SYSMAC CJ Series
CJ2H-CPU6_-EIP
CJ2H-CPU6_
CJ2M-CPU_
CJ2 CPU Unit Software
USER’S MANUAL
OMRON, 2008
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or
by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of
OMRON.
No patent liability is assumed wi th respe ct to the use o f the information contained herein. Moreover , because OMRON is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without
notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no responsibility
for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in
this publication.
SYSMAC CJ Series
CJ2H-CPU6@-EIP
CJ2H-CPU6@
CJ2M-CPU@@
CJ2 CPU Unit Software
User’s Manual
Revised February 2010
Introduction
Thank you for purcha sing a CJ- series CJ2H-CPU6@(-EIP) or CJ2M-CPU@@ Programmab le Controller.
This manual contains information required to use the CJ2H-CPU6@(-EIP) or CJ2M-CPU@@. Please
thoroughly read and understand this manual bef ore y ou use the CJ2H-CPU6@(-EIP) or CJ2M-CPU@@.
Intended Audience
This manual is intended for the following personnel, who must also have knowledge of electrical systems (an electrical engineer or the equivalent).
• Personnel in charge of installing FA systems
• Personn el in charge of designing FA systems.
• Personnel in charge of managing FA systems and facilities.
Applicable Products
CJ-series CJ2 CPU Units
• CJ2H-CPU6@-EIP
• CJ2H-CPU6@
•CJ2M-CPU3@
•CJ2M-CPU1@
In this manual, the following notation is used to indicate the CPU Units.
• CJ2H-CPU6@(-EIP): Indicates the CJ2H-CPU6@-EIP and CJ2H-CPU6@ CPU Units.
• CJ2M-CPU@@: Indicates the CJ2M-CPU3@ and CJ2M-CPU1@ CPU Units.
Information on the CJ2 CPU Units is provided in the f o llo wing man uals . Refer to the appropriate manual
for the information that is required.
This Manual
Mounting
and Setting
1
Hardware
2
Wiring
CJ-series CJ2 CPU Unit
Hardware User’s Manual
(Cat. No. W472)
• Unit part names and
specifications
• Basic system
configuration
• Unit mounting
procedure
• Setting procedure for
DIP switch and rotary
switches on the front of
the CPU Unit
For details on built-in
EtherNet/IP port, refer to
the EtherNet/IP Unit Operation Manual (W465)
CJ-series CJ2 CPU Unit
Software User’s Manual
(Cat. No. W473)
CS/CJ/NSJ Series
Instructions Reference
Manual (Cat. No. W474)
Connecting
Online to
3
the PLC
Software
4
Setup
Creating the
5
Program
Checking
and
Debugging
6
Operation
• Wiring the Power
Supply Unit
• Wring Basic I/O Units
and external I/O
devices
CX-Programmer Support
Software Connecting
Cables
Procedures for connecting
the CX-Programmer
Support Software
Software setting methods for the
CPU Unit (including I/O memory
allocation, PLC Setup settings,
Special I/O Unit parameters,
CPU Bus Unit parameters, and
routing tables.)
For details on built-in EtherNet/IP
port, refer to the EtherNet/IP Unit Operation Manual (W465).
• Program types and basic
information
• CPU Unit operation
• Internal memory
• Data management using
file memory in the CPU
Unit
• Built-in CPU functions
• Settings
Detailed information
on programming
instructions
Maintenance
and
7
Troubleshooting
2
• Checking I/O wiring, setting the
Auxiliary Area settings, and
performing trial operation
• Monitoring and debugging with
the CX-Programmer
Error codes and
remedies if a problem
occurs
CJ2 CPU Unit Software User’s Manual
Manual Configuration
The CJ2 CPU manuals are organized in the sections listed in the following tables. Ref e r to the appropriate section in the manuals as required.
Hardware User’s Manual (Cat. No. W472)
SectionContent
Section 1 Overview
Section 2 Basic System Configu-
ration and Devices
Section 3 Nomenclature and
Functions
Section 4 Support Software
Section 5 Installation
Section 6 Troubleshooting
Section 7 Inspection and Mainte-
nance
Section 8 Backup OperationsThis section describes the procedure to back up PLC data.
Appendices
This section gives an overview of the CJ2 CPU Units and describes the features and
specifications.
This section describes the system configuration for the CJ2 CPU Unit.
This section describes the part names and functions of the CPU Unit and Configuration
Units.
This section describes the types of Support Software to use to perform programming and
debugging and how to connect the PLC to the Support Software.
This section describes the installation locations and how to wire CPU Units and Configuration Units.
This section describes how to check the status for errors that occur during system operation and the remedies for those errors.
This section describes periodic inspection, the service life of the Battery and Power Supply Unit, and how to replace the Battery.
The appendices provide Unit dimensions, details on fatal and non-fatal errors, information on connecting to serial ports on the CPU Unit, the procedure for installing the USB
driver on a computer, and information on load short-circuit protection and line disconnection detection.
SectionContent
Section 1 Overview
Section 2 Internal Memory in the
CPU Unit
Section 3 CPU Unit OperationThis section describes the internal operation of the CPU Unit.
Section 4 CPU Unit InitializationThis section describes the initial setup of the CPU Unit.
Section 5 Understanding Pro-
gramming
Section 6 I/O Memory AreasThis section describes the I/O memory areas in the CPU Unit.
Section 7 File Operations
Section 8 I/O Allocations and
Unit Settings
Section 9 PLC Setup
Section 10 CPU Unit FunctionsThis section describes functions that are built into the CPU Unit.
Section 11 Programming Devices
and Communications
Section 12 CPU Unit Cycle TimeThis section describes how to monitor and calculate the cycle time.
Appendices
This section gives an overview of the CJ2 CPU Units and describes the features and
specifications.
This section describes the types of memory in the CPU Unit and the data that is stored.
This section describes program types and programming details, such as symbols and
programming instructions.
This section describes the files that can be stored in the CPU Unit, the storage destination for those files, and file operations.
This section describes the I/O allocations used to exchange data between the CPU Unit
and other Units.
This section describes details on the PLC Setup settings, which are used to perform
basic settings for the CPU Unit.
This section describes the procedure for connecting the CJ2 CPU Unit to the CX-Programmer or other Support Software and to other devices.
The appendices provide information on programming instructions, execution times, number of steps, Auxiliary Area words and bits, a memory map of the continuous PLC memory addresses, I/O memory operation when power is interrupted, and a comparison of
CJ-series and CS-series PLCs.
This section provides basic information on designing ladder programs for a CS/CJ/NSJseries CPU Unit.
This section provides a summary of instructions used with a CS/CJ/NSJ-series CPU
Unit.
This section describes the functions, operands and sample programs of the instructions
that are supported by a CS/CJ/NSJ-series CPU Unit.
This section provides the instruction execution times for each CS/CJ/NSJ-series CPU
Unit instruction.
The appendices provide a list of instructions by function code and by mnemonic and an
ASCII table for the CS/CJ/NSJ-series CPU Units.
4
CJ2 CPU Unit Software User’s Manual
Manual Structure
Page Structure
The following page structure is used in this manual.
Level 2 heading
Level 3 heading
A step
in a procedure
Special Information
(See below.)
5-2Installation
5-2-1 Connecting PLC Components
The Units that make up a CJ-series PLC can be connected simply by pressing the Units together and
locking the sliders by moving them toward the back of the Units. The End Cover is connected in the
same way to the Unit on the far right side of the PLC.
1. Join the Units so that the connectors fit exactly.
2. The yellow sliders at the top and bottom of each Unit lock the Units together. Move the sliders
toward the back of the Units as shown below until they click into place.
Precautions for Correct UsePrecautions for Correct Use
If the locking tabs are not secured properly, the connectors may become loose and not function
properly. Be sure to slide the locking tabs until they are securely in place.
Hook
Connector
Move the sliders toward the back
until they lock into place.
Hook holes
Release
Lock
Slider
5 Installation
Level 1 heading
Level 2 heading
Level 3 heading
Gives the current
headings.
noitallatsnI 2-5
5
Page tab
Gives the number
of the section.
gnitcennoC 1-2-5
P
opmoC CL
stnen
Manual name
CJ2 CPU Unit Hardware User’s Manual
This illustration is provided only as a sample and may not literally appear in this manual.
Special Information
Special information in this manual is classified as follows:
Precautions for Safe Use
Precautions on what to do and what not to do to ensure using the product safely.
Precautions for Correct Use
Precautions on what to do and what not to do to ensure proper operation and performance.
Additional Information
Additional information to increase understanding or make operation easier.
A-5 Operation for Power Interruptions................................................................. ... .................A-14 3
A-5-1Power OFF Operation.............................................................................................................A-143
A-5-2Instruction Execution for Power Interruptions .........................................................................A-145
A-6 EtherNet/IP Connections from Windows XP (SP2 or Higher) or Windows Vista...........A-147
A-6-1Changing Windows Firewall Settings......................................................................................A-147
A-7 PLC Comparison Charts: CJ-series and CS-series PLCs ...............................................A-150
A-8 Functions Supported for Unit Versions.............................................................................A-154
Index ................................................................................................................Index-1
Revision History .......................................................................................Revision-1
CJ2 CPU Unit Software User’s Manual
15
16
CJ2 CPU Unit Software User’s Manual
Read and Understand this Manual
Please read and understand this manu al bef o re using the product. Please consult your OMRON representative
if you have any questions or comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a
period of one year (or other period if specified) from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NONINFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE
PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR
INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.
In no event shall the re sponsibility of OMRON f or any act e xceed the individual price of the product on which
liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS
REGARDING THE PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS
WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO
CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
CJ2 CPU Unit Software User’s Manual
17
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the
combination of products in the customer's application or use of the products.
At the customer's request, OMRON will provide applicable third party certification documents identifying
ratings and limitations of use that apply to the products. This information by itself is not sufficient for a
complete determination of the suitability of the products in combination with the end product, machine,
system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not
intended to be an e xhaustive list of all possible uses of the products , nor is it intende d to imply that t he uses
listed may be suitable for the products:
• Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or
uses not described in this manual.
• Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical
equipment, amusement machines, vehicles, safety equipment, and installations subject to separate
industry or government regulations.
• Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the produ cts.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR
PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO
ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any
consequence thereof.
18
CJ2 CPU Unit Software User’s Manual
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other
reasons.
It is our practice to change model numbers when published ratings or features are changed, or when
significant construction changes are made. However, some specifications of the products may be changed
without any notice. When in doubt, special model numbers may be assigned to fix or establish key
specifications for y our application on your request. Please consult with your OMRON representative at any
time to confirm actual specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not t o be used for manufacturing purposes, even when
tolerances are shown.
PERFORMANCE DATA
Perf ormance data given in this manual is provided as a guide fo r the user in determining suitability and does
not constitute a warranty. It may represent the result of OMRON's test cond itions, and the users must
correlate it to actual application requirements. Actual performance is subject to the OMRON Warranty and
Limitations of Liability.
ERRORS AND OMISSIONS
The information in this manual has been carefully checked and is believed to be accurate; however, no
responsibility is assumed for clerical, typographical, or proofreading errors, or omissions.
CJ2 CPU Unit Software User’s Manual
19
20
CJ2 CPU Unit Software User’s Manual
Safety Precautions
Definition of Precautionary Information
The following notation is used in this manual to provide precautions required to ensure safe usage of a
CJ-series PLC. The safety precautions that are provided are extremely important to safety. Always re ad
and heed the information provided in all safety precautions.
WARNING
Caution
Precautions for Safe Use
Indicates precautions on what to do and what not to do to ensure using the product safely.
Precautions for Correct Use
Indicates precautions on what to do and what not to do to ensure proper operation and performance.
Indicates a potentially hazardous situation which, if not avoided,
could result in death or serious injury. Additionally, there may be
severe property damage.
Indicates a potentially hazardous situation which, if not avoided,
may result in minor or moderate injury, or property damage.
CJ2 CPU Unit Software User’s Manual
21
Symbols
The triangle symbol indicates precautions (including warnings).
The specific operation is shown in the triangle and explained in
text. This example indicates a precaution for electric shock.
The circle and slash symbol indicates operations that you must
not do. The specific operation is shown in the circle and
explained in text.
The filled circle symbol indicates operations that you must do.
The specific operation is shown in the circle and explained in
text. This example shows a general precaution for something
that you must do.
The triangle symbol indicates precautions (including warnings).
The specific operation is shown in the triangle and explained in
text. This example indicates a general precaution.
The triangle symbol indicates precautions (including warnings).
The specific operation is shown in the triangle and explained in
text. This example indicates a precaution for hot surfaces.
22
CJ2 CPU Unit Software User’s Manual
WARNING
Do not attempt to take any Unit apart or touch the inside of any Unit while the
power is being supplied. Doing so may result in electric shock.
Do not touch any of th e te rminals or t erminal b lo cks while the power is being
supplied. Doing so may result in electric shock.
Provide safety measures in external circuits (i.e., not in the Programmable
Controller), including the following items, to ensure safety in the system if an
abnormality occurs due to malfunction of the Programmable Controller or
another external factor affecting the operation of the Programmable Controller. "Programmab le Controller" indicates the CPU Unit and all other Units and
is abbreviated "PLC" in this manual. Not doing so may result in serious accidents.
• The PLC will turn OFF all outputs when its self-diagnosis function detects
any error or when a severe failure alarm (FALS) instruction is executed.
Unexpected operation, howe ver, may still occur for errors in the I/O control
section, errors in I/O memory, and other errors that cannot be detected by
the self-diagnosis function. As a countermeasure for all such errors, external safety measures must be provided to ensure safety in the system.
• The PLC outputs may remain ON or OFF due to deposition or burning of
the output relays or destruction of the output transistors. As a countermeasure for such problems, external safety measures must be provided to
ensure safety in the system.
• Provide measures in the computer system and programming to ensure
safety in the overall system even if communications errors or malfunctions
occur in data link communications or remote I/O communications.
Confirm safety before transferring data files stored in the file memory (Memory Card or EM file memory) to the I/O area (CIO) of the CPU Unit using a
peripheral tool. Otherwise, the devices connected to the output unit may malfunction regardless of the operation mode of the CPU Unit.
Fail-safe measures must be taken by the customer to ensure safety in the
event of incorrect, missing, or abnormal signals caused by broken signal
lines, momentary power interruptions, or other causes. Serious accidents
may result from abnormal operation if proper measures are not provided.
CJ2 CPU Unit Software User’s Manual
23
Caution
Execute online edit only after confirming that no adverse effects will be
caused by extending the cycle time. Otherwise, the input signals may not be
readable.
Confirm safety at the destination node before transferring a program, PLC
Setup, I/O tables, I/O memory contents, or parameters to another node or
changing contents of the any of these items. Transferring or changing data
can result in unexpected system operation.
The CJ2 CPU Units automatically back up the user program and parameter
data to flash memory when these are written to the CPU Unit. I/O memory
including the DM, EM, and Holding Areas), however, is not written to flash
memory.
The DM, EM, and Holding Areas can be held during power interruptions with
a battery. If there is a battery error, the contents of these areas may not be
accurate after a power interruption. If the contents of the DM, EM, and Holding Areas are used to control external outputs, prevent inappropriate outputs
from being made whenever the Battery Error Flag (A402.04) is ON.
Tighten the terminal screws on the AC Power Supply Unit to the torque specified in the operation manual. The loose screws may result in burning or malfunction.
Do not touch the Power Supply Unit when power is being supplied or immediately after the power supply is turned OFF. The Pow er Supply Unit will be hot
and you may be burned.
When connecting a personal computer or other peripheral device to a PLC to
which a non-insulated Power Supply Unit (CJ1W-PD022) is mounted, either
ground the 0 V side of the external power supply or do not ground the external power supply at all ground. A short-circuit will occur in the external power
supply if incorrect grounding methods are used. Never ground the 24 V side,
as shown below.
Wiring in Which the 24-V Power Supply Will Short
Non-insulated
DC power supply
24 V
Peripheral
0 V
cable
0 V
24
FG
Power Supply
Unit
CPU Unit
Peripheral device (e.g.,
personal computer)
CJ2 CPU Unit Software User’s Manual
Application Precautions
Observe the following precautions when using a CJ-series PLC.
z Power Supply
• Always use the power supply voltages specified in the user’s manuals. An incorrect voltage may
result in malfunction or burning.
• Exceeding the capacity of the Power Supply Unit may prevent the CPU Unit or other Units from
starting.
• Take appropriate measures to ensure that the specified power with the rated voltage and frequency is supplied. Be particularly careful in places where the power supply is unstab le . An incor rect power supply may result in malfunction.
• Always turn OFF the power supply to the PLC before attempting any of the following. Not turnin g
OFF the power supply may result in malfunction or electric shock.
• Mounting or dismounting Power Supply Units, I/O Units, CPU Units, Option Boards, or any
other Units.
• Assembling the Units.
• Setting DIP switches or rotary switches.
• Connecting cables or wiring the system.
• Connecting or disconnecting the connectors.
• When cross-wiring ter minals, the total current for all the ter minal will flow in the wire. Make sure
that the current capacity of the wire is sufficient.
• Observe the following precautions when using a Power Supply Unit that suppor ts the Replacement Notification Function.
• Replace the Power Supply Unit within six months if the display on the front of the Power Supply Unit alternates between 0.0 and A02, or if the alarm output automatically turns OFF.
• Keep the alarm output cable separated from power line and high-voltage lines.
• Do not apply a voltage or connect a load exceeding the specifications to the alarm output.
• When storing the Power Supply Unit for more than three months, store it at −20 to 30°C and
25% to 70% humidity to preserve the Replacement Notification Function.
• If the P ow er Supply Unit is not insta lled properly, heat buildup may cause the replacement notification signal to appear at the wrong time or may cause interior elements to deteriorate or
become damaged. Use only the standard installation method.
• Do not touch the terminals on the Power Supply Unit immediately after turning OFF the power
supply. Residual voltage may cause electrical shock.
• Observe the following precautions to prevent failure due to difference in electrical potential if the
computer is connected to the PLC.
• Before connecting a laptop computer to the PLC, disconnect the power supply plug of the
computer from the AC outlet. Residual curren t in the AC adaptor may cause differe nce in electrical potential to occur between the computer and the PLC. After you connect the computer
and PLC, supply the power again from the AC adaptor.
• If the computer has an FG term inal, make the connections so that it has the same electrical
potential as the FG (GR) terminal on the PLC.
• If the computer is grounded to a separate location, difference in electrical potential may occur
depending on the grounding conditions.
z Installation
• Do not install the PLC near sources of strong high-frequency noise.
• Before touching a Unit, be sure to first touch a grounded metallic object in order to discharge any
static build-up. Not doing so may result in malfunction or damage.
CJ2 CPU Unit Software User’s Manual
25
• Be sure that the terminal blocks, connectors, Memory Cards, Option Boards, expansion cables,
and other items with locking devices are properly locked into place. I mprope r locking may result in
malfunction.
• The sliders on the tops and bottoms o f the Power Supply Unit, CPU Unit, I/O Units, Special I/O
Units, and CPU Bus Units must be completely locked (until they click into place) after connecting
to adjacent Units. The Unit may not operate properly if the sliders are not locked in place. It may
not be possible to achieve proper functionality if the sliders are not locked.
z Wiring
• Follow the instructions in this manual to correctly perform wiring.
• Double-check all wiring and switch settings before turning ON the power supply. Incorrect wiring
may result in burning.
• Be sure that all terminal screws, and cable connector screws are tightened to the torque specified
in the relevant manuals. Incorrect tightening torque may result in malfunction.
• Mount terminal blocks and connectors only after checking the mounting location carefully.
• Leave the label attached to the Unit when wiring. Removing the label may result in malfunction if
foreign matter enters the Unit.
• Remove the label after the completion of wiring to ensure prop er heat dissipation. Leaving the
label attached may result in malfunction.
• Use crimp terminals for wiring. Do not connect bare stranded wires directly to terminals. Connection of bare stranded wires may result in burning.
• Do not apply voltages to the Input Units in excess of the rated input voltage. Excess voltages may
result in burning.
• Always connect to a ground of 100 Ω or less when installing the Units. Not connecting to a ground
of 100 Ω or less may result in electric shock.
A ground of 100 Ω or less must be installed when sho rting the GR and LG terminals on the Power
Supply Unit.
• Do not apply voltages or connect loads to the Output Units in excess of the maximum switching
capacity. Excess voltage or loads may result in burning.
• Do not pull on the cables or bend the cables beyond their natural limit. Doing either of these may
break the cables.
• Do not place objects on top of the cables or oth er wiring lines. Doing so may break the cables.
• Do not use commercially available RS-232C personal computer cables. Always use the special
cables listed in this manual or make cables according to manual specifications. Using commercially available cables may damage the external devices or CPU Unit.
• Never conne ct p in 6 ( 5-V power supply) on the RS-232C port on the CPU Unit to any device other
than an NT-AL001 Link Adapter, CJ1W-CIF11 Converter, and Programmable Terminals (NV3WM@20L). The external device or the CPU Unit may be damaged.
26
z Handling
• The Power Supply Unit may possibly be damaged if the entire voltage for a dielectric strength test
is applied or shut OFF suddenly using a switch. Use a variable resistor to gradually increase and
decrease the voltage.
• Separate the line ground terminal (LG) from the functional ground terminal (GR) on the Power
Supply Unit before performing withstand voltage tests or insulation resistance tests. Not doing so
may result in burning.
• Make sure that the DIP switches and DM Area are set correctly before starting operation.
• After replacing the CPU Unit, a Special I/O Unit, or a CPU Bus Unit, make sure that the required
data for the DM Area, Holding Area, and other memory areas has been transferred to the new
Unit before restarting operation.
• Confirm that no adverse effect will occur in the system before attempting any of the following. Not
doing so may result in an unexpected operation.
• Changing the operating mode of t he PLC ( includi ng th e setting of the startup operating mod e).
CJ2 CPU Unit Software User’s Manual