8 DIN Economical Two-Wire, Loop-Powered Process Indicator Liquid Crystal Display
TX82B Series
Starts at
$
160
FM Intrinsic
Safety Certification
Powered by 1 to 5 mA,
2.5 Maximum
Voltage Drop
Display to ±1999, ±19,990
or ±199,900
12.7 mm (0.5") LCD100 to 2000 Count
Span Adjust
2000-Count Zero
Suppression or Elevation
1
Short
8 DIN Case
Simple 2-Wire Hook-UpSafe Plug-in Screw-
Clamp Connector
Options
-40 to 85°C (-40 to 185°F)
Operating Temperature
NEMA 4 Splash-Proof
Lens Cover
TX82B is a 1⁄8 DIN-sized 2-wire current-loop indicator that is powered directly by 1 to 5 mA, 4 to 20 mA or 10 to 50 mA process signals, with no need for external power connections. This reduces field wiring costs and provides immunity from most electrical noise encountered in process-control environments. The 2-wire electrical hookup is easy via a plug-in screw­clamp connector, which is standard.
Panel Punches
Available, Visit
omega.com/
panelpunches
Readout of Process Variables
The TX82B provides extensive zero and span adjustment capability for direct readout in percent or in engineering units for process variables such as pressure, flow, temperature, or level. A 12.7 mm (0.50") high LCD display provides 31⁄2 active digits for readout to ±1999, 2 jumper-selectable dummy right-hand zeros for display to ±19,990 or ±199,900, and 5 jumper-selectable decimal points. With the dummy zeros, the TX82B can thus be used to display the weight of heavy trucks in pounds or the volume of large tanks in gallons.
Easy to Configure and Calibrate
Both span and zero are fine­tuned with precision 15-turn potentiometers accessible behind the lens. Coarse zero and span steps as well as the dummy right-hand zero are selected by opening the case and changing push-on jumpers.
Intrinsic Safety Certification
FM intrinsic safety certification is standard. Intrinsic safety certification allows the TX83A to be used in worst-case hazardous environments with no need for an explosion-proof housing, provided
TX82B, $160, shown smaller than actual size.
that an intrinsic safety barrier is used to limit the voltage and current that may be introduced in the hazardous environment.
FM certification (USA) is for class I, II, III, division 1, groups A, B, C, D, E, F, G. The FM certification number is 2Y4A4.AX (3610).
Built for Industrial Environments
The TX82B is housed in a splash­resistant case and requires a depth of less than 100 mm (3.9") behind the panel. A splash-proof lens cover which meets NEMA 4 requirements is optional. Electrical connections are via a 3-pole male header connector on the circuit board and a mating plug-in socket connector with screw clamps, which accommodate wire sizes of 0.5 to
2.5 mm (26 to 16 AWG). These supplied connectors provide easy and reliable electrical connections and meet UL and IEC-348 safety requirements.
Specifications
Signal Input Signal: 1 to 5 mA, 4 to 20 mA or
10 to 50 mA (jumper-selectable)
Linear Range: 0.3 to 50 mA Protection: Up to 200 mA forward,
1000 mA reverse current; forward voltage drop, max 2.5V
N-17
Input Resistance: 50 @ 1 to 5 mA,
199900
Kg
4 to 20 mA
transmitter
Control room
receiver
4 to 20 mA loop
Extended Warranty
Program
SM
12.5 @ 4 to 20 mA, 5 @ 10 to 50 mA Zero Adjust: -2000 to +2000 counts in
4 jumper- selectable ranges plus fine adjustment 00
Span Adjust: 100 to 2000 counts with fine adjustment
NMR: 46 dB, 50/60 Hz CMR (Meter to Case): 120 dB, DC to 60 Hz CMV (Meter to Case): 300 Vac
Accuracy at 25°C
Maximum Error: ±0.1% of rdg ±1 count Zero Tempco: ±0.1 count/°C typical,
±0.3 count/°C max Span Tempco: ±0.005% of span/°C
typical, ±0.015% of span/°C max
Analog-to-Digital Conversion
Technique: Dual-slope, average-value Polarity: Automatic Integration Period: 100 ms Read Rate: 2.5/s
Mechanical
Case:1⁄8 DIN Panel Cutout: 45 H x 92 mm W
(1.77 x 3.62")
Bezel Dimensions:
(1.89 x 3.79 x 0.31")
Depth Behind Bezel: 100 mm (3.94") Case Material: 94V-0 UL-rated
polycarbonate
Weight: 128 g (4.5 oz) Circuit Board Connector:
Three-pole male header
Cable Connector (Standard):
Mating plug-in socket with screw-clamps for wire sizes
0.5 to 2.5 mm
Connector Safety Ratings:
UL and IEC-348
48 H x 96 W x 8 mm T
2
(26-16 AWG)
Environmental
Operating Temperature (Standard):
0 to 55°C (32 to 122°F)
Operating Temperature, Optional:
-40 to 85°C (-40 to 185°F) Relative Humidity: 95% at 40°C
(non-condensing)
Display
Type: 7-segment LCD Height: 12.7 mm (0.50") Symbols: -1.8.8.8.0.0 (3
digits plus 2 jumper-selectable dummy right-hand zeros)
Decimal Points: 5 positions, jumper-selectable
Overrange Indication: 3 least­significant active digits blank
1
2 active
A TX82B process-loop indicator may be added to an existing 1 to 5 mA, 4 to 20 mA or 10 to 50 mA installation to provide a local readout scaled in percent or engineering units. No power wiring is required, since the meter is powered directly by the current loop.
AVAILABLE FOR FAST DELIVERY!
To Order (Specify Model Number)
Model No. Price Description TX82B $160 Current loop indicator TX82B-ET 195 Current loop indicator with extended
ambient range of -40 to 85°C (-40 to 185°F)
Ordering Additional Suffix Cost Description
-FS $45 Custom configuration and calibration
Accessories
Model No. Price Description SPC18 $30 NEMA 4 splash proof lens cover SPC4 30 NEMA 4 heavy-duty splash proof lens cover
with screw clamp
Comes complete with operator’s manual.
Ordering Examples: TX82B, current loop indicator, $160. OCW-3, OMEGCARESMextends standard 1-year warranty to a total of 4 years ($37),
$160 + 37 = $197.
N
program is available for models shown on
OMEGACARE
this page. OMEGACARESMcovers parts,
labor, and equivalent loaners. Ask your
sales representative for full details when
SM
extended warranty
placing an order.
Please see page N-46 for TX1500 Series isolated 2-wire, 4 to 20 mA transmitters.