Omron CP1E-E10DR-A, CP1E-E20SDR-A, CP1E-E10DT-A, CP1E-E10DT1-A, CP1E-E10DR-D User Manual

...
At the end of this document you will find links to products related to this catalog. You can go directly to our shop by
clicking HERE. HERE
Cat. No. W479-E1-06
CP1E CPU Unit Hardware
SYSMAC CP Series CP1E-E_SD_-_, CP1E-N_S_D_-_ CP1E-E_D_-_, CP1E-N_D_-_ CP1E-NA_D_-_
USER´S MANUAL
OMRON, 2009
All rights reserved. No part of this publication may be r e produced, stored in a retrieval system, or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of OMRON.
No patent liability is assumed with respect to the use of the information contained herein. Moreover , because OMRON is con- stantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication.
SYSMAC CP Series CP1E-E
@@
SD@-
@
CP1E-N
@@S@D@-@
CP1E-E
@@D@-@
CP1E-N
@@D@-@
CP1E-NA
@@D@-@
CP1E CPU Unit Hardware
User’s Manual
Revised July 2013
1
CP1E CPU Unit Hardware User’s Manual(W479)
Introduction
Thank you for purchasing a SYSMAC CP-series CP1E Programmable Controller. This manual contains informati on requ ired to use the CP1 E. Read thi s manual comp letely and be su re
you understand the contents before attempting to use the CP1E.
This manual is intended for the following personnel, who must also have knowledge of electrical sys­tems (an electrical engineer or the equivalent).
Personnel in charge of installing FA systems
Personnel in charge of designing FA systems
Personnel in charge of managing FA systems and facilities
z CP-series CP1E CPU Units
Basic Models CP 1E -E (S)D-
A basic model of CPU Unit that support basic control applications using instructions such as basic, movement, arithmetic, and comparison instructions.
Application Models CP1E-N/NA(S)D- An application mod el of CPU Un it that suppor ts connections t o Programmable Termin als, invert­ers, and servo drives.
The CP Series is cent er ed aro und t he CP 1H, CP 1L , and CP 1E CPU Unit s and is designed with the same basic architecture as the CS and CJ Series.
Always use CP-series Expansion Units and CP-series Expansion I/O Units when expanding I/O capacity. I/O words are allocated in the same way as for the CPM1A/CPM2A PLCs, i.e., using fixed areas for inputs and outputs.
Intended Audience
Applicable Products
2
CP1E CPU Unit Hardware User’s Manual(W479)
CP1E CPU Unit Manuals
Information on the CP1E CPU Units is provided in the following manuals. Refer to the appropriate manual for the information that is required.
Mounting and Setting Hardware
1
2
3
4
5
6
7
Wiring
Connecting Online to the PLC
Software Setup
Creating the Program
Checking and Debugging Operation
Maintenance and Troubleshooting
CP1E CPU Unit Hardware User’s Manual(Cat. No. W479)
CP1E CPU Unit Software User’s Manual(Cat. No. W480)
This Manual
· Wiring methods for the power supply
· Wiring methods between external I/O devices and Expansion I/O Units or Expansion Units
Connecting Cables for CX-Programmer Support Software
Error codes and remedies if a problem occurs
Procedures for connecting the CX-Programmer Support Software
Software setting methods for the CPU Units (PLC Setup)
· Checking I/O wiring, setting the Auxiliary Area settings, and performing trial operation
· Monitoring and debugging with the
CX-Programmer
· Program types and basic information
· CPU Unit operation
· Internal memory
· Built-in CPU functions
· Settings
· Names and specifications of the parts of all Units
· Basic system configuration for each CPU Unit
· Connection methods for Expansion I/O Units and Expansion Units
CP1E CPU Unit Instructions Reference Manual(Cat. No. W483)
Detailed information on
programming instructions
3
CP1E CPU Unit Hardware User’s Manual(W479)
The CP1E CPU manuals are organized in the sections listed in the following tables. Refer to the appro­priate section in the manuals as requi red.
Manual Configuration
CP1E CPU Unit Hardware User’s Manual (Cat. No. W479) (This Manual)
Section Contents
Section 1 Overview and Specifica­tions
This section giv es an overview of the CP1E, de sc ribes it s features, and provides its specifications.
Section 2 Basic System Configura­tion and Devices
This section describes the basi c sy ste m con fig uration and unit models of the CP1E.
Section 3 Part Names and Functions This section describes the part names and functions of the CPU Unit,
Expansion I/O Units, and Expansion Units in a CP1E PLC .
Section 4 Programming Device This section describes the features of the CX-Programmer used for pro-
gramming and debugging PLCs, as well as how to connect the PLC with the Programming Device by USB.
Section 5 Installation and Wiring This section describes how to install and wire CP1E Units. Section 6 Troubleshooting This section describes how to troubleshoot problems that may occur
with a CP1E PLC, including the error indications provided by the CP1E Units.
Section 7 Maintenance and Inspec­tion
This section describes periodic inspections, the service life of the Bat­tery, and how to replace the Battery.
Section 8 Using Expansion Units and Expansion I/O Units
This section describes application methods for Expansion Units.
Appendices The appendices provide information on dimensions, wiring diagrams,
and wiring serial communications for the CP1E.
CP1E CPU Unit Software User’s Manual (Cat. No. W480)
Section Contents
Section 1 Overview This section gives an overview of the CP1E, describes its application
procedures.
Section 2 CPU Unit Memory This section describes the types of internal memory in a CP1E CPU
Unit and the data that is stored.
Section 3 CPU Unit Operation This section describes the operation of a CP1E CPU Unit. Section 4 Programming Concepts This section provides basic information on designing ladder programs
for a CP1E CPU Unit.
Section 5 I/O Memory This section describes the types of I/O memory areas in a CP1E CPU
Unit and the details.
Section 6 I/O Allocation This section describes I/O allocation used to exchange data between
the CP1E CPU Unit and other units.
Section 7 PLC Setup This section describes th e PLC Setu p, which are used to perform basic
settings for a CP1E CPU Unit.
Section 8 Overview and Allocation of Built-in Functions
This section lists the built-in functions and desc ribes the o verall applica­tion flow and the allocation of the functions.
Section 9 Quick-response Inputs This section describes the quick-response inputs that can be used to
read signals that are shorter than the cycle time.
Section 10 Interrupts This sect ion describes the interrupts that ca n be used with CP1E PLCs ,
including input interrupts and scheduled interrupts.
4
CP1E CPU Unit Hardware User’s Manual(W479)
Section 11 High-speed Counters This section describes the high-speed counter inputs, high-speed
counter interrupts, and the frequency measurement function.
Section 12 Pulse Outputs This section describes positioning functions such as trapezoidal control,
jogging, and origin searches.
Section 13 PWM Outputs This section describes the variable-duty-factor pulse (PWM) outputs. Section 14 Serial Communications This section describes communications with Programmable Terminals
(PTs) without using communications progr amm in g, no-p r oto co l com m u­nications with general components, and connections with a Modbus­RTU Easy Master, Serial PLC Link, and host computer.
Section 15 Analog I/O Function This section describes the built-in analog function for NA-type CPU
Units.
Section 16 Built-in Functions This section describes PID temperature control, clock functions, DM
backup functions, security functions.
Section 17 Ethernet Option Board This section giv es an o verview of the Ethernet Option Board, describes
its setting methods, I/O memory allocations, troubleshooting, how to connect the CX-Programmer, and how to install an Ethernet network.
Section 18 Operating the Program­ming Device
This section describes basic functions of the CX-Programmer, such as using the CX-Progr amme r to w rite ladd er prog r ams to contro l the CP1E CPU Unit, to transf er the progra ms to the CP1E CPU Uni t, and to deb ug the programs.
Appendices The appendices provide lists of programming instructi ons, the Auxiliary
Area, cycle time response performance, PLC performance at power interruption.
CP1E CPU Unit Instructions Reference Manual (Cat. No. W483)
Section Contents
Section 1 Summary of Instructions This section provi des a summ ary of instruction s used with a CP1E CP U
Unit.
Section 2 Instruction This section d escribes the functi ons , ope r ands and s ampl e prog r ams of
the instructions that are supported by a CP1E CPU Unit.
Section 3 Instruction Execution Times and Number of Steps
This section prov ides the e xecution times f or all instru ctions u sed w ith a CP1E CPU Unit.
Section 4 Monitoring and Comput­ing the Cycle Time
This section describes how to monitor and calculate the cycle time of a CP1E CPU Unit that can be used in the programs.
Appendices The appendices provide a list of instructions by Mnemonic and ASCII
code table for the CP1E CPU Unit.
Section Contents
5
CP1E CPU Unit Hardware User’s Manual(W479)
Manual Structure
The following page structure and icons are used in this manual.
Special information in this manual is classified as follows:
Page Structure and Icons
Special Information
5 - 3
5 Installation and wiring
CP1E CPU Unit Hardware User’s Manual(W479)
5
5-2 Installation
5-2-1 Installation Location
DIN Track Installation
1
2
Release
DIN Track mounting pins
3
DIN Track
DIN Track mounting pins
Precautions for Correct Use
Tighten terminal block screws and cable screws to the following torques. M4: 1.2 N·m M3: 0.5 N·m
Use a screwdriver to pull down the DIN Track mounting pins from the back of the Units to release them, and mount the Units to the DIN Track.
Fit the back of the Units onto the DIN Track by catching the top of the Units on the Track and then pressing in at the bottom of the Units, as shown below.
Press in all of the DIN Track mounting pins to securely lock the Units in place.
5-2 Installation
5-2-1 Installation Location
Level 1 heading Level 2 heading Level 3 heading
Level 2 heading
Step in a procedure
Manual name
Special Information (See below.)
Level 3 heading
Page tab
Gives the current headings.
Indicates a step in a procedure.
Gives the number of the section.
This illustration is provided only as a sample and may not literally appear in this manual.
Icons are used to indicate precautions and additional information.
Precautions for Safe Use Precautions on what to do and what not to do to ensure using the product safely.
Precautions for Correct Use Precautions on what to do and what not to do to ensure proper operation and performance.
Additional Information Additional information to increase understanding or make operation easier.
6
CP1E CPU Unit Hardware User’s Manual(W479)
Terminology and Notation
Term Description
E-type CPU Unit A basic model of CPU Unit that support basic control a pplicatio ns using in struction s such
as basic, movement, arithmetic, and comparison instructions. Basic models of CPU Units are called “E(S)-type CPU Units” in this manual. The models of E(S)-type CPU Units are shown below. CP1E-ED- CP1E-ESD-
N-type CPU Unit An application model of CPU Un it that sup ports connections to Progr ammab le Terminals,
inverters, and servo drives. Application models of CPU Units are called “N(S)-type CPU Units” in this manual. The models of N(S)-type CPU Units are shown below. CP1E-ND- CP1E-NSD- CP1E-NS1D-
NA-Type CPU Unit An application model of CPU Unit that supports built-in analog and connections to Pro-
grammable Terminals, inverters, and servo drives. Application models of CPU Units with built-in analog are called “NA-type CPU Units” in
this manual.
CX-Programmer A programming device that applies for programming and debugging PLCs.
The CX-Programmer inc ludes the M icro PL C Edition CX -Prog ram mer (CX-On e Lite), the CX-Programmer (CX-One) and the CX-Programmer for CP1E.
This manual describes the unique applications and functions of the Micro PLC Edition CX-Programmer version 9.03 or higher/CX-Programmer for CP1E.
“CX-Programmer” refers to the Micro PLC Edition CX-Programmer version 9.03 or higher/CX-Programmer for CP1E in this manual .
Note E20/30/40(S) and N20/30/40(S) CPU Units are supported by CX-Programme r
version 8.2 or higher. E10/14(S), N14/60(S) and NA20 CPU Units are supported by CX-Programmer version 9.03 or higher. E60S CPU Units are supported by CX­Programmer version 9.42 or higher.
7
CP1E CPU Unit Hardware User’s Manual(W479)
Sections in this Manual
1
2
3
4
5
6
7
8
A
1
5
6
7
2
3
4
8
A
Overview and Specifications
Troubleshooting
Maintenance and Inspection
Basic System Configuration and Devices
Part Names and Functions
Programming Device
Installation and Wiring
Using Expansion Units and Expansion I/O Units
Appendices
8
CP1E CPU Unit Hardware User’s Manual(W479)
CONTENTS
Introduction ...............................................................................................................1
CP1E CPU Unit Manuals............................................. .... ..... ..... ................................2
Manual Structure.......................................................................................................5
Safety Precautions............................................ ...................................... .... ..... .......15
Precautions for Safe Use........................................................................................20
Operating Environment Precautions.....................................................................23
Regulations and Standards................................................. ..... .... ..... .....................24
Related Manuals....................................... ..... .... ..... ..................................... ..... ..... ..25
Section 1 Overview and Specifications
1-1 CP1E Overview ........................................................................................................................1-2
1-1-1 Overview of Features..................................................................................................................1-2
1-1-2 Features......................................................................................................................................1-3
1-2 Basic Operating Procedure ....................................................................................................1-8
1-3 Specifications .......................................................................................................................... 1-9
1-3-1 G ene r al Spec ifi catio ns.................................................................................. ...... ........................1-9
1-3-2 Characteristics..........................................................................................................................1-10
1-3-3 Fu nct ion al Spec if ica tio ns..........................................................................................................1-12
1-4 Difference between E/N/NA-type and E/NS(1)-type ............................................... 1-14
Section 2 Basic System Configuration and Devices
2-1 Basic System Configuration...................................................................................................2-2
2-1-1 Basic System Configuration Using an E(S)-type CPU Unit..................................................2-2
2-1-2 Basic System Configuration Using an N/NA(S)-type CPU Unit.........................................2-3
2-2 CPU Units................................................................................................................................. 2-4
2-2-1 CPU Unit Models ........................................................................................................................2-4
2-2-2 Optional Products........................................................................................................................2-9
2-2-3 Unit Versions of CPU Units.......................................................................................................2-10
2-3 Expansion I/O Unit or Expansion Unit................................................................................. 2-12
2-3-1 Expandable CPU Units.............................................................................................................2-12
2-3-2 Connection Methods.................................................................................................................2-12
2-3-3 Maximum Number of I/O Points for an Expansion I/O Unit or Expansion Unit .........................2-12
2-3-4 Expansion I/O Units and Expansion Units ................................................................................2-13
2-3-5 Restrictions on System Configuration.......................................................................................2-15
2-4 Unit Current Consumption and External Power Supply Capacity ....................................2-17
2-4-1 External Power Supply Capacity When Expansion I/O Units or Expansion Units are
Connected.................................................................................................................................2 -17
2-4-2 Current Consumption................................................................................................................2-18
9
CP1E CPU Unit Hardware User’s Manual(W479)
Section 3 Part Names and Functions
3-1 CPU Units................................................................................................................................. 3-2
3-1-1 E10/14/20(S) or N14/20 CPU Units ..........................................................................................3-2
3-1-2 E30/40/60(S), N30/40/60(S) or NA20 CPU Units.................................................................. ..3-7
3-1-3 Common I/O Specifications.......................................................................................................3-13
3-1-4 Optional Serial Communications Port for N/NA(S)-type CPU Units ................................3-19
3-2 Expansion I/O Units............. ....... ...... ....... ...... ....... ...... ...... ....... ...... ....... ...... ....... .................... 3-24
3-2-1 Expansion Input Unit.................................................................................................................3-24
3-2-2 Expansion Output Units............................................................................................................3-25
3-2-3 Expansion I/O Units..................................................................................................................3-27
3-2-4 I/O Specifications......................................................................................................................3-29
Section 4 Programming Device
4-1 Applicable Programming Devices for CP1E..........................................................................4-2
4-1-1 Applicable Programming Devices...............................................................................................4-2
4-1-2 CX-Programmer..........................................................................................................................4-3
4-1-3 Operating Environment and System Configuration.....................................................................4-4
4-1-4 Features of the CX-Programmer.................................................................................................4-4
4-1-5 In sta lli ng the Softwa re........................... ...... ...... ..... ............................................. ...... ..................4-7
4-2 Connecting by USB.................................................... ...... ....... ...... ....... ...... ....... ...... ....... ......... 4-8
4-2-1 Connecting by USB.....................................................................................................................4-8
4-2-2 Installing the USB Driver.............................................................................................................4-9
4-3 Connection Method with a Serial Port................................................................................. 4-16
Section 5 Installation and Wiring
5-1 Fail-safe Circuits......................................................................................................................5-2
5-2 Installation................................................................................................................................5-3
5-2-1 Installation Location....................................................................................................................5-3
5-2-2 Unit Arrangement........................................................................................................................5-6
5-2-3 Installation...................................................................................................................................5-7
5-2-4 Connecting Expansion I/O Units and Expansion Units.............................................................5-12
5-3 Wiring ..................................................................................................................................... 5-14
5-3-1 Wiring Procedure......................................................................................................................5-14
5-3-2 Wiring Power Supply and Ground Lines...................................................................................5-14
5-3-3 I/O Wiring..................................................................................................................................5-17
5-3-4 Wiring Safety and Noise Controls.............................................................................................5-21
5-3-5 Relay Output Noise Reduction Methods...................................................................................5-22
Section 6 Troubleshooting
6-1 Troubleshooting CPU Unit Errors ..........................................................................................6-2
6-1-1 Errors and Remedies..................................................................................................................6-2
6-1-2 Checking Errors ..........................................................................................................................6-2
6-1-3 Checking Detailed Status............................................................................................................6-3
6-1-4 Reading Error Log Information....................................................................................................6-3
6-1-5 Types of Errors............................................................................................................................6-5
6-1-6 Error Processing Flowchart.........................................................................................................6-6
6-1-7 No Operation When Power Is Supplied.......................................................................................6-7
6-1-8 Fatal Errors .................................................................................................................................6-7
6-1-9 CPU Errors................................................................................................................................6-11
6-1-10 Non-fatal Errors..................................... ...... ...... ..... ...... ............................................. ................6-12
6-1-11 Other Errors ..............................................................................................................................6-14
10
CP1E CPU Unit Hardware User’s Manual(W479)
6-2 Troubleshooting Unit Errors.................................................................................................6-15
6-2-1 Inputs ........................................................................................................................................6-15
6-2-2 Outputs......................................................................................................................................6-16
6-2-3 Built-in Analog...........................................................................................................................6-17
6-2-4 CX-Programmer Connection..................................................................................... ..... ...........6-18
Section 7 Maintenance and Inspection
7-1 Periodic Maintenance and Inspection ... ...... ....... ...... ...... ....... ...... ....... ...... ....... ...................... 7-2
7-1-1 Tools Required for Inspections....................................................................................................7-2
7-1-2 Periodic Inspection......................................................................................................................7-2
7-1-3 Inspection and Maintenance.......................................................................................................7-3
7-1-4 Unit Replacement Precautions....................................................................................................7-4
7-2 Replacing the Battery in N/NA(S)-type CPU Units...................................................... 7-5
Section 8 Using Expansion Units and Expansion I/O Units
8-1 Analog Input Units................................................................................................................... 8-2
8-1-1 Overview.....................................................................................................................................8-2
8-1-2 Part Names and Functions..........................................................................................................8-2
8-1-3 Specifications..............................................................................................................................8-3
8-1-4 Flow of Operation........................................................................................................................8-6
8-2 Analog Output Units.............................................................................................................. 8-12
8-2-1 Overview...................................................................................................................................8-12
8-2-2 Part Names and Functions........................................................................................................8-12
8-2-3 Specifications............................................................................................................................8-13
8-2-4 Flow of Operation......................................................................................................................8-16
8-3 Analog I/O Units..................................................................................................................... 8-22
8-3-1 Overview...................................................................................................................................8-22
8-3-2 Part Names and Functions........................................................................................................8-22
8-3-3 Specifications............................................................................................................................8-23
8-3-4 Flow of Operation......................................................................................................................8-29
8-4 Temperature Sensor Units.................................................................................................... 8-36
8-4-1 Overview...................................................................................................................................8-36
8-4-2 Part Names and Functions........................................................................................................8-36
8-4-3 Specifications............................................................................................................................8-37
8-4-4 Flow of Operation......................................................................................................................8-37
8-4-5 Function Descriptions ...............................................................................................................8-46
8-5 CompoBus/S I/O Link Units ................................................................................................. 8-52
8-5-1 Overview...................................................................................................................................8-52
8-5-2 Part Names and Functions........................................................................................................8-52
8-5-3 Specifications............................................................................................................................8-54
8-5-4 Flow of Operation......................................................................................................................8-54
Section A Appendices
A-1 Dimensions .............................................................................................................................A-2
A-1-1 CPU Units...................................................................................................................................A-2
A-1-2 Option Boards.............................................................. ..... ..........................................................A-5
A-1-3 Expansion I/O Units....................................................................................................................A-7
A-1-4 Expansion Units..........................................................................................................................A-9
A-2 Wiring Diagrams............................... ....... ...... ....... ...... ...... ....... ...... ........................................A-11
A-2-1 CPU Units.................................................................................................................................A-11
A-2-2 Expansion I/O Units..................................................................................................................A-20
A-2-3 Expansion Units........................................................................................................................A-27
A-2-4 Serial Communications.......................................... ............................................. ...... ................A-33
11
CP1E CPU Unit Hardware User’s Manual(W479)
A-3 Wiring for Serial Communications.......................................................................................A-39
A-3-1 Recommended RS-232C Wiring..............................................................................................A-39
A-3-2 Recommended RS-422A/485 Wiring .......................................................................................A-42
A-3-3 Converting the Built-in RS-232C Port to RS-422A/485 ......................................................... ...A-45
A-3-4 Reducing Electrical Noise for External Wiring..........................................................................A-48
Index ..................................................................................................................................Index-1
Revision History.................................................................................. Revhist-1
12
CP1E CPU Unit Hardware User’s Manual(W479)
Read and Understand this Manual
Please read and understand this manual before using the product. Please consult your OMRON representative if you have any questions or comments.
Warranty and Limitations of Lia bi lity
WARRANTY
OMRON’s exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON­INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGE S, LOSS OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON’S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
13
CP1E CPU Unit Hardware User’s Manual(W479)
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer’s application or use of the products.
At the customer’s request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product, machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
• Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this manual.
• Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles, safety equipment, and installations subject to separate industry or government regulations.
• Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products. NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR
PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user’s programming of a programmable product, or any consequence thereof.
14
CP1E CPU Unit Hardware User’s Manual(W479)
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this manual is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability.
ERRORS AND OMISSIONS
The information in this manual has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical, or proofreading errors, or omissions.
15
CP1E CPU Unit Hardware User’s Manual(W479)
Safety Precautions
The following notation is use d i n t his m anu al to pr ovide prec aut ion s re qui red t o e nsu r e safe usage of a CP-series PLC. The safety precautions that are provided are extremely important to safety . Alwa ys read and heed the information provided in all safety precautions.
Definition of Precautionary Information
Symbols
The triangle symbol indicates precautions (including warnings). Th e s pe ci fic operation is shown in the triangle and explained in text. This example indicates a precau­tion for electric shock.
The circle and slash symbol indicates operations that you must not do. The specific operation is sh own in the c ircle and explained in text.
The filled circle symbol indicates operations that you must do. The specific operation is shown in the circle and explained in text. This example shows a general prec au­tion for something that you must do.
The triangle symbol indicates precautions (including warnings). Th e s pe ci fic operation is shown in the triangle and explained in text. This example in dicates a general precaution.
The triangle symbol indicates precautions (including warnings). Th e s pe ci fic operation is shown in the triangle and explained in text. This example indicates a precau­tion for hot surfaces.
WARNING
Caution
Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. Additionally, there may be severe property damage.
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury, or property damage.
Precautions for Safe Use Indicates precautions on what to do and what not to do to ensure using the product safely.
Precautions for Correct Use Indicates precautions on what to do and what not to do to ensure proper operation and performance.
16
CP1E CPU Unit Hardware User’s Manual(W479)
Do not attempt to take any Unit apart while the power is being supplied.
Doing so may result in electric shock.
Do not touch any of the terminals or terminal bl ocks while the power is being supplied.
Doing so may result in electric shock.
Provide safety measures in external circuits (i.e., not in the Programmable Con­troller), including the following items, to ensure safety in the system if an abnormality occurs due to malfunction of the PLC or another external factor affecting the PLC operation.
Not doing so may result in serious accidents.
Emergency stop circuits, interlock circuits, limit circuits, and similar safety mea­sures must be provided in external control circuits.
The PLC will turn OFF all outputs when its self-diagnosis function detects any error or when a severe failure alarm (FALS) instruction is executed. Unexpected opera­tion, however, may still occur for errors in the I/O control section, errors in I/O mem­ory, and errors that cannot be detected by the self-diagnosis function. As a countermeasure for all these errors, external safety measures must be provided to ensure safety in the system.
The PLC outputs may remain ON or OFF due to deposition or burning of the output relays or destruction of the output transistors. As a countermeasure for such prob­lems, external safety measures must be provided to ensure safety in the system.
When the 24-VDC output (service power supply to the PLC) is overloaded or short­circuited, the voltage may drop and result in the outputs being turned OFF. As a countermeasure for such problems, external safety measures must be provided to ensure safety in the system.
Fail-safe measures must be taken by the customer to ensure safety in the event of incorrect, missing, or abnormal signals caused by broken signal lines, momentary power interruptions, or other causes.
Serious accidents may result from abnormal operation if proper measures are not provided.
Do not apply the voltage/current outside the specified range to this unit. It may cause a malfunction or fire.
WARNING
17
CP1E CPU Unit Hardware User’s Manual(W479)
Be sure to sufficiently confirm the safety at the destination when you transfer the program or I/O memory or perform procedures to change the I/O memory.
Devices connected to PLC outputs may incorrectly operate regardless of the operat­ing mode of the CPU Unit.
With an E(S)-type CPU Unit or with an N/NA(S)-type CPU Unit without a Bat­tery, the contents of the DM Area (D) * , Holding Area (H), the Counter Present Val­ues (C), the status of Counter Completion Flags (C), and the status of bits in the Auxiliary Area (A) related to clock functions may be unstable when the power supply is turned ON.
*This does not apply to areas backed up to EEPROM using the DM backup function. If the DM backup function is being used, be sure to use one of the following methods
for initialization.
1. Clearing All Areas to All Zeros
Select the Clear Held Memory (HR/DM/CNT) to Zero Check Box in the Startup Data Read Area in the PLC Setup.
2. Clearing Specific Areas to All Zeros or Initializing to Specific Values
Make the settings from a ladder program.
If the data is not initialized, the unit or device may operate unexpectedly because of unstable data.
Execute online edit only after confirming that no adverse effects will be caused by extending the cycle time.
Otherwise, the input signals may not be readable.
Tighten the screws on the terminal block of the AC power supply section to the torque specified in the user’s manual.
The loose screws may result in burning or malfunction.
Do not touch the power supply section when po wer is being supplied or imme­diately after the power supply is turned OFF.
The power supply section and I/O terminal blocks will be hot and you may be burned.
CautionCaution
18
CP1E CPU Unit Hardware User’s Manual(W479)
Pay careful attention to the polarities (+/-) when wiring the DC power supply.
A wrong connection may cause malfunction of the system.
When connecting the PLC to a computer or other peripheral device, either ground the 0-V side of the external power supply or do not ground the external power supply at all.
Otherwise the external power supply may be shorted depending on the connection methods of the peripheral device. DO NOT ground the 24 V-side of the external power supply, as shown in the following diagram.
The DM Area (D), Holding Area (H), Counter Completion Flags (C), and Counter Present Values (C) will be held by the Battery if a Battery is mounted in a CP1E­N/NA (S)D- CPU Unit. When the battery voltage is low, however, I/O mem­ory areas that are held (including the DM, Holding, and Counter Areas) will be unsta­ble. The unit or device may operate unexpectedly because of unstable data.
Use the Battery Error Flag or other measures to stop outputs if external out­puts are performed from a ladder program based on the contents of the DM Area or other I/O memory areas.
Sufficiently check safety if I/O bit status or present values are monitored in the Ladder Section Pane or present values are monitored in the Watch Pane.
If bits are set, reset, force-set, or force-reset by inadvertently pressing a shortcut key, devices connected to PLC outputs may operate incorrectly regardless of the operat­ing mode.
Program so that the memory area of the start address is not exceeded when using a word address or symbol for the offset.
For example, write the program so that processing is executed only when the indirect specification does not cause the final address to exceed the memory area by using an input comparison instruction or other instruction. If an indirect specification causes the address to exceed the area of the start address, the system will access data in other area, and unexpected operation may occur.
Caution
24V
0V
0V
0V
FG
FG
FG
FG
Non-insulated DC power supply
CPU Unit
USB cable or other communications cable
Peripheral device
(e.g., personal computer)
19
CP1E CPU Unit Hardware User’s Manual(W479)
Set the temperature range according to the type of temperature sensor con­nected to the Unit.
Temperature data will not be converted correctly if the temperature range does not match the sensor.
Do not set the temperature range to any values other than those for which tem­perature ranges are given in the following table.
An incorrect setting may cause operating errors.
Caution
20
CP1E CPU Unit Hardware User’s Manual(W479)
Precautions for Safe Use
Observe the following precautions when using a CP-series PLC.
z Po wer Suppl y
Always use the power supply voltages specifi ed in the user’s manuals. An incorrect voltage may
result in malfunction or burn in g.
Take appropriate measures to ensure that the specified power with the rated voltage and fre­quency is supplied. Be particularly careful in places where the power supply is unstable. An incor­rect power supply may result in malfunction.
Double-check all wiring and switch setti ngs before turning ON the power supply. Incorrect wiring may result in burning.
Always turn OFF the power supply to the PLC before attempting any of the following. Not turn ing OFF the power supply may result in malfunction or electric shock.
Mounting or dismounting Expansion Units or Expansion I/O Units
Mounting or dismounting Option Boards
Setting rotary switches
Connecting cables or wiring the system
Connecting or disconnecting the connectors
z Installation
Before touching a Unit , b e s ur e to firs t touch a grounded metallic ob je ct in o rd er to di s ch arge any
static build-up. Not doing so may result in malfunction or damage.
Be sure that the terminal blocks, connectors, Option Boards, and other ite ms with locking devices are properly locked into place. Improper locking may result in malfunction.
z Wiring
Wire correctly according to specified procedures in this manual.
Always use the following size wire when connecting I/O terminal s: AWG22 to AWG18 (0.32 to
0.82 mm
2
).
Install external breakers and take other safety measures against short-circuiting in external wiring. Insufficient safety measures against short-circuiting may result in burning.
Always connect to a ground of 100 Ω or less when installing the Units. Not connecting to a ground of 100 or less may result in electric shock.
Leave the label attached to the top of the Unit w hen wiri ng to prevent the entr y of foreign matter. Removing the label may result in malfunction if foreign matter enters the Unit.
Keep foreign substances, such as wiring chip s, from entering into the Units. It may cause a fire, failure or malfunction. Take protective measures especially at the time of construction.
Remove the label after the completion of wir ing to ensure proper heat dissipation. Leaving the label attached may result in malfunction.
Use crimp terminals for wiring . Do no t c onn ec t b are s tran ded wire s di rectl y to terminals. Connec­tion of bare stranded wires may result in burning.
Do not apply voltages to the inp ut ter m inals in excess of the rated input voltage. Excess voltages may result in burning.
Do not apply voltages or connect loads to the output ter mi nals in excess of the maximum switch­ing capacity. Excess voltage or loads may result in burning.
Disconnect the functional ground t erminal when performing withst and voltage tests. Not dis con­necting the functional ground terminal may result in burning.
21
CP1E CPU Unit Hardware User’s Manual(W479)
Be sure that all the PLC t er minal scr ews and cable connector scr ews are tightened to the torque
specified in the relevant manuals. The tightening torque for the terminals on the CP1W­CIF11/CIF12 terminal block is 0.28 N·m Incorrect tightening torque may result in malfunction.
The following devices can be conn ected to pin 6 (+5V) on th e built-in RS-232C p or t on the CPU Unit or the RS-232C Option Board (CP1W-CIF01) mounted to the CPU Unit. Do not connect pin 6 to any other device.
RS-422A CJ1W-CIF11 Conversion Adapter
RS-232C / RS-422A NT-AL001 Conversion Adapter
NV3W-M20L Programmable Terminal
Use the cables that are specified in the manual for each device. External devices or the CPU Unit
may be damaged if a commercially available RS-232C computer cable is used.
Do not pull on the cables or bend t he cables beyond their natural lim it. Doing e ither of the se may break the cables.
Do not place objects on top of the cables or other wiring lines. Doing so may break the cables.
z Handling
To initialize the DM Area, back up the init ial contents for the DM Area to backup memo ry using
one of the following methods.
Set the number of words of the DM Area to be backed up starting with D0 in the Number of CH of DM for backup Box in the Startup Data Read Area.
Include programming to back up specified words in the DM Area to built-in EEPROM by turning ON A751.15 (DM Backup Save Start Bit).
Check the ladder program for proper execution before actually running it on the Unit. Not checking the program may result in an unexpected operation.
The ladder program and parameter area data in the CP1E CPU Units are backed up in the built-in EEPROM backup memory. The BKUP indicator will light o n the front of the CPU Unit when the backup operation is in progress. Do not turn OFF the power supply to the CPU Unit when the BKUP indicator is lit. The data will not be backed up if power is tur ned OFF and a mem ory er ror will occur the next time the power supply is turned ON.
With a CP1E CPU Unit, data memo ry can be backed up to the built-in EEPROM backup memory. The BKUP indicator will light on the front of the CPU Unit when backup is in progress. Do not turn OFF the power supply to the CPU Unit when the BKUP ind icato r is lit. If the power is tur ned O FF during a backup, the data will not be backed up and will not be transferred to the DM Area in RAM the next time the power supply is turned ON.
Before replacing the battery, supply power to the CPU U nit for at leas t 30 minute s and t hen com ­plete battery replacement within 5 minutes. Memory data may be c orrupted if this pre caution is not observed.
The equipment may operate unexpectedly if inapprop riate param eters are set. Even if the appro­priate parameters are s et, confirm th at equipment will no t be adversely affected before transfer­ring the parameters to the CPU Unit.
After replacing the CPU Unit, make sure that the required data for the DM Area, Holding Area, and other memory areas has been transferred to the new CPU Unit before restarting operation.
Do not attempt to disassemble, repair, or modify any Units. Any attempt to do so may result in mal­function, fire, or electric shock.
Do not drop the Unit or subject the Unit to unusual vibration and shock. Do so may result in failure or fire.
Confirm that no a dverse effect will occur in the system before attempting any of the following. Not doing so may result in an unexpected operation.
Changing the operating mode of the PLC (including the setting of the startup operating mode).
Force-setting/force-resetting any bit in memory.
Changing the present value of any word or any set value in memory.
22
CP1E CPU Unit Hardware User’s Manual(W479)
When replacing parts, be sure to confirm that the rating of a new part is correct. Not doing so may
result in malfunction or burn in g.
Do not touch the Ex pa nsi on I/O Un it Conn ecting Cable while the power is being su ppl ie d i n o rder to prevent malfunction due to static electricity.
Do not turn OFF the power supply to the Unit while data is being transferred.
When transpor ting or stor ing Units or Board, st atic electric ity can destroy LSIs or ICs. Cover the
PCBs with a conductive material and maintain the specified storage temperature.
Do not touch circuit boards or the compon ents mo unted to the m with your bare hand s. There are sharp leads and other parts on the boards that may cause injury if handled improperly.
Double-check the pin numbers when assembling and wiring the connectors.
Never short-circuit the positi ve and negative terminals o f a batter y or charge, disassemble, heat ,
or incinerate the batter y. Do not subject the battery to stron g shocks or deform the battery by applying pressure. Doin g any of these may result in leakage, rupture, heat gen eration, or ignit ion of the battery. Dispose of any battery that has been dropped on the floor or otherwise subjected to excessive shock. Batteries that have been subjected to shock may leak if they are used.
Dispose of the product and batteries according to local ordinances as they apply.
UL standards require that o nly an experienced enginee r can replace the batt ery. Make sure that
an experienced engineer i s in charge of battery replacemen t. Follow the procedure for batter y replacement given in this manual.
The following precaution must be di splayed on all products tha t contain a li thium pr imary batter y (containing at least 6 ppb of perchlorate) a nd that will be expor ted to or trans ported th rough the State of California in the USA. Perchlorate Material - special handling may apply . See http://www.dtsc.ca.gov/hazardouswaste/perchlorate A CP1W-BAT01 or CJ1W-BAT 01 lit hiu m primary batt ery (containing a t l east 6 ppb of p er ch lorate) can be mounted in a CP1E-N/NAD- CPU Unit. Display the precaution given above on your product’s packaging box or shipping box if the product contains a CP1W-BAT01 or CJ1W-BAT01 Battery and is exported to or through the State of California in the USA.
This product is EMC complia nt when assembled in a com plete PL C system. Refer to the applica­ble manual for grounding, cable selection, and any other conditions for EMC compliance.
This is a Class A pr oduct for use in industrial e nvironments. In residential environments it may cause radio interference, in which ca se the user may be req uired to take adequate measures to reduce interference.
z External Circuit s
Always configure the external circuits to turn ON power to the PLC before turning ON power to the
control system. If th e PLC power supply is tur ned ON after the control power supply, temporary errors may result in control syste m sign als beca use the output ter mi nals on DC Output Units and other Units will momentarily turn ON when power is turned ON to the PLC.
Fail-safe measures must be taken by the customer to ensure safety in the event that outputs from output terminals remain ON as a result of intern al circuit failures, which c an occur in rel ays, tran­sistors, and other elements.
If the I/O Hold Bit is turned ON, the outputs from the PLC will not be turned OFF and will maintain their previous status when the PLC is switched from RUN or MONITOR mode to PROGRAM mode. Make sure that the external loads will not produce dangerou s condit ions when this occurs. (When operation stops for a fatal error, including those produced with the FALS instruction, all out­puts from PLC will be turned OFF and only the internal output status in the CPU Unit will be main­tained.)
23
CP1E CPU Unit Hardware User’s Manual(W479)
Operating Environment Precautions
z Perform installation following the instructions in this manual
Follow the instructions in this manual to correctly perform installation.
z Do not operate the control system in the following locations
Locations subject to direct sunlight
Locations subject to temperatures or humidity outside the range specified in the specifications
Locations subject to condensation as the result of severe changes in temperature
Locations subject to corrosive or flammable gases
Locations subject to dust (especially iron dust) or salts
Locations subject to exposure to water, oil, or chemicals
Locations subject to shock or vibration
z Take countermeasures in the following locations
Locations subject to static electricity or other forms of noise
Locations subject to strong electromagnetic fields
Locations subject to possible exposure to radioactivity
Locations close to power supplies
24
CP1E CPU Unit Hardware User’s Manual(W479)
Regulations and Standards
EMC Directives
Low Voltage Directive
z EMC Directives
OMRON devices are electrical compon ents t hat ar e desi gned to be built in to equipme nt and manu­facturing systems. OMRON devices that comply with EMC Directives also conform to the related EMC standards*, so that they can be mor e easily built into other devices or the overall machine. Whether the products c onform to the standards in the sys tem u sed by the cu st ome r, however, must be checked by the customer.
EMC-related performance of the OMRON devices that comply with EC Directives will vary depend­ing on the configuration, wirin g, and other conditi ons of the equi pm ent or cont ro l pane l on which the OMRON devices are installed. The customer must, therefore, perform the final check to confirm that devices and the overall machine conform to EMC standards.
* The applicable EMC (Electromagnetic Compatibility) standard is EN61131-2.
z Low Voltage Directive
Always ensure that devices operating at voltages of 50 to 1,000 VAC and 75 to 1,500 VDC meet the required safety standards for the PLC (EN 61131-2).
z Conformance to EC Directives
The CP1E PLCs com ply with EC Directives. To ensure that the machine o r device in which the CP1E PLC is used complies with EC Directives, the PLC must be installed as follows:
The CP-series PLC must be installed within a control panel.
CP-series PLCs complying with EC Directives also conform to EN61131-2. Radiated emission
characteristics (10 -m regulations) may vary d epending on the c onfiguration of the con trol panel used, other devices connected to the control panel, wirin g, and other condi tions. You must there­fore confirm that the overall machine or equipment complies with EC Directives.
A SYSMAC CP-series PLC is a class A product (for an industrial environment). In residential areas it may cause radio inte rference, in which case the user may be required to take adequate measures to reduce interference.
SYSMAC is a registered trademark for Programmable Controllers made by OMRON Corporation. CX-One is a registered trademark for Programming Software made by OMRON Corporation. Windows is a registered trademark of Microsoft Corporation. Other system names and product names in this document are the trademarks or registered trademarks
of their respective companies.
Conformance to EC Directives
Applicable Directives
Concepts
Trademarks
25
CP1E CPU Unit Hardware User’s Manual(W479)
Related Manuals
The following manuals are related to the CP1E. Use them together with this manual.
Manual name Cat. No. Model numbers Application Contents
SYSMAC CP Series CP1E CPU Unit Hard­ware User’s Manual (this manual)
W479 CP1E-ESD-
CP1E-NSD- CP1E-ED- CP1E-ND- CP1E-NAD-
To learn the hard­ware specifications of the CP1E PLCs
Describes the following information for CP1E PLCs.
Overview and features
Basic system configuration
Part names and functions
Installation and settings
Troubleshooting
Use this manual together with the CP1E CPU Unit Software User’s Manual (Cat. No. W480) and Instructions Reference Manual (Cat. No. W483).
SYSMAC CP Series CP1E CPU Unit Soft­ware User’s Manual
W480 CP1E-ESD-
CP1E-NSD- CP1E-ED- CP1E-ND- CP1E-NAD-
T o learn the software specifications of the CP1E PLCs
Describes the following information for CP1E PLCs.
CPU Unit operation
Internal memory
Programming
Settings
CPU Unit built-in functions
Interrupts
High-speed counter inputs
Pulse outputs
Serial communications
Analog I/O function
Other functions
Use this manual together with the CP1E CPU Unit Hardware User’s Manual (Cat. No. W479) and Instructions Reference Manual (Cat. No. W483).
SYSMAC CP Series CP1E CPU Unit Instruc­tions Reference Manual
W483 CP1E-ESD-
CP1E-NSD- CP1E-ED- CP1E-ND- CP1E-NAD-
To learn program­ming instructions in detail
Describes each programming instruction in detail.
When programming, use this manual together with the CP1E CPU Unit Software User’s Man­ual (Cat. No. W480).
CS/CJ/CP/NSJ Series Communications Com­mands Reference Man­ual
W342 CS1G/H-CPUH
CS1G/H-CPU-V1 CS1D-CPUH CS1D-CPUS CS1W-SCU-V1 CS1W-SCB-V1 CJ1G/H-CPUH CJ1G-CPUP CJ1M-CPU CJ1G-CPU CJ1W-SCU-V1
To learn communica­tions commands for CS/CJ/CP/NSJ­series Controllers in detail
Describes
1) C-mode commands and
2) FINS commands in detail. Read this manual for details on C-mode and
FINS commands addressed to CPU Units.
Note This manual describes comma nds addressed to CPU Units. It
does not cover commands addressed to other Units or ports (e.g., serial communications ports on CPU Units, communications ports on Serial Commun ications Units/Bo ards, and other Co mmunica­tions Units).
SYSMAC CP Series CP1L/CP1E CPU Unit Introduction Manual
W461 CP1L-L10D-
CP1L-L14D- CP1L-L20D- CP1L-M30D- CP1L-M40D- CP1L-M60D- CP1E-ED- CP1E-ND- CP1E-NAD-
To learn the basic setup methods of the CP1L/CP1E PLCs
Describes the following information for CP1L/CP1E PLCs.
Basic configuration and component names
Mounting and wiring
Programming, data transfer, and debugging
using the CX-Programmer
Application program examples
CX-Simulator Operation Manual
W366
CXONE-ALC-V4/ ALD-V4
Operating procedures for CX-Simulator Simulation Support Software for Windows computersUsing simulation in the CX-Programm e r w ith CX-Programmer
Describes the operating procedures for the CX-Simulator.