Omega Products OM5-DT-1-C User Manual

H-43
$
155
Basic Modules
Rugged, Compact
Economical Signal Conditioning
for Mix and Match Capability
Analog Input Modules
for Direct Interface to Sensors and Analog Voltage and Current
Convenient Connection
to User Equipment
OM5 Compact, Low Cost, Modular
RTD Input Models
The OM5-IP, OM5-IC and OM5-IN are designed for 100Ω PT, 10Ω Cu and 120Ω Ni RTDs respectively. The modules have 3 wire compensation and may be used with 2- or 3-wire RTDs. The OM5-IP4 features 4-wire compensation for 100Ω PT RTDs.
Strain Gage Input Models
Designed for 300 to 10 kohm full or half strain gage bridge for dynamic signals. Bandwidth is 10 kHz. Integral 10 V excitation is also provided.
Output Models
Isolated modules that accept process voltage inputs from the system connector and provide an isolated process current signal as output.
Potentiometer Input Models
For use with 3-wire potentiometers and 2-wire slidewire with up to 10 KΩ resistance. The input signal is filtered, isolated and amplified to a high level analog output voltage.
Isolated Voltage Input Models
Designed for either low-level millivolt or high level voltage inputs, these modules can accept from ±10 mV to ±10 V full scale input, with either a 0 to 5 V or ±5 V output. Standard modules have a 4 Hz bandwidth, while for interfacing to dynamic signals, the OM5-WV and OM5-WMV modules feature a 10 kHz bandwidth.
Current Input Models
These modules accept process current signals. A sensing resistor of 20 ohms is used to convert the signal current to a voltage. The resistor is installed as a separate assembly, to facilitate replacement in the event of inadvertent connection of the power line.
Thermocouple Input Models
The isolated thermocouple models incorporate cold junction compensation circuitry which provides 0.5°C accuracy. Open sensor detection is standard.
The OM5 series modular signal conditioners provide a low cost, high performance method of inter­connecting real-world analog signals with data acquisition, monitoring or control systems.
They are designed to interface directly to analog inputs such as thermocouples, RTDs, strain gages and voltage or process current signals. Individual OM5 modules convert these inputs to standardized analog outputs compatible with high-level analog I/O systems. An output module converts a high-level analog output to a process current signal.
The OM5 is designed to provide easy and convenient solutions to signal conditioning problems of both designers and end users in measurement and control applications.
Typical uses include mini- and microcomputer-based measurement systems, standard data acquisition systems, recorders, and dedicated control systems.
The OM5 is ideally suited to applications where monitoring and control of temperature, pressure, flow and other analog signals is required.
H
Signal Conditioners
H-44
SYSTEM CONFIGURATION
The OM5 system is fully modular, for maximum user flexibility. When designing a system, in addition to selecting input and output modules, both a backplane and power supply are required.
The OM5-BP-16 is a 16-position plane with pinouts on system connector that are compatible with the OM3 system; this allows an OM5 to interface to plug-in cards for IBM PCs. Also available for single channel applications is the OM5-BP-SKT single channel backplane.
Two power supplies are available for OM5 systems. The OMX-955 has 1A capacity, and can be used with up to 16 input modules. For systems with larger requirements, the OMX-976 has 3A capacity, and can drive a full complement of 16 output modules.
The OMX-1315 cable mates directly to the OM5-BP-16, and may be connected to the OMX-1324 adapter. The OMX-1324 provides screw terminations for the high level voltage output from the system connector.
Shown with optional sensors
Excitation is provided by two matched current sources which cancels lead resistance effects in 3-wire potentiometers. The excitation current is small (less than 1.0 mA) to minimize self-heating error.
Displacement Transducer Input Modules
The displacement transducer input modules can interface to DC displacement transducers and other devices which require a precision excitation voltage. The transducer excitation is provided from the module by a stable isolated 10 V source.
Two-Wire Transmitter Interface Modules
The OM5-TX are ideal for connecting to 2-wire loop power transmitters. The modules accept 4-20 mA process current input and provide an isolated output voltage.
A/OUT
How to Order
To Assemble a Complete OM5 System, Order:
1. Desired input and output modules
2. Backplane
3. Power Supply: calculate system power requirements from table on H-80
4. Voltage I/O cables and connectors
5. Rack or Surface Mount Kit
The module features an isolated 20 Vdc regulated power supply to provide power to the transmitter. A precision 20 ohm current conversion resistor is supplied with each module.
A/IN
H-45
Model Input Response Number Price Range Time
OM5-IFI-500-C $185 0-500 Hz 300 mS OM5-IFI-1K-C 185 0-1 KHz 300 mS OM5-IFI-3K-C 185 0-3 KHz 170 mS OM5-IFI-5K-C 185 0-5 KHz 90 mS OM5-IFI-10K-C 185 0-10 KHz 90 mS OM5-IFI-25K-C 185 0-25 KHz 20 mS OM5-IFI-50K-C 185 0-50 KHz 20 mS OM5-IFI-100K-C 185 0-100 KHz 20 mS
Compact, Low Cost Modular Signal Conditioners
Frequency Input, Isolated, 0 to 5 Vdc Output
Model Accuracy
OM5-DT Displacement Input ±0.1% span ±10µV RTI1 OM5-II Current Input ±0.05% span +0.05%(/-I
Z
2
) OM5-IFI Frequency Input ±0.05% span OM5-IP/IC RTD Input See ordering table OM5-ITC Non-linearized Thermocouple ±0.05% span ±10µV RTI
1
OM5-IVI Current Output ±0.05% span OM5-LTC Linearized Thermocouple See ordering table OM5-PT Potentiometer Input ±0.08% span OM5-TX Transmitter Input ±0.05% span ±4µV RTI
1
OM5-WBS Strain Input ±0.08% span ±10µV RTI
1
OM5-WMV & OM5-IMV Millivolt Input ±0.05% span ±10µV RTI
1
±0.05% (V
Z
3
)
OM5-WV & OM5-IV Voltage Input ±0.05% span ±0.2mV RTI
1
±0.05% (V
Z
3
)
(1) RTI = Reference to input (2) IZis the current input that results in 0V output (3) VZis the voltage input that results in 0V output
Accuracy
Specifications
Input Ranges: See ordering table Common Mode Voltage, Input to Output:
1500 Vrms max
Non-linearity: 0.02% span Bandwidth:
OM5-II, OM5-IMV, OM5-ITC, OM5-IV, OM5-IP/IC/IN, OM5-LTC, OM5-PT: 4 Hz
OM5-WBS, OM5-WMV, OM5-WV: 10 KHz
OM5-TX: 100 Hz OM5-DT: 1 KHz OM5-IVI: 400 Hz OMF-FR: See ordering table
Input (field) Protection: 240 Vrms max Output Range: See ordering table Output Resistance (input modules): 50Ω Output Current limit (input modules): ±14 mA max Operating Temperature Range: -40 to 85°C Module Dimensions: 2.28" x 2.26" x 0.60"
(58 x 57 x15 mm)
Loading...
+ 4 hidden pages