Omega Products XRU1D120U User Manual

Page 1
K-3
STANDARD TERMINAL BLOCK RELAYS
XRU1D Series
Starts at
$
15
Field Replacement
l Functional Plug-In Bridges l Screw Connections l LED Status Indication l DIN Rail Mount l Only 6.2 mm (0.24") Wide l All Common Input Voltages
Between 24 Vdc to 120 Vac
l NEMA 6 (IP67) Protection l Environmentally Friendly,
Cadmium-Free Contact
l Easy, Cost-Effective and
Replacement Using Engagement Lever
The XR Series Terminal Block Relays are ideal for applications that require a high switching capacity and long electrical service life. The relays are plug-in interfaces that connect to basic terminal blocks. The XR Series utilizes screw technology, as well as offers quick system wiring, superior safety features, clear labeling and a high level of modularity.
Application Description
Used in automation systems, electromechanical relays guarantee a safe connection between process I/O and electronic controls. The following functions are covered by relay coupling elements:
l Electrical isolation between the
input and output circuits
l Independence of the type of
switching current (AC and DC)
l High short-term overload
resistance in the event of short circuits or voltage peaks
l Low switching losses l Ease of operation
Accessories
Power Terminal Block
The XRAPLCESK power terminal block has the same shape as the relay modules and is used to feed in the bridging potentials. The nominal current is 32 A. When the total current is less than or equal to 6 A, supply can take place directly at the connecting terminal blocks of one of the connected relays.
End Cover
The XRAATPBK end cover is required at the start and stop of a relay strip. It can also be used for visual separation of groups of relays as well as separating relays with voltages greater than 250V and separating neighboring bridges with different potentials. It is equipped with pre-scored break out points at the bridging positions so that individual bridges can be passed through as
needed. It may also be necessary to use the end cover between adjacent relays when three phases (L1, L2, L3) are used on the contact side of the relay.
Bridges
The XRAFBST colored, insulated plugin bridge system reduces wiring time by up to 70% compared to conventionally wired relays. The XRAFBST2, 2-position bridges, are suited for bridging a smaller number of relays and total currents <6 A. When a circuit is supplied from both sides, the circuit can be opened at any point, allowing all other modules to continue being supplied at the same time. The XRAFBST500 allow up to 80 modules to be bridged at one time. If bridges with different potentials meet in neighboring modules, the end cover XRAATPBK should be used. All bridges are equipped with a groove for removal with a standard screwdriver.
XRU1D120U, $21, shown larger than actual size.
Page 2
K-4
11
14
12
A2
A1
94 (3.70)
6.2 (0.24)
80 (3.15)
Dimensions:
mm (in)
Schematic for standard terminal block relays
MODEL NO. PRICE DESCRIPTION
XRU1D120U $21 1 PDT relay, 120 Vac/110 Vdc coil voltage XRU1D24 15 1 PDT relay, 24 Vdc coil coltage XRU1D24U 17 1 PDT relay, 24 Vac/Vdc coil voltage
To Order
(Specify Model Number)
AVAILABLE FOR FAST DELIVERY!
Ordering Example: XRU1D120U, 1 PDT relay, $21.
REPLACEMENT RELAYS AND ACCESSORIES
MODEL NO. PRICE DESCRIPTION
XRR1D120U $10.25 Replacement relay for XRU1D120U XRR1D24 7.00 Replacement relay for XRU1D24 and XRU1D24U XRAPLCESK-5PK 125.00 Power terminal block, 5 pack XRAATPBK-5PK 10.50 Black end cover, 5 pack XRAFBST2RD-10PK 14.00 2-position red snap in jumper, 10 pack XRAFBST2BU-10PK 14.00 2-position blue snap in jumper, 10 pack XRAFBST2GY-10PK 14.00 2-position gray snap in jumper, 10 pack XRAFBST500RD-5PK 110.00 80-position red snap in jumper, 5 pack XRAFBST500BU-5PK 110.00 80-position blue snap in jumper, 5 pack XRAFBST500GY-5PK 110.00 80-position gray snap in jumper, 5 pack
SPECIFICATIONS
Input Voltage:
XRU1D24: 24 Vdc XRU1D24U: 24 Vac/Vdc XRU1D120U: 120 Vac/110 Vdc
Typical Input Current:
XRU1D24: 9 mA XRU1D24U: 11 mA (24 Vac),
8.5 mA (24 Vdc) XRU1D120U: 3.5 mA (120 Vac), 3 mA (110 Vdc)
Connection Type: Screw connection Rigid Solid AWG (mm2): 26 to 14
(0.14 to 2.5)
Flexible Stranded AWG (mm2):
26 to 14 (0.14 to 2.5)
Typical Response Time:
XRU1D24: 5 mS XRU1D24U and XRU1D120U: 6 mS
Typical Release Time:
XRU1D24: 8 mS XRU1D24U and XRU1D120U: 15 mS
Input Protection:
XRU1D24: Polarity protection diode,
free-wheeling diode
XRU1D24U and XRU1D120U:
Bridge rectifier
Contact Type: 1 PDT Contact Material: AgSnO Max Switching Voltage: 250 Vac/Vdc
1
Min Switching Voltage: 12 Vac/Vdc Limiting Continuous Current: 6 A
Min Switching Current: 10 mA Min Switching Power: 120 mW Ambient Temp Range: -20 to 60°C
(-4 to 140°F)
Rated Operating Mode:
100% operating factor
Inflammability Class:
V0, in accordance with UL 94
Mechanical Service Life:
2 x 10
7
cycles
1 The separating plate, XRAPLCESK, should be installed for voltages greater than 250V (L1, L2, L3) between identical terminal points of adjacent modules. Potential bridging is then possible with the XRAFBST bridge system.
Page 3
One Omega Drive | Stamford, CT 06907 | 1-888-TC-OMEGA (1-888-826-6342) | info@omega.com
EPG05
www.omega.com
UNITED KINGDOM
www. omega.co.uk
Manchester, England
0800-488-488
UNITED STATES
www.omega.com
1-800-TC-OMEGA
Stamford, CT.
CANADA
www.omega.ca
Laval(Quebec)
1-800-TC-OMEGA
GERMANY
www.omega.de
Deckenpfronn, Germany
0800-8266342
Karviná, Czech Republic
FRANCE
www.omega.fr
Guyancourt, France
088-466-342
CZECH REPUBLIC
www.omegaeng.cz
596-311-899
BENELUX
www.omega.nl
Amstelveen, NL 0800-099-33-44
More than 100,000 Products Available!
Temperature
Calibrators, Connectors, General Test and Measurement Instruments, Glass Bulb Thermometers, Handheld Instruments for Temperature Measurement, Ice Point References, Indicating Labels, Crayons, Cements and Lacquers, Infrared Temperature Measurement Instruments, Recorders Relative Humidity Measurement Instruments, RTD Probes, Elements and Assemblies, Temperature & Process Meters, Timers and Counters, Temperature and Process Controllers and Power Switching Devices, Thermistor Elements, Probes and Assemblies,Thermocouples Thermowells and Head and Well Assemblies, Transmitters, Wire
Flow and Level
Air Velocity Indicators, Doppler Flowmeters, Level Measurement, Magnetic Flowmeters, Mass Flowmeters, Pitot Tubes, Pumps, Rotameters, Turbine and Paddle Wheel Flowmeters, Ultrasonic Flowmeters, Valves, Variable Area Flowmeters, Vortex Shedding Flowmeters
pH and Conductivity
Conductivity Instrumentation, Dissolved Oxygen Instrumentation, Environmental Instrumentation, pH Electrodes and Instruments, Water and Soil Analysis Instrumentation
Data Acquisition
Auto-Dialers and Alarm Monitoring Systems, Communication Products and Converters, Data Acquisition and Analysis Software, Data Loggers Plug-in Cards, Signal Conditioners, USB, RS232, RS485 and Parallel Port Data Acquisition Systems, Wireless Transmitters and Receivers
Pressure, Strain and Force
Displacement Transducers, Dynamic Measurement Force Sensors, Instrumentation for Pressure and Strain Measurements, Load Cells, Pressure Gauges, Pressure Reference Section, Pressure Switches, Pressure Transducers, Proximity Transducers, Regulators, Strain Gages, Torque Transducers, Valves
Heaters
Band Heaters, Cartridge Heaters, Circulation Heaters, Comfort Heaters, Controllers, Meters and Switching Devices, Flexible Heaters, General Test and Measurement Instruments, Heater Hook-up Wire, Heating Cable Systems, Immersion Heaters, Process Air and Duct, Heaters, Radiant Heaters, Strip Heaters, Tubular Heaters
click here to go to the omega.com home page
Loading...