Omron CJ1W-TS561 Instruction Sheet

Model
CJ1W-TS561
Thermocouple input unit
INSTRUCTION SHEET
Thank you for purchasing an OMRON product. Read this instruction sheet thoroughly and familiarise yourself with the functions and characteristics of the product before using it. To ensure safe and correct use of this Unit, also read the Operation- and Programming Manuals for your CJ1 PLC system.
Keep this instruction sheet for future reference.
OMRON MANUFACTURING OF THE NETHERLANDS B.V.
OMRON Corporation 2004 All Rights Reserved
General Specifications
Unit classification CJ-series Basic I/O Unit Compatible Racks CJ-series CPU Rack or
CJ-series Expansion Rack Max. number of Units
10 Units/Rack max.
(This requires a CJ1G or CJ1H CPU) CPU Unit data area for inputs
Basic I/O area CIO0000 – 0999
(3, 4 or 6 words allocated in IO Table) Insulation resistance
20 M min. (at 500 V DC) between
input terminals and PLC I/O bus. Dielectric Strength 500 V AC, 50/60 Hz for 1 min. (detection
current: 1 mA), between Input terminals
and PLC I/O bus. Internal current consumption
220 mA max., 5 V DC,
from the PLC I/O bus. Dimensions 31 x 90 x 65 mm (W x H x D) Weight 150 g max. Other
Other general specifications conform to
the CJ-series general specifications.
See Operation Manual W393.
Characteristics
Unit Description
Thermocouple input K-type or J-type (IEC 60584) Number of inputs 1 to 6 Measurement range K-type: -200.0 to +1300.0 °C
J-type: -100.0 to +850.0 °C Indication resolution 0.1 °C Cold junction compensation
- Accuracy
Internal measurement of terminal
temperature, once in each scan cycle.
± 2.0 °C in a stable temperature
environment (no direct heat or airflow). Temperature value Data representation
16-bit signed integer in units of 0.1 °C:
#F830 = -200.0 °C, #32C8 = +1300.0 °C Indication accuracy * over full operational range (0 – 55 °C ambient temperature)
± 0.5 % of indicated value or ± 0.7 °C
(whichever is larger) ± 1 digit max.
±2.0 °C ± 1 digit max. using a K-type
thermocouple below –100 °C. Input response time (per active input)
40 ms (100 Hz suppression)
67 ms (60 Hz suppression)
80 ms (50 Hz suppression)
400 ms (50+60 Hz suppression) Input update cycle time (all active inputs)
[number of active inputs + 1] x [input
response time] + 40 ms I/O refresh time (influence on PLC cycle time)
1-3 inputs (48pt mode): 0.008 ms
4 inputs (64pt mode): 0.011 ms
5-6 inputs (96pt mode): 0.016 ms
The CJ1W-TS561 is a 6-channel input unit for K-type and J-type thermocouples. It can be installed in any CJ1-series PLC system. It is classified as a basic I/O unit, occupying 48, 64 or 96 I/O points, depending on the number of activated inputs. Always verify that the maximum I/O capacity of the CJ1 CPU is sufficient for the number of required I/O points.
Nomenclature
Unit status indicators
RUN (green)
ERC (red)
Sensor error indicators
1 - 6 (red)
Removable Terminal Block
Connections for Thermocouples 1 - 6
CJ1W-TS561: screw terminal
CJ1W-TS561 (SL): screwless terminal
DIP switches (remove terminal block for access)
Select input types (K-type/J-type)
Select filter functions
Select number of active inputs (1-6)
Terminal Block latch
Slide down to remove
Slide up to lock
* Indication accuracy is guaranteed with the supplied terminal block. Do not replace the supplied terminal block by a different model (e.g. screw type by screwless type or vice versa).
LED indicators
Name State Description
OFF Fatal error or no power supply.
Check the host PLC’s CPU status, and the status of other I/O units. If all other units function normally, replace the Unit.
RUN (Green)
ON
Unit functions normally.
OFF
No fatal errors.
ERC (Red)
ON Incorrect DIP switch setting
Fatal error in the Unit.
Check the CPU unit for error codes.
Re-start the PLC system.
If the ERC LED is still lit, replace the unit.
OFF
Measurement of the corresponding channel is within range, or
Channel has been deactivated by DIP switch settings
ON
Measured temperature out-of-range, or
Thermocouple broken wire
Sensor Error 1 – 6 (Red)
All ON Calibration data not found or incorrect. The Unit
should be returned to OMRON for calibration.
Wiring
Keep the thermocouple wiring as short as possible to avoid electrical interference. Shielded wiring is recommended.
When extending input wiring, always use compensation wires appropriate for the thermocouple type.
For activated but unused inputs, short-circuit the + and ­terminals, to prevent unstable readout on the other inputs.
Keep the input wiring away from power lines including AC power supply lines and high-power lines. Do not run the I/O lines in the same duct or conduit as power lines.
The input circuits are galvanically isolated from the PLC’s I/O bus, but there is no galvanic isolation between individual inputs.
Always ground the terminal on the Power Supply Unit of the PLC. In case of shielded sensor wiring, connect the shields to the same grounding point as the PLC.
Measure Cold Junction
+ Sensor error check
Measure Channel 1
Measure Channel 2
Measure Channel N
Unit initialisation
DIP switches
8 DIP switches are accessible after removing the front terminal block. Switch settings are processed at time of power ON, and should not be changed while the unit is powered.
Default (ex-factory) setting is all switches ON, i.e. all 6 inputs are active and set to K-type thermocouple, with filtering at n x 100 Hz. Be sure to adjust the settings to your requirements before use.
SW 1, 2 and 3 : Input type selection
Any combination of input types (different numbers of K-type/J-type sensors) can be set.
SW State Input type selection
OFF Input channel 1 is J-type 1 ON Input channel 1 is K-type OFF Input channels 2 and 3 are J-type 2 ON Input channels 2 and 3 are K-type OFF Input channels 4, 5 and 6 are J-type 3 ON Input channels 4, 5 and 6 are K-type
SW 4 + 5 : Input filtering (valid for all active input channels)
Use filtering if the measured value is affected by the mains frequency or other sources of electrical interference.
SW4 SW5 Filtering Response time
OFF OFF n x 10 Hz suppression 400 ms each input OFF ON n x 50 Hz suppression 80 ms each input ON OFF n x 60 Hz suppression 67 ms each input ON ON n x 100 Hz suppression 40 ms each input
SW 6+7+8 : Input activation
To prevent broken wire indication for unused inputs, and to reduce the number of input channels occupied in CIO memory, the number of required inputs can be set by SW 6+7+8.
Input words are allocated in the PLC’s CIO area as Basic I/O Unit, i.e. sequentially starting at the leftmost unit. See CJ1-series Operation Manual W393 for details.
Create the I/O table in the PLC after changing the switch settings, to register the correct number of input words in the PLC CPU. The unit is registered as 48-point, 64-point, or 96-point input unit, depending on the number of 16-bit CIO words it occupies.
SW6 SW7 SW8 Active inputs Occupied input words
OFF OFF OFF Not valid, ERC indicator will be ON ON OFF OFF 1 3 CIO words (1 used)* OFF ON OFF 1, 2 3 CIO words (2 used)* ON ON OFF 1, 2, 3 3 CIO words OFF OFF ON 1, 2, 3, 4 4 CIO words ON OFF ON 1, 2, 3, 4, 5 6 CIO words (5 used)* OFF ON ON 1, 2, 3, 4, 5, 6 6 CIO words ON ON ON 1, 2, 3, 4, 5, 6 6 CIO words
* In these cases, more CIO words will be occupied than required for the active inputs. The remaining occupied CIO words will be filled with 0’s, and cannot be used as work bits.
Data representation
Measured temperatures are indicated in °C. Each input value occupies one word (16 bits) in the CIO area and is encoded as a signed integer, with a resolution of 0.1 °C.
Examples: #0300 = 768 (dec) = 76.8 °C #FF85 = -123 (dec) = -12.3 °C
Measured values are updated in CIO memory in each I/O refresh cycle. The following values are to be interpreted as error codes:
Value Description
#7AAA Calibration data invalid or error detected at start-up,
e.g. cold junction temperature out of range. #7BBB Sensor error, broken wire #7CCC Measured value out of range (over max. Temperature) #8CCC Measured value out of range (under min. Temperature)
During initialisation after power ON, data of active inputs will be #0000 until the “Not Ready’ flag turns OFF.
‘Not Ready’ flag
During initialisation after power-on, and in case of internal failure, a ‘Not Ready’ flag will be set in the PLC memory area A050 to A069 (Basic I/O Unit information area, refer to CJ1 Operation Manual W393 for details). The lower bit of each unit is the Not Ready flag; the error code indicated in the remaining bits is relevant for repair purposes only. While this flag is ON, the temperature sensor data indicated by the unit in the CIO area is invalid.
Address Bit When Bit = ON
00 Unit in rack 0, slot 0 is not ready A050
08 Unit in rack 0, slot 1 is not ready
00 Unit in rack 0, slot 2 is not ready A051
… …
00 Unit in rack 1, slot 0 is not ready A055
… …
00 Unit in rack 3, slot 9 is not ready A069
08 Unit in rack 3, slot 10 is not ready
Unit cycle time
The internal processing time for all measurements by the unit is determined by the number of active channels and the filter type.
The cold junction compensation measurement and one sensor error check are executed each cycle.
The cold junction measurement time depends on the input filter setting, whereas the sensor error check takes a fixed 40 ms.
Example: If 4 inputs are active, and filtering is set to n x 50 Hz (response time = 80 ms):
Each measurement cycle takes (4+1) x 80 + 40 ms = 440 ms.
OMRON CORPORATION
Note: Specification subject to change without notice Printed in The Netherlands 1634299-2A
OMRON ELECTRONICS LLC
Phone: 1-847-843-7900 or 1-800-55-OMRON
OMRON CANADA INC.
Phone: 416-286-6465 Phone: 1-514-636-6676 (French)
Loading...