Omron 61F-GP-N8, 61F-GP-N8L 2KM, 61F-GP-N8L 4KM, 61F-GP-N8H, 61F-GP-N8D DATASHEET

...
Conductive Level Controller
61F-GP-N8
Compact Plug-in Level Controllers for Single or Two-point Level Control of Conductive Materials (Liquids and Solids)
• 24/100/110/120/200/220/230/240 VAC operation possible.
• Easy installation on DIN track.
• Low-voltage (AC) electrodes.
• Red LED operation indicator provided.
• Conforms to EMC and LVD Directives.
• UL/CSA approved.
Model Number Structure
Model Number Legend
61F-GP-N8@
1 2 3
1. Plug-in Type
2. Compact 8-pin Type
Level
Controllers
3. Applications
None: General-purpose type L: Long-distance type H: High-sensitivity type (reverse acting) HY: High-sensitivity type (standard acting) D: Low-sensitivity type R: Two-wired type
Ordering Information
List of Models
Application Model number
General-purpose type 61F-GP-N8 Long-distance type 2 km 61F-GP-N8L 2KM
4 km 61F-GP-N8L 4KM High-sensitivity type 61F-GP-N8H Low-sensitivity type 61F-GP-N8D Two-wired type 61F-GP-N8R
Conductive Level Controller 61F-GP-N8 E-5
Accessories (Order Separately)
Selection Guide for Electrode Holders and Separators
Electrode Holders
Applications For city water and other
Mounting style Flange Screw Flange Screw Insulator material Phenol resin Phenol resin Ceramics Teflon Max. temperature 70°C150°C (without water drips or vapor on the
No. of electrodes
general-use electrodes. Easy-to-replace sepa­rate versions facilitate maintenance of elec­trodes.
1 --- --- BF-1 BS-1 3 PS-3S PS-31 --- ---
When mounting space is limited. Special 3-pole holder of small size and light weight. Ideal for soft drink vendors, etc., where only limited space is avail­able.
For low specific liquids. Used for sewage, sea water, etc., having a low specific resis­tance. In sewage use, electrode holders must be installed 10 to 20 cm apart from one another. For acids, alkalis and sea wa­ter, electrode holders may be as much as 1 meter apart to operate properly.
surface of the electrode holder)
When resistance to high pressure is required. Ide­al for use in tanks where temperature or pressure inside the tank is high, e.g. 250°C
250°C (without water drips or vapor on the sur­face of the electrode holder)
Electrode Separators
No. of electrodes Model
1 F03-14 1P 3 F03-14 3P
Selection Guide for Electrodes, Connecting, and Lock Nuts
Applicable liquids Material Models for individual electrode assembly components
Electrode (1m long) Connecting nut Lock nut
Purified city water, industrial water, sewage
Purified city water, industrial water, sewage, dilute alkaline solution
Equivalent to SUS 304 (AISI-304)
SUS316 (AISI-316)
Model Indication
F03-01 SUS201 1 line F03-02 SUS201 --- F03-03 SUS201 ---
F03-01 SUS316 2 lines F03-02 SUS316 6 F03-03 SUS316 316
mark
Model Inscription Model Inscription
E-6 Conductive Level Controller 61F-GP-N8
Specifications
Ratings and Characteristics
Model/Items General-purpose
Controlling materials and operating conditions
Supply voltage 24, 100, 110, 120, 200, 220, 230 or 240 VAC; 50/60 Hz Operating voltage range 85% to 110% of rated voltage Interelectrode voltage 8 VAC 24 VAC 8 VAC Interelectrode current Approx. 1 mA AC max. Approx.
Power consumption Approx. 3.5 VA max. Interelectrode operate
resistance
Interelectrode release resistance
Response time Operate: 80 ms max.
Cable length (see note 2)
Control output 1 A, 250 VAC (Inductive load: cosφ = 0.4)
Ambient temperature Operating: 10°C to 55°C Ambient humidity Operating: 45% to 85% RH Insulation resistance
(see note 3) Dielectric strength
(see note 4) Life expectancy Electrical: 100,000 operations min.
Note: 1. The relay in the 61F-GP-N8H de-energizes when there is water present across the electrodes, whereas the relay in the 61F-GP-N8HY
energizes when there is water present across the electrodes.
2. The length when using completely-insulated, 600-V, 3-conductor (0.75 mm
as the cable diameter or number of conductors becomes larger.
3. The insulation resistance and dielectric strength indicate values between power terminals and electrode terminals, between power ter-
minals and contact terminals, and between electrode terminals and contact terminals.
4. Possible to use with 10 k or less, however, this may cause reset failure.
Controller
61F-GP-N8
For control of ordinary purified water or sew­age water
Approx. 0 to 4 k Approx. 0 to 1.3 k
Approx. 15 k to ∞Ω Approx. 4 k to ∞Ω (for
Release: 160 ms max. 1 km max. 2 km max.
3 A, 250 VAC (Resistive load)
100 M max. (at 500 VDC)
2000 VAC, 50/60 Hz for 1 min.
Mechanical: 5,000,000 operations min.
Long-distance
Controllers
61F-GP-N8L 2KM
(for 2 km)
61F-GP-N8L 4KM
(for 4 km)
For control of ordinary purified water in cas­es where the distance between sewage pumps and water tanks or between re­ceiver tanks and sup­ply tanks is long or where remote control is required.
(for 2 km) Approx. 0 to 0.5 k (for 4 km)
2 km) Approx. 2.5 k to ∞Ω (for 4 km)
4 km max.
High-sensitivity
Controllers
61F-GP-N8H
61F-GP-N8HY
(see note 1)
For control of liquids with high specific re­sistance such as dis­tilled water
0.4 mA AC max.
Approx. 15 k to 70 k (see note 3)
Approx. 300 k to ∞Ω Approx. 4 k to ∞Ω Approx. 15 k to ∞Ω
50 m max. 1 km max. 800 m max.
2
) cabtyre cables. Usable cable lengths will become shorter
Low-sensitivity
Controller
61F-GP-N8D
For control of liquids with low specific re­sistance such as salt water, sewage water, acid chemicals, alkali chemicals
Approx. 1 mA AC max.
Approx. 0 to 1.3 k Approx. 0 to 2 k
Two-wired Controller
61F-GP-N8R
For control of ordinary purified water or sew­age water used in combination with two­wired-type electrode holder (incorporating a resistor of 6.8 kΩ)
Level
Controllers
Conductive Level Controller 61F-GP-N8 E-7
Loading...
+ 7 hidden pages