OMA-GUARDIT
Extended Warranty
Program
SM
Rugged Automatic Alarm Dialer
$
945
Basic Unit
⻬ Monitors Four Analog or
Digital Inputs,
Individually Selectable
⻬ Calls Up to Eight Phone
Numbers on Alarm
Condition
⻬ Digitally Records Alarm
Messages up to 12
Seconds Long Each
⻬ Built-in Surge Protection
⻬ Wall Mount or Panel
Mount
⻬ Rugged Steel
Construction
The OMA-GUARDIT automatic
alarm dialer monitors 4 input
channels. Each channel can be
configured for an analog or digital
signal input. The system utilizes the
public telephone network as a basic
medium for transmission of alarm
messages and status calls. It is field
programmable by the user at the
system's control panel via a
standard touch tone phone handset.
Automatic Alarm Reporting
Upon detection of an alarm
condition, OMA-GUARDIT
automatically calls a list of up to 8
pre-programmed phone numbers
over the standard dial-up telephone
network, calling until it gets an
acknowledgement. When a
connection is made, the system
reports the station identity and the
specific alarm condition in the form
of a digitally pre-recorded voice
message. In addition to standard
phones in office, plant, or home, the
alarm calling sequence can also
include calls to pagers, cellular
phones, and voice mail.
Local Alarm Relay Output
The OMA-GUARDIT provides a
transistor output for TTL or relay
drive (500 mA 24 VDC max)
activated during unacknowledged
OMA-GUARD IT Alarm Dialer
alarm. This output can be used to
activate a local alarm buzzer or
light, can be used to remove power
to machinery when used with a
normally closed relay or activate/
de-activate any device locally when
an alarm condition occurs.
Alarm Acknowledgment
An alarm is acknowledged simply
by pressing a button on the called
phone. When acknowledging an
alarm, a built-in microphone permits
the caller to listen for background
sounds at the site. The user can
also call the system from any
remote phone for a status report of
all points being monitored.
Voice Messaging
The voice transmission consists of
a station identification together with
an alarm message giving details on
the fault. The station identification
and alarm messages are digitally
recorded by the user. By using
electronic voice reporting
technology, OMA-GUARDIT
eliminates the need for often
unreliable audio tape autodialers.
G-5
Set-up and Programming
System set-up, voice recording, and
programming is accomplished via
an external touch-tone phone which
plugs into a standard phone jack on
the system’s front panel. The user
simply follows voice instructions
given over the phone.
System Controls
System operating status is provided
by front panel LED indicators.
System off/disarm/ready controls
are provided on front panel. Surge
protection and noise suppression
are standard.
A Truly Modern Autodialer
OMA-GUARDIT fills the requirement
of a modern autodialer–it should be
extremely reliable and be able to tell
the called party as much information
about the nature of an alarm as
possible so that the right personnel
can respond quickly and
appropriately. Many other
autodialers don’t meet these
requirements.
Specifications
Extended Warranty
Program
SM
ELECTRICAL
Power Requirements: User
supplied 10-14 VDC, 500 mA max.
Power Consumption: 200 mA
minimum standby 500 mA
maximum active
Power Failure: Automatic alarm
for external power failure
Battery Charging: Precision
voltage controlled, automatic rapid
recharge after drain
UNIVERSAL SIGNAL INPUTS
Digital Inputs: Open contacts see
5VDC, closed contacts see 5 mA DC
Analog Inputs: 4-20 mA, single ended.
Maximum voltage drop 10 VDC.
Resolution: 0.2%
Absolute Accuracy: 0.5%
Local Alarm Relay: Transistor
output for TTL or relay drive (500
mA 24 VDC max) activated during
unacknowledged alarm.
RJ11-Telephone Line Jack:
For connection to public telephone
network
PHYSICAL
Surge protection: solid state
protectors on phone, power, and
signal lines
Enclosure: single circuit card in
durable steel cabinet designed for
mounting on control panel wall
or flush mounted inside a larger
control panel with faceplate visible
Weight: 4 pounds, 6 pounds with
battery
Dimensions:
6.85"H x 8.85"W x 2.85"D
Mounting Centers: 3.6"H x 9"W
ENVIRONMENTAL
Temperature Range: 20° to 130°F.
Humidity: 0 to 95%,
non-condensing
TELEPHONE
Rotary pulse or tone dialing. Dials
up to 8 different numbers, each up
to 60 digits long. Time between
alarm phone calls programmable
0.1 to 99.9 minutes. Smart calling
call progress monitoring detects
dial tone, basic ringback and busy
signal. Alarm acknowledgement by
touch tone key or callback.
Compatible with most pager,
cellular, and voicemail systems.
User-furnished standard touch-tone
handset required for programming.
FCC Registered.
PROGRAMMlNG
Standard phone jack on front panel
for programming phone. Voice
menu instructions guide
programming.
FACTORY OPTIONS
AC Power Supply, battery backup,
internal 6 volt; 4 AH gel cell
provides 20 hours operation during
power failure. NEMA 4X enclosure.
SPEECH MESSAGES
User digitally records five
messages, Station ID and four
channel alarm messages. High
definition digital recordings up to
12 seconds per message. Resident
synthesized voice vocabulary for
programming guidance.
OMEGACARESMextended warranty program is
available for models shown on this page. Ask
your sales representative for full details when
placing an order. OMEGACARE
labor and equivalent loaners.
SM
AVAILABLE FOR FAST DELIVERY!
To Order
Model Number Price Description
OMA-GUARDIT $945 Rugged automatic alarm dialer with
OMA-GAC 50 AC power supply
OMA-GBB 65 Battery backup
OMA-GNEMA4X 125 NEMA 4X enclosure
OMA-GUARDIT comes with complete user's manual.
OMEGACARESMextended warranty is available for models shown on this page.
Ask your sales representative for full details when placing order.
Ordering Example: OMA-GUARDIT alarm dialer, OMEGACARE
warranty (adds 1 year to 2-year standard warranty), $945 + 94 =
(Specify Model Number)
4 analog/digital inputs
G-6
SM
1-year extended
$1039.
covers parts,
G