Omega Products TX12 Installation Manual

TX12
PUSH BUTTON PT100 TX
INSTRUCTION
SHEET
1.0 DESCRIPTION
The TX12 head mounted temperature transmitter connects to any standard pt100 resistance sensor and converts the linearised temperature to a (4 to 20) mA signal. The transmitter is a two wire device, and is fully configurable by the user, over a wide temperature range, with the aid of a simple push button. This new TX12 design incorporates additional configuration menus, allowing the user to push button trim the transmitter output at both zero and span, ideal for trimming out sensor errors. The transmitters advanced circuitry guaranties high stability over the wide operating ambient temperature ranges experienced by head mounted devices.
One of the transmitters features is the program LED, which provides visual indication of sensor fault when in normal operation and is also used to guide the operator through the simple menus during configuration.
2.0 RECEIVING AND UNPACKING
Please inspect the packaging and instrument thoroughly for any signs of transit damage. If the instrument has been damaged, please notify your supplier immediately.
3.0 SPECIFICATION @ 20 °C
INPUT Sensor Type PT100 100 R @ 0°C 2 or 3 Wire Sensor Range (-200 to +850) ° C (18 to 390) _ Sensor Connection Screw terminal Minimum span (see note 1) 25 °C Linearisation BS EN 60751(IEC 751) standard / JISC1604 Accuracy (see note 2) ±0.1 ° C±0.05% of Reading Thermal Drift 0.0025 % / °C Excitation current < 200 uA Lead Resistance effect 0.002 ° C/ _ Maximum lead Resistance 20 _ per leg
Note 1 Any span may be selected, full accuracy is only guaranteed
Note 2 Basic measurement accuracy includes the effects of
OUTPUT Type Two wire (4 to 20) mA sink Limits Low 3.8 mA ; high 21.5 mA Accuracy ±(mA out / 2000) or ±5 uA which ever greater Loop Effect ± 0.2 uA / V measured @ 50 Hz 1 V (peak to peak) Thermal Drift ± 1 uA / °C typical ; ±1.5 uA Max Max Load [ (Vsupply – 10)/20 ] K_
GENERAL Update Time 0.5 Seconds Response Time 1 Second to reach 90% of final value Start up time From power up typically 5 Seconds Filter Factor Adaptive Ambient Temperature (-40 to 85) °C Connection Screw Terminal Approvals BS EN 61326 ; 1998 – Electrical equipment for measurement
Factory Default (0 to 100) °C upscale burnout (0.0 °C user trim)
Shop online at: omega.com e-mail: info@omega.com For latest product manuals: omegamanual.info
M4561/0807
for spans greater than the minimum recommended span.
calibration, linearisation and repeatability
and control ANNEX A ; ANNEX F
MADE IN UNITED KINGDOM
4.0 INSTALLATION AND WIRING
SIDE VIEW BASE VIEW
Ø 43.0 mm
33.0 mm
CENTRES
21.0 mm
Mounting holes : two holes 5.5 mm diameter, 33 mm centres Centre Hole sensor wire entry : 4 mm
4.1 Mechanical
The TX12 transmitter has been specifically designed to fit inside a DIN standard probe head enclosure (such as the Status SCH-4 series), which provides adequate protection from moisture, dust, corrosive atmosphere etc. All cable entries must be sealed using the correct size gland. Likewise any probe assembly fitted must be sealed. Care must be taken when locating the transmitter to ensure the working ambient temperature range of (-40 to 85) °C is not exceeded. The TX12 enclosure has a centre hole allowing the sensor wired to enter screw terminals from the transmitter centre, this is applicable when the sensor is mounted directly below the transmitter.
4.2 Electrical
Electrical connections to the transmitter are made to the screw terminal provided on the top face. The sensor wires must be equal length and type for the lead compensation to work correctly. The screw terminals allow for wires to enter either inner or outer direction. The transmitter is protected against reverse connection and over voltage. If no sensor (input) connection is made the transmitter will go into either up or down scale output current, depending on configuration. Figure 2 gives connection details, the output is shown connected to a 24 V supply. The load symbol represent any other device connected in the loop, such as Monitoring equipment , panel indicators and loop isolators. The load value can range from 0 ohms to the max loop load for given supply, refer to section 3 “Max load” for more information. The transmitter conforms with EC directive BS EN 61326 : 1998 when correctly installed in a termination head providing at least IP20 protection and with sensor wires less than 3 metres. Screened or twisted pair wires are recommended for output wires. Always ensure the (4 to 20 ) mA loop is grounded at one point, this would normally be at the monitoring equipment or loop power supply. In normal operation the program LED acts as over-range LED.
Figure 1
Figure 2
5.0 USER CONFIGURATION
READ COMPLETE SECTION BEFORE ATTEMPTING CONFIGURATION PARTICULAR CARE SHOULD BE TAKEN REGARDING TIMEOUTS IN MENU 2 & 3
User Configuration
User configuration uses three menus, each menu sets a different parameter:-
Menu 1 Set range Menu 2 Set direction of output on sensor burnout Menu 3 User trim at 4 mA and 20 mA.
The configuration menus are navigated using the push button and program LED, The push button is located under the hole in the keyhole shaped wiring label. To press the button use a 3 mm screw driver (flat blade) inserted into the hole. The button has a slight click action.
Three types of button press are used:-
Single button press = Advance
Double press within 0.5 seconds = Escape or change direction
Press and hold button > two seconds = Enter
When a menu is selected the Program LED will flash in bursts of one to three flashes, the number of flashes represents the menu number.
Navigating the menus
To access menus, press and hold button > 2 second, then program LED will start to flash, one flash every burst. This Indicates “menu 1” is selected.
Use single button press to advance selection to “menu 2”, the program LED will now show two flashes per burst. The Next single presses will advance the selected menu to menu 3 and the next single press will advance selected menu back to menu 1. Repeated single presses will cycle the selected menu back around menus 1 to 3, in the above sequence.
Double press button to escape from menus, and return to normal. Normal operation can also be selected by turning transmitter power off and on. Note the transmitter will not time out and automatically escape from menus.
Menu 1 Range configuration (No Timeout)
Configuration will require the following tools and equipment :-
DC Supply (12 to 30) V @ 30 mA
Precision resistance decade box to simulate PT100 sensor.
Screw driver flat blade 3mm wide
PT100 resistance tables
Current meter (user trim)
IMPORTANT
Figure 3 Configuration circuit
5.0 USER CONFIGURATION IMPORTANT
READ COMPLETE SECTION BEFORE ATTEMPTING CONFIGURATION PARTICULAR CARE SHOULD BE TAKEN REGARDING TIMEOUTS IN MENU 2 & 3
Figure 3 Configuration circuit
User Configuration
User configuration uses three menus, each menu sets a different parameter:-
Menu 1 Set range Menu 2 Set direction of output on sensor burnout Menu 3 User trim at 4 mA and 20 mA.
The configuration menus are navigated using the push button and program LED, The push button is located under the hole in the keyhole shaped wiring label. To press the button use a 3 mm screw driver (flat blade) inserted into the hole. The button has a slight click action.
Three types of button press are used:-
Single button press = Advance
Double press within 0.5 seconds = Escape or change direction
Press and hold button > two seconds = Enter
When a menu is selected the Program LED will flash in bursts of one to three flashes, the number of flashes represents the menu number.
Navigating the menus
To access menus, press and hold button > 2 second, then program LED will start
to flash, one flash every burst. This Indicates “menu 1” is selected.
Use single button press to advance selection to “menu 2”, the program LED will
now show two flashes per burst. The Next single presses will advance the selected menu to menu 3 and the next single press will advance selected menu back to menu 1. Repeated single presses will cycle the selected menu back around menus 1 to 3, in the above sequence.
Double press button to escape from menus, and return to normal. Normal
operation can also be selected by turning transmitter power off and on. Note the transmitter will not time out and automatically escape from menus.
Using Menus
Menu 1 Range configuration (No Timeout)
Configuration will require the following tools and equipment :-
DC Supply (12 to 30) V @ 30 mA
Precision resistance decade box to simulate PT100 sensor.
Screw driver flat blade 3mm wide
PT100 resistance tables
Current meter (user trim)
To re-range the temperature scale follow the following instructions:-
Refer to figure 3, connect resistance box to TX12 input terminals using three wire
connection. Connect output to a DC supply, observe polarity. Turn power on and allow 1 minute warm up period.
Set calibrator to the equivalent resistance of the PT100 sensor, at required low
range temperature. If the program LED is on at this stage the input is out of range, check resistance and connection.
Press and hold button > 2 seconds to enter menus, menu 1 will then be selected,
indicated by one flash every burst.
Whilst menu 1 is selected, press and hold button > 2 seconds to enter menu 1, at
which stage the program LED toggle on and off at a slow rate.
Allow ten seconds then single press button to store low range setting, the program
LED will now flash at a fast rate.
Set calibrator to the equivalent resistance of the pt100 sensor, at required high
range temperature and allow ten seconds.
Press button to store high range setting, the program LED will flicker for one
second before the transmitter returns to normal operation. The transmitter is now re-ranged.
Menu 2 Burnout Selection (Timeout is 3 Seconds)
Refer to figure 3, Connect output to a DC supply, observe polarity. For this menu the input can be connected or open circuit. Turn power on.
Press and hold button > 2 seconds to enter menus, menu 1 will then be selected, indicated by one flash every burst.
Single press button to advance selection to menu 2, indicated by two flashes of the program LED every burst.
Whilst menu 2 is selected, press and hold button > 2 seconds to enter menu 2, at which stage the program LED will either toggle on and off at a slow indicating low scale burnout or fast rate indicating upscale burnout.
To change burnout direction single press button. The Program LED toggle rate will change to the other setting. Repeated single presses will toggle between up and down scale.
To store setting allow 3 seconds with no button action, the program will then timeout, store new setting then return to normal operation.
Menu 3 User trim (Timeout is 20 Seconds)
This menu allows the user to trim the output current at 4 mA and 20 mA points, (similar function to trim potentiometers) and is very useful for trimming out sensor errors. The input of the transmitter must be connected to either a calibrator or temperature sensor held at a known temperature. The (4 to 20) mA loop current also need to be monitored with a current meter.
Refer to figure 3, connect sensor or resistance box to TX12 input terminals using three wire connection. Connect output to a DC supply, observe polarity, connect current meter in series with loop.Turn power on and allow 1 minute warm
period.
Set calibrator to the equivalent resistance of the PT100 sensor, at required point. Alternatively ensure sensor temperature is at the required calibration point.
The transmitter will automatically trim the 4 mA end if the output is within the active band of (3.8 to 6) mA, and trim the 20 mA end if the output is within the active band of (18 to 21.5) mA. No setting adjustment is performed if the output current not within these two bands. Ensure your calibration points are within these bands.
Press and hold button > 2 seconds to enter menus, menu 1 will then be selected, indicated by one flash every burst.
Single press button to advance selection to menu 2, and single press again select menu 3 indicated by three flashes of the program LED every burst.
Whilst menu 3 is selected, press and hold button > 2 seconds to enter menu 3, which stage the program LED toggle on and off at either a slow rate indicating downward trim direction or fast rate indicating upwards trim direction.
To change trim direction double press button. The Program LED toggle rate toggle to the opposite direction. Repeated double presses will toggle between and down trim direction
To trim output current, single press button to advance current 2 uA in set direction, or press and hold button to auto advance in set direction release button to stop advance. Note after approximately 20 seconds of continuous button press, auto trim rate will speed up. Monitor the current change on the current meter.
To store new setting allow 20 seconds with no button action, the program will then timeout, store new setting then return to normal operation.
Reset to factory default settings
If required the SEM203P can be reset to factory default setting, this procedure also removes any user trim adjustment. Factory default settings are :
Range (0 to 100) °C Burnout up-scale User trim All user adjustment cleared
To reset to factory setting, hold the button down whilst the TX12 is powered up.
Where Do I Find Everything I Need for
Process Measurement and Control?
OMEGA…Of Course!
Shop online at omega.com
M4498/0607
TEMPERATURE
䡺⻬
Thermocouple, RTD & Thermistor Probes, Connectors, Panels &
Assemblies
䡺⻬
Wire: Thermocouple, RTD & Thermistor
䡺⻬
Calibrators & Ice Point References
䡺⻬
Recorders, Controllers & Process Monitors
䡺⻬
Infrared Pyrometers
PRESSURE, STRAIN AND FORCE
䡺⻬
Transducers & Strain Gages
䡺⻬
Load Cells & Pressure Gages
䡺⻬
Displacement Transducers
䡺⻬
Instrumentation & Accessories
FLOW/LEVEL
䡺⻬
Rotameters, Gas Mass Flowmeters & Flow Computers
䡺⻬
Air Velocity Indicators
䡺⻬
Turbine/Paddlewheel Systems
䡺⻬
Totalizers & Batch Controllers
pH/CONDUCTIVITY
䡺⻬
pH Electrodes, Testers & Accessories
䡺⻬
Benchtop/Laboratory Meters
䡺⻬
Controllers, Calibrators, Simulators & Pumps
䡺⻬
Industrial pH & Conductivity
Equipment
DATA ACQUISITION
䡺⻬
Data Acquisition & Engineering Software
䡺⻬
Communications-Based Acquisition Systems
䡺⻬
Plug-in Cards for Apple, IBM & Compatibles
䡺⻬
Datalogging Systems
䡺⻬
Recorders, Printers & Plotters
HEATERS
䡺⻬
Heating Cable
䡺⻬
Cartridge & Strip Heaters
䡺⻬
Immersion & Band Heaters
䡺⻬
Flexible Heaters
䡺⻬
Laboratory Heaters
ENVIRONMENTAL MONITORING AND CONTROL
䡺⻬
Metering & Control Instrumentation
䡺⻬
Refractometers
䡺⻬
Pumps & Tubing
䡺⻬
Air, Soil & Water Monitors
䡺⻬
Industrial Water & Wastewater Treatment
䡺⻬
pH, Conductivity & Dissolved Oxygen Instruments
RETURN REQUESTS/INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN (AR) NUMBER FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING DELAYS). The assigned AR number should then be marked on the outside of the return package and on any correspondence.
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent breakage in transit.
FOR WARRANTY
RETURNS, please have the following information available BEFORE contacting OMEGA:
1. Purchase Order number under which
the product was PURCHASED,
2. Model and serial number of the product
under warranty, and
3. Repair instructions and/or specific
problems relative to the product.
FOR NON-WARRANTY REPAIRS,
consult OMEGA for current repair charges. Have the following information available BEFORE contacting OMEGA:
1. Purchase Order number to cover the
COST of the repair,
2. Model and serial number of the
product, and
3. Repair instructions and/or specific problems
relative to the product.
WARRANTY/DISCLAIMER
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of 13 months from date of purchase. OMEGA’s WARRANTY adds an additional one (1) month grace period to the normal one (1) year product warranty to cover handling and shipping time. This ensures that OMEGA’s customers receive maximum coverage on each product.
If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA’s Customer Service Department will issue an Authorized Return (AR) number immediately upon phone or written request. Upon examination by OMEGA, if the unit is found to be defective, it will be repaired or replaced at no charge. OMEGA’s WARRANTY does not apply to defects resulting from any action of the purchaser, including but not limited to mishandling, improper interfacing, operation outside of design limits, improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of having been tampered with or shows evidence of having been damaged as a result of excessive corrosion; or current, heat, moisture or vibration; improper specification; misapplication; misuse or other operating conditions outside of OMEGA’s control. Components in which wear is not warranted, include but are not limited to contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA neither assumes responsibility for any omissions or errors nor assumes liability for any damages that result from the use of its products in accordance with information provided by OMEGA, either verbal or written. OMEGA warrants only that the parts manufactured by the company will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESSED OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF LIABILITY: The remedies of purchaser set forth herein are exclusive, and the total liability of OMEGA with respect to this order, whether based on contract, warranty, negligence, indemnification, strict liability or otherwise, shall not exceed the purchase price of the component upon which liability is based. In no event shall OMEGA be liable for consequential, incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical applications or used on humans. Should any Product(s) be used in or with any nuclear installation or activity, medical application, used on humans, or misused in any way, OMEGA assumes no responsibility as set forth in our basic WARRANTY / DISCLAIMER language, and, additionally, purchaser will indemnify OMEGA and hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the Product(s) in such a manner.
It is the policy of OMEGA Engineering, Inc. to comply with all worldwide safety and EMC/EMI regulations that apply. OMEGA is constantly pursuing certification of its products to the European New Approach Directives. OMEGA will add the CE mark to every appropriate device upon certification. The information contained in this document is believed to be correct, but OMEGA accepts no liability for any errors it contains, and reserves the right to alter specifications without notice. WARNING: These products are not designed for use in, and should not be used for, human applications.
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords our customers the latest in technology and engineering. OMEGA is a registered trademark of OMEGA ENGINEERING, INC. © Copyright 2007 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied, photocopied, reproduced, translated, or reduced to any electronic medium or machine­readable form, in whole or in part, without the prior written consent of OMEGA ENGINEERING, INC.