Omega Products WMS1B07SP User Manual

SUPPLEMENTARY PROTECTORS
WMS Series
l 1, 2, 3 Pole Models l 1 to 30 Amp Ranges l 3 Different Trip Curves to
Choose From
l CSA 22.2
WMS1C20SP
WMS3C20SP
WMS2C20SP
All models shown smaller than actual size.
Offering maximum reliability and accuracy, the supplementary protectors fit various applications where a fuse may have been previously used. The advantage over fuses is that it is resettable and the device’s status is easily and clearly identified by the position of the handle and the flag indicator. With easy mounting of the device on a 35 mm (1.38") DIN rail it is now easier for the customer to select and apply this modular range, due to the smaller modular width of the device and accessories. The WMS supplementary protector is a dual-rated product for both AC and DC supplies, in accordance with UL 1077, CSA 22.2 and IEC 898 standards and is marked with CE in accordance with the Low Voltage Directive. With this dual standard product, you can include it within your design, knowing that, in the vast majority of cases wherever the equipment is used, the product is in line with the local UL, CSA or IEC (European) requirements. This is very important as the different areas of the world market draw closer together and the need for breakers that meet different standards is a common, everyday occurrence. It is to be applied in conjunction with a branch protector (if branch protection is required) and can be a replacement for
similarly applied fuses. In addition to this, you are able to select a device that provides maximum reliability and accuracy to fit their various applications (of which there are many) due to the availability of a wide range of current ratings from 0.5 to 60 amperes and three different overcurrent characteristic curves. With easy mounting of the device on a 35 mm (1.38") DIN-rail and also the “Quick 3 Step” field mountable accessories, it is
now easier to select and apply this modular range. In addition, utilizing the bus bar comb to connect multiple devices from a single power source, saves time as multiple wire connections are no longer required. Due to the smaller modular width of the device and accessories, it enables them to save space in their panel or equipment—which directly leads to cost savings!
IEC RATING
AMPERE
RATING CURVE VOLTS AC IEC 898, I
0.5 to 5 C, D 240/415 10,000 10,000 50 to 60 B, C, D 240/415 10,000 10,000
SHORT CIRCUIT CAPACITY
IEC 947-2, I
CN
UL/CSA RATING
AMPERE NUMBER
RATING OF POLES CURVE VOLTS AC UL 1077 CSA 235
6 to 60 1 B 120 10,000 10,000
0.5 to 60 1 C, D 120 10,000 10,000 6 to 60 2, 3, 4 B 240 10,000 10,000
0.5 to 60 2, 3, 4 C, D 240 10,000 10,000 6 to 60 1 B 277 6000 6000
0.5 to 60 1 C, D 277 6000 6000 6 to 60 2, 3, 4 B 480 5000 5000
0.5 to 60 2, 3, 4 C, D 480 5000 5000
SHORT CIRCUIT CAPACITY (A)
CU
1
DC RATING
75°
(0.43)
11
7
(0.28)
15
(0.59)
62
(2.44)
44
(1.73)
85
(3.48)
45
(1.77)
18
(0.71)
7
7
(0.28)
15
(0.59)
68
(2.68)
54
(2.13)
31
(1.22)
44
(1.73)
4
(0.16)
75°
7
(0.43)
11
7
(0.28)
15
(0.59)
62
(2.44)
44
(1.73)
85
(3.48)
45
(1.77)
18
(0.71)
7
(0.28)
7
(0.28)
15
(0.59)
68
(2.68)
54
(2.13)
31
(1.22)
44
(1.73)
4
(0.16)
54
(2.13)
75°
7
(0.43)
11
7
(0.28)
15
(0.59)
62
(2.44)
44
(1.73)
85
(3.48)
45
(1.77)
18
(0.71)
7
(0.28)
7
(0.28)
15
(0.59)
68
(2.68)
54
(2.13)
31
(1.22)
44
(1.73)
4
(0.16)
36
(1.42)
54
(2.13)
75°
7
11
7
(0.28)
15
(0.59)
62
(2.44)
44
(1.73)
85
(3.48)
45
(1.77)
18
(0.71)
7
(0.28)
7
(0.28)
15
(0.59)
68
(2.68)
54
(2.13)
31
(1.22)
44
(1.73)
4
(0.16)
35
(1.38)
35
(1.38)
9
(0.35)
9
(0.35)
35
(1.38)
35
(1.38)
9
(0.35)
9
(0.35)
AMPERE NUMBER
RATING OF POLES CURVE VOLTS DC UL 1077 CSA 235
0.5 to 63 1 B, C, D 65 10,000 10,000
0.5 to 63 2 B, C, D 130 10,000 10,000
SHORT CIRCUIT CAPACITY (A)
CABLE SIZE AND TORQUE SETTING - WMS SERIES
AMPERE RATING mm2 AWG Nm lb/in
0.5 to 60 1 to 25 14 to 6 2.8 24.8
CABLE SIZE TIGHTENING TORQUE
Dimensions: mm (inch)
18
(0.71)
Standards and Certifications
UL recognized under UL 1077
l lCSA 22.2 lIEC 898 lIEC 60947-2
Product Description
Dual standard breaker: recognized by
l
UL and CSA under UL 1077 and CSA 22.2
lThird-party approved by KEMA
according to IEC 898
lCE marked in accordance with Low
Voltage Directive (LVD) (73/23/EEC)
lUsed to provide overcurrent protection
where branch protection (for example UL 489 MCCB) is already provided or not required
lInstalled as a component within or part
of an appliance or a piece of electrical equipment
lIdeal replacement for fuses that are
applied as a supplementary protector, i.e., in addition to branch protection (if required)
l 35 mm (1.38") DIN-rail mountable,
utilizing metallic “extra strength” spring clip
2
36
(1.42)
54
(2.13)
lLight gray case with gray handle, that is
marked “O” for OFF and “I” for ON
lUL file number E162396 lCSA file number LR105508-2
Application Description
Cutler-Hammer supplementary protectors are ideal for providing protection in a multitude of applications, including:
lMotor control circuits lControl power transformers lRelays lContactor coils lPLC I/O points lLighting circuits
Features, Benefits and Functions
Current limiting design provides fast
l
short circuit interruption that reduces the let-through energy which can damage the circuit.
lThermal-magnetic overcurrent protection:
Three levels, categorized by B, C and D curves in direct relation to continuous rating of device
–B Curve—3 to 5X: Suited for applications where maximum protection is required for control circuits from low level short circuit faults that could damage the wiring.
45
(1.77)
–C Curve—5 to 10X: Is positioned for medium inrush startup currents, to provide protection for small transformers, pilot devices, etc.
–D Curve—10 to 20X: Provides a magnetic range to allow for higher inrush levels during startup, that are usually seen with motors, transformers and other high inductive systems.
lColor-coded status indicator
window—Red = ON or Green = OFF
lIP20 finger protection. lProvision for dual connection—
line and load: –Fork or pin bus bars –Cable direct into terminal –Cable utilizing ring tung connector
l 35 mm (1.38”) DIN-rail mountable,
utilizing “extra strength” spring clip
Field-Mountable Accessories
Quick 3-step process
l lNo tools required lAuxiliary switch lCombined auxiliary switch and bell alarm lShunt trip
62
(2.44)
(1.73)
44
85
(3.48)
1-Pole
2-Pole
3-Pole
To Order Visit omega.com/wms_protectors for Pricing and Details
1-POLE AMPERE MODEL NO. MODEL NO. MODEL NO.
RATING CURVE B CURVE C CURVE D
1 WMS1C01SP N/A 2 WMS1C02SP WMS1D02SP 3 N/A WMS1C03SP WMS1D03SP 4 WMS1C04SP WMS1D04SP 5 WMS1C05SP WMS1D05SP 6 WMS1B06SP WMS1C06SP WMS1D06SP 7 WMS1B07SP WMS1C07SP WMS1D07SP 8 WMS1B08SP WMS1C08SP WMS1D08SP 10 WMS1B10SP WMS1C10SP WMS1D10SP 13 WMS1B13SP WMS1C13SP WMS1D13SP 15 WMS1B15SP WMS1C15SP WMS1D15SP 16 WMS1B16SP WMS1C16SP WMS1D16SP 20 WMS1B20SP WMS1C20SP WMS1D20SP 25 WMS1B25SP WMS1C25SP WMS1D25SP 30 WMS1B30SP WMS1C30SP WMS1D30SP
2-POLE AMPERE MODEL NO. MODEL NO. MODEL NO.
RATING CURVE B CURVE C CURVE D
1 WMS2C01SP N/A 2 WMS2C02SP WMS2D02SP 3 WMS2C03SP WMS2D03SP 4 WMS2C04SP WMS2D04SP 5 WMS2C05SP WMS2D05SP 6 WMS2B06SP WMS2C06SP WMS2D06SP 7 WMS2B07SP WMS2C07SP WMS2D07SP 8 WMS2B08SP WMS2C08SP WMS2D08SP 10 WMS2B10SP WMS2C10SP WMS2D10SP 13 WMS2B13SP WMS2C13SP WMS2D13SP 15 WMS2B15SP WMS2C15SP WMS2D15SP 16 WMS2B16SP WMS2C16SP WMS2D16SP 20 WMS2B20SP WMS2C20SP WMS2D20SP 25 WMS2B25SP WMS2C25SP WMS2D25SP 30 WMS2B30SP WMS2C30SP WMS2D30SP
3-POLE AMPERE MODEL NO. MODEL NO. MODEL NO.
RATING CURVE B CURVE C CURVE D
1 WMS3C01SP N/A 2 WMS3C02SP WMS3D02SP 3 WMS3C03SP WMS3D03SP 4 WMS3C04SP WMS3D04SP 5 WMS3C05SP WMS3D05SP 6 WMS3B06SP WMS3C06SP WMS3D06SP 7 N/A WMS3C07SP N/A 8 N/A WMS3C08SP WMS3D08SP 10 WMS3B10SP WMS3C10SP WMS3D10SP 13 N/A WMS3C13SP N/A 15 WMS3B15SP WMS3C15SP WMS3D15SP 16 N/A WMS3C16SP WMS3D16SP 20 WMS3B20SP WMS3C20SP WMS3D20SP 25 WMS3B25SP WMS3C25SP WMS3D25SP 30 WMS3B30SP WMS3C30SP WMS3D30SP
N/A
N/A
N/A
3
WST220A, shown actual size.
WAX1A1B shown actual size.
WPKEY shown slightly smaller than actual size.
WAL1A1B shown actual size.
WPLK shown slightly smaller than actual size.
ACCESSORIES
MODEL DESCRIPTION
WAL1A1B Alarm 1A/1B, 240V, 6A WAX1A1B Auxiliary 1A/1B, 240V, 6A WIDL-120PK Identification label (120 per carton) WPKEY Padlock and keys WPLK Padlock provision WST220A Shunt trip, 120 to 220 Vac WST415A Shunt trip, 240 to 415 Vac WST48D Shunt trip, 12 to 48 Vdc
WMS SERIES ACCESSORY TECHNICAL DATA
MODEL AUXILIARY AUXILIARY SHUNT ELECTRICAL CABLE SIZE TIGHTENING TORQUE
NUMBER SWITCH ALARM TRIP UVR CHARACERISTICS MM2 AWG NM LB-IN
WAL1A1B 1 changeover contact No Yes No No 240V ~ 6 A 0.5 to 4 18 to 12 0.8 7.1
WAX1A1B 2 changeover contact Yes No No No 240V ~ 6 A 0.5 to 4 18 to 12 0.8 7.1
WST415A No No Yes No 230 to 415V/110 to 130V 0.5 to 4 18 to 12 0.8 7.1 WST48D No No Yes No 9 to 48V/48V 0.5 to 4 18 to 12 0.8 7.1 WST220A No No Yes No 110V/220V 0.5 to 4 18 to 12 0.8 7.1 WUVR240A No No No Yes 240V~ /110 to 130V 0.5 to 4 18 to 12 0.8 7.1 WUVR48D No No No Yes 48V/24 to 48V 0.5 to 4 18 to 12 0.8 7.1
Ordering Examples: WMS1B06SP, one pole, curve B, 6 A supplementary protector. WMS3D30SP, three pole, curve D, 30 A supplementary protector and WAL1A1B, alarm.
4
10,000
1000
100
10
1
0.1
0.01 110
Current in Multiple of Rated Current
sdnoceS ni emiT
Supplementary Protectors — WMS
Data Sheet Number — 66C1235
100
10,000
1000
100
10
1
0.1
0.01 110
Current in Multiple of Rated Current
sdnoceS ni emiT
Supplementary Protectors — WMS
Data Sheet Number — 66C1236
100
10,000
1000
100
10
1
0.1
0.01 110
Current in Multiple of Rated Current
sdnoceS ni emiT
Supplementary Protectors — WMS
Data Sheet Number –— 66C1237
100
Curve B Time/Current Characterisitc
Curve D Time/Current Characterisitc
Curve C Time/Current Characterisitc
WMS3C20SP, shown actual size.
5