Omicron CP TD1 Reference Manual

Page 1
CP TD1
Reference Manual
Page 2
CP TD1 Reference Manual V 1.44
Article Number: VESD0606 Manual Version: CPC100TD1.AE.6
© OMICRON electronics 2012. All rights reserved.
This manual is a publication of OMICRON electronics GmbH.
All rights including translation reserved. Reproduction of any kind, for example, photocopying, microfilming, optical character recognition and/or storage in electronic data processing systems, requires the explicit consent of OMICRON electronics. Reprinting, wholly or in part, is not permitted.
The product information, specifications, and technical data embodied in this manual represent the technical status at the time of writing and are subject to change without prior notice.
We have done our best to ensure that the information given in this manual is useful, accurate and entirely reliable. However, OMICRON electronics does not assume responsibility for any inaccuracies which may be present.
The user is responsible for every application that makes use of an OMICRON product.
OMICRON electronics translates this manual from the source language English into a number of other languages. Any translation of this manual is done for local requirements, and in the event of a dispute between the English and a non-English version, the English version of this manual shall govern.
2
Page 3

Contents

Contents
Using this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Safety Rules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
1.1 Designated Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
1.2 Functional Components of the CPC 100 and CP TD1. . . . . . . . . . . . . . . . . . . . 16
1.3 Functional Components of the CP TD1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
1.3.1 Grounding Terminal and Booster Input. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
1.3.2 Serial Interface Connector and Measuring Inputs . . . . . . . . . . . . . . . . . . . . . . 18
1.3.3 High-Voltage Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
2 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
2.1 Measurement Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
2.1.1 Setup of Devices with Trolley . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
2.1.2 Setup of Devices without Trolley . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
2.2 CP TD1 Connected to a Test Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
2.3 CP TD1 Connected to CP CAL1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
2.4 Calibrating the CP TD1 Using a Reference Capacitor. . . . . . . . . . . . . . . . . . . . 23
2.4.1 Calibration Tips. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
3 Test Cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
3.1 TanDelta Test Card - Main Page (1/2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
3.2 TanDelta Test Card - Main Page (2/2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
3.3 TanDelta Test Card - Settings Page (1/2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
3.4 TanDelta Test Card - Settings Page (2/2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
3.5 Templates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
4 Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
4.1 Preparations in Substation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
4.2 Connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
4.3 Measurement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
4.4 Disconnection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
5 Capacitance and Dissipation Factor Measurement . . . . . . . . . . . . . . . . . .39
5.1 Theory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
3
Page 4
CP TD1 Reference Manual V 1.44
5.2 Measurement of Capacitance and Dissipation Factor / Power Factor. . . . . . . . 54
5.3 "UST" and "GST" Measurements Using the Guard Technology . . . . . . . . . . . . 58
5.4 References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
6 Power Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65
6.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
6.2 Capacitance and DF Measurement of Transformer Windings. . . . . . . . . . . . . . 70
6.2.1 Three-Winding Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
6.2.2 Two-Winding Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
6.2.3 Auto-Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
6.2.4 Reactors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
6.3 Transformer High-Voltage Bushing Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
6.4 Interpretation of Measurement Results . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
6.4.1 Dissipation Factor Measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
6.4.2 Capacitance Measurement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
6.5 References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
7 Capacitance and DF Measurement on High-Voltage Bushings. . . . . . . . .91
7.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
7.2 Types of Bushings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
7.3 Bushing Troubles. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
7.4 Capacitance and DF Measurement on High-Voltage Bushings. . . . . . . . . . . . . 96
7.5 Ungrounded Specimen Test (UST) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
7.6 Grounded Specimen Test (GST) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
7.7 Hot Collar Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
7.8 Interpretation of Measurement Results . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
7.9 References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
8 Capacitance and DF Measurement of Generators and Motors . . . . . . . .109
9 Capacitance and DF Measurement of Circuit Breakers . . . . . . . . . . . . . .111
9.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
9.2 Oil Circuit Breakers (Dead Tank). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
9.3 Oil Poor Circuit Breakers (Live Tank) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
9.4 SF6 Circuit Breakers (Dead Tank with Bushings) . . . . . . . . . . . . . . . . . . . . . . 112
9.5 Vacuum Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
9.6 Air Magnetic Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
9.7 Oil Circuit Reclosers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
4
Page 5
Contents
10 Capacitance and DF Measurement of Overvoltage Arresters . . . . . . . . .115
11 Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .119
11.1 Technical Data of the CP TD1 in Combination with the CPC 100 . . . . . . . . . . 119
11.1.1 High-Voltage Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
11.1.2 Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
11.2 Environmental Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
11.3 CE Conformity and Safety Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
11.4 Cleaning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
11.5 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
11.5.1 Cables and Clamps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
11.5.2 Optional Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
11.6 Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
12 Appendix. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .129
12.1 Parallel and Serial Equivalent Circuit Diagrams . . . . . . . . . . . . . . . . . . . . . . . 129
12.2 Negative DF Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
12.3 Two- and Three-Winding Transformer Tests (IEEE C57.12.90) . . . . . . . . . . . 132
12.4 Limits for Test Voltages for C2 Testing on Bushings. . . . . . . . . . . . . . . . . . . . 133
12.5 C2 Measurement on High-Voltage Bushings. . . . . . . . . . . . . . . . . . . . . . . . . . 133
12.5.1 Abstract. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
12.5.2 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
12.5.3 Design/Construction of C1 and C2 Capacitance in Condenser Bushings . . . 134
12.5.4 Factors Affecting C1, C2 Capacitance and Power Factor Measurements . . . 136
12.5.5 Conclusions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
12.5.6 Biography . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
12.5.7 References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
12.6 DF Limits of RBP Bushings (Micafil AG) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
12.7 DF Limits of Bushings (B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
12.8 DF Limits of Bushings (C) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
12.9 Transformer Diagnosis. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146
12.9.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
12.9.2 Methods of Analysis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
12.9.3 Fault Localization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
12.9.4 Winding Resistance Measurement and On-Load Tap Changer Test. . . . . . . 151
12.9.5 Four-Wire Connection for Transformer Winding Resistance Measurement. . 155
12.9.6 Safety Aspects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 156
12.9.7 Delta-Connected Windings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
5
Page 6
CP TD1 Reference Manual V 1.44
12.9.8 Winding Resistance Measurement of a 100 MVA Transformer . . . . . . . . . . . 158
12.9.9 Dynamic Behavior of the Diverter Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162
12.9.10 Turns Ratio . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
12.9.11 Excitation Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165
12.9.12 Leakage Reactance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166
12.9.13 Capacitance and DF Measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169
12.9.14 DF Measurements on Transformer Windings . . . . . . . . . . . . . . . . . . . . . . . . . 174
12.9.15 Capacitance Measurements on Transformer Windings . . . . . . . . . . . . . . . . . 175
12.9.16 Capacitance and DF Measurements on Transformer Bushings. . . . . . . . . . . 175
12.9.17 Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
12.10References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180
12.11Temperature Correction Factors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181
12.11.1 Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181
12.11.2 Bushings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182
OMICRON Service Centers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .185
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187
6
Page 7

Using this Manual

This User Manual provides information on how to use the CP TD1 safely, properly and efficiently. The CP TD1 Reference Manual contains important safety rules for working with the CP TD1 and gets you familiar with operating the CP TD1. Following the instructions in this Reference Manual will help you to prevent danger, repair costs and possible down time due to incorrect operation.
The CP TD1 Reference Manual always has to be available on the site where the CP TD1 is used. It must be read and observed by all users of the CP TD1.
Reading the CP TD1 Reference Manual alone does not release you from the duty of complying with all national and international safety regulations relevant to working on power transformers.

Operator Qualifications and Safety Standards

Working on high-voltage assets can be extremely dangerous. Testing with the CP TD1 must be carried out only by qualified, skilled and authorized personnel. Before starting to work, clearly establish the responsibilities.
Preface
Personnel receiving training, instructions, directions, or education on the CP TD1 must be under constant supervision of an experienced operator while working with the equipment.
Testing with the CP TD1 must comply with the internal safety instructions as well as additional relevant documents.
In addition, observe the following safety standards, if applicable:
• EN 50191 (VDE 0104) "Erection and Operation of Electrical Equipment"
• EN 50110-1 (VDE 0105 Part 100) "Operation of Electrical Installations"
• IEEE 510 "IEEE Recommended Practices for Safety in High-Voltage and High-Power Testing"
7
Page 8
CP TD1 Reference Manual V 1.44

Symbols Used

In this manual, the following symbols indicate paragraphs with special safety relevant meaning:
Symbol Description

General

Caution: Equipment damage or loss of data possible
Warning: Personal injury or death of the operating staff or
severe damage to objects possible
Always observe the five safety rules:
• Disconnect completely
• Secure from reconnection
• Verify that the installation is dead
• Carry out grounding and short-circuiting
• Provide protection against adjacent live parts
8
Page 9

Safety Rules

Before operating the CP TD1, read the following safety rules carefully. If you do not understand some safety rules, contact OMICRON electronics before proceeding.
Maintenance and repair of the CP TD1 is only permitted by qualified experts at OMICRON electronics repair centers.

Operating the Measurement Setup

Only personnel qualified in electrical engineering and trained by OMICRON electronics are authorized to operate the CP TD1. Before starting the work, clearly establish the responsibilities.
Personnel receiving training, instructions, directions, or education on the CP TD1 must be under constant supervision of an experienced operator while working with the equipment.
Preface
The operator is responsible for the safety requirements during the whole test.
Warning: Do not enter the high-voltage area if the red warning light of the CPC 100 is on since all outputs carry dangerous voltage or current! Always obey the five safety rules and follow the detailed safety instructions in the respective user manuals.
9
Page 10
CP TD1 Reference Manual V 1.44
Safe area High-voltage area
Figure 1-1 Example for the separation of safe and high-voltage area using
10
different OMICRON electronics devices
Page 11
Preface
Before performing tests using high voltage, observe the following instructions:
• Do not use the test equipment without a good connection to substation
ground.
• Do not insert objects (for example screwdrivers, etc.) into any input/output socket.
• Do not operate the CP TD1 under ambient conditions that exceed the temperature and humidity limits listed in 11.2 "Environmental Conditions" on page 123.
• Make sure to position the test equipment on dry, solid ground.
• Do not operate the CP TD1 in the presence of explosives, gas or vapors.
• Opening the CP TD1 invalidates all warranty claims.
• Do not use an extension cable on a cable reel to prevent an overheating of the cord; run out the extension cord.
• If the CP TD1 does not seem to function properly, do not use it anymore. Please call the OMICRON electronics technical support.

Handling Cables

• Always turn off the CP TD1 completely before you connect or disconnect any cable (disconnect the CPC 100 from mains or press its Emergency Stop button).
• The high-voltage cable must always be well attached and tightly connected to both the CP TD1 and the test object. A loose or even falling off connector at the test object carrying high-voltage is life-hazardous. Make sure the connectors are clean and dry before connecting.
At the CP TD1, press the high-voltage cable’s plug to the connector tightly and turn the screw cap until you feel a mechanical stop. If you notice a rough­running of the screw-cap, clean the screw thread and use a lubricant (vaseline recommended).
At the test object, insert the high-voltage cables’ plugs carefully until you feel a "click" position. Now they are locked. Confirm this by trying to pull them out. This should not be possible now.
Note: Tighten the plugs manually. Do not use any tools for that because that can damage the plugs or connectors.
Insert the yellow banana plug (the high-voltage cable’s grounding) into the respective plug socket.
11
Page 12
CP TD1 Reference Manual V 1.44
• Do not connect any cable to the test object without a visible grounding of the test object.
• The high-voltage cable is double-shielded and therefore safe. However, the last 50cm (20 inch) of this cable have no shield. Therefore, during a test consider this cable a life wire and due to the high-voltage life-hazardous!
Warning: When the CPC 100 is switched on, consider this part of the cable has to be in the high-voltage area due to a hazard of electric shock!
•Never remove any cables from the CP TD1 or the test object during a test.
• Keep clear from zones in which high voltages may occur. Set up a barrier or establish similar adequate means.
• Both low-voltage measuring cables must always be well attached and tightly connected to the CP TD1’s measuring inputs IN A and IN B.
Make sure to insert the red and blue marked cables into the corresponding measuring inputs: IN A = red, IN B = blue.
Tighten the plugs by turning them until you feel a stop. Note: Tighten the plugs manually. Do not use any tools for that because that
can damage the plugs or connectors.
Do not use any other cables than the ones supplied by OMICRON electronics.

Orderly Measures

The CP TD1 Reference Manual or alternatively the e-book in PDF format has always to be available on site where the CP TD1 is being used. It must be read and observed by all users of the CP TD1.
Warning: The CP TD1 may be used only as described in this Reference Manual. Any other use is not in accordance with the regulations.
The manufacturer and/or distributor is not liable for damage resulting from improper usage. The user alone assumes all responsibility and risk.
Following the instructions provided in this User Manual is also considered part of being in accordance with the regulations.
12
Page 13
Preface

Disclaimer

If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.

Static Charges

Static charges on bushings or other apparatus such as transformer windings may be induced by test potentials. While the voltage may not be significant enough to do any damage, it can be a source for serious accidents due to falls caused by reflex action.
High static charges may also be encountered at the bushing capacitance taps if the covers are removed. Also, you should use safety grounds before handling.
Note: Always observe the five safety rules!
13
Page 14
CP TD1 Reference Manual V 1.44
14
Page 15

1 Introduction

1.1 Designated Use

The CP TD1 is an optionally available high-precision test system for on-site insulation tests of high-voltage systems like power and measuring transformers, circuit breakers, capacitors and isolators. With the add-on device CP TD1, the CPC 100 increases its range of possible applications into high-voltage measurements.
The internal switched mode power amplifier enables measuring at different frequencies without interferences with the mains frequency. Automatic test procedures reduce the testing time to a minimum. Test reports are generated automatically.
The CP TD1 comes with its own test card named TanDelta (Tangent Delta), which provides highly accurate measurements of the capacitance Cx and the dissipation factor tanδ (DF) or power factor cos ϕ (PF), respectively.
Introduction
Both the dissipation factor and the power factor grant information about possible losses in the insulation material, which are increasing with age and water content. A change of Cx is a warning indicator for partial breakdowns between the layers of a bushing or a capacitor.
Additionally, the CP TD1 measures the following quantities:
• Actual, apparent and reactive power
• Quality factor QF
• Inductance
• Impedance, phase angle
• Test voltage & current
The CP TD1 works as an add-on device to the CPC 100. Do not connect the CP TD1 to any other device. Do not use the accessories for applications not indicated in this user manual.
Any other use of the CP TD1 but the one mentioned above is considered improper use, and will not only invalidate all customer warranty claims but also exempt the manufacturer from its liability to recourse.
15
Page 16
CP TD1 Reference Manual V 1.44
Cable drum with double-shielded output cable to feed the high voltage to the test object.
High-voltage output with attached screw plug and yellow grounding plug.
Equipment trolley
Booster cable
CPC 100
⇔ CP TD1
(short type). Via this cable CPC 100 controls the CP TD1 output voltage.
CPC 100
CPC 100, CP TD1
and the equipment trolley connected to the trolley’s grounding bar and led to earth.
Grounding cable min. 6mm².
CP TD1
Grounding terminal
Cable drum for measuring cables

1.2 Functional Components of the CPC 100 and CP TD1

16
Page 17
Introduction
CP TD1’s measuring inputs IN A and IN B, connected to the cable drum for the measuring cables.
Swivelling mounting brackets for the CPC 100 (top) and CP TD1 (bottom).
To secure the CPC 100 while pulling the trolley, a safety belt is available (not shown).
Data cable CPC 100 ⇔ CP TD1 (short type). Via this data cable, the CPC 100 software (test card TanDelta) controls the CP TD1.
17
Page 18
CP TD1 Reference Manual V 1.44
Booster Input
Grounding terminal
IN_A measuring input
IN_B measuring input
Serial interface connector

1.3 Functional Components of the CP TD1

1.3.1 Grounding Terminal and Booster Input

1.3.2 Serial Interface Connector and Measuring Inputs

Figure 1-2 Grounding terminal and booster input of the CP TD1
Figure 1-3 Serial interface and measuring inputs of the CP TD1
18
Page 19

1.3.3 High-Voltage Connector

High­voltage connector
Grounding terminal
Figure 1-4 High-voltage connector of the CP TD1
Introduction
19
Page 20
CP TD1 Reference Manual V 1.44
20
Page 21

2 Operation

2.1 Measurement Setup

2.1.1 Setup of Devices with Trolley

The equipment trolley holds the CPC 100, CP TD1 and all required cables. The trolley is equipped with a grounding bar with three knurled screws to ensure a solid connection to the grounding terminals of all devices.

2.1.2 Setup of Devices without Trolley

If the CPC 100 and CP TD1 are to be operated without trolley, place them on their transport cases and connect them with the long type data cable CPC 100 ⇔ CP TD1 (3m) and the long-type booster cable CPC 100 ⇔ CP TD1 (3m). Each device has to be grounded separately with a 6m grounding cable of at least 6mm
2
.
Operation
21
Page 22
CP TD1 Reference Manual V 1.44
CP TD1
CPC 100
IN
Ix
Measurement
PE
12 kV
IN A
IN B
Power transformer
Grounding terminal
Booster Serial
Safe area
HV area

2.2 CP TD1 Connected to a Test Object

22
Page 23

2.3 CP TD1 Connected to CP CAL1

CP TD1
CPC 100
Ix
Measurement
PE
Booster
12 kV
IN A
IN B
Grounding terminal
CP CAL1
Serial
C1
C2
C3
Safe area
HV area
Operation
Measuring mode = UST-A
When using the CP CAL1 for calibration, we recommend to take C1 as reference and to select the calibration frequency in a range between 50 ... 200Hz.

2.4 Calibrating the CP TD1 Using a Reference Capacitor

Warning: For using the CP CAL1, make sure to apply the same procedure as
described in this Reference Manual.
By connecting a reference capacitor (e.g., optional device CP CAL1) with known values of capacity Cref and dissipation factor DFref, in mode UST-A the values Cx and DFx can be measured and then compared to the known reference values.
23
Page 24
CP TD1 Reference Manual V 1.44
If you experience substantial deviations, re-calibrate the CP TD1:
• Cx = C ref / Cmeas and
•DF/PF+=DFref-DFmeas
as described in 3.3 on page 29.
A re-calibration of the CP TD1 is also shown in the test report (.xml file).
Note: If you change the factory-made calibration, the responsibility for the accuracy of the CP TD1 will be in your hands.

2.4.1 Calibration Tips

• For calibration set the averaging factor to maximum and the filter bandwidth
to ± 5Hz (refer to 3.1 ”TanDelta Test Card - Main Page (1/2)” on page 25).
• To reset to the factory settings, select "DF/PF+" to 0.0 ppm and "Cx" to 1.000
(refer to 3.3 ”TanDelta Test Card - Settings Page (1/2)” on page 29).
24
Page 25

3Test Cards

Select for automatic measurement, clear for manual measurement.
*)
.
Selecting enables the list boxes.
Select "Assessment" to automatically assess the test, clear for no assessment.
Enter the nominal values in the entry fields (here "Cref" and "DF ref"; availability and naming depend on the measuring mode). These values serve as reference for the assessment. Their tolerance range can be set on the Settings Page (refer to page 29).
A measurement is rated as ’OK’ if both values are within their tolerance range. The assessment is displayed in the test point tables’s column "?"
Note: While a test is running, new nominal values can already be entered.
Test voltage and frequency.
Selecting a measuring mode and pressing the handwheel displays an image that shows the according arrangement of the internal measurement switch-matrix.
**)
Results table.
Also refer to page 30.
*)

3.1 TanDelta Test Card - Main Page (1/2)

The test card TanDelta can be accessed from C T , V T, T RANSFORMER and O
THERS.
Test Cards
"Auto test points" cleared = manual measurement: Applies the set test
voltage and frequency to the CP TD1’s output. When the measurement is finished, its results are displayed in the results table.
25
Page 26
CP TD1 Reference Manual V 1.44
"Auto test points" selected = automatic measurement: Enables the output
of a series of test points, e.g., combining a series of voltage values with one fixed frequency value creates a voltage ramp. Combining a series of frequency values with one fixed voltage value creates a frequency ramp. Furthermore, a combination of both is possible.
– Set a test voltage and frequency of your choice, and press A
DD TO AUTO.
The values are entered into the list boxes.
– Set a second test voltage and/or frequency, and again press A
A
UTO. The value(s) is/are appended to the list.
DD TO
– Repeat this procedure as often as you need.
Note: You cannot enter the same value twice. Double entries are rejected. If you need identical test points for an increasing and a decreasing voltage ramp, set values very close to each other, e.g., 2000V and 2001V.
The CP TD1 then puts out the specified list of values as follows:
1. All voltages are issued in the exact order they were entered using the first frequency value of the list.
2. All voltages are issued once more in the exact order they were entered using the second frequency value of the list (if any).
3. ... and so forth.
Each combination is one individual measurement, and its result is displayed in the results table with an individual line.
To delete an entry from a list box, place the cursor on the value and press D
ELETE VALUE. Do delete all values from both list boxes, place the cursor on
"Auto test points (V, f)" and press D
ELETE LIST.
During the measurement, the list boxes display the current output values.
26
Page 27
Test Cards
**)
Measuring modes and their according arrangements of the internal switch-matrix in the CP TD1.
The switch-matrix determines what capacities are actually measured.
27
Page 28
CP TD1 Reference Manual V 1.44
The averaging factor determines the number of measurements. A factor of 3 means: the CP TD1 carries out 3 measurements whose results are then averaged. The higher the factor, the more accurate the measurement but the longer the measuring time.
Filter bandwidth of measurement.
Note: If the test frequency equals the default frequency (as set at O
PTIONS | DEVICE SETUP),
the filter bandwidth is always ± 5Hz, regardless of the set value. This even applies if the option "use default frequency of xx.xx Hz" is not specifically selected.
± 5Hz means that interferences at frequencies with an offset of
≥ ± 5Hz from the measuring frequency
will not affect the results.
The smaller the filter bandwidth, the longer the measuring time.
Compound measurement setting.
Cp, DF (tanδ) = parallel capacitance & dissipation factor
Cp, PF (cosϕ) = parallel capacitance & power factor
Cp, Ptest = parallel capacitance & power
Cp, P@10kV = parallel capacitance & power
linearly interpolated to 10 kV test voltage
Qtest, Stest = reactive & apparent power
Z = impedance with phase angle
Cp, Rp = parallel capacitance & parallel resistance
Ls, Rs = serial inductance & serial resistance
Cp, Q = parallel capacitance & quality factor
Ls, Q = series inductance & quality factor

3.2 TanDelta Test Card - Main Page (2/2)

28
Page 29

3.3 TanDelta Test Card - Settings Page (1/2)

At "Assessment Limits", set the tolerance of the Main Page’s nominal values for the assessment.
For the capacitance, the tolerance is entered in percent, for the dissipation factor it’s a multiplier.
Note: Availability and naming of the entry fields depend on the measuring mode, e.g., DF and PF are the same entry field.
The CP TD1 leaves OMICRON factory-calibrated. If a component needs to be exchanged by a spare part, the CP TD1 must be re-calibrated.
To re-calibrate, set the focus onto the test card tab designation TanDelta and press E
DIT CALIB to enable
the entry fields:
• Cx = correction factor for Cmeas (multiplier)
• DF/PF + = corrective value added to dissipation or power factor (can be + or -).
Note: You must enter your name and press U
PDATE
C
ALIB. to complete the re-
calibration.
If selected, the beeper sounds during the entire test to signal the output of hazardous high voltages. If cleared, the beeper sounds at the beginning and the end of the test only.
If selected, the CPC 100 checks whether the shield of the high-voltage cable is connected. For some large inductive loads, the CPC 100 can accidentally report shield check error even when the shield is connected. If this is the case, it makes sense to clear the check box.
The TanDelta Settings page allows for the setting of additional measurement options. To open it, press the S
ETTINGS button on the TanDelta Main Page.
Test Cards
Warning: Never operate the CP TD1 with unconnected shield of the high-
voltage cable. If the "Perform shield check" check box is cleared, make sure that the shield is connected before operating the CP TD1.
29
Page 30
CP TD1 Reference Manual V 1.44
Selecting "Compensations" converts the actually measured dissipation or power factor to normalized values corresponding to an ambient temperature of 20°C. In doing so, the values entered at "Compensations" represent the existing ambient condition.
– Enter oil temperature, ambient temperature (at bushing) and relative
humidity first.
– Then place the cursor on "k". The medium the measurement takes place in, oil or air, determines the k-factor.
– ANSI C57.12
The oil temperature is the determining medium for the k-factor.
– Bushings
The air temperature at the respective bushing is the determining medium for the k-factor. B
USHINGS provides three bushing types to select from: RBP
(Resin Bonded Paper), RIP (Resin Impregnated Paper) and OIP (Oil Impregnated Paper). The k-factor changes accordingly.
Select if you use an external CT.
The entered ratio is used to calculate the measured current accordingly.
Note: "Use ext. CT" can only be selected if there are no measurement results yet.
Returns to TanDelta’s Main Page

3.4 TanDelta Test Card - Settings Page (2/2)

30
Page 31

3.5 Templates

The test procedures for designated applications are controlled by templates available on the CPC Toolsets shipped with your CP TD1 or on the CPC 100 Start Page.
The templates are pairs of XML documents and Microsoft Excel templates designed by OMICRON electronics for designated applications. The XML templates are predefined test procedures, often with comments, that run on the CPC 100 and guide your through the test. Once completed, the XML file is saved, downloaded to the PC and then loaded into the corresponding Microsoft Excel template. There the results are post-processed and a final test report is generated. The template pairs facilitate and speed testing with the CP TD1 and the evaluation of results.
To perform a test using a template, open the template for your application and run the test procedure according to the template.
Test Cards
31
Page 32
CP TD1 Reference Manual V 1.44
32
Page 33

4Application

4.1 Preparations in Substation

Warning: Prior to connecting a test object to the CP TD1, the following steps
need to be carried out by an authorized employee of the utility.
• Turn off and disconnect the high voltage from the test object.
• Protect yourself and your working environment against an accidental re­connection of high voltage by other persons and circumstances.
• Verify a safe isolation of the test object.
Warning: Earth-connect and shorten out the test object’s terminals using a grounding set.
Application
• Protect yourself and your working environment with a suitable protection against other (possibly live) circuits.
• Protect others from accessing the dangerous area and accidentally touching live parts by setting up a suitable barrier and, if applicable, warning lights.
• If there is a longer distance between the location of the CP TD1 and the area of danger (that is, the test object), a second person with an additional "Emergency Stop" button is required.

4.2 Connection

Warning: Make sure to position the test object or CP CAL in the high-voltage
area.
Warning: Never use the CP TD1 without a solid connection to ground with at least 6 mm². Use a ground point as close as possible to the test object.
1. Without trolley:
Properly connect the CPC 100 and CP TD1 grounding terminals to substation ground.
33
Page 34
CP TD1 Reference Manual V 1.44
Connect the CPC 100 grounding terminal to substation ground.
With trolley (optional): Properly connect the CPC 100 and CP TD1 grounding terminals to the trolley’s ground bar. Connect the ground bar to earth.
2. Switch off the CPC 100 at the mains power switch.
3. Connect the CP TD1’s "BOOSTER IN" to the CPC 100’s "EXT. BOOSTER"
with the booster cable.
4. Connect the CP TD1’s "SERIAL" to CPC 100’s "SERIAL" with the data
cable. This cable also provides the power supply for the CP TD1.
5. Make sure that all cable connectors are clean and dry before being tightly
connected.
6. Pull out the measuring cables from the cable drum and connect the test
object to the CP TD1’s measuring inputs IN A and IN B.
7. Connect the high-voltage cable from the test object to the CP TD1’s high-
voltage output.
•At the CP TD1, press the high-voltage cable’s plug to the connector tightly
and turn the screw cap manually without using any tools until you feel a mechanical stop. If you notice a rough-running of the screw-cap, clean the screw thread and use a lubricant (vaseline recommended).
• Insert the yellow banana plug (the high-voltage cable’s grounding) into the
respective plug socket.
• At the test object, insert the high-voltage cable’s plug carefully until you feel
a "click" position. Now they are locked. Confirm this by trying to pull them out. This should not be possible now.
• The high-voltage cable is double-shielded and therefore safe. However, the
last 50 cm (20 inch) of this cable have no shield. Therefore, during a test consider this cable a life wire and due to the high-voltage life-hazardous!
8. Connect the CPC 100 to the mains power supply using the provided cable.
34
Page 35
Application
9. Remove the grounding set from the test object.
Warning: Establish a barrier to the high-voltage area.
10.Turn on the CPC 100 at its mains power switch at the left-hand side.
11. An error message (313) appears if there is no ground connection, neither via
PE (protective earth wire of the power supply) nor via grounding terminal or the power supply has no galvanic connection to ground. The latter is the case on very special power supplies like with diesel generators or when insulation transformers are used.
Warning: This is a safety-relevant message. If the reason for this message is that neither PE nor grounding terminal is connected, it can cause injury or possibly death of the operating staff. For safe operation always make sure that both PE and grounding terminal are connected.
12. If the PE and grounding terminal connection are intact and the error
message still appears, select the "Disable ground check" check box at the
Device Setup tab in the Options view.
Note: After the CPC 100 has been rebooted, the "Disable ground check" check
box is cleared for safety reasons.
13. The green warning light "O" lights up, showing that the CPC 100 output does
not carry a dangerous voltage or current yet.
Note: If none or both warning lights are on, the unit is defective and must not be used anymore.

4.3 Measurement

1. Set up your test in the CPC 100 software.
For a detailed description of how to use the software refer to respective section in the CPC 100 Reference Manual.
2. Selecting the TanDelta - PF test card from the CPC 100’s menu
automatically turns on the CP TD1. If no CP TD1 is connected to the CPC 100, an error message occurs.
3. Set up your measurement in the TanDelta - PF test card (see 3.1 on
page 25).
35
Page 36
CP TD1 Reference Manual V 1.44
4. Once all test cards are prepared and the parameters set, make sure the safety key lock is in position "release" (horizontal).
Warning: If you have a cardiac pacemaker, do not use the CP TD1! Before operating the CP TD1, make sure there is no person with a cardiac pacemaker in the immediate vicinity.
Warning: Never touch any metallic terminals and / housing components without a visible ground connection!
5. Start the test by pressing the green I/ O (test start/stop) push-button on the CPC 100 front panel.
Note: • A test can only be started in the Test Card View and
with all preconditions met (refer to the CPC 100 Reference Manual).
• If voltages I/O (test start/stop) push-button for the first time a warning message appears on the screen.
≥ 1 kV are to be applied, after pressing the
6. If a potentially hazardous voltage and/ or current level is applied to the CPC 100 outputs, the red signal red light "I" starts flashing.

4.4 Disconnection

1. Switch off the high voltage with the I/O (test start/stop) push-button.
Note: Even if you switched off the CPC 100, wait until the red I / O warning light is fully extinguished. As long as this warning light is lit, there is still voltage potential on the output. The green warning light indicates that the CPC 100 outputs are not activated.
2. Press the Emergency Stop button on the CPC 100 front panel.
Only after the I/O push-button is pressed a second time, the voltage is applied to the CPC 100 output.
Rather than starting a test and activating the outputs, pressing the I/O (test start/stop) push-button will then pop up a message box notifying you about this problem.
36
Page 37
Application
3. Turn the safety key to "lock" (vertical) and remove the key to avoid anybody accidentally turning on the high voltage.
Warning: Earth-connect and shorten out the test object’s terminals using a grounding set.
4. Plug off the high-voltage cable from the high-voltage output of the CP TD1.
5. Disconnect the cables from the CP TD1.
37
Page 38
CP TD1 Reference Manual V 1.44
38
Page 39

Capacitance and Dissipation Factor Measurement

5 Capacitance and Dissipation Factor
Measurement
Capacitance (C) and Dissipation Factor (DF) measurement is an established and important insulation diagnosis method. It can detect:
• Insulation failures
• Aging of insulation
• Contamination of insulation liquids with particles
• Water in solid and liquid insulation
• Partial discharges

5.1 Theory

In an ideal capacitor without any dielectric losses, the insulation current is exactly 90° leading according to the applied voltage. For a real insulation with dielectric losses this angle is less than 90°. The angle angle. In a simplified diagram of the insulation, C
δ = 90° - ϕ is called loss
represents the loss-free
p
39
Page 40
CP TD1 Reference Manual V 1.44
I
CP
U C
P
I
RP
R
P
I
capacitance and R serial equivalent circuit diagram with C
the losses (Figure 5-1). Losses can also be represented by
p
and Rs (chapter 12.1). The definition of
s
the dissipation factor and the vector diagram are shown in Figure 5-2.
Figure 5-1 Simplified circuit diagram of a capacitor
40
Page 41
Capacitance and Dissipation Factor Measurement
R
e
I
Rp
U
I
Cp
I
j
Im
δ
δtan
1
R
P
ω C
P
------------------=
Figure 5-2 Definition of dissipation factor (tan
δ) and the vector diagram
41
Page 42
CP TD1 Reference Manual V 1.44
I
m
I
CN
I
CX
δ
U
O
R
e
Withδ 1
δδϕcosδ≅tan≅
«
π
2
-- - ϕ–=
PF
DF
1 DF
2
+
------------------------=
DF
PF
1 PF
2
–
-----------------------=
The correlation between the Dissipation Factor and Power Factor (PF = cos and the vector diagram are shown in Figure 5-3.
Figure 5-3 Correlation between DF and PF
ϕ)
42
Page 43
Capacitance and Dissipation Factor Measurement
Kind of polarization
Suspension Rotation
Electrons Ions Dipoles completely
reversible partly reversible
partly irreversible
All Material Glass Water
Porcelain Polar Plastics Salt Polar Ceramics
The dielectric losses in the insulation are caused by:
• movement of conductive particles
• movement of ions and electrons
• polarization effects (Figure 5-4)
Figure 5-4 Kind of polarization
43
Page 44
CP TD1 Reference Manual V 1.44
Way of electrons
without E with E
core
core
without E
with E
Polarization losses are generated due to suspension and rotation effects. Suspension of electrons is completely reversible. Figure 5-5 shows this mechanism. This kind of polarization is also called "Atom Polarization".
Figure 5-5 Polarization of electrons in the electrical field
Figure 5-6 Polarization of ions in the electrical field
44
Page 45
Capacitance and Dissipation Factor Measurement
without E with E
Figure 5-7 Polarization of dipoles in the electrical field
45
Page 46
CP TD1 Reference Manual V 1.44
E
H
+
H
+
O
2-
A typical dipole is a water molecule. Figure 5-8 shows such a molecule in the electrical field. When the electrical field changes the polarity, the orientation of the water molecule is changed by 180°. This rotation, along with the applied frequency, causes the described losses.
Figure 5-8 Water molecule in the electrical field
Additional losses are known as interfacial polarization. Inter-phase boundaries (e.g., between solid and liquid insulation material) may be charged, i.e., the electrical field moves the charge carriers in the oil; the charge carriers come to rest upon the boundary to the solid insulation material and create a space
46
Page 47
Capacitance and Dissipation Factor Measurement
E
+—
ε 2
γ 2
ε 1 γ 1
charge region. These space charge regions are moved back and forth through the field. This effect, for example, occurs on the interface between transformer oil and solid insulation like paper or transformer board (Figure 5-9).
Figure 5-9 Interfacial polarization
47
Page 48
CP TD1 Reference Manual V 1.44
kV/cm
600
500
400
300
200
100
0
60
50
40
30
20
10
0
Breakdown voltage
Dissipation factor
0 20 40 60 80 100 120 140 160 180 200
Water content mg/kg
tan δ
ε
d
0
/
00
Influence of different parameters like water content, temperature and aging on DF
Figure 5-10 shows the breakdown voltage and the DF in oil, dependent on the water content [2.3]. With low water content, the breakdown voltage is very sensitive; with higher water content, the DF is a good indicator.
Figure 5-10 Breakdown voltage and DF in oil, dependent on the water
content
48
Page 49
Capacitance and Dissipation Factor Measurement
0
/
00
tan δ
10
4
10
3
10
2
10
1
1
-30 -20 -10 0 10 20 30 40 50 60 70 80 90 100 °C Oil temperature
1
2
3
4
Figure 5-11 shows the DF of new and used oil, dependent on the temperature. With higher temperatures, the viscosity of the oil decreases so the particles, ions and electrons can move easier and faster. Thus the DF increases with temperature [2.3].
Figure 5-11 DF of new and aged oil, dependent on temperature
Dissipation Factor: Dependency of the temperature 1 = new oil 2, 3 and 4 = used oil
49
Page 50
CP TD1 Reference Manual V 1.44
F
p20
F
pt
K
-------=
Figure 5-12 and table 5-1 show a temperature correction factor (according to ANSI 57.12.90) for insulation based on mineral oil [2.4].
Figure 5-12 Temperature correction factor for mineral oil insulation [2.4]
where
F
is the power factor corrected to 20°C
p20
F
is the power factor measured at T
pt
T is the test temperature (°C) K is the correction factor
Table 5-1 Temperature correction factor for mineral oil insulation [2.4]
Test temperature T (°C) Correction Factor K
10 0.80 15 0.90 20 1.00 25 1.12 30 1.25 35 1.40 40 1.55 45 1.75 50 1.95
50
Page 51
Capacitance and Dissipation Factor Measurement
0
/
00
1
0.1
0.01
Specific volume resistance ρ
10
14
10
13
10
12
020 406080°C
rr
tan δ
2
1
1,2
Table 5-1 Temperature correction factor for mineral oil insulation [2.4]
Test temperature T (°C) Correction Factor K
55 2.18 60 2.42 65 2.70 70 3.00
Note: The correction factors listed above base on insulated systems using mineral oil as an insulating liquid. Other insulating liquids may have different correction factors.
Figure 5-13 Temperature behavior of silicon liquid [2.3]
51
Page 52
CP TD1 Reference Manual V 1.44
Resin Bonded Paper
Resin Impregnated Paper Oil Impregnated Paper
Dissipation factor x 10
2
Temperature in °C
Dissipation Factor - Dependency of the temperature
Figure 5-14 Temperature behavior RBP, RIP, and OIP bushing [2.5]
The dissipation factor is dependent on the frequency. With modern test devices like the CPC 100 + CP TD1, it is possible to cover a wide frequency range for capacitance and DF measurements. Up to now, fingerprint measurements for comparison are normally available only at line frequency. The following figures show the frequency dependency for transformer windings (oil-paper insulation) and an OIP bushing (Figures 5-15 and 5-16).
52
Page 53
Capacitance and Dissipation Factor Measurement
0.55%
0.50%
0.45%
0.40%
0.35%
0.30%
0.25%
0.0Hz 100 Hz 200Hz 300Hz 400Hz 500Hz
L (f) HL (f) H (f)
0.67%
0.66%
0.65%
0.64%
0.63%
0.62%
0.61%
0.60%
0.0Hz
50.0Hz
100.0Hz
150.0Hz
200.0Hz
250.0Hz
300.0Hz
350.0Hz
400.0Hz
450.0Hz
A B
TR 2-Winding DF (f)
Figure 5-15 Frequency scan winding to winding DF measurement (oil-
paper)
DF (f)
Figure 5-16 Frequency scan of a OIP bushing (Phase A and B)
53
Page 54
CP TD1 Reference Manual V 1.44
1.6%
1.5%
1.4%
1.3%
1.2%
1.1%
1.0%
0.9%
0.8%
0.7%
0.6% 0V 1kV 2kV 3kV 4kV 5kV 6kV 7kV 8kV
The dissipation factor is in many cases also dependent on the test voltage. Figure 5-17 shows a measurement of a 6kV motor. Above 4kV, partial discharges occur. This is the reason for the rise of DF.
Tan Delta Motor 6 kV
Figure 5-17 Voltage scan of a 6 kV motor
5.2 Measurement of Capacitance and Dissipation
54
Factor / Power Factor
Capacitance (C) and Dissipation Factor (DF) measurement was first published by Schering in 1919 [2.1] and utilized for this purpose in 1924 (Figure 5-18). The serial connected C
and R1 represent the test object with losses, C2 the loss-
1
Page 55
Capacitance and Dissipation Factor Measurement
C
1
C
2
R
1
R
3
R
4
C
4
R
1
1
jω C
1
------------ -+
R
3
-------------------------
1
R
4
----- - jωC
4
+
jωC
2
-------------------------=
R
1
R
3
----- -
C
4
C
2
------
R
1
C
4
C
2
------
R
3
×==
C1R3× C2R4× C
1
R
4
R
3
----- -
C
2
×==
δtan R1ωC
1
×=
δtan C
4
R
3
C
2
------
×ω
R
4
R
3
----- -
×× C
2
×=
δωC4× R4×=tan
free reference capacitor. The parallel circuit diagram shown in Figure 5-1 can be transferred as a direct equivalent into this serial diagram at specified frequencies (section 12.1).
Figure 5-18 Schering bridge
Real parts:
Imaginary parts:
55
Page 56
CP TD1 Reference Manual V 1.44
U0(t)
U
N
(t) UX(t)Z
1
Z
2
I
CN
I
CX
Z
N
CXZX, L
X
C
N
Reference path Measurement path
Figure 5-19 CP TD1 measuring principle
The CP TD1 test system utilizes a method similar to that of the Schering bridge. The main difference is that the CP TD1 measuring principle (Figure 5-19) does not require tuning for measuring C and DF. C
is a gas insulated reference
n
capacitor with losses below 10E-5. For laboratory use, such capacitors are regularly used to obtain precise measurements, as the ambient lab temperature normally ranges between 20 - 25 °C (68 - 77 °F). When carrying out on-site measurements, however, temperatures can vary significantly, which results in changes of the electrodes geometry.
56
Page 57
Capacitance and Dissipation Factor Measurement
The CP TD1 takes all these effects into account and compensates for them electronically, so it is now possible for the first time to measure in the field down to DF = 5 x 10E-5. Figure 5-20 shows the complete equivalent circuit diagram.
Figure 5-20 CP TD1 measuring principle
To the present day, the dissipation or dissipation factor was measured only at line frequency. With the power source described in [2.2], it is now possible to make these insulation measurements in a wide frequency range. Beside the possibility to apply frequency scans, measurements can be made at frequencies different from the line frequency and their harmonics. With this principle, measurements are possible also in the presence of high electromagnetic interference in high-voltage substations.
57
Page 58
CP TD1 Reference Manual V 1.44
CoreTL
H
C
H
C
H-L
C
L-T
C
H-T
C
T
C
L
Tank
G

5.3 "UST" and "GST" Measurements Using the Guard Technology

In electrical devices like power transformers there are a lot of insulation gaps, which have to be checked separately:
• Winding to winding
• Winding to tank & core
• Bushings
A three-winding transformer with the different insulation gaps is shown in figure 5-21. Only one phase is drawn. With a three-phase transformer the equivalent circuit diagram is very similar, because normally the phases of the high-voltage (H), the low-voltage (L) and the tertiary (T) windings are connected internally in y or delta. This way only the sum of all three phases can be measured, the single phases can not be measured separately.
Figure 5-21 Three-phase transformer with winding capacitances
H High-Voltage
58
winding
L Low-Voltage winding C L Cap. L to Ground C L-T Cap. L to T
C H Cap. H to Ground C H-L Cap. H to
L
Page 59
Capacitance and Dissipation Factor Measurement
IN A
IN B
C
1
C
2
C
3
UST-A
C = C
1
Guard
Measuring input
T Tertiary winding C T Cap. T to Ground C H-T Cap. H to
T
For the separate measurement of all capacitors a so-called guard technique is necessary. The single capacitors connected to guard are energized but not measured.
In Figure 5-22 a block diagram of the CP TD1 is shown with the guard connection and measuring input. In the example case C capacitors, connected to the CP TD1. C connected to input B and C energized. Only C
is measured, because the relay matrix only connects C1 to
1
is connected to ground. All three capacitors are
3
is connected to input A, C2 is
1
the measuring input (instrument), whereas the currents through C bypassed. C
and C3 are connected to the foot-point of the HV transformer
2
, C2 and C3 are
1
and C3 are
2
(GUARD).
Figure 5-22 CP TD1 block diagram with GUARD and measuring input
To get more familiar with this technique we want to measure C HL, C HT and C H of Figure 5-21. The high-voltage winding is connected to the test voltage (high-voltage output of the CP TD1), the low-voltage winding is connected to IN A and the tertiary winding is connected to IN B.
59
Page 60
CP TD1 Reference Manual V 1.44
IN A
IN B
C
HL
C
HT
C
H
GST
C = CHL + CHT + C
H
If big capacitance values are expected, we should start with a GST measurement first. In the GST mode all connected capacitors are measured in parallel (C HL + C HT + C H). This way we can check if the CP TD1 is overloaded during the measurements or not (Figure 5-23) and we can check the single measurements. The capacitance value out of this measurement must be the sum of the following single measurements.
60
Figure 5-23 CP TD1 block diagram of GST mode
Page 61
Capacitance and Dissipation Factor Measurement
IN A
IN B
C
HL
C
HT
C
H
UST-A
C = C
HL
Now we want to measure C HL. The connection diagram is shown in Figure 5-24. The measuring mode is UST-A.
Figure 5-24 Measurement of C HL in UST-A mode, C HT and C H are
guarded
61
Page 62
CP TD1 Reference Manual V 1.44
IN A
IN B
C
HL
C
HT
C
H
UST-B
C = C
HT
Next measurement is C HT. The connection diagram is shown in Figure 5-25. The measuring mode is UST B. Without the GUARD technique it would not be possible to measure C HT separately, because C HL in series to C LT are in parallel to C HT. Only by connecting L to GUARD the current flowing to L is not measured.
Figure 5-25 Measurement of C HT in UST-B mode, C HL and C H are
guarded
62
Page 63
Capacitance and Dissipation Factor Measurement
IN A
IN B
C
HL
C
HT
C
H
GSTg-A+B
C = C
H
The last measurement is C H. Figure 5-26 shows this connection diagram. The measuring mode is GSTg-A+B. C HL and C HT are not measured, because they are connected to GUARD.
The build-in relay matrix enables the described four different measurements without any rewiring. This principle can be used not only for transformers, but also for any system with partial capacitors inside.
Figure 5-26 Measurement of C H in GST-gA+B mode, C HL and C HT are

5.4 References

[2.1] Schering, H.: "Brücke für Verlustmessungen", Tätigkeitsbericht
[2.2] Hensler, Th., Kaufmann, R., Klapper, U., Krüger, M., Schreiner,
[2.3] Krüger, M.: "Prüfung der dielektrischen Eigenschaften von
[2.4] "IEEE Standard Test Code for Liquid-Immersed Distribution,
guarded
der Physikalisch-Technischen Reichsanstalt, Braunschweig 1919
S.: "Portable testing device", US Patent 6608493, 2003
Isolierflüssigkeiten", ÖZE, No. 5, Vienna, May 1986
Power, and Regulating Transformers", IEEE Std C57.12.90­1999
63
Page 64
CP TD1 Reference Manual V 1.44
[2.5] Seitz, V.: "Vorbeugende Instandhaltung an
Leistungstransformatoren – Betriebsbegleitende Messungen an Stufenschaltern und Durchführungen, OMICRON Anwendertagung 2003, Friedrichshafen
64
Page 65

6 Power Transformers

Cellulose
Overheated Oil
Corona
Arcing

6.1 Introduction

Due to ever-increasing pressure to reduce costs, the power industry is forced to keep old power facilities in operation as long as possible. In most European countries, about one third of the transformers are over 30 years old. Even transformers older than 50 years are still in service. A regular check of the operating conditions becomes more and more important with the advancing age of transformers. The Dissolved Gas Analysis is a proven and meaningful method for finding a fault as soon as possible if increased proportions of hydrogen and hydrocarbon gases are found in the oil. This way, important preventative maintenance can be performed in time to avoid an unexpected total failure.
DGA analysis and interpretation of results [3.1]
On the left are gases the oil specialist looks for in the gas-in-oil-analysis. On the right are possible origins of these gases. When these gases exceed the levels shown in the middle columns, the analyst uses the transformer history, the type of gases present, as well as the relative amounts, to determine any indication of transformer problems.
Power Transformers
Hydrogen H
Acetylene C
Methane CH
Ethylene C
Ethane C
Carbon monoxide
Carbon dioxide
3)
CO 200
2)
CO
Gas Normal
ppm
2
2H2
4
2H4
2H6
2
200 500
2000
Abnormal
1)
ppm
515
50 120
80 170
35 75
1)
2)
500
3500
65
Page 66
CP TD1 Reference Manual V 1.44
C2H
2
C2H
4
-------------
CH
4
H
2
---------- -
C2H
4
C2H
6
-------------
Legend:
Major gases Minor gases
1)
ppm = parts per million by volume (gas/liquid)
2)
Previous limits for CO were 500 and 700 ppm
3)
Previous limits for CO2 were 2000 and 10000 ppm
Behind the absolute value of gas content are the quotients of the gas components, which also allow for additional information (Table 6-1) [3.2].
Table 6-1 Dissolved Gas Analysis [3.2]
Type of fault
PD Partial discharge < 0.01 < 0.1 < 0.2 D1 Discharge with low energy > 1 0.1 - 0.5 > 1 D2 Discharge with high energy 0.6 - 2.5 0.1 - 1 > 2 T1 Thermal fault T < 300°C < 0.01 > 1 < 1 T2 Thermal fault T < 700°C < 0.1 > 1 1 - 4 T3 Thermal fault T > 700°C < 0.2 > 1 > 4
66
Page 67
Power Transformers
Possible Faults and Possible Findings
Table 6-2 Possible Faults and Possible Findings [3.3]
Key gases Possible Faults Possible Findings
H
, possible trace of
2
CH
and C2H6.
4
Possible CO.
, CH4 (some CO if
H
2
discharges involve paper insulation). Possible trace amounts of C
H
.
2H6
, CH4, C2H6, C2H4
2
and the key gas for arcing C
2H2
will be
present perhaps in large amount. If C
is being
2H2
generated, arcing is still going on. CO will be present if paper is being heated.
H
, CO. Thermal fault less than
2
H
, CO, CH4, C2H6,
2
C
2H4
All the above gases and acetylene in large amounts.
Partial discharges (corona)
Low energy discharges (sparking). May be static discharges.
High energy discharges (arcing).
300°C in an area close to paper insulation (paper is being heated).
Thermal fault between 300°C and 700°C.
High energy electrical arcing. Thermal fault of 700°C and above.
Weakened insulation from aging and electrical stress
Pinhole punctures in paper insulation with carbon and carbon tracking.Possible carbon particles in oil.Possible loose shield, pour grounding of metal objects.
Metal fusion (poor contacts in tap changer or lead connections). Weakened insulation from aging and electrical stress. Carbonized oil. Paper destruction if it is in the arc path or overheated.
Discoloration of paper insulation. Overloading and/or cooling problem. Bad connection in leads or tap changer. Stray current path and/or stray magnetic flux.
Paper insulation destroyed. Oil heavily carbonized.
Same as above with metal discoloration. Arcing may have caused a thermal fault
67
Page 68
CP TD1 Reference Manual V 1.44
Transformer Faults
Table 6-3 Transformer Faults [3.3]
Fault Examples
Partial discharges Discharges in gas-filled cavities in insulation,
Discharge of low energy Sparking or arcing between bad connections
Discharge of high energy Flashover, tracking or arcing of high local
Overheating less than 300°C Overloading the transformer in emergency
resulting from incomplete impregnation, high moisture in paper, gas in oil supersaturation or cavitation (gas bubbles in oil), leading to X wax formation on paper.
of different floating potential, from shielding rings, toroids, adjacent discs or conductors of different windings, broken brazing, closed loops in the core. Additional core grounds. Discharges between clamping parts, bushing and tank, high voltage and ground, within windings. Tracking in wood blocks, glue of insulating beam, winding spacers. Dielectric breakdown of oil, load tap changer breaking contact.
energy or with power follow-through. Short circuits between low voltage and ground, connectors, windings, bushings and tank, windings and core, copper bus and tank, in oil duct. Closed loops between two adjacent conductors around the main magnetic flux, insulated bolts of core, metal rings holding core legs.
situations. Blocked or restricted oil flow in windings. Other cooling problem, pumps valves, etc. Stray flux in damping beams of yoke.
68
Page 69
Power Transformers
Table 6-3 Transformer Faults [3.3]
Fault Examples
Overheating 300°C - 700°C Defective contacts at bolted connections
(especially busbar), contacts with tap changer, connections between cable and draw-rod of bushings. Circulating currents between yoke clamps and bolts, clamps and laminations, in ground wiring, bad welds or clamps in magnetic shields. Abraded insulation between adjacent parallel conductors in windings.
Overheating over 700°C Large circulating currents in tank and core.
Minor currents in tank walls created by high uncompensated magnetic field. Shorted core laminations.
Notes on Table :
1. X wax formation comes from paraffinic oils (paraffin based). These are not used in transformers at present in the United States but are predominate in Europe.
2. The last overheating problem in the table says "over 700°C". Recent laboratory discoveries have found that acetyl can be produced in trace amounts of 500°C, which is not reflected in this table. We have several transformers that show trace amounts of acetylene that are probably not active arcing but are the result of high-temperature thermal faults as in the example. It may also be the result of one arc, due to a nearby lightning strike or voltage surge.
3. A bad connection at the bottom of a bushing can be confirmed by comparing infrared scans of the top of a bushing with a sister bushing. When loaded, heat from a poor connection at the bottom will migrate to the top of the bushing, which will display a markedly higher temperature. If the top connection is checked and found tight, the problem is probably a bad connection at the bottom of the bushing.
69
Page 70
CP TD1 Reference Manual V 1.44
In addition to the previous table , it should be taken into account that overheating is often caused by bad contacts in the tap selector. In order to find out the reason for high gas values, further tests have to be performed on the transformer. Common test methods are:
• Winding resistance measurement
• On-Load Tap Changer (OLTC) test
• Turns ratio measurement
• Excitation current measurement
• Measurement of leakage reactance
• Capacitance and Dissipation factor measurement
All the mentioned tests can be done with the CPC 100 + CP TD1. This instrument is the ideal test and analysis instrument for transformer diagnosis with these measuring possibilities.

6.2 Capacitance and DF Measurement of Transformer Windings

General
• The transformer must be taken out of service and completely isolated
• The proper grounding of the transformer tank has to be checked.
• The bushing high-voltage terminals must be isolated from the connection
• All bushing terminals of one winding group, which means A, B, C (and
from the power system.
lines.
Neutral) of high-voltage winding, A, B, C (and Neutral) of low-voltage
70
Page 71
Power Transformers
N (L) C (L)
A (L) B (L)
A (H) B (H) C (H) N (H)
H
L
T
B (T)
C (T)
A (T)
ABC
winding and A, B, C (and Neutral) of tertiary winding have to be connected by a copper wire (see Figure 6-1).
Figure 6-1 Three-winding transformer with connected winding
• The neutral terminals of all Y-connected windings with outside-connected Neutral have to be disconnected from ground (tank).
• If the transformer has a tap changer then it should be set to the neutral position (0 or middle tap).
• Connect the CPC 100 + CP TD1 ground terminal to the transformer's (substation) ground.
• Connect the high-voltage output of the CP TD1, e.g. to the high-voltage winding (according to the connection instructions). Touching any parts
71
Page 72
CP TD1 Reference Manual V 1.44
like the bushings and the transformer tank (flashovers) with the unscreened part of the high-voltage test cable must be avoided.
• Connect the IN A, e.g. to the low-voltage winding, IN B, e.g. to the tertiary winding (according to the connection instructions).
• Short circuit all bushing CTs.
• Do not make high-voltage tests on transformers under vacuum.
• The test voltage should be chosen with respect to the rated voltage of the winding.
• All tests should be made with oil temperatures near 20°C. Temperature corrections can be calculated by using correction curves, but they depend a great deal on the insulation material, the water content and many other parameters. This way the correction has limited accuracy.

6.2.1 Three-Winding Transformer

A transformer contains a complicated insulation system. High- and low-voltage windings have to be insulated to the tank and the core (ground) and against each other. All these insulation gaps should be checked regularly. Normally in a two­winding power transformer, C-Tan-Delta measurements are made for all insulation gaps: HV to LV, HV to ground, LV to ground.
72
Page 73
Power Transformers
N (L) B (L)A (L) C (L)
A (H) B (H) C (H) N (H)
Bushing (A) Bushing (C)Bushing (B)
C H(A) C H(C)C H(B)
C H-L (A)
C H-L(C)C H-L (B)
C H-T (A)
C H-T (B)
C H-T (C)
C L-T(A)C L-T(A)
C L-T (B)
C L-T (C)
C L(C)
C L(B)
C L(A)
C T(C)
C T(B)
C L(A)
A B C
H
L
T
A three-winding transformer is much more complicated so more tests are necessary to measure all gaps. In Figure 6-2, a complete 3-winding power transformer is shown. The tertiary winding is not accessible in this case. When the load is unbalanced, it is necessary for flux compensation in the three limbs of the core.
Figure 6-2 Three-winding transformer with winding to winding and winding
to ground capacitors
73
Page 74
CP TD1 Reference Manual V 1.44
Core
Tank
G
C
L-T
C
H-L
C
H
C
T
C
L
H
LT
A Phase A B Phase B C Phase C
H High-Voltage
winding
C H Cap. H to Ground C H-L Cap. H to
L
L Low-Voltage winding C L Cap. L to Ground C L-T Cap. L to T
T Tertiary winding C T Cap. T to Ground C H-T Cap. H to
T
As shown in Figure 6-2, the three phases of the high-voltage (H), the low-voltage (L) and the tertiary (T) windings are connected internally in y or delta. This way only the sum of all three phases can be measured, the single phases can not be measured separately. Figure 6-3 shows the simplified circuit diagram of the three-phase transformer of Figure 6-2.
Figure 6-3 Three-phase transformer with winding capacitances
74
H High-Voltage
winding
C H Cap. H to Ground C H-L Cap. H to
L
L Low-Voltage winding C L Cap. L to Ground C L-T Cap. L to T
Page 75
Power Transformers
TERT. LOW HIGH
C
HT
C
LT
C
HL
C
T
C
L
C
H
T Tertiary winding C T Cap. T to Ground C H-T Cap. H to
T
To check the winding insulation completely, it is necessary to measure the capacitance and the DF of all insulation gaps (in this case six capacitors).
Caution: All phases and the neutral terminal of one winding (H, L and T) have to be short-circuited. Due to the inductance of the windings resonant effects may occur and influence the measurement.
In IEEE Std. 62-1995 [3.4] the test procedure is described for transformers with two and three windings. Figure 6-4 shows the six measurements.
Figure 6-4 Three-winding transformer test according to IEEE 62-1995
Test Mode Energize Ground Guard UST Measure
GST HIGH – LOW, TERT. – C
GST LOW –
GST TERT. – HIGH, LOW – C
Supplementary test for interwinding insulations
H
TERT., HIGH
–C
L
T
75
Page 76
CP TD1 Reference Manual V 1.44
UST HIGH TERT. – LOW C
UST LOW HIGH – TERT. C
UST TERT. LOW – HIGH C
HL
LT
HT
A more detailed test procedure for two- and three- winding transformers can be found in [3.6]. This test procedure is included in the appendix and is now used as an example to show the test preparation of a 3-winding transformer test with
76
Page 77
Power Transformers
the CPC Editor. Due to the high amount of measuring data, the test is split into three single test files. The first file contains the tests with high-voltage winding connected to the CP TD1 high-voltage output:
Figure 6-5 Input of transformer data
Figure 6-6 Instruction about test lead connections
77
Page 78
CP TD1 Reference Manual V 1.44
Figure 6-7 Measurement of C H and C H-L in GST g-B mode
78
Figure 6-8 Voltage-scan of high-voltage windings to tank and core (GST
gA+B)
Page 79
Power Transformers
Figure 6-9 Frequency-scan of high-voltage windings to tank and core (GST
gA+B)
The other tests for H-L are prepared analog to the examples.
79
Page 80
CP TD1 Reference Manual V 1.44
A second test file contains the tests with the low-voltage winding connected to the high-voltage output of the CP TD1. Figure 6-10 shows the first screen with the connection instructions.
Figure 6-10 Connection instructions for the tests with energized low-voltage
winding
80
Page 81
Power Transformers
A third test file is used for the tests with the tertiary winding connected to the CP TD1 high-voltage output. 6-11 shows the connection instructions for the tests with energized tertiary winding.
Figure 6-11 Connection instructions for the tests with energized tertiary
winding
81
Page 82
CP TD1 Reference Manual V 1.44
The prepared tests are uploaded to the CPC 100 as xml files without results. After the test is done, this xml file with the results is downloaded to the computer and loaded into Microsoft Excel with the OMICRON CPC 100 File Loader (the complete test files are included on the CD-ROM).
Figure 6-12 10 kV results for a three-winding transformer (50 Hz)
Figure 6-12 shows the results for 10 kV:
•1: H+HL
•2: H
•3: HL
• 5: L+LT
•6: L
•7: LT
•9: T+TH
• 10: T
• 11: TH
In line 4, the difference of the capacity values of test 1 - test 2 is calculated so it can be compared to test 3. In lines 8 and 12, the differences of lines 5-6 and 9-10 are calculated to also enable a comparison to tests 7 and 11. This way the reliability of the measured values can be checked. For the tertiary winding, the test voltage was reduced to 5 kV due to the lower rated voltage of this winding.
A voltage scan measurement is shown in Figure 6-13, a frequency scan in Figure 6-14.
82
Page 83
Power Transformers
Voltage and frequency scans enable additional information about the insulation quality. They should be saved as "fingerprint" for future measurements. For all the described measurements only three different connections of the test leads are necessary. Preparing the test in the office by utilizing the CPC Editor, the testing time on-site can be reduced to a minimum.
Figure 6-13 Voltage-scan for H-L (V) (50 Hz)
83
Page 84
CP TD1 Reference Manual V 1.44
Figure 6-14 Frequency scan for H-L (f) (5 kV)
84
Page 85

6.2.2 Two-Winding Transformer

Core
Tank
G
H
L
C
H-L
C
H
C
L
The test of two-winding transformers is easier than the described test procedure for transformers with three windings. Figure 6-15 shows the simplified circuit diagram of a two-winding transformer.
Power Transformers
Figure 6-15 Two-winding transformer with winding capacitances
H High-Voltage
winding
C H Cap. H to Ground C H-L Cap. H to
L
L Low-Voltage winding C L Cap. L to Ground C L-T Cap. L to T
85
Page 86
CP TD1 Reference Manual V 1.44
LOW HIGH
C
HL
C
L
C
H
In Figure 6-16, the test procedure for a two-winding transformer is shown, according to IEEE 62 1995 [3.4].
Figure 6-16 Two-winding transformer test according to IEEE 62-1995
Test Mode Energize Ground Guard UST Measure
GST HIGH – LOW – C
GST LOW – HIGH – C
Alternative test for C
HL
UST HIGH – – LOW C
UST LOW – – HIGH C
H
L
HL
HL
86
Page 87
Power Transformers
Figures 6-17 and 6-18 show the preparation with the CPC Editor and the test results in MS Excel format.
Figure 6-17 Two-winding transformer test preparation with CPC Editor
Figure 6-18 10 kV results for a two-winding transformer (50 Hz)

6.2.3 Auto-Transformer

The auto-transformer has only one winding with a tap for the low-voltage output. Only one measurement is made of the winding to tank and core. All high-voltage and low-voltage terminals are connected together as they are building the high­voltage electrode of the capacity.
87
Page 88
CP TD1 Reference Manual V 1.44

6.2.4 Reactors

Similar to the auto-transformers, reactors also normally have only one winding. Often the low-voltage ends of the three phases are connected outside the tank to the Neutral. In this case we have 2 bushings per phase, which have to be connected for the DF test. We can measure all combinations: phase to phase and phase to tank (ground).

6.3 Transformer High-Voltage Bushing Tests

High-voltage bushings are generally used in power transformers, but also in circuit breakers and in other electrical apparatus. Therefore, the test of bushings is described in chapter 7 ”Capacitance and DF Measurement on High-Voltage Bushings” on page 91.

6.4 Interpretation of Measurement Results

Initial tests on new transformers when it arrives from the manufacturer determines the presence of manufacturing defects or transport damage, and also provides "fingerprint" test values for future comparisons. Periodic tests during the life cycle of the transformer can indicate that the insulation is aging normally or rapidly.

6.4.1 Dissipation Factor Measurement

Environmental Conditions
As already mentioned in chapter 5 ”Capacitance and Dissipation Factor Measurement” on page 39, environmental factors can influence DF measurements greatly. Therefore it is important to record the ambient conditions at the time of testing when comparing test results. The tests should be made with oil temperatures near 20°C. Temperature corrections can be calculated, utilizing correction curves, but they depend very much on the insulation material, the water content and a lot of other parameters. This way the correction has limited accuracy. Testing at temperatures below freezing should be avoided, since the measurement results are not reliable. If the water in the insulation is frozen to ice, it may not be detected by DF testing.
Other factors like relative humidity and the general weather conditions should be recorded in the test report for future reference.
88
Page 89
Power Transformers
For oil paper insulation, the range of the DF values for new and aged transformers are published in some standards like [3.4] and in other literature [3.1], [3.2]. In IEEE Std. 62-1995 [3.1] the following limits for DF values are given:
Table 6-4 DF values for oil paper insulation
Condition of insulation
Transformer Good May be accept-
able
New DF < 0.5% - - Service-aged DF < 0.5% 0.5% < DF < 1% DF > 1%
All values measured at 20 °C
It is always better to measure the values regularly and save them for comparison to tests in the past and in the future. In this way, trends can be observed and the evaluation of results is of much higher quality.
Should be investi-
gated

6.4.2 Capacitance Measurement

The capacitance of the insulation gaps between the windings to each other and to ground depends mainly on the geometry of the winding. Windings may be deformed after transport of the transformer or nearby through faults with high currents. Changes in capacitance serve as an excellent indicator of winding movement and structural problems (displaced wedging, buckling etc.). If a winding damage is suspected then the capacitance measurement should be supplemented by a leakage reactance measurement. A separate test can be done for each phase with this measurement technique. Therefore this method is more sensitive to small changes in one phase.

6.5 References

[3.1] US Bureau of Reclamation: "Maintenance of liquid insulation
mineral oils and Askarels", Facility instructions, standards and techniques - Vol. 3-5, 1992
[3.2] Möllmann, A., Lütge, H.: IEC / VDE Standards für flüssige
Isolierstoffe zur Diagnostik von Transformatoren und Wandlern, ETG-Fachbericht "Diagnostik elektrischer Betriebsmittel", VDE­Verlag GmbH Berlin 2002, S. 205-210
89
Page 90
CP TD1 Reference Manual V 1.44
[3.3] US Bureau of Reclamation: "Transformer Maintenance",
Facility instructions, standards and techniques - Vol. 3-30, 2000
[3.4] ANSI Standard 62-1995: "IEEE Guide for Diagnostic Field
testing of Electric Power Apparatus - Part 1: Oil Filled Power Transformers, Regulators, and Reactors", IEEE New York, 1995
[3.5] US Bureau of Reclamation: "Transformer Diagnostics", Facility
instructions, standards and techniques - Vol. 3-31, 2003
[3.6] IEEE Standard C57.12.90: "IEEE Standard Test Code for
Liquid-Immersed Distribution, Power, and Regulating Transformers", IEEE New York, 1995
90
Page 91

Capacitance and DF Measurement on High-Voltage Bushings

Wall,tank
Main insulation:
• Solid Ceramic, cast insulation, synthetic resin bonded paper, resin impregnated paper, composite
• Liquid: oil
•Gas
Ambient:
•Air indoor outdoor
•Oil
•Gas
Conductor
Flange
7 Capacitance and DF Measurement on
High-Voltage Bushings

7.1 Introduction

High-voltage bushings are essential parts of power transformers, circuit breakers and of other power apparatus. More than 10% of all transformer failures are caused by defective bushings [4.2]. Although the price for a bushing is low compared to the costs of a complete transformer, a bushing failure can damage a transformer completely. A regular capacitance and DF measurement is highly recommended.

7.2 Types of Bushings

Figure 7-1 Principle of bushings
91
Page 92
CP TD1 Reference Manual V 1.44
Tap electrode grounded layer/flange
Grounded layer/flange
C
A
C
B
C
C
C
D
C
E
C
F
C
G
C
H
C
I
C
K
C
J
Testing and maintaining high-voltage bushings are essential for continued successful operation of transformers and circuit breakers. Power outages may occur as the result of a bushing failure. High-voltage bushings used on transformers and breakers exist in many forms, including:
Condenser
This type is most frequently used for high-voltage bushings and it is therefore the main one focused in this guide. Cylindrical conducting layers are arranged coaxially with the conductor within the insulating material. The length and diameter of the cylinders are designed to control the distribution of the electric field in and over the outer surface of the bushing. The partial capacities are switched in series and the voltage drops across the capacities is nearly equal to each other (Figures 7-2 and 7-3) [4.1].
92
Figure 7-2 Condenser bushing design [4.1]
Page 93
Capacitance and DF Measurement on High-Voltage Bushings
CA=CB=CC=CD=CE=CF=CG=CH=CI=C
J
V1 = V2 = V3 = V4 = V5 = V6 = V7 = V8 = V9 = V
10
C
1
C
2
C
K
Tap electrode
(normally grounded)
Grounded layer/flange
Center
conductor
Line-to-ground system voltage
Main insulation
Tap insulation
Notes:
– Equal capacitances, C
center conductor to the grounded condenser layer and flange.
– The tap electrode is normally grounded in service except for certain designs and bushings used
with potential device.
– For bushings with potential taps, the C
power-factor tap, C
through CJ, procedure equal distribution of voltage from the energized
A
capacitance is much greater than C1. For bushings with
and C2 capacitances may be same order of magnitude.
1
2
Figure 7-3 Condenser bushing circuit diagram [4.1]
Condenser bushings may have:
• "Resin-Bonded Paper insulation (RBP)
• "Resin-Impregnated Paper insulation (RIP)
• "Oil-Impregnated Paper insulation (OIP)
Composite
A bushing where the insulation consists of two or more coaxial layers consisting of different insulating materials.
Compound-filled
A bushing where the space between the major insulation or conductor, if no major insulation is used, and the inside surface of a protective weather casing (usually porcelain) is filled with a compound that contains insulating properties.
Dry or unfilled
A bushing consisting of a porcelain tube with no filler in the space between the shell and the conductor. These are usually rated 25 kilovolts and below.
93
Page 94
CP TD1 Reference Manual V 1.44
Oil-filled
A bushing where the space between the major insulation or the conductor, and the inside surface of a protective weather casing is filled with insulating oil.
Oil-immersed
A bushing composed of major insulators that are totally immersed in a bath of insulating oil.
Oil-impregnated paper-insulated
A bushing where the internal structure is made of cellulose material impregnated with oil.
Resin-bonded paper-insulated
A bushing where cellulose material bonded with resin provides the major insulation.
Solid, ceramic
A bushing where a ceramic or other similar material provides the major insulation.
Gas insulated
A bushing that contains compressed gas like SF6 or mixtures of SF6 with other gasses i.e. N2. This type is frequently used for circuit breaker bushings.

7.3 Bushing Troubles

About 90 percent of all preventable bushing failures are caused by moisture entering the bushing through leaky gaskets or other openings. Periodic inspection and diagnostic measurements can prevent most outages due to bushing failures. High-voltage bushings may explode with considerable violence and cause extensive damages to adjacent equipment. Flashovers may be caused by deposits of dirt on the bushings, particularly in areas where there are contaminants such as salts or conducting dusts in the air. These deposits should be removed by periodic cleaning. In [4.3] bushings faults, possible reasons and methods of detection are explained (Table 7-1).
94
Page 95
Capacitance and DF Measurement on High-Voltage Bushings
Table 7-1 Bushing faults, part 1 [4.3]
Failure Possible results Methods of detection
Cracked porcelain Moisture enters;
Oil and/or gas leaks; Filler leaks out
Deterioration of cemented joints
Gasket leaks Moisture enters;
Moisture in insulation Moisture enters Power factor test;
Solder seal leak Moisture enters;
Broken connection between ground sleeve and flange
Voids in compound Internal corona Visual inspection;
Displaced grading shield Internal sparking
Electrical flashover Cracked or broken
Moisture enters; Oil and/or gas leaks; Filler leaks out
Oil and/or gas leaks; Filler leaks out
Filler leaks out
Sparking in apparatus tank or within bushing; Discolored oil
discolors oil
porcelain; Complete failure
Visual inspection; Power factor test; Hot-collar test
Visual inspection; Power factor test; Hot-collar test
Visual inspection; Power factor test; Hot-collar test; Hot-wire test for moisture; Insulation resistance
Hot-collar test Visual inspection;
Power factor test; Hot-collar test; Hot-wire test for moisture; Leak detector
Power factor test; Uncharacteristic odor; Dissolved gas-in-oil analysis (DGA); Thermographic scanning
Power factor test; Hot-collar test
Hot-collar test; Uncharacteristic odor; Thermographic scanning; Dissolved gas-in-oil analysis (DGA)
Visual inspection; Hot-collar test
95
Page 96
CP TD1 Reference Manual V 1.44
Table 7-1 Bushing faults, part 1 [4.3]
Failure Possible results Methods of detection
Lightning Cracked or broken
Corona Internal breakdown;
Short-circuited condenser sections
Darkened oil Radio interference;
porcelain; Complete failure
Radio interference; Treeing along surface of paper or internal surfaces
Increased capacitance; Reduced voltage at capacitance tap terminal; Adds internal stress to insulation
Poor test results
Visual inspection; Test lightning arresters
Power factor test; Hot-collar test; Hot wire test; Radio-influence voltage (RIV) test; Thermographic scanning; Dissolved gas-in-oil analysis (DGA)
Power factor test; Voltage test at capacitance tap; Capacitance test; Thermographic scanning; Dissolved gas-in-oil analysis (DGA)
Power factor test; Hot-collar test
7.4 Capacitance and DF Measurement on High-Voltage
Bushings
The dissipation factor test is the most effective known field test procedure for the early detection of bushing contamination and deterioration. It also measures alternating (AC) test current, which is directly proportional to bushing capacitance.
Bushing dissipation factor and capacitance should be measured when a bushing is first installed and also one year after installation. After these initial measurements, bushing power or dissipation factor and capacitance should be measured at regular intervals (3 to 5 years typically). The measured values should be compared with previous tests and nameplate values.
96
Page 97
Capacitance and DF Measurement on High-Voltage Bushings
Note: Large variations in temperature significantly affect dissipation factor
readings on certain types of bushings. For comparative purposes, readings should be taken at the same temperature. Corrections should be applied before comparing readings taken at different temperatures.
Bushings may be tested by one or more of four different methods, depending upon the type of bushing and the dissipation factor test set available. For more detailed instructions on this test procedure, see the dissipation factor test set instruction book from the appropriate manufacturer. The four test methods are described as follows:

7.5 Ungrounded Specimen Test (UST)

This test measures the insulation between the center conductor and the capacitance tap, the dissipation factor tap, and/or ungrounded flange of a bushing. This test may be applied to any bushing in or out of the apparatus that is either equipped with capacitance or dissipation factor taps, or with the flange that can be isolated from the grounded tank in which the bushing is installed. The insulation resistance between the taps or insulated flanges and ground should be 0.5 M or greater. While in this case anything that is attached to the bushing would also be energized, only the insulation of the bushing between the center conductor and the ungrounded tap or flange would be measured. In the case of bushings equipped with capacitance taps, a supplementary test should always
97
Page 98
CP TD1 Reference Manual V 1.44
UST-A
Equalizers
C1 Layer
Voltage tap Mounting flange C2 layer (always
grounded to flange)
Paper insulation
IN A
IN B
Main conductor
be made on the insulation between the tap and the flange. Most manufacturers list the UST dissipation factor and capacitance values on the bushing nameplate.
98
Figure 7-4 UST bushing test (C1)
When bushings with capacitance or potential taps rated at 110 kV and above are tested by the ungrounded test specimen method, a separate dissipation factor test on the tap insulation should be performed as well.
For capacitance or potential taps, tests are performed at a voltage between 500 and 1,000 volts. The tap is energized with the bushing center conductor and flange grounded. The dissipation factor of a capacitance or potential tap will generally be of the order of 1.0 percent or less. Routine tap insulation tests are not normally recommended for bushings that are rated 69 kilovolts and below with dissipation factor taps. However, a dissipation factor test of the tap insulation should be performed when UST results are questionable or visual examination indicates the dissipation factor tap's condition is questionable. This test procedure is similar to that used earlier for capacitance taps. In such cases, the maximum permissible test potentials should be limited to those given in the
Page 99
Capacitance and DF Measurement on High-Voltage Bushings
GST g A+B
Equalizers
C1 Layer
Voltage tap Mounting flange C2 layer (always
grounded to flange)
Paper insulation Main conductor
IN A
IN B
appendix or as recommended by the bushing manufacturer. The dissipation factor value of the dissipation factor tap insulation for most of the bushings discussed earlier is generally in the order of 1.0 percent or less.

7.6 Grounded Specimen Test (GST)

7.7 Hot Collar Test

Figure 7-5 GST bushing test (C2)
This test measures the quality of the insulation between the current carrying or center conductor and the mounting flange of a bushing. This test is conducted on bushings that have been removed from equipment, bushings connected to de-energized equipment, spare bushings, or bushings that have been isolated from connected windings and interrupters. The test is performed by energizing the bushing conductor and grounding the flange.
This test measures the condition of a specific small section of bushing insulation between an area of the upper porcelain rain shed and the current carrying or center conductor. The test is performed by energizing one or more electrodes placed around the bushing porcelain with the bushing center conductor grounded. This test is used to supplement the three previous tests. It is also
99
Page 100
CP TD1 Reference Manual V 1.44
Mounting flange
Paper insulation
Main conductor
GST
IN A
IN B
used to test bushings in apparatus when the three tests are either inapplicable or impractical, such as, with SF6 bushings. Perform a hot-collar test at every third skirt on SF6 bushings. Hot-collar tests are effective in locating cracks in porcelain, deterioration, or contamination of insulation in the upper section of a bushing, low compound or liquid level, or voids in compound often before such defects are noticeable with the previous tests.
100
Figure 7-6 Bushing "hot collar" test
In tables of the appendix, typical dissipation factors and dissipation factor the manufacturers initially published limits. However, the typical or initial dissipation factor of many bushings is listed on the nameplate. In such cases, field measurement, particularly UST, should compare with the nameplate dissipation factors. In general, any bushing that exhibits a history of continuing increase in dissipation factor should be questioned and scheduled for removal from service.
Measured dissipation factor values should be temperature corrected to 20°C before being compared with reference values which are measured at 20°C.
Temperature correction factors are average values at best, and therefore, subject to some error. The magnitude of error is minimized if tests are performed at temperatures near the reference temperature of 20°C. If questionable dissipation factors are recorded at relatively high temperatures then the bushings should not be condemned until it has been allowed to cool down to near 20°C and repeat tests have been performed. This also applies to bushings
Loading...