U.S.A. and Canada
For Sales 
& Service
D-9
Our Industrial pH Instrumentation and Electrodes product 
line continues to expand, visit omega.com for new details!
Wall-Mounted, Single Setpoint and Proportional pH Control
The PHCN-901 is a pH 
controller with a single setpoint 
for proportional dosage of acid 
or alkaline solutions. Any pH 
electrode with a BNC 
connector can be directly 
attached to the PHCN-900 
series or ORCN-901. The 
proportional control can be fine 
tuned through two dials on the 
front panel. The time cycle is 
adjustable from 0 to 90 seconds 
and the proportional band from
0.0 to 2.0 pH. Coarse and fine as 
well as two offset and slope trimmers 
make accurate setting and 
calibration easy and convenient. 
A pump or electro-valve can be 
wired directly to the controller and 
be powered through the terminals.
The PHCN-901 also provides for 
an alarm relay. The alarm is 
activated when the 
measurements stray away from 
the setpoint by a predetermined 
value in the 0 to 2 pH range. 
A max dosing time from 
1 to 10 minutes is required to be set, 
after which the alarm is activated to warn of an abnormality. The 
alarm can be configured in either normally-closed or normally-open 
state. The PHCN-900 series also provides an isolated output 
signal, which is user selectable between 0 to 20 or 4 to 20 mA. A 
dial on the front panel renders manual temperature compensation 
fast and easy. For automatic compensation, hook up a 3 wire 
Pt 100 RTD to the controller. To speed up wiring, PHCN-900 and 
ORCN-901 series comes with extractable terminal modules. Once 
wired up, the compartment containing the connections is protected 
behind a fire-retardant ABS panel. Several LEDs show whether the 
setpoint or alarm relays are activated from a distance. 
The PHCN-902 is a pH controller with two setpoints for proportional 
dosage of acidic and alkaline solutions. Through two sets of coarse 
and fine trimmers, the setpoints can be accurately fine tuned to any 
value in the 0.00 to 14.00 range. Likewise, two trimmers on the 
front panel make for easy calibration. The proportional control can 
be adjusted to match your application through the time cycle from 
0 to 90 seconds and the proportional band of 0 to 2 pH. Two pumps 
or valves can be wired directly to the controller and be powered 
through the terminals. The PHCN-902 provides for two types of 
alarms. The alarm relay is activated when the measurements are 
beyond the setpoints by more than a predetermined value in the 
0 to 2 pH range. Alternatively, the relay can activate, when one of 
the two independently-adjustable maximum dosing times is 
exceeded. The alarm can be configured in either normally-closed 
or normally-open state and turned off during maintenance. 
The ORCN-901 is an ORP controller with a single setpoint for userselectable dosage of reducing or oxidizing solutions. With 
proportional control, you can fine tune your treatment plant and 
minimize the use of chemicals. The proportional setting can be 
adjusted through the time cycle from 0 to 90 seconds and the band 
from 0 to 200 mV. The setpoint can be accurately adjusted through 
coarse and fine trimmers. A pump or electro-valve can be wired 
directly to the controller and be powered through the terminal. In 
addition to the setpoint relay, the ORCN-901 also provides for an 
alarm relay. The alarm is activated when the measurements exceed 
the operator-adjustable threshold of 0 to 200 mV. For extra security, 
a maximum dosing time from 1 to 10 minutes is required to be set, 
after which the alarm is activated to signal an abnormality. The 
alarm configuration is alterable in a normally-closed or a normallyopen state to accommodate fail-safe installations. Any recorder 
accepting a 0 to 20 or 4 to 20 mA output can also be hooked up to 
the controller. One can judge the controller’s status, even from a 
distance, by observing the dosage or alarm LEDs.
PHCN-901
Starts at
$
505
⻬ Wall Mount 
⻬ Isolated Recorder Output 
⻬ Simple Operation  
⻬ 10 Minute Maximum Dosing Time
PHCN-902, $550 shown smaller 
than actual size.
PHE-1411 laboratory pH electrode, $70, 
sold separately, see pH page C-13 and C-14.

Order Online
Over 100,000 Products Available!
D-10
To download information and to order Industrial 
pH Instrumentation and Electrode products online, 
visit omega.com
Specifications
Range: 0.00 to 14.00 pH; 
ORCN-901: -500 to +1500 mV
Resolution: 0.01 pH; ORCN-901: 1 mV 
Accuracy @20°C/68°F: ±0.02 pH 
ORCN-901: ±5 mV 
Typical EMC Deviation: ±0.1 pH; 
ORCN-901: ±6 mV 
Calibration: PHCN-901, ORCN-901:
One point, through trimmers on the front 
panel; PHCN-902: Two point
Temperature Compensation:
Manual or Automatic with Pt100 RTD 
from -10 to 80°C (14 to 176°F)
Setpoint: PHCN-901: one, selectable 
from 0.00 to 14.00 pH; 
PHCN-902: Two, selectable
Recorder Output: Selectable from 
0 to 20 mA or 4 to 20 mA, isolated
Proportional Control:
Adjustable: pH from 0.0 to 2.0 and time 
cycle from 0 to 90 seconds; 
ORCN-901: Adjustable: mV from 0 to 200 
and time cycle from 0 to 90 seconds 
Dosing Contact: PHCN-901: One 
powered terminal for pH correction (115 or 
240V) (Max 2 A 1,000,000 strokes); 
activated proportionally when 
pH > setpoint for acid dosage or 
pH < setpoint for alkaline dosage
PHCN-902: Two powered terminals for 
acid and alkaline correction 
(115 or 240V) (Max 2 A 
1,000,000 strokes); Proportional acid 
Dosage: activated when pH > setpoint, 
Proportional Alkaline dosage: activated 
when pH < setpoint
ORCN-901: One powered terminal 
for mV correction (115 or 240V) 
(Max 2A 1,000,000 strokes); 
activated proportionally 
mV > setpoint for acid dosage or 
mV < setpoint for alkaline dosage
Alarm Relay: One, activated when pH 
varies (selectable 0 to 2.0) (ORCN-901 
selectable 0 to 200 mV) from the 
setpoint and/or max dosage time 
(1 to 10 minutes) elapses. Isolated, 
(max 2 A, max 240V, resistive load, 
1,000,000 strokes)
Power Supply:
110/115V or 220/240V; 50/60 Hz 
Environment: -10 to 50°C (14 to
122°F); 95% non-condensing 
Enclosure: 181 L x 221 W x 142 H mm 
(7.1 x 8.7 x 5.6") 
Weight: 1.6 kg (3.5 lb)
To Order 
(Specify Model Number)
Model No. Price Description
PHCN-901 $505 Wall mount single setpoint pH controller 
PHCN-902 550 Wall mount dual setpoint pH controller 
ORCN-901 505 Wall mount single setpoint ORP controller 
PHE-6510 134 pH industrial submersible electrode 
(requires mounting assembly)
PHEH-65-10-PT100 141 Mounting assembly with temperature 
compensation (required for PHE-6510)
PHA-4 5 4.00 pH buffer solution 500 mL (1 pt) bottle 
PHA-7 5 7.00 pH buffer solution 500 mL (1 pt) bottle 
PHA-10 5 10.00 pH buffer solution 500 mL (1 pt) bottle 
ORE-6510 159 ORP industrial submersible electrode 
(requires PHEH-65-10 mounting assembly)
PHEH-65-10 55 Mounting assembly for ORE-6510 (required) 
FW-400 84 Reference Book: The Automation, Systems, 
and Instrumentation Dictionary
Comes complete with operator’s manual. 
Ordering Examples: PHCN-901, pH controller, PHE-6510, pH electrode, PHEH-65-10-PT100,
mounting assembly with temperature compensation, PHA-4, pH 4.00 buffer, PHA-7, pH 7.00 
buffer, $505 + 134 + 141 + 5 + 5 = $790.
PHCN-902, dual setpoint pH controller, $550.
FRONT VIEW
181 
(7.1)
164 
(6.45)
110 
(4.33)
204 
(8.03)
221 
(8.70)
pH
9.56
AVAILABLE FOR FAST DELIVERY!
BOTTOM VIEW
142 
(5.60)
55 
(2.16)
99 
(3.90)
5 
(0.19)
110 
(4.33)
DIN or BNC connectors
ORCN-901, $505, shown 
smaller than actual size.
Dimensions: mm (in)

One Omega Drive | Stamford, CT 06907 |  1-888-TC-OMEGA (1-888-826-6342) |  info@omega.com 
www.omega.com
UNITED KINGDOM
www. omega.co.uk
Manchester, England
0800-488-488
UNITED STATES
www.omega.com
1-800-TC-OMEGA
Stamford, CT.
CANADA
www.omega.ca
Laval(Quebec) 
1-800-TC-OMEGA
GERMANY
www.omega.de
Deckenpfronn, Germany
0800-8266342
Karviná, Czech Republic
FRANCE
www.omega.fr
Guyancourt, France
088-466-342
CZECH REPUBLIC
www.omegaeng.cz
596-311-899
BENELUX
www.omega.nl
Amstelveen, NL 
0800-099-33-44
More than 100,000 Products Available!
Temperature
Calibrators, Connectors, General Test and Measurement 
Instruments, Glass Bulb Thermometers, Handheld Instruments 
for Temperature Measurement, Ice Point References, 
Indicating Labels, Crayons, Cements and Lacquers, Infrared 
Temperature Measurement Instruments, Recorders Relative 
Humidity Measurement Instruments, RTD Probes, Elements 
and Assemblies, Temperature & Process Meters, Timers and 
Counters, Temperature and Process Controllers and Power 
Switching Devices, Thermistor Elements, Probes and 
Assemblies,Thermocouples Thermowells and Head and Well 
Assemblies, Transmitters, Wire
Flow and Level
Air Velocity Indicators, Doppler Flowmeters, Level 
Measurement, Magnetic Flowmeters, Mass Flowmeters, 
Pitot Tubes, Pumps, Rotameters, Turbine and Paddle Wheel 
Flowmeters, Ultrasonic Flowmeters,  Valves, Variable Area 
Flowmeters, Vortex Shedding Flowmeters
pH and Conductivity
Conductivity Instrumentation, Dissolved Oxygen 
Instrumentation,  Environmental Instrumentation, pH 
Electrodes and Instruments, Water and Soil Analysis 
Instrumentation
Data Acquisition
Auto-Dialers and Alarm Monitoring Systems, 
Communication Products and Converters, Data 
Acquisition and Analysis Software, Data Loggers 
Plug-in Cards, Signal Conditioners, USB, RS232, RS485 
and Parallel Port Data Acquisition Systems, Wireless 
Transmitters and Receivers
Pressure, Strain and Force
Displacement Transducers, Dynamic Measurement 
Force Sensors, Instrumentation for Pressure and Strain 
Measurements, Load Cells, Pressure Gauges, Pressure 
Reference Section, Pressure Switches, Pressure Transducers, 
Proximity Transducers, Regulators,  
Strain Gages, Torque Transducers, Valves
Heaters
Band Heaters, Cartridge Heaters, Circulation Heaters,  
Comfort Heaters, Controllers, Meters and Switching 
Devices, Flexible Heaters, General Test and Measurement 
Instruments, Heater Hook-up Wire, Heating Cable 
Systems, Immersion Heaters, Process Air and Duct,  
Heaters, Radiant Heaters, Strip Heaters, Tubular Heaters
click here to go to the omega.com home page