Omega Products OM-PQR-HUMIDITY User Manual

OM-PQR1010 Power Line and Environmental Monitor
Extended Warranty
Program
SM
Measures All Types of
Disturbances Including Spikes, Sags, Surges, Common Mode Noise, High Frequency Noise, Dropouts, Power Failures
Average Reading Every Minute for Up to 11 Days on Each Channel
1500 Event Storage Per
Input, 9000 Events Total for 6 Channels
Records Magnitude,
Time and Date of Each Disturbance
Model OM-PQR1010, shown with included temperature probe, AC voltage test leads, DC voltage test leads, RS-232 cable, power cord and Windows software CD.
Shown smaller than actual size.
Electronic equipment is damaged more often by power disturbances than by fire, theft and vandalism combined. Intermittent power problems are the most expensive hidden expense to users of microprocessor-based equipment. The OM-PQR1010 power quality recorder is a state-of-the-art, fully integrated instrument that measures, records and reports power disturbances, aiding in the analysis of power quality in medical, commercial and industrial applications.
The OM-PQR1010 monitor unit will detect a wide range of power disturbances including spikes, sags, surges, common mode noise, dropouts and high frequency noise on two phases of AC voltage and one DC voltage channel; it will also test the temperature, humidity and ac current. For ac current measurement, the OM-PQR1010 is equipped with a pair of banana jacks designed to accept a 10 mV/A output current transducer (CT). Disturbances detected on multiple channels are recorded by their time, date, magnitude and duration in a non-volatile RAM memory. Stored data can then downloaded and analyzed by connecting the OM-PQR1010 to your PC’s serial port and running the included
OM-PQR1010 software
Windows data analysis software. Input connections to the OM-PQR1010 are made between the safety connectors on the back of the unit and the circuit panel to be tested. The OM-PQR1010 operates on standard 110 Vac/220 Vac power. Once plugged in, the OM-PQR1010 immediately begins testing the signals on the input connectors.
Specifications
GENERAL Summary Event Count:
56,000 of each event type
Detail Storage:
1500 events per channel
OM-PQR1010, shown smaller than actual size
Data Retention:
5 years without power
Datalogging Sample Rate:
Programmable from 1 reading per second to 1 reading per 4 minutes
Impulse Detection: 500 nanoseconds Communications: RS-232, 1200 to
19,200 baud (programmable), 8 data bits, 1 stop bit, no parity
Input Connections: ac voltage, safety banana jacks; dc voltage, BNC; current (CT), banana jacks; temperature, phone jack; humidity, mini-DIN
Operating Temperature: 0 to 50 (32 to 122°F), 10 to 80% RH non-condensing
o
C
E-71
Operating Voltage: 12 to 30 Vdc,
80 to 260 Vac
Operating Current: 0.1 A Operating Line Frequency:
DC to 400 Hz
Weight: 1.8 kg (4 lb) Dimensions:
203 mm H x 254 mm W x 51 mm D (8 x 10 x 2")
Power Cord: 1.8 m (6') AC/DC VOLTAGE CHANNELS
DATA LOGGING Range: ac voltage, 80 to 520 Vac
RMS; dc voltage, +1 to +52 Vdc
Accuracy: +1.5% SAGS/SURGES Threshold: 5% and 10%
of average, or user programmed levels
Duration Limits: 1 cycle or 20 ms Accuracy: +1.5% DROPOUTS Threshold: AC voltage, less than
10 V RMS; DC voltage, less than 10% of avg
Duration Limits: longer than 8 ms, shorter than 80 ms
POWER FAILURES Threshold: ac voltage, less than
10 V RMS; dc voltage, less than 10% of avg
Duration Limits: Longer than 80 ms
IMPULSES Resolution: 2 channels:
20 V to > 2500 V peak Threshold: 20, 70, 140, 300, 850,
2.5 kV Duration Limits: 500 nanoseconds
above threshold
Accuracy: +10% HIGH FREQUENCY NOISE Range: 2 volts peak, 10 kHz
to 10 MHz
Accuracy: +10% Response Time: 1 ms AC VOLTAGE LINE FREQUENCY Range: 40 to 400 Hz Accuracy: +1% Response Time: 1 AC cycle Threshold: +2% deviation
from average
HUMIDITY CHANNEL DATA LOGGING Range: 10 to 90%
RH non-condensing
Accuracy: +5%
SAGS/SURGES Threshold: 5% and 10%
of average, or user programmed levels
Duration Limits: 2 seconds Accuracy: +5% CURRENT CHANNEL DATA LOGGING Input: Current transducer
(CT), 10 mV/A output
Range: 0.2 A to 1000 A RMS Accuracy: +1.5% SAGS/SURGES Threshold: 5% and 10%
of average, or user programmed levels
Duration Limits: 20 ms Accuracy: +1.5% DROPOUTS Threshold: Less than 10%
of average Duration Limits: Longer than
8 ms, shorter than 80 ms
POWER FAILURES Threshold: Less than 10%
of average
Duration Limits:
Longer than 80 ms
TEMPERATURE CHANNEL DATALOGGING Sensor: Semiconductor transistor Range: -7 to 121°C (20 to 250°F)
(0.02 to 2.5 Vdc)
Accuracy: +1% Sample Rate: Programmable from
OM-PQR1010, shown smaller than actual size
1 reading per second to 1 reading per 4 minutes
SAGS/SURGES Threshold: 5 and 10% of average,
or user programmed levels Duration Limits: 2 seconds
Accuracy:+1.5%
OM-PQR1010
software
AVAILABLE FOR FAST DELIVERY!
To Order
(Specify Model Number)
Model No. Description
OM-PQR1010 Power line and environmental monitor OM-PQR-HUMIDITY Humidity probe for OM-PQR1010
Each OM-PQR1010 is supplied with 1.8 m (6') power cord, RS-232 communications cable with DB9F termination, Windows 2000/XP data analysis software, temperature probe, one set of ac voltage test leads and one set of dc voltage test leads. Humidity probe must be ordered separately.
Ordering Example: OM-PQR1010 power line and environmental monitor