
sensors
Input
impedance
Input current7.5 mA typical7.5 mA typical5 mA typical
ON voltage/
current
OFF voltage/
current
ON response
*2
time
OFF response
*2
time
Circuit
configuration
High-speed counter inputs
or normal inputs
2-wire and 3-wire sensors
3.3 kΩ3.3 kΩ4.8 kΩ
3 mA min. at 17.0 VDC min. 3 mA min. at 17.0 VDC min. 3 mA min. at 14.4 min.
1 mA max. at 5.0 VDC max.1 mA max. at 5.0 VDC max.1 mA max. at 5.0 VDC max.
E-type CPU Unit: 50 μs min.
N/NA-type CPU Unit: 2.5 μs min.
E-type CPU Unit: 50 μs min.
N/NA-type CPU Unit: 2.5 μs min.
E-type CPU UnitN/NA-type CPU Unit
Inputs: CIO 0.00 to CIO 0.07
COM
IN
3.3kΩ
IN
Input indicator
1000pF
910Ω
High-speed counter inputs,
interrupt inputs, quick-
response inputs
or normal inputs
CIO 0.08 to CIO 0.11,
CIO 0.02 to CIO 0.07
*1
CIO 1.00 to CIO 1.11 and
CIO 2.00 to CIO 2.11
50 μs max. 1 ms max.
50 μs max. 1 ms max.
Inputs: CIO 0.00, CIO 0.01
Internal
circuits
COM
IN
3.3kΩ
IN
Input indicator
1000pF
4.3kΩ
Normal inputs
Internal
circuits
*1
3-10
Inputs: CIO 0.08 to CIO 0.11
and CIO 1.00 to CIO 1.11Inputs: CIO 0.02 to CIO 0.07
COM
IN
4.8kΩ
IN
Input indicator
750Ω
Internal
circuits
COM
IN
3.3kΩ
IN
Input indicator
1000pF
910Ω
Inputs: CIO 0.08 to CIO 0.11, CIO 1.00
to CIO 1.11 and CIO 2.00 to CIO 2.11
IN
4.8kΩ
IN
COM
CP1E CPU Unit Hardware User’s Manual(W479)
Input indicator
750Ω
Internal
circuits
Internal
circuits
3 Part Names and Functions
*1 The bits that can be used depend on the model of CPU Unit.
*2 The response time is the delay caused by hardware. The delay set in the PLC Setup (0 to 32 ms, default: 8 ms)
for a normal input must be added to this value.
Pulse plus direction input mode,
Increment mode
Up/down input mode
N/NA-type: 0.00/0.01N/NA-type: 0.00/0.01
10.0μs min.
ON
OFF
2.5μs
min.
2.5μs
min.
90%
50%
10%
Differential phase mode
20.0μs min.
ON
OFF
ON
OFF
T1T2T3T4
90%
50%
10%
90%
50%
T1, T2, T3, T4: 2.5 μs min.
10%
3-1 CPU Units
ON
OFF
E-type: 0.00 to 0.07
N/NA-type: 0.02 to 0.07
100μs min.
50μs
min.
50μs
min.
90%
50%
10%
ON
OFF
ON
OFF
E-type: 0.00 to 0.03
N/NA-type: 0.02/0.03
200μs min.
T1T2T3T4
Output Specifications for Relay Outputs
CP1E-DR-
ItemSpecification
Maximum switching capacity2 A 250 VAC (cosφ= 1)
2 A 24 VDC (4 A/common)
Minimum switching capacity10 mA 5 VDC
Service life of
relay
ON response time15 ms max.
OFF response time15 ms max.
Circuit configuration
Electrical Resistive
200,000 operations (24 VDC)
load
Inductive
70,000 operations (250 VAC, cosφ = 0.4)
load
Mechanical20,000,000 operations
Output indicator
OUT
90%
50%
10%
90%
50%
T1, T2, T3, T4: 50 μs min.
10%
3
3-1-3 Common I/O Specifications
CP1E CPU Unit Hardware User’s Manual(W479)
Internal
circuits
OUT
COM
250 VAC, 2A,
24 VDC, 2 A
max.
3-11
3 Part Names and Functions
C
Estimating the Service Life of Relays
Under normal conditions, the service life of output contacts is as shown above. The service life of
relays is as shown in the following diagram as a guideline.
CP1E-DR-
1000
700
500
300
200
100
70
)
50
4
30
20
125 VAC cosφ= 0.4
10
Life (x 10
7
5
250 VAC cosφ= 0.4/
3
30 VDC, τ = 7ms
2
1
0.1 0.2 0.3 0.5 0.7 1 2 3 5 7 10
125-VAC resistive load
Contact current (A)
30-VDC/250-VAC
resistive load
Relationship between Continuous Simultaneous ON Rate and Ambient
Temperature
There are restrictions on the power supply voltage and output load current imposed by the ambient
temperature. Make sure that the power supply voltage and output load current are within the following ranges.
CP1E-N14DR-D
CP1E-N20DR-D
100%
Power voltage
21.6VDC
50%
Power voltage
20.4VDC
0%
Ambient temperature
CP1E-14DR-A
CP1E-20DR-A
CP1E-N20DT-
100%
50%
55
˚C
45
40
CP1E-N30DR-DCP1E-N40DR-DCP1E-N60DR-D
100
%
Power voltage
50%
Power voltage
0%
21.6VDC
20.4VDC
35 45 55˚C
Ambient temperature
100%
50%
0%
Power voltage
21.6VDC
Power voltage
20.4VDC
3045
Ambient temperature
100%
Power voltage:
21.6VDC
50%
Power voltage:
20.4VDC
50
0%
55
˚
Ambient temperature
CP1E-NA20DR-A
100%
80%
40 45 55˚C
3-12
0%
Ambient temperature
50
0%
55
˚C
Ambient temperature
50 55˚C
Note The above restrictions apply to the relay output load current from the CPU Unit even if Expansion I/O Units
are not connected.
CP1E CPU Unit Hardware User’s Manual(W479)
3 Part Names and Functions
Output Specifications for Transistor Outputs (Sinking or Sourcing)
N/NA-type CPU Unit: 0.1 ms max.
FuseNot provided.
Circuit
configuration
• N/NA-type CPU Unit: Normal outputs CIO
100.00 to CIO 100.01 (sinking)
Internal
circuits
• N/NA-type CPU Unit: Normal outputs CIO
100.00 to CIO 100.01 (sourcing)
Internal
circuits
Internal
circuits
Internal
circuits
*1
OUT
L
~
OUT
L
24 VDC,
4.5 to 30
COM(–)
COM(+)
OUT
OUT
VDC
24 VDC,
4.5 to 30
VDC
L
~
L
CIO 100.02 to CIO 100.07, CIO 101.00 to
CIO 101.07 and CIO 102.00 to CIO 102.07
1.5V max.
1 ms max.
• E-type CPU Unit: Normal outputs CIO
100.00 to CIO 100.03 (sinking)
• N/NA-type CPU Unit: Normal outputs CIO
100.02 to CIO 102.07 (sinking)
OUT
L
~
OUT
COM(–)
L
24 VDC,
4.5 to 30
VDC
Internal
circuits
• E-type CPU Unit: Normal outputs CIO
100.00 to CIO 100.03 (sourcing)
• N/NA-type CPU Unit: Normal outputs CIO
100.02 to CIO 102.07 (sourcing)
COM(+)
Internal
circuits
OUT
OUT
24 VDC,
4.5 to 30
VDC
L
~
L
*2
3-1 CPU Units
3
3-1-3 Common I/O Specifications
*1 Also do not exceed 0.9 A for the total of CIO 100.00 to CIO 100.03, which are different common.
*2 The bits that can be used depend on the model of CPU Unit.
CP1E CPU Unit Hardware User’s Manual(W479)
3-13
3 Part Names and Functions
Precautions for Correct UsePrecautions for Correct Use
Do not connect a load to an output terminal or apply a voltage in excess of the maximum switching capacity.
Pulse Outputs (CIO 100.00 and CIO 100.01)
ItemSpecification
Maximum switching capacity100 mA 4.5 to 26.4 VDC
Minimum switching capacity7 mA 4.5 to 26.4 VDC
Maximum output frequency100 kHz
Output waveform
OFF
90
%
ON
10
%
4µs min.
2µs min.
The OFF and ON refer to the output transistor. The output transistor is ON at
level “L”.
Additional Information
• The load for the above values is assumed to be the resistive load, and does not take into
account the impedance for the connecting cable to the load.
• Due to distortions in pulse waveforms resulting from connecting cable impedance, the pulse
widths in actual operation may be smaller than the values shown above.
PWM Output (CIO 100.01)
ItemSpecification
Maximum switching capacity30 mA 4.5 to 26.4 VDC
Maximum output frequency32 kHz
PWM output accuracyFor ON duty +1%, -0%:10 kHz output
For ON duty +5%, -0%: 0 to 32 kHz output
Output waveform
OFF
3-14
ON
ON
t
T
ON duty=
t
ON
×
100
T
%
The OFF and ON refer to the output transistor. The output transistor is ON at
level “L”.
CP1E CPU Unit Hardware User’s Manual(W479)
3 Part Names and Functions
Analog I/O (NA-type CPU Units)
The NA-type CPU Units of the CP1E CPU Units are equipped with 2 built-in analog inputs and 1
built-in analog output.
Analog Input Specifications
ItemVoltage inputCurrent input
Number of inputs2 inputs (Allocated 2 words: CIO 90 to CIO 91.)
Input signal range0 to 5 V, 1 to 5 V, 0 to 10 V, or -10
to 10 V
Max. rated input±15 V±30 mA
External input impedance1 MΩ min.Approx. 250Ω
Resolution 1/6000
Overall accuracyAt 25°C±0.3% full scale±0.4% full scale
0 to 55°C±0.6% full scale±0.8% full scale
A/D conversion
data
Averaging functionSupported (Set for individual inputs in the PLC Setup.)
Open-circuit detection functionSupported (Value when disconnected: 8000 hex)
-10 to 10 VF448 to 0BB8 hex FS
Other ranges0000 to 1770 hex FS
0 to 20 mA or 4 to 20 mA
Analog Output Specifications
ItemVoltage outputCurrent output
Number of outputs1 output (Allocated 1 word: CIO 190.)
Output signal range0 to 5 V, 1 to 5 V, 0 to 10 V, or -10
to 10 V
Allowable external output load resistance
External input impedance0.5Ωmax.---
Resolution 1/6000
Overall accuracyAt 25°C±0.4% full scale
0 to 55°C±0.8% full scale
D/A conversion
data
* When the analog current output is 0 to 20mA, the accuracy cannot be ensured at 0.2mA or less.
-10 to 10 VF448 to 0BB8 hex FS
Other ranges0000 to 1770 hex FS
1 kΩ min.600Ω max.
0 to 20 mA* or 4 to 20 mA
3-1 CPU Units
3
3-1-3 Common I/O Specifications
Shared I/O Specifications
ItemSpecification
Conversion time2 ms/point (6 ms total for 2 analog inputs and 1 analog output.)
Isolation method Photocoupler isolation between analog I/O terminals and internal circuits. No
CP1E CPU Unit Hardware User’s Manual(W479)
isolation between analog I/O signals.
3-15
3 Part Names and Functions
3-1-4Optional Serial Communications Port for N/NA-type CPU Units
The Serial Communication Port can be used for a CP1E N/NA-type CPU Unit.
When mounting an Option Board, first remove the slot cover.
Grasp both of the cover’s up/down lock levers at the same time to unlock the cover, and then pull the
cover out.
Then to mount the Option Board, check the alignment and firmly press it in until it snaps into place.
Precautions for Correct UsePrecautions for Correct Use
Always turn OFF the power supply to the PLC before mounting or removing an Option Board.
3-16
CP1E CPU Unit Hardware User’s Manual(W479)
3 Part Names and Functions
Built-in RS-232C Port and CP1W-CIF01 RS-232C Option Board
FrontRear
Communications
status indicator
COMM
RS-232C connector
RS-232C Connector
5
9
1
6
Connector hoodFGFrame ground−
CPU Unit connector
PinAbbr.SignalSignal direction
1FGFrame ground−
2SD(TXD)Send dataOutputs
3RD(RXD)Receive dataInputs
4RS(RTS)Request to sendOutputs
5CS(CTS)Clear to sendInputs
65VPower−
7DR(DSR)Data set readyInputs
8ER(DTR)Data terminal readyOutputs
9SG(0V)Signal ground−
3-1 CPU Units
3
3-1-4 Optional Serial Communications Port for N/NA-type CPU Units
Note The following devices can be connected to pin 6 (+5V) on the built-in RS-232C port on the CPU Unit or the
RS-232C Option Board (CP1W-CIF01) mounted to the CPU Unit. Do not connect pin 6 to any other device.
• RS-422A CJ1W-CIF11 Conversion Adapter
• RS-232C / RS-422A NT-AL001 Conversion Adapter
• NV3W-M20L Programmable Terminal
CP1W-CIF11 or CP1W-CIF12 RS-422A/485 Option Board
FrontRear
Communications
status indicator
COMM
RDA- RDB+ SDA- SDB+ FG
RS-232C connector
CPU Unit connector
DIP switch for operation
settings
CP1E CPU Unit Hardware User’s Manual(W479)
3-17
3 Part Names and Functions
RS-422A/485 Terminal Block
Tighten screws on the terminal
block to 0.28 N.m.
RDA-
RDB+
SDA-
FG
SDB+
DIP switch for operation settings
N
O
12345
PinSetting
1ONON (both ends)Terminating resistance selection
6
OFFOFF
2ON2-wire connections
2-wire or 4-wire selection
*1
OFF4-wire connections
3ON2-wire connections
2-wire or 4-wire selection
*1
OFF4-wire connections
4−−Not used.
5ONRS control enabled
RS control selection for RD
*2
OFFRS control disabled (Data
always received.)
6ONRS control enabled
RS control selection for SD
*3
OFFRS control disabled (Data
always sent.)
*1 Set both pins 2 and 3 to either ON (2-wire) or OFF (4-wire).
*2 To disable the echo-back function, set pin 5 to ON (RS control enabled).
*3 When connecting to a device on the N side in a 1: N connection with the 4-wire method,
set pin 6 to ON (RS control enabled).
Also, when connecting by the 2-wire method, set pin 6 to ON (RS control enabled).
CP1W-CIF41 Ethernet Option Board
FrontRear
Label
Attach the label here to show IP
address and subnet mask.
Ethernet Connector
Used to connect the Ethernet
twisted-pair cable.
LED Indicators
Display the operating status of the Option Board.
CPU Unit connector
3-18
CP1E CPU Unit Hardware User’s Manual(W479)
3 Part Names and Functions
LED Indicators
IndicatorColorStatusMeaning
COMMYellowNot litNot sending or receiving data.
FlashingSending or receiving data.
ERRRedNot litUnit normal.
Lit An fatal error has occurred at the Unit.
FlashingAn no-fatal error has occurred at the unit.
Ethernet Connectors
The following standards and specifications apply to the connectors for the Ethernet twisted-pair
cable.
Electrical specifications: Conforming to IEEE802.3 standards
3-1 CPU Units
Connector structure: RJ45 8-pin Modular Connector (conforming to ISO8877)
Connector PinSignal NameAbbr.Signal Direction
1Transmission data +TD+Output
2Transmission data -TD-Output
3Reception data +RD+Input
4Not used-----5Not used-----6Reception data -RD-Input
7Not used-----8Not used-----HoodFrame groundFG---
Precautions for Correct UsePrecautions for Correct Use
Connecting the Cable
• Turn OFF the PLC’s power supply before connection or disconnecting twisted-pair cable.
• Allow enough space for the bending radius of the twisted-pair cable.
3
3-1-4 Optional Serial Communications Port for N/NA-type CPU Units
CP1E CPU Unit Hardware User’s Manual(W479)
3-19
3 Part Names and Functions
3-2Expansion I/O Units
This section describes the names of the Expansion I/O Unit parts and provides the input specifications
and terminal arrangement. Refer to A-1 Dimensions for the dimensions, A-2 Wiring Diagrams for the
wiring diagrams.
3-2-1Expansion Input Unit
Part Names and Functions
8-point Input Units (CP1W-8ED)
Input terminals
Expansion I/O
connecting cable
Input indicators
Expansion connector
Input indicators
Input terminals
NumberNameFunction
Input terminalsUsed to connect input devices.
Expansion I/O connecting
cable
Input indicatorsInput status is displayed. An indicator will be ON when the input is ON.
Expansion connectorCP-series Expansion I/O Units or Expansion Units can be connected.
This is a connection cable to connect the adjacent CPU Unit, Expansion
I/O Unit, or Expansion Unit. For extended connections or vertical arrangements, use the CP1W-CN811 I/O Connecting Cable (length: 800 mm).
Refer to 5-2-4 Connecting Expansion I/O Units and Expansion Units.
Terminal Arrangements
The first word of input words allocated to the Expansion Input Unit is indicated by CIO m.
3-20
Input Terminal Arrangement
Unit Upper Terminal BlockUnit Lower Terminal Block
0103
COM
0002
CIO m
Note COM terminals are connected inside.
0406
COM 05
07
CP1E CPU Unit Hardware User’s Manual(W479)
3-2-2Expansion Output Units
Part Names and Functions
8-point Output Units
CP1W-8ER/8ET/8ET1
Output terminals
Expansion I/O
connecting cable
Output terminals
Output indicators
Expansion connector
Output indicators
Output terminals
Expansion I/O
connecting cable
Output terminals
3 Part Names and Functions
16-point Output Units
CP1W-16ER/ET/ET1
COMNCCOM COM 04 06 COM
00
01 02 03 05 07
NC
CH
OUT
CH
00 01 02 03 04 05 06
OUT
CH
00 01 02 03 04 05 06 07
CH
00 02 04 05 07 NC
NC
NC
COM 01 03 COM 06 NC
07
16ER
Output indicators
Expansion connector
Output indicators
EXP
3-2 Expansion I/O Units
3
3-2-2 Expansion Output Units
32-point Output Units
CP1W-32ER/ET/ET1
Output indicators
Output terminals
Expansion I/O
connecting cable
Expansion connector
Output terminals
NumberNameFunction
Output terminalsUsed to connect output devices.
Expansion I/O con-
necting cable
This is a connection cable to connect the adjacent CPU Unit, Expansion I/O
Unit, or Expansion Unit. For extended connections or vertical arrangements,
use the CP1W-CN811 I/O Connecting Cable (length: 800 mm).
Output indicatorsOutput status is displayed. An indicator will be ON when output is ON.
Expansion connectorCP-series Expansion I/O Units or Expansion Units can be connected.
Refer to 5-2-4 Connecting Expansion I/O Units and Expansion Units.
CP1E CPU Unit Hardware User’s Manual(W479)
3-21
3 Part Names and Functions
Terminal Arrangements
The first word of output words allocated to the Expansion Output Unit is indicated by CIO n.
8-point Output Units (CP1W-8E)
Unit Upper Terminal BlockUnit Lower Terminal Block
COM 0103
0002
16-point Output Units (CP1W-16E)
Unit Upper Terminal BlockUnit Lower Terminal Block
CIO n
0406
COM 0507
COM : Common terminal
00 to 07 : Output terminal
NCNCCOM COM COMCOM0406
0102030507
00
CIO n
COM : Common terminal
00 to 07 : Output terminal
NC : No connection
NC
NCNC
Units with 32 Output Points (CP1W-32E)
Unit Upper Terminal Block
CIO n
NC COM COM COM COM 0507 COM 02 COM 0507NC NCNC
0001020304060001030406NCNCNC
CIO n
Unit Lower Terminal Block
CIO n+2
0203060001030406 NC000104
NC COM COM COM COM 0507 COM 02 COM 0507
CIO n+1
CIO n+1
CIO n+3
0002040507
COMCOM
010306
CIO n+1
NC
3-22
CIO n+2CIO n+3
COM : Common terminal
00 to 07 : Output terminal
NC : No connection
CP1E CPU Unit Hardware User’s Manual(W479)
3-2-3Expansion I/O Units
Part Names and Functions
3 Part Names and Functions
Input terminals
Expansion I/O
connecting cable
Output terminals
NumberNameFunction
Units with 20 I/O Points
CP1W-20EDR1/EDT/EDT1
Input indicators
Output indicators
Expansion
connector
Input terminals
Expansion I/O
connecting cable
Output terminals
Units with 40 I/O Points
CP1W-40 EDR/EDT/EDT1
Input indicators
Output indicators
Expansion
connector
Input terminalsUsed to connect input devices.
Expansion I/O
connecting cable
This is a connection cable to connect the adjacent CPU Unit, Expansion I/O
Unit, or Expansion Unit. For extended connections or vertical arrangements,
use the CP1W-CN811 I/O Connecting Cable (length: 800 mm).
Output terminalsUsed to connect output devices.
Input indicatorsInput status is displayed. An indicator will be ON when the input is ON.
Expansion connectorCP-series Expansion I/O Units or Expansion Units can be connected.
Refer to 5-2-4 Connecting Expansion I/O Units and Expansion Units.
Output indicatorsOutput status is displayed. An indicator will be ON when the output is ON.
3-2 Expansion I/O Units
3
3-2-3 Expansion I/O Units
CP1E CPU Unit Hardware User’s Manual(W479)
3-23
3 Part Names and Functions
Terminal Arrangements
The first word of input words allocated to the Expansion I/O Unit is indicated by CIO m and the first word
of the output words by CIO n.
20-point I/O Units (CP1W-20ED)
• Input (Unit Upper Terminal Block)
COM 010305070911
NC000204060810
CIO m
COM : Common terminal
00 to 11 : Input terminal
NC : No connection
• Output (Unit Lower Terminal Block)
000102040507
COMCOMCOM 03 COM 06
CIO n
COM : Common terminal
00 to 07 : Output terminal
40-point I/O Units (CP1W-40ED)
• Input (Unit Upper Terminal Block)
CIO m
NCNC COM 010305070911010305070911
NCNC000204060810000204060810
CIO m
COM : Common terminal
00 to 11 : Input terminal
NC : No connection
CIO m+1
CIO m+1
3-24
• Output (Unit Lower Terminal Block)
CIO n
NC0001020405070002040507
NC COM COM COM 03 COM 06 COM0103 COM 06
CIO n
COM : Common terminal
00 to 07 : Output terminal
NC : No connection
CIO n+1
CIO n+1
CP1E CPU Unit Hardware User’s Manual(W479)
3-2-4I/O Specifications
This section describes the I/O specifications common to all Expansion I/O Units.
I/O Specifications
Input Specifications
(CP1W-8ED/20EDR1/20EDT/20EDT1/40EDR/40EDT/40EDT1)
ItemSpecification
Input voltage24 VDC, +10%, -15%
Input impedance4.7 kΩ
Input current5 mA typical
ON voltage14.4 VDC min.
OFF voltage5.0 VDC max.
ON response time1 ms max.*
OFF response time1 ms max.*
Circuit configuration
3 Part Names and Functions
3-2 Expansion I/O Units
3
3-2-4 I/O Specifications
IN
Output indicator
Internal
circuits
COM
4.7kΩ
IN
750Ω
* The response time is the delay caused by hardware. The delay set in the PLC Setup (0 to 32 ms, default: 8 ms)
must be added to this value. For the CP1W-40EDR/EDT/EDT1, a fixed value of 16 ms must be added.
Precautions for Safe Use
Do not apply voltage in excess of the rated voltage to the input terminal.
CP1E CPU Unit Hardware User’s Manual(W479)
3-25
3 Part Names and Functions
Output Specifications for Relay Outputs
(CP1W-8ER/16ER/20EDR1/32ER/40EDR)
ItemSpecification
Maximum switching capacity2 A 250 VAC (cosφ = 1), 2 A 24 VDC (4 A/common)
Minimum switching capacity10 mA 5 VDC
Service
life of
relay
ON response time15 ms max.
OFF response time15 ms max.
Circuit configuration
ElectricalResistive
load
Inductive
load
Mechanical20,000,000 operations
150,000 operations (24 VDC)
100,000 operations (240 VAC, cosφ = 0.4)
Output indicator
OUT
Internal
circuits
OUT
COM
250 VAC, 2A,
24 VDC, 2 A
max.
• Estimating the Service Life of Relays
The service life of output contacts is as shown in the following diagram.
300
200
100
50
)
4
30
20
Life (× 10
10
5
3
2
0.10.2 0.3 0.5 0.7 1 3 5
Contact current (A)
120-VAC resistive load
24 VDC, τ = 7 ms
120 VAC COSφ = 0.4
240 VAC COSφ = 0.4
24-VDC/240-VAC resistive load
Switching frequency: 1,800 operations/hour
2
• Restrictions of CP1W-16ER/32ER
Limit the output load current to satisfy the following derating curve.
CP1W-16ER/32ER
3-26
Output load current(%)
100
50
5543
Ambient temperature (˚C)
CP1E CPU Unit Hardware User’s Manual(W479)
3 Part Names and Functions
C
p
• CP1W-32ER’s maximum number of simultaneously ON output points is 24 (75%).
Relation between Number of ON Outputs and
Ambient Temperature (CP1W-32ER)
Number of inputs ON
simultaneously (%)
75
3-2 Expansion I/O Units
According to the ambient temperature, there are restrictions on power supply voltage and output load
current for the CPU Units connected with the Expansion I/O Units (CP1W-8ER/16ER/20EDR1/
32ER/40EDR). Use the PLC in the range of the power supply voltage and output load current as show
below.
• The ambient temperature is restricted for the CPU Units (CP1E-N/NAD-).
Derating curve of the output load current for Expansion I/O Units (CP1W-8ER/16ER/20EDR1/
32ER/40EDR).
Connected to
CP1E-N30DR-D
100%
Power voltage:
21.6 VDC
50%
Power voltage:
20.4 VDC
0%
Connected to
CP1E-N60DR-D
CP1E-N60DT-D
4535
Ambient temperature
55
0
Ambient temperature (˚C)
55
3
3-2-4 I/O Specifications
Connected to
CP1E-N40DR-D
100%
Powe r
voltage:
21.6 VDC
50%
Powe r
voltage:
20.4 VDC
0%
°
30
Ambient temperature
°C45
50
55
Connected to
CP1E-NA20DT-D
Connected to
CP1E-N30DT-D
100%
Power voltage:
21.6 VDC
50%
Power voltage:
20.4 VDC
0%
Ambient tem
Connected to
CP1E-NA20DR-A
55
erature
Connected to
CP1E-N40DT-D
100%
Powe r
voltage:
21.6 VDC
50%
Powe r
voltage:
20.4 VDC
°C4535
0%
Ambient temperature
55
°C4535
100%
50%
0%
Power voltage:
21.6VDC
Power voltage:
20.4VDC
Ambient temperature
40 45 55˚C
100%
50%
0%
Power voltage:
21.6VDC
Power voltage:
20.4VDC
CP1E CPU Unit Hardware User’s Manual(W479)
40 45 55˚C
Ambient temperature
100%
80%
0%
Ambient temperature
50 55˚C
3-27
3 Part Names and Functions
Output Specifications for Transistor Outputs (Sinking or Sourcing)
Item
Maximum
switching
capacity*
1
Leakage
current
Residual
voltage
ON response
time
OFF response
time
Maximum
number of
simultaneously
ON outputs
*2
Fuse
Circuit
configuration
CP1W-40EDT
4.5 to 30 VDC
0.3 A/output
0.9 A/common
3.6 A/Unit
0.1 mA max.0.1 mA max.0.1 mA max.0.1 mA max.0.1 mA max.
1.5 V max.1.5 V max.1.5 V max.1.5 V max.1.5 V max.
0.1 ms max.0.1 ms max.0.1 ms0.1 ms max.0.1 ms max.
1 ms max.
At 24 VDC +10%/
-5%, 5 to 300 mA
16 points
(100% load)
Sinking
Output indicator
Internal
circuits
CP1W-32ET
CP1W-32ET1
4.5 to 30 VDC
0.3 A/output
0.9 A/common
7.2 A/Unit
1 ms max.
At 24 VDC +10%/
-5%, 5 to 300 mA
24 points
(100% load)
OUT
L
L
OUT
24 VDC/
4.5 to 30 VDC
COM(–)
Specification
CP1W-20EDT
CP1W-20EDT1
24 VDC +10%/-5%
0.3 A/output
0.9 A/common
1.8 A/Unit
1 ms max.
At 24 VDC +10%/
-5%, 5 to 300 mA
8 points
(100% load)
1 fuse/common
Sourcing
Output indicator
Internal
circuits
CP1W-16ET
CP1W-16ET1
4.5 to 30 VDC
0.3 A/output
0.9 A/common
3.6 A/Unit
1 ms max.
At 24 VDC +10%/
-5%, 5 to 300 mA
16 points
(100% load)
COM(+)
OUT
L
L
OUT
CP1W-8ET
CP1W-8ET1
4.5 to 30 VDC
0.3 A/output
0.9 A/common
1.8 A/Unit
1 ms max.
At 24 VDC +10%/
-5%, 5 to 300 mA
8 points
(100% load)
24 VDC/
4.5 to 30 VDC
*1 If the ambient temperature is maintained below 50ºC, up to 0.9 A/common can be used.
(A)
0.9
0.8
Total current per common
0
Ambient temperature
50 55 (˚C)
*2 The fuse cannot be replaced by the user. Replace the Unit if the fuse breaks due to an short-circuit or overcur-
rent.
Precautions for Safe Use
Do not connect a load to an output terminal or apply a voltage in excess of the maximum switching capacity.
3-28
CP1E CPU Unit Hardware User’s Manual(W479)
Programming Device
This section describes the features of the CX-Programmer used for programming and
debugging PLCs, as well as how to connect the PLC with the Programming Device.
A programming device is a software application for initializing, programming, monitoring, and debugging PLCs. This section describes the programming device used by CP1E.
4-1-1Applicable Programming Devices
The programming devices in the following table are used to program and monitor the CP1E Unit.
IBM PC/AT or
equivalent
CX-Programmer
USB
CP1E CPU Unit
ProductModel
CX-Programmer
(CX-One)
Micro PLC Edition
CX-Programmer
(CX-One Lite)
CX-Programmer
for CP1E
Note 1
To use CX-Programmer version 8.2 with a CP1E CPU Unit, the CX-One version 3 auto-update must be
WS02CXPC1-V8
WS02CXPC1-V9
WS02CXPC2-V8
WS02CXPC2-V9
WS02CXPC3
Compatible CX-
Programmer
versions
Version 8.2 or
higher (See note.)
Version 9.03 or
higher
Version 8.2 or
higher
Version 9.03 or
higher
Ver sio n 1.0Versi on 1 .Supported.CXECP1E-20D-
Unit version of
CP1E CPU Unit
Ver sio n 1.Not
Ver sio n 1. Supported
Ver sio n 1.Not
Ver sio n 1.Supported
Support for
Smart Input
supported
supported
Saved pro-
gram file
extension
.CXPRefer to the
.CXPDescribed in
Reference
CX-Programmer Operation
Manual (Cat.
No. W446).
this section.
Applicable
CPU Unit
CP1E-20D-
CP1E-30D-
CP1E-40D-
All units are supported
CP1E-20D-
CP1E-30D-
CP1E-40D-
All units are supported
CP1E-30D-
CP1E-40D-
installed.
2 Use the CX-
•
The CX-Programmer for CP1E and CX-Programmer (CX-One/CX-One Lite) can be used at the same time.
Programmer version 9.12 or higher, when CP1W-CIF41 is applied.
• The CX-Programmer (CX-One/CX-One Lite) and the CX-Programmer for CP1E can be installed on
the same computer and both applications can be run at the same time.
4-2
Precautions for Correct UsePrecautions for Correct Use
• This section describes the unique applications and functions of the Micro PLC Edition CX-
Programmer version 9.03 or higher/CX-Programmer for CP1E. In the remainder of this section, “CX-Programmer” refers to the Micro PLC Edition CX-Programmer version 9.03 or
higher/CX-Programmer for CP1E.
When using the full version of CX-Programmer provided in CX-One, refer to the CX-Program-mer Operation Manual (Cat. No. W446).
• A Programming Console cannot be used for the CP1E. Use the CX-Programmer.
CP1E CPU Unit Hardware User’s Manual(W479)
4 Programming Device
Using Project Files Saved with the CX-Programmer (.CXP) on the CX-
Programmer for CP1E
The CX-Programmer for CP1E cannot open a .CXP project created on the CX-Programmer (CXOne/CX-One Lite). Use programming from a project saved in a .CXP file on the CX-Programmer for
CP1E according to the following procedure.
1
Start the CX-Programmer (CX-One/CX-One Lite) and CX-Programmer for CP1E together.
2
Copy the rungs of the program to be used from the Ladder Programming Window of the CX-Programmer (CX-One/CX-One Lite), and paste them into the CX-Programmer for CP1E.
Additional Information
Files created with the CX-Programmer for CP1E (.CXE) can be opened with CX-Programmer
version 8.2 and higher.
4-1-2CX-Programmer
CX-Programmer
The CX-Programmer is a basic software application for creating and debugging PLC programs.
4-1 Applicable Programming Devices for CP1E
4
4-1-2 CX-Programmer
CX-Programmer
ProgrammingTasksLadder diagrams
Programming functions
Monitoring
PLC Setup
Debugging and maintenance functions
CPU Unit parameters
CP1E CPU Unit Hardware User’s Manual(W479)
4-3
4 Programming Device
4-1-3Operating Environment and System Configuration
The following system is required to operate the CX-Programmer. Make sure your system provides the
following conditions and has the necessary components.
ItemDescription
Supported computerIBM PC/AT or equivalent
CD-ROM or DVD-ROM driveOne or more
Supported operating systemsWindows Vista, Windows XP, Windows 2000 (Service
Pack 2 or later)
CPU Pentium II 333 MHz or faster
RAM256 MB min., 512 MB or more recommended
Required hard disk space600 MB min.
Display800 x 600 SVGA min.
PLC and connection portUSB port
4-1-4Features of the CX-Programmer
Simple Menu Configuration
• With two menu levels, menu commands can be easily found.
• Options have been simplified.
Smart Input Mode That Automatically Displays Candidates
Automatic Instruction Candidate Function
When the first letter of the instruction mnemonic is input, possible instructions are automatically displayed.
Example:
Press the
M Key.
Instructions starting with “M”
will be displayed.
:
4-4
CP1E CPU Unit Hardware User’s Manual(W479)
4 Programming Device
Automatic Address Increment Function
The addresses are automatically incremented to the addresses input last time by 1.
The addresses of inputs and outputs are incremented by 1 respectively.
• +1 bit for a bit address
• +1 word for a word address
Example: When the previous
address was W0.01.
The address is automatically
incremented and W0.02 is displayed.
System-defined Symbol List
Condition Flags are also displayed in a list as candidates.
4-1 Applicable Programming Devices for CP1E
4
Condition flags are displayed
in a list as candidates.
Automatic Symbol Candidate Function
When inputting symbol names, symbol candidates are automatically displayed based on the first
letter.
Example: Enter “1”.
The symbols with addresses
that start with an “1” are
displayed in a list.
4-1-4 Features of the CX-Programmer
CP1E CPU Unit Hardware User’s Manual(W479)
4-5
4 Programming Device
Instructions Can Be Copied with Automatic Address Incrementing
Automatic Address Incrementing
A copied group of ladder instructions can be pasted with a specified address offset (e.g., 16 bits).
Instructions can be reused with
automatic address incrementing
Bit address + n (e.g., 16)
Word address + m (e.g., 10)
Automatic Generation of Symbol Names and I/O Comments
If there is a symbol name or I/O comment when instructions are copied, new symbols and I/O comments will also be automatically generated.
Automatic address
incrementing
Example:
Sensor 02 was automatically
generated from symbol name Sensor01.
Example:
ALARM_1 was automatically generated from
symbol name ALARM.
Example:
LAMP_Blue_1 was automatically
generated from symbol name LAMP_Blue.
4-6
CP1E CPU Unit Hardware User’s Manual(W479)
4-1-5Installing the Software
This section provides a simple description of how to install the CX-Programmer on the hard disk of a
computer.
Preparing for Installation
Check the following items before beginning with the installation.
Available Hard Disk Space
The CX-Programmer can be installed on the hard disk only. At least 600 MB of hard disk space is
required. Make sure that there is enough space available.
Windows Environment and Installation Destination
The CX-Programmer is a software application for a Windows operating environment. The software is
installed on top of Windows. Make sure that Windows Vista, XP or Windows 2000 is installed and
functioning correctly on the computer.
USB Port
4 Programming Device
4-1 Applicable Programming Devices for CP1E
4
To transfer ladder programs from the computer to the CP1E and to use the monitoring functions via
the USB port, enable the computer’s USB port. Refer to the computer’s manual for information on
enabling the USB port.
Installation Procedure
This section describes how to install the software on a computer using the following drive configuration
as an example.
C drive: Hard disk drive
D drive: CD-ROM drive
1
Start Windows and insert the CX-Programmer Master Disk in the CD-ROM drive.
The installation program will be started by the computer’s auto-run function. If the installation
program does not start, select Specify File Name and Run from the Windows Start Menu,
enter “d:\setup” and click the OK Button.
2
Complete the installation process following the instructions provided on-screen.
Precautions for Correct UsePrecautions for Correct Use
Log on as a user with Administrator privileges when uninstalling.
4-1-5 Installing the Software
Uninstalling the CX-Programmer
Uninstall the CX-Programmer when it is no longer required. Uninstall the application using Add and
Remove Applications in the control panel.
Precautions for Correct UsePrecautions for Correct Use
Log on as a user with Administrator privileges when uninstalling.
CP1E CPU Unit Hardware User’s Manual(W479)
4-7
4 Programming Device
4-2Connecting by USB
This section describes how to connect a computer running the CX-Programmer and the CP1E CPU
Unit.
4-2-1Connecting by USB
Preparations for Connection
The USB driver must be installed in the computer to connect the PLC to the computer using the USB
port. Refer to 4-2-2 Installing the USB Driver for the installation of the USB driver.
Connection Methods
Using commercially available USB cable, connect the CX-Programmer to the peripheral USB port on
the CPU Unit.
CX-Programmer
USB port
B connector
A connector
Commercially available
USB cable*
Peripheral USB port
(Conforming to USB 2.0, B connector)
* Commercially available USB cable: 5 m max., for USB 2.0.
CP1E CPU Unit
Precautions for Correct UsePrecautions for Correct Use
The CX-Programmer cannot be used by connecting to the built-in RS-232C port or a Serial
Option Board port of the CP1E CPU Unit.
Connecting Cable
Use the following cable to connect the CP1E CPU Unit to the CX-Programmer.
Port at Unit
Peripheral USB port
(Conforming to USB 2.0,
B connector)
Por t at
computer
USB portUSB 2.0 (or 1.1)Commercially available USB
Network type (com-
munications mode)
Model numbersLength
cable (A connector - B connector)
5m max.
4-8
CP1E CPU Unit Hardware User’s Manual(W479)
Restrictions on Connecting by USB
The following restrictions apply to the connection of the CP1E to a computer due to the USB specifications. Keep these restrictions in mind when using the USB port.
• Only one CP1E CPU Unit can be connected by USB to a single personal computer. It is not possible
to connect multiple CP1E CPU Units simultaneously.
• Do not remove the USB cable while connected online. The application must be offline before the
cable is removed. The CX-Programmer will not go online simply by reinserting the USB cable. Place
the CX-Programmer offline before reinserting the USB cable, then place it online again.
4-2-2Installing the USB Driver
The USB driver for CP1E must be installed on the computer running the CX-Programmer in order to
connect the CP1E to the computer via USB.
When the personal computer is connected to the CP1E by USB cable, the personal computer automatically recognizes the device and the USB driver installation is started.
4 Programming Device
4-2 Connecting by USB
4
Windows 2000 or Vista
Connect the computer’s USB port (1) and the CP1E CPU Unit’s peripheral USB port (3) with a USB
cable (2).
(1)
(3)
(2)
The USB driver will be automatically installed when the cable is connected.
Additional Information
If the software is not automatically installed, refer to Installing a Specified USB Driver later in this
section.
4-2-2 Installing the USB Driver
CP1E CPU Unit Hardware User’s Manual(W479)
4-9
4 Programming Device
Windows XP
Turn ON the power supply to the PLC
1
and connect the peripheral USB port
on the PLC to the personal computer
using a USB cable. The computer will
automatically detect the device when
the cable is connected and display
the following message.
The following dialog box will be dis-
2
played. Select one of the options and
click the Next Button.
The following dialog box will be dis-
3
played. Select the Install the software
automatically (Recommended)
Option and click the Next Button.
4-10
CP1E CPU Unit Hardware User’s Manual(W479)
4 Programming Device
Additional Information
• If the software cannot be installed automatically, refer to Installing a Specified USB Driver later
in this section.
• If the installation media is not inserted or the USB device driver is installed for another port, a
Driver List Dialog Box will be displayed. Make sure that the newest driver is selected and click
the Next Button.
4-2 Connecting by USB
Ignore the following dialog box if it is
4
displayed and click the Continue
Anyway Button.
The following dialog box will be dis-
5
played if the installation is completed
normally. Click the Finish Button.
4
4-2-2 Installing the USB Driver
CP1E CPU Unit Hardware User’s Manual(W479)
4-11
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.