MINI IEC CONTACTORS
AND OVERLOAD RELAYS
D-51
FVNR (Full Voltage
Non-Reversing) Contactors
Panel or Din Rail Mounting
Overload Relays Mount Directly
to Mini Contactors
Test/Off Button and Trip Free
Release on Overload Relays
XT Miniature Controls includes nonreversing contactors, auxiliary contacts
and mini overload relays. A wide range
of applications is possible including small
electrical motors from fractional to 5 hp
(460 Vac) or up to 4 kW (400 Vac).
Due to its compact size, the XT line of mini
controls is best suited to be applied in light
duty loads such as hoisting, packaging,
material handling, heating, lighting and
automation systems. XT mini contactors
are a particularly compact, economic and
environmentally friendly solution wherever
control of small motors or loads is required.
Front mounted snap-on auxiliary contacts
for mini contactors are available with screw
terminals in a variety of contact
configurations. Auxiliary contact modules
are standard with interlocked opposing
contacts, except in the case of early make
or late-break contacts.
The XTOM overload relays are three-pole
electromechanical motor circuit-breakers
using bimetallic elements. They are suitable
for monitoring both DC and AC currents.
Type XTOM overload relays have been
designed to be fitted directly on to XTMC
contactors. In the event of overload
tripping, the auxiliary contacts change over
and disconnect the control voltage circuit
from the corresponding contactor relay,
and thus indirectly switch off the current
to the motor being monitored. The XTOM
relays are adjusted by means of a setting
wheel to suit the motor current rating.
XTMC Series
Starts at
$
54
XTMC9A10A, mini contactor, $54.
XTMCXFA02-5PK, auxiliary
contact (front snap-on),
$70 for pkg of 5.
XTOM004AC1, mini overload
relay (bottom mount), $53.
SPECIFICATIONS
PHYSICAL AND ELECTRICAL
Weight: 0.2 kg (0.44 lb)
Mechanical Life—Operations:
10,000,000
Mechanical Life—Coil @ 50 Hz: 7
Maximum Mechanical Operating
Frequency (ops/hr): 9000
Insulation Voltage (Ui) Vac: 690
Impulse Withstand Voltage
(Uimp) Vac: 6000
Operational Voltage (Ue) Vac: 690
Safe Isolation to VDE 0106 Part 101
and Part 101/A1:
Between Coil and
Contacts (Vac): 300
Between Contacts (Vac): 300
Making Capacity (Amps): 110
Breaking Capacity (Amps):
220/230V: 90
380/400V: 90
500V: 64
660/690V: 54
Short-Circuit Protection Rating
Maximum Fuse (gL/gG):
Type 2 Coordination (A): 10
Type 1 Coordination (A): 20
Degree of Protection: NEMA 1 (IP20)
Protection Against Direct Contact
when Actuated from Front (IEC 536):
Finger- and back-of-hand proof
Terminal Capacity of Main and
Auxiliary Contacts Solid (mm
2
):
1 x (0.75 – 2.5); 2 x (0.75 – 2.5)
Flexible with Ferrule (mm2):
1 x (0.75 – 1.5); 2 x (0.75 – 1.5)
Solid or Stranded (AWG): 18 to 14
Terminal Screw: M3.5
Pozidriv Screwdriver: Size 2
Standard Screwdriver:
0.8 x 5.5 mm (1 x 6")
Max Tightening Torque:
Nm: 1.2
Lb-in: 10.6
Mounting Position: As required,
except vertical with terminals A1/A2
at the bottom
ENVIRONMENTAL
Ambient Temperature: -25 TO 50°C
(-13 TO 122°F)
Mechanical Shock Resistance (IEC/EN
60068-2-27):
Half-Sinusoidal Shock 10 ms
Contactor Without
Auxiliary Contact Module:
Main Contact—Make Contact: 10 g
Main Contact—Break/Make
Contact: 10/8 g
Contactor with Auxiliary
Contact Module:
Main Contact—Make Contact: 10 g
Main Contact—Make/Break
Contact: 20/20 g
Climatic Proofing: Damp heat,
constant, to IEC 60 068-2-78;
Damp heat, cyclic, to IEC 60 068-2-30
Pollution Degree: III/3
All models shown
smaller than actual size