This document provides the reference information for replacing C200H PLC systems with CS1 series PLC.
This document does not include precautions and reminders ;please read and understand the important precautions
and reminders described on the manuals of PLCs (both of PLC used in the existing system and PLC you will use to
replace the existing PLC) before attempting to start operation.
Related Manuals
CPU Units
Man.No. Model Manual
W394 CS1G/H-CPU□□H
CS1G/H-CPU□□-V1
CS1D-CPU□□H
CS1D-CPU□□S
CJ1H-CPU□□H-R
CJ1G/H-CPU□□H
CJ1G-CPU□□P
CJ1M/G-CPU□□
NSJ□-□□□□(B)-□□□
W474 CS1G/H-CPU□□H
CS1G/H-CPU□□-V1
CS1D-CPU□□H
CS1D-CPU□□S
CJ1H-CPU□□H-R
CJ1G/H-CPU□□H
CJ1G-CPU□□P
CJ1M/G-CPU□□
NSJ□-□□□□(B)-□□□
W342 CS1G/H-CPU□□H
CS1G/H-CPU□□-V1
CS1D-CPU□□H
CS1D-CPU□□S
CS1W-SCU□□-V1
CS1W-SCB□□-V1
CJ1H-CPU□□H-R
CJ1G/H-CPU□□H
CJ1G-CPU□□P
CJ1M/G-CPU□□
CJ1W-SCU□□-V1
CP1H-X□□□□-□
CP1H-XA□□□□-□
CP1H-Y□□□□-□
NSJ□-□□□□(B)-□□□
W341 CQM1H-PRO01
CQM1-PRO01
C200H-PRO27
CS1W-KS001
W339 CS1G/H-CPU□□H
CS1G/H-CPU□□-V1
W302 C200HX/HG/HE
-CPU□□/CPU□□-Z
W303 C200HX/HG/HESYSMACα OPERATION MANUAL
W322 C200HX-CPU□□-ZE
C200HG-CPU□□-ZE
C200HE-CPU□□-ZE
W227 CV500/CV1000
C200H/C1000H/C2000H/
3G8F5
CS/CJ/NSJ Series PROGRAMMING MANUAL
CS/CJ/NSJ Series INSTRUCTIONS REFERENCE MANUAL
CS/CJ/CP/NSJ Series Communications Commands REFERENCE MANUAL
CS/CJ Series Programming Consoles OPERATION MANUAL
CS Series OPERATION MANUAL
SYSMACα INSTALLATION GUIDE
SYSMACα OPERATION MANUAL
FINS Commands Reference Manual
Special I/O Units
Man.No. Model Manual
W426 CS1W-NC□71
CJ1W-NC□71(-MA)
W435 CS1W-MCH71
CJ1W-MCH71
W440 CS1W-FLN22
CJ1W-FLN22(100BASE-TX)
W336
W345 CS1W-AD0□□-V1/-AD161
W368 CS1W-PTS□□
W902 CS1W-CT021/041 CS Series High-speed Counter Units OPERATION MANUAL
W378
W384 CS1W-HIO01
W376 CS1W-NC□□□CS Series Position Control Units OPERATION MANUAL
W359 CS1W-MC□□□-V1 CS Series Motion Control Units OPERATION MANUAL
W124 C200H-TS001/002/101/102 C200H Temperature Sensor Units OPERATION MANUAL
W127 C200H-AD001/-DA001 C200H Analog I/O Units OPERATION GUIDE
W229 C200H-AD002/-DA002 C200H Analog I/O Units OPERATION MANUAL
W325 C200H-AD003
W225 C200H-TC001/002/003
W240 C200H-TV001/002/003
W241 C200H-PID01/02/03 C200H PID Control Unit OPERATION MANUAL
W141 C200H-CT001-V1
W311 C200H-CT021 C200H High-speed Counter Units OPERATION MANUAL
W224 C200H-CP114 C200H Cam Positioner Units OPERATION MANUAL
W334 C200HW-NC113/213/413 C200HW Position Control Units OPERATION MANUAL
W137 C200H-NC111 C200H Position Control Units OPERATION MANUAL
W128 C200H-NC112 C200H Position Control Units OPERATION MANUAL
W166 C200H-NC211 C200H Position Control Units OPERATION MANUAL
W314 C200H-MC221C200H Motion Control Units OPERATION MANUAL:INTRODUCTION
W315 C200H-MC221C200H Motion Control Units OPERATION MANUAL:DETAILS
W165 C200H-ASC02C200H ASCII Units OPERATION MANUAL
W306 C200H-ASC11/21/31 C200H ASCII Units OPERATION MANUAL
CS1W-SCB□□-V1
CS1W-SCU□□-V1
CJ1W-SCU□□-V1
CS1W-DA0□□
CS1W-MAD44
CJ1W-AD0□□-V1/-AD042
CJ1W-DA0□□/-DA042V
CJ1W-MAD42
CS1W-PTW□□
CS1W-PDC□□
CS1W-PTR□□
CS1W-PPS□□
CS1W-PMV□□
CJ1W-PTS□□
CJ1W-PDC□□
CJ1W-PH41U
CS1W-HIO01-V1
CS1W-HCP22-V1
CS1W-HCA22-V1
CS1W-HCA12-V1
CS1W-HCP22
CS1W-HCA22
C200H-DA003/-DA004
C200H-MAD01
C200H-TC101/102/103
C200H-TV101/102/103
C200H-CT002
CS/CJ Series Position Control Units OPERATION MANUAL
CS/CJ series Motion Control Units OPERATION MANUAL
CS/CJ Series FL-net Units OPERATION MANUAL
CS/CJ Series Serial Communications Boards Serial Communications Units
OPERATION MANUAL
CS/CJ Series Analog I/O Units OPERATION MANUAL
CS/CJ Series Analog I/O Units OPERATION MANUAL
CS Series Customizable Counter Units OPERATION MANUAL
Series Customizable Counter Units PROGRAMMING MANUAL
CS
C200H Analog I/O Units OPERATION MANUAL
C200H Temperature Control Units OPERATION MANUAL
C200H Heat/Cool Temperature Control Units OPERATION MANUAL
C200H High-speed Counter Units OPERATION MANUAL
Man.No. Model Manual
W304 C200HW-COM01
C200HW-COM02-V1 to
C200HW-COM06-EV1
W257 CVM1-PRS71 Teaching BoxOPERATION MANUAL
C200HW Communication Boards OPERATION MANUAL
Network Communications Units
Man.No. Model Manual
W309 CS1W-CLK23
CS1W-CLK21-V1
CJ1W-CLK23
CJ1W-CLK21-V1
C200HW-CLK21
CVM1-CLK21
CQM1H-CLK21
CS1W-RPT0□
W370 CS1W-CLK13
CS1W-CLK12-V1
CVM1-CLK12(H-PCF Cable)
CS1W-CLK53
CS1W-CLK52-V1
CVM1-CLK52(GI Cable)
W465 CS1W-EIP21
CJ1W-EIP21
CJ2H-CPU6□-EIP
CJ2M-CPU3□
W420 CS1W-ETN21
CJ1W-ETN21
W421 CS1W-ETN21
CJ1W-ETN21(100Base-TX)
W456 CS1W-CRM21
CJ1W-CRM21
W457 CRT1 CRT1 Series CompoNet Slave Units and Repeater Unit OPERATION MANUAL
W380 CS1W-DRM21-V1
CJ1W-DRM21
W267 CS1W/CJ1W/C200HW
DRT1/DRT2
GT1
CVM1
W266 C200HW-SRM21-V1
CS1W-SRM21
CJ1W-SRM21
CQM1-SRM21-V1
SRT1/SRT2
W136 C500-RM001-(P)V1
C120-RM001(-P)
C500-RT001/RT002-(P)V1
C500/C120-LK010(-P)
C200H-RM001-PV1
C200H-RT001/002-P
B500-I/O
W308 C200HW-ZW3DV2/ZW3PC2
3G8F5-CLK11/21
3G8F6-CLK21
(100Base-TX)
Controller Link Units OPERATION MANUAL
Optical Ring Controller Link Units OPERATION MANUAL
Series EtherNet/IP Units OPERATION MANUAL
CS/CJ
CS/CJ Series Ethernet Units OPERATION MANUAL Construction of Networks
CS/CJSeries Ethernet Units OPERATION MANUAL Construction of Applications
CS/CJ Series CompoNet MasterUnits OPERATION MANUAL
CS/CJ Series DeviceNet Units OPERATION MANUAL
DeviceNet OPERATION MANUAL
CompoBus/S OPERATION MANUAL
C series Rack PCs Optical Remote I/O SYSTEM MANUAL
Controller Link Support Software OPERATION MANUAL
Man.No. Model Manual
W120 C500-RM201/RT201
C200H-RM201/RT201/202
G71-IC16/OD16
G72C-ID16/OD16
S32-RS1
W379 CVM1-DRM21-V1
C200HW-DRM21-V1
W347 C200HW-DRT21
CQM1-DRT21
DRT1
W135 C200H-LK401
C500-LK009-V1
C series Rack PCs Wired Remote I/O SYSTEM MANUAL
DeviceNet Master Units OPERATION MANUAL
DeviceNet Slaves OPERATION MANUAL
C Series PC Link SYSTEM MANUAL
Support Software
Man.No. Model Manual
W463 CX-One FA Integrated Tool Package SETUP MANUAL
W446 CX-ProgrammerOPERATION MANUAL
W447 CX-Programmer OPERATION MANUAL : Function Blocks/Structured Text
W464 CX-Integrator OPERATION MANUAL
W344
CXONE-AL□□C-V4
CXONE-AL□□D-V4
CX-Protocol OPERATION MANUAL
Read and Understand this Document
Please read and understand this document before using the product. Please consult yourOMRON representativeif youhave any questions orcomments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free fromdefects in materials and workperiod of oneyear(or other period ifspecified) from dateof sale byOMRON.
OMRON MAKES NOWARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED,REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THEPRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THATTHE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIRINTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED.
manship for a
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES,LOSS OF PRWHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NOEVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON'SANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TOCONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
OFITS OR COMMERCIAL LOSS INANY WAY CONNECTED WITH THE PRODUCTS,
Disclaimers
CHANGE IN SPECIFICATIONS
Productspecifications and accessories may be changed at any timebasedon improvements and other reasons.
It is our practiceto changemodel numbers whenpublishedratings orfeatures are changed, or whensignificant construction changes are made. However, somespecifications of the products may bechanged without any notice. Whenindoubt, special model numbers may be assigned to fix or establishkey specifications for your application on your request.Please consult withyourOMRON representativeat any time toconfirm actual specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensionsand weights are nominal and are not to beused for manufacturing purposes,even whent
olerances are shown.
PERFORMANCE DATA
Performance data given in this manual is provided asa guide for the user in determining suitabilityand doesnot constitutea warranty. It may represent theresult ofOMRON's test conditions, and the users mustcorrelateit toactual application requirements. Actual performanceis subject tothe OMRON Warranty andLimitations of Liability.
ERRORS AND OMISSIONS
The information in this manual has been carefully checked and is believed to beaccurate; howeveresponsibility is assumed for clerical, typographical, or proofreading errors, or omissions.
r, no
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformitywith any standards, codes,or regulations that apply to thecombination of products in the customer's application oruse oftheproducts.
At the customer's request, OMRON will provide applicable third party certification documentsidentifying ratings and limitations of use that apply to the products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product, machine,system, or other applicationor use.
The following are some examples of applications for which particular attentionmust be given.This is not intended to be an exhaustivelist ofall possible usesof the products,nor is it intended to imply that the uses listedmay be suitable for the products:
•Outdoor use,uses involving potential chemical contamination orelectricalinterference, orconditions orusesnot described in thismanual.
•Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,safety equipment,and installations subject toseparateindustry orgovernment regulations.
•Systems, machines, andequipmentthat could present a risk to life orproperty.
Pleaseknowandobserve all prohibitions ofuse applicable tothe products.NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR
PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TOADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for theuser's programming of a programmable product, or any co
2.Selecting the model...............................................................................................................................................3
3.Reading data from C200H....................................................................................................................................7
4.Converting the program for CS1...........................................................................................................................9
5.Writing data to CS1.............................................................................................................................................11
Appendix A. Instructions converted by Change Model on CX-Programmer..........................................................13
Appendix B. Change of unit area allocation............................................................................................................14
Appendix C. Change in PLC Settings.....................................................................................................................14
Appendix D. Change of execution timing etc..........................................................................................................14
Appendix E. Table of Input/Output Units.................................................................................................................15
This replacement guide describes the procedure to rebuild the system which uses the C200H-series PLC by
introducing the CS1-series PLC instead. The CS-series has functions which can replace the functions and
operation of C200H-series PLC. Take the below work flow to replace your system. Also, refer to the reference
pages for details.
1. Work flow
1) Preliminary Steps: Take the following steps before starting the replacement work.
Start
Selecting the model
Select the unit,programming software, and connectingcable to replace C200H with CS1.Some C200H Unitscan be used with CS1. However, some Units can not be used with CS1. Read the reference pages(recommended models and precautions) and select the models.
Description ReferencePages
2. Selecting the model
Preparing Units
Reading PLCdata
Converting and modifyingdata
Continue toactual replacement work
Prepare the units, programming software,and connectingcable.
Load the program, I/OMemory andother settings fromthe C200H using the programming software and connectingcable.
Convert the data readfromC200H for CS1.Most of thedatacan be automaticallyconverted; however, someinstructions and some Unit data can not be converted.Refertothe reference pages and modifythe data and programseparately.
2) Actual replacement work: Take the steps below to replace the C200H to CS1.
Replacing Units
Wiring
Installthe prepared Units instead of C200H Units.*Refer totheCS1G/H-CPUxxH/CS1G/H-CPUxx-EV1 CS
SERIES CPU UNITS OPERATIAN MANUAL (Cat. No. W339)and User's manualfor SpecialI/O Units and CPU Bus
Units for details aboutinstallation.
Wiring for theinstalledUnits.*Refer to theCS1G/H-CPUxxH/CS1G/H-CPUxx-EV1 CS
SERIES CPU UNITS OPERATIAN MANUAL (Cat.No.W339) and User's manualforSpecialI/O Units and CPU Bus
Units for details about wiring.
Description Referencpagese
3. Reading data from C200H
4. Converting and changingthe program for CS1
Table.6Related Manuals
Writing the data toCS
Checking operation
Replacementcompletion
Transfertheconverted data to CS1 To checkthewiring, operate Input/Outputtoseeiftheyoperate correctly.
TurnONthe powerand check the operation.
1.Ifproductionis conducted between uploading theprogramand executingreplacement
work, data handled bythe programmay change.If so,upload the data right before the
replacement work,modifydata (ifnecessary),and download itto the new PLC.
2.The cycle time of C200H and CS1 are different, which may effect system operation.If
so, itis necessary to adjustcycle timefromthe PLC settings.
5.Writing the data to CS1
2. Selecting the model
Outline of the system configuration
SYSMAC Support Software
CX-Programmer
PC
CX-Programmer
PC
C200H
Expansion Backplanes
CS1
Expansion Backplanes
The table below lists the models of C200H-series and each corresponding models of CS1-series. Select the
CS1-series model which is compatible with the C200H-series model. Or, select the CS1-series model with similar
specification to the C200H-series Unit.
Refer to the CS1G/H-CPU□□H/CS1G/H-CPU□□-EV1 CS SERIES CPU UNITS OPERATIAN MANUAL (Cat. No.
W339) for details of the Units.
< CPU Units and Power Supply Units >
Unit name C200H-series CS1-series Description
CPU Units C200H-CPU01
CPU Unit-mounting Host Link Units Power Supply Units
to convert RS232C into RS422. To use RUN output, prepare Output Unit separately. With 24 VDC service power supplyTo use RUN output, prepare Output Unit separately. With maintenance forecast monitor.
With RUN output.
With RUN output.
To use RUN output, prepare Output Unit separately. To use RUN output, prepare Output Unit separately. Respectively for 3, 5, 8, and 10 slots. The installation hole position is the same.
Memory Cassette
Unit name C200H-series CS1-series Description
Memory Unit Memory Unit (RAM type)
C200H-MR431
(Battery type)
C200H-MR432
(Capacitor type)
C200H-MR831
(Battery type)
C200H-MR832
(Capacitor type)
C200H-MR433
(Battery type, with clock function) C200H-MR833
(Battery type, with clock function)
EEP ROM Unit
C200H-ME431 C200H-ME432
(with clock function) C200H-ME831 C200H-ME832
(with clock function)
C200H-MP831 None The CS Series CPU Units have a nonvolatile
None The CS Series CPU Units have a nonvolatile
memoryfor user program in it. The memoryunit is unnecessary. They also have the clock function.
None The CS Series CPU Units have a nonvolatile
memoryfor user program in it. The memoryunit is unnecessary. They also have the clock function. The program file and the parameters are stored in the memory card. It is possible to execute operation by reading them at power ON. (Automatic Transfers at Power ON)
memoryfor user program in it. The memoryunit is unnecessary. They also have the clock function. The program file and the parameters are stored in the memory card. It is possible to execute operation by reading them at power ON. (Automatic Transfers at Power ON)
<I/O Expansion System>
Unit name C200H-series CS1-series Description
Power Supply Units
C200HW-PA204C
C200HW-PA204S
C200HW-PA204R
C200HW-PA209R
C200H-PS211 C200HW-PD024
C200HW-PD025
Backplanes (Expansion Backplanes)
Connecting Cables for Expansion Backplanes CS1W-CN□□1 This cable connects a CS1 CPU Backplane
C200H-PS221 C200HW-PA204
C200H-BC031(-□□) C200H-BC051(-□□) C200H-BC081(-□□) C200H-BC101(-□□) C200H-CN□□1 CS1W-CN□□3 This cable connects a CS1 CPU Backplane
(AC Power Supply Unit)
(AC Power Supply Unit)
(AC Power Supply Unit)
(AC Power Supply Unit)
(AC Power Supply Unit)
(DC Power Supply Unit)
(DC Power Supply Unit) CS1W-BI033/BI032 CS1W-BI053/BI052 CS1W-BI083/BI082 CS1W-BI103/BI102
With maintenance forecast monitor.
With 24 VDC power supply.
The RUN output does not operate.
The RUN output does not operate.
Respectively for 3, 5, 8, and 10 slots The installation hole position is the same.
and a CS1 Expansion Backplanes.
and an Expansion I/O Backplanes (C200HW-BI□□1-V2).
<I/O Units, CPU Bus Units>
Unit name C200H-series CS1-series Description
Basic I/O Units C200H-I□□□
Special I/OUnit
Communication Units [SYSMAC LINK]
[SYSNET]
[Host Link] [Serial Communication] C200HHost Link Unit can not be used with
C200H-series Basic I/O Units can be used with CS1-series CPU Units. Refer to Appendix E. Table of Input/Output Units for CS1 Basic Input/Output Units corresponding to C200H Basic Input/Output Units. We recommend replacing the C200H-series Basic Units with CS1-series Basic I/OUnits for maintenance purpose. C200H-series Special I/O Units can be used with CS1-series CPU Units.However, there are some remarks to be followed. To improve the system performance and to facilitate maintenance, we recommend you to use the CS-series Units instead. C200HW-SLK□□ can not be used with CS1-series CPU Unit. Refer to the SYSMAC CS1W-SLK11/21
SYSMAC LINK Units OPERATIAN MANUAL (Cat. No. W367) for details about
SYSMAC LINK. We recommend you to use the Controller Link instead. Refer to theController Link Units (Wire
type) Operation Manual (Cat. No. W309) and Controller Link Units (H-PCF Optical Fiber Cable ring connection) Operation Manual (Cat. No. W370) for details.
SYSNET can not be used with CS1-series CPU Unit. We recommend you to renewal the system with Controller Link instead. Refer to the Controller Link Units (Wire
type) Operation Manual (Cat. No. W309) andController Link Units (H-PCF Optical Fiber Cable ring connection) Operation Manual (Cat. No. W370) for details.
CS1-series CPU Unit. Refer to the SYSMAC CS/CJ Series Serial
Communications Boards/Units OPERATIAN MANUAL (Cat. No. W336) for
details. The CS-series does not have the Optical-type Serial Communications Board/Unit. Use the wire-type instead, or use an external optical link module. Use one of the left CS1-series Unit/Board.
Use one of the left CS1-series Unit/Board.
PC Link Unit can be used with CS1-series CPU Unit. However, link area allocation, etc. must be modified. We recommend you to use the Controller Link instead. Refer to the Controller Link Units (Wire
type) Operation Manual (Cat. No. W309) andController Link Units (H-PCF Optical Fiber Cable ring connection) Operation Manual (Cat. No. W370) for details.
SYSBUS Unit can be used with CS1-series CPU Unit. However, relayarea allocation, etc. must be modified.
To improve the system performance and to facilitate maintenance, we recommend you to use left networks instead. Refer to the CS/CJ series CompoNet
Master Units Operation Manual (Cat. No. W456) andCompoNet Slave Units and Repeater Unit OPERATION MANUAL (Cat. No. W457) for details of CompoNet.
Refer to the SYSMAC CS/CJ series CS-series: CS1W-DRM21(-V1)CJ Series: CJ1W-DRM21 DeviceNet Units OPERATIAN MANUAL (Cat. No. W380) for
details about DeviceNet. Refer to the C200HW-SRM21-V1
CS1W-SRM21, CJ1W-SRM21 CQM1-SRM21-V1 SRT1 Series SRT2 Series CompoBus/S OPERATIAN MANUAL (Cat. No. W226) for details about
CompoBus/S.
<Support software and peripheral devices>
Name C200H-series CS1-series Description
Support software SYSMAC Support Software
Peripheral Interface Unit, connecting cable
Programming Console C120-PRO15
PROM Writer C500-PRW06 None EPROM can not be used with CS1-series.
Floppydisk interface C500-FD103 None Save the data using a PC
Printer interface unit C500-PRT01
CX-Programmer
C200H-IP007 CS1W-CN226/626To load the program onto CX-Programmer
C120-PRO25
C2000-MP103-V□
CX-One CXONE-AL□□C-V□/ AL□□D-V□(CX-Programmer Ver.3.0 or higher)
C200H-PRO27(+CS1W-CN□□4)CQM1-PRO01(+CS1W-CN114)
None Print the data using a PC
SYSMAC Support Software can not be used with CS1-series CPU Unit.
from C200H, C200H-IP007 and cable (CQM1-CIF02) are required. CS1W-CN□□4 is a Programming Console Connecting Cable. A cassette interface can not be used.
Save the data using a PC (CX-Programmer).
(CX-Programmer).
(CX-Programmer).
Other remarks
(1) The CPU Unit and Power Supply Unit are separated with CS1-series, though they are combined with
C200H-series. The two series use different Backplanes. However, the installation hole position is the
same.
(2) The DIN track (PFP-50N/100N/100N2) and mounting bracket (C200H-DIN01) can be used for the CS1
backplane, too.
(3) The backplane of the CS1-series has an installation structure to be insulated from the control board etc.,
Insulation Plates for CPU Backplanes (C200HW-ATT31/51/81/A1) is unnecessary.
(4) I/O Unit bracket can not be used with CS1-series. The Units of CS1-series can be secured with screws.
They do not require brackets.
3. Reading data from C200H
Load the ladder program, and Data Memory from the C200H using the CX-Programmer.
Required items
Peripheral Interface Unit and
Support software (PC)
connecting cable
PC
CX-Programmer
CX-One (CXONE-AL□□C-V□, CXONE-AL□□D-V□) Or, CX-Programmer (WS02-CXPC□-V□) C200H-IP007 and CQM1-CIF02 Or, C120-LK201-V1 and XW2Z-200P-V
C200H
Connecting cable
CQM1-CIF02 (Or,XW2Z-200P-V)
Peripheral Interface Unit
C200H-IP007 (Or, C120-LK201-V1)
(1) Attach the Peripheral Interface Unit onto the C200H and connect it with a PC.
(2) Start up the CX-Programmer.
(On the Start menu, select All Program - OMRON - CX-One - CX-Programmer - CX-Programmer.)
(3) Select C200H for the Device Type. (Select File - New to display below dialog).
(4) Connect the PLC and the CX-Programmer online. (Select PLC - Work Online).
(5) Transfer the ladder program and I/O table. (Select PLC - Transfer - From PLC.)
Press the OK button to s
(6) Transfer the PLC memorydata (Data Memory). (Select PLC on the menu bar and then click Edit - Memory.)
tart transfer.
Scroll and check all the areas. Press the Transfer from PLC button to start transfer.
(7) Make the CX-Programmer offline. (Select PLC - Work Online.)
(8) Save the program by specifying the project name. (Select File - Save As).
4. Converting the program for CS1
On the CX-Programmer, convert the program for CS1.
(1) Start the CX-Programmer and open the program file for C200H. (Select File - Open.)
(2) Change the Device Type from C200H to CS1. (Select PLC - Change Model to display below dialog.)
(3) The instructions are
automatically converted. The Output Window shows the conversion results. Double-click
an error shown on the Output Window to jump to the corresponding section of the ladder program.
Errors and warnings at conversion will be displayed.
Double-click an error or a warning to jump to the corresponding circuit.
Some instructions cannot be converted. Modify the ladder program referring to Appendix A. Instructions converted
by Change Model on CX-Programmer.
You can check the program by selecting Program - Compile (Program Check). The Output Window shows the
checking results.
(4) The PLC memory data cannot be maintained when PLC model is changed. Open the PLC Memory window for
both C200H and CS-series PLCs and copy and paste the necessary memory data after conversion
Select the necessary PLC Memory on the C200H PLC Memory window and
copy and paste it onto the PLC Memory of the CS series PLC.
.
(5) The I/O allocation of C200H-series is partly different from that CS1-series. Refer to Appendix B. Change of data
area allocation and modify the ladder program.
(6) The PLC settings of C200H-series are partly different from that of CS1-series. Refer to Appendix C. Change in
PLC s
ettingsand change the PLC settings.
(7) Select Program - Compile to check the program. If an error is detected, correct it.
(8) Save the program by specifying the project name. (Select File - Save As.)
5. Writing data to CS1
Transfer the converted and modified program, PLC settings and Data Memory to the CS1.
Required items Support software
Connecting cable CS1W-CN226/626
(PC)
PC
CX-Programmer
CX-One CXONE-AL□□C-V□/ AL□□D-V□(CX-Programmer)
CS1
Connecting cable
CS1W-CN226/626
Peripheral porton CPU Unit
(1) Connect the CS1 and the PC.
(2) Start the CX-Programmer and open the converted program file.
(3) Connect the CS1 and the CX-Programmer online.
(4) Transfer the ladder program and PLC settings to the CS1. (Select PLC - Transfer - To PLC.)
Click the check boxes for Program and PLC Settings. Press the OK button to start transfer.
(5) Select PLC on the menu bar and then click Edit - Memory to display below dialog. Transfer the PLC memory
(Data Memory: D and Holding Relay: HR) after selecting the transfer data. Click the Transfer to PLC button.
(6) Make the CX-Programmer offline.
6. Appendix
Appendix A. Instructions converted by Change Model on CX-Programmer
(1) The data type of operand is changed from BCD data to BIN data for some instructions.
(2) The number of operand is changed for some instructions.
(3) Interrupt control instructions must be changed. (Use MSKS, MSKR, CLI, DI, and EI).
Refer to the list below for detail. The table lists the instructions which are automatically converted producing some difference
between instructions before and after conversion. The other instructions are automatically converted.
Instruction forC200H
JMP(04)
JME(05) JME(5) or
WSFT(16) Same as C200H #0 is added to the Operand1.
ASFT(017) XFERC(565) MOVBC(568) DISTC(566) COLLC(567) CMPL(060) MCMP(019) LINE(063) Changed from BCD data to BIN data. COLM(064) Changed from BCD data to BIN data. SEC(065) HMS(066) ++B(594)
--B(596) +B(404) +BL(405)
-B(414)
-BL(415) *B(424) *BL(425) /B(434) /BL(435) +(400)
-(410) *(420) /(430) APR(069)
Use a differentiated execution condition for the SNXT instruction.
MSG(46)
Not supported BCNTC(621) WDT(094) Control data configuration is different. IORF(097)
Enter the settings from PLC settings. Not supported ――Enter the settings from PLC settings. SEND(090) Control data configuration is different. RECV(098) Control data configuration is different.
When #0 is set to the Operands, JMP is converted to JMP0 and operand is deleted. If #0 is not set, same as C200H.When #0 is set to the Operands, JME is converted to JME0 and operand is deleted. If #0 is not set, same as C200H.
WSFT D1 D2 -> WSFT #0 D1 D2 Same as C200H Same Same as C200H Same Same as C200H Same Same as C200H Same Same as C200H Same Same as C200H Same Same as C200H Same
Same as C200H Same Same as C200H Same Same as C200H Same Same as C200H Same Same as C200H Same Same as C200H Same Same as C200H Same Same as C200H Same Same as C200H Same Same as C200H Same Same as C200H Same Same as C200H Same Same as C200H Same Same as C200H Same Same as C200H Same Same as C200H Same Same as C200H Same
Combine and use below instructions: MSKS(690), CLI(691), MSKR(692), DI(693), EI(694)
The CIO, Holding, Work, Auxiliary, DM, and EM Area are all converted into the WR relay. Same as C200H Same
FAL N -> FAL N #0
FALS N -> FALS N #0 #0 is added to Operand 1. MSG S -> MSG #0 S Number of characters (words) to be registered from first message word (S) is changed from 16 characters (8 words) to 32 characters (16 words). Use MSG(46), instead. Same as C200H Same
On CS1, Unit No, of C200H Group-2 High-densityI/O Units is disabled. Specify the allocation by using IORF in the same way as Basic I/O Units.
#0: 1 -> 0 = #0: Same
#0: 1 -> 0 = #0: Same
Changed from 2 to 3
Same Same
Same
Changed from 1 to 2.
Changed from 1 to 2.
Changed from 1 to 2.
―
Same
Same Same
Appendix B. Change of unit area allocation
This section describes the difference of unit area allocation in C200H and CS1-series. Refer to related manuals for details.
Item C200H-series CS1-series Description
I/O allocation
Basic I/O
I/O allocation
Special I/O
I/O allocation (Group-2 High-densityI/O Units)
Auxiliary Relay Area SR 236 to 255 (1) AR Area and Bit.
Link Relay Area (PC Link) LR00 to LR63 CIO 1000 to 1063
SYSBUS Remote I/O 50 to 99 CIO 3000 to 3049
Abnormal historystorage area
"Free location and fixed channel" "Free location and free channel"
IR 100 to 199 (10words allocated for each Unit No.) DM1000 to 1999 (100words allocated for each Unit No.)
IR 30 to 49 (2 or 4 words allocated for each Unit)
DM 969 to 999 AR 100 to A199 Change the program if the
Change the channel and bit address used in the program.
CIO 2000 to 2199 (10words allocated for each Unit No.) DM20000 to 21999 (100words allocated for each Unit No.) Change the channel and bit address used in the program. The allocation is decided in the same wayas a Basic I/O Units depending on the installed position (rack and slot).Change the channel and bit address used in the program.
Change the channel and bit address used in the program. (2) Condition flags and clock pulse Change the operation flags in the program to the condition flags. Use the global symbols such as P_0.1ms and P_1ms instead of the clock pulse.
Change the channel and bit address used in the program.
Change the channel and bit address used in the program.
For CS1-series, it isnecessary to register I/O table.
Refer to CS1G/H-CPU**H
/CS1G/H-CPU**-EV1 CS SERIES CPU UNITS OPERATIAN MANUAL
(Cat. No. W339) for details on I/O allocation.
Operation flags and condition flags of CS1 can be specified by label.
Error History Area is read inthe program.
Appendix C. Change in PLC Settings
Mode at Power ON Setting switch on the memory unit Select the "Mode" at power ON from
Constant Cycle Time Function
Item C200H-series CS1-series Description
PLC settings.
Constant Cycle Time (FUN18) Enter the value in the "Constant Cycle
Time" from PLC settings.
Appendix D. Change of execution timing etc.
Interrupt execution method and execution timing
Cycle Time - The cycle time is shortened with CS1.
Read-protection function FUN49 Use password protection function of
Item C200H-series CS1-series Description
Write the interrupt program in subroutine.
Write the interrupt program in interrupt task.
If the system operation is affected bycycle time, check the operation with the converted program.
CX-Programmer.
Use DI (DISABLE INTERRUPTS) instruction and EI (ENABLE INTERRUPTS) instruction when simultaneity of data is required between the Cycle Tasks and Interrupt Tasks.
For CS1, an Interrupt Task is executed even when an instruction is being executed or I/O refreshing. To obtain the same cycle time as C200H, set the time from the "Constant Cycle Time" in the PLC settings
Appendix E. Table of Input/Output Units
- Input Unit
(1)If different terminal block or connector is used, you have to change the wiring.
(2)If the input circuit specification is not the same, check if there is no problem in operation.
(3)If the number of circuit is different (increased), wire and connect the terminals and each common terminals.
(4)If the current consumption is different, check if enough power supply capacity is provided.
(5)C200H-series Units can be used with CS1-series CPU Units.
(6)Refer to related manuals for details, even if functions of C200H-series are supported by CS1-series Units,
since a part of specifications may differ.
DC Input Unit
C200H-series Unit Corresponding CS-series Unit Description Difference
DC Input Unit with terminal block for 8 inputs Replace this unit with a DC Input Unit with 16 inputs.
DC Input Unit with terminal block for 16 inputs.
DC Input Unit with connector for 32 inputs.
DC Input Unit with connector for 32 inputs.
DC Input Unit with connector for 32 inputs.
DC Input Unit with connector for 64 inputs.
DC Input Unit with connector for 64 inputs.
DC Input Unit with connector for 64 inputs.
1)Terminal block
2)Input points (8 -> 16 points)
3)Input circuit specification Input voltage range (12 to 24 VDC -> 24VDC) Input impedance (2kΩ-> 3.3kΩ) ON Voltage(10.2VDC->14.4VDC) OFF Voltage(3VDC->5VDC)
4) Internal current consumption(5VDC: 10mA->100mA)
1) Terminal block
2) Number of circuit (16 points/common x1 circuit -> 8 points/common x2 circuits)
No replacement model TTL Input Unit with connector for 32 inputs. The CS-series does not have the
same type of Unit. Use the C200H-ID501 with CS1, or use 24VDC Input Unit (CS1W-ID231) or TTL Input/Output Unit (CS1W-MD561) instead.
<AC Input Unit>
C200H-series Unit Corresponding CS-series Unit Description Difference
C200H-IA121 CS1W-IA111
100-120VAC/10mA, and Terminal block, 8 inputs
C200H-IA221 CS1W-IA211
200-240VAC/10mA, and Terminal block, 8 inputs
C200H-IA122/IA122V CS1W-IA111
100-120VAC/10mA, Terminal block, 16 inputs, IA122V: Complying with EC Directive
C200H-IA222/IA222V CS1W-IA211
200-240VAC/10mA, Terminal block, 16 inputs, IA222V: Complying with EC Directive
100-120VAC/10mA, 100 to 120VDC/1.5mA, Terminal block, 16 inputs
200-240VAC/10mA, Terminal block, 16 inputs
100-120VAC/10mA, 100 to 120VDC/1.5mA, Terminal block, 16 inputs
200-240VAC/10mA, Terminal block, 16 inputs
100VAC Input Unit with terminal block for 8 inputs. Replace this unit with a 100VAC Input Unit with 16 inputs.
200VAC Input Unit with terminal block for 8 inputs. Replace this unit with a 200VAC Input Unit with 16 inputs. 100VAC Input Unit with terminal block for 16 inputs.
200VAC Input Unit with terminal block for 16 inputs.
1) Terminal block
2) Input points (8 -> 16 points)
3) Input circuit specification Input impedance (9.7kΩ/50Hz->10kΩ/50Hz)ON Voltage (60V->65V)
4) Internal current consumption (5VDC:10mA->110mA)
1) Terminal block
2) Input points (8 -> 16 points)
3) Internal current consumption (5VDC:10mA->110mA)
1)Terminal block
2)Number of circuit(16 points/common x1 circuit ->8 points/common x2 circuits)
3)Input circuit specification Input impedance (9.7kΩ/50Hz->10kΩ/50Hz)ON Voltage (60VAC->65VAC) Internal current consumption (5VDC:10mA->110mA)
1) Terminal block
2) Number of circuit (16 points/common x1 circuit ->8 points/common x2 circuits)
3)Internal current consumption(5VDC:10mA->110mA)
<AC/DC Input Unit>
C200H-series Unit Corresponding CS-series Unit Description Difference
C200H-IM211 CS1W-ID211
12-24 VAC/VDC , Terminal block, 8 inputs
C200H-IM212 CS1W-ID211
24 VAC/VDC , Terminal block, 16 inputs
24 VDC, 7mA, Terminal block, 16 inputs
24 VDC, 7mA, Terminal block, 16 inputs
AC/DC Input Unit with terminal block for 8 inputs. Replace this unit with a DC Input Unit with 16 inputs. *The CS-series does not have theAC/DC Input Unit. If this Unit is used with AC inputs, continue using this Unit or change the wiring for DC inputs
AC/DC Input Unit with terminal block for 16 inputs. Replace this unit with a DC Input Unit with 16 inputs. *The CS-series does not have the AC/DC Input Unit. If this Unit is used with AC inputs, continue using this Unit or change the wiring for DC inputs.
1) Terminal block
2) Input points (8 -> 16 points)
3) Input circuit specification Input voltage range(12 to 24 VAC/VDC->24VDC) Input impedance(2kΩ->3.3kΩ) ON Voltage (10.2VDC->14.4VDC) OFF Voltage (3VDC->5VDC) Internal current consumption (5VDC:10mA->100mA)
250 VAC or 120 VDC, 2 A max., terminal block, 8 outputs (Independent contacts)
250 VAC or 120 VDC, 2 A max., terminal block, 8 outputs (Independent contacts)
250 VAC or 120 VDC, 2 A max. , terminal block, 8 outputs (Independent contacts)
250 VAC or 120 VDC, 2 A max., terminal block, 16 outputs
250 VAC or 120 VDC, 2 A max., terminal block, 16 outputs
250 VAC or 120 VDC, 2 A max. 16 outputs
Relay Output Units with terminal block for 5 outputs (independent contacts). Replace this unit with a RelayOutput Unit with 8 outputs (independent contacts).
Relay Output Units with terminal block for 8 outputs (independent contacts).
Relay Output Units with terminal block for 8 outputs (independent contacts).
Relay Output Units with terminal block for 8 outputs. Replace this unit with a RelayOutput Unit with 16 outputs.
Relay Output Units with terminal block for 12 outputs. Replace this unit with a RelayOutput Unit with 16 outputs.
Relay Output Units with terminal block for 12 outputs. Replace this unit with a RelayOutput Unit with 16 outputs.
0.5A/point, 8A/Unit) Voltage range(12 to 48 VDC-> 12 to 24VDC) Residual voltage(1.4V->1.5V) ON response time(0.2ms->0.5ms) OFF response time(0.3ms->1.0ms)
4) Internal current consumption(5VDC:140mA->170mA)
Transistor Output Units with terminal block for 12 outputs. Replace this unit with a Transistor Output Unit with 16 outputs.
Transistor Output Units with terminal block for 16 outputs.
Transistor Output Units with terminal block for 16 outputs.
Transistor Output Units with connector for 32 outputs.
Transistor Output Units with connector for 32 outputs. *The CS-series does not have Unit which supports Dynamic Output. Continue using this C200H Unit or change the wiring for static mode.
Transistor Output Units with connector for 32 outputs.
1) Terminal block
2) Output points (12-> 16 points)
3) Number of circuit (12 points/common x1 circuit ->8 points/common x2 circuits)
4) Output circuit specification Output voltage range (5 to 24 VDC -> 24VDC)
5) Internal current consumption (5VDC:10mA->170mA, 26VDC:75mA-> 0mA)
6) External power supply (Not required -> 24VDC:40mA)
1) Terminal block
2) Number of circuit (16 points/common x1 circuit ->8 points/common x2 circuits)
3) Output circuit specification Residual voltage (1.4V->1.5V) ON response time(0.2ms->0.5ms) OFF response time(0.3ms->1.0ms)
1) Terminal block
2) Number of circuit (16 points/common x1 circuit ->8 points/common x2 circuits)
0.5A/point, 5A/Unit) Residual voltage (0.8V->1.5V) ON response time (0.1ms->0.5ms) OFF response time (0.3ms->1ms)
4) Internal current consumption (5VDC:160mA-> 170mA)
5) External power supply (24 VDC: 35mA-> 40mA)
6) Alarm output (Supported -> Not supported)
1) Number of circuit (32 points/common x1 circuit ->16 points/common x2 circuits)
2) Output circuit specification Output voltage range (5 to 24 VDC-> 12 to 24VDC) Residual voltage (0.8V->1.5V) ON response time (0.1ms->0.5ms) OFF response time(0.4ms->1ms)
3) Internal current consumption(DC5V:180mA->270mA)
4) External power supply (5 to 24 VDC:110mA -> 12 to 24VDC:50mA)
1) Connector
2) Output method (Dynamic or Static mode
-> Static only)The specification of static is as follows.
3) Number of circuit (8 points/common x 4 circuits ->16 points/common x2 circuits)
4) Output circuit specification Output voltage range(5 to 24 VDC -> 12 to 24VDC) Residual voltage (0.7V->1.5V) ON response time (0.2ms->0.5ms) OFF response time (0.6ms->1ms)
5) Internal current consumption (5VDC:220mA->270mA)
6) External power supply (5 to 24 VDC:90mA -> 12 to 24VDC:50mA)
1) Number of circuit (32 points/common x1 circuit ->16 points/common x2 circuits)
0.5A/point, 2.5A/Common, 5A/Unit) Residual voltage (0.8V->1.5V) ON response time (0.1ms->0.5ms) OFF response time (0.3ms->1ms)
3) Internal current consumption (5VDC:180mA -> 270mA)
<Transistor Output Units>
C200H-series Unit Corresponding CS-series Unit Description Difference
C200H-OD219 CS1W-OD261
4.5 to 26.3 VDC, Sinking,
0.1A, Connector, 64 outputs (Group2)
12-24 VDC, 0.3A, Sinking, Connector, 64 outputs
Transistor Output Units with connector for 64 outputs..
1) Number of circuit (32 points/common x2 circuit ->16 points/common x4 circuits)
2) Output circuit specification Output voltage range (5 to 24 VDC-> 12 to 24VDC) Residual voltage (0.8V->1.5V) ON response time (0.1ms->0.5ms) OFF response time(0.4ms->1ms)
3) Internal current consumption (5VDC:270mA->390mA)
<TTL Output Unit>
C200H-series Unit Corresponding CS-series Unit Description Difference
C200H-OD501
5 VDC, 35A, Connector, 32 outputs (Special I/O)
No replacement model
TTL Output Unit with connector for 32 outputs. The CS-series does not have the same type of Unit. Continue using this Unit or use Transistor Output Unit (CS1W-OD231) or TTL Input/Output Unit (CS1W-MD561) instead.
<Triac Output Unit>
C200H-series Unit Corresponding CS-series Unit Description Difference
C200H-OA223 CS1W-OA201
250VAC, 1.2A, Terminal block, 8 outputs
C200H-OA221 CS1W-OA201
250VAC, 1.2A, Terminal block, 8 outputs
C200H-OA224 CS1W-OA211
0.5 A 250 V AC,0.5A, Terminal block, 12 outputs
C200H-OA222V CS1W-OA211
250 V AC, 0.3A, Terminal block, 12 outputs (CE)
250VAC, 1.2A, Terminal block, 8 outputs
250VAC, 1.2A, Terminal block, 8 outputs
0.5 A 250 V AC, 0.5A, Terminal block, 16 outputs
0.5 A 250 V AC, 0.5A, Terminal block, 16 outputs
Triac Output Units with terminal block for 8 outputs.
Triac Output Units with terminal block for 8 outputs.
Triac Output Units with terminal block for 12 outputs. Replace this unit with a Triac Output Unit with 16 outputs.
Triac Output Units with terminal block for 12 outputs. Replace this unit with a Triac Output Unit with 16 outputs.
1) Terminal block
2) Output circuit specification Max. Inrush Current (15A: Pulsewidth 100ms, 30A: Pulsewidth 10ms->10A: Pulsewidth 100ms and 20A: Pulsewidth 10ms)
3) Internal current consumption (5VDC:180mA->230mA)
1) Terminal block
2) Output circuit specification Max. Inrush Current (No regulation ->10A: Pulsewidth 100ms and 20A: Pulsewidth 10ms) Residual voltage (1.2VAC-> 50 to 1200mA:
1.5VAC 10 to 50mA: 5VAC) OFF response time (1/2 of load frequency or less -> 1/2 of load frequency+1 ms or less)
3) Internal current consumption (5VDC:140mA->230mA)
1) Terminal block
2) Output points (12 -> 16 points)
3) Number of circuit (12 points/common x1 circuit ->8 points/common x2 circuits)
4) Output circuit specification Max. Switching Capacity (0.5 A 250 V AC, 2 A/Unit-> 0.5 A 250 V AC, 2 A/common, 4 A/Unit) Max. Inrush Current (10A: pulse width: 100 ms, 20A: pulse width: 10 ms-> 15A: pulse width: 10ms) Min. Switching Capacity (10VAC: 100mA, 24VAC: 50mA, 100VAC: 10mA->75VAC: 50mA) Residual voltage (1.5 V AC max. (50 to 500 mA)/5 -> 1.6 VAC (10 to 50 mA)
5) Internal current consumption (5VDC:270mA->406mA)
1) Terminal block
2) Output points (12 -> 16 points)
3) Number of circuit (12 points/common x1 circuit ->8 points/common x2 circuits)
4) Output circuit specification Max. Inrush Current (No regulation ->15A: Pulsewidth 10ms) Min. Switching Capacity (VAC: 10 mA (resistive load)/40 mA (inductive load) ->75VAC:50mA Residual voltage(1.2VAC->1.6VAC) ON response time (1/2 of load frequency or less -> 1 ms or less)OFF response time (1/2 of load frequency or less-> 1/2 of load frequency+1 ms or less)
5) Internal current consumption (5VDC:200mA->406mA)
■Input/Output Units
(1) The CS-series has two Input/Output Units: CS1W-MD261 and MD561. The unit area allocation is different
from
C200H-series input/output units, since the number of input/output of CS-series unit is 32 points each.
(2) C200H-series Units can be used with CS1-series CPU Unit.
(3) Refer to related manuals for details, even if functions of C200H-series are supported by CS1-series Units, since
a part of specifications may differ.
<DC Input/Transistor Output Unit>
C200H-series Unit Corresponding CS-series Unit Description Difference
24VDC/16 inputs, 5 to 24VDC/16 outputs (Sinking), Connector (Special I/O)
No replacement model
No replacement model
Input/Output Unit with connector for 16 inputs/16 outputs. The CS-series does not have the same type of Unit. Use this Unit with CS1, or use CS1W-MD261 or MD561 instead.
Input/Output Unit with connector for 16 inputs/16 outputs. The CS-series does not have the same type of Unit. Use this Unit with CS1, or use CS1W-MD261 or MD561 instead.
<TTL Input/Output Units>
C200H-series Unit Corresponding CS-series Unit Description Difference
Input/Output Unit with connector for 16 inputs/16 outputs. The CS-series does not have the same type of Unit. Use this Unit with CS1, or use CS1W-MD261 or MD561 instead.
2010-2011
P069-E1-03
0611(1210)
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.