Smart Temperature
Transmitters
TX13
U K, J, N, E, T, R, S
Thermocouples and
mV Inputs
U Pushbutton Configuration
U 56 Preprogrammed
Ranges Ready-to-Use
U User Trim—Null Out
Sensor Error
U Programmable Burnout
with Sensor Fail Indicator
U Galvanically Isolated
The TX13 is a “smart” in-head
transmitter that accepts thermocouple
temperature sensors and converts
sensor output over a configured
range to a standard industrial (4 to
20 mA) transmission signal.
A simple pushbutton operation
allows the user to select TC type,
burnout direction, select fixed ranges
and trim 4 and 20 mA points. The
in head transmitter incorporates the
latest digital technology to ensure
accurate drift-free performance.
If required the desired range can
be specified at the time of order,
removing the need for user
configuration. If the range is not
specified then the transmitter will be
shipped with the default range of
0 to 1000°C (32 to 1832°F) Type K.
Specifications
Isolation: Tested to 250 Vdc
Sensor Burnout: Either up or down
scale output
Cold Junction:
Range: -40 to 85°C (-40 to 185°F)
Accuracy: ±0.5°C (0.9°F)
Tracking: ±0.05°C/°C (0.9°F/°F)
Stability:
Offset: 0.1°C/°C (0.18°F/°F)
Span: 0.05°C/°C (0.18°F/°F)
Output
Output Type: 2 wire, 4 to 20 mA current
loop
Output Range: 4.0 to 20.0 mA
Output Connection: Screw terminal
Maximum Output: 21.5 mA
(in high burnout condition)
Minimum Output: 3.8 mA
(in low burnout condition)
Accuracy: (mA output/2000) or 5 uA
(whichever is the greater)
Loop Voltage Effect: 0.2 uA/V
Thermal Drift: 1 uA/°C
Maximum Output Load:
[(Vsupply-10)/20] kΩ
(Example: 700 Ω @ 24V)
Update Time: 500 mS
Response Time: 1 second
Start Up Time: 4 seconds
(1 out < 4 mA during start up)
Warm-Up Time: 1 minute to full accuracy
Power Supply: 10 to 30 Vdc
Environmental
Ambient Operating Range:
-40 to 85°C (-40 to 185°F)
Ambient Storage Temperature:
-50 to 90°C (-58 to 194°F)
Ambient Humidity Range:
10 to 90% RH non-condensing
Physical
Dimensions: 43 Dia x 21 mm H
(1.7 x 0.8")
Weight: 31 g (0.07 lb) (encapsulated)
Specifications @ 20°C–Input
Sensor Range °C (°F) Accuracy
-200 to 1370 ±0.5°C (0.9°F) or ±0.1% whichever
(-328 to 2498) the greater
-100 to 1200 ±0.5°C (0.9°F) or ±0.1% whichever
(-148 to 2192) the greater
-100 to 1000 ±0.5°C (0.9°F) or ±0.1% whichever
(-148 to 1832) the greater
-180 to 1300 ±0.5°C (0.9°F) or ±0.1% whichever
(-292 to 2372) the greater
-100 to 400 ±0.5°C (0.9°F) or ±0.1% whichever
(-148 to 752) the greater
-10 to 1760 ±0.5°C (0.9°F) or ±0.1% whichever
(14 to 3200) the greater over range 800 to 1600
-10 to 1760 ±0.5°C (0.9°F) or ±0.1% whichever
(14 to 3200) the greater over range 800 to 1600
(14 to 158)
-10 to 70 ±0.02% of full scale
mV
EMC - BS EN 61326: 1998: Electrical
equipment for measurement control and
laboratory use
ANNEX A: Immunity test requirements for
equipment intended for use in industrial
locations
ANNEX F: Test configurations, operational
conditions and performance criteria for
transducers with integrated or remote signal
conditioning
IEC 61000-4-2: Electrostatic discharge
IEC 61000-4-3: EM field
IEC 61000-4-4: Transient burst (output)
IEC 61000-4-5: Surge (output)
Note: Sensor input wires to be less than
3 m (10') to comply.
Approvals
TX13 shown
actual size.
To Order Visit omega.com/tx13 for Pricing and Details
Model No. Description
TX13 Thermocouple/mV smart transmitter
TX2-100 2-conductor shielded cables, 30 m (100')
PSR-24S Regulated power supply, 24 Vdc, 400 mA,
screw terminal
PSR-24L Regulated power supply, 24 Vdc, 400 mA, UL,
stripped leads
PSR-24L-230 Regulated power supply, 24 Vdc, 400 mA,
stripped leads, 230 Vac input, CE
TX-SCALED Scaling charge for factory set up of range
(specify temperature range)
Comes complete with operator’s manual.
Ordering Example: TX13, thermocouple smart transmitter.
N-36